Jet Fans

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

JET-FANS

Ventilation Systems

DYNAIR INDUSTRIAL VENTILATION

JET-FANS

A Dynair Jet Fans Ventilation System provides an efficient and cost effective solution for normal ventilation or smoke extraction in enclosed, multi-storey and underground car parks. The jet fans principle offers different possibilities for two different targets: normal ventilation for CO removal and High Temperature ventilation for smoke extraction in case of fire. A combination of both is possible through dual purpose jet fans. Jet fan ventilation systems typically consist of three ventilation elements (supply, impulse and discharge) managed through a CO and/or Smoke detection and control system. Supply elements may consist of access ramp, ventilation shaft, side wall openings eventually with the addition, when necessary, of supply fans. Jet fans are the impulse elements, necessary to set air into motion towards the direction of the discharge elements. Discharge elements can be, again, openings in the walls or shafts with the addition, when necessary, of extract fans.

The advantages of a Jet Fan Ventilation System are several : No need for expensive distribution ductwork and grilles within the car park Space saving, thanks to reduced obstructions within the car park Reduced system resistance, by elimination of ductwork. Main extract fans can therefore, be selected at lower speed and size reducing absorbed power, running cost and noise levels Reduced running costs and absorbed power through a proper air quality (pollution levels) monitoring. The ventilation system is only operated when necessary Reduced design time, without complicated duct systems to be considered in design stage Optimised system design, as the effectiveness of the ventilation system can be analysed and optimised using CFD simulation Tailored solution, through a dedicated approach to each project specific requirements.

Read carefully all the information in this manual. Take particular care of the sections preceded by ATTENTION, because if not observed, they can cause damages to people, things and(or to the fan itself. NOTE: preserve this manual for eventual future consultations. We reserve the right to change this manual, the product and accessories without updating previous productions and manuals. The manual is composed of 4 pages. 1.0 GENERAL INFORMATIONS - ACCEPTANCE This instructions refer to the fan series DIC-ATEX. All fan are balanced and checked before expedition. The identification of the fan is by mean of the label of the fan itself. Our fan are guaranteed as stated by current laws. Guarantee starts from the delivery date and cover the faults for which is agreed are caused by material defect or manufacturing errors. If there are signs of damages at the receiving of the goods, please notify the forwarder and contact us immediately.. Do not use or repair damaged fans, or any guarantee will cease. Check the conformity of the fan to the order (execution, rotation, power and polarit of the motor installed, accessories, etc.), Dynair will not accept back any fan not conform after installation. Dynair declines every responsibility for damages cause by an improper use of the fan and/or by the infringement of the instruction in this manual. 2.0 AIM AND LIMIT OF THIS MANUAL The aim of this manual is to allow a safety installation and use of our fans, so the instruction here reported must be followed and applied completely and in all its parts. The manual must be considered as part of the fan, so it will be conserved for eventually consultations for all the time of use of the fan itself. This recommendations are not enough to guarantee a safe use of the fan; every operation performed moving parts and/or under voltage are safe only if performed by a qualified technician. Following the instruction for the use of the fan requires the check for the conformity with all the directives, laws, norm, in force in the country of installation of the fan. 2.0 AIM AND LIMIT OF THIS MANUAL The aim of this manual is to allow a safety installation and use of our fans, so the instruction here reported must be followed and applied completely and in all design of manual must be considered as part of Dynair offers an important support in theits parts. The a Jet Fans Ventilation System. the fan, so it will be conserved for eventually consultations for all the time of use of the fan itself. This recommendations are not enough to guarantee a safe use of the provide assistance to system On request (and with terms to be agreed), we canfan; every operation performed moving parts and/or safe only technician. Following the designers under voltage arethe check if performed by a qualifiedthe directives, laws, norm, instruction for the use of thanks to precise and reliable CFD (Computational Fluid Dynamic) the fan requires for the conformity with all in force in simulations,installationout by our trained staff using powerful dedicated work-stations the country of carried of the fan.

and the most updated software from CF Design (USA). Thanks to our support, designers can verify and validate the selection of number, size and positioning of the fans, through precise velocity vectors charts, static pressure contours, simulations of smoke spreading and any other information required for each specific project. CFD software is used to analyze complex systems and make a precise model of the airflow (direction and speed), of the pressure and of the temperature in each point of the system. Analysis of a car park design using CFD is an effective way to ensure that the distribution of air is sufficient to effectively ventilate the car park. CFD can be used to model both normal ventilation for CO removal and High Temperature ventilation for smoke extraction in case of fire.

JET-FANS

JET-FANS

CONSTRUCTION
The fan casing is made in electrolytically galvanized steel sheet. The impellor has hub and airfoil profile blades made in aluminium. Two silencers are fitted at both ends of the fan, with an especially designed smooth bell shape to improve performance and reduce losses and noise generation. A protection guard and a deflector (two deflectors in case of truly reversible version), are fitted for safety purposes and for optimal air discharge.

MODELS
It is possible to choose between two different sizes of jet fan, depending on the performance required, with impellor diameter of 310 mm or 400 mm. Each size is available in a truly (100 %) reversible version "CC-JR", or unidirectional version "CC-JD".

MOTOR
Motors power supply is are 400 V, 50 Hz. Motors are suitable for DOL (direct on line) start. Motor protection is IP 55 and the insulation is class F or H, depending on model.

HIGH TEMPERATURE RESISTANCE


It is possible to choose between two different jet-fan ratings: 200C for hour or 300C for 1 hour. Other ratings can be quoted upon request.

SERVICE SWITCH
On each jet fan, a service switch is supplied as standard, fitted on the outside of the fan casing.

INSTALLATION
Each jet fan is supplied with fixing brackets, for ceiling (or wall) installation. It is recommendable for jet fans be installed at least 0.5 m from beams on the inlet side and at least 2.0 m from beams on the outlet side (beam height: 400 mm).

JET-FANS

JET-FANS

TECHNICAL DATA
MODEL SPEED rpm CC-JD 312 CC-JD 312/4 HT 200C 1/2h CC-JD 312/4 HT 300C 1h CC-JD 402 CC-JD 402/4 HT 200C 1/2h CC-JD 402/4 HT 300C 1h CC-JR 312 CC-JR 312/4 HT 200C 1/2h CC-JR 312/4 HT 300C 1h CC-JR 402 CC-JR 402/4 HT 200C 1/2h CC-JR 402/4 HT 300C 1h 2880 2880/1440 2880/1440 2880 2880/1440 2880/1440 2880 2880/1440 2880/1440 2880 2880/1440 2880/1440 MOTOR POWER kW 0,55 0,55/0,15 0,75/0,12 1,5 1,5/0,4 1,5/0,25 0,55 0,55/0,15 0,75/0,12 1,5 1,5/0,4 1,5/0,25 MOTOR RATED CURRENT A 1,35 2/0,48 1,8/0,4 3,20 3,50/1 3,6/0,7 1,35 2/0,48 1,8/0,4 3,20 3,50/1 3,6/0,7 VOLTAGE FREQUENCY V/Hz 400/50 400/50 400/50 400/50 400/50 400/50 400/50 400/50 400/50 400/50 400/50 400/50

PERFORMANCE
MODEL AIRFLOW m3/s CC-JD 312 CC-JD 312/4 HT 200C 1/2h CC-JD 312/4 HT 300C 1h CC-JD 402 CC-JD 402/4 HT 200C 1/2h CC-JD 402/4 HT 300C 1h CC-JR 312 CC-JR 312/4 HT 200C 1/2h CC-JR 312/4 HT 300C 1h CC-JR 402 CC-JR 402/4 HT 200C 1/2h CC-JR 402/4 HT 300C 1h 1,28 1,28/0,64 1,28/0,64 2,88 2,88/1,44 2,88/1,44 1,09 1,09/0,55 1,09/0,55 2,46 2,46/1,23 2,46/1,23 AIR SPEED m/s 17,3 17,3/8,7 17,3/8,7 22,3 22,3/11,2 22,3/11,2 14,6 14,6/7,3 14,6/7,3 19,2 19,2/9,6 19,2/9,6 THRUST N 27 27/7 27/7 78 78/20 78/20 20 20/5 20/5 58 58/14 58/14 SOUND PRESSURE db(A) @ 3m 54 54/43 54/43 58 58/47 58/47 52 52/41 52/41 56 56/45 56/45

CC-JD (UNIDIRECTIONAL) DIMENSIONS

A B

Protection grid D I

Deflector

Service switch

F H

Model 31 40

A 415 500

B 375 460

C 415 500

D 241 271

E 630 800

F 200 230

G 134 134

H 1595 1965

I 6 6

kg 65 80

CC-JR (TRULY REVERSIBLE) DIMENSIONS

A B

Deflector D I

Deflector

Service switch

F H

Model 31 40

A 415 500

B 375 460

C 415 500

D 241 271

E 630 800

F 200 230

G 134 134

H 1730 2100

I 6 6

kg 65 80

JET-FANS

You might also like