Aplab AU3000 PDF
Aplab AU3000 PDF
Aplab AU3000 PDF
Mid range computers, local area networks and telecommunications equipment which provide the information that we need to succeed, are part of a rapidly changing business environment. This is the information so vital, it must always be available. A 100% uptime can only be achieved with support from a true Online Uninterruptible Power Systems (UPS). Get Over The Power Problems Recent findings reveal that power problems are the greatest threat to your critical equipments uptime. Business depends on continuous quality power to avoid revenue losses resulting from system failures. The power problems that endanger your critical systems are sags, surges, noise, brown outs, black outs etc. Requirements of quality power protection are: l To provide a clean and stable supply which is
isolated from contaminated utility mains. l To provide continuous AC sinewave power from the charged batteries in case of extreme brown outs or black outs. l To facilitate system expansion by providing features such as Extended back up time, Hand in hand operation for extremely low input supply, Quick recharge facility which enables to charge the batteries in minimum time. l To improve overall system reliability and uptime by providing auto switch over to AC reserve or Bypass supply. All the above features are packaged in Aplab AU3000 Series which is compact, user friendly and simple to install.
SPECIFICATIONS MODEL
RATED POWER INPUT At pf = 0.8 Voltage Frequency OUTPUT Voltage Frequency Regulation Transient Response Inverter Technology Crest Factor Distortion Short Term Overload Efficiency (Typical) Load Power Factor Static Bypass Type BATTERY DC Voltage Backup Time Recharge Time GENERAL Protections
AU 3050
5 KVA 4KW
AU 3075
7.5 KVA 6 KW
50Hz +3Hz
AU 3100
10 KVA 8 KW
230V AC/240V AC (Any One Voltage) Single Phase, Sine Wave 50Hz 0.5Hz Free Running, optional 0.05% & 50Hz 3Hz Sync Mode 1% (Typical) Less than 5% for 100% Load Variation. Recovery in 2 - 3 Cycles PWM (On-Line Double Conversion with IGBT) 3 :1 < 2% (linear Load) 110% for 30 min, 150% for 10sec, 200% for 5 Cycles AC to AC >85% (Linear Load) 0.8 Lagging Optional Feature, with Transfer Time (in Sync Mode) less than 5 msec Sealed Maintenance Free/Lead Acid Tubular (Users Choice) 204V DC (17 nos./12V DC) 384V DC (32 nos./12V DC)
Typically 30 min to 2 hrs. (Higher Back up Time on request) 10 to 12 hrs. Mains Over/Under Voltage, Phase Fail, DC Over/Under Voltage, Inverter Over/Under Voltage, Inverter Overload, Overheat, Built-in Soft/Cold Start and Snubber Circuits for Devices Mains ON, Inverter ON, Battery On Charge, Mains abnormal, Low Battery Imminent, DC Over/Under Voltage, Inverter Over/Under Voltage, Inverter Overload, Overheat, Optional: Load On Inverter, Load On Aux. Supply, Manual Bypass On 16x2 LCD for I/P & O/P Volts, DC Volts, Frequency, Load & Battery percentage (optional-I/P Volts) Built-in Buzzer Operates on Fault Conditions UPS Output is Isolated from Mains Input RS232 (Optional) IP-21 RAL: 9016 (white) & 293C (Blue) 120 100 400W x 650D x 800H 0 C - 45 C (50 C Peak)
O O O
LED Indicators
Digital Metering Audible Alarm Isolation PC Interface Protection Class Finish Weight (Kgs) approx Dimensions (mm) ENVIRONMENT Temperature Humidity
120
POWER ELECTRONICS DIVISION APLAB LIMITED A-5, WAGLE ESTATE, THANE 400 604. INDIA. TEL: 022-2582 1861 FAX: 91-022-2582 3137 E-MAIL: [email protected] www.aplab.com
lBANGALORE Tel: 23463462 Fax: 080-3464128 E-mail: [email protected] lCHENNAI Tel: 26680472 Fax: 044-26680473 Email: [email protected] lKOLKATA Tel: 22848834 Fax: 033-22454294 Email: [email protected] lMUMBAI Tel:29201787 Fax: 022-29209066 Email: [email protected] lNEW DELHI Tel.: 23515183 Fax: 011-23634709 E-mail: [email protected] lSECUNDERABAD Tel.: 27843351 Fax: 040-27897788 Email: [email protected]