EM MultiVIV OutdoorUnits 06 15 20150601125716

Download as pdf or txt
Download as pdf or txt
You are on page 1of 156
At a glance
Powered by AI
The document discusses specifications for LG variable refrigerant flow outdoor units ranging from 6 to 42 tons.

The document describes safety symbols indicating hazardous situations that could result in death, serious injury, or minor/moderate injury as well as situations that may result in equipment or property damage only.

The table of contents includes sections on mechanical specifications, electrical data, outdoor unit dimensions, wiring diagrams, refrigerant flow diagrams, acoustic data, accessories, equipment selection, and design guidelines.

ENGINEERING MANUAL

Variable Refrigerant Flow Outdoor Units


6.0 to 42.0 Tons

PROPRIETARY DATA NOTICE


This document, as well as all reports, illustrations, data, information,
and other materials are the property of LG Electronics U.S.A., Inc., and are
disclosed by LG Electronics U.S.A., Inc. only in confidence.
This document is for design purposes only.

A summary list of safety precautions is on page 3.

For more technical materials such as submittals, catalogs, installation,


owners, and service manuals, visit www.lghvac.com.

For continual product development, LG Electronics U.S.A., Inc. reserves the right to change specifications without notice.
LG Electronics U.S.A., Inc.

TABLE OF CONTENTS
Unit Nomenclature.................................................................................. 4
Outdoor Units and Heat Recovery Units.............................................. 4
Indoor Units.......................................................................................... 5

Placement Considerations.................................................................116
Heat Pump and Heat Recovery Outdoor Units 116
Heat Recovery Unit.......................................................................... 121

Acronyms................................................................................................ 6

Refrigerant Piping Design and Layout Best Practices 123


Design Guideline Summary.............................................................. 124
Pipe Sizing for ARUN Series Heat Pump Systems 126
Pipe Sizing for ARUB Series Heat Recovery Systems 130
LG Engineered Y-branch Kits........................................................... 133
LG Engineered Header Kits.............................................................. 138
LATS Calculated Refrigerant Charge............................................... 140
Selecting Field-Supplied Copper Tubing.......................................... 143
General Information / Guidelines...................................................... 146

Mechanical Specifications..................................................................... 8
Multi V IV Heat Pump and Heat Recovery Outdoor Units........8
Multi V IV Heat Recovery Units.... ........................................................9
General Data......................................................................................... 10
Electrical Data....................................................................................... 31
Outdoor Unit Dimensions.................................................................... 35
Heat Recovery Unit Dimensions......................................................... 41
Wiring Diagrams................................................................................... 44

Electrical Connections....................................................................... 153


ARUN Series Heat Pump Systems (208-230V & 460V) 154
ARUB Series Heat Recovery
Systems (208-230V & 460V)............................................................ 155

Refrigerant Flow Diagrams.................................................................. 60


Acoustic Data........................................................................................ 89
Outdoor Unit Accessories................................................................... 97
Indoor Unit Quick Reference............................................................. 102
Equipment Selection Procedure....................................................... 108
Building Ventilation Design Guide.....................................................113

TABLE OF SYMBOLS
DANGER

This symbol indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
This symbol indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.

CAUTION

This symbol indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
This symbol indicates situations that may result in equipment or property damage accidents only.
This symbol indicates an action should not be completed.

UNIT NOMENCLATURE
Outdoor and Heat Recovery Units

Outdoor Units (ODU)


ARU

072

MULTI V IV Outdoor Unit Engineering Manual

Family
ARU = Multi V Outdoor Unit (Refrigerant R410A)
Type
N = Inverter Heat Pump
B = Inverter Heat Recovery
Nominal Capacity
(Nominal cooling capacity in Btu/h)
072 = 72,000
192 = 192,000
096 = 96,000
216 = 216,000
121 = 121,000
240 = 240,000
144 = 144,000
264 = 264,000
168 = 168,000
288 = 288,000

312/313 = 312,000
336/337 = 336,000
360 = 360,000
384 = 384,000
408 = 408,000

432 = 432,000
456 = 456,000
480 = 480,000
504 = 504,000

Electrical Ratings
B = 208230V/60Hz/3Ph
D = 460V/60Hz/3Ph
Airflow Configuration
T = Top Discharge
Efficiency
E = High Efficiency
Generation
4 = Fourth

Heat Recovery Units (HRU)


PRHR

02

2A

Family
PRHR = Multi V Heat Recovery (HR) unit (Refrigerant R410A)
Number of Ports
02 = Two Ports
03 = Three Ports
04 = Four Ports
Series Number
2A = Series Number
4

INTRODUCTION

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

UNIT NOMENCLATURE
Indoor Units

Indoor Units (IDU)


ARN

07

TN

Family
ARN = Multi V Indoor Unit
(Refrigerant R410A)
Type
U = DC Inverter Heat Pump
Indoor Unit Nominal Capacity
05 = 5,000 Btu/h
18 = 18,000 Btu/h
07 = 7,000 Btu/h
24 = 24,000 Btu/h
09 = 9,000 Btu/h
28 = 28,000 Btu/h
12 = 12,000 Btu/h
30 = 30,000 Btu/h
15 = 15,000 Btu/h
36 = 36,000 Btu/h

42 = 42,000 Btu/h
48 = 48,000 Btu/h
54 = 54,000 Btu/h
76 = 76,000 Btu/h
96 = 96,000 Btu/h

Introduction

Electrical Ratings
3 = 208230V/60Hz/1Ph
Model

B3 = Ducted (low static - bottom return)


B4 = Ducted (low static - bottom return)
B8 = Ducted (high static)
BG = Ducted (high static)
BR = Ducted (high static)
CE = Floor Standing (small frame)
CF = Floor Standing (large frame)
L1 = Ducted (low static)

L2 = Ducted (low static)


L3 = Ducted (low static)
NJ = Vertical/Horizontal Air Handling Unit
NK = Vertical/Horizontal Air Handling Unit
SB = Wall Mounted
SC = Wall Mounted
TT = 1-Way Ceiling Cassette
TU = 1-Way Ceiling Cassette

TL = 2-Way Ceiling Cassette


TM = 4-Way Ceiling Cassette
TN = 4-Way Ceiling Cassette
TP = 4-Way Ceiling Cassette
TQ = 4-Way Ceiling Cassette
TR = 4-Way Ceiling Cassette
VE = Convertible Surface Mounted
VJ = Ceiling Suspended

Feature
U = Uncased
A, C, L, R = Standard*
G = Low Static
*Plasma filter kit accessories are available separately. Always follow all local, state, and national building codes with the use of
this or any product.
Generation
2 = Second
4 = Fourth
A = Second, Revision A

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

INTRODUCTION

ACRONYMS

MULTI V IV Outdoor Unit Engineering Manual

%OA

Percentage Outdoor Air

IDU

Indoor Unit

%RA

Percentage Return Air

IEQ

Indoor Environmental Quality (LEED Related)

ABS

Acrylonitrile Butadiene Styrene

ISO

International Organization for Standardization

AC

Air Conditioner

IUCF

Indoor Unit Correction Factor

ACP

Advanced Control Platform

KTL

Korea Testing Laboratories

AHRI

Air-Conditioning, Heating, and Refrigeration Institute

LEED

Leadership in Energy and Environmental Design

ASHRAE

American Society of Heating, Refrigeration, and


Air Conditioning

LGAP

LG Air Conditioner Protocol

AHU

Air Handling Unit

MAT

Mixed Air Temperature

AWG

American Wire Gauge

MBh

Thousands BTUs per hour

BLDC

Brushless Digitally Controlled/Direct

MCA

Maximum Circuit Ampacity

Btu/h

British Thermal Units per hour

MFS

Maximum Fuel Size

CCR

Corrected Capacity Ratio

MOCP

Maximum Overcurrent Protection

CDOA

Coupled Dedicated Outdoor Air

MR

Materials and Resources (LEED Related)

CFM

Cubic Feet per Minute

CI

Commercial Interiors (LEED Related)

COP

Coefficient Of Performance

NEC

CR

Combination Ratio

NO

Normally Open

CR

Credit (LEED Related)

OAT

Outdoor Air Temperature

CS

Core and Shell (LEED Related)

O&M

Existing Building Operations and Maintenance (LEED Related)

DB

Dry Bulb

ODU

Outdoor Unit

dB(A)

Decibels with A frequency weighting

OUCF

Outdoor Unit Correction Factor

DDOAS

Decoupled Dedicated Outdoor Air

PDI

Power Distribution Integrator

NC

New Construction (LEED Related)


Normally Closed
National Electrical Code

DI

Digital Input

PI

Power Input

DO

Digital Output

PR

Prerequisite (LEED Related)

EA

Energy and Atmosphere (LEED Related)

PTAC

Packaged Terminal Air Conditioner

EEV

Electronic Expansion Valve

PVE

Polyvinyl Ether

ELF

Equivalent Length in Feet

RAT

Return Air Temperature

EPDM

Ethylene Propylene Diene M-Class Rubber

RCL

Refrigerant Concentration Limit

ESP

External Static Pressure

RP

Regional Priority (LEED Related)

ETL

Electronic Testing Laboratories

RUR

Running Unit Ratio

FLA

Full Load Amps

K12

K-12 Schools (LEED Related)

GND

Ground

USGBC

U.S. Green Building Council (LEED Related)

HACR

Heating, Air Conditioning, and Refrigeration

VAH

Vertical Air Handler

HiPOR

High Pressure Oil Return

VAV

Variable Air Volume

H/M/L

High/Medium/Low

VRF

Variable Refrigerant Flow

HVAC

Heating, , Ventilation and Air Conditioning

VRP

Ventilation Rate Procedure

IAQ

Indoor Air Quality

WB

Wet Bulb

ID

Innovations in Design (LEED Related)

WE

Water Efficiency (LEED Related)

INTRODUCTION

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

PRODUCT DATA
Mechanical Specifications on page 8
General Data on page 10
Electrical Data on page 31
Outdoor Unit Dimensions on page 35
Heat Recovery Unit Dimensions on page 41
Wiring DiagramsOutdoor Units on page 44
Refrigerant Flow Diagrams on page 60
Acoustic Data on page 89
Outdoor Unit Accessories on page 97
Indoor Unit Quick Reference on page 102

MECHANICAL SPECIFICATIONS
VRF Multi V IV Outdoor Units

Multi V IV Outdoor Units

MULTI V IV Outdoor Unit Engineering Manual

General

LG Multi V IV Variable Refrigerant Flow


(VRF) comprises of a Heat Pump system or
a Heat Recovery System with a single, dual
or triple frame outdoor unit connected to
indoor units with a single refrigerant piping
system connectable using factory designed
and supplied Y-branches and Headers, and
having integrated controls.
An LG Multi V IV Heat pump system is a
VRF system that can operate in either cooling or heating mode, whereas an LG Multi V
IV Heat Recovery system is a VRF system
that can operate in either heating or cooling
mode simultaneously. The Heat Recovery
unit is capable of being designed for minimum piping and maximum design flexibility.
Each piping port is independently capable of
operating in either heating or cooling mode
regardless of the mode other piping ports
on the same heat recovery unit. The system
shall be capable of changing mode of individual indoor units or zones (cooling to heating or heating to cooling) within a maximum
time of three (3) minutes to ensure indoor
temperature can be properly maintained.
LG components are manufactured in a facility registered to ISO 9001 and ISO 14001,
which is a set of standards applying to environmental protection set by the International
Organization for Standardization (ISO). The
units are listed by Intertek Electrical Testing
Laboratories (ETL) and bear the ETL label.
Wiring in these units are in accordance with
the National Electrical Code (NEC).

Temperature Ranges
Heat Pump Systems

Heat Pump systems can operate in heating


only mode from -13F to +61F ambient wet
bulb. Heat Pump systems can operate in
cooling mode from 14F to 122F. Optional
low ambient cooling kit extends cooling only
operating range from 14F to -9.9F.

Heat Recovery Systems

Heat Recovery systems can operate in


heating only mode (i.e. all indoor units in
heating mode) from -13F to +61F ambient
wet bulb.
Heat Recovery systems can operate in
cooling-only mode from 14F to 122F
8

PRODUCT DATA

dry bulb. Optional low ambient cooling kit


extends cooling only operation range (i.e.
all indoor units in cooling mode) from 14F
to -9.9F. Heat Recovery cooling or heating
based synchronous operation range is 14F
to 61F.

Casing / Frame

Heat Pump and Heat Recovery outdoor units


are constructed with galvanized steel, bonderized and finished with a baked enamel
paint. Each frame has a removable inspection panel no greater than six (6) inches tall
and twelve (12) inches wide to allow access
to service tool connection, dip switches, auto
addressing and error codes. The entire front
panel of the outdoor unit is removable for
maintenance.
Outdoor unit frames are completely factory
assembled, piped and wired. Dual and triple
frame outdoor units need to be field piped
with factory designed and supplied Y-branch
kits to manifold them together into a single
refrigerant circuit.

Refrigerant System

The refrigeration system consists of a single


refrigeration circuit and uses R410A refrigerant. The outdoor unit is provided with factory
installed components, including a refrigerant
strainer, check valves, oil separator, accumulator, four-way reversing valve, electronic
controlled expansion valve (EEV), high
and low side charging ports, high pressure
safety switch, service valves, and interconnecting piping. Also included is an integral
subcooler assembly consisting of a double
spiral tube-type subcooling heat exchanger
and EEV providing refrigerant subcooling
modulation up to 23F.

Refrigeration Oil Control


Oil return system utilizes the following
technologies:

HiPOR (High Pressure Oil Return)

Oil is captured from compressor discharge


by the centrifugal oil separator and then
returned to the compressor through a separator oil injection pipe, preventing mixing of
oil and refrigerant on the suction side of the
compressor.

Smart Oil Control

Monitors the oil level inside the compressor


and only initiates oil return cycle to flush
oil in pipe system back to the compressor,
when the oil level is too low. Timed oil return
cycles are eliminated and compressor is
protected from running at oil levels that are
too low.

Compressors

All 3-phase outdoor unit frames 80MBh


are equipped with one hermetic digitally
controlled inverter driven scroll compressor
to modulated capacity (variable from 15 to
150Hz, modulate in 0.5Hz increments). All 3
phase outdoor unit frames 80MBh nominal
capacity are equipped with two digitally
controlled inverter-driven hermetic scroll
compressors to modulated capacity (variable
from 15 to 150Hz, modulate in 0.5 Hz
increments). An internal thermal overload
and a factory-mounted 60 watt crankcase
heater is included on all compressors.

Outdoor Unit Coil

Heat Pump and Heat Recovery outdoor unit


coils are of a nonferrous construction with
louvered fins on copper tubing, and are
protected with an integral metal guard.
Coil fins have a factory applied corrosion
resistant GoldFin material with hydrophilic
coating.

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

MECHANICAL SPECIFICATIONS
Multi V IV Outdoor Units / Multi V Heat Recovery Units

Fans and Motors

All outdoor unit frames <80MBh include one direct drive, variable
speed propeller type fan. All outdoor unit frames >80MBh include two
direct drives, variable speed propeller type fans.
All fan motors have inherent protection, permanently lubricated bearings, and are variable speed with a maximum speed up to 1,100 rpm.
Raised guards are provided to limit contact with moving parts.
All Heat Pump and Heat Recovery outdoor units have vertical
discharge airflow. Optional factory-provided air guides can be field
installed to change discharge airflow from vertical to horizontal.
Outdoor units have a static pressure capability up to 0.32 WG with a
DIP switch setting to accommodate additional external static pressure.

Controls

Heat pump and heat recovery outdoor units are factory wired with
necessary electrical control components, integral microprocessors,
printed circuit boards, thermistors, sensors, terminal blocks, and lugs
for power wiring.
The control circuit between the indoor units, heat recovery unit(s)
(Multi V heat recovery systems only) and the outdoor unit is a
variable low voltage DC communication completed using a twoconductor, stranded, and shielded cable for the RS-485 daisy chain
communication.
Microprocessor-based algorithms provide component protection,
soft-start capability, refrigeration system pressure, temperature,
defrost, and ambient control.

Electrical

Both Heat Pump and Heat Recovery outdoor units are available in
choice of 208-230V 60 Hz, 3-phase or 460V, 60 Hz, 3-phase power
supply. The units include over/undercurrent protection.

General

Multi V heat recovery units are for use with Multi V heat recovery
outdoor units to permit simultaneous heating and cooling operation.
Heat recovery units have two (2), three (3), or four (4) ports for connections to indoor units. Each port is capable of connecting from one
(1) indoor unit up to eight (8) indoor units up to a maximum nominal
capacity of 54 MBh. Individual indoor units 54 MBh nominal capacity must use two (2) neighboring heat recovery unit ports twinned
together with a Y-branch kit.
Heat recovery ports can operate in heating or cooling mode independently, regardless of the mode of any other port on the unit or in the
system except where heat recovery units are twinned.

Casing and Construction

Heat recovery units are completely factory assembled, internally


piped, wired, and are designed for indoor installation. Casing is constructed of galvanized steel, and houses piping, valves and controls
to divert refrigerant controlling each port to operate in either heating
or cooling mode. Heat recovery units contain one double spiral subcooling heat exchanger per port, are internally insulated, and do not
require a condensate drain.

Refrigerant Valves

Each heat recovery port is circuited with two two-position solenoid


valves to control R410A refrigerant flow path. Optional isolation
valves can be field supplied and installed for ease of service externally at the heat recovery unit or any other position in the piping
system so that servicing may be accomplished without evacuating
the entire system refrigerant charge.

Refrigerant System

Heat recovery units require R410A refrigerant. The units can be


piped in series or parallel to minimize material cost and labor. Up to

Four-port Heat Recovery Unit.


16 Heat Recovery units can be
piped in series as long as the total
indoor unit nominal capacity does
not exceed 192 MBh. Other piping
length parameters:
Indoor units up to 131 equivalent feet of piping length from
the Heat Recovery unit to
which it is connected.
Indoor units up to 295 equivalent feet of piping length from the first branch.
Indoor units cannot exceed 131 feet in elevation connected to
separate parallel heat recovery units (HRUs).
Elevation difference between the highest and lowest elevation
indoor unit cannot exceed 131 feet.
Elevation difference between the highest and lowest elevation
heat recovery unit cannot exceed 49 feet.
Elevation difference between indoor units connected to one HRU
or series connected HRUs cannot exceed 49 feet.
All refrigerant lines from the outdoor unit to the heat recovery units,
and from the heat recovery units to the indoor units must be separately field insulated.

Electrical

Heat recovery units require 208-230V, 1-phase, 60 Hz electrical


power, and are capable of operation within 10% of nominal voltage.

Controls

Heat recovery units include factory installed control boards and


integral microprocessors that communicate with the main control
board in the outdoor unit and interface with the VRF equipment
controls system. The control circuit cable between the indoor units,
heat recovery unit, and the outdoor unit must be field installed and
provided using a two-conductor, stranded and shielded cable for the
RS-485 daisy chain communication.

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

PRODUCT DATA

Product Data

Multi V Heat Recovery Units

GENERAL DATA

MULTI V IV Outdoor Unit Engineering Manual

ARUN Series Heat Pump Outdoor Unit Specifications

Table 1: Single-Frame 208-230V Heat Pump Units.


6.0 Ton
Combination Unit Model Number
ARUN072BTE4
Individual Component Model Numbers
Cooling Performance
72,000
Nominal Cooling Capacity (Btu/h)1
69,000
Rated Cooling Capacity (Btu/h)2
Heating Performance
81,000
Nominal Heating Capacity (Btu/h)1
2
77,000
Rated Heating Capacity (Btu/h)
Operating Range
14 to 122
Cooling (F DB)3
-13 to +61
Heating (F WB)
Compressor
HSS DC Scroll x 1
Inverter Quantity
PVE/FVC68D
Oil/Type
Fan (Top Discharge)
Propeller (BLDC)
Type
0.75 x 1
Motor Output (kW) x Qty.
Motor/Drive
0 - 850
Operating Range Cooling
(RPM)
80 - 850
Heating
7,400
Maximum Air Volume (CFM)
Unit Data
R410A
Refrigerant Type
EEV/Indoor Unit
Refrigerant Control/Location
1 - 13
Min. to Max. No. Indoor Units/System4
58.5
Sound Pressure dB(A)5
430
Net Unit Weight (lbs.)
452
Shipping Weight (lbs.)
2 x 18
Communication Cables6,7
Heat Exchanger
Material and Fin Coating
3/14
Rows/Fins per inch
Piping8
3/8 Braze
Liquid Line Connection (in., OD)
3/4 Braze
Vapor Line Connection (in., OD)
16.9
Factory Charge lbs. of R410A

8.0 Ton
ARUN096BTE4
-

10.0 Ton
ARUN121BTE4
-

12.0
ARUN144BTE4
-

14.0
ARUN168BTE4
-

96,000
92,000

120,000
114,000

144,000
138,000

168,000
160,000

108,000
103,000

135,000
129,000

162,000
154,000

189,000
180,000

14 to 122
-13 to +61

14 to 122
-13 to +61

14 to 122
-13 to +61

14 to 122
-13 to +61

HSS DC Scroll x 1
PVE/FVC68D

HSS DC Scroll x 1
PVE/FVC68D

HSS DC Scroll x 2
PVE/FVC68D

HSS DC Scroll x 2
PVE/FVC68D

Propeller (BLDC)
Propeller (BLDC)
Propeller (BLDC)
0.60 x 2
0.60 x 2
0.60 x 2
Brushless Digitally Controlled/Direct
0 - 1,050
0 - 1,050
0 - 1,100
80 - 1,050
80 - 1,050
80 - 1,100
9,850
9,850
10,200

Propeller (BLDC)
0.60 x 2

R410A
EEV/Indoor Unit
1 - 16
59.0
540
573
2 x 18

R410A
EEV/Indoor Unit
1 - 29
59.5
628
661
2 x 18

PRODUCT DATA

R410A
EEV/Indoor Unit
1- 24
59.5
628
661
2 x 18

Copper Tube/Aluminum Fin and GoldFin/Hydrophilic


3/14
3/14
3/14
3/8 Braze
7/8 Braze
23.6

1
Nominal capacity applied with non-ducted indoor units, and is rated 0 ft. above sea level with 25 ft.
of refrigerant line per indoor unit and a 0 ft. level difference between outdoor and indoor units. All capacities are net with a Combination Ratio between 95105%.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80F dry bulb (DB) and 67F
wet bulb (WB) and outdoor ambient conditions of 95F dry bulb (DB) and 75F wet bulb (WB).
Nominal heating capacity rating obtained with air entering the indoor unit at 70F dry bulb (DB) and
59F wet bulb (WB) and outdoor ambient conditions of 47F dry bulb (DB) and 43F wet bulb (WB).
2
Rated capacity is certified under AHRI Standard 1230. See www.ahrinet.org for information.
3
Cooling range with Low Ambient Baffle Kit (sold separately) is -9.9F to +122F.
4
The System Combination Ratio must be between 50130%.

10

R410A
EEV/Indoor Unit
1 - 20
59.0
540
573
2 x 18

1/2 Braze
1-1/8 Braze
23.6

1/2 Braze
1-1/8 Braze
23.6

0 - 1,100
80 - 1,100
10,200

3/14
5/8 Braze
1-1/8 Braze
23.6

Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded, and must comply
with applicable local and national codes. Ensure the communication cable is properly grounded at the
master unit only. Do not ground the ODU-IDU communication cable at any other point.
7
Power wiring cable is field provided and must comply with the applicable local and national codes. See
page 31 for detailed electrical data.
8
Refer to the Refrigerant Piping section of this manual for correct line sizing. Contractor must use LG
manufactured Y-Branch and Header Kits only. Designer must verify refrigerant piping design
configuration using LGs computerized refrigerant piping (LATS Multi V) software to validate the pipe
design.
5
6

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

GENERAL DATA
ARUN Series Heat Pump Outdoor Unit Specifications

18.0 Ton
ARUN216BTE4
ARUN072BTE4 +
ARUN144BTE4

20.0 Ton
ARUN240BTE4
ARUN096TE4 +
ARUN144BTE4

22.0 Ton
ARUN264BTE4
ARUN121BTE4 +
ARUN144BTE4

216,000
206,000

240,000
228,000

264,000
250,000

243,000
230,000

270,000
256,000

297,000
282,000

14 to 122
-13 to +61

14 to 122
-13 to +61

14 to 122
-13 to +61

HSS DC Scroll x 3
PVE/FVC68D

HSS DC Scroll x 3
PVE/FVC68D

HSS DC Scroll x 3
PVE/FVC68D

Propeller (BLDC)
Propeller (BLDC)
0.75 + 0.60 x 2
0.60 x 2 + 0.60 x 2
Brushless Digitally Controlled/Direct
0 - 1,100
0 - 1,100
80 - 1,100
80 - 1,100
17,600
20,050

Propeller (BLDC)
0.60 x 2 + 0.60 x 2
0 - 1,100
80 - 1,100
20,050

R410A
EEV/Indoor Unit

R410A
EEV/Indoor Unit

R410A
EEV/Indoor Unit

1 - 35

1 - 39

1 - 42

62.0
430 + 628
452 + 661
2 x 18

62.3
540 + 628
573 + 661
2 x 18

62.3
540 + 628
573 + 661
2 x 18

Copper Tube/Aluminum Fin and GoldFin/Hydrophilic


3/14
3/14
3/8 + 1/2 Braze
3/4 + 1-1/8 Braze
16.9 + 23.6

1
Nominal capacity applied with non-ducted indoor units, and is rated 0 ft. above sea level with 25 ft.
of refrigerant line per indoor unit and a 0 ft. level difference between outdoor and indoor units. All capacities are net with a Combination Ratio between 95105%.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80F dry bulb (DB) and 67F
wet bulb (WB) and outdoor ambient conditions of 95F dry bulb (DB) and 75F wet bulb (WB).
Nominal heating capacity rating obtained with air entering the indoor unit at 70F dry bulb (DB) and
59F wet bulb (WB) and outdoor ambient conditions of 47F dry bulb (DB) and 43F wet bulb (WB).
2
Rated capacity is certified under AHRI Standard 1230. See www.ahrinet.org for information.
3
Cooling range with Low Ambient Baffle Kit (sold separately) is -9.9F to +122F.
4
The System Combination Ratio must be between 50130%.

3/8 + 1/2 Braze


7/8 + 1-1/8 Braze
23.6 + 23.6

Product Data

Table 2: Dual-Frame 208-230V Heat Pump Units.


Combination Unit Model
16.0 Ton
Number
ARUN192BTE4
Individual Component Model
ARUN072BTE4 +
Numbers
ARUN121BTE4
Cooling Performance
192,000
Nominal Cooling Cap. (Btu/h)1
2
184,000
Rated Cooling Cap. (Btu/h)
Heating Performance
216,000
Nominal Heating Cap. (Btu/h)1
2
206,000
Rated Heating Cap. (Btu/h)
Operating Range
14 to 122
Cooling (F DB)3
-13 to +61
Heating (F WB)
Compressor
HSS DC Scroll x 2
Inverter Quantity
PVE/FVC68D
Oil/Type
Fan (Top Discharge)
Propeller (BLDC)
Type
0.75 + 0.60 x 2
Motor Output (kW) x Qty.
Motor/Drive
0 - 1,050
Cooling
Oper. Range
(RPM)
80 - 1,050
Heating
17,250
Maximum Air Volume (CFM)
Unit Data
R410A
Refrigerant Type
EEV/Indoor Unit
Refrigerant Control/Location
Min. to Max. No. Indoor Units/
1 - 32
System4
5
61.8
Sound Pressure dB(A)
430 + 540
Net Unit Weight (lbs.)
452 + 573
Shipping Weight (lbs.)
2 x 18
Communication Cables6,7
Heat Exchanger
Material and Fin Coating
3/14
Rows/Fins per inch
Piping8
3/8 + 1/2 Braze
Liquid Line Conn. (in., OD)
3/4
+ 1-1/8 Braze
Vapor Line Conn. (in., OD)
16.9 + 23.6
Factory Charge lbs. of R410A

3/14
1/2 + 1/2 Braze
1-1/8 + 1-1/8 Braze
23.6 + 23.6

Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded, and must comply
with applicable local and national codes. Ensure the communication cable is properly grounded at the
master unit only. Do not ground the ODU-IDU communication cable at any other point.
7
Power wiring cable is field provided and must comply with the applicable local and national codes. See
page 31 for detailed electrical data.
8
Refer to the Refrigerant Piping section of this manual for correct line sizing. Contractor must use LG
manufactured Y-Branch and Header Kits only. Designer must verify refrigerant piping design configuration using LGs computerized refrigerant piping (LATS Multi V) software to validate the pipe design.
5
6

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

PRODUCT DATA

11

GENERAL DATA
ARUN Series Heat Pump Outdoor Unit Specifications

Table 3: Dual-Frame 208-230V Heat Pump Units, continued.


Combination Unit Model Number

MULTI V IV Outdoor Unit Engineering Manual

Individual Component Model Numbers


Cooling Performance
Nominal Cooling Cap. (Btu/h)1
Rated Cooling Cap. (Btu/h)2
Heating Performance
Nominal Heating Cap. (Btu/h)1
Rated Heating Cap. (Btu/h)2
Operating Range
Cooling (F DB)3
Heating (F WB)
Compressor
Inverter Quantity
Oil/Type
Fan (Top Discharge)
Type
Motor Output (kW) x Qty.
Motor/Drive
Cooling
Operation Range (RPM)
Heating
Maximum Air Volume (CFM)
Unit Data
Refrigerant Type
Refrigerant Control/Location
Min. to Max. No. Indoor Units/System4
Sound Pressure dB(A)5
Net Unit Weight (lbs.)
Shipping Weight (lbs.)
Communication Cables6,7
Heat Exchanger
Material and Fin Coating
Rows/Fins per inch
Piping8
Liquid Line Conn. (in., OD)
Vapor Line Conn. (in., OD)
Factory Charge lbs. of R410A

24.0 Ton
ARUN288BTE4
ARUN144BTE4 +
ARUN144BTE4

26.0 Ton
ARUN313BTE4
ARUN144BTE4 +
ARUN168BTE4

28.0 Ton
ARUN337BTE4
ARUN168BTE4 +
ARUN168BTE4

288,000
274,000

312,000
296,000

336,000
320,000

324,000
308,000

351,000
334,000

378,000
361,000

14 to 122
-13 to +61

14 to 122
-13 to +61

14 to 122
-13 to +61

HSS DC Scroll x 4
PVE/FVC68D

HSS DC Scroll x 4
PVE/FVC68D

HSS DC Scroll x 4
PVE/FVC68D

Propeller (BLDC)
0.60 x 2 + 0.60 x 2

Propeller (BLDC)
0.60 x 2 + 0.60 x 2

0 - 1,100
80 - 1,100
20,400

Propeller (BLDC)
0.60 x 2 + 0.60 x 2
Brushless Digitally Controlled/Direct
0 - 1,100
80 - 1,100
20,400

R410A
EEV/Indoor Unit
1 - 45
62.5
628 + 628
661 + 661
2 x 18

R410A
EEV/Indoor Unit
1 - 52
62.5
628 + 628
661 + 661
2 x 18

R410A
EEV/Indoor Unit
1 - 55
62.5
628 + 628
661 + 661
2 x 18

3/14

12

PRODUCT DATA

Copper Tube/Aluminum Fin and GoldFin/Hydrophilic


3/14

1/2 + 1/2 Braze


1-1/8 + 1-1/8 Braze
23.6 + 23.6

1
Nominal capacity applied with non-ducted indoor units, and is rated 0 ft. above sea level with 25 ft.
of refrigerant line per indoor unit and a 0 ft. level difference between outdoor and indoor units. All capacities are net with a Combination Ratio between 95105%.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80F dry bulb (DB) and 67F
wet bulb (WB) and outdoor ambient conditions of 95F dry bulb (DB) and 75F wet bulb (WB).
Nominal heating capacity rating obtained with air entering the indoor unit at 70F dry bulb (DB) and
59F wet bulb (WB) and outdoor ambient conditions of 47F dry bulb (DB) and 43F wet bulb (WB).
2
Rated capacity is certified under AHRI Standard 1230. See www.ahrinet.org for information.
3
Cooling range with Low Ambient Baffle Kit (sold separately) is -9.9F to +122F.
4
The System Combination Ratio must be between 50130%.

0 - 1,100
80 - 1,100
20,400

1/2 + 5/8 Braze


1-1/8 + 1-1/8 Braze
23.6 + 23.6

3/14

5/8 + 5/8 Braze


1-1/8 + 1-1/8 Braze
23.6 + 23.6

Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded, and must comply
with applicable local and national codes. Ensure the communication cable is properly grounded at the
master unit only. Do not ground the ODU-IDU communication cable at any other point.
7
Power wiring cable is field provided and must comply with the applicable local and national codes. See
page 31 for detailed electrical data.
8
Refer to the Refrigerant Piping section of this manual for correct line sizing. Contractor must use LG
manufactured Y-Branch and Header Kits only. Designer must verify refrigerant piping design configuration using LGs computerized refrigerant piping (LATS Multi V) software to validate the pipe design.
5
6

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

GENERAL DATA
ARUN Series Heat Pump Outdoor Unit Specifications

Motor Output (kW) x Qty.


Motor/Drive
Cooling
Operating
Range (RPM) Heating
Maximum Air Volume (CFM)
Unit Data
Refrigerant Type
Refrigerant Control/Location
Min. to Max. No. Indoor Units/
System5
Sound Pressure dB(A)6
Net Unit Weight (lbs.)
Shipping Weight (lbs.)
Communication Cables7,8
Heat Exchanger
Material and Fin Coating
Rows/Fins per inch
Piping9
Liquid Line Conn. (in., OD)
Vapor Line Conn (in., OD)
Factory Charge lbs. of R410A

28.0 Ton
ARUN336BTE4
ARUN096BTE4 +
ARUN096BTE4 +
ARUN144BTE4

30.0 Ton
ARUN360BTE4
ARUN096BTE4 +
ARUN121BTE4 +
ARUN144BTE4

32.0 Ton
ARUN384BTE4
ARUN096BTE4 +
ARUN145BTE4 +
ARUN145BTE4

34.0 Ton
ARUN408BTE4
ARUN121BTE4 +
ARUN145BTE4 +
ARUN145BTE4

336,000
320,000

360,000
342,000

384,000
366,000

408,000
390,000

378,000
361,000

405,000
387,000

432,000
412,000

459,000
437,000

14 to 122
-13 to +61

14 to 122
-13 to +61

14 to 122
-13 to +61

14 to 122
-13 to +61

HSS DC Scroll x 4
PVE/FVC68D

HSS DC Scroll x 4
PVE/FVC68D

HSS DC Scroll x 5
PVE/FVC68D

HSS DC Scroll x 5
PVE/FVC68D

Propeller (BLDC)
Propeller (BLDC)
Propeller (BLDC)
0.60 x 2 + 0.60 x 2
0.60 x 2 + 0.60 x 2
0.60 x 2 + 0.60 x 2
+ 0.60 x 2
+ 0.60 x 2
+ 0.60 x 2
Brushless Digitally Controlled/Direct
0 - 1,100
0 - 1,100
0 - 1,100
80 - 1,100
80 - 1,100
80 - 1,100
29,900
29,900
30,250

Propeller (BLDC)
0.60 x 2 + 0.60 x 2
+ 0.60 x 2

R410A
EEV/Indoor Unit

R410A
EEV/Indoor Unit

R410A
EEV/Indoor Unit

R410A
EEV/Indoor Unit

R410A
EEV/Indoor Unit

1 - 52

1 - 55

1 - 58

1 - 61

1 - 64

63.8
430 + 540 + 628
452 + 573 + 661
2 x 18

63.9
540 + 540 + 628
573 + 573 + 661
2 x 18

63.9
540 + 540 + 628
573 + 573 + 661
2 x 18

64.1
540 + 672 + 672
573 + 705 + 705
2 x 18

64.1
540 + 672 + 672
573 + 705 + 705
2 x 18

0.75 + 0.60 x 2
+ 0.60 x 2
0 - 1,100
80 - 1,100
27,450

3/14
3/8+3/8+1/2 Braze
3/4+7/8+1-1/8 Braze
16.9 + 23.6 + 23.6

Copper Tube/Aluminum Fin and GoldFin/Hydrophilic


3/14
3/14
3/14
3/8+3/8+1/2 Braze
7/8+7/8+1-1/8 Braze
23.6 + 23.6 + 23.6

1
ARUN145BTE4/ARUN145DTE4, ARUN169BTE4/ARUN169DTE4 frames are ONLY for use in large
capacity triple frame combinations. They cannot be used as stand alone models or in a dual frame
combination. These frames ARE NOT interchangeable with ARUN121BTE4/ARUN121DTE4, ARUN144BTE4/ARUN144DTE4, ARUN168BTE4/ARUN168DTE4 single frame models.
2
Nominal capacity applied with non-ducted indoor units, and is rated 0 ft. above sea level with 25 ft.
of refrigerant line per indoor unit and a 0 ft. level difference between outdoor and indoor units. All
capacities are net with a Combination Ratio between 95105%.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80F dry bulb (DB) and 67F
wet bulb (WB) and outdoor ambient conditions of 95F dry bulb (DB) and 75F wet bulb (WB).
Nominal heating capacity rating obtained with air entering the indoor unit at 70F dry bulb (DB) and
59F wet bulb (WB) and outdoor ambient conditions of 47F dry bulb (DB) and 43F wet bulb (WB).
3
Rated capacity is certified under AHRI Standard 1230. See www.ahrinet.org for information.
4
Cooling range with Low Ambient Baffle Kit (sold separately) is -9.9F to +122F.

Product Data

Table 4: Triple-Frame 208-230V Heat Pump Units.


Combination Unit Model
26.0 Ton
Number
ARUN312BTE4
ARUN072BTE4 +
Individual Component Model
ARUN096BTE4 +
1
Numbers
ARUN144BTE4
Cooling Performance
312,000
Nominal Cooling Cap. (Btu/h)2
296,000
Rated Cooling Cap. (Btu/h)3
Heating Performance
351,000
Nominal Heating Cap. (Btu/h)2
334,000
Rated Heating Cap. (Btu/h)3
Operating Range
14 to 122
Cooling (F DB)4
-13 to +61
Heating (F WB)
Compressor
HSS DC Scroll x 4
Inverter Quantity
PVE/FVC68D
Oil/Type
Fan (Top Discharge)
Propeller (BLDC)
Type

0 - 1,100
80 - 1,100
30,250

3/14

3/8+1/2+1/2 Braze
3/8+5/8+5/8 Braze
1/2+5/8+5/8 Braze
7/8+1-1/8+1-1/8 Braze 7/8+1-1/8+1-1/8 Braze 1-1/8+1-1/8+1-1/8 Braze
23.6 + 23.6 + 23.6
23.6 + 23.6 + 23.6
23.6 + 23.6 + 23.6

The System Combination Ratio must be between 50130%.


Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
7
All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded, and must comply
with applicable local and national codes. Ensure the communication cable is properly grounded at the
master unit only. Do not ground the ODU-IDU communication cable at any other point.
8
Power wiring cable is field provided and must comply with the applicable local and national codes. See
page 31 for detailed electrical data.
9
Refer to the Refrigerant Piping section of this manual for correct line sizing. Contractor must use LG
manufactured Y-Branch and Header Kits only. Designer must verify refrigerant piping design configuration using LGs computerized refrigerant piping (LATS Multi V) software to validate the pipe design.
5
6

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

PRODUCT DATA

13

GENERAL DATA
ARUN Series Heat Pump Outdoor Unit Specifications

Table 5: Triple-Frame 208-230V Heat Pump Units, continued.


Combination Unit Model
Number

MULTI V IV Outdoor Unit Engineering Manual

Individual Component Model


Numbers1

36.0 Ton
ARUN432BTE4
ARUN145BTE4 +
ARUN145BTE4 +
ARUN145BTE4

38.0 Ton
ARUN456BTE4
ARUN145BTE4 +
ARUN145BTE4 +
ARUN169BTE4

40.0 Ton
ARUN480BTE4
ARUN145BTE4 +
ARUN169BTE4 +
ARUN169BTE4

42.0 Ton
ARUN504BTE4
ARUN169BTE4 +
ARUN169BTE4 +
ARUN169BTE4

Cooling Performance
432,000
456,000
480,000
504,000
Nominal Cooling Cap. (Btu/h)2
414,000
436,000
458,000
479,000
Rated Cooling Cap. (Btu/h)3
Heating Performance
486,000
513,000
540,000
567,000
Nominal Heating Cap. (Btu/h)2
462,000
488,000
514,000
539,000
Rated Heating Cap. (Btu/h)3
Operating Range
14 to 122
14 to 122
14 to 122
14 to 122
Cooling (F DB)4
-13 to +61
-13 to +61
-13 to +61
-13 to +61
Heating (F WB)
Compressor
HSS DC Scroll x 6
HSS DC Scroll x 6
HSS DC Scroll x 6
HSS DC Scroll x 6
Inverter Quantity
PVE/FVC68D
PVE/FVC68D
PVE/FVC68D
PVE/FVC68D
Oil/Type
Fan (Top Discharge)
Propeller (BLDC)
Propeller (BLDC)
Propeller (BLDC)
Propeller (BLDC)
Type
0.60 x 2 + 0.60 x 2 + 0.60 x 2 0.60 x 2 + 0.60 x 2 + 0.60 x 2 0.60 x 2 + 0.60 x 2 + 0.60 x 2 0.60 x 2 + 0.60 x 2 + 0.60 x 2
Motor Output (kW) x Qty.
Brushless Digitally Controlled/Direct
Motor/Drive
0
1,100
0
- 1,100
0 - 1,100
0 - 1,100
Cooling
Operating
Range (RPM) Heating
80 - 1,100
80 - 1,100
80 - 1,100
80 - 1,100
30,600
30,600
30,600
30,600
Maximum Air Volume (CFM)
Unit Data
R410A
R410A
R410A
R410A
Refrigerant Type
EEV/Indoor Unit
EEV/Indoor Unit
EEV/Indoor Unit
EEV/Indoor Unit
Refrigerant Control/Location
Min. to Max. No. Indoor Units/
1 - 64
1 - 64
1 - 64
1 - 64
System5
64.3
64.3
64.3
64.3
Sound Pressure dB(A)6
672 + 672 + 672
672 + 672 + 672
672 + 672 + 672
672 + 672 + 672
Net Unit Weight (lbs.)
705 + 705 + 705
705 + 705 + 705
705 + 705 + 705
705 + 705 + 705
Shipping Weight (lbs.)
2 x 18
2 x 18
2 x 18
2 x 18
Communication Cables7,8
Heat Exchanger
Copper Tube/Aluminum Fin and GoldFin/Hydrophilic
Material and Fin Coating
3/14
3/14
3/14
3/14
Rows/Fins per inch
Piping9
5/8+5/8+5/8 Braze
5/8+5/8+5/8 Braze
5/8+5/8+5/8 Braze
5/8+5/8+5/8 Braze
Liquid Line Conn. (in., OD)
1-1/8+1-1/8+1-1/8 Braze
1-1/8+1-1/8+1-1/8 Braze
1-1/8+1-1/8+1-1/8 Braze
1-1/8+1-1/8+1-1/8 Braze
Vapor Line Conn (in., OD)
23.6 + 23.6 + 23.6
23.6 + 23.6 + 23.6
23.6 + 23.6 + 23.6
23.6 + 23.6 + 23.6
Factory Charge lbs. of R410A
1
ARUN145BTE4/ARUN145DTE4, ARUN169BTE4/ARUN169DTE4 frames are ONLY for use in large
capacity triple frame combinations. They cannot be used as stand alone models or in a dual frame
combination. These frames ARE NOT interchangeable with ARUN121BTE4/ARUN121DTE4, ARUN144BTE4/ARUN144DTE4, ARUN168BTE4/ARUN168DTE4 single frame models.
2
Nominal capacity applied with non-ducted indoor units, and is rated 0 ft. above sea level with 25 ft.
of refrigerant line per indoor unit and a 0 ft. level difference between outdoor and indoor units. All
capacities are net with a Combination Ratio between 95105%.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80F dry bulb (DB) and 67F
wet bulb (WB) and outdoor ambient conditions of 95F dry bulb (DB) and 75F wet bulb (WB).
Nominal heating capacity rating obtained with air entering the indoor unit at 70F dry bulb (DB) and
59F wet bulb (WB) and outdoor ambient conditions of 47F dry bulb (DB) and 43F wet bulb (WB).
3
Rated capacity is certified under AHRI Standard 1230. See www.ahrinet.org for information.
4
Cooling range with Low Ambient Baffle Kit (sold separately) is -9.9F to +122F.

14

PRODUCT DATA

The System Combination Ratio must be between 50130%.


Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
7
All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded, and must comply
with applicable local and national codes. Ensure the communication cable is properly grounded at the
master unit only. Do not ground the ODU-IDU communication cable at any other point.
8
Power wiring cable is field provided and must comply with the applicable local and national codes. See
page 31 for detailed electrical data.
9
Refer to the Refrigerant Piping section of this manual for correct line sizing. Contractor must use LG
manufactured Y-Branch and Header Kits only. Designer must verify refrigerant piping design configuration using LGs computerized refrigerant piping (LATS Multi V) software to validate the pipe design.
5
6

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

GENERAL DATA
ARUN Series Heat Pump Outdoor Unit Specifications

Table 6: Single-Frame 460V Heat Pump Units.


Combination Unit Model Number

8.0 Ton
ARUN096DTE4
-

10.0 Ton
ARUN121DTE4
-

12.0
ARUN144DTE4
-

14.0
ARUN168DTE4
-

72,000
69,000

96,000
92,000

120,000
114,000

144,000
138,000

168,000
160,000

81,000
77,000

108,000
103,000

135,000
129,000

162,000
154,000

189,000
180,000

14 to 122
-13 to +61

14 to 122
-13 to +61

14 to 122
-13 to +61

14 to 122
-13 to +61

14 to 122
-13 to +61

HSS DC Scroll x 1
PVE/FVC68D

HSS DC Scroll x 1
PVE/FVC68D

HSS DC Scroll x 1
PVE/FVC68D

HSS DC Scroll x 2
PVE/FVC68D

HSS DC Scroll x 2
PVE/FVC68D

Propeller (BLDC)
0.75 x 1

Propeller (BLDC)
Propeller (BLDC)
Propeller (BLDC)
0.60 x 2
0.60 x 2
0.60 x 2
Brushless Digitally Controlled/Direct
0 - 1,050
0 - 1,050
0 - 1,100
80 - 1,050
80 - 1,050
80 - 1,100
9,850
9,850
10,200

Propeller (BLDC)
0.60 x 2

R410A
EEV/Indoor Unit

R410A
EEV/Indoor Unit

R410A
EEV/Indoor Unit

R410A
EEV/Indoor Unit

R410A
EEV/Indoor Unit

1 - 13

1 - 16

1 - 20

1 - 24

1 - 29

58.5
430
452
2 x 18

59.0
540
573
2 x 18

59.0
540
573
2 x 18

59.5
628
661
2 x 18

59.5
628
661
2 x 18

0 - 850
80 - 850
7,400

3/14
3/8 Braze
3/4 Braze
16.9

Copper Tube/Aluminum Fin and GoldFin/Hydrophilic


3/14
3/14
3/14
3/8 Braze
7/8 Braze
23.6

Nominal capacity applied with non-ducted indoor units, and is rated 0 ft. above sea level with 25 ft.
of refrigerant line per indoor unit and a 0 ft. level difference between outdoor and indoor units. All
capacities are net with a Combination Ratio between 95105%.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80F dry bulb (DB) and 67F
wet bulb (WB) and outdoor ambient conditions of 95F dry bulb (DB) and 75F wet bulb (WB).
Nominal heating capacity rating obtained with air entering the indoor unit at 70F dry bulb (DB) and
59F wet bulb (WB) and outdoor ambient conditions of 47F dry bulb (DB) and 43F wet bulb (WB).
2
Rated capacity is certified under AHRI Standard 1230. See www.ahrinet.org for information.
3
Cooling range with Low Ambient Baffle Kit (sold separately) is -9.9F to +122F.
4
The System Combination Ratio must be between 50130%.
1

1/2 Braze
1-1/8 Braze
23.6

1/2 Braze
1-1/8 Braze
23.6

Product Data

Individual Component Model Numbers


Cooling Performance
Nominal Cooling Capacity (Btu/h)1
Rated Cooling Capacity (Btu/h)2
Heating Performance
Nominal Heating Capacity (Btu/h)1
Rated Heating Capacity (Btu/h)2
Operating Range
Cooling (F DB)3
Heating (F WB)
Compressor
Inverter Quantity
Oil/Type
Fan (Top Discharge)
Type
Motor Output (kW) x Qty.
Motor/Drive
Operating Range Cooling
(RPM)
Heating
Maximum Air Volume (CFM)
Unit Data
Refrigerant Type
Refrigerant Control/Location
Min. to Max. Number Indoor Units/
System4
Sound Pressure dB(A)5
Net Unit Weight (lbs.)
Shipping Weight (lbs.)
Communication Cables6,7
Heat Exchanger
Material and Fin Coating
Rows/Fins per inch
Piping8
Liquid Line Connection (in., OD)
Vapor Line Connection (in., OD)
Factory Charge lbs. of R410A

6.0 Ton
ARUN072DTE4
-

0 - 1,100
80 - 1,100
10,200

3/14
5/8 Braze
1-1/8 Braze
23.6

Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded, and must comply
with applicable local and national codes. Ensure the communication cable is properly grounded at the
master unit only. Do not ground the ODU-IDU communication cable at any other point.
7
Power wiring cable is field provided and must comply with the applicable local and national codes. See
page 32 for detailed electrical data.
8
Refer to the Refrigerant Piping section of this manual for correct line sizing. Contractor must use LG
manufactured Y-Branch and Header Kits only. Designer must verify refrigerant piping design
configuration using LGs computerized refrigerant piping (LATS Multi V) software to validate the pipe
design.
5
6

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

PRODUCT DATA

15

GENERAL DATA

MULTI V IV Outdoor Unit Engineering Manual

ARUN Series Heat Pump Outdoor Unit Specifications

Table 7: Dual-Frame 460V Heat Pump Units.


Combination Unit Model
16.0 Ton
Number
ARUN192DTE4
Individual Component Model
ARUN072DTE4 +
Numbers
ARUN121DTE4
Cooling Performance
192,000
Nominal Cooling Cap. (Btu/h)1
2
184,000
Rated Cooling Cap. (Btu/h)
Heating Performance
216,000
Nominal Heating Cap. (Btu/h)1
206,000
Rated Heating Cap. (Btu/h)2
Operating Range
14 to 122
Cooling (F DB)3
-13 to +61
Heating (F WB)
Compressor
HSS DC Scroll x 2
Inverter Quantity
PVE/FVC68D
Oil/Type
Fan (Top Discharge)
Propeller (BLDC)
Type
0.75 + 0.60 x 2
Motor Output (kW) x Qty.
Motor/Drive
0 - 1,050
Cooling
Oper. Range
(RPM)
80 - 1,050
Heating
17,250
Maximum Air Volume (CFM)
Unit Data
R410A
Refrigerant Type
EEV/Indoor Unit
Refrigerant Control/Location
Min. to Max. No. Indoor Units/
1 - 32
System4
5
61.8
Sound Pressure dB(A)
430 + 540
Net Unit Weight (lbs.)
452 + 573
Shipping Weight (lbs.)
2 x 18
Communication Cables6,7
Heat Exchanger
Material and Fin Coating
3/14
Rows/Fins per inch
Piping8
3/8 + 1/2 Braze
Liquid Line Conn. (in., OD)
3/4 + 1-1/8 Braze
Vapor Line Conn. (in., OD)
16.9 + 23.6
Factory Charge lbs. of R410A

18.0 Ton
ARUN216DTE4
ARUN072DTE4 +
ARUN144DTE4

20.0 Ton
ARUN240DTE4
ARUN096DTE4+
ARUN144DTE4

22.0 Ton
ARUN264DTE4
ARUN121DTE4 +
ARUN144DTE4

216,000
206,000

240,000
228,000

264,000
250,000

243,000
230,000

270,000
256,000

297,000
282,000

14 to 122
-13 to +61

14 to 122
-13 to +61

14 to 122
-13 to +61

HSS DC Scroll x 3
PVE/FVC68D

HSS DC Scroll x 3
PVE/FVC68D

HSS DC Scroll x 3
PVE/FVC68D

Propeller (BLDC)
Propeller (BLDC)
0.75 + 0.60 x 2
0.60 x 2 + 0.60 x 2
Brushless Digitally Controlled/Direct
0 - 1,100
0 - 1,100
80 - 1,100
80 - 1,100
17,600
20,050

Propeller (BLDC)
0.60 x 2 + 0.60 x 2

R410A
EEV/Indoor Unit

R410A
EEV/Indoor Unit

R410A
EEV/Indoor Unit

1 - 35

1 - 39

1 - 42

62.0
430 + 628
452 + 661
2 x 18

62.3
540 + 628
573 + 661
2 x 18

62.3
540 + 628
573 + 661
2 x 18

Copper Tube/Aluminum Fin and GoldFin/Hydrophilic


3/14
3/14
3/8 + 1/2 Braze
3/4 + 1-1/8 Braze
16.9 + 23.6

Nominal capacity applied with non-ducted indoor units, and is rated 0 ft. above sea level with 25 ft.
of refrigerant line per indoor unit and a 0 ft. level difference between outdoor and indoor units. All
capacities are net with a Combination Ratio between 95105%.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80F dry bulb (DB) and 67F
wet bulb (WB) and outdoor ambient conditions of 95F dry bulb (DB) and 75F wet bulb (WB).
Nominal heating capacity rating obtained with air entering the indoor unit at 70F dry bulb (DB) and
59F wet bulb (WB) and outdoor ambient conditions of 47F dry bulb (DB) and 43F wet bulb (WB).
2
Rated capacity is certified under AHRI Standard 1230. See www.ahrinet.org for information.
3
Cooling range with Low Ambient Baffle Kit (sold separately) is -9.9F to +122F.
4
The System Combination Ratio must be between 50130%.
1

16

PRODUCT DATA

0 - 1,100
80 - 1,100
20,050

3/8 + 1/2 Braze


7/8 + 1-1/8 Braze
23.6 + 23.6

3/14
1/2 + 1/2 Braze
1/2 + 1-1/8 Braze
23.6 + 23.6

Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded, and must comply
with applicable local and national codes. Ensure the communication cable is properly grounded at the
master unit only. Do not ground the ODU-IDU communication cable at any other point.
7
Power wiring cable is field provided and must comply with the applicable local and national codes. See
page 32 for detailed electrical data.
8
Refer to the Refrigerant Piping section of this manual for correct line sizing. Contractor must use LG
manufactured Y-Branch and Header Kits only. Designer must verify refrigerant piping design configuration using LGs computerized refrigerant piping (LATS Multi V) software to validate the pipe design.
5
6

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

GENERAL DATA
ARUN Series Heat Pump Outdoor Unit Specifications

Table 8: Dual-Frame 460V Heat Pump Units, continued.


Combination Unit Model Number
Individual Component Model Numbers

26.0 Ton
ARUN313DTE4
ARUN144DTE4 +
ARUN168DTE4

28.0 Ton
ARUN337DTE4
ARUN168DTE4 +
ARUN168DTE4

288,000
274,000

312,000
296,000

336,000
320,000

324,000
308,000

351,000
334,000

378,000
361,000

14 to 122
-13 to +61

14 to 122
-13 to +61

14 to 122
-13 to +61

HSS DC Scroll x 4
PVE/FVC68D

HSS DC Scroll x 4
PVE/FVC68D

HSS DC Scroll x 4
PVE/FVC68D

Propeller (BLDC)
0.60 x 2 + 0.60 x 2

Propeller (BLDC)
0.60 x 2 + 0.60 x 2

0 - 1,100
80 - 1,100
20,400

Propeller (BLDC)
0.60 x 2 + 0.60 x 2
Brushless Digitally Controlled/Direct
0 - 1,100
80 - 1,100
20,400

R410A
EEV/Indoor Unit
1 - 45
62.5
628 + 628
661 + 661
2 x 18

R410A
EEV/Indoor Unit
1 - 52
62.5
628 + 628
661 + 661
2 x 18

R410A
EEV/Indoor Unit
1 - 55
62.5
628 + 628
661 + 661
2 x 18

3/14

Nominal capacity applied with non-ducted indoor units, and is rated 0 ft. above sea level with 25 ft.
of refrigerant line per indoor unit and a 0 ft. level difference between outdoor and indoor units. All
capacities are net with a Combination Ratio between 95105%.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80F dry bulb (DB) and 67F
wet bulb (WB) and outdoor ambient conditions of 95F dry bulb (DB) and 75F wet bulb (WB).
Nominal heating capacity rating obtained with air entering the indoor unit at 70F dry bulb (DB) and
59F wet bulb (WB) and outdoor ambient conditions of 47F dry bulb (DB) and 43F wet bulb (WB).
2
Rated capacity is certified under AHRI Standard 1230. See www.ahrinet.org for information.
3
Cooling range with Low Ambient Baffle Kit (sold separately) is -9.9F to +122F.
4
The System Combination Ratio must be between 50130%.
1

0 - 1,100
80 - 1,100
20,400

Copper Tube/Aluminum Fin and GoldFin/Hydrophilic


3/14

1/2 + 1/2 Braze


1-1/8 + 1-1/8 Braze
23.6 + 23.6

1/2 + 5/8 Braze


1-1/8 + 1-1/8 Braze
23.6 + 23.6

Product Data

Cooling Performance
Nominal Cooling Cap. (Btu/h)1
Rated Cooling Cap. (Btu/h)2
Heating Performance
Nominal Heating Cap. (Btu/h)1
Rated Heating Cap. (Btu/h)2
Operating Range
Cooling (F DB)3
Heating (F WB)
Compressor
Inverter Quantity
Oil/Type
Fan (Top Discharge)
Type
Motor Output (kW) x Qty.
Motor/Drive
Cooling
Operation Range (RPM)
Heating
Maximum Air Volume (CFM)
Unit Data
Refrigerant Type
Refrigerant Control/Location
Min. to Max. No. Indoor Units/System4
Sound Pressure dB(A)5
Net Unit Weight (lbs.)
Shipping Weight (lbs.)
Communication Cables6,7
Heat Exchanger
Material and Fin Coating
Rows/Fins per inch
Piping8
Liquid Line Conn. (in., OD)
Vapor Line Conn. (in., OD)
Factory Charge lbs. of R410A

24.0 Ton
ARUN288DTE4
ARUN144DTE4 +
ARUN144DTE4

3/14

5/8 + 5/8 Braze


1-1/8 + 1-1/8 Braze
23.6 + 23.6

Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded, and must comply
with applicable local and national codes. Ensure the communication cable is properly grounded at the
master unit only. Do not ground the ODU-IDU communication cable at any other point.
7
Power wiring cable is field provided and must comply with the applicable local and national codes. See
page 32 for detailed electrical data.
8
Refer to the Refrigerant Piping section of this manual for correct line sizing. Contractor must use LG
manufactured Y-Branch and Header Kits only. Designer must verify refrigerant piping design configuration using LGs computerized refrigerant piping (LATS Multi V) software to validate the pipe design.
5
6

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

PRODUCT DATA

17

GENERAL DATA

MULTI V IV Outdoor Unit Engineering Manual

ARUN Series Heat Pump Outdoor Unit Specifications

Table 9: Triple-Frame 460V Heat Pump Units.


Combination Unit Model
26.0 Ton
Number
ARUN312DTE4
ARUN072DTE4 +
Individual Component Model
ARUN096DTE4 +
Numbers1
ARUN144DTE4
Cooling Performance
312,000
Nominal Cooling Cap. (Btu/h)2
296,000
Rated Cooling Cap. (Btu/h)3
Heating Performance
351,000
Nominal Heating Cap. (Btu/h)2
334,000
Rated Heating Cap. (Btu/h)3
Operating Range
14 to 122
Cooling (F DB)4
-13 to +61
Heating (F WB)
Compressor
HSS DC Scroll x 4
Inverter Quantity
PVE/FVC68D
Oil/Type
Fan (Top Discharge)
Propeller (BLDC)
Type
Motor Output (kW) x Qty.

0.75 + 0.60 x 2
+ 0.60 x 2

28.0 Ton
ARUN336DTE4
ARUN096DTE4 +
ARUN096DTE4 +
ARUN144DTE4

30.0 Ton
ARUN360DTE4
ARUN096DTE4 +
ARUN121DTE4 +
ARUN144DTE4

32.0 Ton
ARUN384DTE4
ARUN096DTE4 +
ARUN145DTE4 +
ARUN145DTE4

34.0 Ton
ARUN408DTE4
ARUN121DTE4 +
ARUN145DTE4 +
ARUN145DTE4

336,000
320,000

360,000
342,000

384,000
366,000

408,000
390,000

351,000
334,000

405,000
387,000

432,000
412,000

459,000
437,000

14 to 122
-13 to +61

14 to 122
-13 to +61

14 to 122
-13 to +61

14 to 122
-13 to +61

HSS DC Scroll x 4
PVE/FVC68D

HSS DC Scroll x 4
PVE/FVC68D

HSS DC Scroll x 5
PVE/FVC68D

HSS DC Scroll x 5
PVE/FVC68D

Propeller (BLDC)
Propeller (BLDC)
Propeller (BLDC)
0.60 x 2 + 0.60 x 2
0.60 x 2 + 0.60 x 2
0.60 x 2 + 0.60 x 2
+ 0.60 x 2
+ 0.60 x 2
+ 0.60 x 2
Brushless Digitally Controlled/Direct
0 - 1,100
0 - 1,100
0 - 1,100
80 - 1,100
80 - 1,100
80 - 1,100
29,900
29,900
30,250

Propeller (BLDC)
0.60 x 2 + 0.60 x 2
+ 0.60 x 2

Motor/Drive
0 - 1,100
0 - 1,100
Cooling
Operating
Range (RPM) Heating
80 - 1,100
80 - 1,100
27,450
30,250
Maximum Air Volume (CFM)
Unit Data
R410A
R410A
R410A
R410A
R410A
Refrigerant Type
EEV/Indoor Unit
EEV/Indoor Unit
EEV/Indoor Unit
EEV/Indoor Unit
EEV/Indoor Unit
Refrigerant Control/Location
Min. to Max. No. Indoor Units/
1 - 52
1 - 55
1 - 58
1 - 61
1 - 64
System5
63.8
63.9
63.9
64.1
64.1
Sound Pressure dB(A)6
430 + 540 + 628
540 + 540 + 628
540 + 540 + 628
540 + 628 + 628
540 + 628 + 628
Net Unit Weight (lbs.)
452 + 573 + 661
573 + 573 + 661
573 + 573 + 661
573 + 661 + 661
573 + 661 + 661
Shipping Weight (lbs.)
2 x 18
2 x 18
2 x 18
2 x 18
2 x 18
Communication Cables7,8
Heat Exchanger
Copper Tube/Aluminum Fin and GoldFin/Hydrophilic
Material and Fin Coating
3/14
3/14
3/14
3/14
3/14
Rows/Fins per inch
Piping9
3/8 + 3/8 + 1/2 Braze 3/8 + 3/8 + 1/2 Braze 3/8 + 1/2 + 1/2 Braze 3/8 + 5/8 + 5/8 Braze 1/2 + 5/8 + 5/8 Braze
Liquid Line Conn. (in., OD)
3/4 + 7/8 + 1-1/8 Braze 7/8 + 7/8 + 1-1/8 Braze 7/8+1-1/8+1-1/8 Braze 7/8+1-1/8+1-1/8 Braze 1-1/8+1-1/8+1-1/8 Braze
Vapor Line Conn (in., OD)
16.9 + 23.6 + 23.6
23.6 + 23.6 + 23.6
23.6 + 23.6 + 23.6
23.6 + 23.6 + 23.6
23.6 + 23.6 + 23.6
Factory Charge lbs. of R410A
1
ARUN145BTE4/ARUN145DTE4, ARUN169BTE4/ARUN169DTE4 frames are ONLY for use in large
capacity triple frame combinations. They cannot be used as stand alone models or in a dual frame
combination. These frames ARE NOT interchangeable with ARUN144BTE4/ARUN144DTE4, ARUN168BTE4/ARUN168DTE4 single frame models.
2
Nominal capacity applied with non-ducted indoor units, and is rated 0 ft. above sea level with 25 ft.
of refrigerant line per indoor unit and a 0 ft. level difference between outdoor and indoor units. All
capacities are net with a Combination Ratio between 95105%.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80F dry bulb (DB) and 67F
wet bulb (WB) and outdoor ambient conditions of 95F dry bulb (DB) and 75F wet bulb (WB).
Nominal heating capacity rating obtained with air entering the indoor unit at 70F dry bulb (DB) and
59F wet bulb (WB) and outdoor ambient conditions of 47F dry bulb (DB) and 43F wet bulb (WB).
3
Rated capacity is certified under AHRI Standard 1230. See www.ahrinet.org for information.
4
Cooling range with Low Ambient Baffle Kit (sold separately) is -9.9F to +122F.

18

PRODUCT DATA

The System Combination Ratio must be between 50130%.


Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
7
All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded, and must comply
with applicable local and national codes. Ensure the communication cable is properly grounded at the
master unit only. Do not ground the ODU-IDU communication cable at any other point.
8
Power wiring cable is field provided and must comply with the applicable local and national codes. See
page 32 for detailed electrical data.
9
Refer to the Refrigerant Piping section of this manual for correct line sizing. Contractor must use LG
manufactured Y-Branch and Header Kits only. Designer must verify refrigerant piping design configuration using LGs computerized refrigerant piping (LATS Multi V) software to validate the pipe design.
5
6

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

GENERAL DATA
ARUN Series Heat Pump Outdoor Unit Specifications

38.0 Ton
ARUN456DTE4
ARUN145DTE4 +
ARUN145DTE4 +
ARUN169DTE4

40.0 Ton
ARUN480DTE4
ARUN145DTE4 +
ARUN169DTE4 +
ARUN169DTE4

42.0 Ton
ARUN504DTE4
ARUN169DTE4 +
ARUN169DTE4 +
ARUN169DTE4

456,000
436,000
592,800

480,000
458,000
624,000

504,000
479,000
655,200

513,000
488,000

540,000
514,000

567,000
539,000

14 to 122
-13 to +61

14 to 122
-13 to +61

14 to 122
-13 to +61

HSS DC Scroll x 6
PVE/FVC68D

HSS DC Scroll x 6
PVE/FVC68D

HSS DC Scroll x 6
PVE/FVC68D

Propeller (BLDC)
Propeller (BLDC)
0.60 x 2 + 0.60 x 2 + 0.60 x 2 0.60 x 2 + 0.60 x 2 + 0.60 x 2
Brushless Digitally Controlled/Direct
0 - 1,100
0 - 1,100
80 - 1,100
80 - 1,100
30,600
30,600

Propeller (BLDC)
0.60 x 2 + 0.60 x 2 + 0.60 x 2
0 - 1,100
80 - 1,100
30,600

R410A
EEV/Indoor Unit

R410A
EEV/Indoor Unit

R410A
EEV/Indoor Unit

1 - 64

1 - 64

1 - 64

64.3
672 + 672 + 672
705 + 705 + 705
2 x 18

64.3
672 + 672 + 672
705 + 705 + 705
2 x 18

64.3
672 + 672 + 672
705 + 705 + 705
2 x 18

Copper Tube/Aluminum Fin and GoldFin/Hydrophilic


3/14
3/14
5/8 + 5/8 + 5/8 Braze
1-1/8 + 1-1/8 + 1-1/8 Braze
23.6 + 23.6 + 23.6

1
ARUN145BTE4/ARUN145DTE4, ARUN169BTE4/ARUN169DTE4 frames are ONLY for use in large
capacity triple frame combinations. They cannot be used as stand alone models or in a dual frame
combination. These frames ARE NOT interchangeable with ARUN144BTE4/ARUN144DTE4, ARUN168BTE4/ARUN168DTE4 single frame models.
2
Nominal capacity applied with non-ducted indoor units, and is rated 0 ft. above sea level with 25 ft.
of refrigerant line per indoor unit and a 0 ft. level difference between outdoor and indoor units. All
capacities are net with a Combination Ratio between 95105%.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80F dry bulb (DB) and 67F
wet bulb (WB) and outdoor ambient conditions of 95F dry bulb (DB) and 75F wet bulb (WB).
Nominal heating capacity rating obtained with air entering the indoor unit at 70F dry bulb (DB) and
59F wet bulb (WB) and outdoor ambient conditions of 47F dry bulb (DB) and 43F wet bulb (WB).
3
Rated capacity is certified under AHRI Standard 1230. See www.ahrinet.org for information.
4
Cooling range with Low Ambient Baffle Kit (sold separately) is -9.9F to +122F.

5/8 + 5/8 + 5/8 Braze


1-1/8 + 1-1/8 + 1-1/8 Braze
23.6 + 23.6 + 23.6

3/14
5/8 + 5/8 + 5/8 Braze
1-1/8 + 1-1/8 + 1-1/8 Braze
23.6 + 23.6 + 23.6

The System Combination Ratio must be between 50130%.


Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
7
All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded, and must comply
with applicable local and national codes. Ensure the communication cable is properly grounded at the
master unit only. Do not ground the ODU-IDU communication cable at any other point.
8
Power wiring cable is field provided and must comply with the applicable local and national codes. See
page 32 for detailed electrical data.
9
Refer to the Refrigerant Piping section of this manual for correct line sizing. Contractor must use LG
manufactured Y-Branch and Header Kits only. Designer must verify refrigerant piping design configuration using LGs computerized refrigerant piping (LATS Multi V) software to validate the pipe design.
5
6

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

PRODUCT DATA

19

Product Data

Table 10: Triple-Frame 460V Heat Pump Units, continued.


Combination Unit Model
36.0 Ton
Number
ARUN432DTE4
ARUN145DTE4 +
Individual Component Model
ARUN145DTE4 +
1
Numbers
ARUN145DTE4
Cooling Performance
432,000
Nominal Cooling Cap. (Btu/h)2
414,000
Rated Cooling Cap. (Btu/h)3
4
561,600
Max. Nominal Cooling Cap.
Heating Performance
486,000
Nominal Heating Cap. (Btu/h)2
462,000
Rated Heating Cap. (Btu/h)3
Operating Range
14 to 122
Cooling (F DB)4
-13 to +61
Heating (F WB)
Compressor
HSS DC Scroll x 6
Inverter Quantity
PVE/FVC68D
Oil/Type
Fan (Top Discharge)
Propeller (BLDC)
Type
0.60 x 2 + 0.60 x 2 + 0.60 x 2
Motor Output (kW) x Qty.
Motor/Drive
0 - 1,100
Cooling
Operating
Range (RPM) Heating
80 - 1,100
30,600
Maximum Air Volume (CFM)
Unit Data
R410A
Refrigerant Type
EEV/Indoor Unit
Refrigerant Control/Location
Min. to Max. No. Indoor Units/
1 - 64
System5
6
64.3
Sound Pressure dB(A)
672 + 672 + 672
Net Unit Weight (lbs.)
705 + 705 + 705
Shipping Weight (lbs.)
2 x 18
Communication Cables7,8
Heat Exchanger
Material and Fin Coating
3/14
Rows/Fins per inch
Piping9
5/8 + 5/8 + 5/8 Braze
Liquid Line Conn. (in., OD)
1-1/8 + 1-1/8 + 1-1/8 Braze
Vapor Line Conn (in., OD)
23.6 + 23.6 + 23.6
Factory Charge lbs. of R410A

GENERAL DATA

MULTI V IV Outdoor Unit Engineering Manual

ARUB Series Heat Recovery Outdoor Unit Specifications

Table 11: Single-Frame 208-230V Heat Recovery Units.


6.0 Ton
Combination Unit Model Number
ARUB072BTE4
Individual Component Model Numbers
Cooling Performance
72,000
Nominal Cooling Capacity (Btu/h)1
69,000
Rated Cooling Capacity (Btu/h)2
Heating Performance
81,000
Nominal Heating Capacity (Btu/h)1
77,000
Rated Heating Capacity (Btu/h)2
Operating Range
14 to 122
Cooling (F DB)3
-13
to +61
Heating (F WB)
14 to 81
Synchronous Cooling Based (F DB)
14 to 61
Synchronous Heating Based (F DB)
Compressor
HSS DC Scroll x 1
Inverter Quantity
PVE/FVC68D
Oil/Type
Fan (Top Discharge)
Propeller (BLDC)
Type
0.75 x 1
Motor Output (kW) x Qty.
Motor/Drive
0 - 850
Operating Range Cooling
(RPM)
80 - 850
Heating
7,400
Maximum Air Volume (CFM)
Unit Data
R410A
Refrigerant Type
EEV/Indoor Unit
Refrigerant Control/Location
Min. to Max. Number Indoor Units/
1 - 13
System4
58.5
Sound Pressure dB(A)5
430
Net Unit Weight (lbs.)
452
Shipping Weight (lbs.)
2 x 18
Communication Cables6,7
Heat Exchanger
Material and Fin Coating
3/14
Rows/Fins per inch
Piping8
3/8 Braze
Liquid Line Connection (in., OD)
3/4 Braze
Low Pressure Vapor Line Conn (in., OD)
5/8 Braze
High Pressure Vapor Line Conn (in, OD)
16.9
Factory Charge lbs. of R410A

8.0 Ton
ARUB096BTE4
-

10.0 Ton
ARUB121BTE4
-

12.0
ARUB144BTE4
-

14.0
ARUB168BTE4
-

96,000
92,000

120,000
114,000

144,000
138,000

168,000
160,000

108,000
103,000

135,000
129,000

162,000
154,000

189,000
180,000

14 to 122
-13 to +61
14 to 81
14 to 61

14 to 122
-13 to +61
14 to 81
14 to 61

14 to 122
-13 to +61
14 to 81
14 to 61

14 to 122
-13 to +61
14 to 81
14 to 61

HSS DC Scroll x 1
PVE/FVC68D

HSS DC Scroll x 1
PVE/FVC68D

HSS DC Scroll x 2
PVE/FVC68D

HSS DC Scroll x 2
PVE/FVC68D

Propeller (BLDC)
Propeller (BLDC)
Propeller (BLDC)
0.60 x 2
0.60 x 2
0.60 x 2
Brushless Digitally Controlled/Direct
0 - 1,050
0 - 1,050
0 - 1,100
80 - 1,050
80 - 1,050
80 - 1,100
9,850
9,850
10,200

Propeller (BLDC)
0.60 x 2

R410A
EEV/Indoor Unit

R410A
EEV/Indoor Unit

R410A
EEV/Indoor Unit

R410A
EEV/Indoor Unit

1 - 16

1 - 20

1 - 24

1 - 29

59.0
540
573
2 x 18

59.0
540
573
2 x 18

59.5
628
661
2 x 18

59.5
628
661
2 x 18

Copper Tube/Aluminum Fin and GoldFin/Hydrophilic


3/14
3/14
3/14
3/8 Braze
7/8 Braze
3/4 Braze
23.6

Nominal capacity applied with non-ducted indoor units, and is rated 0 ft. above sea level with 25 ft.
of refrigerant line per indoor unit and a 0 ft. level difference between outdoor and indoor units. All
capacities are net with a Combination Ratio between 95105%.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80F dry bulb (DB) and 67F
wet bulb (WB) and outdoor ambient conditions of 95F dry bulb (DB) and 75F wet bulb (WB).
Nominal heating capacity rating obtained with air entering the indoor unit at 70F dry bulb (DB) and
59F wet bulb (WB) and outdoor ambient conditions of 47F dry bulb (DB) and 43F wet bulb (WB).
2
Rated capacity is certified under AHRI Standard 1230. See www.ahrinet.org for information.
3
Cooling range with the Low Ambient Baffle Kit (sold separately) is -9.9F to +122F and is achieved only
when all indoor units are operating in cooling mode. Does not impact synchronous operating range.
4
The System Combination Ratio must be between 50130%.
1

20

PRODUCT DATA

1/2 Braze
1-1/8 Braze
3/4 Braze
23.6

1/2 Braze
1-1/8 Braze
7/8 Braze
23.6

0 - 1,100
80 - 1,100
10,200

3/14
5/8 Braze
1-1/8 Braze
7/8 Braze
23.6

Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded, and must comply
with applicable local and national codes. Ensure the communication cable is properly grounded at the
master unit only. Do not ground the ODU-IDU communication cable at any other point.
7
Power wiring cable is field provided and must comply with the applicable local and national codes. See
page 33 for detailed electrical data.
8
Refer to the Refrigerant Piping section of this manual for correct line sizing. Contractor must use LG
manufactured Y-Branch and Header Kits only. Designer must verify refrigerant piping design configuration using LGs computerized refrigerant piping (LATS Multi V) software to validate the pipe design.
5
6

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

GENERAL DATA
ARUB Series Heat Recovery Outdoor Unit Specifications

18.0 Ton
ARUB216BTE4
ARUB072BTE4 +
ARUB144BTE4

20.0 Ton
ARUB240BTE4
ARUB096TE4 +
ARUB144BTE4

22.0 Ton
ARUB264BTE4
ARUB121BTE4 +
ARUB144BTE4

216,000
206,000

240,000
228,000

264,000
250,000

243,000
230,000

270,000
256,000

297,000
282,000

14 to 122
-13 to +61
14 to 81
14 to 61

14 to 122
-13 to +61
14 to 81
14 to 61

14 to 122
-13 to +61
14 to 81
14 to 61

HSS DC Scroll x 3
PVE/FVC68D

HSS DC Scroll x 3
PVE/FVC68D

HSS DC Scroll x 3
PVE/FVC68D

Propeller (BLDC)
Propeller (BLDC)
0.75 + 0.60 x 2.
0.75 + 0.60 x 2
Brushless Digitally Controlled/Direct
0 - 1,100
0 - 1,100
80 - 1,100
80 - 1,100
17,600
20,050

Propeller (BLDC)
0.75 + 0.60 x 2

R410A
EEV/Indoor Unit
1 - 35
62.0
430 + 628
452 + 661
2 x 18

R410A
EEV/Indoor Unit
1 - 42
62.3
540 + 628
573 + 661
2 x 18

Copper Tube/Aluminum Fin and GoldFin/Hydrophilic


3/14
3/14

Nominal capacity applied with non-ducted indoor units, and is rated 0 ft. above sea level with 25 ft.
of refrigerant line per indoor unit and a 0 ft. level difference between outdoor and indoor units. All
capacities are net with a Combination Ratio between 95105%.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80F dry bulb (DB) and 67F
wet bulb (WB) and outdoor ambient conditions of 95F dry bulb (DB) and 75F wet bulb (WB).
Nominal heating capacity rating obtained with air entering the indoor unit at 70F dry bulb (DB) and
59F wet bulb (WB) and outdoor ambient conditions of 47F dry bulb (DB) and 43F wet bulb (WB).
2
Rated capacity is certified under AHRI Standard 1230. See www.ahrinet.org for information.
3
Cooling range with the Low Ambient Baffle Kit (sold separately) is -9.9F to +122F and is achieved only
when all indoor units are operating in cooling mode. Does not impact synchronous operating range.
4
The System Combination Ratio must be between 50130%.
1

R410A
EEV/Indoor Unit
1 - 39
62.3
540 + 628
573 + 661
2 x 18

3/8 + 1/2 Braze


3/4 + 1-1/8 Braze
5/8 + 7/8 Braze
16.9 + 23.6

3/8 + 1/2 Braze


7/8 + 1-1/8 Braze
3/4 + 7/8 Braze
23.6 + 23.6

Product Data

Table 12: Dual-Frame 208-230V Heat Recovery Units.


16.0 Ton
Combination Unit Model Number
ARUB192BTE4
ARUB072BTE4 +
Individual Component Model Numbers
ARUB121BTE4
Cooling Performance
192,000
Nominal Cooling Cap. (Btu/h)1
2
184,000
Rated Cooling Cap. (Btu/h)
Heating Performance
216,000
Nominal Heating Cap. (Btu/h)1
2
206,000
Rated Heating Cap. (Btu/h)
Operating Range
14 to 122
Cooling (F DB)3
-13 to +61
Heating (F WB)
14 to 81
SynchronousCooling Based (F DB)
14 to 61
SynchronousHeating Based (F DB)
Compressor
HSS DC Scroll x 2
Inverter Quantity
PVE/FVC68D
Oil/Type
Fan (Top Discharge)
Propeller (BLDC)
Type
0.75 + 0.60 x 2
Motor Output (kW) x Qty.
Motor/Drive
0 - 1,050
Cooling
Oper. Range
(RPM)
80 - 1,050
Heating
17,250
Maximum Air Volume (CFM)
Unit Data
R410A
Refrigerant Type
EEV/Indoor Unit
Refrigerant Control/Location
1 - 32
Min. to Max. No. Indoor Units/System4
61.8
Sound Pressure dB(A)5
430 + 540
Net Unit Weight (lbs.)
452 + 573
Shipping Weight (lbs.)
2 x 18
Communication Cables6,7
Heat Exchanger
Material and Fin Coating
3/14
Rows/Fins per inch
Piping8
3/8 + 1/2 Braze
Liquid Line Conn. (in., OD)
3/4 + 1-1/8 Braze
Low Press. Vapor Line Conn. (in., OD)
5/8 + 3/4 Braze
High Press. Vapor Line Conn (in, OD)
16.9 + 23.6
Factory Charge lbs. of R410A

0 - 1,100
80 - 1,100
20,050

3/14
1/2 + 1/2 Braze
1-1/8 + 1-1/8 Braze
3/4 + 7/8 Braze
23.6 + 23.6

Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded, and must comply
with applicable local and national codes. Ensure the communication cable is properly grounded at the
master unit only. Do not ground the ODU-IDU communication cable at any other point.
7
Power wiring cable is field provided and must comply with the applicable local and national codes. See
page 33 for detailed electrical data.
8
Refer to the Refrigerant Piping section of this manual for correct line sizing. Contractor must use LG
manufactured Y-Branch and Header Kits only. Designer must verify refrigerant piping design configuration using LGs computerized refrigerant piping (LATS Multi V) software to validate the pipe design.
5
6

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

PRODUCT DATA

21

GENERAL DATA
ARUB Series Heat Recovery Outdoor Unit Specifications

Table 13: Dual-Frame 208-230V Heat Recovery Units, continued.


Combination Unit Model Number
Individual Component Model Numbers

MULTI V IV Outdoor Unit Engineering Manual

Cooling Performance
Nominal Cooling Cap. (Btu/h)1
Rated Cooling Cap. (Btu/h)2
Heating Performance
Nominal Heating Cap. (Btu/h)1
Rated Heating Cap. (Btu/h)2
Operating Range
Cooling (F DB)3
Heating (F WB)
SynchronousCooling Based (F DB)
SynchronousHeating Based (F DB)
Compressor
Inverter Quantity
Oil/Type
Fan (Top Discharge)
Type
Motor Output (kW) x Qty.
Motor/Drive
Cooling
Operation. Range (RPM)
Heating
Maximum Air Volume (CFM)
Unit Data
Refrigerant Type
Refrigerant Control/Location
Min. to Max. No. Indoor Units/System4
Sound Pressure dB(A)5
Net Unit Weight (lbs.)
Shipping Weight (lbs.)
Communication Cables6,7
Heat Exchanger
Material and Fin Coating
Rows/Fins per inch
Piping8
Liquid Line Conn. (in., OD)
Low Press. Vapor Line Conn. (in., OD)
High Press. Vapor Line Conn (in, OD)
Factory Charge lbs. of R410A

24.0 Ton
ARUB288BTE4
ARUB144BTE4 +
ARUB144BTE4

26.0 Ton
ARUB313BTE4
ARUB144BTE4 +
ARUB168BTE4

28.0 Ton
ARUB337BTE4
ARUB168BTE4 +
ARUB168BTE4

288,000
274,000

312,000
296,000

336,000
320,000

324,000
308,000

351,000
334,000

378,000
361,000

14 to 122
-13 to +61
14 to 81
14 to 61

14 to 122
-13 to +61
14 to 81
14 to 61

14 to 122
-13 to +61
14 to 81
14 to 61

HSS DC Scroll x 4
PVE/FVC68D

HSS DC Scroll x 4
PVE/FVC68D

HSS DC Scroll x 4
PVE/FVC68D

Propeller (BLDC)
0.60 x 2 + 0.60 x 2

Propeller (BLDC)
0.60 x 2 + 0.60 x 2

0 - 1,100
80 - 1,100
20,400

Propeller (BLDC)
0.60 x 2 + 0.60 x 2
Brushless Digitally Controlled/Direct
0 - 1,100
80 - 1,100
20,400

R410A
EEV/Indoor Unit
1 - 45
62.5
628 + 628
661 + 661
2 x 18

R410A
EEV/Indoor Unit
1 - 52
62.5
628 + 628
661 + 661
2 x 18

R410A
EEV/Indoor Unit
1 - 55
62.5
628 + 628
661 + 661
2 x 18

3/14

22

PRODUCT DATA

Copper Tube/Aluminum Fin and GoldFin/Hydrophilic


3/14

1/2 + 1/2 Braze


1-1/8 + 1-1/8 Braze
7/8 + 7/8 Braze
23.6 + 23.6

Nominal capacity applied with non-ducted indoor units, and is rated 0 ft. above sea level with 25 ft.
of refrigerant line per indoor unit and a 0 ft. level difference between outdoor and indoor units. All
capacities are net with a Combination Ratio between 95105%.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80F dry bulb (DB) and 67F
wet bulb (WB) and outdoor ambient conditions of 95F dry bulb (DB) and 75F wet bulb (WB).
Nominal heating capacity rating obtained with air entering the indoor unit at 70F dry bulb (DB) and
59F wet bulb (WB) and outdoor ambient conditions of 47F dry bulb (DB) and 43F wet bulb (WB).
2
Rated capacity is certified under AHRI Standard 1230. See www.ahrinet.org for information.
3
Cooling range with the Low Ambient Baffle Kit (sold separately) is -9.9F to +122F and is achieved only
when all indoor units are operating in cooling mode. Does not impact synchronous operating range.
4
The System Combination Ratio must be between 50130%.
1

0 - 1,100
80 - 1,100
20,400

1/2 + 5/8 Braze


1-1/8 + 1-1/8 Braze
7/8 + 7/8 Braze
23.6 + 23.6

3/14

5/8 + 5/8 Braze


1-1/8 + 1-1/8 Braze
7/8 + 7/8 Braze
23.6 + 23.6

Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded, and must comply
with applicable local and national codes. Ensure the communication cable is properly grounded at the
master unit only. Do not ground the ODU-IDU communication cable at any other point.
7
Power wiring cable is field provided and must comply with the applicable local and national codes. See
page 33 for detailed electrical data.
8
Refer to the Refrigerant Piping section of this manual for correct line sizing. Contractor must use LG
manufactured Y-Branch and Header Kits only. Designer must verify refrigerant piping design configuration using LGs computerized refrigerant piping (LATS Multi V) software to validate the pipe design.
5
6

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

GENERAL DATA
ARUB Series Heat Recovery Outdoor Unit Specifications

Motor Output (kW) x Qty.

0.75 + 0.60 x 2
+ 0.60 x 2

Motor/Drive
0 - 1,100
Cooling
Operating
Range (RPM) Heating
80 - 1,100
27,450
Maximum Air Volume (CFM)
Unit Data
R410A
Refrigerant Type
EEV/Indoor Unit
Refrigerant Control/Location
1 - 52
Min. to Max. No. Indoor Units/System5
63.8
Sound Pressure dB(A)6
430 + 540 + 628
Net Unit Weight (lbs.)
452 + 573 + 661
Shipping Weight (lbs.)
7,8
2 x 18
Communication Cables
Heat Exchanger
Material and Fin Coating
3/14
Rows/Fins per inch
Piping9
3/8+3/8+1/2 Braze
Liquid Line Connection (in., OD)
Low Pressure Vapor Line Conn (in., OD) 3/4+7/8+1-1/8 Braze
High Pressure Vapor Line Conn (in, OD) 5/8+3/4+7/8 Braze
16.9 + 23.6 + 23.6
Factory Charge lbs. of R410A

28.0 Ton
ARUB336BTE4
ARUB096BTE4 +
ARUB096BTE4 +
ARUB144BTE4

30.0 Ton
ARUB360BTE4
ARUB096BTE4 +
ARUB121BTE4 +
ARUB144BTE4

32.0 Ton
ARUB384BTE4
ARUB096BTE4 +
ARUB145BTE4 +
ARUB145BTE4

34.0 Ton
ARUB408BTE4
ARUB121BTE4 +
ARUB145BTE4 +
ARUB145BTE4

336,000
320,000

360,000
342,000

384,000
366,000

408,000
390,000

378,000
361,000

405,000
387,000

432,000
412,000

459,000
437,000

14 to 122
-13 to +61
14 to 81
14 to 61

14 to 122
-13 to +61
14 to 81
14 to 61

14 to 122
-13 to +61
14 to 81
14 to 61

14 to 122
-13 to +61
14 to 81
14 to 61

HSS DC Scroll x 4
PVE/FVC68D

HSS DC Scroll x 4
PVE/FVC68D

HSS DC Scroll x 5
PVE/FVC68D

HSS DC Scroll x 5
PVE/FVC68D

Propeller (BLDC)
Propeller (BLDC)
Propeller (BLDC)
0.60 x 2 + 0.60 x 2
0.60 x 2 + 0.60 x 2
0.60 x 2 + 0.60 x 2
+ 0.60 x 2
+ 0.60 x 2
+ 0.60 x 2
Brushless Digitally Controlled/Direct
0 - 1,100
0 - 1,100
0 - 1,100
80 - 1,100
80 - 1,100
80 - 1,100
29,900
29,900
30,250

Propeller (BLDC)
0.60 x 2 + 0.60 x 2
+ 0.60 x 2

R410A
EEV/Indoor Unit
1 - 55
63.9
540 + 540 + 628
573 + 573 + 661
2 x 18

R410A
EEV/Indoor Unit
1 - 64
64.1
540 + 672 + 672
573 + 705 + 705
2 x 18

R410A
EEV/Indoor Unit
1 - 58
63.9
540 + 540 + 628
573 + 573 + 661
2 x 18

0 - 1,100
80 - 1,100
30,250

R410A
EEV/Indoor Unit
1 - 61
64.1
540 + 672 + 672
573 + 705 + 705
2 x 18

Copper Tube/Aluminum Fin and GoldFin/Hydrophilic


3/14
3/14
3/14
3/8+3/8+1/2 Braze
7/8+7/8+1-1/8 Braze
3/4+3/4+7/8 Braze
23.6 + 23.6 + 23.6

1
ARUB145BTE4/ARUB145DTE4, ARUB169BTE4/ARUB169DTE4 frames are ONLY for use in
large capacity triple frame combinations. They cannot be used as stand alone models or in a dual
frame combination. These frames ARE NOT interchangeable with ARUB144BTE4/ARUB144DTE4,
ARUB168BTE4/ARUB168DTE4 single frame models.
2
Nominal capacity applied with non-ducted indoor units, and is rated 0 ft. above sea level with 25 ft.
of refrigerant line per indoor unit and a 0 ft. level difference between outdoor and indoor units. All
capacities are net with a Combination Ratio between 95105%.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80F dry bulb (DB) and 67F
wet bulb (WB) and outdoor ambient conditions of 95F dry bulb (DB) and 75F wet bulb (WB).
Nominal heating capacity rating obtained with air entering the indoor unit at 70F dry bulb (DB) and
59F wet bulb (WB) and outdoor ambient conditions of 47F dry bulb (DB) and 43F wet bulb (WB).
3
Rated capacity is certified under AHRI Standard 1230. See www.ahrinet.org for information.
4
Cooling range with the Low Ambient Baffle Kit (sold separately) is -9.9F to +122F and is achieved only

3/8+1/2+1/2 Braze
7/8+1-1/8+1-1/8 Braze
3/4+3/4+7/8 Braze
23.6 + 23.6 + 23.6

3/14

3/8+5/8+5/8 Braze
7/8+1-1/8+1-1/8 Braze
3/4+7/8+7/8 Braze
23.6 + 23.6 + 23.6

1/2+5/8+5/8 Braze
1-1/8+1-1/8+1-1/8 Braze
3/4+7/8+7/8 Braze
23.6 + 23.6 + 23.6

when all indoor units are operating in cooling mode. Does not impact synchronous operating range.
5
The System Combination Ratio must be between 50130%.
6
Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
7
All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded, and must comply
with applicable local and national codes. Ensure the communication cable is properly grounded at the
master unit only. Do not ground the ODU-IDU communication cable at any other point.
8
Power wiring cable is field provided and must comply with the applicable local and national codes. See
page 33 for detailed electrical data.
9
Refer to the Refrigerant Piping section of this manual for correct line sizing. Contractor must use LG
manufactured Y-Branch and Header Kits only. Designer must verify refrigerant piping design configuration
using LGs computerized refrigerant piping (LATS Multi V) software to validate the pipe design.

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

PRODUCT DATA

23

Product Data

Table 14: Triple-Frame 208-230V Heat Recovery Units.


26.0 Ton
Combination Unit Model Number
ARUB312BTE4
ARUB072BTE4 +
Individual Component Model Numbers1 ARUB096BTE4 +
ARUB144BTE4
Cooling Performance
312,000
Nominal Cooling Cap. (Btu/h)2
296,000
Rated Cooling Cap. (Btu/h)3
Heating Performance
351,000
Nominal Heating Cap. (Btu/h)2
334,000
Rated Heating Cap. (Btu/h)3
Operating Range
14 to 122
Cooling (F DB)4
-13
to +61
Heating (F WB)
14 to 81
SynchronousCooling Based (F DB)
14 to 61
SynchronousHeating Based (F DB)
Compressor
HSS DC Scroll x 4
Inverter Quantity
PVE/FVC68D
Oil/Type
Fan (Top Discharge)
Propeller (BLDC)
Type

GENERAL DATA

MULTI V IV Outdoor Unit Engineering Manual

ARUB Series Heat Recovery Outdoor Unit Specifications

Table 15: Triple-Frame 208-230V Heat Recovery Units, continued.


36.0 Ton
Combination Unit Model Number
ARUB432BTE4
ARUB145BTE4 +
Individual Component Model Numbers1
ARUB145BTE4 +
ARUB145BTE4
Cooling Performance
432,000
Nominal Cooling Cap. (Btu/h)2
414,000
Rated Cooling Cap. (Btu/h)3
Heating Performance
486,000
Nominal Heating Cap. (Btu/h)2
462,000
Rated Heating Cap. (Btu/h)3
Operating Range
14 to 122
Cooling (F DB)4
-13 to +61
Heating (F WB)
14 to 81
Synchronous Cooling Based (F DB)
14 to 61
Synchronous Heating Based (F DB)
Compressor
HSS DC Scroll x 6
Inverter Quantity
PVE/FVC68D
Oil/Type
Fan (Top Discharge)
Propeller (BLDC)
Type
Motor Output (kW) x Qty.

0.60 x 2 + 0.60 x 2
+ 0.60 x 2

38.0 Ton
ARUB456BTE4
ARUB145BTE4 +
ARUB145BTE4 +
ARUB169BTE4

40.0 Ton
ARUB480BTE4
ARUB145BTE4 +
ARUB169BTE4 +
ARUB169BTE4

42.0 Ton
ARUB504BTE4
ARUB169BTE4 +
ARUB169BTE4 +
ARUB169BTE4

456,000
436,000

480,000
458,000

504,000
479,000

513,000
488,000

540,000
514,000

567,000
539,000

14 to 122
-13 to +61
14 to 81
14 to 61

14 to 122
-13 to +61
14 to 81
14 to 61

14 to 122
-13 to +61
14 to 81
14 to 61

HSS DC Scroll x 6
PVE/FVC68D

HSS DC Scroll x 6
PVE/FVC68D

HSS DC Scroll x 6
PVE/FVC68D

Propeller (BLDC)
Propeller (BLDC)
0.60 x 2 + 0.60 x 2
0.60 x 2 + 0.60 x 2
+ 0.60 x 2
+ 0.60 x 2
Brushless Digitally Controlled/Direct
0 - 1,100
0 - 1,100
80 - 1,100
80 - 1,100
30,600
30,600

Propeller (BLDC)
0.60 x 2 + 0.60 x 2
+ 0.60 x 2

Motor/Drive
0 - 1,100
0 - 1,100
Cooling
Operating
Range (RPM) Heating
80 - 1,100
80 - 1,100
30,600
30,600
Maximum Air Volume (CFM)
Unit Data
R410A
R410A
R410A
R410A
Refrigerant Type
EEV/Indoor Unit
EEV/Indoor Unit
EEV/Indoor Unit
EEV/Indoor Unit
Refrigerant Control/Location
1 - 64
1 - 64
1 - 64
1 - 64
Min. to Max. No. Indoor Units/System5
64.3
64.3
64.3
64.3
Sound Pressure dB(A)6
672 + 672 + 672
672 + 672 + 672
672 + 672 + 672
672 + 672 + 672
Net Unit Weight (lbs.)
705 + 705 + 705
705 + 705 + 705
705 + 705 + 705
705 + 705 + 705
Shipping Weight (lbs.)
2 x 18
2 x 18
2 x 18
2 x 18
Communication Cables7,8
Heat Exchanger
Copper Tube/Aluminum Fin and GoldFin/Hydrophilic
Material and Fin Coating
3/14
3/14
3/14
3/14
Rows/Fins per inch
Piping9
1/2 + 5/8 + 5/8 Braze
5/8 + 5/8 + 5/8 Braze
5/8 + 5/8 + 5/8 Braze
5/8 + 5/8 + 5/8 Braze
Liquid Line Connection (in., OD)
Low Pressure Vapor Line Conn (in., OD) 1-1/8+1-1/8+1-1/8 Braze 1-1/8+1-1/8+1-1/8 Braze 1-1/8+1-1/8+1-1/8 Braze 1-1/8+1-1/8+1-1/8 Braze
3/4 + 7/8 + 7/8 Braze
7/8 + 7/8 + 7/8 Braze
7/8 + 7/8 + 7/8 Braze
7/8 + 7/8 + 7/8 Braze
High Pressure Vapor Line Conn (in, OD)
23.6 + 23.6 + 23.6
23.6 + 23.6 + 23.6
23.6 + 23.6 + 23.6
23.6 + 23.6 + 23.6
Factory Charge lbs. of R410A

1
ARUB145BTE4/ARUB145DTE4, ARUB169BTE4/ARUB169DTE4 frames are ONLY for use in
large capacity triple frame combinations. They cannot be used as stand alone models or in a dual
frame combination. These frames ARE NOT interchangeable with ARUB144BTE4/ARUB144DTE4,
ARUB168BTE4/ARUB168DTE4 single frame models.
2
Nominal capacity applied with non-ducted indoor units, and is rated 0 ft. above sea level with 25 ft.
of refrigerant line per indoor unit and a 0 ft. level difference between outdoor and indoor units. All
capacities are net with a Combination Ratio between 95105%.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80F dry bulb (DB) and 67F
wet bulb (WB) and outdoor ambient conditions of 95F dry bulb (DB) and 75F wet bulb (WB).
Nominal heating capacity rating obtained with air entering the indoor unit at 70F dry bulb (DB) and
59F wet bulb (WB) and outdoor ambient conditions of 47F dry bulb (DB) and 43F wet bulb (WB).
3
Rated capacity is certified under AHRI Standard 1230. See www.ahrinet.org for information.
4
Cooling range with the Low Ambient Baffle Kit (sold separately) is -9.9F to +122F and is achieved only
when all indoor units are operating in cooling mode. Does not impact synchronous operating range.

24

PRODUCT DATA

The System Combination Ratio must be between 50130%.


Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
7
All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded, and must comply
with applicable local and national codes. Ensure the communication cable is properly grounded at the
master unit only. Do not ground the ODU-IDU communication cable at any other point.
8
Power wiring cable is field provided and must comply with the applicable local and national codes. See
page 33 for detailed electrical data.
9
Refer to the Refrigerant Piping section of this manual for correct line sizing. Contractor must use LG
manufactured Y-Branch and Header Kits only. Designer must verify refrigerant piping design configuration
using LGs computerized refrigerant piping (LATS Multi V) software to validate the pipe design.
5
6

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

GENERAL DATA
ARUB Series Heat Recovery Outdoor Unit Specifications

Table 16: Single-Frame 460V Heat Recovery Units.


Combination Unit Model Number

8.0 Ton
ARUB096DTE4
-

10.0 Ton
ARUB121DTE4
-

12.0
ARUB144DTE4
-

14.0
ARUB168DTE4
-

72,000
69,000

96,000
92,000

120,000
114,000

144,000
138,000

168,000
160,000

81,000
77,000

108,000
103,000

135,000
129,000

162,000
154,000

189,000
180,000

14 to 122
-13 to +61
14 to 81
14 to 61

14 to 122
-13 to +61
14 to 81
14 to 61

14 to 122
-13 to +61
14 to 81
14 to 61

14 to 122
-13 to +61
14 to 81
14 to 61

14 to 122
-13 to +61
14 to 81
14 to 61

HSS DC Scroll x 1
PVE/FVC68D

HSS DC Scroll x 1
PVE/FVC68D

HSS DC Scroll x 1
PVE/FVC68D

HSS DC Scroll x 2
PVE/FVC68D

HSS DC Scroll x 2
PVE/FVC68D

Propeller (BLDC)
0.75 x 1

Propeller (BLDC)
Propeller (BLDC)
Propeller (BLDC)
0.60 x 2
0.60 x 2
0.60 x 2
Brushless Digitally Controlled/Direct
0 - 1,050
0 - 1,050
0 - 1,100
80 - 1,050
80 - 1,050
80 - 1,100
9,850
9,850
10,200

Propeller (BLDC)
0.60 x 2

R410A
EEV/Indoor Unit

R410A
EEV/Indoor Unit

R410A
EEV/Indoor Unit

R410A
EEV/Indoor Unit

R410A
EEV/Indoor Unit

1 - 13

1 - 16

1 - 20

1 - 24

1 - 29

58.5
430
452
2 x 18

59.0
540
573
2 x 18

59.0
540
573
2 x 18

59.5
628
661
2 x 18

59.5
628
661
2 x 18

0 - 850
80 - 850
7,400

3/14
3/8 Braze
3/4 Braze
5/8 Braze
16.9

Copper Tube/Aluminum Fin and GoldFin/Hydrophilic


3/14
3/14
3/14
3/8 Braze
7/8 Braze
3/4 Braze
23.6

Nominal capacity applied with non-ducted indoor units, and is rated 0 ft. above sea level with 25 ft.
of refrigerant line per indoor unit and a 0 ft. level difference between outdoor and indoor units. All
capacities are net with a Combination Ratio between 95105%.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80F dry bulb (DB) and 67F
wet bulb (WB) and outdoor ambient conditions of 95F dry bulb (DB) and 75F wet bulb (WB).
Nominal heating capacity rating obtained with air entering the indoor unit at 70F dry bulb (DB) and
59F wet bulb (WB) and outdoor ambient conditions of 47F dry bulb (DB) and 43F wet bulb (WB).
2
Rated capacity is certified under AHRI Standard 1230. See www.ahrinet.org for information.
3
Cooling range with the Low Ambient Baffle Kit (sold separately) is -9.9F to +122F and is achieved only
when all indoor units are operating in cooling mode. Does not impact synchronous operating range.
4
The System Combination Ratio must be between 50130%.
1

1/2 Braze
1-1/8 Braze
3/4 Braze
23.6

1/2 Braze
1-1/8 Braze
7/8 Braze
23.6

Product Data

Individual Component Model Numbers


Cooling Performance
Nominal Cooling Capacity (Btu/h)1
Rated Cooling Capacity (Btu/h)2
Heating Performance
Nominal Heating Capacity (Btu/h)1
Rated Heating Capacity (Btu/h)2
Operating Range
Cooling (F DB)3
Heating (F WB)
Synchronous Cooling Based (F DB)
Synchronous Heating Based (F DB)
Compressor
Inverter Quantity
Oil/Type
Fan (Top Discharge)
Type
Motor Output (kW) x Qty.
Motor/Drive
Operating Range Cooling
(RPM)
Heating
Maximum Air Volume (CFM)
Unit Data
Refrigerant Type
Refrigerant Control/Location
Min. to Max. Number Indoor Units/
System4
Sound Pressure dB(A)5
Net Unit Weight (lbs.)
Shipping Weight (lbs.)
Communication Cables6,7
Heat Exchanger
Material and Fin Coating
Rows/Fins per inch
Piping8
Liquid Line Connection (in., OD)
Low Pressure Vapor Line Conn (in., OD)
High Pressure Vapor Line Conn (in, OD)
Factory Charge lbs. of R410A

6.0 Ton
ARUB072DTE4
-

0 - 1,100
80 - 1,100
10,200

3/14
5/8 Braze
1-1/8 Braze
7/8 Braze
23.6

Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded, and must comply
with applicable local and national codes. Ensure the communication cable is properly grounded at the
master unit only. Do not ground the ODU-IDU communication cable at any other point.
7
Power wiring cable is field provided and must comply with the applicable local and national codes. See
page 34 for detailed electrical data.
8
Refer to the Refrigerant Piping section of this manual for correct line sizing. Contractor must use LG
manufactured Y-Branch and Header Kits only. Designer must verify refrigerant piping design configuration using LGs computerized refrigerant piping (LATS Multi V) software to validate the pipe design.
5
6

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

PRODUCT DATA

25

GENERAL DATA
ARUB Series Heat Recovery Outdoor Unit Specifications

Table 17: Dual-Frame 460V Heat Recovery Units.


Combination Unit Model Number
Individual Component Model Numbers

MULTI V IV Outdoor Unit Engineering Manual

Cooling Performance
Nominal Cooling Cap. (Btu/h)1
Rated Cooling Cap. (Btu/h)2
Heating Performance
Nominal Heating Cap. (Btu/h)1
Rated Heating Cap. (Btu/h)2
Operating Range
Cooling (F DB)3
Heating (F WB)
SynchronousCooling Based (F DB)
SynchronousHeating Based (F DB)
Compressor
Inverter Quantity
Oil/Type
Fan (Top Discharge)
Type
Motor Output (kW) x Qty.
Motor/Drive
Cooling
Operation. Range (RPM)
Heating
Maximum Air Volume (CFM)
Unit Data
Refrigerant Type
Refrigerant Control/Location
Min. to Max. No. Indoor Units/System4
Sound Pressure dB(A)5
Net Unit Weight (lbs.)
Shipping Weight (lbs.)
Communication Cables6,7
Heat Exchanger
Material and Fin Coating
Rows/Fins per inch
Piping8
Liquid Line Conn. (in., OD)
Low Pressure Vapor Line Conn. (in., OD)
High Pressure Vapor Line Conn (in, OD)
Factory Charge lbs. of R410A

16.0 Ton
ARUB192DTE4
ARUB072DTE4 +
ARUB121DTE4

18.0 Ton
ARUB216DTE4
ARUB072DTE4 +
ARUB144DTE4

20.0 Ton
ARUB240DTE4
ARUB096DTE4 +
ARUB144DTE4

22.0 Ton
ARUB264DTE4
ARUB121DTE4+
ARUB144DTE4

192,000
184,000

216,000
206,000

240,000
228,000

264,000
250,000

216,000
206,000

243,000
230,000

270,000
256,000

297,000
282,000

14 to 122
-13 to +61
14 to 81
14 to 61

14 to 122
-13 to +61
14 to 81
14 to 61

14 to 122
-13 to +61
14 to 81
14 to 61

14 to 122
-13 to +61
14 to 81
14 to 61

HSS DC Scroll x 2
PVE/FVC68D

HSS DC Scroll x 3
PVE/FVC68D

HSS DC Scroll x 3
PVE/FVC68D

HSS DC Scroll x 3
PVE/FVC68D

Propeller (BLDC)
0.75 + 0.60 x 2

Propeller (BLDC)
Propeller (BLDC)
0.75 + 0.60 x 2
0.60 x 2 + 0.60 x 2
Brushless Digitally Controlled/Direct
0 - 1,100
0 - 1,100
80 - 1,100
80 - 1,100
17,600
20,050

Propeller (BLDC)
0.60 x 2 + 0.60 x 2

0 - 1,050
80 - 1,050
17,250
R410A
EEV/Indoor Unit
1 - 32
61.8
430 + 540
452 + 573
2 x 18

3/14

26

PRODUCT DATA

R410A
EEV/Indoor Unit
1 - 39
62.3
540 + 628
573 + 661
2 x 18

Copper Tube/Aluminum Fin and GoldFin/Hydrophilic


3/14
3/14

3/8 + 1/2 Braze


3/4 + 1-1/8 Braze
5/8 + 3/4 Braze
16.9 + 23.6

Nominal capacity applied with non-ducted indoor units, and is rated 0 ft. above sea level with 25 ft.
of refrigerant line per indoor unit and a 0 ft. level difference between outdoor and indoor units. All
capacities are net with a Combination Ratio between 95105%.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80F dry bulb (DB) and 67F
wet bulb (WB) and outdoor ambient conditions of 95F dry bulb (DB) and 75F wet bulb (WB).
Nominal heating capacity rating obtained with air entering the indoor unit at 70F dry bulb (DB) and
59F wet bulb (WB) and outdoor ambient conditions of 47F dry bulb (DB) and 43F wet bulb (WB).
2
Rated capacity is certified under AHRI Standard 1230. See www.ahrinet.org for information.
3
Cooling range with the Low Ambient Baffle Kit (sold separately) is -9.9F to +122F and is achieved only
when all indoor units are operating in cooling mode. Does not impact synchronous operating range.
4
The System Combination Ratio must be between 50130%.
1

R410A
EEV/Indoor Unit
1 - 35
62.0
430 + 628
452 + 661
2 x 18

3/8 + 1/2 Braze


3/4 + 1-1/8 Braze
5/8 + 7/8 Braze
16.9 + 23.6

3/8 + 1/2 Braze


7/8 + 1-1/8 Braze
3/4 + 7/8 Braze
23.6 + 23.6

0 - 1,100
80 - 1,100
20,050
R410A
EEV/Indoor Unit
1 - 42
62.3
540 + 628
573 + 661
2 x 18

3/14
1/2 + 1/2 Braze
1-1/8 + 1-1/8 Braze
3/4 + 7/8 Braze
23.6 + 23.6

Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded, and must comply
with applicable local and national codes. Ensure the communication cable is properly grounded at the
master unit only. Do not ground the ODU-IDU communication cable at any other point.
7
Power wiring cable is field provided and must comply with the applicable local and national codes. See
page 34 for detailed electrical data.
8
Refer to the Refrigerant Piping section of this manual for correct line sizing. Contractor must use LG
manufactured Y-Branch and Header Kits only. Designer must verify refrigerant piping design configuration using LGs computerized refrigerant piping (LATS Multi V) software to validate the pipe design.
5
6

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

GENERAL DATA
ARUB Series Heat Recovery Outdoor Unit Specifications

Table 18: Dual-Frame 460V Heat Recovery Units, continued.


Combination Unit Model Number
Individual Component Model Numbers

26.0 Ton
ARUB313DTE4
ARUB144DTE4 +
ARUB168DTE4

28.0 Ton
ARUB337DTE4
ARUB168DTE4 +
ARUB168DTE4

288,000
274,000

312,000
296,000

336,000
320,000

324,000
308,000

351,000
334,000

378,000
361,000

14 to 122
-13 to +61
14 to 81
14 to 61

14 to 122
-13 to +61
14 to 81
14 to 61

14 to 122
-13 to +61
14 to 81
14 to 61

HSS DC Scroll x 4
PVE/FVC68D

HSS DC Scroll x 4
PVE/FVC68D

HSS DC Scroll x 4
PVE/FVC68D

Propeller (BLDC)
0.60 x 2 + 0.60 x 2

Propeller (BLDC)
0.60 x 2 + 0.60 x 2

0 - 1,100
80 - 1,100
20,400

Propeller (BLDC)
0.60 x 2 + 0.60 x 2
Brushless Digitally Controlled/Direct
0 - 1,100
80 - 1,100
20,400

R410A
EEV/Indoor Unit
1 - 45
62.5
628 + 628
661 + 661
2 x 18

R410A
EEV/Indoor Unit
1 - 52
62.5
628 + 628
661 + 661
2 x 18

R410A
EEV/Indoor Unit
1 - 55
62.5
628 + 628
661 + 661
2 x 18

3/14

Nominal capacity applied with non-ducted indoor units, and is rated 0 ft. above sea level with 25 ft.
of refrigerant line per indoor unit and a 0 ft. level difference between outdoor and indoor units. All
capacities are net with a Combination Ratio between 95105%.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80F dry bulb (DB) and 67F
wet bulb (WB) and outdoor ambient conditions of 95F dry bulb (DB) and 75F wet bulb (WB).
Nominal heating capacity rating obtained with air entering the indoor unit at 70F dry bulb (DB) and
59F wet bulb (WB) and outdoor ambient conditions of 47F dry bulb (DB) and 43F wet bulb (WB).
2
Rated capacity is certified under AHRI Standard 1230. See www.ahrinet.org for information.
3
Cooling range with the Low Ambient Baffle Kit (sold separately) is -9.9F to +122F and is achieved only
when all indoor units are operating in cooling mode. Does not impact synchronous operating range.
4
The System Combination Ratio must be between 50130%.
1

0 - 1,100
80 - 1,100
20,400

Copper Tube/Aluminum Fin and GoldFin/Hydrophilic


3/14

1/2 + 1/2 Braze


1-1/8 + 1-1/8 Braze
7/8 + 7/8 Braze
23.6 + 23.6

1/2 + 5/8 Braze


1-1/8 + 1-1/8 Braze
7/8 + 7/8 Braze
23.6 + 23.6

Product Data

Cooling Performance
Nominal Cooling Cap. (Btu/h)1
Rated Cooling Cap. (Btu/h)2
Heating Performance
Nominal Heating Cap. (Btu/h)1
Rated Heating Cap. (Btu/h)2
Operating Range
Cooling (F DB)3
Heating (F WB)
SynchronousCooling Based (F DB)
SynchronousHeating Based (F DB)
Compressor
Inverter Quantity
Oil/Type
Fan (Top Discharge)
Type
Motor Output (kW) x Qty.
Motor/Drive
Cooling
Operation. Range (RPM)
Heating
Maximum Air Volume (CFM)
Unit Data
Refrigerant Type
Refrigerant Control/Location
Min. to Max. No. Indoor Units/System4
Sound Pressure dB(A)5
Net Unit Weight (lbs.)
Shipping Weight (lbs.)
Communication Cables6,7
Heat Exchanger
Material and Fin Coating
Rows/Fins per inch
Piping8
Liquid Line Conn. (in., OD)
Low Pressure Vapor Line Conn. (in., OD)
High Pressure Vapor Line Conn (in, OD)
Factory Charge lbs. of R410A

24.0 Ton
ARUB288DTE4
ARUB144DTE4 +
ARUB144DTE4

3/14

5/8 + 5/8 Braze


1-1/8 + 1-1/8 Braze
7/8 + 7/8 Braze
23.6 + 23.6

Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded, and must comply
with applicable local and national codes. Ensure the communication cable is properly grounded at the
master unit only. Do not ground the ODU-IDU communication cable at any other point.
7
Power wiring cable is field provided and must comply with the applicable local and national codes. See
page 34 for detailed electrical data.
8
Refer to the Refrigerant Piping section of this manual for correct line sizing. Contractor must use LG
manufactured Y-Branch and Header Kits only. Designer must verify refrigerant piping design configuration using LGs computerized refrigerant piping (LATS Multi V) software to validate the pipe design.
5
6

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

PRODUCT DATA

27

GENERAL DATA

MULTI V IV Outdoor Unit Engineering Manual

ARUB Series Heat Recovery Outdoor Unit Specifications

Table 19: Triple-Frame 460V Heat Recovery Units.


26.0 Ton
Combination Unit Model Number
ARUB312DTE4
ARUB072DTE4 +
Individual Component Model Numbers1 ARUB096DTE4 +
ARUB144DTE4
Cooling Performance
312,000
Nominal Cooling Cap. (Btu/h)2
296,000
Rated Cooling Cap. (Btu/h)3
Heating Performance
351,000
Nominal Heating Cap. (Btu/h)2
334,000
Rated Heating Cap. (Btu/h)3
Operating Range
14 to 122
Cooling (F DB)4
-13 to +61
Heating (F WB)
14 to 81
Synchronous Cooling Based (F DB)
14 to 61
Synchronous Heating Based (F DB)
Compressor
HSS DC Scroll x 4
Inverter Quantity
PVE/FVC68D
Oil/Type
Fan (Top Discharge)
Propeller (BLDC)
Type
Motor Output (kW) x Qty.

0.75 + 0.60 x 2
+ 0.60 x 2

28.0 Ton
ARUB336DTE4
ARUB096DTE4 +
ARUB096DTE4 +
ARUB144DTE4

30.0 Ton
ARUB360DTE4
ARUB096DTE4 +
ARUB121DTE4 +
ARUB144DTE4

32.0 Ton
ARUB384DTE4
ARUB096DTE4 +
ARUB145DTE4 +
ARUB145DTE4

34.0 Ton
ARUB408DTE4
ARUB121DTE4 +
ARUB145DTE4 +
ARUB145DTE4

336,000
320,000

360,000
342,000

384,000
366,000

408,000
390,000

378,000
361,000

405,000
387,000

432,000
412,000

459,000
437,000

14 to 122
-13 to +61
14 to 81
14 to 61

14 to 122
-13 to +61
14 to 81
14 to 61

14 to 122
-13 to +61
14 to 81
14 to 61

14 to 122
-13 to +61
14 to 81
14 to 61

HSS DC Scroll x 4
PVE/FVC68D

HSS DC Scroll x 4
PVE/FVC68D

HSS DC Scroll x 5
PVE/FVC68D

HSS DC Scroll x 5
PVE/FVC68D

Propeller (BLDC)
Propeller (BLDC)
Propeller (BLDC)
0.60 x 2 + 0.60 x 2
0.60 x 2 + 0.60 x 2
0.60 x 2 + 0.60 x 2
+ 0.60 x 2
+ 0.60 x 2
+ 0.60 x 2
Brushless Digitally Controlled/Direct
0 - 1,100
0 - 1,100
0 - 1,100
80 - 1,100
80 - 1,100
80 - 1,100
29,900
29,900
30,250

Propeller (BLDC)
0.60 x 2 + 0.60 x 2
+ 0.60 x 2

Motor/Drive
0 - 1,100
Cooling
Operating
Range (RPM) Heating
80 - 1,100
27,450
Maximum Air Volume (CFM)
Unit Data
R410A
R410A
R410A
R410A
Refrigerant Type
EEV/Indoor Unit
EEV/Indoor Unit
EEV/Indoor Unit
EEV/Indoor Unit
Refrigerant Control/Location
1 - 52
1 - 55
1 - 58
1 - 61
Min. to Max. No. Indoor Units/System5
63.8
63.9
63.9
64.1
Sound Pressure dB(A)6
430 + 540 + 628
540 + 540 + 628
540 + 540 + 628
540 + 672 + 672
Net Unit Weight (lbs.)
452 + 573 + 661
573 + 573 + 661
573 + 573 + 661
573 + 705 + 705
Shipping Weight (lbs.)
2 x 18
2 x 18
2 x 18
2 x 18
Communication Cables7,8
Heat Exchanger
Copper Tube/Aluminum Fin and GoldFin/Hydrophilic
Material and Fin Coating
3/14
3/14
3/14
3/14
Rows/Fins per inch
Piping9
3/8+3/8+1/2 Braze 3/8+3/8+1/2 Braze 3/8+1/2+1/2 Braze 3/8+5/8+5/8 Braze
Liquid Line Conn. (in., OD)
Low Pressure Vapor Line Conn. (in., OD) 3/4+7/8+1-1/8 Braze 7/8+7/8+1-1/8 Braze 7/8+1-1/8+1-1/8 Braze 7/8+1-1/8+1-1/8 Braze
High Pressure Vapor Line Conn (in, OD) 5/8+3/4+7/8 Braze 3/4+3/4+7/8 Braze 3/4+3/4+7/8 Braze 3/4+7/8+7/8 Braze
16.9 + 23.6 + 23.6 23.6 + 23.6 + 23.6 23.6 + 23.6 + 23.6 23.6 + 23.6 + 23.6
Factory Charge lbs. of R410A
1
ARUB145BTE4/ARUB145DTE4, ARUB169BTE4/ARUB169DTE4 frames are ONLY for use in
large capacity triple frame combinations. They cannot be used as stand alone models or in a dual
frame combination. These frames ARE NOT interchangeable with ARUB144BTE4/ARUB144DTE4,
ARUB168BTE4/ARUB168DTE4 single frame models.
2
Nominal capacity applied with non-ducted indoor units, and is rated 0 ft. above sea level with 25 ft.
of refrigerant line per indoor unit and a 0 ft. level difference between outdoor and indoor units. All
capacities are net with a Combination Ratio between 95105%.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80F dry bulb (DB) and 67F
wet bulb (WB) and outdoor ambient conditions of 95F dry bulb (DB) and 75F wet bulb (WB).
Nominal heating capacity rating obtained with air entering the indoor unit at 70F dry bulb (DB) and
59F wet bulb (WB) and outdoor ambient conditions of 47F dry bulb (DB) and 43F wet bulb (WB).
3
Rated capacity is certified under AHRI Standard 1230. See www.ahrinet.org for information.
4
Cooling range with the Low Ambient Baffle Kit (sold separately) is -9.9F to +122F and is achieved only

28

PRODUCT DATA

0 - 1,100
80 - 1,100
30,250
R410A
EEV/Indoor Unit
1 - 64
64.1
540 + 672 + 672
573 + 705 + 705
2 x 18
3/14
1/2+5/8+5/8 Braze
1-1/8+1-1/8+1-1/8 Braze
3/4+7/8+7/8 Braze
23.6 + 23.6 + 23.6

when all indoor units are operating in cooling mode. Does not impact synchronous operating range.
5
The System Combination Ratio must be between 50130%.
6
Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
7
All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded, and must comply
with applicable local and national codes. Ensure the communication cable is properly grounded at the
master unit only. Do not ground the ODU-IDU communication cable at any other point.
8
Power wiring cable is field provided and must comply with the applicable local and national codes. See
page 34 for detailed electrical data.
9
Refer to the Refrigerant Piping section of this manual for correct line sizing. Contractor must use LG
manufactured Y-Branch and Header Kits only. Designer must verify refrigerant piping design configuration
using LGs computerized refrigerant piping (LATS Multi V) software to validate the pipe design.

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

GENERAL DATA
ARUB Series Heat Recovery Outdoor Unit Specifications

1
ARUB145BTE4/ARUB145DTE4, ARUB169BTE4/ARUB169DTE4 frames are ONLY for use in
large capacity triple frame combinations. They cannot be used as stand alone models or in a dual
frame combination. These frames ARE NOT interchangeable with ARUB144BTE4/ARUB144DTE4,
ARUB168BTE4/ARUB168DTE4 single frame models.
2
Nominal capacity applied with non-ducted indoor units, and is rated 0 ft. above sea level with 25 ft.
of refrigerant line per indoor unit and a 0 ft. level difference between outdoor and indoor units. All
capacities are net with a Combination Ratio between 95105%.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80F dry bulb (DB) and 67F
wet bulb (WB) and outdoor ambient conditions of 95F dry bulb (DB) and 75F wet bulb (WB).
Nominal heating capacity rating obtained with air entering the indoor unit at 70F dry bulb (DB) and
59F wet bulb (WB) and outdoor ambient conditions of 47F dry bulb (DB) and 43F wet bulb (WB).
3
Rated capacity is certified under AHRI Standard 1230. See www.ahrinet.org for information.
4
Cooling range with the Low Ambient Baffle Kit (sold separately) is -9.9F to +122F and is achieved only
when all indoor units are operating in cooling mode. Does not impact synchronous operating range.

The System Combination Ratio must be between 50130%.


Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
7
All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded, and must comply
with applicable local and national codes. Ensure the communication cable is properly grounded at the
master unit only. Do not ground the ODU-IDU communication cable at any other point.
8
Power wiring cable is field provided and must comply with the applicable local and national codes. See
page 34 for detailed electrical data.
9
Refer to the Refrigerant Piping section of this manual for correct line sizing. Contractor must use LG
manufactured Y-Branch and Header Kits only. Designer must verify refrigerant piping design configuration
using LGs computerized refrigerant piping (LATS Multi V) software to validate the pipe design.
5
6

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

PRODUCT DATA

29

Product Data

Table 20: Triple-Frame 460V Heat Recovery Units, continued.


36.0 Ton
38.0 Ton
40.0 Ton
42.0 Ton
Combination Unit Model Number
ARUB432DTE4
ARUB456DTE4
ARUB480DTE4
ARUB504DTE4
ARUB145DTE4 +
ARUB145DTE4 +
ARUB145DTE4 +
ARUB169DTE4 +
Individual Component Model Numbers1
ARUB145DTE4 +
ARUB145DTE4 +
ARUB169DTE4 +
ARUB169DTE4 +
ARUB145DTE4
ARUB169DTE4
ARUB169DTE4
ARUB169DTE4
Cooling Performance
432,000
456,000
480,000
504,000
Nominal Cooling Cap. (Btu/h)2
414,000
436,000
458,000
479,000
Rated Cooling Cap. (Btu/h)3
Heating Performance
486,000
513,000
540,000
567,000
Nominal Heating Cap. (Btu/h)2
462,000
488,000
514,000
539,000
Rated Heating Cap. (Btu/h)3
Operating Range
14 to 122
14 to 122
14 to 122
14 to 122
Cooling (F DB)4
-13 to +61
-13 to +61
-13 to +61
-13 to +61
Heating (F WB)
14 to 81
14 to 81
14 to 81
14 to 81
SynchronousCooling Based (F DB)
14 to 61
14 to 61
14 to 61
14 to 61
SynchronousHeating Based (F DB)
Compressor
HSS DC Scroll x 6
HSS DC Scroll x 6
HSS DC Scroll x 6
HSS DC Scroll x 6
Inverter Quantity
PVE/FVC68D
PVE/FVC68D
PVE/FVC68D
PVE/FVC68D
Oil/Type
Fan (Top Discharge)
Propeller (BLDC)
Propeller (BLDC)
Propeller (BLDC)
Propeller (BLDC)
Type
0.60x2 + 0.60x2 + 0.60x2 0.60x2 + 0.60x2 + 0.60x2 0.60x2 + 0.60x2 + 0.60x2 0.60x2 + 0.60x2 + 0.60x2
Motor Output (kW) x Qty.
Brushless Digitally Controlled/Direct
Motor/Drive
0 - 1,100
0 - 1,100
0 - 1,100
0 - 1,100
Cooling
Operating Range (RPM)
80 - 1,100
80 - 1,100
80 - 1,100
80 - 1,100
Heating
30,600
30,600
30,600
30,600
Maximum Air Volume (CFM)
Unit Data
R410A
R410A
R410A
R410A
Refrigerant Type
EEV/Indoor Unit
EEV/Indoor Unit
EEV/Indoor Unit
EEV/Indoor Unit
Refrigerant Control/Location
1 - 64
1 - 64
1 - 64
1 - 64
Min. to Max. No. Indoor Units/System5
64.3
64.3
64.3
64.3
Sound Pressure dB(A)6
672 + 672 + 672
672 + 672 + 672
672 + 672 + 672
672 + 672 + 672
Net Unit Weight (lbs.)
705 + 705 + 705
705 + 705 + 705
705 + 705 + 705
705 + 705 + 705
Shipping Weight (lbs.)
2 x 18
2 x 18
2 x 18
2 x 18
Communication Cables7,8
Heat Exchanger
Copper Tube/Aluminum Fin and GoldFin/Hydrophilic
Material and Fin Coating
3/14
3/14
3/14
3/14
Rows/Fins per inch
Piping9
5/8 + 5/8 + 5/8 Braze
5/8 + 5/8 + 5/8 Braze
5/8 + 5/8 + 5/8 Braze
5/8 + 5/8 + 5/8 Braze
Liquid Line Conn. (in., OD)
Low Pressure Vapor Line Conn. (in., OD) 1-1/8+1-1/8+1-1/8 Braze 1-1/8+1-1/8+1-1/8 Braze 1-1/8+1-1/8+1-1/8 Braze 1-1/8+1-1/8+1-1/8 Braze
7/8 + 7/8 + 7/8 Braze
7/8 + 7/8 + 7/8 Braze
7/8 + 7/8 + 7/8 Braze
7/8 + 7/8 + 7/8 Braze
High Pressure Vapor Line Conn (in, OD)
23.6 + 23.6 + 23.6
23.6 + 23.6 + 23.6
23.6 + 23.6 + 23.6
23.6 + 23.6 + 23.6
Factory Charge lbs. of R410A

GENERAL DATA
Heat Recovery Unit Specifications and Electrical Data

Figure 2: Three-Port Heat Recovery Unit.

MULTI V IV Outdoor Unit Engineering Manual

Figure 1: Two-Port Heat Recovery Unit.

Figure 3: Four-Port Heat Recovery Unit.

Heat recovery units can only be used with LG heat recovery systems.
Table 21: Heat Recovery Unit Specifications.
Model

PRHR022A

PRHR032A

PRHR042A

Number of Ports

Max. Connectable No. of Indoor Units

16

24

32

Max. Connectable No. of Indoor Units on each port

Max. Port Capacity (each port)

Btu/h

54,000

54,000

54,000

Max. Unit Capacity (sum of ports)

Btu/h

192,000

192,000

192,000

Net Weight

lbs.

45

49

Dimensions (W x H x D)

inches

40

17-7/8 x 8-5/8 x 18-15/16

Casing

Galvanized steel plate

To Indoor Units
Connecting Pipes

To Outdoor
Units

Liquid Pipe (inches)

3/8

Vapor Pipe (inches)

5/8

Liquid (inches)

3/8

1/2

5/8

Low-pressure Vapor (inches)

7/8

1-1/8

1-1/8

High-pressure Vapor (inches)

3/4

7/8

7/8

Insulation Material

Polyethylene

Minimum Circuit Amps (MCA)

Current

0.1

0.15

Maximum Fuse Amps (MFA)

0.2

15

Power Supply

1, 208-230V, 60Hz

Table 22: Heat Recovery Unit Electrical Data.


Unit Model No.

30

V / Hz / Ph

Input (kW)
Cooling

Heating

PRHR022A

208-230 / 60 / 1

0.026

0.026

PRHR032A

208-230 / 60 / 1

0.033

0.033

PRHR042A

208-230 / 60 / 1

0.040

0.040

PRODUCT DATA

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

ELECTRICAL DATA
ARUN Series Heat Pump Outdoor Units

Table 23: 208-230V, 60Hz, 3-Phase Heat Pump Units.


Compressor (Comp.)

Condenser Fan
Motor(s)
Amps

Motor Amps
Nom.
Tons

ARUN072BTE4
ARUN096BTE4
ARUN121BTE4
ARUN144BTE4
ARUN168BTE4
ARUN192BTE4
ARUN216BTE4
ARUN240BTE4
ARUN264BTE4
ARUN288BTE4
ARUN313BTE4
ARUN337BTE4
ARUN312BTE4
ARUN336BTE4
ARUN360BTE4
ARUN384BTE4
ARUN408BTE4
ARUN432BTE4
ARUN456BTE4
ARUN480BTE4
ARUN504BTE4

Motor RLA (Ea.)

Comp.
Qty.

1
1
1
2
2
2
3
3
3
4
4
4
4
4
4
5
5
6
6
6
6

Frame
1
2
3
Comp. Comp. Comp. Comp. Comp. Comp.
A
B
A
B
A
B
17.0
27.3
27.4
19.0
20.7
17.0
17.0
27.3
27.4
19.0
20.7
20.7
17.0
27.3
27.3
27.3
27.4
27.2
27.2
27.2
27.2

19.0
20.7
19.0
20.7
20.7
17.0
17.0
17.0
17.0

27.4
19.0
19.0
19.0
19.0
19.0
20.7
27.3
27.3
27.4
27.2
27.2
27.2
27.2
27.2
27.2

For component model nos. see the specification tables on p. 10-14.


Voltage tolerance is 10%.
Maximum allowable voltage unbalance is 2%.
MCA = Minimum Circuit Ampacity.

19.0
19.0
19.0
19.0
19.0
20.7
17.0
17.0
17.0
17.0
17.0
17.0

19.0
19.0
19.0
27.2
27.2
27.2
27.2
27.2
27.2

19.0
19.0
19.0
17.0
17.0
17.0
17.0
17.0
17.0

Fan
Qty.

1
2
2
2
2
3
3
4
4
4
4
4
5
6
6
6
6
6
6
6
6

FLA (Ea.)
Frame
1

4.0
6.0
6.0
6.0
6.0
4.0
4.0
6.0
6.0
6.0
6.0
6.0
4.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0

6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0

6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0

MOCP

RFA

Frame

Frame

Frame

25.3
40.1
40.3
48.8
52.5
25.3
25.3
40.1
40.3
48.8
48.8
52.5
25.3
40.1
40.1
40.1
40.3
57.0
57.0
57.0
57.0

40.3
48.8
48.8
48.8
48.8
52.5
52.5
40.1
40.1
40.3
57.0
57.0
57.0
57.0
57.0
57.0

48.8
48.8
48.8
57.0
57.0
57.0
57.0
57.0
57.0

40
60
60
60
70
40
40
60
60
60
60
70
40
60
60
60
60
80*
80*
80*
80*

60
60
60
60
60
70
70
60
60
60
80*
80*
80*
80*
80*
80*

60
60
60
80*
80*
80*
80*
80*
80*

35
50
50
60
70
35
35
50
50
60
60
70
35
50
50
50
50
80
80
80
80

50
60
60
60
60
70
70
50
50
50
80
80
80
80
80
80

60
60
60
80
80
80
80
80
80

Product Data

6.0
8.0
10.0
12.0
14.0
16.0
18.0
20.0
22.0
24.0
26.0
28.0
26.0
28.0
30.0
32.0
34.0
36.0
38.0
40.0
42.0

Unit Model
Nos.

MCA

Maximum Overcurrent Protection (MOCP) is calculated as follows: (Largest motor FLA x 2.25) + (Sum of
other motor FLA) rounded down to the nearest standard fuse size.
RFA = Recommended Fuse Amps.
*SCCR rating: 5kA RMS Symmetrical.

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

PRODUCT DATA

31

ELECTRICAL DATA
ARUN Series Heat Pump Outdoor Units

Table 24: 460V, 60Hz, 3-Phase Heat Pump Units.

Condenser Fan
Motor(s)
Amps

Compressor (Comp.)
Motor Amps

MULTI V IV Outdoor Unit Engineering Manual

Nom. Unit Model Nos.


Comp.
Tons
Qty.

6.0
8.0
10.0
12.0
14.0
16.0
18.0
20.0
22.0
24.0
26.0
28.0
26.0
28.0
30.0
32.0
34.0
36.0
38.0
40.0
42.0

ARUN072DTE4
ARUN096DTE4
ARUN121DTE4
ARUN144DTE4
ARUN168DTE4
ARUN192DTE4
ARUN216DTE4
ARUN240DTE4
ARUN264DTE4
ARUN288DTE4
ARUN313DTE4
ARUN337DTE4
ARUN312DTE4
ARUN336DTE4
ARUN360DTE4
ARUN384DTE4
ARUN408DTE4
ARUN432DTE4
ARUN456DTE4
ARUN480DTE4
ARUN504DTE4

1
1
1
2
2
2
3
3
3
4
4
4
4
4
4
5
5
6
6
6
6

Motor RLA (Ea.)

Fan
Frame
Qty.
1
2
3
Comp. Comp. Comp. Comp. Comp. Comp.
A
B
A
B
A
B
11.7
16.5
17.1
12.9
13.9
11.7
11.7
16.5
17.1
12.9
13.9
13.9
11.7
16.5
16.5
16.5
17.1
16.2
16.2
16.2
16.2

12.9
13.9
12.9
13.9
13.9
12.9
12.9
12.9
12.9

For component model nos. see the specification tables on p. 15-19.


Voltage tolerance is 414-528V.
Maximum allowable voltage unbalance is 2%.
MCA = Minimum Circuit Ampacity.

32

PRODUCT DATA

17.1
12.9
12.9
12.9
12.9
12.9
13.9
16.5
16.5
17.1
16.2
16.2
16.2
16.2
16.2
16.2

12.9
12.9
12.9
12.9
12.9
13.9
12.9
12.9
12.9
12.9
12.9
12.9

12.9
12.9
12.9
16.2
16.2
16.2
16.2
16.2
16.2

12.9
12.9
12.9
12.9
12.9
12.9
12.9
12.9
12.9

1
2
2
2
2
3
3
4
4
4
4
4
5
6
6
6
6
6
6
6
6

FLA (Ea.)
Frame
1

2.1
2.6
2.6
2.6
2.6
2.1
2.1
2.6
2.6
2.6
2.6
2.6
2.1
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6

2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6

2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6

MCA

MOCP

RFA

Frame

Frame

Frame

16.7
23.2
24.0
31.6
33.9
16.7
16.7
23.2
24.0
31.6
31.6
33.9
16.7
23.2
23.2
23.2
24.0
35.8
35.8
35.8
35.8

24.0
31.6
31.6
31.6
31.6
33.9
33.9
23.2
23.2
24.0
35.8
35.8
35.8
35.8
35.8
35.8

31.6
31.6
31.6
35.8
35.8
35.8
35.8
35.8
35.8

25
35
40
40
45
25
25
35
40
40
40
45
25
35
35
35
40
50
50
50
50

40
40
40
40
40
45
45
35
35
40
50
50
50
50
50
50

40
40
40
50
50
50
50
50
50

25
30
30
40
45
25
25
30
30
40
50
50
25
30
30
30
30
50
50
50
50

30
40
40
40
40
50
50
30
30
30
50
50
50
50
50
50

40
40
40
50
50
50
50
50
50

Maximum Overcurrent Protection (MOCP) is calculated as follows: (Largest motor FLA x 2.25) + (Sum of
other motor FLA) rounded down to the nearest standard fuse size.
RFA = Recommended Fuse Amps.

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

ELECTRICAL DATA
ARUB Series Heat Recovery Outdoor Units

Table 25: 208-230V, 60Hz, 3-Phase Heat Recovery Units.

Condenser Fan
Motor(s)
Amps

Compressor (Comp.)
Motor Amps
Nom.
Tons

ARUB072BTE4
ARUB096BTE4
ARUB121BTE4
ARUB144BTE4
ARUB168BTE4
ARUB192BTE4
ARUB216BTE4
ARUB240BTE4
ARUB264BTE4
ARUB288BTE4
ARUB313BTE4
ARUB337BTE4
ARUB312BTE4
ARUB336BTE4
ARUB360BTE4
ARUB384BTE4
ARUB408BTE4
ARUB432BTE4
ARUB456BTE4
ARUB480BTE4
ARUB504BTE4

Comp.
Qty.

1
1
1
2
2
2
3
3
3
4
4
4
4
4
4
5
5
6
6
6
6

Motor RLA (Ea.)


Fan
Frame
Qty.
1
2
3
Comp. Comp. Comp. Comp. Comp. Comp.
A
B
A
B
A
B
17.0
27.3
27.4
19.0
20.7
17.0
17.0
27.3
27.4
19.0
20.7
20.7
17.0
27.3
27.3
27.3
27.4
27.2
27.2
27.2
27.2

19.0
20.7
19.0
20.7
20.7
17.0
17.0
17.0
17.0

27.4
19.0
19.0
19.0
19.0
19.0
20.7
27.3
27.3
27.4
27.2
27.2
27.2
27.2
27.2
27.2

For component model nos. see the specification tables on p. 20-24.


Voltage tolerance is 10%.
Maximum allowable voltage unbalance is 2%.
MCA = Minimum Circuit Ampacity.

19.0
19.0
19.0
19.0
19.0
20.7
17.0
17.0
17.0
17.0
17.0
17.0

19.0
19.0
19.0
27.2
27.2
27.2
27.2
27.2
27.2

19.0
19.0
19.0
17.0
17.0
17.0
17.0
17.0
17.0

1
2
2
2
2
3
3
4
4
4
4
4
5
6
6
6
6
6
6
6
6

FLA (Ea.)
Frame
1

4.0
6.0
6.0
6.0
6.0
4.0
4.0
6.0
6.0
6.0
6.0
6.0
4.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0

6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0

6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0

MOCP

RFA

Frame

Frame

Frame

25.3
40.1
40.3
48.8
52.5
25.3
25.3
40.1
40.3
48.8
48.8
52.5
25.3
40.1
40.1
40.1
40.3
57.0
57.0
57.0
57.0

40.3
48.8
48.8
48.8
48.8
52.5
52.5
40.1
40.1
40.3
57.0
57.0
57.0
57.0
57.0
57.0

48.8
48.8
48.8
57.0
57.0
57.0
57.0
57.0
57.0

40
60
60
60
70
40
40
60
60
60
60
70
40
60
60
60
60
80*
80*
80*
80*

60
60
60
60
60
70
70
60
60
60
80*
80*
80*
80*
80*
80*

60
60
60
80*
80*
80*
80*
80*
80*

35
50
50
60
70
35
35
50
50
60
60
70
35
50
50
50
50
80
80
80
80

50
60
60
60
60
70
70
50
50
50
80
80
80
80
80
80

60
60
60
80
80
80
80
80
80

Maximum Overcurrent Protection (MOCP) is calculated as follows: (Largest motor FLA x 2.25) + (Sum of
other motor FLA) rounded down to the nearest standard fuse size.
RFA = Recommended Fuse Amps.
*SCCR rating: 5kA RMS Symmetrical.

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

PRODUCT DATA

33

Product Data

6.0
8.0
10.0
12.0
14.0
16.0
18.0
20.0
22.0
24.0
26.0
28.0
26.0
28.0
30.0
32.0
34.0
36.0
38.0
40.0
42.0

Unit Model
Nos.

MCA

ELECTRICAL DATA
ARUB Series Heat Recovery Outdoor Units

Table 26: 460V, 60Hz, 3-Phase Heat Recovery Units.

Condenser Fan
Motor(s)
Amps

Compressor (Comp.)
Motor Amps

MULTI V IV Outdoor Unit Engineering Manual

Nom. Unit Model Nos.


Comp.
Tons
Qty.

6.0
8.0
10.0
12.0
14.0
16.0
18.0
20.0
22.0
24.0
26.0
28.0
26.0
28.0
30.0
32.0
34.0
36.0
38.0
40.0
42.0

ARUB072DTE4
ARUB096DTE4
ARUB121DTE4
ARUB144DTE4
ARUB168DTE4
ARUB192DTE4
ARUB216DTE4
ARUB240DTE4
ARUB264DTE4
ARUB288DTE4
ARUB313DTE4
ARUB337DTE4
ARUB312DTE4
ARUB336DTE4
ARUB360DTE4
ARUB384DTE4
ARUB408DTE4
ARUB432DTE4
ARUB456DTE4
ARUB480DTE4
ARUB504DTE4

1
1
1
2
2
2
3
3
3
4
4
4
4
4
4
5
5
6
6
6
6

Motor RLA (Ea.)

Fan
Frame
Qty.
1
2
3
Comp. Comp. Comp. Comp. Comp. Comp.
A
B
A
B
A
B
11.7
16.5
17.1
12.9
13.9
11.7
11.7
16.5
17.1
12.9
13.9
13.9
11.7
16.5
16.5
16.5
17.1
16.2
16.2
16.2
16.2

12.9
13.9
12.9
13.9
13.9
12.9
12.9
12.9
12.9

For component model nos. see the specification tables on p. 25-29.


Voltage tolerance is 414-528V.
Maximum allowable voltage unbalance is 2%.
MCA = Minimum Circuit Ampacity.

34

PRODUCT DATA

17.1
12.9
12.9
12.9
12.9
12.9
13.9
16.5
16.5
17.1
16.2
16.2
16.2
16.2
16.2
16.2

12.9
12.9
12.9
12.9
12.9
13.9
12.9
12.9
12.9
12.9
12.9
12.9

12.9
12.9
12.9
16.2
16.2
16.2
16.2
16.2
16.2

12.9
12.9
12.9
12.9
12.9
12.9
12.9
12.9
12.9

1
2
2
2
2
3
3
4
4
4
4
4
5
6
6
6
6
6
6
6
6

FLA (Ea.)
Frame
1

2.1
2.6
2.6
2.6
2.6
2.1
2.1
2.6
2.6
2.6
2.6
2.6
2.1
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6

2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6

2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6

MCA

MOCP

RFA

Frame

Frame

Frame

16.7
23.2
24.0
31.6
33.9
16.7
16.7
23.2
24.0
31.6
31.6
33.9
16.7
23.2
23.2
23.2
24.0
35.8
35.8
35.8
35.8

24.0
31.6
31.6
31.6
31.6
33.9
33.9
23.2
23.2
24.0
35.8
35.8
35.8
35.8
35.8
35.8

31.6
31.6
31.6
35.8
35.8
35.8
35.8
35.8
35.8

25
35
40
40
45
25
25
35
40
40
40
45
25
35
35
35
40
50
50
50
50

40
40
40
40
40
45
45
35
35
40
50
50
50
50
50
50

40
40
40
50
50
50
50
50
50

25
30
30
40
45
25
25
30
30
40
50
50
25
30
30
30
30
50
50
50
50

30
40
40
40
40
50
50
30
30
30
50
50
50
50
50
50

40
40
40
50
50
50
50
50
50

Maximum Overcurrent Protection (MOCP) is calculated as follows: (Largest motor FLA x 2.25) + (Sum of
other motor FLA) rounded down to the nearest standard fuse size.
RFA = Recommended Fuse Amps.

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

OUTDOOR UNIT DIMENSIONS


ARUN072BTE4/ ARUN072DTE4, ARUB072BTE4 / ARUB072DTE4

Airflow

TOP
Top View

Y
Airflow

1"Diameter Wiring
knockout

L2

L6

L1

Piping
g Entry
knockout
k
2-1/2"Diameter
Wiring knockout

Front View
M4

Side View
1/2" Diameter Hole

29-15/16"

66-1/8"

L1

7-1/4"

L2

2-15/16"

L3

3-1/8"

L4

5-1/2"

L5

5-3/8"

L6

22-7/16"

L7

2-9/16"

L8

2-9/16"

L9

24-3/16"

L10

2-9/16"

L11

3-5/16"

M1

29-1/16"

M2

7/16"

M3

2-5/8"

M4

31-3/16"

Center of Gravity
X

17-5/8"

13-1/2"

29-5/8"

Note - All dimensions have a


tolerance of 0.25 in.

M1

M2

X
M3

L9

L5

L4

L11

2-1/2"Diameter
twist cap

36-1/4"

Product Data

Access
Panel

= Center of Gravity
Bottom Mounting Holes

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

PRODUCT DATA

35

OUTDOOR UNIT DIMENSIONS


ARUN/ARUB096BTE4/DTE4, ARUN/ARUB121BTE4/DTE4, ARUN/ARUB144BTE4/DTE4,
ARUN/ARUB145BTE4/DTE4, ARUN/ARUB168BTE4/DTE4, ARUN/ARUB169BTE4/DTE4

MULTI V IV Outdoor Unit Engineering Manual

Airflow

Top View

Airflow

L1 L2

1"Diameter wiring
knockout

L9

2-1/2"Diameter
wiring knockout

L4

L5

L6
X

M3

Front View
M4

M1

M2

1/2" Diameter
hole

L7

Side View

L8

48-13/16"

29-15/16"

66-1/8"

L1

7-1/4"

L2

2-15/16"

L3

3-1/8"

L4

5-1/2"

L5

5-3/8"

L6

2-9/16

L7

24-3/16"

L8

2-9/16"

L9

3-5/16"

M1

29-1/16"

M2

7/16"

M3

2-5/8"

M4

43-3/8"

Center of Gravity
X

17-5/8"

13-1/2"

29-5/8"

Note - All dimensions have a


tolerance of 0.25 in.
Bottom Mounting Holes

= Center of Gravity

ARUN145BTE4/ARUN145DTE4, ARUB145BTE4/ARUB145DTE4, ARUN169BTE4/ARUN169DTE4, ARUB169BTE4/ARUB169DTE4, frames


are ONLY for use in large capacity triple frame combinations. They cannot be used as stand alone models or in a dual frame combination. These
frames ARE NOT interchangeable with ARUN144BTE4/ARUN144DTE4, ARUB144BTE4/ARUB144DTE4, ARUN169BTE4/ARUN169DTE4,
ARUB169BTE4/ARUB169DTE4 single frame models.
36

PRODUCT DATA

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

OUTDOOR UNIT DIMENSIONS


ARUN192BTE4 / 192DTE4, ARUN216BTE4 / 216DTE4,
ARUB192BTE4 / 192DTE4, ARUB216BTE4 / 216DTE4

W1
Airflow

48-13/16"

29-15/16"

Airflow

66-1/8"

L1

7-1/4"

L2

2-15/16"

L3

3-1/8"

L4

5-1/2"

L5

5-3/8"

L6

2-9/16

L7

24-3/16"

L8

2-9/16"

L9

3-5/16"

M1

29-1/16"

M2

7/16"

M3

2-5/8"

M4

31-3/16"

M5

2-5/8"

M6

43-3/8"

Y2

D
H

L3

Min. 2-3/4"

Z1

Piping Entry
knockout

Center of Gravity

1"Diameter wiring
knockout

L1

2-1/2"Diameter
wiring knockout

M2

M4

M5

Side View
M6

1/2" Diameter
hole

M1

M3

X2

Front View

Product Data

W2

Airflow

L5
X1

36-1/4"

W2

Airflow

L4

W1

X1

17-5/8"

X2

24-3/4"

Y1

13-1/2"

Y2

21-9/16"

Z1

29-5/8"

Z2

29-7/8"

Note - All dimensions have a


tolerance of 0.25 in.
= Center of Gravity
Bottom Mounting Holes

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

PRODUCT DATA

37

OUTDOOR UNIT DIMENSIONS


ARUN/ARUB240-264-288-313-337BTE4/DTE4

Airflow

Airflow

TOP
Top View
Airflow

1"Diameter wiring

L1 L2

L9

2-1/2"Diameter
wiring knockout

L4

L6

Front View
M4

M3

M2

M3
3

L5

M4

1/2" Diameter
hole

L7

L8

Side View

M1

MULTI V IV Outdoor Unit Engineering Manual

Min. 2-3/4"

48-13/16"

29-15/16"

66-1/8"

L1

7-1/4"

L2

2-15/16"

L3

3-1/8"

L4

5-1/2"

L5

5-3/8"

L6

2-9/16

L7

24-3/16"

L8

2-9/16"

L9

3-5/16"

M1

29-1/16"

M2

7/16"

M3

2-5/8"

M4

43-3/8"

Center of Gravity
X

24-3/4"

21-9/16"

29-7/8"

Note - All dimensions have a


tolerance of 0.25 in.
= Center of Gravity
Bottom Mounting Holes

38

PRODUCT DATA

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

Airflow

L3

Y1

Z1

L1

M2

M1

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

M3

L4

X1

L5

M4

Piping Entry
knockout

M5

Min. 2-3/4"

X2

Bottom Mounting Holes

M6

Front View

Top View

X2
M5

M6

Airflow

Airflow

Min. 2-3/4"

W2

W2

TOP

Airflow

1/2" Diameter
hole

2-1/2"Diameter
wiring knockout

1"Diameter wiring
knockout

Y2

Product Data

W1

L6

Side View

L7

Airflow

L8

48-13/16"
29-15/16"
66-1/8"
7-1/4"
2-15/16"
3-1/8"
5-1/2"
5-3/8"
2-9/16
24-3/16"
2-9/16"
3-5/16"
29-1/16"
7/16"
2-5/8"
31-3/16"
2-5/8"
43-3/8"

W2
D
H
L1
L2
L3
L4
L5
L6
L7
L8
L9
M1
M2
M3
M4
M5
M6

29-5/8"
29-7/8"

Z1
Z2

= Center of Gravity

Note - All dimensions have a


tolerance of 0.25 in.

13-1/2"
21-9/16"

Y1

24-3/4"

X2
Y2

17-5/8"

X1

Center of Gravity

36-1/4"

W1

OUTDOOR UNIT DIMENSIONS

ARUN312BTE4 / 312DTE4, ARUB312BTE4 / 312DTE4

PRODUCT DATA

39

PRODUCT DATA

L4

M3

L1 L2

M2

40

M1

L5

M4

Airflow

M3

Min. 2-3/4"

Bottom Mounting Holes

M4

Front View

Top View

Airflow

M3

Min. 2-3/4"

M4

A
Airflow

1/2" Diameter
hole

2-1/2"Diameter
wiring knockout

1"Diameter wiring
knockout

TOP

L6

Side View

L7

L8

MULTI V IV Outdoor Unit Engineering Manual

66-1/8"

3-1/8"
5-1/2"
5-3/8"
2-9/16
24-3/16"
2-9/16"
3-5/16"
29-1/16"
7/16"
2-5/8"
43-3/8"

L3
L4
L5
L6
L7
L8
L9
M1
M2
M3
M4

21-9/16"
29-7/8"

Y
Z

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

= Center of Gravity

Note - All dimensions have a


tolerance of 0.25 in.

24-3/4"
X

Center of Gravity

2-15/16"

L2

7-1/4"

29-15/16"

L1

48-13/16"

OUTDOOR UNIT DIMENSIONS


ARUN/ARUB336-360-384-408-432-456-480-504BTE4/DTE4

L9

HEAT RECOVERY UNIT DIMENSIONS


PRHR022A

Product Data

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

PRODUCT DATA

41

HEAT RECOVERY UNIT DIMENSIONS

MULTI V IV Outdoor Unit Engineering Manual

PRHR032A

42

PRODUCT DATA

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

HEAT RECOVERY UNIT DIMENSIONS


PRHR042A

Product Data

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

PRODUCT DATA

43

WIRING DIAGRAMS
ARUN072BTE4 208-230V Heat Pump

MAIN PCB COMMUNICATION


TERMINAL

MULTI V IV Outdoor Unit Engineering Manual

LOW PRESSURE SENSOR


HIGH PRESSURE SENSOR

OUTDOOR AIR THERMISTOR

MAIN ELECTRONIC
EXPANSION VALVE 1
SUB-COOLING ELECTRONIC
EXPANSION VALVE
MAIN ELECTRONIC
EXPANSION VALVE 2
OIL BALANCE ELECTRONIC
EXPANSION VALVE
VAPOR INJECTION ELECTRONIC
EXPANSION VALVE 1
VAPOR INJECTION ELECTRONIC
EXPANSION VALVE 2

TERMINAL BLOCK

44

PRODUCT DATA

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

WIRING DIAGRAMS
ARUN096BTE4, ARUN121BTE4, ARUN144BTE4, ARUN168BTE4 208-230V
Heat Pump

MAIN PCB COMMUNICATION


TERMINAL

LOW PRESSURE SENSOR


HIGH PRESSURE SENSOR

OUTDOOR AIR THERMISTOR

SUCTION PIPE THERMISTOR

Product Data

MAIN ELECTRONIC EXPANSION


VALVE 1
SUB-COOLING ELECTRONIC
EXPANSION VALVE
MAIN ELECTRONIC EXPANSION
VALVE 2
OIL BALANCE ELECTRONIC
EXPANSION VALVE
VAPOR INJECTION ELECTRONIC
EXPANSION VALVE 1
VAPOR INJECTION ELECTRONIC
EXPANSION VALVE 2

TERMINAL BLOCK

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

PRODUCT DATA

45

WIRING DIAGRAMS

MULTI V IV Outdoor Unit Engineering Manual

ARUN145BTE4, ARUN169BTE4 208-230V Heat Pump

ARUN145BTE4/ARUN145DTE4, ARUN169BTE4/ARUN169DTE4 frames are ONLY for use in large capacity triple frame combinations.
They cannot be used as stand alone models or in a dual frame combination. These frames ARE NOT interchangeable with ARUN144BTE4/
ARUN144DTE4, ARUN168BTE4/ARUN168DTE4 single frame models.
46

PRODUCT DATA

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

WIRING DIAGRAMS
ARUN072DTE4 460V Heat Pump

MAIN PCB COMMUNICATION


TERMINAL

LOW PRESSURE SENSOR


HIGH PRESSURE SENSOR

OUTDOOR AIR THERMISTOR

Product Data

MAIN ELECTRONIC EXPANSION


VALVE 1
SUB-COOLING ELECTRONIC
EXPANSION VALVE
MAIN ELECTRONIC EXPANSION
VALVE 2
OIL BALANCE ELECTRONIC
EXPANSION VALVE
VAPOR INJECTION ELECTRONIC
EXPANSION VALVE 1
VAPOR INJECTION ELECTRONIC
EXPANSION VALVE 2

TERMINAL BLOCK

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

PRODUCT DATA

47

WIRING DIAGRAMS
ARUN096DTE4, ARUN121DTE4 460V Heat Pump

MULTI V IV Outdoor Unit Engineering Manual

MAIN PCB COMMUNICATION


TERMINAL

LOW PRESSURE SENSOR


HIGH PRESSURE SENSOR

OUTDOOR AIR THERMISTOR

MAIN ELECTRONIC
EXPANSION VALVE 1
SUB-COOLING ELECTRONIC
EXPANSION VALVE
MAIN ELECTRONIC EXPANSION
VALVE 2
OIL BALANCE ELECTRONIC
EXPANSION VALVE
VAPOR INJECTION ELECTRONIC
EXPANSION VALVE 1
VAPOR INJECTION ELECTRONIC
EXPANSION VALVE 2
MAIN PCB COMMUNICATION
TERMINAL
TERMINAL BLOCK

48

PRODUCT DATA

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

WIRING DIAGRAMS
ARUN144DTE4, ARUN168DTE4 460V Heat Pump

MAIN PCB COMMUNICATION


TERMINAL

LOW PRESSURE SENSOR


HIGH PRESSURE SENSOR

OUTDOOR AIR THERMISTOR

SUCTION PIPE THERMISTOR

Product Data

MAIN ELECTRONIC
EXPANSION VALVE 1
SUB-COOLING ELECTRONIC
EXPANSION VALVE
MAIN ELECTRONIC
EXPANSION VALVE 2
OIL BALANCE ELECTRONIC
EXPANSION VALVE
VAPOR INJECTION ELECTRONIC
EXPANSION VALVE 1
VAPOR INJECTION ELECTRONIC
EXPANSION VALVE 2

TERMINAL BLOCK

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

PRODUCT DATA

49

WIRING DIAGRAMS

MULTI V IV Outdoor Unit Engineering Manual

ARUN145DTE4, ARUN169DTE4 460V Heat Pump

ARUN145BTE4/ARUN145DTE4, ARUN169BTE4/ARUN169DTE4 frames are ONLY for use in large capacity triple frame combinations.
They cannot be used as stand alone models or in a dual frame combination. These frames ARE NOT interchangeable with ARUN144BTE4/
ARUN144DTE4, ARUN168BTE4/ARUN168DTE4 single frame models.
50

PRODUCT DATA

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

WIRING DIAGRAMS
ARUB072BTE4 208-230V Heat Recovery

MAIN PCB COMMUNICATION


TERMINAL

LOW PRESSURE SENSOR


HIGH PRESSURE SENSOR

OUTDOOR AIR THERMISTOR

Product Data

MAIN ELECTRONIC
EXPANSION VALVE 1
SUB-COOLING ELECTRONIC
EXPANSION VALVE 1
SUB-COOLING ELECTRONIC
EXPANSION VALVE 2
OIL BALANCE ELECTRONIC
EXPANSION VALVE
VAPOR INJECTION ELECTRONIC
EXPANSION VALVE 1
VAPOR INJECTION ELECTRONIC
EXPANSION VALVE 2

TERMINAL BLOCK

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

PRODUCT DATA

51

WIRING DIAGRAMS
ARUB096BTE4, ARUB121BTE4 208-230V Heat Recovery

MULTI V IV Outdoor Unit Engineering Manual

MAIN PCB COMMUNICATION


TERMINAL

LOW PRESSURE SENSOR


HIGH PRESSURE SENSOR
LIQUID PIPE THERMISTOR

OUTDOOR AIR THERMISTOR

MAIN ELECTRONIC
EXPANSION VALVE 1
SUB-COOLING ELECTRONIC
EXPANSION VALVE
MAIN ELECTRONIC EXPANSION
VALVE 2
OIL BALANCE ELECTRONIC
EXPANSION VALVE
VAPOR INJECTION ELECTRONIC
EXPANSION VALVE 1
VAPOR INJECTION ELECTRONIC
EXPANSION VALVE 2

TERMINAL BLOCK

52

PRODUCT DATA

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

WIRING DIAGRAMS
ARUB144BTE4, ARUB168BTE4 208-230V Heat Recovery

MAIN PCB COMMUNICATION


TERMINAL

LOW PRESSURE SENSOR


HIGH PRESSURE SENSOR

OUTDOOR AIR THERMISTOR

Product Data

MAIN ELECTRONIC EXPANSION


VALVE 1
SUB-COOLING ELECTRONIC
EXPANSION VALVE
MAIN ELECTRONIC EXPANSION
VALVE 2
OIL BALANCE ELECTRONIC
EXPANSION VALVE
VAPOR INJECTION ELECTRONIC
EXPANSION VALVE 1
VAPOR INJECTION ELECTRONIC
EXPANSION VALVE 2

TERMINAL BLOCK

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

PRODUCT DATA

53

WIRING DIAGRAMS

MULTI V IV Outdoor Unit Engineering Manual

ARUB145BTE4, ARUB169BTE4 208-230V Heat Recovery

ARUB145BTE4/ARUB145DTE4, ARUB169BTE4/ARUB169DTE4 frames are ONLY for use in large capacity triple frame combinations. They
cannot be used as stand alone models or in a dual frame combination. These frames ARE NOT interchangeable with ARUB144BTE4/ARUB144DTE4, ARUB168BTE4/ARUB168DTE4 single frame models.
54

PRODUCT DATA

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

WIRING DIAGRAMS
ARUB072DTE4 460V Heat Recovery

MAIN PCB COMMUNICATION


TERMINAL

LOW PRESSURE SENSOR


HIGH PRESSURE SENSOR

OUTDOOR AIR THERMISTOR

Product Data

MAIN ELECTRONIC EXPANSION


VALVE 1
SUB-COOLING ELECTRONIC
EXPANSION VALVE
MAIN ELECTRONIC EXPANSION
VALVE 2
OIL BALANCE ELECTRONIC
EXPANSION VALVE
VAPOR INJECTION ELECTRONIC
EXPANSION VALVE 1
VAPOR INJECTION ELECTRONIC
EXPANSION VALVE 2

TERMINAL BLOCK

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

PRODUCT DATA

55

WIRING DIAGRAMS
ARUB096DTE4, ARUB121DTE4 460V Heat Recovery

MULTI V IV Outdoor Unit Engineering Manual

MAIN PCB COMMUNICATION


TERMINAL

LOW PRESSURE SENSOR


HIGH PRESSURE SENSOR

OUTDOOR AIR THERMISTOR

MAIN ELECTRONIC EXPANSION


VALVE 1
SUB-COOLING ELECTRONIC
EXPANSION VALVE
MAIN ELECTRONIC EXPANSION
VALVE 2
OIL BALANCE ELECTRONIC
EXPANSION VALVE
VAPOR INJECTION ELECTRONIC
EXPANSION VALVE 1
VAPOR INJECTION ELECTRONIC
EXPANSION VALVE 2

TERMINAL BLOCK

56

PRODUCT DATA

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

WIRING DIAGRAMS
ARUB144DTE4, ARUB168DTE4 460V Heat Recovery

MAIN PCB COMMUNICATION


TERMINAL

LOW PRESSURE SENSOR


HIGH PRESSURE SENSOR

OUTDOOR AIR THERMISTOR

Product Data

MAIN ELECTRONIC EXPANSION


VALVE 1
SUB-COOLING ELECTRONIC
EXPANSION VALVE
MAIN ELECTRONIC EXPANSION
VALVE 2
OIL BALANCE ELECTRONIC
EXPANSION VALVE
VAPOR INJECTION ELECTRONIC
EXPANSION VALVE 1
VAPOR INJECTION ELECTRONIC
EXPANSION VALVE 2

TERMINAL BLOCK

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

PRODUCT DATA

57

WIRING DIAGRAMS

MULTI V IV Outdoor Unit Engineering Manual

ARUB145DTE4, ARUB169DTE4 460V Heat Recovery

ARUB145BTE4/ARUB145DTE4, ARUB169BTE4/ARUB169DTE4 frames are ONLY for use in large capacity triple frame combinations. They
cannot be used as stand alone models or in a dual frame combination. These frames ARE NOT interchangeable with ARUB144BTE4/ARUB144DTE4, ARUB168BTE4/ARUB168DTE4 single frame models.
58

PRODUCT DATA

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

WIRING DIAGRAMS
PRHR022A, PRHR032A, PRHR042A Heat Recovery Units

Product Data

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

PRODUCT DATA

59

REFRIGERANT FLOW DIAGRAMS


Cooling Mode

ARUN072BTE4 / 072DTE4, ARUN096BTE4 / 096DTE4,


ARUN121BTE4 / 121DTE4 Heat Pump
Indoor Heat Exchanger

Indoor Heat Exchanger


Electronic
Expansion Valve

Electronic
Expansion Valve

MULTI V IV Outdoor Unit Engineering Manual

Fan

Outdoor
Temperature
Sensor

Fan

Fan

High Temperature High Pressure Gas


High Temperature High Pressure Liquid
Low Temperature Low Pressure Gas

Charging Port

High Pressure
Sensor

Pressure
Switch

Gas Pipe

Liquid Pipe

4-Way Valve

Outdoor Unit
HEX Temperature
Sensor
Lower HEX
Hot Gas Valve

Liquid Pipe
Temperature
Sensor

SC Suction

Suction
Temperature
Sensor

S
S

Upper HEX
Hot Gas Valve
S

Upper
Outdoor
EEV

Inverter
Comp1

Receiver

Oil Return
S

Sub-cooling Circuit
Outlet Temperature
Sensor

Comp
Discharge
Temperature
Sensor

Lower
Outdoor
EEV

Oil

Separator

Low
Pressure
Sensor

Accum
Receiver
Outlet

Comp
Vapor
Injection

Sub-cooling HEX

Sub-cooling Circuit
Inlet Temperature
Sensor

Receiver
Inlet

Sub-cooling

*8 ton and 10 ton units have 2 fans

60

PRODUCT DATA

Press ure Sensor

Temperature Sensor

Check Valve

Press ure Switch

SVC Valve

EEV

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

Soleno id Valve

Remarks

Strainer

REFRIGERANT FLOW DIAGRAMS


ARUN072BTE4 / 072DTE4, ARUN096BTE4 / 096DTE4,

Heating Mode

ARUN121BTE4 / 121DTE4 Heat Pump


Indoor Heat Exchanger

Indoor Heat Exchanger

Electronic
Expansion Valve

Electronic
Expansion Valve

Fan

Fan

Outdoor
Temperature
Sensor

Fan

High Temperature High Pressure Gas


High Temperature High Pressure Liquid
Low Temperature Low Pressure Gas

Charging Port

Pressure
Switch

Product Data

High Pressure
Sensor

Gas Pipe

Liquid Pipe

4-Way Valve

Outdoor Unit
HEX Temperature
Sensor
Lower HEX
Hot Gas Valve

Liquid Pipe
Temperature
Sensor

SC suction

Suction
Temperature
Sensor

S
S

Upper HEX
Hot Gas Valve
S

Lower
Outdoor
EEV

Inverter
Comp1

Receiver

Oil Return
S

Sub-cooling Circuit
Outlet Temperature
Sensor

Comp
Discharge
Temperature
Sensor

Upper
Outdoor
EEV

Separator

Low
Pressure
Sensor

Accum
Receiver
Outlet

Comp
Vapor
Injection

Oil

Sub-cooling HEX

Sub-cooling Circuit
Inlet Temperature
Sensor

Receiver
Inlet

Sub-cooling

*8 ton and 10 ton units have 2 fans

Press ure Sensor

Temperature Sensor

Check Valve

Press ure Switch

SVC Valve

EEV

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

Soleno id Valve

Remarks

Strainer

PRODUCT DATA

61

REFRIGERANT FLOW DIAGRAMS


ARUN072BTE4 / 072DTE4, ARUN096BTE4 /

Oil Return and Defrost Operation

096DTE4, ARUN121BTE4 / 121DTE4 Heat Pump


Indoor HEX

EEV

Fan
Indoor Unit
HR Unit
s

Indoor HEX

EEV
s

Fan

MULTI V IV Outdoor Unit Engineering Manual

Indoor Unit
s

Indoor HEX

EEV
s

s
s

Fan

Indoor Unit

Indoor HEX

EEV

Fan
Indoor Unit

High Temperature High Pressure Gas


High Temperature High Pressure Liquid
Low Temperature Low Pressure Gas

*
Outdoor
Temperature
Sensor

Fan

Fan

Charging Port

High Pressure
Sensor

Pressure
Switch

High Pressure Gas Pipe


Low Pressure Gas Pipe
Liquid Pipe

4-Way Valve

Outdoor Unit
HEX Temperature
Sensor
Lower HEX
Hot Gas Valve

SC Suction

Suction
Temperature
Sensor

S
S

Upper HEX
Hot Gas Valve

Low
Pressure
Sensor

Accum
S

Inverter
Comp1

Receiver

Oil Return
S

Lower
Outdoor
EEV
Sub-cooling Circuit
Outlet Temperature
Sensor

Receiver
Outlet

Comp
Discharge
Temperature
Sensor

Upper
Outdoor
EEV

Oil

Separator

Liquid Pipe
Temperature
Sensor

Comp
Vapor
Injection

Sub-cooling HEX

Sub-cooling Circuit
Inlet Temperature
Sensor

Receiver
Inlet

Sub-cooling

*8 ton and 10 ton units have 2 fans

62

PRODUCT DATA

Press ure Sensor

Temperature Sensor

Check Valve

Press ure Switch

SVC Valve

EEV

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

Soleno id Valve

Remarks

Strainer

REFRIGERANT FLOW DIAGRAMS


ARUN072BTE4 / 072DTE4, ARUN096BTE4 /

Upper HEX Defrost Operation

Indoor HEX

096DTE4, ARUN121BTE4 / 121DTE4 Heat Pump

EEV

Fan
Indoor Unit
HR Unit
s

Indoor HEX

EEV
s

Fan

Indoor Unit
s

s
s

Indoor HEX

EEV
s

s
s

Fan

Indoor Unit

Indoor HEX

Product Data

EEV

Fan
Indoor Unit

*
Outdoor
Temperature
Sensor

Fan

Fan

High Temperature High Pressure Gas


High Temperature High Pressure Liquid
Low Temperature Low Pressure Gas

Charging Port

High Pressure
Sensor

Pressure
Switch

High Pressure Gas Pipe


Low Pressure Gas Pipe

Active Path
Outdoor unit
HEX Temperature
Sensor

Liquid Pipe
4-Way Valve

Lower HEX
Hot Gas Valve

SC Suction

Suction
Temperature
Sensor

S
S

Upper HEX
Hot Gas Valve
S

Inverter
Comp1

Receiver

Oil Return
S

Lower
Outdoor
EEV
Sub-cooling Circuit
Outlet Temperature
Sensor

Receiver
Outlet

Comp
Discharge
Temperature
Sensor

Upper
Outdoor
EEV

Oil

Separator

Low
Pressure
Sensor

Accum

Liquid Pipe
Temperature
Sensor

Comp
Vapor
Injection

Sub-Cooling HEX

Sub-cooling Circuit
Inlet Temperature
Sensor

Receiver
Inlet

Sub-cooling

*8 ton and 10 ton units have 2 fans


**Active path: The refrigerant circuit(s) of an outdoor unit coil that provide(s) continuous heating capacity during split coil defrost operation.

Press ure Sensor

Temperature Sensor

Check Valve

Press ure Switch

SVC Valve

EEV

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

Soleno id Valve

Remarks

Strainer

PRODUCT DATA

63

REFRIGERANT FLOW DIAGRAMS


Low HEX Defrost Operation

ARUN072BTE4 / 072DTE4, ARUN096BTE4 /


096DTE4, ARUN121BTE4 / 121DTE4 Heat Pump
Indoor HEX

EEV

Fan
Indoor Unit
HR Unit
s

Indoor HEX

EEV
s

Fan

MULTI V IV Outdoor Unit Engineering Manual

Indoor Unit
s

Indoor HEX

EEV
s

s
s

Fan

Indoor Unit

Indoor HEX

EEV

Fan
Indoor Unit

High Temperature High Pressure Gas


High Temperature High Pressure Liquid
Low Temperature Low Pressure Gas

*
Outdoor
Temperature
Sensor

Fan

Fan

Charging Port

Active Path

High Pressure
Sensor

Pressure
Switch

High Pressure Gas Pipe


Low Pressure Gas Pipe

Liquid Pipe
4-Way Valve

Outdoor Unit
HEX Temperature
Sensor
Lower HEX
Hot Gas Valve

SC Suction

Suction
Temperature
Sensor

S
S

Upper HEX
Hot Gas Valve

Low
Pressure
Sensor

Accum
S

Inverter
Comp1

Receiver

Oil Return
S

Lower
Outdoor
EEV
Sub-cooling Circuit
Outlet Temperature
Sensor

Receiver
Outlet

Comp
Discharge
Temperature
Sensor

Upper
Outdoor
EEV

Oil

Separator

Liquid Pipe
Temperature
Sensor

Comp
Vapor
Injection

Sub-cooling HEX

Sub-cooling Circuit
Inlet Temperature
Sensor

Receiver
Inlet

Sub-cooling

*8 ton and 10 ton units have 2 fans


**Active path: The refrigerant circuit(s) of an outdoor unit coil that provide(s) continuous heating capacity during split coil defrost operation.

64

PRODUCT DATA

Press ure Sensor

Temperature Sensor

Check Valve

Press ure Switch

SVC Valve

EEV

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

Soleno id Valve

Remarks

Strainer

REFRIGERANT FLOW DIAGRAMS


Cooling Mode

ARUN144BTE4 / 144DTE4, ARUN145BTE4 / 145DTE4,


ARUN168BTE4 / 168DTE4, ARUN169BTE4 / 169DTE4 Heat Pump
Indoor Heat Exchanger

Indoor Heat Exchanger

Electronic
Expansion Valve

Electronic
Expansion Valve

Fan

Fan

Outdoor
Temperature
Sensor

Fan

High Temperature High Pressure Gas


High Temperature High Pressure Liquid
Low Temperature Low Pressure Gas

Charging Port

High Pressure Pressure


Sensor
Switch

Product Data

Gas Pipe
Liquid Pipe

Lower HEX
Hot Gas Valve

SC Suction

Upper HEX
Hot Gas Valve

Upper
Outdoor
EEV

Liquid Pipe
Temperature
Sensor

4-Way Valve

Outdoor Unit
HEX Temperature
Sensor

Suction
Temperature
Sensor

Accum

Lower
Outdoor
EEV
Sub-cooling Circuit
Outlet Temperature
Sensor

Receiver
Outlet

Low
Pressure
Sensor

Oil
Separ
-ator

Comp1
Discharge
Temperature
Sensor
Oil
Balance

Receiver

Oil

Comp1 Separ
-ator
Vapor
Injection

Inverter
Comp1

Comp2
Discharge
Temperature
Sensor

Comp2
Vapor
Injection

Inverter
Comp2

Oil Return

Sub-cooling HEX

Sub-cooling Circuit
Inlet Temperature
Sensor

ARUN145BTE4/145DTE4,
ARUN169BTE4/169DTE4
frames are ONLY for use in
large capacity triple frame
combinations. They cannot be
used as stand alone models
or in a dual frame combination. These frames ARE
NOT interchangeable with
ARUN144BTE4/144DTE4,
ARUN168BTE4/168DTE4
single frame models.

Receiver
Inlet

Sub-cooling

*8 ton and 10 ton units have 2 fans

Press ure Sensor

Temperature Sensor

Check Valve

Press ure Switch

SVC Valve

EEV

Soleno id Valve

Remarks

Strainer

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

PRODUCT DATA

65

REFRIGERANT FLOW DIAGRAMS


Heating Mode

ARUN144BTE4 / 144DTE4, ARUN145BTE4 / 145DTE4,


ARUN168BTE4 / 168DTE4, ARUN169BTE4 / 169DTE4 Heat Pump
Indoor Heat Exchanger

Indoor Heat Exchanger

Electronic
Expansion Valve

Electronic
Expansion Valve

Fan

MULTI V IV Outdoor Unit Engineering Manual

Fan

Outdoor
Temperature
Sensor

Fan

High Temperature High Pressure Gas


High Temperature High Pressure Liquid
Low Temperature Low Pressure Gas

Charging Port

High Pressure
Sensor

Pressure
Switch

Gas Pipe
Liquid Pipe

Lower HEX
Hot Gas Valve

SC Suction

Upper HEX
Hot Gas Valve

Upper
Outdoor
EEV

Liquid Pipe
Temperature
Sensor

4-Way Valve

Outdoor Unit
HEX Temperature
Sensor

Suction
Temperature
Sensor
Low
Pressure
Sensor

Accum

Low
Outdoor
EEV
Sub-cooling Circuit
Outlet Temperature
Sensor

Receiver
Outlet`

Comp1
Discharge
Temperature
Sensor
Oil
Balance

Receiver

Oil

Comp1 Separ
-ator
Vapor
Injection

Inverter
Comp1

Comp2
Discharge
Temperature
Sensor

Comp2
Vapor
Injection

Inverter
Comp2

Oil Return

Sub-Cooling HEX

Sub-cooling Circuit
Inlet Temperature
Sensor

Oil
Separ
-ator

Receiver
Inlet

ARUN145BTE4/145DTE4,
ARUN169BTE4/169DTE4
frames are ONLY for use in
large capacity triple frame
combinations. They cannot be
used as stand alone models
or in a dual frame combination. These frames ARE
NOT interchangeable with
ARUN144BTE4/144DTE4,
ARUN168BTE4/168DTE4
single frame models.

Sub-cooling

*8 ton and 10 ton units have 2 fans

66

Press ure Sensor

Temperature Sensor

Check Valve

Press ure Switch

SVC Valve

EEV

PRODUCT DATA

Soleno id Valve

Remarks

Strainer

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

REFRIGERANT FLOW DIAGRAMS


ARUN144BTE4 / 144DTE4, ARUN145BTE4 / 145DTE4,

Oil Return and Defrost

ARUN168BTE4 /168DTE4, ARUN169BTE4 / 169DTE4 Heat Pump

Operation

Indoor Heat Exchanger

Indoor Heat Exchanger

Electronic
Expansion Valve

Electronic
Expansion Valve

Fan

Fan

Outdoor
Temperature
Sensor

Fan

High Temperature High Pressure Gas


High Temperature High Pressure Liquid
Low Temperature Low Pressure Gas

Charging Port

High Pressure Pressure


Sensor
Switch

Product Data

Gas Pipe
Liquid Pipe

Lower HEX
Hot Gas Valve

SC Suction

Upper HEX
Hot Gas Valve

Upper
Outdoor
EEV

Liquid Pipe
Temperature
Sensor

4-Way Valve

Outdoor unit
HEX Temperature
Sensor

Suction
Temperature
Sensor

Accum

Lower
Outdoor
EEV
Sub-cooling Circuit
Outlet Temperature
Sensor

Receiver
Outlet

Low
Pressure
Sensor

Oil
Separ
-ator

Comp1
Discharge
Temperature
Sensor
Oil
Balance

Receiver

Oil

Comp1 Separ
-ator
Vapor
Injection

Inverter
Comp1

Comp2
Discharge
Temperature
Sensor

Comp2
Vapor
Injection

ARUN145BTE4/145DTE4,
ARUN169BTE4/169DTE4
frames are ONLY for use in
large capacity triple frame
combinations. They cannot be
used as stand alone models
or in a dual frame combination. These frames ARE
NOT interchangeable with
ARUN144BTE4/144DTE4,
ARUN168BTE4/168DTE4
single frame models.

Inverter
Comp2

Oil Return

Sub-cooling HEX

Sub-cooling Circuit
Inlet Temperature
Sensor

Receiver
Inlet

Sub-cooling

*8 ton and 10 ton units have 2 fans

Press ure Sensor

Temperature Sensor

Check Valve

Press ure Switch

SVC Valve

EEV

Soleno id Valve

Remarks

Strainer

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

PRODUCT DATA

67

REFRIGERANT FLOW DIAGRAMS


ARUN144BTE4 / 144DTE4, ARUN145BTE4 / 145DTE4,

Upper HEX Defrost

ARUN168BTE4 / 168DTE4, ARUN169BTE4 / 169DTE4 Heat Pump


Indoor Heat Exchanger

Indoor Heat Exchanger

Electronic
Expansion Valve

Electronic
Expansion Valve

Fan

MULTI V IV Outdoor Unit Engineering Manual

Fan

Outdoor
Temperature
Sensor

Operation

Fan

High Temperature High Pressure Gas


High Temperature High Pressure Liquid
Low Temperature Low Pressure Gas

Charging Port

High Pressure Pressure


Sensor
Switch

Gas Pipe
Liquid Pipe

Active Path

Lower HEX
Hot Gas Valve

SC Suction

Upper HEX
Hot Gas Valve

Low
Outdoor
EEV

Liquid Pipe
Temperature
Sensor

4-Way Valve

Outdoor Unit
HEX Temperature
Sensor

Upper
Outdoor
EEV
Sub-cooling Circuit
Outlet Temperature
Sensor

Suction
Temperature
Sensor

Accum
Receiver
Outlet

Comp1
Discharge
Temperature
Sensor
Oil
Balance

Receiver

Oil

Comp1 Separ
-ator
Vapor
Injection

Inverter
Comp1

Comp2
Discharge
Temperature
Sensor

Comp2
Vapor
Injection

ARUN145BTE4/145DTE4,
ARUN169BTE4/169DTE4
frames are ONLY for use in
large capacity triple frame
combinations. They cannot be
used as stand alone models
or in a dual frame combination. These frames ARE
NOT interchangeable with
ARUN144BTE4/144DTE4,
ARUN168BTE4/168DTE4
single frame models.

Inverter
Comp2

Oil Return

Sub-cooling HEX

Sub-cooling Circuit
Inlet Temperature
Sensor

Low
Pressure
Sensor

Oil
Separ
-ator

Receiver
Inlet

Sub-cooling

*8 ton and 10 ton units have 2 fans


**Active path: The refrigerant circuit(s) of an outdoor unit coil that provide(s) continuous heating capacity during split coil defrost operation.

68

Press ure Sensor

Temperature Sensor

Check Valve

Press ure Switch

SVC Valve

EEV

PRODUCT DATA

Soleno id Valve

Remarks

Strainer

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

REFRIGERANT FLOW DIAGRAMS


Low HEX Defrost

ARUN144BTE4 / 144DTE4, ARUN145BTE4 / 145DTE4,

Operation

ARUN168BTE4 /168DTE4 , ARUN169BTE4 / 169DTE4 Heat Pump


Indoor Heat Exchanger

Indoor Heat Exchanger

Electronic
Expansion Valve

Electronic
Expansion Valve

Fan

Fan

Outdoor
Temperature
Sensor

Fan

High Temperature High Pressure Gas


High Temperature High Pressure Liquid
Low Temperature Low Pressure Gas

Charging Port

Product Data

High Pressure Pressure


Sensor
Switch

Active Path

Gas Pipe

Liquid Pipe

Lower HEX
Hot Gas Valve

SC Suction

Upper HEX
Hot Gas Valve

Low
Outdoor
EEV

Liquid Pipe
Temperature
Sensor

4-Way Valve

Outdoor Unit
HEX Temperature
Sensor

Suction
Temperature
Sensor

Accum

Upper
Outdoor
EEV
Sub-cooling Circuit
Outlet Temperature
Sensor

Low
Pressure
Sensor

Oil

Comp1 Separ
-ator
Vapor
Injection

Comp1
Discharge
Temperature
Sensor
Oil
Balance

Receiver

Receiver
Outlet

Oil
Separ
-ator

Inverter
Comp1

Comp2
Discharge
Temperature
Sensor

ARUN145BTE4/145DTE4,
ARUN169BTE4/169DTE4
frames are ONLY for use in
large capacity triple frame
combinations. They cannot be
used as stand alone models
or in a dual frame combination. These frames ARE
NOT interchangeable with
ARUN144BTE4/144DTE4,
ARUN168BTE4/168DTE4
single frame models.

Comp2
Vapor
Injection

Inverter
Comp2

Oil Return

Sub-cooling HEX

Sub-cooling Circuit
Inlet Temperature
Sensor

Receiver
Inlet

Sub-cooling

*8 ton and 10 ton units have 2 fans


**Active path: The refrigerant circuit(s) of an outdoor unit coil that provide(s) continuous heating capacity during split coil defrost operation.

Press ure Sensor

Temperature Sensor

Check Valve

Press ure Switch

SVC Valve

EEV

Soleno id Valve

Remarks

Strainer

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

PRODUCT DATA

69

REFRIGERANT FLOW DIAGRAMS


ARUB072BTE4 / 072DTE4, ARUB096BTE4 / 096DTE4,

Cooling Mode

ARUB121BTE4 / 121DTE4 Heat Recovery


Indoor HEX

EEV

Fan
Indoor Unit
HR Unit
s

Indoor HEX

EEV
s

Fan

MULTI V IV Outdoor Unit Engineering Manual

Indoor Unit
s

Indoor HEX

EEV
s

s
s

Fan

Indoor Unit

Indoor HEX

EEV

Fan
Indoor Unit

*
Outdoor
Temperature
Sensor

Fan

Fan

High Temperature High Pressure Gas


High Temperature High Pressure Liquid
Low Temperature Low Pressure Gas

Charging Port

High Pressure
Sensor

High Pressure Gas Pipe

Pressure
Switch

Low Pressure Gas Pipe

Liquid Pipe
4-Way Valve

Outdoor Unit
HEX Temperature
Sensor
Lower HEX
Hot Gas Valve

SC Suction

Suction
Temperature
Sensor

S
S

Upper HEX
Hot Gas Valve
S

Inverter
Comp1

Receiver

Oil Return
S

Lower
Outdoor
EEV
Sub-cooling Circuit
Outlet Temperature
Sensor

Receiver
Outlet

Comp
Discharge
Temperature
Sensor

Upper
Outdoor
EEV

Oil

Separator

Low
Pressure
Sensor

Accum

Liquid Pipe
Temperature
Sensor

Comp
Vapor
Injection

Sub-cooling HEX

Sub-cooling Circuit
inlet Temperature
Sensor

Receiver
inlet

Sub-cooling

*8 ton and10 ton units have 2 fans

70

PRODUCT DATA

Press ure Sensor

Temperature Sensor

Check Valve

Press ure Switch

SVC Valve

EEV

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

Soleno id Valve

Remarks

Strainer

REFRIGERANT FLOW DIAGRAMS


Cooling at Low Ambient Temperatures

ARUB072BTE4 / 072DTE4, ARUB096BTE4 /

096DTE4, ARUB121BTE4 / 121DTE4 Heat Recovery


Indoor HEX

EEV

Fan
Indoor Unit
HR Unit
s

Indoor HEX

EEV
s

Fan

Indoor Unit
s

s
s

Indoor HEX

EEV
s

s
s

Fan

Indoor Unit

Indoor HEX

Product Data

EEV

Fan
Indoor Unit

High Temperature High Pressure Gas


High Temperature High Pressure Liquid
Low Temperature Low Pressure Gas

*
Outdoor
Temperature
Sensor

Fan

Fan

Charging Port

High Pressure
Sensor

High Pressure Gas Pipe

Pressure
Switch

Low Pressure Gas Pipe


Liquid Pipe
4-Way Valve

Outdoor Unit
HEX Temperature
Sensor
Lower HEX
Hot Gas Valve

SC Suction

Suction
Temperature
Sensor

S
S

Upper HEX
Hot Gas Valve

Accum
Receiver
Outlet

Comp
Vapor
Injection

Liquid Pipe
Temperature
Sensor

Comp
Discharge
Temperature
Sensor
Inverter
Comp1

Receiver

Lower
Outdoor
EEV

Separator

Low
Pressure
Sensor

Upper
Outdoor
EEV

Oil

Oil Return
S

Sub-cooling Circuit
Outlet Temperature
Sensor

Sub-cooling HEX

Sub-cooling Circuit
Inlet Temperature
Sensor

Receiver
Inlet

Sub-cooling

*8 ton and 10 ton units have 2 fans

Press ure Sensor

Temperature Sensor

Check Valve

Press ure Switch

SVC Valve

EEV

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

Soleno id Valve

Remarks

Strainer

PRODUCT DATA

71

REFRIGERANT FLOW DIAGRAMS


ARUB072BTE4 / 072DTE4, ARUB096BTE4 / 096DTE4,

Heating

ARUB121BTE4 / 121DTE4 Heat Recovery


Indoor HEX

EEV

Fan
Indoor Unit
HR Unit
s

Indoor HEX

EEV
s

Fan

MULTI V IV Outdoor Unit Engineering Manual

Indoor Unit
s

Indoor HEX

EEV
s

s
s

Fan

Indoor Unit

Indoor HEX

EEV

Fan
Indoor Unit

*
Outdoor
Temperature
Sensor

Fan

Fan

High Temperature High Pressure Gas


High Temperature High Pressure Liquid
Low Temperature Low Pressure Gas

Charging Port

High Pressure
Sensor

Pressure
Switch

High Pressure Gas Pipe


Low Pressure Gas Pipe

Liquid Pipe
4-Way Valve

Outdoor Unit
HEX Temperature
Sensor
Lower HEX
Hot Gas Valve

SC Suction

Suction
Temperature
Sensor

S
S

Upper HEX
Hot Gas Valve
S

Inverter
Comp1

Receiver

Oil Return
S

Lower
Outdoor
EEV
Sub-cooling Circuit
Outlet Temperature
Sensor

Receiver
Outlet

Comp
Discharge
Temperature
Sensor

Upper
Outdoor
EEV

Separator

Low
Pressure
Sensor

Accum

Liquid Pipe
Temperature
Sensor

Comp
Vapor
Injection

Oil

Sub-cooling HEX

Sub-cooling Circuit
inlet Temperature
Sensor

Receiver
Inlet

Sub-cooling

*8 ton and 10 ton units have 2 fans

72

PRODUCT DATA

Press ure Sensor

Temperature Sensor

Check Valve

Press ure Switch

SVC Valve

EEV

Soleno id Valve

Remarks

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

Strainer

REFRIGERANT FLOW DIAGRAMS


Oil Return and Defrost Operation

ARUB072BTE4 / 072DTE4, ARUB096BTE4 /


096DTE4, ARUB121BTE4 / 121DTE4 Heat Recovery

Indoor HEX

EEV

Fan
Indoor Unit
HR Unit
s

Indoor HEX

EEV
s

Fan

Indoor Unit
s

s
s

Indoor HEX

EEV
s

s
s

Fan

Indoor Unit

Indoor HEX

Product Data

EEV

Fan
Indoor Unit

High Temperature High Pressure Gas


High Temperature High Pressure Liquid
Low Temperature Low Pressure Gas

*
Outdoor
Temperature
Sensor

Fan

Fan

Charging Port

High Pressure
Sensor

Pressure
Switch

High Pressure Gas Pipe


Low Pressure Gas Pipe
Liquid Pipe

Outdoor Unit
HEX Temperature
Sensor

4-Way Valve

Lower HEX
Hot Gas Valve

SC Suction

Suction
Temperature
Sensor

S
S

Upper HEX
Hot Gas Valve

Accum
S

Inverter
Comp1

Receiver

Oil Return
S

Lower
Outdoor
EEV
Sub-cooling Circuit
Outlet Temperature
Sensor

Receiver
Outlet

Comp
Discharge
Temperature
Sensor

Upper
Outdoor
EEV

Oil

Separator

Low
Pressure
Sensor

Liquid Pipe
Temperature
Sensor

Comp
Vapor
Injection

Sub-cooling HEX

Sub-cooling Circuit
Inlet Temperature
Sensor

Receiver
Inlet

Sub-cooling

*8 ton and 10 ton units have 2 fans

Press ure Sensor

Temperature Sensor

Check Valve

Press ure Switch

SVC Valve

EEV

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

Soleno id Valve

Remarks

Strainer

PRODUCT DATA

73

REFRIGERANT FLOW DIAGRAMS


ARUB072BTE4 / 072DTE4, ARUB096BTE4 /

Cooling-based Simultaneous Operation

096DTE4, ARUB121BTE4 / 121DTE4 Heat Recovery


Indoor HEX

EEV

Fan
Indoor Unit
HR Unit
s

Indoor HEX

EEV
s

Fan

MULTI V IV Outdoor Unit Engineering Manual

Indoor Unit
s

Indoor HEX

EEV
s

s
s

Fan

Indoor Unit

Indoor HEX

EEV

Fan
Indoor Unit

High Temperature High Pressure Gas


High Temperature High Pressure Liquid
Low Temperature Low Pressure Gas

*
Outdoor
Temperature
Sensor

Fan

Fan

Charging Port

High Pressure
Sensor

Pressure
Switch

High Pressure Gas Pipe


Low Pressure Gas Pipe

Liquid Pipe
4-Way Valve

Outdoor Unit
HEX Temperature
Sensor
Lower HEX
Hot Gas Valve

SC Suction

Suction
Temperature
Sensor

S
S

Upper HEX
Hot Gas Valve

Low
Pressure
Sensor

Accum
S

Comp
Discharge
Temperature
Sensor
Inverter
Comp1

Receiver

Oil Return
S

Lower
Outdoor
EEV
Sub-cooling Circuit
Outlet Temperature
Sensor

Liquid Pipe
Temperature
Sensor

Upper
Outdoor
EEV

Receiver
Outlet

Oil

Separator

Comp
Vapor
Injection

Sub-cooling HEX

Sub-cooling Circuit
Inlet Temperature
Sensor

Receiver
Inlet

Sub-cooling

*8 ton and 10 ton units have 2 fans

74

PRODUCT DATA

Press ure Sensor

Temperature Sensor

Check Valve

Press ure Switch

SVC Valve

EEV

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

Soleno id Valve

Remarks

Strainer

REFRIGERANT FLOW DIAGRAMS


Heating-based Simultaneous Operation

ARUB072BTE4 / 072DTE4, ARUB096BTE4 /

096DTE4, ARUB121BTE4 / 121DTE4 Heat Recovery


Indoor HEX

EEV

Fan
Indoor Unit
HR Unit
s

Indoor HEX

EEV
s

Fan

Indoor Unit
s

s
s

Indoor HEX

EEV
s

s
s

Fan

Indoor Unit

Indoor HEX

Product Data

EEV

Fan
Indoor Unit

*
Outdoor
Temperature
Sensor

Fan

Fan

High Temperature High Pressure Gas


High Temperature High Pressure Liquid
Low Temperature Low Pressure Gas

Charging Port

High Pressure
Sensor

Pressure
Switch

High Pressure Gas Pipe


Low Pressure Gas Pipe

Liquid Pipe
Outdoor unit
HEX Temperature
Sensor

4-Way Valve

Lower HEX
Hot Gas Valve

SC Suction

Suction
Temperature
Sensor

S
S

Upper HEX
Hot Gas Valve
S

Inverter
Comp1

Receiver

Oil Return
S

Lower
Outoor
EEV
Sub-cooling Circuit
Outlet Temperature
Sensor

Receiver
Outlet

Comp
Discharge
Temperature
Sensor

Upper
Outdoor
EEV

Oil

Separator

Low
Pressure
Sensor

Accum

Liquid Pipe
Temperature
Sensor

Comp
Vapor
Injection

Sub-cooling HEX

Sub-cooling Circuit
Inlet Temperature
Sensor

Receiver
Inlet

Sub-cooling

*8 ton and 10 ton units have 2 fans

Press ure Sensor

Temperature Sensor

Check Valve

Press ure Switch

SVC Valve

EEV

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

Soleno id Valve

Remarks

Strainer

PRODUCT DATA

75

REFRIGERANT FLOW DIAGRAMS


Balanced Simultaneous Operation

ARUB072BTE4 / 072DTE4, ARUB096BTE4 /

096DTE4, ARUB121BTE4 / 121DTE4 Heat Recovery


Indoor HEX

EEV

Fan
Indoor Unit
HR Unit
s

Indoor HEX

EEV
s

Fan

MULTI V IV Outdoor Unit Engineering Manual

Indoor Unit
s

Indoor HEX

EEV
s

s
s

Fan

Indoor Unit

Indoor HEX

EEV

Fan
Indoor Unit

High Temperature High Pressure Gas


High Temperature High Pressure Liquid
Low Temperature Low Pressure Gas

*
Outdoor
Temperature
Sensor

Fan

Fan

Charging Port

High Pressure
Sensor

High Pressure Gas Pipe

Pressure
Switch

Low Pressure Gas Pipe


Liquid Pipe
4-Way Valve

Outdoor Unit
HEX Temperature
Sensor
Lower HEX
Hot Gas Valve

SC Suction

Suction
Temperature
Sensor

S
S

Upper HEX
Hot Gas Valve

Accum

Liquid Pipe
Temperature
Sensor

Comp
Vapor
Injection
Comp
Discharge
Temperature
Sensor

Inverter
Comp1

Receiver

Oil Return
S

Lower
Outdoor
EEV
Sub-cooling Circuit
Outlet Temperature
Sensor

Receiver
Outlet

Separator

Low
Pressure
Sensor

Upper
Outdoor
EEV

Oil

Sub-cooling HEX

Sub-cooling Circuit
Inlet Temperature
Sensor

Receiver
Inlet

Sub-cooling

*8 ton and 10 ton units have 2 fans

76

PRODUCT DATA

Press ure Sensor

Temperature Sensor

Check Valve

Press ure Switch

SVC Valve

EEV

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

Soleno id Valve

Remarks

Strainer

REFRIGERANT FLOW DIAGRAMS


ARUB072BTE4 / 072DTE4, ARUB096BTE4 /

Upper HEX Defrost Operation

096DTE4, ARUB121BTE4 / 121DTE4 Heat Recovery


Indoor HEX

EEV

Fan
Indoor Unit
HR Unit
s

Indoor HEX

EEV
s

Fan

Indoor Unit
s

s
s

Indoor HEX

EEV
s

s
s

Fan

Indoor Unit

Indoor HEX

Product Data

EEV

Fan
Indoor Unit

*
Outdoor
Temperature
Sensor

Fan

Fan

High Temperature High Pressure Gas


High Temperature High Pressure Liquid
Low Temperature Low Pressure Gas

Charging Port

High Pressure
Sensor

Pressure
Switch

High Pressure Gas Pipe


Low Pressure Gas Pipe

Active Path
Outdoor unit
HEX Temperature
Sensor

Liquid Pipe
4-Way Valve

Lower HEX
Hot Gas Valve

SC Suction

Suction
Temperature
Sensor

S
S

Upper HEX
Hot Gas Valve
S

Inverter
Comp1

Receiver

Oil Return
S

Lower
Outdoor
EEV
Sub-cooling Circuit
Outlet Temperature
Sensor

Comp
Discharge
Temperature
Sensor

Upper
Outdoor
EEV

Receiver
Outlet

Separator

Low
Pressure
Sensor

Accum

Liquid Pipe
Temperature
Sensor

Comp
Vapor
Injection

Oil

Sub-Cooling HEX

Sub-cooling Circuit
Inlet Temperature
Sensor

Receiver
Inlet

Sub-cooling

*8 ton and 10 ton units have 2 fans


**Active path: The refrigerant circuit(s) of an outdoor unit coil that provide(s) continuous heating capacity during split coil defrost operation.

Press ure Sensor

Temperature Sensor

Check Valve

Press ure Switch

SVC Valve

EEV

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

Soleno id Valve

Remarks

Strainer

PRODUCT DATA

77

REFRIGERANT FLOW DIAGRAMS


Low HEX Defrost Operation

ARUB072BTE4 / 072DTE4, ARUB096BTE4 /


096DTE4, ARUB121BTE4 / 121DTE4 Heat Recovery
Indoor HEX

EEV

Fan
Indoor Unit
HR Unit
s

Indoor HEX

EEV
s

Fan

MULTI V IV Outdoor Unit Engineering Manual

Indoor Unit
s

Indoor HEX

EEV
s

s
s

Fan

Indoor Unit

Indoor HEX

EEV

Fan
Indoor Unit

High Temperature High Pressure Gas


High Temperature High Pressure Liquid
Low Temperature Low Pressure Gas

*
Outdoor
Temperature
Sensor

Fan

Fan

Charging Port

Active Path

High Pressure
Sensor

Pressure
Switch

High Pressure Gas Pipe


Low Pressure Gas Pipe

Liquid Pipe
4-Way Valve

Outdoor Unit
HEX Temperature
Sensor
Lower HEX
Hot Gas Valve

SC Suction

Suction
Temperature
Sensor

S
S

Upper HEX
Hot Gas Valve

Low
Pressure
Sensor

Accum
S

Inverter
Comp1

Receiver

Oil Return
S

Lower
Outdoor
EEV
Sub-cooling Circuit
Outlet Temperature
Sensor

Receiver
Outlet

Comp
Discharge
Temperature
Sensor

Upper
Outdoor
EEV

Oil

Separator

Liquid Pipe
Temperature
Sensor

Comp
Vapor
Injection

Sub-cooling HEX

Sub-cooling Circuit
Inlet Temperature
Sensor

Receiver
Inlet

Sub-cooling

*8 ton and 10 ton units have 2 fans


**Active path: The refrigerant circuit(s) of an outdoor unit coil that provide(s) continuous heating capacity during split coil defrost operation.

78

PRODUCT DATA

Press ure Sensor

Temperature Sensor

Check Valve

Press ure Switch

SVC Valve

EEV

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

Soleno id Valve

Remarks

Strainer

REFRIGERANT FLOW DIAGRAMS


Cooling Mode

ARUB144BTE4 / 144DTE4, ARUB145BTE4 / 145DTE4,

ARUB168BTE4 / 168DTE4, ARUB169BTE4 / 169DTE4 Heat Recovery


Cooling Operation
Indoor HEX

EEV

Fan
Indoor Unit
HR Unit
s

Indoor HEX

EEV

Fan

s
s

Indoor Unit
s
s

Indoor HEX

EEV
s
s

Fan

Indoor Unit

Indoor HEX

Product Data

EEV

Fan
Indoor Unit

Outdoor
Temperature
Sensor

Fan

High Temperature High Pressure Gas


High Temperature High Pressure Liquid
Low Temperature Low Pressure Gas

Charging Port

High Pressure Pressure


Sensor
Switch

High Pressure Gas Pipe


Low Pressure Gas Pipe
Liquid Pipe

4-Way Valve

Outdoor Unit
HEX Temperature
Sensor
Lower HEX
Hot Gas Valve

SC Suction

Upper HEX
Hot Gas Valve

Upper
Outdoor
EEV

Liquid Pipe
Temperature
Sensor
Suction
Temperature
Sensor

Accum
Receiver
Outlet

Lower
Outdoor
EEV

Sub-cooling Circuit
Outlet Temperature
Sensor

Sub-cooling HEX

Sub-cooling Circuit
Inlet Temperature
Sensor

Low
Pressure
Sensor

Oil
Separ
-ator

Comp1
Vapor
Injection

Comp1
Discharge
Temperature
Sensor

Oil
Balance

Receiver

Inverter
Comp1

Oil
Separ
-ator

Comp2
Discharge
Temperature
Sensor

Comp2
Vapor
Injection

Inverter
Comp2

Oil Return
Receiver
Inlet

ARUB145BTE4/145DTE4,
ARUB169BTE4/169DTE4
frames are ONLY for use in
large capacity triple frame
combinations. They cannot be
used as stand alone models
or in a dual frame combination. These frames ARE
NOT interchangeable with
ARUB144BTE4/144DTE4,
ARUB168BTE4/168DTE4
single frame models.

Sub-cooling

*8 ton and 10 ton units have 2 fans

Press ure Sensor

Temperature Sensor

Check Valve

Press ure Switch

SVC Valve

EEV

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

Soleno id Valve

Remarks

Strainer
PRODUCT DATA

79

REFRIGERANT FLOW DIAGRAMS


ARUB144BTE4 / 144DTE4, ARUB145BTE4 / 145DTE4,

Cooling at Low

ARUB168BTE4 / 168DTE4, ARUB169BTE4 / 169DTE4 Heat Recovery

Ambient Temp.

Indoor HEX

EEV

Fan
Indoor Unit
HR Unit
s

Indoor HEX

EEV

Fan

s
s

MULTI V IV Outdoor Unit Engineering Manual

Indoor Unit
s
s

Indoor HEX

EEV
s
s

Fan

Indoor Unit

Indoor HEX

EEV

Fan
Indoor Unit

Outdoor
Temperature
Sensor

Fan

High Temperature High Pressure Gas


High Temperature High Pressure Liquid
Low Temperature Low Pressure Gas

Charging Port

High Pressure Pressure


Sensor
Switch

High Pressure Gas Pipe


Low Pressure Gas Pipe
Liquid Pipe

4-Way Valve

Outdoor Unit
HEX Temperature
Sensor
Lower HEX
Hot Gas Valve

SC Suction

Upper HEX
Hot Gas Valve

Upper
Outdoor
EEV

Liquid Pipe
Temperature
Sensor
Suction
Temperature
Sensor

Accum

Lower
Outdoor
EEV
Sub-cooling Circuit
Outlet Temperature
Sensor

Receiver
Outlet

Sub-cooling HEX

Sub-cooling Circuit
Inlet Temperature
Sensor

Low
Pressure
Sensor

Oil
Separ
-ator

Comp1
Discharge
Temperature
Sensor
Oil
Balance

Receiver

Oil

Comp1 Separ
-ator
Vapor
Injection

Inverter
Comp1

Comp2
Discharge
Temperature
Sensor

Comp2
Vapor
Injection

Inverter
Comp2

Oil Return
Receiver
Inlet

ARUB145BTE4/145DTE4,
ARUB169BTE4/169DTE4
frames are ONLY for use in
large capacity triple frame
combinations. They cannot be
used as stand alone models
or in a dual frame combination. These frames ARE
NOT interchangeable with
ARUB144BTE4/144DTE4,
ARUB168BTE4/168DTE4
single frame models.

Sub-cooling

*8 ton and 10 ton units have 2 fans

80

PRODUCT DATA

Press ure Sensor

Temperature Sensor

Check Valve

Press ure Switch

SVC Valve

EEV

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

Soleno id Valve

Remarks

Strainer

REFRIGERANT FLOW DIAGRAMS


ARUB144BTE4 / 144DTE4, ARUB145BTE4 / 145DTE4,

Heating Mode

ARUB168BTE4 / 168DTE4, ARUB169BTE4 / 169DTE4 Heat Recovery


Indoor HEX

EEV

Fan
Indoor Unit
HR Unit
s

Indoor HEX

EEV

Fan

s
s

Indoor Unit
s
s

Indoor HEX

EEV
s
s

Fan

Indoor Unit

Indoor HEX

Product Data

EEV

Fan
Indoor Unit

Outdoor
Temperature
Sensor

Fan

High Temperature High Pressure Gas


High Temperature High Pressure Liquid
Low Temperature Low Pressure Gas

Charging Port

High Pressure Pressure


Sensor
Switch

High Pressure Gas Pipe


Low Pressure Gas Pipe
Liquid Pipe

4-Way Valve

Outdoor Unit
HEX Temperature
Sensor
Lower HEX
Hot Gas Valve

SC Suction

Upper HEX
Hot Gas Valve

Upper
Outdoor
EEV

Liquid Pipe
Temperature
Sensor
Suction
Temperature
Sensor
Low
Pressure
Sensor

Accum

Lower
Outdoor
EEV
Sub-cooling Circuit
Outlet Temperature
Sensor

Receiver
Outlet`

Sub-cooling HEX

Sub-cooling Circuit
Inlet Temperature
Sensor

Comp1 Separ
-ator
Vapor
Injection

Comp1
Discharge
Temperature
Sensor
Oil
Balance

Receiver

Oil

Oil
Separ
-ator

Inverter
Comp1

Comp2
Discharge
Temperature
Sensor

Comp2
Vapor
Injection

Inverter
Comp2

Oil Return
Receiver
Inlet

Sub-cooling

ARUB145BTE4/145DTE4,
ARUB169BTE4/169DTE4
frames are ONLY for use in
large capacity triple frame
combinations. They cannot be
used as stand alone models
or in a dual frame combination. These frames ARE
NOT interchangeable with
ARUB144BTE4/144DTE4,
ARUB168BTE4/168DTE4
single frame models.

*8 ton and 10 ton units have 2 fans

Press ure Sensor

Temperature Sensor

Check Valve

Press ure Switch

SVC Valve

EEV

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

Soleno id Valve

Remarks

Strainer
PRODUCT DATA

81

REFRIGERANT FLOW DIAGRAMS


ARUB144BTE4 / 144DTE4, ARUB145BTE4 / 145DTE4,

Oil Return and Defrost


Operation
ARUB168BTE4 / 168DTE4, ARUB169BTE4 / 169DTE4 Heat Recovery
Indoor HEX

EEV

Fan
Indoor Unit
HR Unit
s

Indoor HEX

EEV

Fan

s
s

MULTI V IV Outdoor Unit Engineering Manual

Indoor Unit
s
s

Indoor HEX

EEV
s
s

Fan

Indoor Unit

Indoor HEX

EEV

Fan
Indoor Unit

Outdoor
Temperature
Sensor

Fan

High Temperature High Pressure Gas


High Temperature High Pressure Liquid
Low Temperature Low Pressure Gas

Charging Port

High Pressure Pressure


Sensor
Switch

High Pressure Gas Pipe


Low Pressure Gas Pipe
Liquid Pipe

4-Way Valve

Outdoor Unit
HEX Temperature
Sensor
Lower HEX
Hot Gas Valve

SC Suction

Upper HEX
Hot Gas Valve

Upper
Outdoor
EEV

Liquid Pipe
Temperature
Sensor
Suction
Temperature
Sensor

Accum

Lower
Outdoor
EEV
Sub-cooling Circuit
Outlet Temperature
Sensor

Receiver
Outlet

Sub-Cooling HEX
Sub-cooling

Sub-cooling Circuit
Inlet Temperature
Sensor

Low
Pressure
Sensor

Oil
Separ
-ator

Comp1
Discharge
Temperature
Sensor
Oil
Balance

Receiver

Oil

Comp1 Separ
-ator
Vapor
Injection

Inverter
Comp1

Comp2
Discharge
Temperature
Sensor

Comp2
Vapor
Injection

Inverter
Comp2

Oil Return
Receiver
Inlet

ARUB145BTE4/145DTE4,
ARUB169BTE4/169DTE4
frames are ONLY for use in
large capacity triple frame
combinations. They cannot be
used as stand alone models
or in a dual frame combination. These frames ARE
NOT interchangeable with
ARUB144BTE4/144DTE4,
ARUB168BTE4/168DTE4
single frame models.

Sub-cooling

*8 ton and 10 ton units have 2 fans

82

PRODUCT DATA

Press ure Sensor

Temperature Sensor

Check Valve

Press ure Switch

SVC Valve

EEV

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

Soleno id Valve

Remarks

Strainer

REFRIGERANT FLOW DIAGRAMS


Cooling-based

ARUB144BTE4 / 144DTE4, ARUB145BTE4 / 145DTE4,

Simul. Operation

ARUB168BTE4 / 168DTE4, ARUB169BTE4 / 169DTE4 Heat Recovery


Indoor HEX

EEV

Fan
Indoor Unit
HR Unit
s

Indoor HEX

EEV

Fan

s
s

Indoor Unit
s
s

Indoor HEX

EEV
s
s

Fan

Indoor Unit

Indoor HEX

Product Data

EEV

Fan
Indoor Unit

Outdoor
Temperature
Sensor

Fan

High Temperature High Pressure Gas


High Temperature High Pressure Liquid
Low Temperature Low Pressure Gas

Charging Port

High Pressure Pressure


Sensor
Switch

High Pressure Gas Pipe


Low Pressure Gas Pipe
Liquid Pipe

4-Way Valve

Outdoor Unit
HEX Temperature
Sensor
Lower HEX
Hot Gas Valve

SC Suction

Upper HEX
Hot Gas Valve

Upper
Outdoor
EEV

Liquid Pipe
Temperature
Sensor
Suction
Temperature
Sensor

Accum
Receiver
Outlet

Lower
Outdoor
EEV

Sub-cooling Circuit
Outlet Temperature
Sensor

Sub-Cooling HEX
Sub-cooling

Sub-cooling Circuit
Inlet Temperature
Sensor

Low
Pressure
Sensor

Oil
Separ
-ator

Comp1
Discharge
Temperature
Sensor
Oil
Balance

Receiver

Oil

Comp1 Separ
-ator
Vapor
Injection

Inverter
Comp1

Comp2
Discharge
Temperature
Sensor

Comp2
Vapor
Injection

Inverter
Comp2

Oil Return
Receiver
Inlet

ARUB145BTE4/145DTE4,
ARUB169BTE4/169DTE4
frames are ONLY for use in
large capacity triple frame
combinations. They cannot be
used as stand alone models
or in a dual frame combination. These frames ARE
NOT interchangeable with
ARUB144BTE4/144DTE4,
ARUB168BTE4/168DTE4
single frame models.

Sub-cooling

*8 ton and 10 ton units have 2 fans

Press ure Sensor

Temperature Sensor

Check Valve

Press ure Switch

SVC Valve

EEV

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

Soleno id Valve

Remarks

Strainer

PRODUCT DATA

83

REFRIGERANT FLOW DIAGRAMS


ARUB144BTE4 / 144DTE4, ARUB145BTE4 / 145DTE4,

Heating-based

ARUB168BTE4 / 168DTE4, ARUB169BTE4 / 169DTE4 Heat Recovery


Indoor HEX

Simul. Operation

EEV

Fan
Indoor Unit
HR Unit
s

Indoor HEX

EEV

Fan

s
s

MULTI V IV Outdoor Unit Engineering Manual

Indoor Unit
s
s

Indoor HEX

EEV
s
s

Fan

Indoor Unit

Indoor HEX

EEV

Fan
Indoor Unit

Outdoor
Temperature
Sensor

Fan

High Temperature High Pressure Gas


High Temperature High Pressure Liquid
Low Temperature Low Pressure Gas

Charging Port

High Pressure Pressure


Sensor
Switch

High Pressure Gas Pipe


Low Pressure Gas Pipe
Liquid Pipe

4-Way Valve

Outdoor Unit
HEX Temperature
Sensor
Lower HEX
Hot Gas Valve

SC Suction

Upper HEX
Hot Gas Valve

Upper
Outdoor
EEV

Liquid Pipe
Temperature
Sensor
Suction
Temperature
Sensor
Low
Pressure
Sensor

Accum

Lower
Outdoor
EEV
Sub-cooling Circuit
Outlet Temperature
Sensor

Receiver
Outlet`

Sub-cooling HEX

Sub-cooling Circuit
Inlet Temperature
Sensor

Oil
Separ
-ator

Comp1
Discharge
Temperature
Sensor
Oil
Balance

Receiver

Oil

Comp1 Separ
-ator
Vapor
Injection

Inverter
Comp1

Comp2
Discharge
Temperature
Sensor

Comp2
Vapor
Injection

Inverter
Comp2

Oil Return
Receiver
Inlet

Sub-cooling

ARUB145BTE4/145DTE4,
ARUB169BTE4/169DTE4
frames are ONLY for use in
large capacity triple frame
combinations. They cannot be
used as stand alone models
or in a dual frame combination. These frames ARE
NOT interchangeable with
ARUB144BTE4/144DTE4,
ARUB168BTE4/168DTE4
single frame models.

*8 ton and 10 ton units have 2 fans

84

PRODUCT DATA

Press ure Sensor

Temperature Sensor

Check Valve

Press ure Switch

SVC Valve

EEV

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

Soleno id Valve

Remarks

Strainer

REFRIGERANT FLOW DIAGRAMS


ARUB144BTE4 / 144DTE4, ARUB145BTE4 / 145DTE4,

Balanced

ARUB168BTE4 / 168DTE4, ARUB169BTE4 / 169DTE4 Heat Recovery

Simul. Operation
Indoor HEX

EEV

Fan
Indoor Unit
HR Unit
s

Indoor HEX

EEV

Fan

s
s

Indoor Unit
s
s

Indoor HEX

EEV
s
s

Fan

Indoor Unit

Indoor HEX

Product Data

EEV

Fan
Indoor Unit

Outdoor
Temperature
Sensor

Fan

High Temperature High Pressure Gas


High Temperature High Pressure Liquid
Low Temperature Low Pressure Gas

Charging Port

High Pressure Pressure


Sensor
Switch

High Pressure Gas Pipe


Low Pressure Gas Pipe
Liquid Pipe

4-Way Valve

Outdoor unit
HEX Temperature
Sensor
Lower HEX
Hot Gas Valve

SC Suction

Upper HEX
Hot Gas Valve

Upper
Outdoor
EEV

Liquid Pipe
Temperature
Sensor
Suction
Temperature
Sensor

Accum

Lower
Outdoor
EEV
Sub-cooling Circuit
Outlet Temperature
Sensor

Receiver
Outlet

Sub-cooling HEX

Sub-cooling Circuit
Inlet Temperature
Sensor

Low
Pressure
Sensor

Oil
Separ
-ator

Oil

Comp1 Separ
-ator
Vapor
Injection

Comp1
Discharge
Temperature
Sensor
Oil
Balance

Receiver

Inverter
Comp1

Comp2
Discharge
Temperature
Sensor

Comp2
Vapor
Injection

Inverter
Comp2

Oil Return
Receiver
Inlet

Sub-cooling

ARUB145BTE4/145DTE4,
ARUB169BTE4/169DTE4
frames are ONLY for use in
large capacity triple frame
combinations. They cannot be
used as stand alone models
or in a dual frame combination. These frames ARE
NOT interchangeable with
ARUB144BTE4/144DTE4,
ARUB168BTE4/168DTE4
single frame models.

*10HP,12HP(8Ton, 10Ton) have 2 fans

Press ure Sensor

Temperature Sensor

Check Valve

Press ure Switch

SVC Valve

EEV

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

Soleno id Valve

Remarks

Strainer

PRODUCT DATA

85

REFRIGERANT FLOW DIAGRAMS


Upper HEX Defrost

ARUB144BTE4 / 144DTE4, ARUB145BTE4 / 145DTE4,

Operation

ARUB168BTE4 / 168DTE4, ARUB169BTE4 / 169DTE4 Heat Recovery


Indoor HEX

EEV

Fan
Indoor Unit
HR Unit
s

Indoor HEX

EEV

Fan

s
s

MULTI V IV Outdoor Unit Engineering Manual

Indoor Unit
s
s

Indoor HEX

EEV
s
s

Fan

Indoor Unit

Indoor HEX

EEV

Fan
Indoor Unit

Outdoor
Temperature
Sensor

Fan

High Temperature High Pressure Gas


High Temperature High Pressure Liquid
Low Temperature Low Pressure Gas

Charging Port

High Pressure Pressure


Sensor
Switch

High Pressure Gas Pipe


Low Pressure Gas Pipe
Liquid Pipe

Active Path
4-Way Valve

Outdoor Unit
HEX Temperature
Sensor
Lower HEX
Hot Gas Valve

SC Suction

Upper HEX
Hot Gas Valve

Upper
Outdoor
EEV

Liquid Pipe
Temperature
Sensor
Suction
Temperature
Sensor

Accum

Lower
Outdoor
EEV
Sub-cooling Circuit
Outlet Temperature
Sensor

Receiver
Outlet

Sub-Cooling HEX
Sub-cooling

Sub-cooling Circuit
Inlet Temperature
Sensor

Low
Pressure
Sensor

Oil
Separ
-ator

Comp1
Discharge
Temperature
Sensor
Oil
Balance

Receiver

Oil

Comp1 Separ
-ator
Vapor
Injection

Inverter
Comp1

Comp2
Discharge
Temperature
Sensor

ARUB145BTE4/145DTE4,
ARUB169BTE4/169DTE4
frames are ONLY for use in
large capacity triple frame
combinations. They cannot be
used as stand alone models
or in a dual frame combination. These frames ARE
NOT interchangeable with
ARUB144BTE4/144DTE4,
ARUB168BTE4/168DTE4
single frame models.

Comp2
Vapor
Injection

Inverter
Comp2

Oil Return
Receiver
Inlet

Sub-cooling

*8 ton and 10 ton units have 2 fans


**Active path: The refrigerant circuit(s) of an outdoor unit coil that provide(s) continuous heating capacity during split coil defrost operation.

86

PRODUCT DATA

Press ure Sensor

Temperature Sensor

Check Valve

Press ure Switch

SVC Valve

EEV

Soleno id Valve

Remarks

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

Strainer

REFRIGERANT FLOW DIAGRAMS


Low HEX Defrost

ARUB144BTE4 / 144DTE4, ARUB145BTE4 / 145DTE4,

Operation

ARUB168BTE4 / 168DTE4, ARUB169BTE4 / 169DTE4 Heat Recovery


Indoor HEX

EEV

Fan
Indoor Unit
HR Unit
s

Indoor HEX

EEV

Fan

s
s

Indoor Unit
s
s

Indoor HEX

EEV
s
s

Fan

Indoor Unit

Indoor HEX

Product Data

EEV

Fan
Indoor Unit

Outdoor
Temperature
Sensor

Fan

High Temperature High Pressure Gas


High Temperature High Pressure Liquid
Low Temperature Low Pressure Gas

Charging Port

High Pressure Pressure


Sensor
Switch

Active Path

High Pressure Gas Pipe


Low Pressure Gas Pipe
Liquid Pipe

4-Way Valve

Outdoor Unit
HEX Temperature
Sensor
Low HEX
Hot Gas Valve

SC Suction

Upper HEX
Hot Gas Valve

Upper
Outdoor
EEV

Liquid Pipe
Temperature
Sensor
Suction
Temperature
Sensor

Accum

Lower
Outdoor
EEV
Sub-cooling Circuit
Outlet Temperature
Sensor

Receiver
Outlet

Sub-Cooling HEX
Sub-cooling
HEX

Sub-cooling Circuit
Inlet Temperature
Sensor

Low
Pressure
Sensor

Comp1 Separ
-ator
Vapor
Injection

Comp1
Discharge
Temperature
Sensor
Oil
Balance

Receiver

Oil

Oil
Separ
-ator

Inverter
Comp1

Comp2
Discharge
Temperature
Sensor

Comp2
Vapor
Injection

Inverter
Comp2

Oil Return
Receiver
Inlet

ARUB145BTE4/145DTE4,
ARUB169BTE4/169DTE4
frames are ONLY for use in
large capacity triple frame
combinations. They cannot be
used as stand alone models
or in a dual frame combination. These frames ARE
NOT interchangeable with
ARUB144BTE4/144DTE4,
ARUB168BTE4/168DTE4
single frame models.

Sub-cooling

*8 ton and 10 ton units have 2 fans


**Active path: The refrigerant circuit(s) of an outdoor unit coil that provide(s) continuous heating capacity during split coil defrost operation.

Press ure Sensor

Temperature Sensor

Check Valve

Press ure Switch

SVC Valve

EEV

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

Soleno id Valve

Remarks

Strainer

PRODUCT DATA

87

REFRIGERANT FLOW DIAGRAMS

MULTI V IV Outdoor Unit Engineering Manual

PRHR022A, PRHR032A, PRHR042A Heat Recovery Units

A : Switch operation between cooling and heating.


B : Decreases noise following subcooling operation between inlet of one indoor unit and outlet of another indoor unit during simultaneous
operation.
C : Prevents liquid from entering high-pressure vapor valve and heat recovery unit during cooling mode.
D : Controls pressure between the high and low pressure vapor pipes during simultaneous operation.

88

PRODUCT DATA

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

ACOUSTIC DATA
Sound Pressure Levels - Measurement Location

Table 27: Heat Pump Sound Pressure Levels.


Heat Pump Models
208-230V
460V

ARUN072DTE4
ARUN096DTE4
ARUN121DTE4
ARUN144DTE4
ARUN145DTE4
ARUN168DTE4
ARUN169DTE4
ARUN192DTE4
ARUN216DTE4
ARUN240DTE4
ARUN264DTE4
ARUN288DTE4
ARUN313DTE4
ARUN337DTE4
ARUN312DTE4
ARUN336DTE4
ARUN360DTE4
ARUN384DTE4
ARUN408DTE4
ARUN432DTE4
ARUN456DTE4
ARUN480DTE4
ARUN504DTE4

dB(A)
58.5
59.0
59.0
59.5
59.5
59.5
59.5
61.8
62.0
62.3
62.3
62.5
62.5
62.5
63.8
63.9
63.9
64.1
64.1
64.3
64.3
64.3
64.3

Table 28: Heat Recovery Sound Pressure Levels.


Heat Recovery Models
208-230V
460V

ARUB072BTE4
ARUB096BTE4
ARUB121BTE4
ARUB144BTE4
ARUB145BTE4
ARUB168BTE4
ARUB169BTE4
ARUB192BTE4
ARUB216BTE4
ARUB240BTE4
ARUB264BTE4
ARUB288BTE4
ARUB313BTE4
ARUB337BTE4
ARUB312BTE4
ARUB336BTE4
ARUB360BTE4
ARUB384BTE4
ARUB408BTE4
ARUB432BTE4
ARUB456BTE4
ARUB480BTE4
ARUB504BTE4

ARUB072DTE4
ARUB096DTE4
ARUB121DTE4
ARUB144DTE4
ARUB145DTE4
ARUB168DTE4
ARUB169DTE4
ARUB192DTE4
ARUB216DTE4
ARUB240DTE4
ARUB264DTE4
ARUB288DTE4
ARUB313DTE4
ARUB337DTE4
ARUB312DTE4
ARUB336DTE4
ARUB360DTE4
ARUB384DTE4
ARUB408DTE4
ARUB432DTE4
ARUB465DTE4
ARUB480DTE4
ARUB504DTE4

dB(A)
58.5
59.0
59.0
59.5
59.5
59.5
59.5
61.8
62.0
62.3
62.3
62.5
62.5
62.5
63.8
63.9
63.9
64.1
64.1
64.3
64.3
64.3
64.3

3.3 ft
3.3 ft

Measurement taken 3.3 above finished floor, and at a distance of


3.3 from face of unit.
Measurements taken with no attenuation and units operating at full
load normal operating condition.
Sound level will vary depending on a range of factors such as
construction (acoustic absorption coefficient) of particular area in
which the equipment is installed.
Sound level may be increased in static pressure mode or if an air
guide is used.
Sound levels are measured in dB(A)3.
Tested in anechoic chamber per ISO Standard 3745.

ARUN145BTE4/ARUN145DTE4, ARUB145BTE4/ARUB145DTE4,
ARUN169BTE4/ARUN169DTE4, ARUB169BTE4/ARUB169DTE4
frames are ONLY for use in large capacity triple frame combinations. They cannot be used as stand alone models or in a dual
frame combination. These frames ARE NOT interchangeable with
ARUN144BTE4/ARUN144DTE4, ARUB144BTE4/ARUB144DTE4,
ARUN168BTE4/ARUN168DTE4, ARUB168BTE4/ARUB168DTE4
single frame models.

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

PRODUCT DATA

89

Product Data

ARUN072BTE4
ARUN096BTE4
ARUN121BTE4
ARUN144BTE4
ARUN145BTE4
ARUN168BTE4
ARUN169BTE4
ARUN192BTE4
ARUN216BTE4
ARUN240BTE4
ARUN264BTE4
ARUN288BTE4
ARUN313BTE4
ARUN337BTE4
ARUN312BTE4
ARUN336BTE4
ARUN360BTE4
ARUN384BTE4
ARUN408BTE4
ARUN432BTE4
ARUN456BTE4
ARUN480BTE4
ARUN504BTE4

Figure 4: Sound Pressure Measurement Location.

ACOUSTIC DATA
Sound Pressure Levels - Heat Pump

Heat Pump Sound Pressure Levels

70

70

70

NC-65

60

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20

63

NC-15

250

500

1 000

2 000 4 000

NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20
Approximate
Hearing
Threshold
10

8 000

Octave Band Center Frequency (Hz)

63

NC-60

250

500

1 000

2 000 4 000

NC-50

NC-40

NC-30

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20
Approximate
Hearing
Threshold
10

63

NC-60

NC-50

500

1 000

2 000 4 000

NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20
Approximate
Hearing
Threshold

NC-15

250

NC-55

50

NC-20

125

NC-65

10

8 000

63

Octave Band Center Frequency (Hz)

Octave Band Sound Pressure Level (0 dB = 20 Pa)

70

Octave Band Sound Pressure Level (0 dB = 20 Pa)

70

50

500

1 000

2 000 4 000

NC-50

NC-40

NC-30

10

8 000

NC-50
NC-45
NC-40
NC-35
NC-30
NC-25

125

250

500

1 000

2 000 4 000

Octave Band Center Frequency (Hz)

NC-60

PRODUCT DATA

8 000

NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20
Approximate
Hearing
Threshold

NC-20
NC-15

NC-65

60

10

63

Octave Band Sound Pressure Level (0 dB = 20 Pa)

NC-55

Octave Band Sound Pressure Level (0 dB = 20 Pa)

NC-60

63

NC-15

125

250

500

1 000

2 000 4 000

8 000

ARUN360BTE4, ARUN360DTE4

NC-65

10

63

NC-20

Octave Band Center Frequency (Hz)

70

Approximate
Hearing
Threshold

NC-25

20

70

20

NC-35

30

70

30

NC-45

40

80

40

8 000

NC-55

50

80

50

2 000 4 000

NC-60

80

60

1 000

NC-65

Octave Band Center Frequency (Hz)

ARUN312BTE4, ARUN336BTE4,
ARUN312DTE4, ARUN336DTE4

500

Approximate
Hearing
Threshold

NC-15

250

250

60

NC-20

125

NC-15

125

Octave Band Center Frequency (Hz)

70

NC-55

63

NC-20

ARUN264BTE4, ARUN288BTE4,
ARUN264DTE4, ARUN288DTE4
80

60

NC-25

20

80

NC-60

NC-35

30

80

NC-65

NC-45

40

10

8 000

Octave Band Center Frequency (Hz)

60

NC-55

50

Approximate
Hearing
Threshold

NC-15

125

NC-65

60

NC-20

ARUN216BTE4, ARUN240BTE4,
ARUN216DTE4, ARUN240DTE4

ARUN192BTE4, ARUN192DTE4

Octave Band Sound Pressure Level (0 dB = 20 Pa)

NC-60

NC-20

125

NC-65

60

Octave Band Sound Pressure Level (0 dB = 20 Pa)

80

10

90

ARUN144BTE4, ARUN145BTE, ARUN168BTE4,


ARUN144DTE4, ARUN145DTE, ARUN168DTE4

80

Octave Band Sound Pressure Level (0 dB = 20 Pa)

Octave Band Sound Pressure Level (0 dB = 20 Pa)

ARUN096BTE4, ARUN121BTE4,
ARUN096DTE4, ARUN121DTE4

80

Approximate
Hearing
Threshold

Octave Band Sound Pressure Level (0 dB = 20 Pa)

MULTI V IV Outdoor Unit Engineering Manual

ARUN072BTE4, ARUN072DTE4

NC-60

125

250

500

1 000

2 000 4 000

Octave Band Center Frequency (Hz)

8 000

NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20
Approximate
Hearing
Threshold

NC-20
NC-15

NC-65

60

10

63

NC-20
NC-15

125

250

500

1 000

2 000 4 000

Octave Band Center Frequency (Hz)

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

8 000

ACOUSTIC DATA
Sound Pressure Levels - Heat Pump / Heat Recovery

Heat Pump Sound Pressure Levels, continued


ARUN384BTE4,
ARUN384BTE4,ARUN384DTE4
ARUN384DTE4
ARUN408BTE4,
ARUN408BTE4,ARUN408DTE4
ARUN408DTE4

ARUN456BTE4, ARUN480DTE4, ARUN504BTE4


ARUN408BTE4, ARUN408DTE4, ARUN504DTE4

ARUN432BTE4,
ARUN432BTE4,ARUN432DTE4
ARUN432DTE4

ARUB096BTE4, ARUB121BTE4,
ARUB096DTE4, ARUB121DTE4
80

70

70

70

NC-65

60

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20

10

63

125

250

500

1 000

2 000 4 000

NC-65

60

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20
Approximate
Hearing
Threshold

NC-20
NC-15

10

8 000

Octave Band Center Frequency (Hz)

Octave Band Sound Pressure Level (0 dB = 20 Pa)

80

Approximate
Hearing
Threshold

63

250

500

1 000

2 000 4 000

70

70

NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20
Approximate
Hearing
Threshold
10

63

NC-60

125

250

500

1 000

2 000 4 000

8 000

NC-50

80

NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20
Approximate
Hearing
Threshold
10

Octave Band Center Frequency (Hz)

ARUB312BTE4, ARUB336BTE4,
ARUB312DTE4, ARUB336DTE4

NC-55

50

NC-20
NC-15

NC-65

63

Octave Band Sound Pressure Level (0 dB = 20 Pa)

70

Octave Band Sound Pressure Level (0 dB = 20 Pa)

80

60

125

NC-40

250

500

1 000

2 000 4 000

8 000

NC-35

30

NC-30
NC-25

20

63

NC-20
NC-15

125

250

1 000

2 000 4 000

8 000

NC-65
NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20
Approximate
Hearing
Threshold
10

Octave Band Center Frequency (Hz)

63

NC-20
NC-15

125

250

500

1 000

2 000 4 000

8 000

Octave Band Center Frequency (Hz)

Due to our policy


of continuous product
innovation, some specifications may change without notification.
ARUB360BTE4,
ARUB360DTE4
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.
80

500

60

NC-20
NC-15

NC-45

40

ARUB264BTE4, ARUB288BTE4,
ARUB264DTE4, ARUB288DTE4

80

NC-60

NC-50

Octave Band Center Frequency (Hz)

ARUB216BTE4, ARUB240BTE4,
ARUB216DTE4 , ARUB240DTE4

NC-65

NC-55

50

10

8 000

80

60

NC-60

Approximate
Hearing
Threshold

NC-15

125

NC-65

60

NC-20

Octave Band Center Frequency (Hz)

ARUB192BTE4, ARUB192DTE4

Octave Band Sound Pressure Level (0 dB = 20 Pa)

ARUB144BTE4, ARUB168BTE4,
ARUB144DTE4, ARUB168DTE4

80

Octave Band Sound Pressure Level (0 dB = 20 Pa)

Octave Band Sound Pressure Level (0 dB = 20 Pa)

ARUB072BTE4, ARUB072DTE4

Product Data

Heat Recovery Sound Pressure Levels

80

PRODUCT DATA

91

NC-55

50

ACOUSTIC DATA
NC-50
NC-45

40

NC-40

NC-65

60

NC-60
NC-55

50

NC-50
NC-45

40

NC-40

Sound Pressure Levels - Heat Recovery


NC-35

30

NC-30
NC-25

20
Approximate
Hearing
Threshold
10

NC-35

30

NC-30
NC-25

20
Approximate
Hearing
Threshold

NC-20
NC-15

125

250

500

1 000

2 000 4 000

10

8 000

125

250

500

1 000

2 000 4 000

NC-50

NC-40

NC-30

Approximate
Hearing
Threshold

NC-15

10

8 000

NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25

10

63

125

250

500

1 000

2 000 4 000

Octave Band Center Frequency (Hz)

ARUB432BTE4, ARUB432DTE4

NC-60

PRODUCT DATA

8 000

NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20
Approximate
Hearing
Threshold

NC-20
NC-15

NC-65

60

10

63

Octave Band Sound Pressure Level (0 dB = 20 Pa)

70

20

63

NC-20
NC-15

125

250

500

1 000

2 000 4 000

8 000

Octave Band Center Frequency (Hz)

70

30

NC-25

20

70

40

NC-35

30

80

50

NC-45

40

80

60

NC-55

50

80

Approximate
Hearing
Threshold

92

NC-60

ARUB360BTE4, ARUB360DTE4

Octave Band Sound Pressure Level (0 dB = 20 Pa)

Octave Band Sound Pressure Level (0 dB = 20 Pa)

MULTI V IV Outdoor Unit Engineering Manual

ARUB312BTE4, ARUB336BTE4,
ARUB312DTE4, ARUB336DTE4

63

NC-65

60

NC-20

Octave Band Center


FrequencyPressure
(Hz)
Octave Band Center Frequency (Hz)
Heat Recovery
Sound
Levels, continued
63

Octave Band Sound Pressure Level (0 dB = 20

NC-60

Octave Band Sound Pressure Level (0 dB = 20 P

Octave Band Sound Pressure Level (0 dB = 20 P

NC-65

60

125

250

500

1 000

2 000 4 000

8 000

Octave Band Center Frequency (Hz)

ARUB432BTE4, ARUB432DTE4

NC-65

60

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20
Approximate
Hearing
Threshold

NC-20
NC-15

ARUB384BTE4, ARUB384DTE4
ARUB408BTE4, ARUB408DTE4

10

63

NC-20
NC-15

125

250

500

1 000

2 000 4 000

Octave Band Center Frequency (Hz)

ARUB456BTE4, ARUB480DTE4, ARUB504BTE4


ARUB408BTE4, ARUB408DTE4, ARUB504DTE4

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

8 000

ACOUSTIC DATA
Sound Power Levels

Data is valid under diffuse field conditions.


Data is valid under nominal operating conditions.
Sound level may be increased in static pressure mode or if air
guide is used.
Sound power level is measured using rated conditions, and tested
in a reverberation room per ISO 3741 standards.
Sound level will vary depending on a range of factors such as
construction (acoustic absorption coefficient) of particular area in
which the equipment is installed.
Reference acoustic intensity: 0dB = 10E-6W/m2
Table 29: Heat Pump Sound Power Levels.
Heat Pump Models
208-230V
460V

dB(A)

ARUN072DTE4
ARUN096DTE4
ARUN121DTE4
ARUN144DTE4
ARUN145DTE4
ARUN168DTE4
ARUN169DTE4
ARUN192DTE4
ARUN216DTE4
ARUN240DTE4
ARUN264DTE4
ARUN288DTE4
ARUN313DTE4
ARUN337DTE4
ARUN312DTE4
ARUN336DTE4
ARUN360DTE4
ARUN384DTE4
ARUN408DTE4
ARUN423DTE4
ARUN384DTE4
ARUN408DTE4
ARUN432DTE4
ARUN456DTE4
ARUN480DTE4
ARUN504DTE4

78.0
79.0
79.0
79.5
79.5
79.5
79.5
81.5
81.8
82.3
82.3
82.5
82.5
82.5
83.6
83.9
83.9
84.1
84.1
84.3
84.3
84.3
84.3
84.3
84.3
84.3

Heat Pump Sound Power Levels


ARUN072BTE4, ARUN072DTE4

ARUB072BTE4
ARUB096BTE4
ARUB121BTE4
ARUB144BTE4
ARUB145BTE4
ARUB168BTE4
ARUB169BTE4
ARUB192BTE4
ARUB216BTE4
ARUB240BTE4
ARUB264BTE4
ARUB288BTE4
ARUB313BTE4
ARUB337BTE4
ARUB312BTE4
ARUB336BTE4
ARUB360BTE4
ARUB384BTE4
ARUB408BTE4
ARUB432BTE4
ARUB384BTE4
ARUB408BTE4
ARUB432BTE4
ARUB456BTE4
ARUB480BTE4
ARUB504BTE4

ARUN096BTE4 , ARUN121BTE4,
ARUN096DTE4, ARUN121DTE4

100

100

90

90

NR-90

NR-90

80

NR-80

70

NR-75
NR-70

60

NR-65
NR-60

50

NR-55
NR-50

40

NR-45

NR-85
NR-80

70

NR-75
NR-70

60

NR-65
NR-60

50

NR-55
NR-50

40

NR-45

NR-40

30

NR-35

125

250

500

1000

2000

4000

Octave Band Center Frequency (Hz)

8000

NR-85
NR-80

70

NR-75
NR-70

60

NR-65
NR-60

50

NR-55
NR-50

40

NR-45

NR-40

30

NR-35

NR-30

20

NR-90

80

Sound Power Level (0dB = 10E-6Pa)

NR-85

Sound Power Level (0dB = 10E-6Pa)

Sound Power Level (0dB = 10E-6Pa)

80

NR-40

30

NR-35

NR-30

20

78.0
79.0
79.0
79.5
79.5
79.5
79.5
81.5
81.8
82.3
82.3
82.5
82.5
82.5
83.6
83.9
83.9
84.1
84.1
84.3
84.3
84.3
84.3
84.3
84.3
84.3

ARUN144BTE4, ARUN145BTE4, ARUN168BTE4,


ARUN144DTE4, ARUN145DTE4, ARUN168DTE4

100

90

ARUB072DTE4
ARUB096DTE4
ARUB121DTE4
ARUB144DTE4
ARUB145DTE4
ARUB168DTE4
ARUB169DTE4
ARUB192DTE4
ARUB216DTE4
ARUB240DTE4
ARUB264DTE4
ARUB288DTE4
ARUB313DTE4
ARUB337DTE4
ARUB312DTE4
ARUB336DTE4
ARUB360DTE4
ARUB384DTE4
ARUB408DTE4
ARUB432DTE4
ARUB384DTE4
ARUB408DTE4
ARUB432DTE4
ARUB465DTE4
ARUB480DTE4
ARUB504DTE4

Product Data

ARUN072BTE4
ARUN096BTE4
ARUN121BTE4
ARUN144BTE4
ARUN145BTE4
ARUN168BTE4
ARUN169BTE4
ARUN192BTE4
ARUN216BTE4
ARUN240BTE4
ARUN264BTE4
ARUN288BTE4
ARUN313BTE4
ARUN337BTE4
ARUN312BTE4
ARUN336BTE4
ARUN360BTE4
ARUN384BTE4
ARUN408BTE4
ARUN432BTE4
ARUN384BTE4
ARUN408BTE4
ARUN432BTE4
ARUN456BTE4
ARUN480BTE4
ARUN504BTE4

ARUN145BTE4/ARUN145DTE4, ARUB145BTE4/ARUB145DTE4,
ARUN169BTE4/ARUN169DTE4, ARUB169BTE4/ARUB169DTE4
frames are ONLY for use in large capacity triple frame combinations. They cannot be used as stand alone models or in a dual
frame combination. These frames ARE NOT interchangeable with
ARUN144BTE4/ARUN144DTE4, ARUB144BTE4/ARUB144DTE4,
ARUN168BTE4/ARUN168DTE4, ARUB168BTE4/ARUB168DTE4
single frame models.
Table 30: Heat Recovery Sound Power Levels.
Heat Recovery Models
dB(A)
208-230V
460V

125

250

500

1000

2000

4000

Octave Band Center Frequency (Hz)

8000

NR-30

20

125

250

500

1000

2000

4000

8000

Octave Band Center Frequency (Hz)

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

PRODUCT DATA

93

ACOUSTIC DATA
Sound Power Levels - Heat Pump

Heat Pump Sound Power Levels, continued

ARUN240BTE4, ARUN264BTE
ARUN264BT
ARUN240BTE4,
ARUN240DTE4, ARUN264DT
ARUN264DT
ARUN240DTE4,

ARUN216BTE4, ARUN216DTE4
ARUN216DTE4
ARUN216BTE4,

ARUN192BTE4, ARUN192DTE4
ARUN192DTE4
ARUN192BTE4,

ARUN169BTE4, ARUN169DTE4
100

100
100

100
100

100
100

90

NR-70

60

NR-65
NR-60

50

NR-55
NR-50

40

NR-45

NR-45
NR-45
NR-45
NR-40
NR-40
NR-40
NR-35
NR-35
NR-35
NR-30
NR-30
NR-30

8000
008000

NR-35

20

NR-60
NR-60

5050

NR-55
NR-55
NR-50
NR-50

4040

NR-45
NR-45

3030

NR-70
NR-70

6060

NR-65
NR-65
NR-60
NR-60

5050

NR-55
NR-55
NR-50
NR-50

4040

NR-45
NR-45

7070

6060

5050

4040

NR-40
NR-40

3030

NR-35
NR-35

125

250

500

1000

2000

4000

8000

NR-35
NR-35

NR-30
NR-30

2020

125
125

ARUN240BTE4,
ARUN264BTE4,
ARUN216BTE4,ARUN216DTE4
ARUN216DTE4
ARUN216BTE4,
ARUN240DTE4, ARUN264DTE4
100
100100

3030

500
500

1000 2000
2000
1000

NR-85
NR-85
NR-85
NR-80
NR-80
NR-80

70
70 70

NR-75
NR-75
NR-75
NR-70
NR-70
NR-70
NR-65
NR-65
NR-65

60
60 60

NR-60
NR-60
NR-60

50
50 50

NR-55
NR-55
NR-55
NR-50
NR-50
NR-50

40
40 40

NR-45
NR-45
NR-45
NR-40
NR-40
NR-40

30
30 30

NR-35
NR-35
NR-35

125
125125

NR-30
NR-30
NR-30

250
500
1000 2000
4000
8000
10002000
2000 4000
4000 8000
8000
250250 500500 1000

ARUN336BTE4, ARUN360BTE4,
ARUN312BTE4,ARUN312DTE4
ARUN312DTE4
ARUN312BTE4,
ARUN336DTE4,
ARUN360DTE4

Sound Power Level (0dB = 10E-6Pa)


Sound
SoundPower
PowerLevel
Level(0dB
(0dB==10E-6Pa)
10E-6Pa)
40

30

NR-30
NR-30
NR-30

100
100

20

80
80

NR-85
NR-85
NR-85
NR-80
NR-80
NR-80
NR-75
NR-75
NR-75

70
70

NR-70
NR-70
NR-70
NR-65
NR-65
NR-65

60
60

NR-60
NR-60
NR-60
NR-55
NR-55
NR-55
NR-50
NR-50
NR-50
NR-45
NR-45
NR-45
NR-40
NR-40
NR-40
NR-35
NR-35
NR-35

50
50

40
40

30
30

2020

125
125

250
250

500
500

1000 2000
2000
1000

400
4000

OctaveBand
BandCenter
CenterFrequency
Frequency(Hz)
(Hz)
Octave

ARUN336BTE4, ARUN360BTE
ARUN360BT
ARUN336BTE4,
ARUN336DTE4, ARUN360DTE
ARUN360DT
ARUN336DTE4,
100
100

80 80

NR-85
NR-85
NR-80
NR-80

3030

NR-40
NR-40
NR-35
NR-35

NR-80
NR-80
NR-75
NR-75

7070

70 70

NR-75
NR-75
NR-70
NR-70
NR-70
NR-70
NR-65
NR-65

6060

60 60

NR-65
NR-65
NR-60
NR-60
NR-60
NR-60
NR-55
NR-55

5050

50 50

NR-55
NR-55
NR-50
NR-50
NR-50
NR-50
NR-45
NR-45

4040

40 40

8080

125
125
125

PRODUCT DATA

NR-75
NR-75
NR-70
NR-70

6060

NR-65
NR-65
NR-60
NR-60

5050

NR-55
NR-55
NR-50
NR-50

4040

NR-45
NR-45

3030

NR-35
NR-35

NR-35
NR-35
NR-30
NR-30

125
125

250
250

500
500

1000 2000
2000
1000

4000 8000
8000
4000

OctaveBand
BandCenter
CenterFrequency
Frequency(Hz)
(Hz)
Octave

ARUN384BTE4, ARUN384DTE4
ARUN408BTE4, ARUN408DTE4

90

90
NR-90
NR-90

70

60

50

40

30

20

NR-85
NR-85
NR-80
NR-80

70

NR-75
NR-75
NR-70
NR-70

60

NR-65
NR-65
NR-60
NR-60

50

NR-55
NR-55
NR-50
NR-50

40

NR-45
NR-45

20

NR-90

80

NR-85
NR-80

70

NR-75
NR-70

60

NR-65
NR-60

50

NR-55
NR-50

40

NR-45

NR-40
NR-40

30

NR-35
NR-35

NR-40

30

NR-35

NR-30
NR-30

125
125

250
250

500
1000 2000
4000
8000
500
1000 2000
4000
8000

Octave Band Center Frequency (Hz)


Octave Band Center Frequency (Hz)

6060

5050

4040

3030

NR-30

20

125

250

500

1000

2000

4000

8000

Octave Band Center Frequency (Hz)

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

2020

125
125

250
250

500
500

1000 2000
2000
1000

400
4000

OctaveBand
BandCenter
CenterFrequency
Frequency(Hz)
(Hz)
Octave

100

80

7070

NR-30
NR-30

2020

125
250
500 1000
1000 2000
2000 4000
4000 8000
8000NR-30
125
250
500
125 250250 500500 1000
1000 2000
2000 4000
4000 8000
8000
125
Octave
BandCenter
CenterFrequency
Frequency
(Hz)
Octave
Band
(Hz)

Octave
Band
Center
Frequency
(Hz)
Octave
Band
Center
Frequency
(Hz)

80

8080

NR-40
NR-40

ARUN336BTE4,ARUN360BTE4,
ARUN360BTE4,
ARUN336BTE4,
ARUN336DTE4,ARUN360DTE4
ARUN360DTE4
ARUN336DTE4,

NR-30
NR-30
NR-30

250
500
1000 2000
4000
8000
250
500
1000 2000
4000
8000
250
500
1000 2000
4000
8000

NR-80
NR-80

7070

NR-30

20 20

NR-85
NR-85

NR-45
NR-45
NR-40
NR-40

30 30
2020

9090
NR-90
NR-90

NR-90
NR-90
NR-85
NR-85

8080

90

Octave Band Center Frequency (Hz)


Octave Band Center Frequency (Hz)
Octave Band Center Frequency (Hz)

94

4000 8000
8000
4000

100
100

100
100

90
90

20
20

1000 2000
2000
1000

NR-90
NR-90

NR-90
NR-90
NR-90

50

500
500

9090

Octave Band Center Frequency (Hz)


Octave
Band
Center
Frequency
(Hz)
Octave
Band
Center
Frequency
(Hz)

60

250
250

ARUN313BTE4,
ARUN337BTE4,
ARUN312BTE4,ARUN312DTE4
ARUN312DTE4
ARUN312BTE4,
ARUN313DTE4, ARUN337DTE4

ARUN288BTE4
ARUN288DTE4
ARUN288BTE4
, ,ARUN288DTE4
ARUN240BTE4,
ARUN264BTE4,
ARUN240BTE4,
ARUN264BTE4,
ARUN240DTE4,
ARUN264DTE4
ARUN240DTE4,
ARUN264DTE4
100
100
90 90

80
80 80

70

125
125

OctaveBand
BandCenter
CenterFrequency
Frequency(Hz)
(Hz)
Octave

9090
NR-90
NR-90
NR-90

80

NR-30
NR-30

2020

4000 8000
8000
4000

100100

90
90 90

20
20 20

250
250

OctaveBand
BandCenter
CenterFrequency
Frequency(Hz)
(Hz)
Octave

Octave Band Center Frequency (Hz)

90

8000
8000
00

NR-65
NR-65

NR-75
NR-75

NR-30

NR-90
NR-90
NR-90

NR-60
NR-60
NR-60
NR-55
NR-55
NR-55
NR-50
NR-50
NR-50
NR-45
NR-45
NR-45
NR-40
NR-40
NR-40
NR-35
NR-35
NR-35

6060

7070

NR-40
NR-40

30

100

NR-70
NR-70
NR-70
NR-65
NR-65
NR-65

NR-70
NR-70

8080

NR-40

NR-85
NR-85
NR-85
NR-80
NR-80
NR-80
NR-75
NR-75
NR-75

NR-75
NR-75

NR-80
NR-80

Sound Power Level (0dB = 10E-6Pa)


Sound Power Level (0dB = 10E-6Pa)

NR-55
NR-55
NR-55
NR-50
NR-50
NR-50

7070

NR-85
NR-85

Sound Power Level (0dB = 10E-6Pa)


Sound Power Level (0dB = 10E-6Pa)

NR-60
NR-60
NR-60

NR-80
NR-80

Sound Power Level (0dB = 10E-6W/m 2 )

NR-70
NR-70
NR-70
NR-65
NR-65
NR-65

8080

NR-85
NR-85

Sound Power Level (0dB = 10E-6Pa)


Sound Power Level (0dB = 10E-6Pa)

NR-75

8080

Sound Power Level (0dB = 10E-6Pa)


Sound
Power
Level
= 10E-6Pa)
Sound
Power
Level
(0dB(0dB
= 10E-6Pa)
Sound Power Level (0dB = 10E-6Pa)

NR-75
NR-75
NR-75

9090
NR-90
NR-90

Sound Power Level (0dB = 10E-6Pa)


Sound Power Level (0dB = 10E-6Pa)

NR-80

70

Sound Power Level (0dB = 10E-6Pa)


Sound Power Level (0dB = 10E-6Pa)

Sound Power Level (0dB = 10E-6W/m 2 )

NR-85

Sound Power Level (0dB = 10E-6Pa)


Sound
SoundPower
PowerLevel
Level(0dB
(0dB==10E-6Pa)
10E-6Pa)

NR-80
NR-80
NR-80

9090
NR-90
NR-90

NR-90
NR-90
NR-90
NR-85
NR-85
NR-85

9090

Sound Power Level (0dB = 10E-6Pa)


Sound Power Level (0dB = 10E-6Pa)

44

MULTI V IV Outdoor Unit Engineering Manual

NR-90

80

ACOUSTIC DATA
Sound Power Levels - Heat Pump / Heat Recovery

Heat Pump Sound Power Levels, continued


ARUN456BTE4, ARUN480BTE4, ARUN504BTE4
ARUN456DTE4, ARUN480DTE4, ARUN504DTE4

ARUN432BTE4, ARUN432DTE4

100
100

90
90

NR-90

80

Sound Power Level (0dB = 10E-6W/m 2 )

Sound Power Level (0dB = 10E-6W/m2 )

NR-90
NR-85
NR-80

70

NR-75
NR-70

60

NR-65
NR-60

50

NR-55
NR-50

40

80

NR-85
NR-80

70

NR-75
NR-70

60

NR-65
NR-60

50

NR-55
NR-50

40

NR-45

NR-45

NR-40

NR-40

30

30

NR-35

20

125

250

500

1000

2000

4000

NR-35
NR-30

NR-30

20

8000

125

250

500

1000

2000

4000

8000

Octave Band Center Frequency (Hz)

Octave Band Center Frequency (Hz)

ARUB096BTE4, ARUB121BTE4,
ARUB096DTE4, ARUB121DTE4

ARUB072BTE4, ARUB072DTE4
100

ARUB144BTE4, ARUB145BTE4, ARUB168BTE4,


ARUB144DTE4, ARUB145DTE4, ARUB168DTE4

100

90

100

90

90

NR-90

NR-90

80

NR-80

70

NR-75
NR-70

60

NR-65
NR-60

50

NR-55
NR-50

40

NR-45

NR-80

70

NR-75
NR-70

60

NR-65
NR-60

50

NR-55
NR-50

40

NR-45

NR-40

30

30

NR-35

125

250

500

1000

2000

4000

NR-85
NR-80

70

NR-75
NR-70

60

NR-65
NR-60

50

NR-55
NR-50

40

NR-45

NR-40

NR-40

30

NR-35

NR-30

20

NR-90

80

NR-85

Sound Power Level (0dB = 10E-6Pa)

NR-85

Sound Power Level (0dB = 10E-6Pa)

Sound Power Level (0dB = 10E-6Pa)

80

NR-35

NR-30

20

8000

125

Octave Band Center Frequency (Hz)

250

500

1000

2000

4000

NR-30

20

8000

125

Octave Band Center Frequency (Hz)

ARUB169BTE4, ARUB169DTE4

Product Data

Heat Recovery Sound Power Levels

250

500

1000

2000

4000

8000

Octave Band Center Frequency (Hz)

ARUB192BTE4, ARUB192DTE4

ARUB240BTE4, ARUB264BTE4,
ARUB240DTE4, ARUB264DTE4

ARUB216BTE4, ARUB216DTE4

100

100

100

100

90

90

90

NR-75
NR-70

60

NR-65
NR-60

50

NR-55
NR-50

40

NR-45

NR-80

70

NR-75
NR-70

60

NR-65
NR-60

50

NR-55
NR-50

40

NR-45

NR-40

30

NR-35

30

NR-35

250

500

1000

2000

4000

8000

NR-80

70

NR-75
NR-70

60

NR-65
NR-60

50

NR-55
NR-50

40

NR-45

125

250

500

1000

2000

4000

8000

30

NR-35

20

125

250

500

1000

2000

4000

8000

NR-7

NR-7

60

NR-6

NR-6

50

NR-5

NR-5

40

NR-4

NR-4

30

NR-3

NR-3

20

Octave Band Center Frequency (Hz)

Due to our policy of continuous product innovation, some specifications may change without notification.
ARUB312DTE4
ARUB288DTE4
Electronics U.S.A., Inc.,
Englewood Cliffs, NJ. All rights reserved. LGARUB312BTE4,
is a registered trademark
of LG Corp.
LGARUB288BTE4,
100

NR-8

70

NR-30

Octave Band Center Frequency (Hz)

Octave Band Center Frequency (Hz)

NR-8

NR-40

NR-30

20

NR-9

80

NR-85

NR-40

NR-30

125

80

NR-85

Sound Power Level (0dB = 10E-6Pa)

NR-80

80

NR-90

Sound Power Level (0dB = 10E-6Pa)

NR-85

70

20

90

NR-90

Sound Power Level (0dB = 10E-6Pa)

Sound Power Level (0dB = 10E-6W/m 2 )

NR-90

80

100

125

250

500

1000

2000

4000

Octave Band Center Frequency (Hz)

ARUB336BTE4, ARUB360BTE4,
ARUB336DTE4,
PRODUCT DATAARUB360DTE4
| 95
100

8000

NR-70

ACOUSTIC DATA
60

NR-65
NR-60

50

NR-55

Sound Power Levels - Heat Recovery

NR-50

40

NR-45

NR-80

70

NR-75
NR-70

60

NR-65
NR-60

50

NR-55
NR-50

40

NR-45

NR-40

30

30

NR-35

125

250

500

1000

2000

4000

Octave Band Center Frequency (Hz)


Heat Recovery Sound Power Levels, continued

MULTI V IV Outdoor Unit Engineering Manual

NR-65
NR-60
NR-60
NR-55
NR-55
NR-50
NR-50
NR-45
NR-45
NR-40

NR-50
NR-55
NR-45
NR-50
NR-40
NR-45
NR-35
NR-40

60

NR-70
NR-65

20

20

NR-65
NR-60
NR-60
NR-55
NR-55
NR-50
NR-50
NR-45

1000

2000

4000

125

250

500

1000

2000

4000

Frequency
125Octave
250Band Center
500
1000
2000 (Hz)4000

NR-80

70

NR-75
NR-70

60

NR-65
NR-60

50

NR-55
NR-50

40

20

NR-45

NR-80

70

NR-75
NR-70

60

NR-65
NR-60

50

NR-55
NR-50

40

NR-45

30

NR-35

125

250

500

1000

2000

4000

20

8000

125

250

500

1000

2000

4000

8000

NR-90

Octave Band Center Frequency (Hz)

100

90

NR-90
NR-85

90

NR-75
NR-80

70

NR-70
NR-75

60

NR-65
NR-70

60

NR-60
NR-65

50

NR-55
NR-60

50
40

NR-50
NR-55

40
30

NR-40
NR-45
NR-35
NR-40

30
20

NR-30
NR-35

NR-45
NR-50

125

250

500

1000

2000

4000

250

500

1000

2000

4000

80

NR-85
NR-80

70

NR-75
NR-70

60

NR-65
NR-60

50

NR-55
NR-50

40

NR-40

30

NR-30

20

NR-85
NR-80

70

NR-75
NR-70

60

NR-65
NR-60

50

NR-55
NR-50

40

NR-45
NR-40

30

NR-35

NR-35

NR-30

8000

80

NR-45

8000

Octave Band Center Frequency (Hz)


125

NR-90
NR-90

125

250

500

1000

2000

4000

NR-30

20

125

250

500

1000

2000

4000

8000

8000

Octave Band Center Frequency (Hz)

ARUB456BTE4, ARUB480BTE4, ARUB504BTE4


ARUB456DTE4, ARUB480DTE4, ARUB504DTE4
100

90
NR-90

80

NR-85
NR-80

70

NR-75
NR-70

60

NR-65
NR-60

50

NR-55
NR-50

40

NR-45
NR-40

30

NR-35
NR-30

125

250

500

1000

2000

4000

8000

Octave Band Center Frequency (Hz)

PRODUCT DATA

NR-80

NR-75

NR-70

60

NR-65

NR-60

50

NR-55

NR-50

40

NR-45

NR-40

30

NR-35

NR-30

125

250

500

1000

2000

4000

Octave Band Center Frequency (Hz)

ARUB432BTE4, ARUB432DTE4

100

NR-90

NR-85

70

20

8000

Octave Band Center Frequency (Hz)

Sound Power Level (0dB = 10E-6W/m2 )

4000

NR-30

ARUB384BTE4, ARUB384DTE4
ARUB408BTE4, ARUB408DTE4

NR-80
NR-85

2000

NR-40

NR-35

Octave Band Center Frequency (Hz)

96

1000

80

NR-85

Octave Band Center Frequency (Hz)

8000

70

20

500

90

NR-30

8000 NR-30

80

20

250

100

80

NR-85

30

NR-35
NR-30

80

NR-30

NR-30

125

NR-90

90

8000

NR-35

Octave Band Center Frequency (Hz)

NR-40

NR-40
NR-35

90

8000

NR-45

ARUB336BTE4, ARUB360BTE4,
ARUB336DTE4, ARUB360DTE4

100

NR-30
NR-35

NR-50

20

8000

90

NR-45
NR-40

Octave Band Center


Frequency (Hz)
ARUB336BTE4,
ARUB360BTE4,
ARUB336DTE4, ARUB360DTE4
ARUB336BTE4,
ARUB360BTE4,
100
ARUB336DTE4, ARUB360DTE4

Sound Sound
Power Power
Level (0dB
10E-6Pa)
Level=(0dB
= 10E-6Pa)

NR-55
NR-60

NR-75
NR-70

30

NR-90
NR-85

NR-60
NR-65

70

30

NR-90

NR-65
NR-70

NR-80
NR-75

40

4
4

NR-70
NR-75

70

40

8000

NR-75
NR-80

NR-85
NR-80

50

8000
NR-30

NR-80
NR-85

NR-85

50

NR-35
NR-30

500

100

80

NR-90

60

NR-40
NR-35

250

ARUB312BTE4, ARUB312DTE4

ARUB288BTE4, ARUB288DTE4

Sound Power Level (0dB = 10E-6W/m 2 )

NR-70
NR-65

NR-55

40

Octave Band Center Frequency (Hz)

100

Sound Power Level (0dB = 10E-6W/m2 )

NR-75
NR-70

NR-60

50

NR-90

80

Sound
Power
Level
(0dB(0dB
= 10E-6Pa)
Sound
Power
Level
= 10E-6Pa)

NR-80
NR-75

125

NR-90

80

NR-85

NR-85
NR-80

NR-65

NR-40

Sound Power Level (0dB = 10E-6Pa)

NR-90

NR-90

NR-70

60

30

NR-35

20

8000

90

90
90

NR-75

NR-30

Sound Power Level (0dB = 10E-6Pa)

100
100

ARUB240BTE4, ARUB264BTE4,
ARUB240BTE4, ARUB264BTE4,
ARUB240DTE4, ARUB264DTE4
ARUB240DTE4, ARUB264DTE4

Sound Power Level (0dB = 10E-6Pa)

4
4

NR-80

70

NR-40

NR-30

20

Sound Power Level (0dB = 10E-6Pa)

NR-75

Sound Power Level (0dB = 10E-6Pa)

Sound Power Level (0dB = 10E-6Pa)

NR-80

70

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

8000

OUTDOOR UNIT ACCESSORIES

Air Guides

(PRAGX2S0 and PRAGX3S0)


Optional air guides are available for Multi V IV outdoor units to change the discharge direction from vertical to
horizontal.
Use PRAGX2SO air guides with the following models:
ARUN072BTE4, ARUN072DTE4, ARUB072BTE4, ARUB072DTE4.
Use PRAGX3SO air guides with the following models:
ARUN096BTE4, ARUN121BTE4, ARUN144BTE4, ARUN145BTE4, ARUN168BTE4, ARUN169BTE4,
ARUN096DTE4, ARUN121DTE4, ARUN144DTE4, ARUN145DTE4, ARUN168DTE4, ARUN169DTE4
ARUB096BTE4, ARUB121BTE4, ARUB144BTE4, ARUB145BTE4, ARUB168BTE4, ARUB169BTE4,
ARUB096DTE4, ARUB121DTE4, ARUB144DTE4, ARUB145DTE4, ARUB168DTE4, ARUB169DTE4

Multi V Hail Guard Kits

Figure 5: Air Guide.

Figure 6: Hail Guard Kit.

(ZHGDKA01A and ZHGDKA04A)

Product Data

Optional hail guard kits help protect the heat exchangers in Multi V IV outdoor units.
Each kit includes:
Right wind baffle
Left wind baffle
Rear wind baffle
(50) #10 x 1/2 self-drilling hex head screws
Use ZHGDKA01A with the following Multi V IV models:
6-ton Outdoor Units ARUN072BT4, ARUN072DT4, ARUB072BT4, ARUB072DT4
Use ZHGDKA04A with the following Multi V IV models:
8-ton to 14-ton Outdoor Units ARUN096BTE4, ARUN096DTE4, ARUN121BTE4,
ARUN121DTE4, ARUN144BTE4, ARUN144DTE4, ARUN145BTE4, ARUN145DTE4, ARUN168BTE4, ARUN168DTE4, ARUN169BTE4,
ARUN169DTE4
ARUB096BTE4, ARUB096DTE4, ARUB121BTE4, ARUB121DTE4, ARUB144BTE4, ARUB144DTE4, ARUB145BTE4, ARUB145DTE4,
ARUB168BTE4, ARUB168DTE4, ARUB169BTE4, ARUB169DTE4
See submittals at www.lg-vrf.com to verify how many kits are needed for each combination frame.

ARUN145BTE4-DTE4 / ARUB145BTE4-DTE4, ARUN169BTE4-DTE4 / ARUB169BTE4-DTE4 frames are ONLY for use in large capacity
triple frame combinations. They cannot be used as stand alone models or in a dual frame combination. These frames ARE NOT interchangeable with ARUN144BTE4-DTE4 / ARUB144BTE4-144DTE4, ARUN168BTE4-DTE4 / ARUB168BTE4-144DTE4 single frame models.

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

PRODUCT DATA

97

OUTDOOR UNIT ACCESSORIES

Low Ambient Baffle Kits

Figure 7: ZLABKA01A Low Ambient Kit for 6-ton Outdoor Units


Top Discharge Elbow

(ZLABKA01A and ZLABKA03A)

Top Discharge Elbow

Use ZLABKA01A with the following Multi V IV models:


6-ton Outdoor Units ARUN072BT4, ARUN072DT4, ARUB072BT4,
ARUB072DT4

Side Wind Baffle

Front View

Top Discharge Elbow

PRODUCT DATA

Side Wind Baffle

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

Side Wind Baffle

Top Discharge Elbow

Side Wind Baffle

ARUN145BTE4-DTE4 / ARUB145BTE4-DTE4, ARUN169BTE4DTE4 / ARUB169BTE4-DTE4 frames are ONLY for use in large
capacity triple frame combinations. They cannot be used as stand
alone models or in a dual frame combination. These frames ARE
NOT interchangeable with ARUN144BTE4-DTE4 / ARUB144BTE4144DTE4, ARUN168BTE4-DTE4 / ARUB168BTE4-144DTE4 single
frame models.

98

Side View

Figure 8: ZLABKA03A Low Ambient Kit for 8-ton to 14-ton Outdoor Units

Use ZLABKA03A with the following Multi V IV models:


8-ton to 14-ton Outdoor Units ARUN096BTE4, ARUN096DTE4,
ARUN121BTE4, ARUN121DTE4, ARUN144BTE4, ARUN144DTE4,
ARUN145BTE4, ARUN145DTE4, ARUN168BTE4, ARUN168DTE4,
ARUN169BTE4, ARUN169DTE4,
ARUB096BTE4, ARUB096DTE4, ARUB121BTE4, ARUB121DTE4,
ARUB144BTE4, ARUB144DTE4, ARUB145BTE4, ARUB145DTE4,
ARUB168BTE4, ARUB168DTE4, ARUB169BTE4, ARUB169DTE4
See submittals at www.lg-vrf.com to verify how many kits are needed
for each combination frame.

Side Wind Baffle

Each kit includes:


Right wind baffle
Left wind baffle
Rear wind baffle
Top discharge elbow with motorized damper and 24V damper
actuator
(50) #10 x 1/2 self-drilling hex head screws
Sealtite connector (for routing of actuator control and power wiring
down to outdoor unit electrical box)
PRVC2 Control kit is a required accessory (sold separately)

Side Wind Baffle

MULTI V IV Outdoor Unit Engineering Manual

Optional low ambient baffle kits allow for Multi V IV outdoor unit
operation down to -9.9F in cooling mode. Can be applied to heat
pump and heat recovery systems. When used with heat recovery
systems, low ambient cooling to -9.9F is possible only when all
indoor units are operating in cooling mode. Does not impact synchronous operating range.

OUTDOOR UNIT ACCESSORIES

Table 31: Summary DataSpeciality Application Devices


Speciality Application
Device

Name

Model No.

Simple Dry Contact

PQDSB1

Dry Contact for


Economizer, occupied/
unoccupied

PQDSBC1

Dry Contact Unit for


24V Thermostat

PDRYCB300

Digital Output
(DO) Kit

PEXPMB000

Application

Indoor
Unit

On/Off, Run Status,


Error Status
On/Off, Mode,
Controller Lock, Power
Save, Run Status,
Error Status
On/Off, Thermo On/
Off, Mode, Fan Speed,
Run Status, Error
Status

Comm
Bus

On/Off

Third party equipment


AC
control. Allows system
Smart IV
expansion through
and
Digital and Analog
ACP IV
inputs and outputs.

Binary
Signals
Input/
Output

Description

1/2

Enables the indoor unit to be


controlled and monitored by third
party controls using binary inputs
and outputs.

2/2

---

Enables the indoor unit to be


controlled and monitored by a third
party thermostat or controller.

0/1

One 25A DPST normally open relay.


Used with central controller to control
third party device manually or by
schedule.

---

3 Digital Inputs: Dry Contact input only


3 Digital Outputs: Max. 2A@30VAC/DC
4 Analog Outputs: 0 to 10 VDC,
configurable; 0 to 20 mA, configurable
4 Universal Inputs individually
configurable as analog or digital:
Analog: Voltage. Current. Thermistor
(NTC, PT, Ni)
Digital for Dry Contact input only

Indoor
Unit

Third party
supplemental heat
control

0/1

Adds coordinated control of an


external heater with normal heat
pump operations.

PRARH1

Indoor
Unit

Third party
supplemental heat
control

0/2

Adds coordinated control of an


external heater with normal heat
pump operations.

Power Distribution
Indicator (PDI)
Premium

PQNUD1S41

Comm
Bus

Energy
consumption
monitoring

8 Watt
Node
Meters

Monitors total outdoor unit power


consumption for up to eight systems,
and distributes per indoor unit based
on weighted calculation.

Mode Selector Switch

PRDSBM

Outdoor
Unit

Multi V Heat
Pump Only

---

Locks outdoor unit into Heat,


Cool, or Fan Mode.

Auxiliary Heater
Relay Kit

Auxiliary Two-Stage
Heater Relay Kit

PRARH0
PRARS0

Before specifying or placing an order, refer to the V-Net Network Solution Engineering Product Data Book and review the detailed technical data provided to fully understand the capabilities and limitations of these
devices.
For information on controller compatibility refer to the Controls and Options Table on page 38.

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

PRODUCT DATA

99

Product Data

I/O Module

PQNFP00T0

Connect
to

OUTDOOR UNIT ACCESSORIES

MULTI V IV Outdoor Unit Engineering Manual

Table 32: Summary DataCentral Controllers (connect to the outdoor unit terminals Internet A, Internet B)
No. of Binary
Devices Systems Devices Comm
Central
Power,
Name
Model No.
per
per Comm per Comm Bus Signals
Controller
Input/
Conn
Controller
Bus
Bus
Ports Output

AC Smart IV

PACS4B000

128

16

128

2 DI /
2 DO

AC Ez

PQCSZ250S0

32

16

256

---

Advanced
Control
Platform IV
(ACP IV)

PACP4B000

256

16

64

10/4

Description

Monitors / operates indoor units


through a touch screen. Manages
up to 128 devices. Advanced
functions include programmable
schedules, temperature setpoint
range lock, remote controller lock,
run time limit, manual control and
24 VAC
scheduling of digital output kit,
peak/demand control, visual floor
plan navigation, web access,
operation and error history log, one
digital input and two digital outputs
for device interlocking and error
e-mail notification.

12 VDC,
ODU

Provides for scheduling in addition


to basic indoor unit control and
monitoring.

Provides for scheduling, remote


controller lock, setpoint range limit,
web access, peak/demand control,
24 VAC PDI integration, and AC Manager
Plus integration advanced
functionality in addition to basic unit
control and monitoring.

Before specifying or placing an order, refer to the V-Net Network Solution Engineering Product Data Book and review the detailed technical data provided to fully understand the capabilities and limitations of these devices.
For information on controller compatibility refer to the Controls and Options Table on page 38.

Table 33: Summary DataIntegration Solutions (connect to outdoor unit terminals Internet A, Internet B)
No. of
Devices Systems
Devices Comm
Integration
per
Name
Model No.
per
per Comm
Power
Solution
Bus
Controller Comm
Bus
Bus
Ports

Binary
Signals
Input/
Output

ACP IV
BACnet
Gateway*

PQNFB17C1

256

16

256

24 VAC

10/4

LonWorks
Gateway*

PLNWKB100

64

16

64

24 VAC

2/2

Description

Allow integration of LG equipment


for control and monitoring by open
protocol BACnet and LonWorks
building automation and controls
systems.*

Before specifying or placing an order, refer to the V-Net Network Solution Engineering Product Data Book and review the detailed technical data provided to fully understand the capabilities and limitations of these devices.
For information on controller compatibility refer to the Controls and Options Table on page 38.
* BACnetTM is a trademark of ASHRAE; LonWorksTM is a trademark of Echlelon Corporation.

100

PRODUCT DATA

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

OUTDOOR UNIT ACCESSORIES

LG Monitoring View (LGMV) Diagnostic Software and Cable


(PRCTSL1 and PRCTFE1)

Product Data

LGMV software allows the service technician or commissioning agent to connect a computer USB port
to the outdoor unit main printed circuit board (PCB) using an accessory cable without the need for a
separate interface device. The main screen for LGMV shall allow user to view the following real time data
on one screen:
Actual inverter compressor speed
temperature
Software
version
Target inverter compressor speed
Front outdoor coil pipe temperature
Installer
Actual outdoor fan speed
Back outdoor coil pipe temperature
name
Target outdoor unit fan speed
Liquid line pipe temperature
Model
number of outdoor units
Actual superheat
Subcooler inlet temperature
Site
name
Target superheat
Subcooler outlet temperature
Actual subcooler circuit superheat
Average indoor unit (IDU) pipe temperature Total number of connected indoor units
Communication indicator lights
Target subcooler circuit superheat
Inverter compressor operation indicator
Indoor unit capacity
light
Main EEV position
Indoor unit operating mode
Four-way
reversing
valve
operation
Subcooling EEV position
indicator
light
Indoor unit fan speed
Inverter compressor current transducer
Pressure graph showing actual low pres Indoor unit EEV position
value
sure and actual high pressure levels
Indoor unit room temperature
Outdoor air temperature
Indoor unit inlet pipe temperature
Actual high pressure/saturation temperature Error code display
Indoor unit outlet pipe temperature
Actual low pressure/saturation temperature Operating mode indicator
Target high pressure
Indoor unit error code
Suction temperature
Inverter compressor discharge temperature Target low pressure
PCB (printed circuit board) version
Constant speed compressor discharge
Additional screens can be accessed by tabs on the main screen:
1. Cycleview: Graphic of internal components including:
Compressors showing actual speeds
Temperature and pressure sensors
EEVs
Four-way reversing valve
IDUs
Outdoor fans showing status and speeds
Liquid injection valves
2. Graph: Full screen graph of actual high and low pressures and high and low pressure limits. A sliding bar enables user to go back in time and view data.
3. Control IDU: Enables user to turn on all IDUs default setpoints of 86F in heat mode or 64F in cool
mode.
Figure 9: MV Cycleview.
4. Setting: Converts metric values to imperial values.
5. Making Data: Recording of real time data to a separate file created to be stored on the users computer.
6. Loading Data: Recorded data from a saved .CSV file can be loaded to create an LGMV session.
7. Electrical Data: The lower half of main screen is changed to show the following:
Inverter compressor
Constant compressor
- Amps
- Current transducer value
- Volts
- Phase
- Power Hz
- Inverter control board fan Hz
The software is available in a high version with all of the features listed above. The low version has all features as the high version without
Target High Pressure and Target Low Pressure values shown on main screen.
In lieu of connecting to the ODU, user has the option to connect to IDU with the use of a USB to RS-485 connector kit. When connected
through IDU, user will not be able to record data.
This software can be used to both commission new systems and troubleshoot existing systems. LGMV data can be recorded to a .CSV file
and emailed to an LG representative to assist with diagnostic evaluations.

Recommended Minimum PC Configuration:

CPU: Pentium IV 1.6 GHz


Operating System: Windows NT/2000/XP/Vista
Main Memory: 256 MB

Hard Disk: 600 MB when operating


Web Browser: Internet Explorer 5.0

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

PRODUCT DATA

101

INDOOR UNIT QUICK REFERENCE

Table 34: Summary DataWall-Mounted / Ceiling Cassette Indoor Units.


Unit/Type

Wall MountedART COOLTM


Mirror

MULTI V IV Outdoor Unit Engineering Manual

Wall MountedStandard

Ceiling CassetteOne Way

ARNU*****

053 SBR4
073 SBR4
093 SBR4
123 SBR4
153 SBR4
183 SCR4
243 SCR4
053 SBL4
073 SBL4
093 SBL4
123 SBL4
153 SBL4
183 SCL4
243 SCL4
073 TUC4
093 TUC4
123 TUC4
183 TTC4

Ceiling CassetteTwo Way

243 TTC4
183 TLC4
243 TLC4

Ceiling CassetteFour Way


(2' x 2')

Ceiling CassetteFour Way


(3' x 3')

053 TRC4
073 TRC4
093 TRC4
123 TRC4
153 TQC4
183 TQC4
243 TPC4
283 TPC4
073 TNA4
093 TNA4
123 TNA4
153 TNA4
183 TNA4
243 TNA4
363 TNC4
243 TMA4
283 TMA4
363 TMA4
423 TMC4
483 TMC4

2
3

102

PRODUCT DATA

Cooling3 Heating3

35-1/4 x 8-1/8 x 11-7/16

40-9/16 x 9-11/16 x 12-13/16

35-1/4 x 8-15/16 x 11-7/16

40-5/16 x 9-7/8 x 12-13/16


Body: 33-7/8 x 17-3/4 x 6-11/16
Panel: 43-5/16 x 19-3/4 x 1-3/8
Body: 46-1/2 x 17-3/4 x 6-7/8
Panel: 55-15/16 x 19-3/4 x 1-3/8
Body: 32-11/16 x 21-5/8 x 8-7/8
Panel: 41-5/16 x 25-3/16 x 1-5/8

Body: 22-7/16 x 22-7/16 x 8-7/16


Panel: 27-9/16 x 27-9/16 x 7/8
Body: 22-7/16 x 22-7/16 x 10-3/32
Panel: 27-9/16 x 27-9/16 x 7/8
Body: 33-1/16 x 33-1/16 x 8
Panel: 37-3/8 x 37-3/8 x 1-7/16

Body: 33-1/16 x 33-1/16 x 9-11/16


Panel: 37-3/8 x 37-3/8 x 1-7/16

Body: 33-1/16 x 33-1/16 x 11-5/16


Panel: 37-3/8 x 37-3/8 x 1-7/16

All indoor units require 208230V/60Hz/1Ph and an AWG18-2 communication cable.


Model number shows nominal capacity and frame size designator.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80F dry bulb (DB) and
67F wet bulb (WB) and outdoor ambient conditions of 95F dry bulb (DB) and 75F wet bulb (WB).
1

Nominal Capacity
Btu/h

Dimensions
(W x D x H)
(inches)

Air Flow Rate


(CFM)
(H/M/L4)

5,500
7,500
9,600
12,300
15,400
19,100
24,200
5,500
7,500
9,600
12,300
15,400
19,100
24,200
7,500

6,100
8,500
10,900
13,600
17,100
21,500
27,300
6,100
8,500
10,900
13,600
17,100
21,500
27,300
8,500

230/212/194
247/230/194
290/247/194
336/290/230
371/318/247
441/424/399
494/449/406
1,120/1,080/1,050
1,190/1,120/1,050
1,260/1,190/1,050
1,420/1,260/1,120
1,550/1,350/1,190
1,120/1,050/980
1,280/1,140/1,000
290/258/226

9,600

10,900

325/304/290

12,300

13,600

353/325/290

19,100

21,500

470/427/385

24,200

24,200

515/470/406

19,100

21,500

459/424/353

24,200

27,300

601/530/459

5,500
7,500
9,600
12,300
15,400
19,100
24,200
28,000
7,500
9,600
12,300
15,400
19,100
24,200
36,200
24,200
28,000
36,200
42,000
48,100

6,100
8,500
10,900
13,600
17,100
21,500
27,300
31,500
8,500
10,900
13,600
17,100
21,500
27,300
40,600
27,300
31,500
40,600
43,800
51,200

265/247/212
265/247/212
283/265/251
307/283/247
388/353/328
396/388/353
600/530/459
671/565/494
459/424/388
477/424/388
494/459/424
530/459/424
565/530/424
742/671/600
883/777/706
777/706/635
812/741/635
918/812/706
1,059/918/812
1,130/953/883

Pipe
Weight Connections
(lbs.) (inches, O.D.)
(Liquid, Vapor)
24

34

22

31

1/4, 1/2

3/8, 5/8

1/4, 1/2

3/8, 5/8

Body: 33
Panel: 10

1/4, 1/2

Body: 42
Panel: 13

3/8, 5/8

Body: 49
Panel: 11
Body: 29
Panel: 7
Body: 32
Panel: 7
Body: 35
Panel: 7
Body: 48
Panel: 13

Body: 54
Panel: 13

1/4, 1/2
3/8, 5/8

1/4, 1/2

3/8, 5/8

Body: 59
Panel: 13

Nominal heating capacity rating obtained with air entering the indoor unit at 70F dry bulb (DB) and 60
F wet bulb (WB) and outdoor ambient conditions of 47F dry bulb (DB) and 43F wet bulb (WB).
4
H/M/L = High/Medium/Low

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

INDOOR UNIT QUICK REFERENCE

Table 35: Summary DataRecessed Mounted Indoor Units.


Unit/Type

Ducted High Static

Ducted Low Static Built In

Vertical/Horizontal Air
Handling Unit

Dimensions
(W x D x H)
(inches)

7,500
9,600
12,300
15,400
19,100
24,200
28,000
36,200
42,000
48,100
54,000
76,400
95,900
7,500
9,600
12,300
15,400
19,100
24,000
7,500
9,600
12,300
15,400
19,100
24,200
12,000

8,500
10,900
13,600
17,100
21,500
27,300
31,500
40,600
43,800
51,200
61,400
86,000
107,500
8,500
10,900
13,600
17,100
21,500
27,300
8,500
10,900
13,600
17,100
21,500
27,300
13,500

441/406/332
452/406/332
477/427/332
487/417/293
537/487/417
671/537/487
915/851/770
1,141/1,024/894
1,218/1,141/1,084
1,568/1,395/1,183
1,819/1,678/1,395
2,050/1,766/1,766
2,542/2,260/2,260
270/230/200
320/250/200
360/310/250
450/360/310
530/450/360
710/570/430
283/229/194
318/247/212
353/283/229
388/353/283
494/424/353
600/530/353
530/480/380

183 NJA4

18,000

20,000

580/530/480

24,000
30,000
36,000
42,000
48,000
54,000

27,000
34,000
40,000
46,000
54,000
60,000

710/640/480
880/800/630
990/880/800
1,250/1,100/1,000
1,400/1,260/1,000
1,475/1,400/1,260

18 x 21-1/4 x 48-11/16

25 x 21-1/4 x 55-3/16

All indoor units require 208230V/60Hz/1Ph and an AWG18-2 communication cable.


Model number shows nominal capacity and frame size designator.
3
Nominal cooling capacity rating obtained with air entering the indoor unit at 80F dry bulb (DB) and
67F wet bulb (WB) and outdoor ambient conditions of 95F dry bulb (DB) and 75F wet bulb (WB).
2

Cooling3 Heating3

Air Flow Rate


(CFM)
(H/M/L4)

073 BGA4
093 BGA4
123 BGA4
153 BGA4
183 BGA4 46-1/2 x 17-3/4 x 11-3/4
243 BGA4
283 BGA4
363 BGA4
423 BGA4
483 BRA4
48-7/16 x 23-3/8 x 15
543 BRA4
763 B8A4
61-1/2 x 27-1/8 x 18-1/8
963 B8A4
073 L1G4
27-9/16 x 27-9/16 x 7-1/2
093 L1G4
123 L2G4
153 L2G4 35-7/16 x 27-9/16 x 7-1/2
183 L2G4
243 L3G4 43-5/16 x 27-9/16 x 7-1/2
073 B3G4
093 B3G4
32-5/8 x 22-5/8 x 7-1/2
123 B3G4
153 B3G4
183 B4G4
43-5/16 x 22-5/8 x 7-1/2
243 B4G4
123 NJA4
243 NJA4
303 NJA4
363 NJA4
423 NKA4
483 NKA4
543 NKA4

Nominal Capacity
Btu/h

Pipe
Max.
Weight Connections
ESP
(lbs.) (inches, O.D.) (inches)
(Liquid, Vapor)

84

0.62
3/8, 5/8

112
192

0.78
3/8, 3/4
3/8, 7/8

0.98

39
1/4, 1/2
51
60
46

57

0.19

3/8. 5/8

1/4, 1/2

0.15

3/8, 5/8
1/4, 1/2

117
121

1.0
3/8, 5/8

165

Nominal heating capacity rating obtained with air entering the indoor unit at 70F dry bulb (DB) and 60
F wet bulb (WB) and outdoor ambient conditions of 47F dry bulb (DB) and 43F wet bulb (WB).
4
H/M/L = High/Medium/Low

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

PRODUCT DATA

103

Product Data

Ducted Low Static

ARNU*****

INDOOR UNIT QUICK REFERENCE

Table 36: Summary DataSurface Mounted / Floor Standing Indoor Units.

Unit/Type

Ceiling Suspended

Dimensions
(W x D x H)
(inches)

ARNU****

183VJA2

Nominal Capacity
Btu/h
Cooling3 Heating3
19,100

21,500

Air Flow
Rate
(CFM)
(H/M/L4)
565/495/424

MULTI V IV Outdoor Unit Engineering Manual

37-7/16 x 8-11/16 x 25-5/8

Convertible Surface Mounted

243VJA2

24,200

27,300

636/565/495

093VEA2

9,600

10,900

268/243/219

12,300

13,600

325/268/244

073 CEA4

7,500

8,500

300/265/229

093 CEA4

9,600

10,900

335/300/265

12,300

13,600

371/335/300

15,400

17,100

406/353/335

19,100

21,500

565/494/424

24,200

27,300

635/565/494

7,500

8,500

300/265/229

9,600

10,900

335/300/265

12,300

13,600

371/335/300

153 CEU4

15,400

17,100

406/353/335

183 CFU4

19,100

21,500

565/494/424

24,200

27,300

635/565/494

42 x 8 x 25

153 CEA4
183 CFA4
243 CFA4

Floor Standing Uncased

52-15/16 x 8 x 25

073 CEU4
093 CEU4
123 CEU4

243 CFU4

38-1/2 x 7-15/16 x 25-3/16

49-7/16 x 7-1/2 x 25-3/16

All indoor units require 208230V/60Hz/1Ph and an AWG18-2 communication cable.


Model number shows nominal capacity and frame size designator.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80F dry bulb (DB) and
67F wet bulb (WB) and outdoor ambient conditions of 95F dry bulb (DB) and 75F wet bulb (WB).
1
2
3

104

PRODUCT DATA

3/8, 5/8

31

123VEA2

123 CEA4

1/4, 1/2
55

35-7/16 x 7-7/8 x 19-5/16

Floor Standing Cased

Pipe
Weight Connections
(lbs.) (inches, O.D.)
(Liquid, Vapor)

60

75

46

58

1/4, 1/2

1/4, 1/2

3/8, 5/8

1/4, 1/2

3/8, 5/8

Nominal heating capacity rating obtained with air entering the indoor unit at 70F dry bulb (DB) and 60
F wet bulb (WB) and outdoor ambient conditions of 47F dry bulb (DB) and 43F wet bulb (WB).
4
H/M/L = High/Medium/Low

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

INDOOR UNIT ACCESSORIES

Table 37: Summary DataZone Controllers


Zone Controller

Name

Model No.

Simple Controller with


mode selection

Simple Controller
without mode selection

PQRCVCL0Q

Max Wire
Case Color Length
(ft)
Black

PQRCVCL0QW

White

PQRCHCA0Q

Black

PQRCHCA0QW

White

Description

164

Allows control of indoor unit on/off, operation mode, fan speed,


and temperature setpoint for up to 16 indoor units.

164

Allows control of indoor unit on/off, fan speed, and temperature


setpoint for up to 16 indoor units.

LG Premium
Controller

PREMTA000

Ivory

164

LG Programmable
Thermostat

PREMTB10U

White

164

Wireless Handheld

PQWRHQ0FDB

Ivory

----

Allows control of indoor unit on/off, operation mode, fan speed,


and temperature setpoint.

Wall-Mounted Remote
Temperature Sensor

PQRSTA0

Ivory

50

Allows remote temperature measurement for cassette and


ducted units.

Before specifying or placing an order, refer to the V-Net Network Solution Engineering Product Data Book and review the detailed technical data provided to fully understand the capabilities and limitations of these
devices.
For information on controller compatibility refer to the Controls and Options Table on page 106.

Table 38: Summary DataZone Controller Communication Cables


Communication Cable

Name
Wired Remote Group
Control Cable Assembly
Wired Remote/Group Control
Extension Cable

Model No.

Wire Length (ft.)

Description

PZCWRCG3

33

Required when grouping multiple indoor units with a single


zone controller.

PZCWRC1

33

Increases the distance between a remote controller and an


indoor unit or between indoor units in a control group.

Before specifying or placing an order, refer to the V-Net Network Solution Engineering Product Data Book and review the detailed technical data provided to fully understand the capabilities and limitations of these
devices.
For information on controller compatibility refer to the Controls and Options Table on page 106.
Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

PRODUCT DATA

105

Product Data

Allows control of indoor unit on/off, operation mode, occupied/


unoccupied temperature setpoints, fan speed, and air flow
direction for up to 16 indoor units. Programmable schedule with 5
events per day with control of occupied/unoccupied, on/off,
mode, setpoints and fan speed. Advanced functions include
two setpoint autochangeover, minimum difference between
setpoints, setback, timed override, target energy consumption
display, check energy display and master/slave.
Allows control of indoor unit on/off, operation mode, occupied
and unoccupied temperature setpoints, fan speed, and airflow
direction for up to 16 indoor units. Programmable schedule with
5 events per day with control of occupied unoccupied, on/off,
mode, setpoints and fan speed. Advanced functions include two
setpoint autochangeover, minimum difference between setpoints,
setback and timed override.

INDOOR UNIT CONTROLS AND OPTIONS

Table 39: Indoor UnitsControls and Options.

Airflow
Operation
Controllers Filter
Others

MULTI V IV Outdoor Unit Engineering Manual

Feature

Wall
Wall
Mount, Mount,
1-Way 2-Way
ART Cassette
Std. COOL
Cassette
Finish Mirror

Nominal Size
524 724
(MBh)
1
1
Air supply outlets
Airflow direction (left/right) manual auto
Auto airflow direction

(up/down)
3
3
Fan speed (Heating mode)
4
4
Fan speed (Cooling mode)
3
3
Fan speed (fan mode)
Chaos swing

(random louver swing)


Chaos wind (random

fan speed)
Jet-cool (power

cooling)
E.S.P. control
High ceiling
Auto-restart after

power restore

Hot start

Diagnostics

Auto changeover1

Auto operation6

Auto clean (coil dry)

Child lock

Dual thermistor control

Dual set-point control

Filter life display


Power consumption

display (with PDI)

Forced operation
Group control Requires
the use of one Group

control cable kit


(PZCWRCG3) for every
additional indoor unit

Timer (on/off)

Weekly schedule

Test operation mode


o

Plasma3

Washable anti-fungal2
7-day programmable
o
o
controller
o
o
Simple controller w/mode
o
Simple controller w/o mode o
o
o
Wireless controller
Condensate lift
Ventilation air

Casing
Standard grille
Auto elevation grille
Suction grille
Suction canvas
Aux. heat kit

724

For Heat Recovery systems only.


Primary washable filters.
3
Plasma filter kit accessories available separately, except for ArtCool Mirror
which is included as standard.
1
2

106

PRODUCT DATA

4-Way
Cassette

Duct Vert.- Vert.Duct Duct Low Horiz.


Floor
Floor
Ceiling Convert.
High Low Static, AHU Horiz.
Surface
Mount,
Mount,
Suspend. Mount Cased Uncased
Static Static Bottom (NJ) AHU
(NK)
Return

1824 518 2448 796 724 724 12-36 42-53 1824

4
5
4

4
5
4

4
5
4

4
5
4

912

1
1
manual manual

724

724

3
3
3

3
3
3

3
4
3

3
4
3

o
o
o

o
o
o

o
o
o

3
3
3

3
3
3

3
3
3

3
3
3

3
3
3

o
o
o

o
o
o4

o
o
o4

o
o4

o
o

o
o

o
o

o
o

o
o4

o
o4

o
o

Requires 7-day programmable zone controller.


Requires ventilation kit PTVK430 or PTVK410+PTVK420 (For TP, TN, TM
frames)(Temperature, humidity, and volume limitations apply).
6
Heat Pump systems only.
4
5

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

= Standard feature
o = Unit option

APPLICATION
GUIDELINES

Equipment Selection Procedure on page 108


Building Ventilation Design Guide on page 113
Placement Considerations on page 116

EQUIPMENT SELECTION PROCEDURE

MULTI V IV Outdoor Unit Engineering Manual

LATS Multi V Piping Design Software

The proper design and installation of the refrigerant piping system is a


critical element of a Multi V system. Multi V Heat Pump systems require
two pipes between components a liquid line and a vapor line. Multi V
Heat Recovery systems require three pipes between the outdoor unit
and the heat recovery unit a liquid line, a low-pressure vapor line,
and a high-pressure vapor line. A properly designed refrigerant piping
system ensures that refrigerant is delivered to the indoor unit coils for
optimal system performance and capacity.
LG Air Conditioner Technical Solution (LATS) software is a total design
solution for LG Multi V air conditioning systems. This
Windows-based application assists the design engineer with
specifying and sizing outdoor and indoor units (by calculating
component capacity based on design conditions), laying out the refrigeration distribution pipe system, checking piping limitations, calculating
refrigerant charge, and generating equipment schedules and piping diagrams in (.dxf) format for use on CAD building design drawings.*
* Windows is a registered mark of Microsoft Corporation.

To ensure that the refrigerant piping design meets LGs quality standards, a LATS refrigerant piping design must be provided with
every Multi V order. Following the installation, if any changes or variations to the design are necessary, a new LATS file must be
created and provided to LG prior to system commissioning to ensure the proper pipe size has not changed.

Adjusting LATS Multi V Output for Altitude

When a system is installed at elevations significantly above sea level, consider the impact air density has on the capacity of the indoor and
air-source units. LATS does not de-rate indoor unit capacity for high altitude applications. Be sure to apply locally accepted correction factors
when calculating actual indoor unit capacities at that altitude.

Design Choices

LATS Multi V software is flexible, offering the HVAC system engineer an easy to use Tree mode.

Tree Mode

Using the Tree mode, the engineer can quickly create a one-line schematic drawing of a Multi V system. Integration of the engineered pipe
system into the building drawings is done at a later date by the
Figure 10: Screenshot of LATS Pipe System Design Tool in Tree Mode.
draftsperson using standard drafting software tools.
Import building loads from an external file (.xls format).
System components selected using an easy drag and drop
process.
Automatically analyzes and checks the design complies with most
piping design limitations.
Sizes refrigerant piping.
Generates a system engineering report (.xls format).
Generates an equipment schedule (.xls or .dxf format).
Generates a system piping diagram (.dxf format).

LATS Report

LATS Multi V software generates a report file (.xls format) containing project design parameters, cooling and heating design day
system component performance, and capacity data. The report
calculates the system combination ratio, calculates the system
refrigerant charge, and provides detailed bill of material information
including a list of Multi V outdoor units, air handlers, control devices, accessories, refrigerant pipe sizes segregated by building, by system,
by pipe size, and by pipe segments.
108

APPLICATION GUIDELINES

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

EQUIPMENT SELECTION PROCEDURE

The following procedure is a representation on how LATS Multi


V Piping Design software works when designing a Multi V HVAC
system. It should not replace the use of LGs LATS Multi V
complimentary selection software, but should instead be used in
conjunction with it. Contact your LG representative to obtain a
copy of the software and the users manual.

Always use LATS Multi V Software

When using the LATS Multi V software, the default indoor design day
conditions of 80.6F DB / 67 F WB in cooling mode and 68F DB /
56.7F WB in heating mode may need to be adjusted to reflect the
designer's preferred return air design temperature.
Data provided in the LATS tree mode diagram or report file is not
valid until the Auto-Piping and System Check routines are run
without errors. Errors will be reported immediately in pop-up
dialog boxes or red lines surrounding indoor unit(s) and / or along
pipe segments. If errors are indicated, modify the pipe system
design and / or system components and re-run LATS.

Zone the BuildingMulti V IV Heat


Pump Systems

Multi V IV Heat Pump is a two-pipe heat pump system that can cool
or heat, but not both simultaneously. When designing a heat pump
system, the designer typically combines spaces with similar load
profiles located near or adjacent to each other into thermal zones.
After combining like spaces into thermal zones that will be served by
a single (or grouped) indoor unit(s), calculate the peak cooling and
heating loads for each thermal zone.

Zone the BuildingMulti V IV Heat


Recovery Systems

Multi V IV Heat Recovery is a three-pipe heat pump system that


can cool and heat simultaneously. To maximize the amount of heat
recovered and optimize the system operating efficiency, it is best
to combine spaces that require heating and cooling concurrently
on each Multi V pipe system. LG multi-port heat recovery units are
designed to serve spaces that need cooling and others that need
heating at the same time. The heating/cooling operating mode

Calculate the Ventilation Method

Decide how ventilation air will be introduced to each space. Some


models of Multi V indoor units have field-installed accessories
available to accommodate the direct connection of ventilation
ductwork to the unit. It is recommended, however, that additional
considerations be assessed and understood when using direct
connection accessories. For more information, contact your LG
applied equipment representative or visit www.lg-vrf.com for
technical product information.

In all cases, LG recommends ducting pre-treated room neutral,


ventilation air directly to the space. If the ventilation air is not
tempered to room neutral conditions before introduction to the
conditioned space, remember to add the ventilation air load(s) to
the space load before sizing the indoor unit(s). Local codes or
other professional design guidelines, such as ASHRAE 62.1, will
dictate the volume of ventilation air required.
It may be prudent to oversize the dedicated outdoor air system
considering there will be a few days of the year when weather
conditions exceed the design day conditions. This will minimize
the possibility of ventilation air conditions causing the space
temperature to drift outside design day parameters in the case where
a decoupled outside air system is used, or the indoor unit's entering
air temperature falls outside the approved design temperature range
if a coupled outside air system is used.

Designing for Extreme Climatic


Conditions

The Multi V IV air-cooled outdoor unit(s) may have to operate in


weather conditions more extreme than a typical design day. Design
days are the days of the year that either cooling or heating capacity
is needed the most. In light of this, it may be prudent to size the
outdoor unit considering the anticipated worst weather day
conditions to ensure adequate capacity year round.
When design outdoor ambient conditions are outside the cataloged
air-cooled outdoor unit operating range, the net refrigeration effect
(capacity) delivered to the indoor units cannot be guaranteed. As a
result, the outdoor units net refrigeration capacity available for use
by the indoor units will be slightly reduced under certain extreme ambient air conditions. (For cooling and heating capacity performance

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

APPLICATION GUIDELINES

109

Application Guidelines

To properly select, size, and verify that the Multi V system


components are optimized, follow the recommendations and
instructions provided in this section:
Zone the building.
Determine the ventilation method.
Select the indoor unit(s).
Select the outdoor unit(s).
Perform system sizing checks.
Calculate the Corrected Capacity Ratio (CCR).
Determine the system Combination Ratio (CR).
Determine the Running (indoor) Unit Ratio (RUR).

selection is made at the heat recovery units' outbound pipe port,


independent of the adjacent ports' operating mode.
In many buildings, to optimize system design, spaces on opposite
sides of the building are combined on a single pipe system served by
a common Multi V IV Heat Recovery outdoor unit. If the building
has multiple floors, connected load diversity is often maximized by
combining spaces located on different floors (maximum 131 feet
vertical height difference between indoor system components). Each
building will be unique. To discover the best combination of spaces,
use a building energy modeling software.

MULTI V IV Outdoor Unit Engineering Manual

EQUIPMENT SELECTION PROCEDURE

data, see the separate Multi V IV Performance Data Manual on


www.lg-vrf.com.)
In lieu of designing for extreme weather conditions beyond the
cataloged temperature range, consider limiting the maximum
and / or minimum temperature of the air around the Multi V outdoor
air-cooled unit, or consider a Multi V water-cooled unit.
When installing a Multi V outdoor unit indoors, provide a condensate drain pan with drain in locations where frozen run-off water
may present a slipping danger. Also, the air guide accessory (sold
separately) should be installed when mounting outdoor units indoors,
to prevent short cycling of discharge air.

Determine how many indoor units will be required. Refer to the


specification tables to obtain the maximum number of indoor units
allowed on Multi V IV Heat Pump and Heat Recovery units. If the
quantity of indoor units exceeds the maximum allowed for the outdoor model selected, consider increasing the size of the outdoor unit
or split the indoor units into two groups served by separate outdoor
units.
Calculate the entering mixed air conditions. Verify the entering air
temperature is below 76F WB in cooling mode and above 59 F in
heating mode.
To calculate the indoor unit entering mixed air temperature:

Heating Season

(RAT x %RA) + (OAT x %OA)


100
Where:
OAT = Outside air temperature
MAT = Mixed air temperature
%RA = Percentage of return air
RAT = Return air temperature
%OA = Percentage of outdoor air

Provide a ventilated equipment enclosure equipped with an auxiliary


heat source, or place the outdoor unit(s) within the confines of the
building envelope. On retrofit projects, it is best practice to
position the outdoor unit(s) in former chiller, boiler, or air handler
rooms. These strategies are commonly used on air-cooled projects
to eliminate extreme over-sizing of the outdoor unit(s).
The enclosure will eliminate other potential operational problems
from occurring, including the build-up of snow and ice on the unit
case, fan shroud and fan blade, limit the capacity reduction effect of
operating the outdoor unit at extremely low temperatures, and may
reduce the size and initial cost of the Multi V IV outdoor unit.

MAT =

When the indoor unit entering air temperature is outside the


cataloged operational limits, operational abnormalities may occur.
These include frost accumulating on the coil, low or high suction
temperature, low or high head pressure, low or high discharge
temperature, or complete system shutdown.

Cooling Season

An enclosure housing the outdoor unit or roof structure designed


to shade the outdoor unit will protect the unit(s) from the negative
impact of direct sun exposure, hail, and on sunny days, increase the
cooling capacity by reducing the refrigerant condensing temperature.
When the designer provides the LATS software with
ambient air design conditions that are above or below the cataloged
operational temperature range, the software will override the
designers specified conditions and will size the refrigerant pipe
system using the maximum or minimum cataloged ambient air
operating temperature. The report generated by LATS will reflect the outdoor ambient air conditions the designer provides,
but the indoor and outdoor unit(s) cooling and heating corrected
capacities calculated and shown in the report will be based on
the cataloged ambient air operating temperature limits. On these
projects, the designer must manually estimate the corrected
cooling and heating capacity of the outdoor unit when specified
ambient conditions are outside the cataloged range.

Select the Indoor Unit(s)

The building sensible cooling load is typically the critical load to


satisfy. In coastal areas or humid applications, such as high
occupancy spaces, both the latent and sensible cooling loads
should be considered. In areas where the cooling and heating loads
are similar or the heating load may exceed the total cooling load,
the designer should verify the indoor unit selection satisfies both the
heating and cooling requirements.

110

APPLICATION GUIDELINES

Indoor unit nominal cooling capacity ratings, among other


parameters, are based on an entering air condition of 80F DB /
67F WB and a 95F DB outdoor ambient temperature. Nominal
heating capacity ratings are based on an indoor unit entering air
condition of 70F DB and an outdoor ambient air temperature of
47F DB / 43F WB.

Capacity Correction

The corrected cooling/heating capacity is different from the nominal


cooling / heating capacity. The corrected capacity reported by LATS
includes changes in unit performance after considering refrigerant
line pressure drop, the system's Combination Ratio (CR), and the
effect design ambient operating conditions has on the systems
cooling capability.
Depending on the location of the building, additional capacity
correction factors may need to be applied to the corrected capacity
values provided by LATS . (For correction factors, see the separate
Multi V IV Performance Data Manual on www.lg-vrf.com.)

Altitude Correction

On air-cooled systems, the impact of air density must be considered


on systems installed at a significant altitude above sea level. To
calculate the effect on the indoor units cooling capacity, manually
apply locally accepted altitude correction factors. LATS does not
de-rate indoor unit capacity for altitude.

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

EQUIPMENT SELECTION PROCEDURE

Minimum Air Change Requirements

Avoid over-sizing indoor units in an attempt to increase the air


exchange rate in the space. VRF systems are designed for
minimum airflow over the coil to maximize latent capacity while
cooling, maintain a comfortable, consistent discharge air
temperature while heating, and minimize fan motor power
consumption. In extreme cases, over-sizing indoor units may
compromise the outdoor units ability to effectively match the space
load(s).

Check the Indoor Unit Selection(s)

Select the Outdoor Unit

After all indoor units are properly sized to offset the applicable loads
in each space, begin the selection of the outdoor unit by choosing a
size that meets both the block load cooling requirement and offsets
the sum of the peak heating load.
After making an outdoor unit selection, look up the outdoor units
corrected cooling and heating capacity at the specified ambient
design conditions. Use values reported by LATS or find it in the
tables provided in the separate Multi V IV Performance Data Manual
on www.lg-vrf.com.
In LATS always run the Auto-Pipe and System Check features
following any change in the outdoor unit selection to verify the
system design is acceptable.

Capacity Correction

For air-cooled systems operating in cooling mode, a capacity


correction factor may apply to account for the length of the systems
liquid pipe and elevation difference between the outdoor unit and the
indoor unit(s). If the outdoor units corrected cooling capacity was
derived from the LATS report, the elevation difference correction
factor has already been applied. If the corrected cooling capacity
was found using corrected capacity tables found in the separate
Multi V IV Performance Data Manual on www.lg-vrf.com, apply the
appropriate elevation difference factor also found in the Performance
Data Manual (choice of table depends on the architecture of the
system design). Multiply the outdoor unit corrected cooling capacity
by the elevation difference correction factor. For high altitude
locations, locally accepted altitude correction factors must be
manually applied to outdoor unit capacity. LATS will not de-rate
outdoor unit capacity for altitude.

The outdoor unit heating capacity may need to be adjusted for frost
accumulation on air-cooled systems. If design day conditions are
below the dew-point of the surrounding air, frost may not be a
problem and no correction factor is needed. In certain weather
conditions, however, frost may form and accumulate on the aircooled outdoor unit coil and impact the coils ability to transfer heat.
If significant frost accumulates on the outdoor unit coil, a defrost
algorithm will start automatically. The timing between defrost periods
is determined by the system's ability to achieve a target head
pressure value.
LATS will automatically apply a frost accumulation factor if the check
box labeled Defrost Factor in the outdoor unit selection dialog box
is marked. The dialog box can be accessed by double-clicking on
the outdoor unit image. If checked, the corrected outdoor unit
capacity provided by the LATS report and displayed on the tree
mode piping diagram will already be adjusted for outdoor unit coil
frost accumulation.
If the corrected heating capacity was found using the Performance
Data tables, the frost accumulation factor must be applied. (For
correction factors, see the separate Multi V IV Performance Data
Manual on www.lg-vrf.com.).

Check the Indoor Unit Selection(s)

After applying the appropriate correction factors to the outdoor unit,


verify the corrected cooling capacity is at least equal to the total
building load (considering building diversity, if applicable), and the
corrected heating capacity is at least equal to the sum of the peak
heating loads for all spaces and/or thermal zones served by the
system.

System Sizing Checks

Calculate the Corrected Capacity Ratio (CCR)

The systems CCR is defined as the sum of the space loads divided
by the outdoor unit corrected capacity after all applicable correction
factors are applied. Calculate this ratio for both the cooling and
heating design days.
CCR%(Clg) =

CCR%(Htg) =

(
(

Total Cooling Block Load


Actual Corrected Outdoor
Unit Cooling Capacity
Heating Peak Load
Actual Corrected Outdoor
Unit Heating Capacity

)
)

x 100 100%

x 100 100%

The outdoor unit selected should be large enough to offset the total
block cooling load for all spaces served by the VRF system during
the peak cooling load hour on the cooling design day (account for
ventilation air cooling load if the ventilation air has not been
pretreated to room neutral conditions).

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

APPLICATION GUIDELINES

111

Application Guidelines

Verify the sensible (and total) corrected cooling capacity. For each
indoor unit the corrected capacity must be at least equal to the sum
of the appropriate cooling design day space load(s) (plus ventilation
load, if applicable) for the space(s) served by the indoor unit.
Verify the corrected heating capacity. For each indoor unit, the
corrected capacity must be at least equal to the sum of the
heating design day space load (plus ventilation load, if applicable)
for all spaces served by the indoor unit.

Frost Accumulation

MULTI V IV Outdoor Unit Engineering Manual

EQUIPMENT SELECTION PROCEDURE

The corrected cooling capacity ratio (CCR% [clg]) should never


exceed 100% plus building diversity. If it does, increase the size of
the outdoor unit or change the system design by moving some of
the building load and associated indoor unit(s) to another Multi V
system.
The outdoor unit should also be large enough to offset the sum
of the buildings space heating loads without considering building
diversity. In the heating season, it is typical that all spaces served
by the system will peak simultaneously in the early morning, thus
building diversity should never be considered. If the corrected heating capacity ratio (CCR% [htg]) exceeds 100%, increase the size of
the outdoor unit or change the system design by moving some of the
building load to another Multi V system.

Determine the System Combination Ratio (CR)

The system's CR compares the nominal capacity of all connected


indoor units with the nominal capacity of the outdoor unit serving
them. Locate nominal capacity information for indoor and outdoor
units in the General Data Tables of their respective Engineering
Manuals.
For example,
If a VRF system has an outdoor unit with a nominal capacity of C
and four indoor units having nominal capacity ratings of W, X, Y, and
Z respectively, the CR would be determined as follows:
CR% =

W+X+Y+Z
C

x 100

The Multi V system will not commission, start or operate unless the
CR is between 50% and 130%.
If the CR is over 100%, the designer is under-sizing the outdoor unit
relative to the combined nominal capacity of the connected indoor
units. In some applications, under-sizing of the outdoor unit is
prudent as it reduces the initial equipment investment and will
properly perform as long as the designer:
1. Knows the indoor unit(s) are oversized relative to the actual
load(s) in the spaces served.
2. Knows the space loads will peak at different times of the day (i.e.,
building has "load diversity").
In some designs, over-sized indoor units may be unavoidable in the
case where the smallest size indoor unit available from LG is larger
than what is necessary to satisfy the space load. This scenario may
occur when an indoor unit selection one size down from the selected
unit is slightly short of fulfilling the design load requirements, and the
designer must choose the next largest size unit.

112

APPLICATION GUIDELINES

If the outdoor unit is properly sized to offset the buildings total


cooling block load and the system's combination ratio is above
130%, indoor units are likely oversized. In applications where all
indoor units are right-sized and there is no building diversity, the
systems CR will likely be 100%.
If the CR is above 130%, review the indoor unit choices and
downsize, or select a larger outdoor unit. Consider moving indoor
units to another Multi V, Multi F, or single-split system if the
outdoor unit size cannot be increased.
If the CR falls below 50%, select a smaller outdoor unit or consider
adding more or larger indoor unit(s) to the system. This situation
is common on multi-phase projects where the design calls for the
majority of indoor units be added to the system at a later date. To
raise the CR above the minimum 50% requirement:
3. Consider including additional indoor units on the first phase
4. Design two smaller systems in lieu of a single larger system.
Connect all first phase indoor units to the outdoor unit being
installed on the first phase, and delay the installation of the
additional outdoor unit until a later date.

Conclusions and Recommendations

Always use LATS Multi V system design software to check a


design.
Validate that each indoor unit is appropriately sized. Before
validating, if the indoor units have been properly sized, the outdoor
units size must be temporarily adjusted to make the systems CR
100%.
Using the indoor units corrected capacity for cooling and heating
provided by LATS and apply a correction factor for altitude if appropriate.
Verify that the outdoor unit selection for each system is properly
sized. Verify that the corrected capacity for cooling and heating
provided by LATS is sufficient to offset the block building space
load after applying additional correction factors for capacity and
frost accumulation, if appropriate.
For each Multi V system, calculate the cooling and heating design
days
1. Corrected Capacity Ratio (CCR).
2. Combination Ratio (CR).
After these system checks are complete and design limitations are
adhered, the systems indoor and outdoor components should be
properly sized and the systems performance should now be
optimized. The VRF system component size selections should be
acceptable.
At any time, if further system design assistance is needed or you
have a unique application you would like to discuss, contact your LG
applied equipment representative for assistance.

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

BUILDING VENTILATION DESIGN GUIDE

Building Ventilation Design Guide

ASHRAE 62.1 and local codes specify the minimum volume of outdoor air that must be provided to an occupied space. Outdoor air is
required to minimize adverse health effects, and it provides acceptable indoor air quality for building occupants. The five methods of
accomplishing this with LG Multi V IV systems are summarized here.
Disclaimer

Although we believe that these building ventilation methods have been portrayed accurately, none of the methods have been tested, verified,
or evaluated by LG Electronics, U.S.A., Inc., In all cases, the designer, installer, and contractor should understand if the suggested method is
used, it is used at their own risk. LG Electronics U.S.A., Inc., takes no responsibility and offers no warranty, expressed or implied, in law or in
fact, including but not limited to any implied warranty of merchantability or fitness for a particular purpose.
For a complete copy of Standard 62.1-2010, refer to the American Standard of Heating and Air Conditioning Engineers (ASHRAE)
website at www.ashrae.org.
For more information on how to properly size a ventilation air pretreatment system, refer to the article, "Selecting DOAS Equipment with
Reserve Capacity" by John Murphy, published in the ASHRAE Journal, April 2010.
Provide a separate, dedicated outdoor-air system designed to filter, condition, and dehumidify ventilation air and deliver it directly to the
conditioned space through a separate register or grille. This approach requires a separate independent ventilation duct system not
associated with the Multi V IV system.
LG recommends using the DDOAS method in all installations.

Advantages

Does not add additional heating or cooling loads to indoor units.


May be used with a full lineup of the indoor units.
The outdoor air unit may supply neutral air to the occupant space
even when the Multi V indoor unit fan changes speed or cycles on
and off. DDOAS controls do not have to be interlocked with the
Multi V IV system.
In lieu of installing localized smaller outside air treatment
equipment throughout the building, this method centralizes the
ventilation air source making service and filter changes easier.
Third-party demand control ventilation controls are more readily
accommodated.

Disadvantages

Ceiling space is required to accommodate ductwork between the


centralized outdoor air unit and ceiling diffusers.

Methodology illustrations are for examples only and do not depict


actual indoor units for the specific outdoor unit pairing. These are
generic illustrations to show ventilation design only.

Ceiling Diffuser

Multi V Ceiling-Cassette Indoor Unit

Outdoor Air

Outdoor Air Unit / ERV

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

APPLICATION GUIDELINES

113

Application Guidelines

Method 1: Decoupled Dedicated Outdoor Air System (DDOAS)

BUILDING VENTILATION DESIGN GUIDE

Method 2: Unconditioned Outdoor Air (Non-Ducted, Natural Ventilation)

Natural ventilation devices, such as operable windows or louvers may be used to ventilate the building when local code permits. The open
area of a window or the free area of a louver must meet the minimum percentage of the net occupied floor area.

Advantages

MULTI V IV Outdoor Unit Engineering Manual

Occupants control the volume of the ventilation air manually.


Useful for historic buildings that have no ceiling space available for
outdoor air ductwork.
May be used with the full lineup of Multi V indoor units.

Disadvantages

In some locations, it may be difficult to control humidity levels when


windows are open.
Thermal comfort levels may be substandard when windows are
open.
Indoor units may have to be oversized to account for the added
heating and cooling loads when windows are open.
Provides outdoor air to perimeter spaces only. Additional mechanical ventilation system may be required to satisfy requirements for
interior spaces.
Outdoor air loads may be difficult to calculate since the quantity of
outdoor air is not regulated.
May affect indoor unit proper operation when open.

Method 3: Unconditioned Outdoor Air Ducted to Indoor Units

Untreated outdoor air is channeled through a duct system that is piped to the return air duct on Multi V concealed indoor units or to the frame
of Multi V 1-way and 4-way cassettes.
Outside air may flow backward through the return air-filter grille when the indoor unit fan speed slows or stops in response to changes in the
space load. This may result in captured particulate on the filter media being blown back into the conditioned space.

Advantages

May require less ductwork if indoor units are


placed near outdoor walls or a roof deck.
Controls must be interlocked to shut off the
outdoor air supply fan when the space is
unoccupied.
Third-party demand-control ventilation
controls may be installed to regulate outdoor
intake based on the CO2 levels of the
occupied space.

114

APPLICATION GUIDELINES

Disadvantages

Fan(s) will be required to push outdoor air to the indoor unit. Indoor units are engineered
for low sound levels and are not designed to overcome the added static pressure caused
by the outdoor air source ductwork.
Ventilation air must be pre-filtered before mixing with the return air stream. LG indoor
cassette models are configured to introduce the ventilation air downstream of the return
air filter media.
Ducted, 1-way, and 4-way cassette models are the only indoor units that accept the
connection of an outdoor air duct to the unit case.
Mixed air conditions must be between a minimum of 59F DB while operating in heating
and a maximum of 76F WB while operating in cooling. Depending on the ventilation air
volume requirement, the location choices are limited where untreated outside air may be
introduced to the building using this method.
Larger indoor units may be required to satisfy for additional outdoor air.
Motorized dampers may be required to prevent outdoor air flow through the indoor unit
when the indoor unit is not operating.
An LG Dry Contact adapter may be necessary to interlock the motorized damper with the
indoor unit.
While operating in heating, the untreated outdoor air may delay the start of the indoor unit
fan impacting building comfort.
In most cases, in lieu of using the factory mounted return-air thermistor on indoor units, a
remote wall temperature sensor or zone controller will be needed for each indoor unit to
provide an accurate reading of the conditioned area temperature.

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

BUILDING VENTILATION DESIGN GUIDE

Method 4: Unconditioned Outdoor Air (Non-Ducted, Fan Assisted Ventilation)


When approved by local codes, the fan assisted ventilation method uses exhaust fans to remove air from the building, and outdoor air is
drawn into occupied spaces through a wall louver or gravity roof intake hood. Supply fans can also be used to push the outdoor air into the
space and building positive pressure will vent the exhaust air through louvers or roof-mounted exhaust hoods. Outdoor air is neither cooled
nor heated before entering the building.
This may result in loss of building pressurization control, increasing infiltration loads with adverse effects.

Disadvantages

Advantages

In some locations of the country, it may be difficult to control


humidity levels while outdoor air louvers/hoods are opened.
Thermal comfort levels may be substandard when louvers/hoods
are opened.
Indoor units may have to be oversized to account for the added
heating/cooling loads when louvers/hoods are open.
Hot, cold, and/or humid areas may be present if the outdoor air is
not evenly distributed to the different spaces.

Method 5: Coupled Dedicated Outdoor Air (CDOA)

A separate, dedicated outdoor air system delivers air directly to a Multi V indoor unit or to the return air duct system. After mixing with the
return air stream, ventilation air passes through the indoor unit and into the conditioned space. The pretreatment system is capable of
filtering, conditioning, and dehumidifying outdoor air to room neutral conditions.
Outside air may flow backward through the return air-filter grille when the indoor unit fan speed is reduced or stops when the space load is
satisfied. This may result in captured particulate on the filter media being blown back into the conditioned space.

Advantages

Separate ceiling registers or grilles for introduction of the outside air to the conditioned
space may be avoided.

Disadvantages

Ducted, 1-way, and 4-way cassette indoor units are the only models designed for direct
connection of an outside air duct.
The building occupant may not notice the outdoor air pretreatment system has malfunctioned until the unconditioned outdoor air exceeds the indoor unit mixed air limits of 59F
DB for heating and 76F WB for cooling.
If the coil entering air condition limitation is exceeded, the indoor unit may malfunction
and ceases to operate.
If the outdoor air unit cooling or heating system fails, the malfunction may be masked by
the indoor unit ramping up operating parameters to compensate for the failure.
Motorized dampers may be required to prevent outdoor air from entering the indoor unit
while the indoor unit has cycled off.
An LG Dry Contact adapter is necessary to interlock the motorized damper with the
indoor unit fan operation.
In lieu of using the factory mounted return-air thermistor, a remote wall temperature
sensor or zone controller may be required to provide an accurate conditioned space
temperature reading.

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

APPLICATION GUIDELINES

115

Application Guidelines

Outdoor air may be manually controlled by the occupant or automatic controls may be installed to open/close outdoor air dampers
or to turn on/off ventilation fans.
Useful for large open spaces like warehouses, garages, and
workshops.
Outdoor air volume is a known quantity. Air loads may be easier to
calculate since fans will regulate the amount of outdoor air.
May be used with a full lineup of Multi V indoor units.

PLACEMENT CONSIDERATIONS
Outdoor Units

MULTI V IV Outdoor Unit Engineering Manual

Selecting the Best LocationOutdoor Units

Select a location for installing the outdoor unit that will meet the following conditions:
Where the unit will not be subjected to direct thermal radiation from other heat sources.
Where operating sound from the unit will not disturb inhabitants of surrounding buildings.
Where the unit will not be exposed to direct, strong winds.
Where there is enough strength to bear the weight of the unit.
Include space for drainage to ensure condensate flows properly out of the unit when it is in heating mode.
Include enough space for air flow and for service access.
To avoid the possibility of fire, do not install the unit in an area where combustible gas may generate, flow, stagnate, or leak.
Do not install the unit in a location where acidic solution and spray (sulfur) are often used.
Do not use the unit in environments where oil, steam, or sulfuric gas are present.
Install a fence to prevent vermin from crawling into the unit or unauthorized individuals from accessing it.
To ensure the outdoor unit operates properly, certain measures are required in locations where there is a possibility of heavy snowfall or
severe windchill or cold:
1. Prepare for severe winter wind chills and heavy snowfall, even in areas of the country where these are unusual phenomena.
2. Position the outdoor unit so that its airflow fans are not buried by direct, heavy snowfall. If snow piles up and blocks the airflow, the
system may malfunction.
3. Remove any snow that has accumulated 3-15/16 inches or more on the top of the outdoor unit.
4. Place the outdoor unit on a raised platform at least 19-11/16 inches higher than the average annual snowfall for the area. In environments
where there is a possibility of heavy snow, the H frame height must be more than two (2) times the amount of average annual snowfall,
and should not exceed the width of the outdoor unit (see page 277). If the frame width is wider than the outdoor unit, snow may accumulate.
5. Install a snow protection hood or an air guide.
6. To prevent snow and heavy rain from entering the outdoor unit, install the air guide and/or hail guard kits.
Additionally, the following conditions should be taken into considerations when the unit operates in defrost mode:
If the outdoor unit is installed in a highly humid environment (near an ocean, lake, etc.), ensure that the site is well-ventilated and has a lot
of natural light. (Example: Install on a rooftop.)
Sidewalks or parking lots near the outdoor unit may accumulate moisture after unit operates in defrost mode that can turn to ice.
The indoor unit may take longer to provide heat, or heating performance will be reduced in winter if the unit is installed:
1. In a narrow, shady location.
2. Near a location that has a lot of ground moisture.
3. In a highly humid environment.
4. In an area in which condensate does not drain properly.

116

APPLICATION GUIDELINES

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

PLACEMENT CONSIDERATIONS
Outdoor Units

General Mounting

Figure 11: Outdoor UnitMounting Methods1.

Securely attach the outdoor unit to a condenser


pad, base rails, or other mounting platform that
is securely anchored to the ground or building
structure. Refer to dimensional drawings in the
Product Data section on pages 35 to 40, and
follow the applicable local code for clearance,
mounting, anchor, and vibration attenuation
requirements.

At least 3/8 inch


At least 7-7/8 inches

All referenced materials are to be field-supplied.


Images are not to scale. All dimensions 0.25
inches.
1

7-7/8

7-7/8

2-15/16

Mounting Platform

The underlying structure or foundation must be designed to support the weight of the unit. Avoid placing the unit in a low lying area where
water may accumulate.

Tie-Downs and Wind Restraints

The strength of the Multi V IV frame is adequate to be used with field-provided wind restraint tie-downs. The overall tie-down configuration
must be approved by a local professional engineer. Always refer to local codes when designing a wind restraint system.

Dealing with Snow and Ice

In climates that experience snow buildup, place the unit on a raised platform to ensure proper condenser airflow. The raised support platform
must be high enough to allow the unit to remain above possible snow drifts. Mount the unit on a field-provided snow stand at a minimum
height that is equal to the average annual snowfall, plus 20 inches. Design the mounting base to prevent snow accumulation on the platform
in front or back of the unit case. If necessary, provide a field fabricated hood to keep snow and ice and/or drifting snow from accumulating
on the coil surfaces. Install the optional hail guard kit and air guide accessories (sold separately) to prevent snow or rain from accumulating
on the fan inlet and outlet guards. When the system is commissioned, set the controller for snow throw operation. In all cases, connected
duct work and accessories must provide a combined air pressure drop rating that does not exceed 0.32" WG.
When deciding on a location to place the outdoor unit, be sure to choose an area where run-off from defrost mode will not
accumulate and freeze on sidewalks or driveways.
Snow throw mode does not prevent ice from forming on the fan blade or discharge grille.

Ambient Air Conditions

Avoid exposing the outdoor unit to steam, combustible gases, or other corrosive elements. Avoid exposing the unit to discharge from boiler
stacks, chimneys, steam relief ports, other air conditioning units, kitchen vents, plumbing vents, and other sources of extreme temperature,
gases, or substances that may degrade performance or cause damage to the unit.
When installing multiple outdoor units, avoid placing the units where discharge of one outdoor unit will blow into the inlet side of an adjacent
unit.

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

APPLICATION GUIDELINES

117

Application Guidelines

3-15/16

2-15/16

Unit : inch

A: Corners must be firmly attached,


otherwise, the support will bend.
B: Use a 3/8 inch or 5/16 inch hexagon nut with a spring washer.
C: Anti-vibration material.
D: Include enough space for refrigerant piping and electrical wiring
when installing through the bottom
of the unit.
E: H-beam support.
F: Concrete support.

PLACEMENT CONSIDERATIONS
Outdoor Units

Installation Space

Proper airflow through the outdoor unit coil is critical for proper unit operation. When installing the outdoor unit, consider service, inlet, and
outlet, and minimum allowable space requirements as illustrated in the diagrams below.
Figure 12: Minimum Space Requirements.

MULTI V IV Outdoor Unit Engineering Manual

Description

Example No.1
7/16 Space A, C 1-7/8

Installation Area

Front

Front

Unit(s) is (are)
enclosed by
(4) walls

Front

Front

Front

Front

A 7/16
B 11-13/16
C 7/16
D 20

A 2
B 3-15/16
C 2
D 20

A 7/16
B 11-13/16
C 7/16
D 36
E 2-3/4

A 2
B 3-15/16
C 2
D 36
E 3-15/16

A 7/16
B 11-13/16
C 7/16
D 36
E 2-3/4
F 24

A 2
B 3-15/16
C 2
D 36
E 3-15/16
F 20

A 7/16
B 11-13/16
C 7/16
D 36
E 2-3/4
F 36
G 20

A 2
B 3-15/16
C 2
D 36
E 3-15/16
F 36
G 20

Front

Front

A 7/16
B 11-13/16

No limitations on wall height


Two (2) sides
are walls

Example No. 2
Space A, C 1-7/8

Front

No limitations on
wall height

A 200(7-7/8)
B 300(11-13/16)
E 400(15-3/4)

Front

Wall height
limitations (when
the unit[s] is [are]
surrounded by
four [4] walls)

118

APPLICATION GUIDELINES

Wall height at the front of the unit must be 59-1/16 inches.


Wall height at the inlet side of the unit must be 19-11/16 inches.
There are no height limitations for the walls at the sides of the unit.
If the wall height at the front and inlet sides of the unit are higher than allowable limits,
additional space muct be included.
- Additional Space on the inlet side by 1/2 of h1.
- Additional Space on the front side by 1/2 of h2
- h2 = A(Actual height) - 59-1/16 inches
- h1 = B(Actual height) - 19-11/16 inches
Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

PLACEMENT CONSIDERATIONS
Outdoor Units

Installing Outdoor Units Indoors

LG Multi V outdoor units are engineered to be mounted outdoors and include technology designed to minimize the negative effects of winter
weathers freezing rain, sleet, and snow. Some building projects, however, necessitate placing the HVAC outdoor units indoors:
Lack of ground space.
Lack of an appropriate outdoor location that meets system design requirements.
When mounting on the roof is not an option due to a lack of roof space.
Roof warranty will be voided if mechanical equipment is placed on the membrane.
On retrofit projects, a former chiller/boiler/air handler equipment room, mechanical area, or penthouse already exists.
Where a project has vertical, self-contained VAV air handlers on each floor (in lieu of a centralized mechanical room).
To curtail the potential need for redundant zone heating devices such as wall-fin radiators or duct heaters.
In extremely cold environments where there is a significant amount of run-time at temperatures well below freezing outside the outdoor unit
ambient air temperature range published in this engineering manual.

Benefits of Installing Outdoor Units Indoors

Design Considerations Include:

Enclosure types and elements such as louvers, rain hoods, dampers and controls, heating methods and sizing of heating devices
Heating strategies
Duct design
Condensate handling

General Guidelines

Follow ASHRAE 62.1 design guidelines.


Depending on the project / application, a roof over the outdoor units in combination with a wind break may be all that is necessary.
Consider the potential for snow accumulation near louvers/roof openings. Outside air intakes and discharge ducts/louvers should be engineered to clear anticipated snow accumulation levels by at least one (1) foot.
In situations where operation is anticipated at temperatures of -13F and lower, ancillary heat should be provided to heat the outdoor unit
coils to assure continuous compressor operation and heating.
It may be necessary to use an air guide accessory to prevent discharge air from short-cycling back to the coil inlet.
Another option is to field manufacture ductwork and mount on top of the unit to encompass the outdoor unit fan discharge and connect to
the exterior discharge grille on the building.
Avoid using a single duct on multi-fan units to prevent short cycling. Provide a dedicated duct for each outdoor unit fan discharge.
Consider the direction of prevailing winds and opening placement. If possible, locate inlet openings upwind of discharge openings and other
exhaust outlets.
When inlet and outlet openings are placed on the same wall, minimum distance between the two openings should be approximately three
(3) feet (minimum distance varies significantly with variations in outlet opening face velocity).
If roof-mounted ventilation openings are used, strategically locate the inlet ventilation opening(s) upwind of the outlet opening(s).
Discharge and supply ductwork should be designed to avoid weather related long periods of water entrainment and the potential for microbial growth.

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

APPLICATION GUIDELINES

119

Application Guidelines

Shelters the outdoor unit from direct exposure to prevailing winds that decrease the heating capability of the outdoor unit.
Protects equipment from freezing precipitation and/or potential ice build-up that could hinder unit operation.
Maintains coil heat transfer efficiency by reducing the number of and shortening the cycle time for defrost operation.
Easier maintenance and servicing during inclement weather.
When mounted in a fully enclosed space, limiting the ambient air temperature may allow the Multi V system designer to eliminate oversizing
the outdoor unit to compensate for loss of capacity at low ambient temperatures.
May also curtail the need to provide inefficient redundant zone heating devices such as wall-fin radiators and second-stage ancillary heating devices.

PLACEMENT CONSIDERATIONS
Outdoor Units / Indoor Units

MULTI V IV Outdoor Unit Engineering Manual

Provide a means to drain the condensate generated during heating mode and defrost cycle in addition to rainwater that infiltrates the inlet
louver enclosed area.
Install a field-provided drain pan under the outdoor units and provide a path to a nearby floor drain.
If the ambient air temperature is expected to drop below 32F in the enclosure, heat the bottom surface of the pan, drain line, and floor
drain so that the condensate does not freeze before reaching the drain.
Allow for ventilation intake and exhaust air based on maximum outdoor unit fan capacity.
Select the size, type and orientation of architectural louvers with adequate "net free area" face velocity to ensure the total external static
pressure from the outdoor unit fan does not exceed design limitations (see specification data tables).
No obstructions should be placed in front of the louver that could hamper the free flow (throw) of air.
Roof top openings and / or discharge and supply louvers should be equipped with screens to prevent bird and insect infiltration.
As always, the best solution for each project balances acceptable heating performance (considering local weather conditions), capital costs,
life cycle energy consumption, and limitations set forth by local building codes. For more detailed information on how to design indoor spaces
for LG Multi V outdoor units, see the white paper "Air-Source VRF Mechanical Room Design Considerations for Outdoor Unit Placement in
Enclosures" on www.lg-vrf.com.

Selecting the Best LocationIndoor Units


General Dos

Place the unit where air circulation will not be blocked.


Place the unit where drainage can be obtained easily and to minimize the length of the condensate drain piping.
Place the unit where noise prevention is taken into consideration.
Ensure there is sufficient supply air and maintenance space.
Locate the indoor unit in a location where it can be easily connected to the outdoor unit / heat recovery unit.
Follow the clearance and installation area weight requirements designated for each indoor unit type
General Donts

Avoid installing the unit near high-frequency generators.


Do not install the unit near a doorway.
The unit should not be installed near a heat or steam source, or where considerable amounts of oil, iron powder, or flour are used. (These
materials may generate condensate, cause a reduction in heat exchanger efficiency, or the drain to malfunction. If this is a potential problem, install a ventilation fan large enough to vent out these materials.)
For more detailed installation requirements for each specific indoor unit type, refer to the Indoor Unit Engineering and /
or Installation Manuals.

Installing in an Area Exposed to Unconditioned Air

In some installation applications, areas (floors, walls) in some rooms may be exposed to unconditioned air (room may be above or next to an
unheated garage or storeroom). To countermeasure:
Verify that carpet is or will be installed (carpet may increase the temperature by three [3] degrees).
Add insulation between the floor joists.
Install radiant heat or another type of heating system to the floor.

The unit should not be installed where sulfuric acid and flammable or corrosive gases are generated, vented into, or stored. There is risk of
fire, explosion, and physical injury or death.
The unit may be damaged, may malfunction, and / or will not operate as designed if installed in any of the conditions listed.

If the unit is installed near a body of water, the installation parts are at risk of being corroded. Appropriate anti-corrosion methods should be
taken for the unit and all installation parts.
120

APPLICATION GUIDELINES

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

PLACEMENT CONSIDERATIONS
Heat Recovery Units

Heat recovery units are for use with ARUB Series heat recovery systems only.
Select an installation space for the heat recovery unit that meets the following conditions:
Install the heat recovery unit indoors in a level and upright position.
Ensure there is enough space in the installation area for service access.
Refrigerant pipes must not exceed lengths specified by LG Electronics.
Do not install the heat recovery unit in a location where it would be subjected to strong radiation heat from heat sources.
Avoid an installation environment where oil splattering, vapor spray, or high-frequency electric noise could occur.
Install the heat recovery unit in a location where any sound it may generate will not disturb occupants in the surrounding rooms.
Install the refrigerant piping and electrical wiring system in an easily accessible location.
Condensate drain piping is not required.
Figure 13: Dimensions for Heat Recovery Units.

Figure 14: Minimum Service Clearances for Heat Recovery Units.

18-15/16

Application Guidelines

3-15/16 more
(Servicing space)

13-5/8

Cap the pipes at the end of


series-connected branches
of heat recovery units.

11-13/16
more

11-13/16
more

Servicing space

Servicing space

2
3

17-3/4

3-15/16 more
(Servicing space)

Table 36: Heat Recovery Unit Parts.

4-7/8

Tag
No.

5-1/16

2-3/8

1
2

6
16-1/2

1-3/16

5-7/16

3
4

8-5/8

7-3/16

6-7/8
1
2

Servicing space2

Servicing space2

17-3/4

2-7/16

17-3/4
more

11-13/16
more

Inspection door 1
(servicing space)

17-7/8

6
7

Part Name
Low pressure vapor pipe
connection port
High pressure vapor pipe
connection port
Liquid pipe connection
port
Indoor unit vapor pipe
connection port
Indoor unit liquid pipe
connection port
Control box
Hanger bracket

Connection Size(in.)/Type
PRHR022A PRHR032A PRHR042A
7/8 Braze

1-1/8 Braze 1-1/8 Braze

3/4 Braze

7/8 Braze

7/8 Braze

3/8 Braze

1/2 Braze

5/8 Braze

5/8 Braze

5/8 Braze

5/8 Braze

3/8 Braze

3/8 Braze

3/8 Braze

3/8 or 5/16

3/8 or 5/16

3/8 or 5/16

6-7/8

Locate the inspection door at the control box side of the heat recovery unit.
If reducers are used, space for service access must be increased to match the dimensions of the reducer.
Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

APPLICATION GUIDELINES

121

PLACEMENT CONSIDERATIONS
Heat Recovery Units

Figure 15: Heat Recovery Unit Types.

MULTI V IV Outdoor Unit Engineering Manual

PRHR022A (Two [2] ports)

PRHR032A (Three [3] ports)

3 4
1 2

PRHR042A (Four [4] ports)

1. Each heat recovery unit has a capacity up to 192,000 Btu/h.


2. Heat recovery units connected in series have a total capacity up to 192,000 Btu/h per series string. Series string is defined as heat
recovery units piped in series.
3. Elevation difference between heat recovery units connected in series is permitted, but should not exceed 16 feet.
4. Each port on the heat recovery unit has a capacity up to 54,000 Btu/h.
5. Each port can be connected to a maximum of eight (8) indoor units. When multiple indoor units are connected to one port, all indoor units
on that port must operate in the same mode (cooling or heating).
6. If an indoor unit larger than 54,000 Btu/h is to be used, two (2) ports must be twinned using a reverse Y-branch.
7. Connect largest indoor unit to first port of the heat recovery unit.
8. Elevation difference between the heat recovery unit and the indoor unit(s) should not exceed 49 feet.

122

APPLICATION GUIDELINES

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

REFRIGERANT PIPING
DESIGN & LAYOUT
BEST PRACTICES
Design Guideline Summary on page 124

Pipe Sizing for ARUN Series Heat Pump Systems on page 126
Pipe Sizing for ARUB Series Heat Recovery Systems on page 130
LG Engineered Y-branch Kits on page 133
LG Engineered Header Kits on page 138
LATS Calculated Refrigerant Charge on page 140
Selecting Field-Supplied Copper Tubing on page 143
General Information / Guidelines on page 146

REFRIGERANT PIPING DESIGN


Piping Design Guideline Summary

The proper design and installation of the refrigerant piping system is a critical element of a Multi V system. As detailed on page 108, LG
provides engineers LG Air Conditioner Technical Solution (LATS) software to help design LG Multi V air conditioning systems. The following
pages are examples of manual pipe size calculations for Multi V refrigerant piping systems.

MULTI V IV Outdoor Unit Engineering Manual

The information represents how LATS Multi V Piping Design software works when designing the piping system for Multi V
heat pump and heat recovery units. It should not replace the use of LGs LATS Multi V complimentary selection software, but
should instead be used in conjunction with it. Contact your LG representative to obtain a copy of the software and the users
manual.

Refrigerant Piping System Quality Assurance

To ensure that the refrigerant piping design meets LGs quality standards, a LATS refrigerant piping design software report must be provided
with every Multi V IV order. Following the installation, if any changes or variations to the design were necessary, an as-built LATS piping
design software report must be provided to LG prior to system commissioning.
Systems that are close to the standard application limits may be converted into a conditional application by field changes to pipe equivalent
lengths. User should always check the LATS report actual pipe layout versus pipe limits. The user may want to increase pipe lengths when
conditions close to the standard application limits are present, forcing increased pipe diameters seen in conditional applications to be used
and avoiding pipe changes due to field installation variations.

Any field changes, such as re-routing, shortening or lengthening a pipe segment, adding or eliminating elbows and/or fittings, re-sizing,
adding, or eliminating indoor units, changing the mounting height or moving the location of a device or fitting during installation should be
done with caution and ALWAYS VERIFIED in LATS MULTI V SOFTWARE before supplies are purchased or installed. Doing so ensures
profitable installation, eliminates rework, and ensures easier system commissioning.

Creating a Balanced Piping System

Unlike designing duct-work or chilled and hot water pipe systems where balancing dampers, ball valves, orifices, circuit setters, or other
flow control devices can be installed to modify or balance the flow of cooling medium, these cannot be used in a VRF system. Therefore,
variable refrigerant flow systems have to be designed to be self balanced. Balanced liquid refrigerant distribution is solely dependent on
the designer choosing the correct pipe size for each segment. Pipe sizing considerations include pipe length, pipe segment pressure drop
relative to other pipe segments in the system, type and quantity of long radius elbows, bends present, fitting installation orientation, and end
use device elevation differences.

It is imperative the designer avoids creating excessive pressure drop. When liquid refrigerant is subjected to excessive pressure drop, liquid
refrigerant will change state and flash to vapor. Vapor present in a stream of liquid refrigerant before reaching the electronic expansion
valve (EEV) results in a loss of system control and causes damage to the valve. The pipe system must be designed in a manner that avoids
the creation of unwanted vapor.

124

REFRIGERANT DESIGN

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

REFRIGERANT PIPING DESIGN


Piping Design Guideline Summary

Elevation Differential HRU to HRU: 49'

Longest pipe length: 656' actual (738' equiv.)


Elevation Differential
HRU to IDU: 49'

Elevation Differential Two IDUs


Connected to One HRU: 49'

Max. Total Equivalent Piping Length: 3,280'

Max. Total Equivalent Piping Length: 3,280'

Table 37: Equivalent Piping Length for Y-branches, Headers, and Other Piping Components.
Component
Long Radius Elbow (ft.)
Y-branch (ft.)1
Header (ft.)
Heat Recovery Unit (ft.)
(For ARUB Heat Recovery Units only)

1/4

3/8

1/2

5/8

3/4

7/8

0.5

0.6

0.7

0.8

1.2

1.3

Size (Inches)
1
1-1/8 1-1/4 1-3/8 1-1/2 1-5/8 1-3/4 2-1/8
1.5

1.6

1.8

2.0

2.1

2.3

2.5

2.8

1.6
3.3
8.2

Kit for ARUN Heat Pump systems contains two Y-branches: one for liquid and one for vapor; Kit for ARUB Heat Recovery systems contains three Ybranches: one for liquid, one for low-pressure vapor, one for high-pressure vapor.
1

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

REFRIGERANT DESIGN

125

Refrigerant Piping Design & Layout Best Practices

Elevation Differential ODU to IDU: 360'

Elevation Differential IDU to IDU: 131'

Longest pipe length after first branch: 131' (295' conditional)

Figure 17: Typical VRF Heat Recovery System Building Layout Listing
the Piping Limitations..

Elevation Differential ODU to IDU: 360'

Elevation Differential IDU to IDU: 131'

Longest pipe length: 656' actual (738' equiv.)

Figure 16: Typical VRF Heat Pump System Building Layout Listing the
Piping Limitations.

REFRIGERANT PIPING DESIGN


Piping Design Guideline Summary

Pipe Sizing for ARUN Series Heat Pump Systems


Figure 18: Heat Pump Triple-Frame Connections.
Slave2
Slave1

MULTI V IV Outdoor Unit Engineering Manual

Master

ARCNN21 and ARCNN31


Outdoor Unit Connector
Pipe Accessories

A1

A2
ARCNN21

A3

(Multi-frame Outdoor Unit


Y-branch Connector)

D (main pipe
sized by LATS)

B
ARCNN31

To Indoor Units

(Multi-frame Outdoor Unit


Y-branch Connector)

For dual-frame systems, the pipe segment connecting the two outdoor unit frames contains a Y-branch connector. The
two pipe segments ("A") that connect the multi-frame Y-branch fitting to each outdoor unit frame must be the same
diameter of the outdoor unit pipe connection.
Similar for triple-frame systems, the pipe segments ("A1, A2, A3") that connect the multi-frame outdoor unit Y-branch
fittings to the outdoor unit frames must also match the outdoor unit frame pipe diameter. Main pipe segment D diameters are sized by LATS. See the table below to properly size the diameter of pipe segment B.
Table 38: Heat Pump Triple-Frame Connection Pipe Sizes.
Size (tons)
26
28
30
32
34
36
38
40
42

Model

Master

Slave1

Slave2

ARUN312BTE4
ARUN312DTE4
ARUN336BTE4
ARUN336DTE4
ARUN360BTE4
ARUN360DTE4
ARUN384BTE4
ARUN384DTE4
ARUN408BTE4
ARUN408DTE4
ARUN432BTE4
ARUN432DTE4
ARUN456BTE4
ARUN456DTE4
ARUN480BTE4
ARUN480DTE4
ARUN504BTE4
ARUN504DTE4

ARUN144BTE4
ARUN144DTE4
ARUN144BTE4
ARUN144DTE4
ARUN144BTE4
ARUN144DTE4
ARUN145BTE4
ARUN145DTE4
ARUN145BTE4
ARUN145DTE4
ARUN145BTE4
ARUN145DTE4
ARUN169BTE4
ARUN169DTE4
ARUN169BTE4
ARUN169DTE4
ARUN169BTE4
ARUN169DTE4

ARUN096BTE4
ARUN096DTE4
ARUN096DTE4
ARUN096DTE4
ARUN121BTE4
ARUN121DTE4
ARUN145BTE4
ARUN145DTE4
ARUN145BTE4
ARUN145DTE4
ARUN145BTE4
ARUN145DTE4
ARUN145BTE4
ARUN145DTE4
ARUN169BTE4
ARUN169DTE4
ARUN169BTE4
ARUN169DTE4

ARUN072BTE4
ARUN072DTE4
ARUN096BTE4
ARUN096DTE4
ARUN096BTE4
ARUN096DTE4
ARUN096BTE4
ARUN096DTE4
ARUN121BTE4
ARUN121DTE4
ARUN145BTE4
ARUN145DTE4
ARUN145BTE4
ARUN145DTE4
ARUN145BTE4
ARUN145DTE4
ARUN169BTE4
ARUN169DTE4

Liquid

5/8"

3/4"

Vapor

1-1/8"

1-3/8"

Largest-capacity outdoor units must be the master in a multi-frame system and placed in the position closest to pipe segment "D" in
the figure above.
Single-compressor outdoor units (72,000 Btu/h capacity) cannot be the master outdoor units in a multi-frame system.
Master outdoor unit capacity must be greater than or equal to the slave1 outdoor unit capacity, and, where applicable, slave1 outdoor
unit capacity must be greater than or equal to the slave2 outdoor unit capacity.
Insulate all refrigerant system piping and piping connections separately as detailed on page 151.
126

REFRIGERANT DESIGN

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

REFRIGERANT PIPING DESIGN


Piping Design Guideline Summary
The following is an example of manual pipe size calculations. Designers are highly encouraged to use LATS instead of manual calculations.

Y-branch Pipe Sizing When Installing a Triple-Frame System


Example: Five (5) indoor units connected

Slave2 ODU
Slave1 ODU
Master ODU

Elevation1: 360 feet

Larger-capacity outdoor units must be the


master in a multi-frame system.
Single-compressor outdoor units (72,000 Btu/h
capacity) cannot be the master outdoor unit in
a multi-frame system.
Master outdoor unit capacity must be greater
than or equal to the slave1 outdoor unit capac- ity, and, where applicable, slave1 outdoor unit
capacity must be greater than or equal to the
slave2 outdoor unit capacity.

Y-branch

To
outdoor
units

33
feet

To indoor units

Length: 492 feet (656 feet conditional application)


: 131 feet (295 feet conditional application)
B

Y-branch

IDU

B
C
IDU

IDU

C
C
IDU

Elevation2: 131 feet

IDU

Header Pipe Sizing When Installing a Single Outdoor Unit System


Example: Six (6) indoor units connected

ODU

Elevation1: 360 feet

ODU: Outdoor Unit.


IDU: Indoor Units.
A: Main Pipe from Outdoor Unit to Header.
C: Header to Indoor Unit.

Length: 492 feet (656 feet conditional application)


: 131 feet (295 feet
Header
conditional application)

C
IDU

IDU

C
IDU

C
IDU

C
IDU

Elevation2: 131 feet

Brazed Cap

C
IDU

See pages 128-129 for refrigerant pipe diameter and pipe length tables.
Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

REFRIGERANT DESIGN

127

Refrigerant Piping Design & Layout Best Practices

height1 16-7/16 feet

ODU: Outdoor Units.


IDU: Indoor Units.
A: Main Pipe from Outdoor Unit to Y-branch.
B: Y-branch to Y-branch.
C: Y-branch to Indoor Unit.

REFRIGERANT PIPING DESIGN


Piping Design Guideline Summary
The following is an example of manual pipe size calculations. Designers are highly encouraged to use LATS instead of manual calculations.

Combination Y-branch Pipe and Header Pipe Sizing When Installing a DualFrame System
Example: Five (5) indoor units connected

Slave ODU

ODU: Outdoor Units.


IDU: Indoor Units.
A: Main Pipe from Outdoor Unit to First Y-branch.
B: Y-branch to Y-branch / Header.
C: Y-branch / Header to Indoor Unit.

height1

Master ODU

To indoor units

fee

Larger-capacity outdoor units must be the master in a multiframe system.


Single-compressor outdoor units (72,000 Btu/h capacity)
cannot be the master outdoor units in a multi-frame system.
Master outdoor unit capacity must be greater than or equal
to the slave outdoor unit capacity.
Y-branches and other header branches cannot be installed
downstream of the initial header branch.

Header

A
B
Y-branch
(first)

IDU

IDU

IDU

Brazed Cap

131 feet

MULTI V IV Outdoor Unit Engineering Manual

33

Y-branch

To
outdoor unit

C
Y-branch
(second)

See pages 128-129 for refrigerant pipe diameter and pipe


length tables.
Table 39: Main Pipe (A) Diameter from Outdoor Unit to First Y-branch / Header Branch.
ODU
Capacity
(ton)
6
8
10-12
12-14*
14-18
20
22-28
30-42

Pipe diameter when pipe


length is <295 feet
(Standard)

Pipe diameter when pipe


length is 295 feet
(ODU IDU)

Pipe diameter when height


differential (ODU IDU)
is >164 feet

Liquid pipe Vapor pipe Liquid pipe Vapor pipe Liquid pipe Vapor pipe
(inches OD) (inches OD) (inches OD) (inches OD) (inches OD (inches OD)
3/8
3/8
1/2
5/8
5/8
5/8
3/4
3/4

3/4
7/8
1-1/8
1-1/8
1-1/8
1-3/8
1-3/8
1-5/8

1/2
1/2
5/8
3/4
3/4
3/4
7/8
7/8

*ARUN145BTE4 / ARUN145DTE4 and ARUN169BTE4 / ARUN169DTE4 only.

7/8
1-1/8
No Increase
1-1/4
1-1/4
No Increase
1-1/2
No Increase

Table 41: Indoor Unit Connecting Pipe from Branch (C).


Indoor Unit Capacity1
Liquid pipe (inches OD)
19,100
54,600
76,400

1/4
3/8
3/8

1/2
1/2
5/8
3/4
3/4
3/4
7/8
7/8

No Increase
No Increase
No Increase
No Increase
No Increase
No Increase
No Increase
No Increase

IDU

Table 40: Refrigerant Pipe Diameter (B) from


Y-branch to Y-branch / Header.
Downstream Total Liquid pipe Vapor pipe
Capacity of IDUs (inches OD) (inches OD)
(Btu/h)1
19,100
54,600
76,400
114,700
172,000
229,400
248,500
344,000
592,500

REFRIGERANT DESIGN

1/4
3/8
3/8
3/8
1/2
5/8
5/8
3/4
3/4

1/2
5/8
3/4
7/8
1-1/8
1-1/8
1-3/8
1-3/8
1-5/8

1
For the first branch pipe, use the branch pipe that matches main
pipe A diameter.

Vapor pipe (inches OD)


1/2
5/8
3/4

1
9,600-24,200 Btu/h 4-way 3 feet x 3 feet Cassette and 15,400-24,200 Btu/h High Static Ducted indoor units have 3/8 (liquid) and 5/8
(vapor).

128

IDU

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

REFRIGERANT PIPING DESIGN


Piping Design Guideline Summary
The following is an example of manual pipe size calculations. Designers are highly encouraged to use LATS instead of manual calculations.
Table 42: Pipe Capabilities.
Length

Elevation1

height1

Longest actual pipe length


Equivalent pipe length1
492 feet (656 feet conditional application)
574 feet (738 feet conditional application)
Longest pipe length after first branch
131 feet (295 feet conditional application)
Elevation differential (Outdoor Unit Indoor Unit)
Height 360 feet
Elevation differential (Indoor Unit Indoor Unit)
height 131 feet
Elevation differential (Outdoor Unit Outdoor Unit)
16.4 feet
33 feet (Max. 43 feet for ODU 12 tons)
Distance between ODU to ODU
20 inches
Distance between fittings and IDU
20 inches
Distance between fittings and Y-branches / Headers
20 inches
Distance between two Y-branches / Headers

For calculation purposes, assume equivalent pipe length of Y branches to be 1.6 feet, and the equivalent pipe length of headers to be 3.3 feet.

Always reference the LATS Multi V software report.


Connection piping from branch to branch cannot exceed the main
pipe diameter (A) used by the outdoor unit.
Y-branches and other header branches cannot be installed downstream of the initial header branch.

Install the header branch so that the pipe distances between


the between the connected indoor units are minimized. Large
differences in pipe distances can cause indoor unit performances
to fluctuate.

Conditional Applications

Conditional application is computed in LATS. See below for an explanation of when pipes are upsized.
If the equivalent length between the first Y-branch to the farthest indoor unit is >131 feet (up to 295 feet maximum):
Pipe segment diameters between the first Y-branch and the second Y-branch should be sized up by one. This applies to both liquid and
vapor pipes. If the next size up is not available, or if the piping segment diameters are the same as main pipe (A) diameters, sizing up is
not possible.
While calculating the entire refrigerant pipe length, pipe lengths for B should be multiplied by two: A+(Bx2)+C 3,281 feet.
Length of pipe (C) from each indoor unit to the closest Y-branch or header 131 ft.
[Length of pipe from outdoor unit to farthest indoor unit (A+B+C)] - [Length of pipe from outdoor unit to closest indoor unit (A+B+C)] 131
feet.
If the pipe (B) diameters after the first branch are bigger than the main pipe (A) diameters, pipe (B) should changed to match main pipe (A)
sizes.
Example: When an indoor unit combination ratio of 120% is connected to a 22-ton outdoor unit:
Outdoor unit main pipe (A) diameters: 1-3/8 inches (vapor) and 5/8 inches (liquid).
1. Pipe (B) diameters: 1-3/8 (vapor) and 3/4 (liquid) (after the first branch, when indoor unit combination ratio is 120% [26 tons]).
2. After the first branch, pipe (B) diameters must be changed to 1-3/8 inches (vapor) and 5/8 inches (liquid) to match main pipe (A)
sizes.
Instead of using the total indoor unit capacity to choose main pipe (A) diameters, use outdoor unit capacity to choose downstream main pipe
(A) diameters. Do not permit connection pipes (B) from branch to branch to exceed main pipe (A) diameters as indicated by outdoor unit
capacity. Example: When an indoor unit combination ratio of 120% is connected to a 20-ton outdoor unit (24 tons), and indoor unit with a
7,000 Btu/h capacity is located at the first branch:
1. Main pipe (A) diameters on a 20-ton outdoor unit: 1-1/8 inches (vapor) and 5/8 inches (liquid).
2. Pipe diameters between first and second branches, however, are: 1-3/8 (vapor) and 3/4 (liquid) (connected downstream indoor unit
capacity is 20 tons).
3. If main pipe (A) diameters of a 20-ton outdoor unit are 1-1/8 (vapor) and 5/8 (liquid), then the pipe diameters between the first and
second branches should be changed to match.

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

REFRIGERANT DESIGN

129

Refrigerant Piping Design & Layout Best Practices

Elevation2

Total pipe length


A + B + C 3,280 feet

REFRIGERANT PIPING DESIGN


Piping Design Guideline Summary
The following is an example of manual pipe size calculations. Designers are highly encouraged to use LATS instead of manual calculations.

Pipe Sizing for ARUB Series Heat Recovery Systems


Figure 19: Heat Recovery Triple-Frame Connections.
Slave2
Slave1

MULTI V IV Outdoor Unit Engineering Manual

Master

ARCNB21 and ARCNB31


Outdoor Unit Connector
Pipe Accessories

A1

A2

A3
ARCNB21

(Multi-frame Outdoor Unit


Y-branch Connector)

D (main pipe
sized by LATS)

To Heat
Recovery Units

ARCNB31

(Multi-frame Outdoor Unit


Y-branch Connector)

For dual-frame systems, the pipe segment connecting the two outdoor unit frames contains a Y-branch connector. The
two pipe segments ("A") that connect the multi-frame Y-branch fitting to each outdoor unit frame must be the same
diameter of the outdoor unit pipe connection.
Similar for triple-frame systems, the pipe segments ("A1, A2, A3") that connect the multi-frame outdoor unit Y-branch
fittings to the outdoor unit frames must also match the outdoor unit frame pipe diameter. Main pipe segment D diameters are sized by LATS. See the table below to properly size the diameter of pipe segment B.
Table 43: Heat Recovery Triple-Frame Connection Pipe Sizes.
Size (tons)
26
28
30
32
34
36
38
40
42

Model

Master

Slave1

Slave2

ARUB312BTE4
ARUB312DTE4
ARUB336BTE4
ARUB336DTE4
ARUB360BTE4
ARUB360DTE4
ARUB384BTE4
ARUB384DTE4
ARUB408BTE4
ARUB408DTE4
ARUB432BTE4
ARUB432DTE4
ARUB456BTE4
ARUB456DTE4
ARUB480BTE4
ARUB480DTE4
ARUB504BTE4
ARUB504DTE4

ARUB144BTE4
ARUB144DTE4
ARUB144BTE4
ARUB144DTE4
ARUB144BTE4
ARUB144DTE4
ARUB145BTE4
ARUB145DTE4
ARUB145BTE4
ARUB145DTE4
ARUB145BTE4
ARUB145DTE4
ARUB169BTE4
ARUB169DTE4
ARUB169BTE4
ARUB169DTE4
ARUB169BTE4
ARUB169DTE4

ARUB096BTE4
ARUB096DTE4
ARUB096DTE4
ARUB096DTE4
ARUB121BTE4
ARUB121DTE4
ARUB145BTE4
ARUB145DTE4
ARUB145BTE4
ARUB145DTE4
ARUB145BTE4
ARUB145DTE4
ARUB145BTE4
ARUB145DTE4
ARUB169BTE4
ARUB169DTE4
ARUB169BTE4
ARUB169DTE4

ARUB072BTE4
ARUB072DTE4
ARUB096BTE4
ARUB096DTE4
ARUB096BTE4
ARUB096DTE4
ARUB096BTE4
ARUB096DTE4
ARUB121BTE4
ARUB121DTE4
ARUB145BTE4
ARUB145DTE4
ARUB145BTE4
ARUB145DTE4
ARUB145BTE4
ARUB145DTE4
ARUB169BTE4
ARUB169DTE4

Liquid

B
Low Pressure
Vapor

5/8"

3/4"

1-1/8"

1-3/8"

High Pressure
Vapor
7/8"

1-1/8"

Largest-capacity outdoor units must be the master in a multi-frame system and placed in the position closest to pipe segment "D" in
the figure above.
Single-compressor outdoor units (72,000 Btu/h capacity) cannot be the master outdoor units in a multi-frame system.
Master outdoor unit capacity must be greater than or equal to the slave1 outdoor unit capacity, and, where applicable, slave1 outdoor
unit capacity must be greater than or equal to the slave2 outdoor unit capacity.
Insulate all refrigerant system piping and piping connections separately as detailed on page 151.
130

REFRIGERANT DESIGN

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

REFRIGERANT PIPING DESIGN


Piping Design Guideline Summary
The following is an example of manual pipe size calculations. Designers are highly encouraged to use LATS instead of manual calculations.

Pipe Sizing for ARUB Series Heat Recovery Systems

Example: Triple-frame system, four (4) heat recovery units,


one (1) header, and twelve (12) indoor units connected

Slave2
ODU Slave1
ODU

height1
16-7/16 feet

Master ODU

Y-branch (second)

Case 1
C

49 feet

Elevation4

Elevation1

Elevation2

IDU

To indoor units

HRU

Connection piping from branch to branch cannot exceed the main


pipe diameter (A) used by the outdoor unit.
Install the header branches or heat recovery units so that the pipe
distances between the connected indoor units are minimized.
Large differences in pipe distances can cause indoor unit performances to fluctuate.
Y-branches and other headers branches cannot be installed downstream of the initial header branch.
Total capacity of indoor units in series connection of heat
recovery units 192,400 Btu/h.
If large capacity indoor units (>12,000 Btu/h with piping sizes
>5/8 / 3/8) are installed, the valve group setting should be used.
(Refer to the PCB of the heat recovery unit for the valve group
control setting.)
Always reference the LATS Multi V software report.

Y-branch

To
outdoor unit

HRU

C
IDU

HRU

IDU

HRU

Case 2
IDU

C
IDU

IDU

16 feet

IDU

Y-branch (first)
C

B
Header
C
IDU

C
Elevation3

Closest
IDU

Brazed
cap

C
IDU

Farthest
IDU

IDU

Case 1: Maximum height is 131 feet if installed with a Y-branch.


Case 2: Maximum height is 16 feet in heat recovery control unit series connection.

See pages 131-132 for refrigerant pipe diameter and pipe length
tables.

Larger-capacity outdoor units must be the master in a multi-frame


system.
Single-compressor outdoor units (72,000 Btu/h capacity) cannot be the
master outdoor unit in a multi-frame system.
Master outdoor unit capacity must be greater than or equal to the
slave1 outdoor unit capacity, and, where applicable, slave1 outdoor unit
capacity must be greater than or equal to the slave2 outdoor unit
capacity.

Table 44: Main Pipe (A) Diameter from Outdoor Unit to First Y-branch.
ODU
Capacity
(ton)
6
8
10
12
12-14*
14-16
18-20
22-28
30-42

Standard Pipe Diameter


Liquid Pipe
(inches OD)
3/8
3/8
1/2
1/2
5/8
5/8
5/8
3/4
3/4

Low Pressure Vapor High Pressure Vapor


Pipe (inches OD)
Pipe (inches OD)
3/4
7/8
1-1/8
1-1/8
1-1/8
1-1/8
1-3/8
1-3/8
1-5/8

*ARUB145BTE4 / ARUB145DTE4 and ARUB169BTE4 / ARUB169DTE4 only.

5/8
3/4
3/4
7/8
7/8
7/8
1-1/8
1-1/8
1-1/8

Pipe diameter when pipe length is 295 feet or when height


differential (ODU IDU) is >164 feet
Liquid Pipe
Low Pressure Vapor High Pressure Vapor
(inches OD)
Pipe (inches OD)
Pipe (inches OD)
1/2
1/2
5/8
5/8
3/4
3/4
3/4
7/8
7/8

No Increase
No Increase
No Increase
No Increase
No Increase
No Increase
No Increase
No Increase
No Increase

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

No Increase
No Increase
No Increase
No Increase
No Increase
No Increase
No Increase
No Increase
No Increase

REFRIGERANT DESIGN

131

Refrigerant Piping Design & Layout Best Practices

ODU: Outdoor Units.


HRU: Heat Recovery Units.
IDU: Indoor units.
A: Main Pipe from Outdoor Unit to First Y-branch.
B: Heat Recovery Unit to Heat Recovery Unit, Y-branch to Heat
Recovery Unit, Heat Recovery Unit to Header, or Y-branch to Y-branch.
C: Heat Recovery Unit / Header to Indoor Unit.

REFRIGERANT PIPING DESIGN


Piping Design Guideline Summary
The following is an example of manual pipe size calculations. Designers are highly encouraged to use LATS instead of manual calculations.

MULTI V IV Outdoor Unit Engineering Manual

Table 45: Refrigerant Pipe (B) Diameter between Y-branches and Y-branches / Heat Recovery Unit / Headers.
Vapor pipe (inches OD)
Downstream IDU total capacity (Btu/h) Liquid pipe (inches OD)
Low pressure
High pressure
19,100
<54,600
<76,400
<114,700
<172,000
<229,400
<248.500
<344,000
<592,500

1/4
3/8
3/8
3/8
1/2
5/8
5/8
3/4
3/4

Table 46: Indoor Unit Connecting Pipe from Branch (C).


Indoor Unit Capacity1
Liquid pipe (inches OD)
19,100
54,600
76,400
95,900

1/4
3/8
3/8
3/8

1/2
5/8
3/4
7/8
1-1/8
1-1/8
1-3/8
1-3/8
1-5/8

3/8
1/2
5/8
3/4
7/8
7/8
1-1/8
1-1/8
1-3/8

Vapor pipe (inches OD)


1/2
5/8
3/4
7/8

9,600-24,200 Btu/h 4-way 3 feet x 3 feet Cassette and 15,400-24,200 Btu/h High Static Ducted IDUs have 3/8 (liquid) and 5/8 (vapor).

Table 47: Pipe Capabilities.


Longest actual pipe length
Equivalent pipe length1
492 feet (656 feet conditional application)
574 feet (738 feet conditional application)
Longest pipe length after first branch

131 feet (295 feet conditional application)


Elevation differential (Outdoor Unit Indoor Unit)
Elevation1
Height 360 feet
Elevation differential (Indoor Unit Indoor Unit)
Elevation2
height 131 feet
Elevation differential (Indoor Unit Heat Recovery Unit) [single heat recovery unit or series heat recovery units]
Elevation3
49 feet
Elevation differential (Indoor Unit Indoor Unit [connected to same Heat Recovery Unit])
Elevation4
49 feet
Elevation differential (Outdoor Unit Outdoor Unit)
height1
16.4 feet
33 feet (Max. 43 feet for Outdoor Unit 12 tons)
Distance between Outdoor Unit to Outdoor Unit
20 inches
Distance between fittings and Indoor Unit
20 inches
Distance between fittings and Y-branches / Headers
20 inches
Distance between two Y-branches / Headers

Length

Total pipe length


A + B + C 3,280 feet

Height differential between two Heat Recovery Units if installed with a


Y-branch
Height differential between two series-piped Heat Recovery Units

49 feet
16 feet

For calculation purposes, assume equivalent pipe length of Y-branches to be 1.6 feet, and the equivalent pipe length of headers to be 3.3 feet.

Conditional Applications

Conditional application is computed in LATS. See below for an explanation of when pipes are upsized.
If the equivalent length between the first Y-branch to the farthest indoor unit is >131 feet (maximum 295 feet):
Pipe segment diameters between the first branch and the last branch should be sized up by one. This applies to both liquid and low / high
vapor pipes. If the next size up is not available, or if the pipe segment diameters are the same as main pipe (A) diameters, sizing up is not
possible.
While calculating total refrigerant piping length, pipe (B) segment lengths between the first Y-branch and second Y-branch, and between the second
Y-branch and the heat recovery unit should be calculated by two.
Length of pipe (C) from each indoor unit to the closest Y-branch, header, or heat recovery unit 49 feet.
[Length of pipe from outdoor unit to farthest indoor unit (A+B+C)] - [Length of pipe from outdoor unit to closest indoor unit (A+B+C)] 131 feet.
132

REFRIGERANT DESIGN

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

REFRIGERANT PIPING DESIGN


LG Engineered Y-branch Kits

No Substitutions

Only LG supplied Y-branch fittings can be used to join one pipe segment to two or more segments. Third-party or field-fabricated Tees, Yfittings, Headers, or other branch fittings are not qualified for use with LG Multi V IV systems. The only field-provided fittings allowed in a Multi
V IV piping system are 45 and 90 elbows.

Y-Branch Kits

LG Y-Branch Kits Consist of:

Y-branches:
For heat pump systems - one liquid line and one vapor line (two [2] total)
For heat recovery systems - one liquid line, one low-pressure vapor line, and one highpressure vapor line(three [3] total)
Reducer fittings as applicable.
Molded clam-shell type peel and stick insulation covers.

Figure 20: Indoor Unit Y-branch Vertical


Installation Alignment Specification.

Vertical up configuration.

Vertical down configuration.

Indoor Unit Y-Branches

Indoor unit Y-branches may be installed in horizontal or vertical configurations. When


installed vertically, position the Y-branch so the straight-through leg is 3 of plumb. When
installed horizontally, position the Y-branch so the take-off leg is level and shares the same
horizontal plane as the straight-through leg 5 rotation.
Indoor unit Y-branches should always be installed with the single port facing the outdoor unit,
the two-port end facing indoor units (or heat recovery unit for heat recovery systems only).
The first indoor unit Y-branch kit must be located at least three (3) feet from
the outdoor unit. Provide a minimum of 20 inches between a Y-branch and any Figure 21: Horizontal Configuration.
other fittings or indoor unit piped in series.
Branch Leg
Straight-through Leg
There is no limitation on the number of indoor unit Y-branches that can be
installed, but there is a limitation on the number of indoor units connected to a
single outdoor unit.
It is recommended that when a Y-branch is located in a pipe chase or other
Y-branch Inlet
concealed space, access doors should be provided for inspection access.

Outdoor Unit Y-Branches

Outdoor unit Y-branches can only be installed in a horizontal configuration. When installed
horizontally, position the Y-branch so it is within 5 from level.
Outdoor unit Y-branches must always be installed with the two-port ends connected to the
piping directly coming from the
Figure 23: Y-branch Insulation and Pipe Detail.
outdoor units, and the single
port connected to the indoor unit
refrigerant piping system supporting the indoor units. Outdoor
unit Y-branches are usually
installed close to the outdoor
unit, leaving enough space for
servicing and maintenance.

Horizontal Plane

Figure 22: Diagram of an Incorrect Outdoor


Unit Y-branch Installation.

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

ext

n
To

or

do

in
To

nc

bra

it

un

REFRIGERANT DESIGN

133

Refrigerant Piping Design & Layout Best Practices

LG Y-branch and kits are highly engineered devices designed to evenly divide the flow of refrigerant, and are used to join one pipe segment
to two or more segments. There are two types of Y-branches used in LG VRF systems: Y-branches that combine two or three outdoor units
to make up one large-capacity outdoor unit (also known as multi-frame connectors), or Y-branches used with the indoor units in the refrigerant piping system at each transition. Field-supplied T fittings or Y branches will not be accepted. Do not install Y-branches backwards;
refrigerant flow cannot make U-turns through Y-branches. The equivalent pipe length of each Y-branch (1.6) must be added to each pipe
segment entered into LATS piping design software.

REFRIGERANT PIPING DESIGN


LG Engineered Y-branch Kits

Indoor Unit Y-branches for ARUN Series Heat Pump Systems


Unit: Inch

Vapor pipe

Models
I.D. 1/2

Liquid pipe

I.D. 1/2

I.D. 5/8

I.D. 5/8

2-15/16

I.D. 1/2

ARBLN01621

I.D. 3/8

I.D. 1/2

O.D. 5/8

O.D. 3/8
2-3/4

2-3/4
I.D. 7/8

I.D. 3/4

I.D. 1

I.D. 5/8

I.D. 3/4

I.D. 5/8

ARBLN03321

I.D. 3/4

I.D. 7/8

I.D. 3/4

O.D. 1-1/4

I.D. 7/8

O.D. 1/2

I.D. 5/8

18-9/16
20-3/8
I.D. 3/4

2
3-9/16

4-3/4
I.D. 1/2
3
O.D. 5/8

I.D. 7/8

I.D. 3/4

O.D. 5/8

I.D. 1/2
I.D. 3/8

2
I.D. 3/4

I.D. 5/8

I.D. 1/2 3-13/16


3

16-3/8
17-1/2

I.D. 1-5/8

I.D. 7/8

2
2-3/4

4-15/16

5-1/8

O.D. 1-1/8

I.D. 3/4
I.D. 5/8

I.D. 1-1/2

O.D. 1-3/8
3

I.D. 7/8

I.D. 3/4

I.D. 1-5/8
O.D. 1-1/2

I.D. 5/8

2-3/4

4-3/8

I.D. 1-1/8
2

I.D. 1-1/8
I.D. 1-3/8
I.D. 7/8

I.D. 1-1/2

I.D. 3/8
O.D. 1/2

I.D. 1/4
2

4-3/4
I.D. 1-1/2

I.D. 1-5/8

I.D. 3/8

I.D. 1-1/8

I.D. 1-3/8

I.D. 1-3/8

3-5/16
3

3-9/16

I.D. 1/2
I.D. 3/4

14-5/8
15-1/2

4-3/4

REFRIGERANT DESIGN

O.D. 3/4

I.D. 1/2
2

I.D. 5/8

I.D. 3/4

3-13/16

I.D. 1-3/8

I.D. 1-1/4

O.D. 7/8

I.D. 5/8

I.D. 1/2

I.D. 1/2

14-13/16
15-215/16
I.D. 1-1/8

I.D. 5/8

I.D. 3/4

I.D. 5/8

I.D. 5/8
2

ARBLN07121

2-15/16

I.D. 1/4

4-3/8

I.D. 7/8

I.D. 1-1/4

I.D. 1/2

12-5/8
13-1/16

I.D. 3/4

I.D. 1-1/8

O.D. 7/8

I.D. 3/8

I.D. 1

3-3/16

2-3/4

I.D. 1/2

I.D. 7/8
O.D. 3/4

O.D. 1

I.D. 1/4

3-5/16

I.D. 1-1/8

I.D. 3/8

I.D. 3/8

I.D. 1/2

15-3//8
16-1/4

O.D. 3/4

I.D. 1/2

I.D. 1/2
2

ARBLN14521

2-15/16

I.D. 1/4

11-1/16
11-1/2

11-1/16
11-1/2
I.D. 3/4

134

I.D. 1/4

I.D. 3/8

MULTI V IV Outdoor Unit Engineering Manual

I.D. 3/8

I.D. 1/4

I.D. 5/8

O.D. 3/4
3

4-3/8

I.D. 7/8

O.D. 1/2

I.D. 3/8
I.D. 1/4)

3
3-3/16

4-3/4

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

4-3/8

REFRIGERANT PIPING DESIGN


LG Engineered Y-branch Kits

Indoor Unit Y-branches for ARUB Series Heat Recovery Units


Unit: Inch

Models

Low-Pressure Vapor Pipe


I.D. 1/2

I.D. 1/2

I.D. 5/8

Liquid pipe
I.D. 3/8

I.D. 1/4

I.D. 5/8

High-Pressure Vapor Pipe


I.D. 3/8

I.D. 1/4

I.D. 3/8

I.D. 3/8

I.D. 1/2

I.D. 1/2

I.D. 5/8

ARBLB01621

2-15/16

I.D. 3/8

2-15/16

I.D. 5/8

I.D. 1/2

I.D. 5/8

11-1/16
11-1/2

11-1/16
11-1/2

2-15/16

13-13/16
14-11/16

I.D. 1/2

I.D. 3/4
1

O.D. 3/8
2-3/4

2-3/4
I.D. 7/8
I.D. 1

I.D. 3/4

I.D. 5/8

I.D. 3/4

I.D. 5/8

ARBLB03321

I.D. 3/4

I.D. 1/2 3-5/16

15-3/8
16-1/4
I.D. 7/8

I.D. 1/2

I.D. 1-1/8

I.D. 3/8

O.D. 3/4
1

3-3/16

I.D. 1/2
I.D. 1/4

I.D. 5/8

I.D. 5/8

I.D. 1/2

1
I.D. 1-1/4

I.D. 3/4

I.D. 5/8

I.D. 1/2

14-13/16
15-15/16
I.D. 1-1/8

I.D. 1-3/8

O.D. 3/4

O.D. 1-1/4
1

I.D. 3/8

I.D. 7/8

O.D. 1/2

I.D. 1-1/2
18-9/16
20-3/8

ARBLB14521
I.D. 3/4
I.D. 5/8
O.D. 7/8
3

I.D. 1-5/8
2
I.D. 1/2

O.D. 5/8

O.D. 1-3/8
3

3-9/16

4-3/4
3

I.D. 3/4
I.D. 5/8

I.D. 3/4

I.D. 5/8

O.D. 5/8
I.D.
1-5/8

I.D. 1/2
I.D. 3/8

3
4-3/8

I.D. 7/8

O.D. 1/2

3-13/16

I.D. 1-1/4
I.D. 1-1/8

I.D. 1-1/8
17-7/8
19-3/8
O.D. 1/2

4-3/8

I.D. 1
3

O.D. 1
I.D. 7/8

I.D. 3/8

2
2-3/4

4-3/8

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

O.D. 3/4

I.D. 7/8

I.D. 5/8

I.D. 1/2

4-3/4

3-3/16

I.D. 3/4

O.D. 1
I.D. 3/4

I.D. 1
2

I.D. 7/8

O.D. 1-1/8

I.D. 1/2

I.D. 1-1/4
I.D. 1-1/8

I.D. 3/8
I.D. 1/4

3
3-3/16

I.D. 5/8

4-3/8

I.D. 1-1/4

3-13/16

I.D. 3/4

3
2-3/4

O.D. 3/4

O.D. 3/4

I.D. 5/8

I.D. 1-3/8

I.D 1/2

16-3/8
17-1/2

I.D. 1-1/2

5-1/8
2

2-3/4

4-15/16

I.D. 7/8

O.D. 1-1/2

I.D. 7/8

I.D. 1

2
2-3/4

I.D. 1-1/8
I.D. 1-3/8
I.D. 7/8

O.D. 3/4

I.D. 3/8

3
2-3/4

I.D. 3/4

I.D. 3/4
2

I.D. 7/8

O.D. 1/2

I.D. 5/8

I.D. 1-1/8
2

I.D. 1

15
16-1/8

O.D. 1/2

4-3/8

I.D. 1-3/8
I.D. 1-1/2

I.D. 1-5/8

I.D. 7/8

I.D. 1-1/8

I.D. 3/8
I.D. 1/4

I.D. 1-1/8

4-3/4

I.D. 1-3/8

I.D. 1/2

2-3/4

3-9/16

3-5/16

14-5/8
15-1/2

4-3/4

O.D. 5/8
I.D. 3/8

I.D. 1

I.D. 1/2
I.D. 3/4

3-13/16

I.D. 3/4
I.D. 1/2
2

I.D. 5/8

I.D. 3/4

3-13/16

I.D. 1-1/4

O.D. 7/8

I.D. 1/2

O.D. 5/8

4-3/8

I.D. 5/8

I.D.
5/8
3

I.D. 3/4
I.D. 7/8

16-9/16
17-1/2

2-15/16

4-3/8

I.D. 1-1/8

I.D. 5/8

I.D. 3/4
I.D. 7/8

I.D. 1

I.D. 1

I.D. 7/8

I.D. 7/8

I.D. 1/4

12-5/8
13-1/16

I.D. 7/8
O.D. 1

3
2-3/4

I.D. 3/8

I.D. 3/8

I.D. 3/4

I.D. 3/4

I.D. 1/2

I.D. 1/2
2

O.D. 3/4

I.D. 3/8

O.D. 5/8

ARBLB07121

I.D. 1/4

4-3/4

4-3/8

REFRIGERANT DESIGN

135

Refrigerant Piping Design & Layout Best Practices

I.D. 5/8
I.D. 1/2

REFRIGERANT PIPING DESIGN


LG Engineered Y-branch Kits

Outdoor Unit Y-branches for ARUN Series Heat Pump Systems

For Dual-Frame Heat Pump Systems

Unit: inch
Multi-Frame
Connector

Combination

Vapor pipe

Liquid pipe

16-3/8
16-1/16

I.D. 1-1/8

13-1/16
12-3/8

I.D. 1-1/8

I.D. 5/8

I.D. 5/8
I.D. 1/2

I.D. 1-3/8

3-5/16

I.D. 3/8

I.D. 3/4

I.D. 1/2 I.D. 5/8

ARCNN21

I.D. 1-1/2
I.D. 1-5/8

I.D. 1-1/8
O.D.1-3/8

O.D. 3/4

I.D. 7/8

I.D. 7/8

O.D. 1-1/8

I.D. 1/2
I.D. 3/8

O.D. 5/8

I.D.
3/4

5-1/8

2-3/4

4-3/4

4-3/8

For Triple-Frame Heat Pump Systems


Combination specification

Multi-Frame
Connector

Vapor pipe
16-3/8
16-1/16

I.D. 1-1/8

Liquid pipe
13-1/16
12-3/8
I.D. 5/8

I.D. 5/8

I.D. 1-1/8

I.D. 1/2

I.D. 1-1/4

4-3/8

I.D. 7/8

I.D. 1-3/8

I.D. 3/8

I.D. 3/4

I.D. 1/2

ARCNN21
I.D. 1-1/2
I.D. 1-5/8

3-5/16

I.D. 5/8

I.D. 1-1/8

I.D. 7/8

O.D.1-3/8

O.D. 3/4

O.D. 1-1/8

I.D.
3/4

5-1/8

I.D. 1/2
I.D. 3/8

O.D. 5/8

I.D. 7/8

2-3/4

4-3/4

4-3/8

16
13-15/16

13-3/16
11-1/16

I.D. 1-1/2

B
I.D. 1-5/8 I.D. 1-3/8

I.D. 1-3/8

B
ARCNN31

REFRIGERANT DESIGN

O.D. 3/4

O.D. 3/4

O.D. 1-3/8
O.D.1-1/8

I.D. 5/8

I.D. 7/8

I.D. 1/2

O.D. 1/2

4-3/8

4-3/4

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

I.D. 1/2

I.D. 3/8

I.D. 1/4

X2

I.D.
3/4

3-5/16

O.D. 3/4

I.D. 5/8

4-15/16

I.D.
7/8

I.D. 1-1/8
I.D. 1-5/8

136

4-3/8

MULTI V IV Outdoor Unit Engineering Manual

I.D. 1-1/4

4-3/8

I.D. 7/8

4-3/8

REFRIGERANT PIPING DESIGN


LG Engineered Y-branch Kits

Outdoor Unit Y-branches for ARUB Series Heat Recovery Units


For Dual-Frame Heat Recovery Systems

Unit: inch
Low-Pressure Vapor Pipe

Liquid Pipe
13-1/16

16-3/8
4.2
I.D. 1-1/8

I.D. 3/8

I.D. 1/2

I.D. 3/4

4-3/8

I.D. 1-3/8

I.D. 5/8

I.D. 1-5/8

I.D. 1/2

I.D. 1-1/2
O.D. 1-3/8

I.D. 7/8

5-1/8

4-3/8

I.D. 7/8

I.D.7/8

O.D.1

2-3/4

I.D. 3/8

O.D. 1
I.D. 3/4

I.D. 3/8

O.D. 1/2

I.D. 5/8

O.D. 5/8

I.D. 1

17-7/8
19-5/16

I.D. 1/2

O.D. 3/4

I.D. 7/8

O.D. 1-1/8

I.D.1-1/4

I.D.1-1/4
I.D. 1
I.D. 1-1/8

I.D. 1-1/8

ARCNB21
I.D. 1-1/8

I.D. 1-1/8

I.D. 1-1/4

I.D. 3/4

O.D. 3/4

3-/16
I.D. 5/8

I.D. 1/2

X2

2-3/4

4-3/4

4-3/8

4-3/4

4-3/8

For Triple-Frame Heat Recovery Systems


Unit: inch
Multi-Frame
Connector

Liquid Pipe

Low-Pressure Vapor Pipe

13-1/16

16-3/8
4.2
I.D. 1-1/8

I.D. 1-1/8

I.D. 7/8

I.D. 1-3/8

I.D.1-3/8

12-3/8

I.D. 5/8

4-3/8

I.D. 1-1/4

High-Pressure Vapor Pipe

I.D. 5/8

I.D. 3/8

I.D. 1/2

I.D. 3/4

3-5/16

Combination specification

ARCNB21
O.D. 1-3/8

I.D. 3/4

O.D.1-3/8

4-15/16

I.D. 7/8

4-3/4

I.D.1-1/8

I.D. 3/4

I.D.3/4

I.D. 5/8

O.D. 3/4

I.D. 1/2

4-3/8

I.D. 1/2

4-3/8

4-3/4

O.D. 1/2

I.D. 5/8 I.D.1/2


I.D. 3/8
I.D. 1/4

X2
I.D.
3/4

3-/16
I.D. 5/8

O.D. 3/4

I.D. 1-3/8

I.D. 1-3/8
I.D. 1-5/8

I.D. 1-1/2

O.D. 7/8

I.D. 3/4 I.D. 5/8

O.D. 5/8

I.D. 1/2

2-3/4

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

4-15/16

18-9/16
20-3/8

4-3/4

4-3/8

I.D. 1-1/8

I.D. 1-1/8
I.D. 1-3/8
I.D. 7/8

I.D. 1-1/2

4-3/8

I.D. 1-3/8

O.D. 1-1/8

I.D. 3/4
X2

4-3/8

I.D.7/8

I.D.1-5/8

I.D. 7/8

I.D.7/8

O.D.1

2-3/4

13-3/16
11-1/16

I.D.1-5/8 I.D. 1-3/8

I.D. 3/8
2-3/4

I.D. 3/8

4-3/4

ARCNB31

O.D. 5/8

O.D. 1

16
13-15/16

I.D. 1-1/2

O.D. 1/2

I.D. 5/8

4-3/8

17-7/8
19-5/16

I.D. 1/2

O.D. 3/4

I.D. 7/8

O.D. 1-1/8

5-1/8

I.D. 7/8

I.D. 1

I.D.1-1/4
I.D. 1
I.D. 1-1/8

I.D. 1-1/8

3-5/16

I.D. 1-5/8

I.D. 1/2

I.D. 1-1/8

I.D. 1-1/2

I.D.1-1/4

I.D. 1-1/8

I.D. 1-1/4

I.D. 1-5/8
O.D. 1-1/2

O.D. 1-3/8

I.D.1-1/2
I.D.1-5/8

5-1/8

3-9/16

I.D. 7/8

O.D. 1-1/8
4-3/4

REFRIGERANT DESIGN

I.D.
3/4

137

Refrigerant Piping Design & Layout Best Practices

I.D. 7/8

I.D.1-3/8

12-3/8

I.D. 5/8

I.D. 1-1/8

I.D. 1-1/4

High-Pressure Vapor Pipe

3-5/16

Combination specification

Multi-Frame
Connector

REFRIGERANT PIPING DESIGN


LG Engineered Header Kits

No Substitutions

Only LG supplied Y-branch and Header fittings can be used to join one pipe segment to two or more segments. Third-party or field-fabricated
Tees, Y-fittings, Headers, or other branch fittings are not qualified for use with LG Multi V IV systems. The only field-provided fittings allowed in
a Multi V IV piping system are 45 and 90 long radius elbows.
Install Correctly

MULTI V IV Outdoor Unit Engineering Manual

Y-branches can be installed upstream between the Header and the outdoor unit, but a Y-branch cannot be installed between a header
and an indoor unit.
To avoid the potential of uneven refrigerant distribution through a header fitting, minimize the difference in equivalent pipe length between the header fitting and each connected indoor unit.

Header Kits

Figure 24: Header KitHorizontal Rotation Limit (Must be Installed Level with No Rotation).

LG Header kits are highly engineered devices


designed to evenly divide the flow of refrigerant, and
are used to join one pipe segment to two or more
segments. Header kits are intended for use where
multiple indoor units are in the same vicinity and
it would be better to home-run the run-out pipes
back to a centralized location. If connecting multiple
indoor units that are far apart, Y-branches may be
more economical.

Largest IDU

Smaller IDUs

Header Inlet

LG Header Kits Consist of:

Two headers (one liquid line, one vapor line).


Reducer fittings as applicable.
Molded clam-shell type peel and stick insulation
coversone for the liquid line and one for the vapor
line.

Header End View

-0.0

Connect IDUs

Figure 25: Header Insulation and Pipe Detail.

Y-branches can be installed upstream between the Header and the


outdoor unit, but a Y-branch cannot be installed between a Header
and an indoor unit. Headers must be installed in a horizontal and
level position with the distribution ports of the fitting in the same horizontal plane as the straight-through branch.
When connecting indoor units to a Header, always connect the unit
with the largest nominal capacity to the port closest to the outdoor
unit. Then install the next largest indoor unit to the next port, working down to the smallest indoor unit. Do not skip ports.
All indoor units connected to a single Header fitting should be
located with an elevation difference between indoor units that does
not exceed 49 feet.

+0.0

Field supplied copper pipe

Field supplied insulation

Field supplied copper pipe LG supplied header LG supplied insulation jacket

138

REFRIGERANT DESIGN

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

REFRIGERANT PIPING DESIGN


LG Engineered Header Kits

Unit: Inch

Models

Vapor pipe

Liquid pipe
14-3/16

14-3/16

4 branch

I.D. 1/2

ARBL054

I.D. 5/8

I.D. 1/2

4-3/4

4-3/4
I.D. 1/4
I.D. 5/8

5-15/16

4-3/4

4-3/4

I.D. 1/2

I.D. 5/8

I.D. 5/8

4 branch
ARBL104

I.D. 5/8

4-3/4
I.D. 1/4

I.D. 3/4

5-15/16

4-3/4

ID15.88(5/8)
I.D. 5/8

I.D. 3/8

I.D 7/8

I.D. 1

I.D. 3/8

I.D. 1/2

4-3/4

I.D. 5/8

I.D. 3/4

5-15/16

I.D. 3/8

I.D. 3/8

I.D. 5/8

I.D. 5/8
I.D. 3/4

I.D. 1-1/8

I.D. 1

5-15/16

4-3/4

ARBL2010

I.D. 5/8

I.D. 1/4

4-3/4

I.D. 3/8
I.D. 3/8

I.D. 7/8

I.D. 1/2

5-15/16

I.D. 3/8

27-9/16
7-3/16

10 branch

4-3/4

I.D. 1/4

30-9/16

I.D. 1/2

I.D. 3/8

28-3/8
6-5/16

ARBL1010

5-15/16

4-3/4

I.D. 1/2

I.D. 7/8

29-7/8

I.D. 1/2

I.D. 1/4

I.D. 1/4

4-3/4

I.D. 1

I.D. 1-1/8

10 branch

5-15/16

4-3/4

27-9/16
6-5/16

ARBL107

I.D. 1/4

I.D. 3/8

22-7/8

ID12.7(1/2)
I.D. 1/2

I.D. 3/8

14-3/16
6-5/16

I.D. 1-1/8

7 branch

5-15/16

4-3/4

I.D. 1/2

15-3/4
I.D. 1/2

I.D. 1/4

I.D. 3/8

5-15/16

4-3/4

I.D. 3/4

I.D. 5/8

Refrigerant Piping Design & Layout Best Practices

I.D. 5/8

I.D. 3/8

21-1/4
4-3/4

ARBL057

5-15/16

4-3/4

I.D. 1/2

21-1/4

I.D. 1/2

I.D. 3/8

I.D. 3/8

I.D. 5/8

I.D. 3/4

7 branch

I.D. 1/4

I.D. 3/4

I.D. 1-1/4
I.D. 1-3/8

4-3/4

4-1/4

21-1/2

I.D. 5/8

I.D. 1/4

I.D. 1/4
5-15/16

I.D. 3/8

I.D. 1-1/8

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

4-3/4

I.D. 3/8

5-15/16

I.D. 3/4
I.D. 5/8

REFRIGERANT DESIGN

139

REFRIGERANT PIPING DESIGN


LATS Calculated Refrigerant Charge Example

Consider refrigerant safety in all designs.


LG Multi V IV outdoor units ship from the factory with a charge of R410A refrigerant. This charge serves as the base charge and will not be
sufficient for the system to operate. A trim charge will need to be added after the system is installed that is based on system design. LATS
Multi V piping design software will calculate the size of the refrigerant piping and calculate the refrigerant charge; this added trim refrigerant
charge is shown on the LATS Multi V output.

MULTI V IV Outdoor Unit Engineering Manual

The example LATS Multi V design software report below shows both the base charge and the calculated trim charge (Tables 48-53). The
information used in the tables below are obtained from a LATS-generated report.

Project Name: Multi V IV Heat Recovery System Test Update System No: 1/1
Table 48: Design Conditions.

DB (F)
80.6

Indoor
WB (F)
67.1

Summer

Outdoor
DB (F)
WB (F)

RH (%)
50

93.9

73.9

DB (F)
68.0

Indoor
WB (F)
56.8

Winter
RH (%)
50

Outdoor
DB (F)
WB (F)
17.1

16.2

Table 49: Outdoor Unit Specifications.


Model Name

Max. Indoor
Unit
Connectivity

Max. Total
Over Load
(kBtu/h/%)

Indoor Unit to
Outdoor Unit
Ratio

Product
Charge1
(lbs.)

ARUB121DTE4

20

156.0 (130%)

1.26:1

23.6

Product Charge = Factory charge of outdoor unit.


2
Additional Ref Amount = Trim charge.
1

Table 50: Piping Specifications.


Index (from
Piping Dia. (Inches)
LATS selection)
Liquid : Vapor
P28
P22
P0
P1
P27
P21

Length (Feet)1

1/2 : 3/4 : 1+1/8


3/8 : 3/4 : 7/8
1/4 : 1/2
3/8 : 5/8
3/8 : 5/8 : 3/4
3/8 : 1/2 : 5/8

20.0
15.0
130.0
50.0
35.0
16.0

1
It is imperative to know the as-built physical length of each segment of liquid line, to calculate the
total refrigerant charge required. An accurate as built field-verified piping diagram is required to verify
within LATS that piping is within limits, proper pipe sizing, and refrigerant charge.

Table 53: Indoor Units.


Model Name

ARNU183SCL4
ARNU183TQC4
ARNU243BGA4
ARNU123SBL4
ARNU123SER2
ARNU183NJA4
ARNU123VEA2
ARNU183CFU4
Total

140

REFRIGERANT DESIGN

Quantity
1
1
1
2
1
1
1
1
9

Additional Rated / Corrected Capacity


(kBtu/h)
Ref. Amount2
(lbs.)
Cooling
Heating
18.26

120.0 / 126.0 135.0 / 127.8

Rated / Corrected
Power Input (kW)
Cooling
Heating

8.5 / 9.2

8.7 / 10.6

Table 51: Branches / Headers / Common Pipes / Heat Recovery Units.


Model Name
Quantity
ARBLB03321
PRHR042A
PRHR032A
PRHR022A

1
1
1
1

Table 52: Accessories.


Index Model
Description
Name Quantity
IDU PT-UMC
1
Std. Grille - Four-way Cassette (TN, TM, TP)

Description

Wall Mounted (18 MBh)


Ceiling Cassette - Four-Way (18 MBh)
Ceiling-Concealed Ducted - High Static (24 MBh)
Wall Mounted (12 MBh)
Art Cool Mirror (12 MBh)
Vertical / Horizontal Air Handling Unit (18 MBh)
Convertible Surface (12 MBh)
Floor Standing - Without Case (18 MBh)
-

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

REFRIGERANT PIPING DESIGN


LATS Calculated Refrigerant Charge Example

Figure 26: LATS Tree Diagram for Multi V IV Heat Recovery System Test Update System No: 1/1 Example.

1. Using the LATS Tree diagram, document the linear feet of straight liquid piping and the quantity and type of each fitting by pipe diameter
into System Refrigerant Charge Calculator.
2. Calculate the total linear feet of liquid line piping in the system. It is imperative to know the as-built physical length of each segment of
liquid line to calculate the total refrigerant charge required. An accurate as built field-verified piping diagram is required to verify within
LATS that piping is within limits, proper pipe sizing, and refrigerant charge. Record the values on lines 17.
3. Count the number of indoor units. Group them by model type and nominal capacity as indicated in the description field on lines 835.
Record the quantity of units in each group, multiply each by their specific correction factor, and add the sum in the Total (lbs.) column.
4. Count the number of heat recovery units, record the quantity, multiply by the specific correction factor, and record the sum in the Total
(lbs.) column on line 36.
5. Sum the total values on lines 1-36 and place in the field labeled "Additional Refrigerant Charge Required" on line 37.
6. Record the quantity of each outdoor unit frame, multiple total of each by their specific correction factor on lines 38a-g, and enter the total
on line 39 (Total Factory Refrigerant Charge).
7. Add the Additional Refrigerant Charge Required to the Total Factory Refrigerant Charge. This is the Total System Charge. Record on line
40

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

REFRIGERANT DESIGN

141

Refrigerant Piping Design & Layout Best Practices

Determining the Total System Charge (Refer to Table 54)

REFRIGERANT PIPING DESIGN


LATS Calculated Refrigerant Charge Example

Table 54: System Refrigerant Charge Calculator (lbs.).


Job Name_______________________________________
System Tag or ID____________________________________

Project Manager__________________________________
Date___________________________________________

Line #

MULTI V IV Outdoor Unit Engineering Manual

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37

38

39
40

Description

Linear feet of 1/4" liquid line tubing


Linear feet of 3/8" liquid line tubing2
Linear feet of 1/2" liquid line tubing2
Linear feet of 5/8" liquid line tubing2
Linear feet of 3/4" liquid line tubing2
Linear feet of 7/8" liquid line tubing2
Linear feet of 1" liquid line tubing2
Wall Mounted + Art Cool Mirror
Wall Mounted + Art Cool Mirror
1-Way Cassette
1-Way Cassette
2-Way Cassette
4-Way 2' x 2' Cassette
4-Way 2' x 2' Cassette
4-Way 2' x 2' Cassette
4-Way 3 x 3 Cassette
4-Way 3' x 3' Cassette
4-Way 3 x 3 Cassette
4-Way 3' x 3' Cassette
4-Way 3' x 3' Cassette
High Static Ducted
High Static Ducted
High Static Ducted
Low Static Ducted
Low Static Ducted
Low Static Ducted
Low Static Ducted Bottom Return
Low Static Ducted Bottom Return
Vertical / Horizontal Air Handling Unit
Vertical / Horizontal Air Handling Unit
Vertical / Horizontal Air Handling Unit
Ceiling Suspended
Convertible Surface MountCeiling / Wall
Floor Standing
Floor Standing
PRHR022A, PRHR032A, PRHR042A
Additional Refrigerant Charge Required
2

Chassis I.D.

SB, SE
SC, S8
TU
TT
TL
TR
TR
TQ
TNA
TPC
TMA
TNC
TMC
BG
BR
B8
L1
L2
L3
B3
B4
NJ
NJ
NK
VJ
VE
CE (U)
CF (U)

Size

5k to 15k
18k to 24k
7k to 12k
18k to 24k
18k to 24k
5k to 7k
9k to 12k
15k to 18k
7k to 24k
24k to 28k
24k to 36k
36k
42k to 48k
7k to 42k
48k to 54k
76k to 96k
7k to 9k
12k to 18k
24k
7k to 15k
18k to 24k
12k to 30k
36k
42k to 54k
18k to 24k
9k to 12k
7k to 15k
18k to 24k

Quantity

CF (Ref.)1
0.015
0.041
0.079
0.116
0.179
0.238
0.323
0.53
0.62
0.44
0.64
0.35
0.40
0.55
0.71
0.89
1.06
1.08
1.41
1.41
0.97
1.34
2.20
0.31
0.42
0.55
0.37
0.82
1.04
1.57
2.00
0.77
0.22
0.37
0.82
1.1

Total (lbs.)

38a
ARU*072***4
72k
16.9
38b
ARU*096***4
96k
23.6
38c
ARU*121***4
121k
23.6
38d
ARU*144***4
144k
23.6
Outdoor Unit Factory Refrigerant Charge
38e
ARU*145***4
144k
23.6
38f
ARU*168***4
168K
23.6
38g
ARU*169***4
168K
23.6
Total Factory Refrigerant Charge (sum of refrig. charge for all Outdoor Units in the system)
Total System Charge: Sum of Additional Refrigerant Charge Required and Total Factory Refrigerant Charge

CF (Ref.) = Correction Factor for Refrigerant Charge.


For refrigerant charge purposes, consider only the liquid line; ignore the vapor line(s).
3
ARU*145BTE4/145DTE4 & ARU*169BTE4/169DTE4 frames are ONLY for large capacity triple frame combinations. They cannot be used as stand alone
models or in a dual frame combination. These ARE NOT interchangeable with ARU*144BTE4/144DTE4 & ARU*168BTE4/168DTE4 single frame models.
1
2

142

REFRIGERANT DESIGN

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

LAYOUT BEST PRACTICES


Selecting Field-Supplied Copper Tubing

Type ACR copper is the only approved refrigerant pipe material for
use with LG Multi V commercial air conditioning products. ACR rated
tubing is the only type that ships with yellow caps. Approved tubing
for use with Multi V products will be marked "R410 RATED" along the
length of the tube.
Drawn temper (rigid) ACR copper tubing is available in sizes 3/8
through 2-1/8 inches (ASTM B 280, clean, dry, and capped).

Annealed temper (soft) ACR copper tubing is available in sizes 1/4


through 2-1/8 inches (ASTM B 280, clean, dry, and capped).
Tube wall thickness should meet local code requirements and be
approved for a maximum operating pressure of 551 psi. When bending tubing, use the largest radii possible to reduce the equivalent
length of installed pipe; also, bending radii greater than ten (10) pipe
diameters can minimize pressure drop. Be sure no traps or sags are
present when rolling out soft copper tubing coils.

Table 55: ACR Rated Copper Tubing Material.

Table 56: ACR Rated Piping Tube Thicknesses.


1/4
3/8
1/2
5/8
OD (in)

Type

Seamless Phosphorous Deoxidized

Class

UNS C12200 DHP

Material

Straight Lengths

H58 Temper

Coils

O60 Temper

Min. Bend
Radius (in)
Min. Wall
Thickness (in)

Copper Expansion and Contraction

Under normal operating conditions, the vapor pipe temperature of a


Multi V IV system can vary as much as 180F. With this large
variance in pipe temperature, the designer must consider pipe
expansion and contraction to avoid pipe and fitting fatigue failures.
Refrigerant pipe along with the insulation jacket form a cohesive
unit that expands and contracts together. During system operation,
thermal heat transfer occurs between the pipe and the surrounding
insulation.
If the pipe is mounted in free air space, no natural restriction to
movement is present if mounting clamps are properly spaced and
installed. When the refrigerant pipe is mounted underground in a
utility duct stacked among other pipes, natural restriction to linear
movement is present. In extreme cases, the restrictive force of
surface friction between insulating jackets could become so great
that natural expansion ceases and the pipe is fixed in place. In this
situation, opposing force caused by change in refrigerant fluid/vapor
temperature can lead to pipe/fitting stress failure.
The refrigerant pipe support system must be engineered to allow
free expansion to occur. When a segment of pipe is mounted
between two fixed points, provisions must be provided to allow pipe
expansion to naturally occur. The most common method is the
inclusion of expansion Loop or U-bends mounted in the horizontal
plane. When expansion loops are placed in a vertical riser, the loop
is to be formed in a horizontal fashion resulting in a torsional movement during expansion and contraction. Each segment of pipe has
a natural fixed point where no movement occurs. This fixed point is
located at the center point of the segment assuming the entire pipe
is insulated in a similar fashion. The natural fixed point of the pipe
segment is typically where the expansion Loop or U-bend should be.
Linear pipe expansion can be calculated using the following formula:
LE = C x L x (Tr Ta) x 12
LE
C
L
TR
Ta
12

=
=
=
=
=
=

Anticipated linear tubing expansion (in.)


Constant (For copper = 9.2 x 10-6 in./in.F)
Length of pipe (ft.)
Refrigerant pipe temperature (F)
Ambient air temperature (F)
Inches to feet conversion (12 in./ft.)

Rigid or Soft ACR Rated


for R410A

3/4

7/8

1-1/8 1-3/8 1-5/8

Rigid or Solid ACR Rated for R410A

.563

.9375

1.5

2.25

3.0

3.0

3.5

4.0

4.5

.03

.03

.03

.03

.03

.03

.03

.04

.05

1. From Table 57, find the row corresponding with the actual length
of the straight pipe segment.
2. Estimate the minimum and maximum temperature of the pipe
typical pipe temperature change range: High Pressure Vapor:
ambient temperature to 215F; Low Pressure Vapor: ambient to
35F; Liquid pipe: ambient, 80F, 110F. Choose the two most
extreme. In the column showing the minimum pipe temperature,
look up the anticipated expansion distance. Do the same for the
maximum pipe temperature.
3. Calculate the difference in the two expansion distance values.
The result will be the anticipated change in pipe length.

Example:

A Multi V IV heat pump system is installed and the design shows that
there is a 260 feet straight segment of tubing between a Y-branch
and an indoor unit. The system operates 24 hours per day. In heating, this pipe transports hot gas vapor to the indoor units at 120F.
In cooling, the same tube is a suction line returning refrigerant vapor
to the outdoor unit at 40F. Look up the copper tubing expansion at
each temperature and calculate the difference.

Vapor Line

Transporting Hot Vapor: 260 ft. pipe at 120F = 3.64 in.


Transporting Suction Vapor: 260 ft. pipe at 40F = 1.04 in.
Anticipated Change in Length: 3.64 in. 1.04 in. = 2.60 in.

Liquid Line

The liquid temperature remains the same temperature; only the


direction of flow will reverse. Therefore, no significant change in
length of the liquid line is anticipated.
When creating an expansion joint, the joint depth should be a
minimum of two times the joint width. Although different types of
expansion arrangements are available, the data for correctly sizing
an expansion loop is provided in Table 58. Use soft copper with
long radius bends on longer runs or long radius elbows for shorter
pipe segments. Using the anticipated linear expansion (LE) distance
calculated, look up the Expansion Loop or U-bend minimum design
dimensions. If other types of expansion joints are chosen, design
per ASTM B-88 Standards.

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

REFRIGERANT DESIGN

143

Refrigerant Piping Design & Layout Best Practices

LG recommends soft copper use to be limited to 1/2". Use hard drawn for larger sizes to avoid sags and kinks that lead to oil trapping.

LAYOUT BEST PRACTICES


Selecting Field-Supplied Copper Tubing

Table 57: Linear Thermal Expansion of Copper Tubing in Inches.

MULTI V IV Outdoor Unit Engineering Manual

Pipe
Length1 35
0.04
10

40

45

50

55

60

65

70

Fluid Temperature F
75 80 85 90

95 100 105 110 115 120 125 130

0.04

0.05

0.06

0.06

0.07

0.08

0.08

0.09

0.09

0.10

0.10

0.11

0.11

0.11

0.12

0.13

0.14

0.15

0.15

20

0.08

0.08

0.10

0.12

0.13

0.14

0.15

0.16

0.17

0.18

0.19

0.20

0.21

0.22

0.22

0.23

0.26

0.28

0.29

0.30

30

0.12

0.12

0.15

0.18

0.20

0.21

0.23

0.24

0.26

0.27

0.29

0.30

0.32

0.33

0.32

0.35

0.39

0.42

0.44

0.45

40

0.16

0.16

0.20

0.24

0.26

0.28

0.30

0.32

0.34

0.36

0.38

0.40

0.42

0.44

0.43

0.46

0.52

0.56

0.58

0.60

50

0.20

0.20

0.25

0.30

0.33

0.35

0.38

0.40

0.43

0.45

0.48

0.50

0.53

0.55

0.54

0.58

0.65

0.70

0.73

0.75

60

0.24

0.24

0.30

0.36

0.39

0.42

0.45

0.48

0.51

0.54

0.57

0.60

0.63

0.66

0.65

0.69

0.78

0.84

0.87

0.90

70

0.28

0.28

0.35

0.42

0.46

0.49

0.53

0.56

0.60

0.63

0.67

0.70

0.74

0.77

0.76

0.81

0.91

0.98

1.02

1.05

80

0.32

0.32

0.40

0.48

0.52

0.56

0.60

0.64

0.68

0.72

0.76

0.80

0.84

0.88

0.86

0.92

1.04

1.12

1.16

1.20

90

0.36

0.36

0.45

0.54

0.59

0.63

0.68

0.72

0.77

0.81

0.86

0.90

0.95

0.99

0.97

1.04

1.17

1.26

1.31

1.35

100

0.40

0.40

0.50

0.60

0.65

0.70

0.75

0.80

0.85

0.90

0.95

1.00

1.05

1.10

1.08

1.15

1.30

1.40

1.45

1.50

120

0.48

0.48

0.60

0.72

0.78

0.84

0.90

0.96

1.02

1.08

1.14

1.20

1.26

1.32

1.30

1.38

1.56

1.68

1.74

1.80

140

0.56

0.56

0.70

0.84

0.91

0.98

1.05

1.12

1.19

1.26

1.33

1.40

1.47

1.54

1.51

1.61

1.82

1.96

2.03

2.10

160

0.64

0.64

0.80

0.96

1.04

1.12

1.20

1.28

1.36

1.44

1.52

1.60

1.68

1.76

1.73

1.84

2.08

2.24

2.32

2.40

180

0.72

0.72

0.90

1.08

1.17

1.26

1.35

1.44

1.53

1.62

1.71

1.80

1.89

1.98

1.94

2.07

2.34

2.52

2.61

2.70

200

0.80

0.80

1.00

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

2.10

2.20

2.16

2.30

2.60

2.80

2.90

3.00

220

0.88

0.88

1.10

1.32

1.43

1.54

1.65

1.76

1.87

1.98

2.09

2.20

2.31

2.42

2.38

2.53

2.86

3.08

3.19

3.30

240

0.96

0.96

1.20

1.44

1.56

1.68

1.80

1.92

2.04

2.16

2.28

2.40

2.52

2.64

2.59

2.76

3.12

3.36

3.48

3.60

260

1.04

1.04

1.30

1.56

1.69

1.82

1.95

2.08

2.21

2.34

2.47

2.60

2.73

2.86

2.81

2.99

3.38

3.64

3.77

3.90

280

1.12

1.12

1.40

1.68

1.82

1.96

2.10

2.24

2.38

2.52

2.66

2.80

2.94

3.08

3.02

3.22

3.64

3.92

4.06

4.20

300

1.20

1.20

1.50

1.80

1.95

2.10

2.25

2.40

2.55

2.70

2.85

3.00

3.15

3.30

3.24

3.45

3.90

4.20

4.35

4.50

320

1.28

1.28

1.60

1.92

2.08

2.24

2.40

2.56

2.72

2.88

3.04

3.20

3.36

3.52

3.46

3.68

4.16

4.48

4.64

4.80

340

1.36

1.36

1.70

2.04

2.21

2.38

2.55

2.72

2.89

3.06

3.23

3.40

3.57

3.74

3.67

3.91

4.42

4.76

4.93

5.10

360

1.44

1.44

1.80

2.16

2.34

2.52

2.70

2.88

3.06

3.24

3.42

3.60

3.78

3.96

3.89

4.14

4.68

5.04

5.22

5.40

380

1.52

1.52

1.90

2.28

2.47

2.66

2.85

3.04

3.23

3.42

3.61

3.80

3.99

4.18

4.10

4.37

4.94

5.32

5.51

5.70

400

1.60

1.60

2.00

2.40

2.60

2.80

3.00

3.20

3.40

3.60

3.80

4.00

4.20

4.40

4.32

4.60

5.20

5.60

5.80

6.00

420

1.68

1.68

2.10

2.52

2.73

2.94

3.15

3.36

3.57

3.78

3.99

4.20

4.41

4.62

4.54

4.83

5.46

5.88

6.09

6.30

440

1.76

1.76

2.20

2.64

2.86

3.08

3.30

3.52

3.74

3.96

4.18

4.40

4.62

4.84

4.75

5.06

5.72

6.16

6.38

6.60

460

1.84

1.84

2.30

2.76

2.99

3.22

3.45

3.68

3.91

4.14

4.37

4.60

4.83

5.06

4.97

5.29

5.98

6.44

6.67

6.90

480

1.92

1.92

2.40

2.88

3.12

3.36

3.60

3.84

4.08

4.32

4.56

4.80

5.04

5.28

5.18

5.52

6.24

6.72

6.96

7.20

500

2.00

2.00

2.50

3.00

3.25

3.50

3.75

4.00

4.25

4.50

4.75

5.00

5.25

5.50

5.40

5.75

6.50

7.00

7.25

7.50

Pipe length baseline temperature = 0F. "Expansion of Carbon, Copper and Stainless Steel Pipe," The Engineers' Toolbox, www.engineeringtoolbox.com.

144

REFRIGERANT DESIGN

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

LAYOUT BEST PRACTICES


Selecting Field-Supplied Copper Tubing

Figure 27: Coiled Expansion Loops and Offsets (Plan View).


L

Loop

Small Tubing U-bend (<3/4 in.)

Refrigerant Piping Design & Layout Best Practices

Large Tubing U-bend (>3/4 in.)

Table 58: Radii of Coiled Expansion Loops and Developed Lengths of Expansion Offsets.
Anticipated Linear
Expansion (LE) (inches)
1/2
1
1-1/2
2
2-1/2
3
3-1/2
4

Nominal Tube Size (OD) inches


1/2
3/4
1

1/4

3/8

1-1/4

1-1/2

R1

11

12

13

L
R1
L2
R1
L2
R1
L2
R1
L2
R1
L2
R1
L2
R1
L2

38

44

50

59

67

74

80

10

11

13

15

17

18

54

63

70

83

94

104

113

11

12

14

16

18

20

22

66

77

86

101

115

127

138

12

14

16

19

21

23

25

77

89

99

117

133

147

160

14

16

18

21

24

26

29

86

99

111

131

149

165

179

15

17

19

23

26

29

31

94

109

122

143

163

180

196

16

19

21

25

28

31

34

102

117

131

155

176

195

212

17

20

22

26

30

33

36

109

126

140

166

188

208

226

R = Centerline Length of Pipe.


2
L = Centerline Minimum Radius (inches).
1

All expansion Loops and Offsets should be installed in the horizontal plane to prevent the possibility of trapping oil. Loops and Offsets in vertical risers should also be installed in a horizontal plane.

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

REFRIGERANT DESIGN

145

LAYOUT BEST PRACTICES


General Information / Guidelines

Definitions

Main: The piping segment between the outdoor unit and the first Y-branch.
Branch: A segment of pipe between two Y-branches.
Run-out: The segment of pipe connecting an indoor unit to a Y-branch.

MULTI V IV Outdoor Unit Engineering Manual

Layout Procedure

1. Draft a one-line diagram of the proposed piping system connecting outdoor unit to heat recovery and indoor units. Follow the
pipe limitations listed on pages 129 and 132.
2. Calculate the physical length of each pipe segment and note it on
the drawing.

Physical Pipe Length: Actual length of straight segment(s) of pipe.


Equivalent Pipe Length: Actual length of pipe plus equivalent
lengths of elbows, Y-branches, and valves.

3. Calculate the equivalent pipe length of each pipe segment.


4. Input the pipe lengths into the LATS software and perform Auto
Pipe Sizing check and System Check. LATS will automatically
calculate pipe sizes.

Using Elbows

Field-supplied elbows are allowed as long as they are long radius and designed for use with R410A refrigerant. The designer, however,
should be cautious with the quantity and size of fittings used, and must account for the additional pressure losses in equivalent pipe length
calculation for each branch. The equivalent pipe length of each elbow must be added to each pipe segment in the LATS program. See page
125.

Field-Provided Isolation Ball Valves

LG allows installing field-supplied ball valves with Schrader ports at each indoor unit. Full-port isolation ball valves with Schrader ports (positioned between valve and indoor unit) rated for use with R410A refrigerant should be used on both the liquid and vapor lines.
If valves are not installed and a single indoor unit needs to be removed or repaired, the entire system must be shut down and evacuated. If
isolation ball valves are installed, and an indoor unit needs to be repaired, the unaffected indoor units can remain operational. Reclamation of
refrigerant, then, can be confined to a single indoor unit.
Position valves with a minimum distance of three (3) to six (6) inches of pipe on either side of the valve, and place between six (6) and twelve
(12) inches from the heat recovery unit, Y-branch, or header. If ball valves are installed closer to the indoor unit, oil may accumulate where it
cannot be returned to the air-source unit and may cause a shortage of oil in the compressor.
Valves shall be easily accessible for service. If necessary, install drywall access doors or removable ceiling panels, and position the valves
to face the access door or ceiling panel opening. Mount valves with adequate space between them to allow for placement of adequate pipe
insulation around the valves. Recommended best practice is to clearly label and document locations of all service valves, heat recovery
control units, Y-branches, and headers.

Obstacles

Figure 28: Installing Piping Above and Below an Obstacle.

When an obstacle, such as an I-beam or concrete T, is in the path


of the planned refrigerant pipe run, it is best practice to route the
pipe over the obstacle. If adequate space is not available to route
the insulated pipe over the obstacle, then route the pipe under the
obstacle. In either case, it is imperative the horizontal section of pipe
above or below the obstacle be a minimum of three (3) times greater
than the longest vertical rise (or fall) distance.

3X

Above an obstacle.

In-line Refrigeration Components

Below an obstacle.

Components such as oil traps, solenoid valves, filter-dryers, sight glasses, tee fittings, and other after-market accessories are not permitted
on the refrigerant piping system between the outdoor units and the indoor / heat recovery units. Multi V IV air-source systems are provided
with redundant systems that assure oil is properly returned to the compressor. Sight-glasses and solenoid valves may cause vapor to form
in the liquid stream. Over time, dryers may deteriorate and introduce debris into the system. The designer and installer should verify the
refrigerant piping system is free of traps, sagging pipes, sight glasses, filter dryers, etc.

146

REFRIGERANT DESIGN

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

LAYOUT BEST PRACTICES


General Information / Guidelines

No Pipe Size Substitutions

Use only the pipe size selected by the LATS Multi V pipe system design software. Using a different size is prohibited and may result in a
system malfunction or failure to work at all.

Pipe Supports

Figure 29: Pipe Hanger Details.

Use a 4" + long sheet curved sheet metal saddles between hanger
bracket and insulation to promote linear expansion/contraction.

Figure 30: Typical Pipe Support Location


Change in Pipe Direction.

Max. 12"

~ 12" 19"

Figure 31: Pipe Support at


Indoor Unit.
B

Figure 32: Pipe Support at Y-branch Fitting.


Max. 12"

Max. 12"

A + B ~ 12" 19"

Figure 33: Pipe Support at Header Fitting.


Max. 12"

Max. 12"

Max. 12"

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

REFRIGERANT DESIGN

147

Refrigerant Piping Design & Layout Best Practices

A properly installed pipe system should be adequately supported


to avoid pipe sagging. Sagging pipes become oil traps that lead to
equipment malfunction.
Pipe supports should never touch the pipe wall; supports shall be
installed outside (around) the primary pipe insulation jacket. Insulate
the pipe first because pipe supports shall be installed outside
(around) the primary pipe insulation jacket. Clevis hangers should
be used with shields between the hangers and insulation. Field
provided pipe supports should be designed to meet local codes. If
allowed by code, use fiber straps or split-ring hangers suspended
from the ceiling on all-thread rods (fiber straps or split ring hangers
can be used as long as they do not compress the pipe insulation).
Place a second layer of insulation over the pipe insulation jacket to
prevent chafing and compression of the primary insulation within the
confines of the support pipe clamp.
A properly installed pipe system will have sufficient supports to avoid
pipes from sagging during the life of the system. As necessary,
place supports closer for segments where potential sagging could
occur. Maximum spacing of pipe supports shall meet local codes.
If local codes do not specify pipe support spacing, pipe shall be
supported:
Maximum of five feet (5) on center for straight segments of pipe up
to 3/4" outside diameter size.
Maximum of six feet (6) on center for pipe up to one inch (1)
outside diameter size.
Maximum of eight feet (8) on center for pipe up to two inches (2)
outside diameter size.
Wherever the pipe changes direction, place a hanger within twelve
(12) inches on one side and within twelve to nineteen (12 to 19)
inches of the bend on the other side. Support piping at indoor units
as shown. Support Y-Branch and Header fittings as shown.

LAYOUT BEST PRACTICES


General Information / Guidelines

Pipe Sleeves at Penetrations

LG requires that all pipe penetrations through walls, floors, and pipes buried underground be properly insulated and routed through an
appropriate wall sleeve of sufficient size to prevent compression of refrigerant pipe insulation and promote free movement of the pipe within
the sleeve. Use 4"+ curved sheet metal saddles between the bottom surface of the pipe and the bottom surface of the penetration. Underground refrigerant pipe shall be routed inside a protective sleeve to prevent insulation deterioration.

MULTI V IV Outdoor Unit Engineering Manual

Figure 34: Pipe Sleeve Options.

Diameter of penetrations shall be determined by pipe diameter plus the thickness of the insulation.

Underground Refrigerant Piping

Refrigerant pipe installed underground should be routed inside a vapor tight


protective sleeve to prevent insulation deterioration and water infiltration. Refrigerant pipe installed inside underground casing must be continuous without
any joints. Underground refrigerant pipe must be located at a level below the
frost line.

Figure 35: Typical Arrangement of Refrigerant Pipe and


Cable(s) in a Utility Conduit.
Vapor Line
Insulation Material
Liquid Line
Pipe Sleeve

Provide expansion joints in long pipe segments and place in an accessible


conduit box for inspection. Use galvanized curved sheet metal saddles at all
mounting points. Pipe should be allowed to move freely linearly.
Table 59: Utility Conduit Sizes.
Liquid Pipe1
1/4 (1.0)3
3/8 (1-1/8)3
1/2 (1-1/2)4
5/8 (1-5/8)4
3/4 (1-3/4)4

1/2 (2.02,5)

Vapor Pipe1
5/8 (2-1/82,5)

3/4 (2-1/42,5)

OD pipe diameter in inches; Values in parenthesis () indicate OD of pipe with insulation jacket.
2
Diameter of pipe with insulation. Thickness of pipe insulation is typical. Actual required thickness may
vary based on surrounding ambient conditions and should be calculated and specified by the design
engineer.
3
Insulation thickness (value in parenthesis) = 3/8 inch.
4
Insulation thickness (value in parenthesis) = 1 inch.
5
Insulation thickness (value in parenthesis) = 3/4 inch.
1

148

REFRIGERANT DESIGN

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

Insulation
Material
Min. 18 Gauge
Power/Communication
Cable

LAYOUT BEST PRACTICES


General Information / Guidelines

Refrigerant Piping for Separated Outdoor Units

Dual-frame and triple-frame systems should be installed with all outdoor units located next to each other. In conditions when the dual-frame
and triple-frame units need to be separated, the following rules should be followed:

Pipe Connection between Outdoor UnitsStandard Length

To IDUs / HRUs

33 feet (Max)

To IDUs / HRUs

Pipe Connection between Outdoor Units when Length is 6-/58 feet

To IDUs / HRUs

6-5/8 feet

Oil Trap Installation between Outdoor Units when Length


is 6-/58 feet
If the distance between the
outdoor units is >6-5/8 feet,
install an oil trap on the
vapor pipes.
6-5/8 feet

To IDUs / HRUs

Oil Trap
8 inches

Installation When One ODU is Positioned


Lower than the Main Pipe or Other ODUs
If an outdoor unit is lower than the
main pipe, an oil trap must be installed.
If an oil trap is not installed, oil will accumulate
in the outdoor unit that is installed lower than the other
outdoor units.

6-5/8 feet
Oil Trap

Oil Trap
To IDUs / HRUs

6-5/8 feet

6-5/8 feet

Oil Trap

To IDUs / HRUs

6-5/8 feet

6-5/8 feet

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

REFRIGERANT DESIGN

149

Refrigerant Piping Design & Layout Best Practices

Maximum pipe length


after the first branch
between the outdoor units

LAYOUT BEST PRACTICES


General Information / Guidelines

Installation When the Main Refrigerant Pipe is Installed Above the Outdoor Units
Main Refrigerant Pipe Installed Above Units

Liquid Line
Low Pressure Vapor
High Pressure Vapor

Inverted
Traps
Required
(Typical
6 Places)

To IDUs/HRUs

Typical Y-Branch

Min 20" *

Inverted Trap

Outdoor
Units

Min 20"*

* 20" Minimum pipe segment lengths between ODU Y-Branch connectors provide
optimum refrigerant flow with the least amount of noise generating turbulence. When
possible maintain 20" minimum.

A + B < 6-5/8'

MULTI V IV Outdoor Unit Engineering Manual

8"

Pipe Slope

Horizontal pipe slope should be away from the outdoor units, otherwise refrigerant and oil will migrate toward the outdoor units and accumulate in the pipe segment serving the frame that is not running or at the lowest elevation.
Figure 36: Allowable Pipe Slopes.

Toward indoor unit

Toward indoor unit

Toward indoor unit

Pipe slope (two or more)


Toward indoor unit

150

REFRIGERANT DESIGN

Cannot exceed 10

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

LAYOUT BEST PRACTICES


General Information / Guidelines

Refrigerant Piping Installation

Proper system operation depends on the installer using best practices and utmost care while assembling the piping system as one of the
main causes of refrigerant leaks is defective connections. For VRF systems, the installer needs to know how perform both flared and brazed
connections successfully.
Figure 37: Dimensions of the Flare.

Flaring Practices

90 2

Brazing Practices

45

R=0.4~0.8

Refrigerant piping system joints are brazed in the field. Multi V IV refrigeration system components
contain very small capillary tubes, small orifices, electronic expansion valves, oil separators, and heat
exchangers that can easily become blocked.
Table 60: Flared Connection Dimensions.
Use adapters to assemble different sizes of pipe.
Pipe
A
Do not use flux, soft solder, or anti-oxidant agents; use a 15% silver phosphoIndoor Unit
Vapor
Liquid
(in.
rous copper brazing alloy.
(Btu/h)
Vapor (in.) Liquid (in.)
(in. O.D.) O.D.)
Protect isolation valves, electronic expansion valves, and other heat-sensitive
19,100
1/2
1/4
5/8 ~ 11/16 7/16 ~ 1/2
control components from excessive heat with a wet rag or a heat barrier spray
<54,600
5/8
3/8
5/8 ~ 11/16 5/8 ~ 11/16
product
76,400

3/4

3/8

3/4 ~ 13/16

5/8 ~ 11/16

During installation, it is imperative to keep the piping system free of contaminants and debris such as copper burrs, slag, or carbon dust.

Refrigerant Safety Standards

ASHRAE Standards 15-2010 and 34-2010 address refrigerant safety and the maximum allowable concentration of refrigerant in an occupied
space. Refrigerant will dissipate into the atmosphere, but a certain volume of air is required to safely dissipate the refrigerant. For R410A
refrigerant, the maximum allowable concentration of refrigerant is 26 lbs./1,000 cubic feet (Addendum L modified the RCL to 26) of occupied
spaces. Buildings with 24-hour occupancy allow half of that concentration.
If a VRF system develops a refrigerant leak, the entire refrigerant charge of the system will dump into the area where the leak occurs. To
meet ASHRAE Standards 15 and 34, the smallest room volume on the system must be calculated and compared to the maximum allowable
concentration. If the concentration level is higher than allowed, the following are some design suggestions to eliminate the problem:
Split dual-frame and triple-frame systems into single-frame systems that have lower refrigerant charges.
Add transfer grilles in the ceiling or walls of the smaller rooms to increase the volume of the room.
Remove the smallest space from the system and serve it with a smaller mini-split system.

Refrigerant Piping System Insulation

All refrigerant piping including Y-branch and Header connections, field-provided isolation ball valves, service valves, and elbows shall be
completely insulated using closed cell pipe insulation. The liquid and vapor lines must be insulated separately.
To prevent heat loss/heat gain through the refrigerant piping, all refrigerant piping including liquid lines, high-pressure vapor lines, and lowpressure vapor lines shall be insulated separately. Insulation shall be a minimum 1/2 thick, and thickness may need to be increased based
on ambient conditions and local codes. Maximum pipe temperature is 248F and minimum pipe temperature is -40F
All insulation joints shall be glued with no air gaps. Insulation material shall fit snugly against the refrigeration pipe with no air space between
it and the pipe. Insulation passing through pipe hangers, inside conduit, and/or sleeves must not be compressed. Protect insulation inside
hangers and supports with a second layer. All pipe insulation exposed to the sun and outdoor elements shall be properly protected with PVC,
aluminum vapor barrier, or alternatively placed in a weather-resistant enclosure such as a pipe rack with a top cover; and meet local codes.
LG-provided Y-branches are shipped from the factory with pre-formed peel-and-stick foam insulation jackets, with a 1.84 lb./ft.3 density, 1/2
thickness, and meet UL94 MF-1 flammability.
The design engineer should perform calculations to determine if the factory-supplied insulation jackets are sufficient to meet local codes and
avoid sweating. Add additional insulation if necessary. Check the fit of the insulation jacket after the header fitting and all run-out pipes are
installed. Mark all pipes at the point where the insulation jacket ends. Remove the jacket. Install field provided insulation on the run-out and
main trunk pipes first. Install the LG-provided insulation plugs on the ends of all unused header ports. Peel the adhesive glue protector slip
from the insulation jacket and install the clam-shell jacket over the fitting.
Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

REFRIGERANT DESIGN

151

Refrigerant Piping Design & Layout Best Practices

Flared fittings are used to connect the indoor units and heat recovery units to the refrigerant piping
system. Always use the proper size tool to finish the flare, creating a 45 flare (see table and diagram).
When connecting the flare nuts, coat the inside and outside with PVE refrigeration oil only. Hand tighten
the nuts at first, then, use a torque wrench and a backup wrench to finish. Avoid overtightening the flare
nuts.

MULTI V IV Outdoor Unit Engineering Manual


152

ELECTRICAL CONNECTIONS

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

ELECTRICAL
CONNECTIONS

ARUN Series Heat Pump Systems on page 154


ARUB Series Heat Recovery Systems on page 155

ARUN SERIES HEAT PUMP SYSTEMS


Triple Frame, 208-230V and 460V

Figure 38: Typical Multi V IV Heat Pump VRF System Power and Communications Wiring Schematic.
3 Phase 3 Wires
Power supply
60Hz 208-230V or
60Hz 460V

Master

Main Switch

R(L1) S(L2) T(L3)

R(L1) S(L2) T(L3)

Switch
Fused
Power supply Disconnect
1 Phase 60Hz
208-230V

MULTI V IV Outdoor Unit Engineering Manual

L1

Slave1

Slave2

R(L1) S(L2) T(L3)

Switch

Switch

Fused
Disconnect

Fused
Disconnect

L2

Disconnect

Power Line
(2-wire Cable)
Power Line
(3-wire Cable)

Communication Line
(2-wire Cable)

Pull box
(Installer option)

Pull box
(Installer
option)

Power Line
(2-wire Cable)

Pull box
(Installer
option)

Power Line
(2-wire Cable)

Power Line
(2-wire Cable)

Power Line
(2-wire Cable)

Communication Line
(3-wire Cable)

Indoor Units

Ground wiring is required to prevent accidental electrical shock during current leakage, communication problems from electrical noise,
and motor current leakage. Do not connect the ground line to the pipes.
Install a main shutoff switch that interrupts all power sources simultaneously.
If the system operates in reversed phase, it may break the compressors and other components.
If there is a possibility of reversed phase, phase loss, momentary blackout, or the power goes on and off while the system is operating,
install a field-supplied phase loss protection circuit. Operating the system in reverse phase may break the compressor and other unit
components.
Heat Pump
Between Indoor and Master Outdoor unit
SODU
B

IDU
A

3(A) 4(B)

INTERNET
A

DRY1 DRY2 GND

12 V

Master
Outdoor Unit

SODU
B

IDU
A

The GND terminal at the main PCB is a negative


terminal for dry contact, not a ground.
Make sure that terminal number of master
and slave outdoor units match. (A-A,B-B)

IDU
A

IDU
A

12 V

Master
Outdoor Unit

DRY1 DRY2 GND

12 V

Slave1
Outdoor Unit

DRY1 DRY2 GND

12 V

Slave2
Outdoor Unit

INTERNET
A

DRY1 DRY2 GND

INTERNET
A

SODU
B

SODU

3(A) 4(B)

INTERNET

Communications cables are shielded, grounded at the outdoor unit(s) only. Maintain polarity throughout the communication network.
154

ELECTRICAL CONNECTIONS

Due to our policy of continuous product innovation, some specifications may change without notification.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

ARUB SERIES HEAT RECOVERY SYSTEMS


Triple Frame, 208-230V and 460V

Figure 39: Typical Multi V IV Heat Recovery VRF System Power and Communications Wiring Schematic.
3 Phase 3 Wires
Power supply
60Hz 208-230V or
60Hz 460V

Master
R(L1) S(L2) T(L3)

Main Switch

R(L1) S(L2) T(L3)

Switch

Power supply
1 Phase 60Hz
208-230V

Fused
Disconnect

Slave1

Slave2

R(L1) S(L2) T(L3)

Switch

Switch

Fused
Disconnect

Fused
Disconnect

L1 L2
Power Line
(2-wire Cable)
Power Line
(3-wire Cable)

Disconnect

Communication Line
(2-wire Cable)
Pull box
(Installer
option)

Pull box
(Installer
option)

HR unit
Power Line
(2-wire Cable)

Power Line
(2-wire Cable)

Power Line
(2-wire Cable)

Power Line
(2-wire Cable)
Communication Line
(3-wire Cable)

Indoor Units

Ground wiring is required to prevent accidental electrical shock during current leakage, communication problems from electrical noise,
and motor current leakage . Do not connect the ground line to the pipes.
Install a main shutoff switch that interrupts all power sources simultaneously.
If the system operates in reversed phase, it may break the compressors and other components.
If there is a possibility of reversed phase, phase loss, momentary blackout, or the power goes on and off while the system is operating,
install a field-supplied phase loss protection circuit. Operating the system in reverse phase may break the compressor and other unit
components.

Between Indoor and Master Outdoor unit


SODU B

SODU A

IDU B

IDU A

INT B

SODU
INT A

Master
Outdoor Unit

IDU
A

HR unit

3(A) 4(B)

SODU

INTERNET

IDU
A

12 V

Master
Outdoor Unit

DRY1 DRY2 GND

12 V

Slave1
Outdoor Unit

DRY1 DRY2 GND

12 V

Slave2
Outdoor Unit

INTERNET
A

DRY1 DRY2 GND

3(A) 4(B)
SODU
B

IDU

INTERNET
A

The GND terminal at the main PCB is a negative terminal


for dry contact, not a ground line.
Make sure that terminal number of master and slave outdoor units
match. (A-A,B-B)

Communications cables are shielded, grounded at the outdoor unit(s) only. Maintain polarity throughout the communication network.
Due to our policy of continuous product innovation, some specifications may change without notification. ELECTRICAL CONNECTIONS
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. LG is a registered trademark of LG Corp.

155

Electrical Connections

Pull box
(Installer
option)

20001747

ISO 9001: 2008

LG ELECTRONICS INC.

LG Electronics
Commercial Air Conditioning Division
11405 Old Roswell Road
Alpharetta, Georgia 30009
www.lg-vrf.com

EM_MultiVIV_OutdoorUnits_06_15
Supersedes: EM-MultiVIV-OutdoorUnits-05-15
EM-MultiVIV-OutdoorUnits-03-15
EM-MultiVIV-OutdoorUnits-01-15
LG Electronics Commercial Products Support
1-888-865-3026 USA
Follow the prompts for commercial A/C products.

You might also like