160KVA Green Power - Transformerless

Download as pdf or txt
Download as pdf or txt
You are on page 1of 0

Green Power 2.

0
DELPHYS GP from 160 to 500 kVA/kW
ultra high energy efficiency and maximum power availability up to 4 MW
T
h
r
e
e
-
p
h
a
s
e

U
P
S
The solution for
> Data centres
> Telecommunications
> Service sector
> IT Networks / Infrastructures
G
A
M
M
E

D
G
P
5
0
0

A
Energy saving: high efficiency
without compromise
Offers the highest efficiency in the market
using VFI Double Conversion Mode, the
only UPS working-mode that assures total
load protection against all mains quality
problems.
Ultra high efficiency output independently
attested by an international certification
organization in a wide range of load and
voltage operating condition.
Ultra high efficiency in VFI mode is
provided by an innovative topology (3-Level
technology) that has been developed for all
the Green Power UPS ranges.
Full rated power: kW=kVA
No power downgrading when supplying the
latest generation of servers in typical data
centre conditions.
Full power UPS design up to 35 C with
25% more power compared to UPS with
PF=0.8 and 11% more power compared to
UPS with PF=0.9.
Suitable also for leading power factor
loads down to 0.9 without apparent power
derating
Significant cost-saving (TCO)
Maximum energy saving thanks to 96%
output efficiency in true double conversion
mode: 50% saving on energy losses
compared to legacy UPS gives significant
savings in energy bill.
Up to 99% efficiency with FAST ECOMODE.
UPS self-paying with energy saving.
Energy Saver mode for global efficiency
improvement on parallel systems.
kW=kVA means maximum power available
with the same size of UPS, and therefore
less /kW.
With its clean IGBT rectifier, GREEN
POWER 2.0 UPS significantly optimize the
upstream infrastructure without over rating
the supply system (i.e.generator sets,
switches, cables, protection devices).
High efficiency minimizes the amount of
battery for an equivalent back-up time.
Extended battery life and performance:
- long life battery
- very wide input voltage and frequency.
EBS (Expert Battery System) charging
management improves battery service life.
Accurate battery monitoring with UPS
interactivity for even more prolonged service
life.
Attestations
B U R E A U
V E R I T A S
Green Power 2.0 is attested
by Bureau Veritas
Energy saving + Full rated power = reduced TCO
Advantages
Better performance
than the EU Code of Conduct
on efciency of AC UPS
Flywheel
COMPATIBLE
Green Power 2.0
DELPHYS GP from 160 to 500 kVA/kW
Three-phase UPS
Parallel systems
To fulfil the most demanding needs for power
supply availability, flexibility and the installation
to be upgraded.
Modular parallel configurations up to 4 MW,
development without constraint.
Distributed or centralized bypass flexibility.
Twin channel architecture with Static
Transfer Systems.
Distributed or shared battery for energy
storage optimization on parallel systems.
Standard electrical features
Dual input mains.
Integrated maintenance bypass.
Backfeed protection: detection circuit.
EBS (Expert Battery System) for battery
management.
Redundant cooling.
Technical data
DELPHYS GP
Sn [kVA] 160 200 320 400 500
Pn [kW] 160 200 320 400 500
Input / output 3/3
Parallel configuration up to 4 MW
INPUT
Rated voltage 400 V 3ph
Voltage tolerance 200 V to 480 V
(1)
Rated frequency 50/60 Hz
Frequency tolerance 10 Hz
Power factor / THDI > 0.99 / < 2.5%
OUTPUT
Rated voltage 3ph + N 400 V
Voltage tolerance static load 1 % dynamic load in accordance with VFI-SS-111
Rated frequency 50/60 Hz
Frequency tolerance 2% (configurable for GenSet compatibility)
Total output voltage distortion
linear load
ThdU < 1.5%
Total output voltage distortion
non-linear load (lEC 62043-3)
ThdU <3%
Short-circuit current up to 3.4 x In
Overload 125% for 10 minutes, 150% for 1 minute
(1)
Crest factor 3:1
BYPASS
Rated voltage rated output voltage
Voltage tolerance 15% (configurable with from 10% to 20%)
Rated frequency 50/60 Hz
Frequency tolerance 2% (configurable for GenSet compatibility)
EFFICIENCY
Online mode @ 40 % of load up to 96%
Online mode @ 75 % of load up to 96%
Online mode @ 100 % of load up to 96%
Fast EcoMode up to 99%
ENVIRONMENT
Operating ambient temperature from 10C up to +40
(1)
C (from 15C to 25C for maximum battery life)
Relative humidity 0 % - 95 % without condensation
Maximum altitude 1000 m without derating (max. 3000 m)
Acoustic level at 1 m (ISO 3746) < 65 dBA < 67 dBA < 68 dBA < 70 dBA < 72 dBA
UPS CABINET
Dimensions W x D x H 700 x 800 x 1930 mm 1400 x 800 x 1930 mm
1600 x 950 x
1930 mm
Weight 470 kg 490 kg 980 kg 1000 kg 1500 kg
Degree of protection IP20 (other IP as option)
Colours cabinet: RAL 7012, door: silver grey
STANDARDS
Safety EN 62040-1, EN 60950-1
EMC EN 62040-2
Performance EN 62040-3 (VFI-SS-111)
Product declaration CE
(1) Conditions apply.
Electrical options
External maintenance bypass.
Extended back-up time.
Extended battery charger capability.
Shared battery.
Flywheel compatible.
Isolation transformer.
Backfeed isolation device.
ACS synchronisation system.
BHC INTERACTIVE.
Cold start.
FAST ECOMODE.
Standard mechanical features
IP20.
Battery temperature sensor.
Mechanical options
IP31 or higher.
Anti-dust filter.
Standard communication
features
User-friendly multilingual interface with
graphic display.
2 slots for communication options.
RS232 serial port for modem.
Ethernet connection (WEB/SNMP/MODBUS
TCP/email).
USB port for event log access.
Communication options
Advanced server shutdown options for
stand-alone and virtual servers.
4 additional slots for communication options.
ADC interface (configurable voltage-free
contacts).
PROFIBUS.
SMS alert.
Remote maintenance
T.SERVICE: maintenance software
for continuous 24/7 monitoring of the
SOCOMEC UPS.
www.socomec.com
Non contractual document.