Socomec Masterys BC & Delphys BC
Socomec Masterys BC & Delphys BC
Socomec Masterys BC & Delphys BC
Single-phase and
three-phase UPS
Certifications
A complete, cost-effective
solution
Online double conversion mode with an
output power factor of 0.9 providing 12%
more active power compare to UPS with a
power factor of 0.8.
Dual input mains allows you to manage
independent power sources.
Increased system availability placing two
UPS in parallel for 1+1 redundancy.
Internal manual bypass for easy
maintenance without power interruption.
Internal batteries providing more than 1 hour
runtime.
Multilanguage display.
34
MASTE 049 C
MASTE 062 A
DEFYS 191 A
Business Critical
Standard communication
features
IN/OUT KVA
BC 115
3/1
15
Communication options
BC 120
3/1
20
Dry-contact interface.
Remote mimic panel (MASTERYS BC).
MODBUS TCP.
MODBUS/JBUS RTU (DELPHYS BC).
Profibus.
NET VISION: professional WEB/SNMP
interface for UPS monitoring and shutdown
management of several operating systems.
BC 315
3/3
15
BC 320
3/3
20
BC 330
3/3
30
BC 340
3/3
40
Cabinet type S
Cabinet type M
Cabinet type T
MASTE 057 A
Electrical options
UPS
30 40
50 60
70
Remote maintenance
T.SERVICE: maintenance software
for continuous 24/7 monitoring of the
SOCOMEC UPS.
Technical data
Sn [kVA]
Pn [kW](0 C 35 C)
Input/output 3/1
Input/output 3/3
Parallel configuration
INPUT
Rated voltage
Voltage tolerance
Rated frequency
Power factor / THDI
OUTPUT
Rated voltage
Voltage tolerance
Rated frequency
Frequency tolerance
Overload
Crest factor
BYPASS
Rated voltage
Voltage tolerance
Rated frequency
Frequency tolerance
EFFICIENCY
Online mode @ 100% of load
ENVIRONMENT
Operating ambient temperature
Relative humidity
Maximum altitude
Acoustic level at 1 m (ISO 3746)
UPS CABINET
Dimensions W x D x H
Weight
(2)
15
13.5
20
18
MASTERYS BC 15-120
40
60
36
54
30
27
80
72
100
90
120
108
1+1
400 V 3ph + N
400 V 3ph
240 V to 480 V(1)
50/60Hz 10%
0.99/<3%
1ph + N: 230 V (can be configured 220/240 V) / 3ph + N: 400 V (can be configured 380/415 V)
static load 1% dynamic load in accordance with VFI-SS-111
50/60 Hz
2% (configurable from 1% to 8%)
125% for 10 minutes, 150% for 1 minute
3:1
rated output voltage
15% (configurable with from 10% to 20%)
50/60 Hz
2% (configurable for Genset compatibility)
up to 93.5%
from 0C up to +35C (from 15C to 25C for maximum battery life)
0% - 95% without condensation
1000 m without derating (max. 3000 m)
< 55 dBA
< 62 dBA
< 65 dBA
< 52 dBA
110 kg
135 kg
Degree of protection
Colours
STANDARDS
Safety
EMC
Performance
Product declaration
180 kg
200 kg
< 68 dBA
700 x 800 x 1930 mm
410 kg
430 kg
480 kg
500 kg
IP20
RAL 7012
EN 62040-1 (TV SD certified), EN 60950-1
EN 62040-2
EN 62040-3 (VFI-SS-111)
CE
dcg_84083
ISO 9001
FM 28237
www.socomec.com
General
Catalogue 2012-2013
Non contractual document.
ISO14001
EMS 553476
35