VFD Manual
VFD Manual
VFD Manual
Thank you for choosing DELTAs high-performance VFD-S Series. The VFD-S Series is
manufactured with high-quality components and materials and incorporate the latest microprocessor
technology available.
This manual is to be used for the installation, parameter setting, troubleshooting, and daily
maintenance of the AC motor drive. To guarantee safe operation of the equipment, read the following
safety guidelines before connecting power to the AC motor drive. Keep this operating manual at
hand and distribute to all users for reference.
To ensure the safety of operators and equipment, only qualified personnel familiar with AC motor
drive are to do installation, start-up and maintenance. Always read this manual thoroughly before
using VFD-S series AC Motor Drive, especially the WARNING, DANGER and CAUTION notes.
Failure to comply may result in personal injury and equipment damage. If you have any questions,
please contact your dealer.
PLEASE READ PRIOR TO INSTALLATION FOR SAFETY.
DANGER!
1.
AC input power must be disconnected before any wiring to the AC motor drive is made.
2.
A charge may still remain in the DC-link capacitors with hazardous voltages, even if the power
has been turned off. To prevent personal injury, please ensure that power has been turned off
before opening the AC motor drive and wait ten minutes for the capacitors to discharge to safe
voltage levels.
3.
4.
The AC motor drive may be destroyed beyond repair if incorrect cables are connected to the
input/output terminals. Never connect the AC motor drive output terminals U/T1, V/T2, and W/T3
directly to the AC mains circuit power supply.
5.
Ground the VFD-S using the ground terminal. The grounding method must comply with the laws
of the country where the AC motor drive is to be installed. Refer to the Basic Wiring Diagram.
6.
VFD-S series is used only to control variable speed of 3-phase induction motors, NOT for 1phase motors or other purpose.
7.
VFD-S series shall NOT be used for life support equipment or any life safety situation.
WARNING!
1.
DO NOT use Hi-pot test for internal components. The semi-conductor used in the AC motor
drive is easily damaged by high-pressure.
2.
There are highly sensitive MOS components on the printed circuit boards. These components
are especially sensitive to static electricity. To prevent damage to these components, do not
touch these components or the circuit boards with metal objects or your bare hands.
3.
Only qualified personnel are allowed to install, wire and maintain AC motor drive.
CAUTION!
1.
Some parameter settings will cause the motor to run immediately after applying power.
2.
DO NOT install the AC motor drive in a place subjected to high temperature, direct sunlight,
high humidity, excessive vibration, corrosive gases or liquids, or airborne dust or metallic
particles.
3.
Only use AC motor drives within specification. Failure to comply may result in fire, explosion or
electric shock.
4.
To prevent personal injury, please keep children and unqualified people away from the
equipment.
5.
When the motor cable between the AC motor drive and motor is too long, the layer insulation of
the motor may be damaged. Please use a frequency inverter duty motor or add an AC output
reactor to prevent damage to the motor. Refer to appendix B Reactor for details.
6.
The rated voltage for the AC motor drive must be 240V ( 480V for 460V models) and the
mains supply current capacity must be 5000A RMS (10000A RMS for the 40hp (30kW)
models).
Table of Contents
Preface ..............................................................................................................i
Table of Contents ...........................................................................................iii
Chapter 1 Introduction .................................................................................1-1
1.1 Receiving and Inspection.................................................................... 1-1
1.1.1 Nameplate Information................................................................ 1-1
1.1.2 Model Explanation ...................................................................... 1-1
1.1.3 Series Number Explanation ........................................................ 1-2
1.1.4 Drive Frames .............................................................................. 1-2
1.2 Appearances....................................................................................... 1-2
1.3 Installation Steps ................................................................................ 1-3
1.4 Storage ............................................................................................... 1-4
Chapter 2 Installation and Wiring ...............................................................2-1
2.1 Ambient Conditions............................................................................. 2-1
2.2 Installation........................................................................................... 2-1
2.3 Dimensions ......................................................................................... 2-3
2.4 Wiring ............................................................................................... 2-16
2.4.1 Basic Wiring .............................................................................. 2-17
2.4.2 External Wiring.......................................................................... 2-21
2.4.3 Main Terminals Connections .................................................... 2-22
2.4.4 Control Terminals...................................................................... 2-24
2.4.5 Main Circuit Terminals .............................................................. 2-28
Chapter 1 Introduction
MODEL : VFD007S23A
INPUT
MADE IN XXXXX
Series Name
Version Type
Input Voltage
11:Single phase 115V
21:Single phase 230V
23:Three phase 230V
43:Three phase 460V
S Series
Applicable motor capacity
002: 0.25HP(0.2kW)
004: 0.5HP(0.4kW)
007: 1 HP(0.7kW)
022: 3 HP(2.2kW)
1-1
007S23A 0T 6 01
Production number
Production week
Production year 2006
Production factory
(Taoyuan)
Model
If the nameplate information does not correspond to your purchase order or if there are
any problems, please contact your distributor.
S1
S2
Power range
0.25-2hp
(0.2-1.5kW)
Models
VFD002S11A/11B/21A/21B/21E/23A,
VFD004S11A/11B/21A/21B/21E/23A/43A/43B/43E,
VFD007S21A/21B/21E/23A/43A/43B/43E, VFD015S23D
1-5hp
VFD007S11A/11B, VFD015S21D/21E/21U/43D/43E/43U,
(0.75-3.7kW)
VFD022S21D/21E/21U/23D/43D/43E/43U
1.2 Appearances
VFD002S11A/11B/21A/21B/23A,
1-2
HEAT SINK
DIVISION
PLATE
SCREW
Installation Steps
1.
Remove front cover screw and open.
2.
Remove Division Plate. If using optional
conduit bracket, please refer to next
page.
3.
Connect AC Input Power and motor leads.
Never connect the AC drive output
terminals U/T1, V/T2, W/T3 to main AC
Input power.
4.
Reinstall Division Plate.
SCREW
SCREW
1-3
CONDUIT
BRACKET
SCREW
SCREW
1.4 Storage
The AC motor drive should be kept in the shipping carton or crate before installation. In order to
retain the warranty coverage, the AC motor drive should be stored properly when it is not to be used
for an extended period of time. Storage conditions are:
Store in a clean and dry location free from direct sunlight or corrosive fumes.
Store within an ambient temperature range of -20 C to +60 C.
Store within a relative humidity range of 0% to 90% and non-condensing environment.
Store within an air pressure range of 86kPa to 106kPa.
CAUTION!
1.
DO NOT store in an area with rapid changes in temperature. It may cause condensation and
frost.
2.
DO NOT place on the ground directly. It should be stored properly. Moreover, if the surrounding
environment is humid, you should put exsiccator in the package.
1-4
3.
If the AC motor drive is stored for more than 3 months, the temperature should not be higher
than 30 C. Storage longer than one year is not recommended, it could result in the degradation
of the electrolytic capacitors.
4.
When the AC motor drive is not used for a long time after installation on building sites or places
with humidity and dust, its best to move the AC motor drive to an environment as stated above.
1-5
1-6
Air Temperature:
Relative Humidity:
Atmosphere pressure:
Installation Site Altitude:
Vibration:
Storage
Transportation
Temperature:
Relative Humidity:
Atmosphere pressure:
Vibration:
Pollution Degree
CAUTION!
1.
Operating, storing or transporting the AC motor drive outside these conditions may cause
damage to the AC motor drive.
2.
2.2 Installation
1.
Mount the AC motor drive vertically on a flat vertical surface by using bolts or screws. Other
directions are not allowed.
2.
The AC motor drive will generate heat during operation. Allow sufficient space around the unit
for heat dissipation.
3.
The heat sink temperature may rise to 90C when running. The material on which the AC motor
drive is mounted must be noncombustible and be able to withstand this high temperature.
4.
When the AC motor drive is installed in a confined space (e.g. cabinet), the surrounding
temperature must be within 10 ~ 40C with good ventilation. DO NOT install the AC motor drive
in a space with bad ventilation.
2-1
5.
When installing multiple AC motor drives in the same cabinet, they should be adjacent in a row
with enough space. When installing one AC motor drive below another one, use a metal
separation barrier between the AC motor drives to prevent mutual heating. Refer to figure below
for details.
6.
Prevent fiber particles, scraps of paper, saw dust, metal particles, etc. from adhering to the
heatsink.
Mounting Clearances
150mm
(6inch)
Air Flow
50mm
(2inch)
50mm
(2inch)
150mm
(6inch)
2-2
2.3 Dimensions
(Dimensions are in millimeter and [inch])
Frame S1: VFD002S11A, VFD002S21A, VFD002S23A
8.1 [0.32]
5.0 [0.20]
11.1 [0.44]
3.0 [0.12]
5.0 [0.20]
88.0 [3.47]
13.0 [0.51]
148.0 [5.83]
5.8 [0.23]
132.2 [5.21]
85.0 [3.35]
74.0 [2.92]
2-3
5 . 8 [0. 23 ]
88 .0 [3 .4 7 ]
67 .8 [2 .6 7]
5. 0 [0 . 20 ]
2-4
13 .0 [0 .5 1]
5 . 0 [0. 20 ]
8.1 [0.32]
3.0 [0.12]
1 6.0 [ 0.63]
73 .0 [2 .8 8 ]
14 8.0 [ 5.83]
1 3 .0 [0 .5 1]
13 2.2 [5.21]
74 .0 [2 .9 2]
1 1.1 [ 0.44]
8 5 .0 [3 .3 5]
85 .0 [3 .3 5]
5. 8 [0. 23 ]
10 2. 0 [ 4. 02]
5 . 0 [0. 2 0 ]
8.1 [0.32]
5. 0 [0. 20 ]
1 1.1 [0.44]
3.0 [ 0.12]
1 4 8.0 [5.83]
2. 8 [0. 11 ]
1 32.2 [5.21]
74 .0 [2 .9 2]
2-5
67 .8 [2 .6 7]
5 . 0 [0. 20 ]
2-6
2 7 .0 [1 .0 6]
8 .1 [ 0 .32]
5. 0 [0. 20 ]
11.1 [0 .44]
3.0 [0.12]
73 .0 [2 .8 8]
10 2. 0 [ 4. 02]
2. 8 [0 . 11 ]
1 48 .0 [5.83 ]
1 32 .2 [5.21 ]
5. 8 [0. 23 ]
16 .0 [0.63 ]
85 .0 [3 .3 5]
74 .0 [2 .9 2 ]
85 .0 [3 .3 5]
5. 8 [0. 23 ]
12 4. 0 [ 4. 89]
5. 0 [0. 20 ]
8.1 [ 0.32]
5. 0 [0. 20 ]
1 1.1 [ 0.44]
3.0 [0 .12]
14 8.0 [ 5.83]
2. 8 [0. 11 ]
13 2.2 [ 5.21]
74 .0 [2 .9 2]
2-7
67 .8 [2 .6 7]
5. 0 [0. 20 ]
2-8
50 .0 [1 .9 7]
8.1 [0.32]
5. 0 [0. 20 ]
11 .1 [0.44]
3. 0 [0.12]
16.0 [0.63]
73 .0 [2 .8 8]
12 4. 0 [ 4. 89]
2. 8 [0. 11 ]
148.0 [5.83]
5. 8 [0. 23 ]
1 32.2 [5.21]
85 .0 [3 .3 5]
74 .0 [2 .9 2]
85 .0 [3 .3 5]
5. 8 [0. 23 ]
12 6. 0 [ 4. 96]
5. 0 [0. 20 ]
8.1 [0.32]
5. 0 [0. 20 ]
1 1.1 [ 0.44]
3.0 [0 .12]
14 8.0 [ 5.83]
3. 0 [0. 12 ]
13 2.2 [ 5.21]
74 .0 [2 .9 2]
2-9
67 .8 [2 .6 7]
5. 0 [0. 20 ]
2-10
5 1 .0 [2 .0 1]
8 .1 [0 .32]
5. 0 [0. 2 0 ]
11 .1 [0 .44]
3 . 0 [0 .1 2]
16 .0 [0.63]
73 .0 [2 .8 8]
12 6. 0 [ 4 . 96]
3. 0 [0. 1 2 ]
1 4 8.0 [5.83]
5 . 8 [0. 23 ]
1 32 .2 [5.21 ]
85 .0 [3 .3 5]
74 .0 [2 .9 2]
85 .0 [3 .3 5]
5. 8 [ 0. 23 ]
12 7. 0 [ 5. 00]
5. 0 [ 0. 20 ]
8.3 [ 0.33]
14 8.0 [ 5.83]
8. 5 [ 0. 33 ]
13 3.7 [ 5.27]
74 .0 [2 .9 2]
2-11
10 0. 0 [ 3. 94]
12 9. 0 [ 5. 08]
5. 5 [0. 22 ]
2-12
9 .5 [0 .38]
1 .0 [0 .04]
5. 5 [0. 22 ]
6 .5 [ 0.26]
1 86.0 [7.33]
5. 4 [0. 21 ]
1 73.0 [6.81]
86 .5 [3 .4 1]
10 0. 0 [ 3. 94]
5. 5 [0. 22 ]
9.5 [0 .38]
1.0 [0 .04]
5. 5 [0. 22 ]
53 .5 [2 .11]
6.5 [0.26]
67 .8 [2 .6 7]
16 .0 [0 .63]
73 .0 [2 .8 8]
12 9. 0 [ 5. 08]
18 6.0 [7.33]
5. 4 [0. 21 ]
173 .0 [6.82]
86 .5 [3 .4 1]
2-13
10 0 . 0 [ 3. 9 4]
5. 4 [0. 21 ]
12 9. 3 [ 5 . 09]
5. 5 [0 . 22 ]
2-14
6 .5 [0.26]
5. 5 [0. 22 ]
9 .5 [0 .37]
1.0 [0.04]
1 8 6 .0 [ 7.33]
8. 5 [0. 33 ]
1 7 3 .0 [ 6.82]
86 .5 [3 .4 1]
5.4 [0.21]
129.3 [5.09]
67.8 [2.67]
5.5 [0.22]
5.5 [0.22]
53.9 [2.12]
9.5 [0.37]
1.0 [0.04]
16.0 [0.63]
73.0 [2.88]
186.0 [7.33]
8.5 [0.33]
173.0 [6.82]
86.5 [3.41]
6.5 [0.26]
100.0 [3.94]
2-15
2.4 Wiring
After removing the front cover, check if the power and control terminals are clear of debris. Be sure
to observe the following precautions when wiring.
General Wiring Information
Applicable Codes
All VFD-S series are Underwriters Laboratories, Inc. (UL) and Canadian Underwriters
Laboratories (cUL) listed, and therefore comply with the requirements of the National
Electrical Code (NEC) and the Canadian Electrical Code (CEC).
Installation intended to meet the UL and cUL requirements must follow the instructions
provided in Wiring Notes as a minimum standard. Follow all local codes that exceed UL
and cUL requirements. Refer to the technical data label affixed to the AC motor drive and
the motor nameplate for electrical data.
The "Line Fuse Specification" in Appendix B, lists the recommended fuse part number
for each S-Series part number. These fuses (or equivalent) must be used on all
installations where compliance with U.L. standards is a required.
2-16
2.
No loose wires?
3.
A charge may still remain in the DC bus capacitors with hazardous voltages even if the
power has been turned off. To prevent personal injury, please ensure that the power is
turned off and wait ten minutes for the capacitors to discharge to safe voltage levels
before opening the AC motor drive.
DANGER!
1.
All the units must be grounded directly to a common ground terminal to prevent electric shock,
fire and interference.
2.
Only qualified personnel familiar with AC motor drives are allowed to perform installation, wiring
and commissioning.
3.
Make sure that the power is off before doing any wiring to prevent electric shocks.
2-17
For VFDXXXSXXA/B/D/U
E
R/L1
S/L2
T/L3
SA
MC
OFF
ON
RB
RC
17V
Grounding resistance
less than 100
MC
17V
4.7k
17V
4.7k
17V
4.7k
17V
4.7k
4.7k
17V
17V
4.7k
47K
2-18
For VFDXXXSXXE
NPN (sink mode)
Braking resistor (optional)
select 80 120W, 200 120W
400 120W
Jumper
Main Circuit Power
+1
E
R/L1
S/L2
T/L3
NFB
R/L1
S/L2
T/L3
Recommended Circuit
when power supply
is turned OFF by a
fault output
SA
MC
OFF
ON
RB
RC
+2/B1
+17V
CPU
2.4
MC
Factory default
Forward/Stop
Reverse/Stop
Reset
Multi-step 1
Multi-step 2
Multi-step 3
Comm. signal (sink)
Analog voltage 3
010VDC
Potentiometer Pot. 2
3K5K
Analog current 1
Factory default: output freq. (Pot.)
determined by the Potentiometer
on the control panel.
Main circuit (power) terminals
B2
U/T1
V/T2
W/T3
47 AFM
11V
M0
GND
M1
M2
NPN
M3
PNP
M4
J2
RA
RB
RC
M5
GND
E
+10V 10mA
(MAX)
2 1
AVI 3
47K
250
GND
IM
3~
Grounding resistance
less than 100
47K
17V
AC Motor
Potentiometer(1K )
Analog output
DC 010V
Mo1
Multi-function Photocoupler
output below 48VDC 50mA
Factory default: Indicates
MCM during operation
RJ-11
6 1
2-19
For VFDXXXSXXE
PNP (source mode)
Braking resistor (optional)
select 80 120W, 200 120W
400 120W
Jumper
Main Circuit Power
NFB
R/L1
S/L2
T/L3
Recommended Circuit
when power supply
is turned OFF by a
fault output
SA
MC
OFF
+2/B1
+1
E
R/L1
S/L2
T/L3
ON
RB
RC
B2
U/T1
+17V
CPU
MC
2.4
V/T2
W/T3
Forward/Stop
Reverse/Stop
Reset
47 AFM
47K
Multi-step 1
Multi-step 2
Multi-step 3
Analog voltage 3
010VDC
Potentiometer Pot. 2
3K5K
Analog current 1
Factory default: output freq. (Pot.)
determined by the Potentiometer
on the control panel.
Main circuit (power) terminals
11V
M0
GND
M1
M2
NPN
M3
PNP
M4
RA
RB
J2
RC
M5
GND
E
+10V 10mA
(MAX)
2 1
AVI 3
250
GND
47K
IM
3~
Grounding resistance
less than 100
AC Motor
Potentiometer(1K )
Analog output
DC 010V
Mo1
Multi-function Photocoupler
output below 48VDC 50mA
Factory default: Indicates
MCM during operation
RJ-11
6 1
2-20
Items
FUSE/NFB
Magnetic
contactor
Fuse/NFB
(Optional)
Magnetic
contactor
(Optional)
Input AC
Line Reactor
Zero-phase
Reactor
EMI Filter
R/L1
S/L2
T/L3
+1
DC
Choke
+2/B1
Braking
Resistor
B2
U/T1
V/T2
Explanations
Power
supply
EMI filter
(Optional)
To reduce electromagnetic
interference, please refer to Appendix
B for more details.
Brake
resistor
(Optional)
W/T3
Zero-phase
Reactor
Output AC
Line Reactor
Motor
2-21
L/L1, N/L2
+2/B1, B2
+2/B1, +1
Forward
running
2-22
+2/B1
B2
WARNING!
Short-circuiting [+2/B1, B2] can damage the AC motor drive.
Grounding terminals (
Make sure that the leads are connected correctly and the AC drive is properly grounded.
(Ground resistance should not exceed 0.1.)
Use ground leads that comply with local regulations and keep them as short as possible.
Multiple VFD-S units can be installed in one location. All the units should be grounded
directly to a common ground terminal, as shown in the figure below. Ensure there are
no ground loops.
excellent
good
not allowed
2-23
+10V
RA
RB
RC
MO1
MCM
Operation freq.
setting
potentiometer
VR : 3K~5K
Corrector
potentiometer
VR : 1K~5K
Freq. meter
0~10 VDC
Full scale voltmeter
RJ11
Multi-step speed 3
Multi-step speed 2
Multi-step speed 1
Reset
Reverse/Stop
Forward/Stop
6~1
B. XXXSXXE
Multi-step speed 3
2-24
Terminal
Symbol
Terminal Function
M0
M1
Multi-function input 1
M2
Multi-function input 2
M3
Multi-function input 3
Terminal
Symbol
Terminal Function
M4
Multi-function input 4
M5
Multi-function Input 5
+17V
DC Voltage Source
GND
AFM
0~10V
ondometer
Max. 2mA
GND
Internal Circuit
RA
RB
RC
Resistive Load:
5A(N.O.)/3A(N.C.) 240VAC
5A(N.O.)/3A(N.C.) 24VDC
Inductive Load:
1.5A(N.O.)/0.5A(N.C.) 240VAC
1.5A(N.O.)/0.5A(N.C.) 24VDC
Refer to Pr.3-06 for programming
MO1-DCM
MO1
Mo1
Multi-function Output 1
(Photocoupler)
MCM
internal circuit
MCM
+10V
2-25
Terminal
Symbol
Terminal Function
AVI circuit
+10V
ACI
J1
AVI
AVI
GND
Internal Circuit
AVI
ACI circuit
ACI
ACI
J1
GND
Internal Circuit
AVI
C
GND
ferrite core
2-26
General
Keep control wiring as far as possible from the power wiring and in separate conduits to
avoid interference. If necessary let them cross only at 90 angle.
The AC motor drive control wiring should be properly installed and not touch any live
power wiring or terminals.
NOTE
If a filter is required for reducing EMI (Electro Magnetic Interference), install it as close as
possible to AC drive. EMI can also be reduced by lowering the Carrier Frequency.
When using a GFCI (Ground Fault Circuit Interrupter), select a current sensor with
sensitivity of 200mA, and not less than 0.1-second detection time to avoid nuisance
tripping.
DANGER!
Damaged insulation of wiring may cause personal injury or damage to circuits/equipment if it comes
in contact with high voltage.
2-27
Power terminal
AC Input Line
Ter minal
Groun d
Motor
Conne ction
Power Terminal:
Torque: 12 kgf-cm (10 lbf-in)
Wire Gauge: 14-20 AWG (2.1-0.5mm2)
Wire Type: Copper only, 75oC
2-28
Power terminal
AC Input Line
Ter minal
Motor
Conne ction
Power Terminal:
Torque: 12 kgf-cm (10 lbf-in)
Wire Gauge: 14-20 AWG (2.1-0.5mm2)
Wire Type: Copper only, 75oC
2-29
Power terminal
AC Input Line
Terminal
Motor
Conne ction
Power Terminal:
Torque: 12 kgf-cm (10 lbf-in)
Wire Gauge: 14-20 AWG (2.1-0.5mm2)
Wire Type: Copper only, 75oC
2-30
VFD007S11A/B
Power terminal
AC Input Line
Terminal
G roun d
Motor
Conne ction
Power Terminal:
Torque: 20 kgf-cm (17.4 lbf-in)
Wire Gauge: 10-18 AWG (5.3-0.8mm2)
Wire Type: stranded copper only, 75oC
2-31
VFD015S21U/43D/43E/43U, VFD022S21U/23D/43D/43E/43U
Power terminal
AC Input Line
Terminal
Groun d
Motor
Conne ction
Br ak ing DC Reacto r
Res istor
Power Terminal:
Torque: 20 kgf-cm (17.4 lbf-in)
Wire Gauge: 10-18 AWG (5.3-0.8mm2)
Wire Type: stranded copper only, 75oC
2-32
VFD015S21D/E, VFD022S21D/E
Power terminal
AC Input Line
Ter minal
G roun d
Motor
Conne ction
Br ak ing DC Reacto r
Res istor
Power Terminal:
Torque: 20 kgf-cm (17.4 lbf-in)
Wire Gauge: 10-18 AWG (5.3-0.8mm2)
Wire Type: stranded copper only, 75oC
2-33
2-34
Chapter 3 Start Up
MIN. MAX.
STOP
RUN
STOP/RESET
MODE
PROG
DATA
3-1
Operation Command
Source
Frequency Source
Keypad
RUN
MI2
MI3
Operate from
external signal
GND
Parameter
setting:
4-05=10
4-06=11
STOP/RESET
External terminals
input:
M0-GND
M1-GND
AVI, ACI
2.
3.
Pressing
RUN
should press
press
4.
key for forward running. And if you want to change to reverse running, you
key in
STOP/RESET
key.
key.
If the results of trial run are normal, please start the formal run.
3-2
NOTE
1. Stop running immediately if any fault occurs and refer to the troubleshooting guide for solving the
problem.
2. Do NOT touch output terminals U/T1, V/T2, W/T3 when power is still applied to R/L1, S/L2, T/L3
even when the AC motor drive has stopped. The DC-link capacitors may still be charged to
hazardous voltage levels, even if the power has been turned off.
3. To avoid damage to components, do not touch them or the circuit boards with metal objects or
your bare hands.
3-3
3-4
LED indication
Light during RUN,
STOP, FWD and
REV operation.
RUN
FWD
REV
Potentiometer for
frequency setting.
Could be the Master
Frequency input
by setting Pr.2-00.
Mode Key
Change between
different display
modes.
MIN. MAX.
STOP
RUN Key
Start inverter drive operation.
STOP/RESET Key
Stop inverter drive operation
and reset the inverter after
faults occurred.
RUN
STOP/RESET
PROG
DATA
MODE
PROG/DATA Key
Set the different parameters
and enter information.
UP and DOWN Key
Sets the parameter number
or changes the numerical
data such as the freq.
reference.
STOP
Descriptions
Displays the AC drive Master Frequency.
Displays the actual output frequency at terminals U/T1, V/T2, and W/T3.
User defined unit (where U = F x Pr.00.05)
Displays the output current at terminals U/T1, V/T2, and W/T3.
4-1
Display Message
Descriptions
The internal PLC process step currently being performed.
Displays the DC-BUS voltage
Displays the output voltage
Displays the AC motor drive forward run status.
Displays the AC motor drive reverse run status.
The counter value (C).
Displays the selected group.
Displays the selected parameter.
Displays the actual stored value of the selected parameter.
Display End for approximately 0.5 second if input has been. After a
parameter value has been set, the new value is automatically stored in
memory. To modify an entry, use the
keys.
4-2
START
GO START
Setting parameters
or
Success to
set parameter.
To shift data
START
or
or
4-3
4-4
Chapter 5 Parameters
The VFD-S parameters are divided into 11 groups by property for easy setting. In most applications,
the user can finish all parameter settings before start-up without the need for re-adjustment during
operation.
User Parameters
Group 1:
Basic Parameters
Group 2:
Group 3:
Group 4:
Group 5:
Group 6:
Protection Parameters
Group 7:
Motor Parameters
Group 8:
Special Parameters
Group 9:
Communication Parameters
Group A:
PID Parameters
5-1
Explanation
Identity Code of the AC Motor Drive
Rated Current Display of the AC
Motor Drive
Parameter Reset
0-05
0-06
0-07
0-08
0-09
User-Defined Coefficient K
Software Version
Password Input
Password Set
Memory Mode Selections
Settings
Read-only
Read-only
d09: All parameters are reset to
factory settings (50Hz,
220V/380V)
d10: All parameters are reset to
factory settings (60Hz,
220V/440V)
d0: Display the frequency command
value (LED F)
d1: Display the actual output
frequency (LED H)
d2: Multifunction display, see Pr.0004
d3: Display output current (LED A)
d4: Display forward/reverse
command (Frd/rEv)
d0: Display User-Defined Unit (u)
d1: Display Counter Value (C)
d2: Display Process Operation (1.tt)
d3: Display DC-BUS Voltage ( u )
d4: Display output voltage (E)
d5: Display frequency commands of
PID (P)
d6: Display analog feedback signal
value (b) (%)
d0.1 to d160
Read-only
d0 to d999
d0 to d999
d0 to d63
Factory
NOTE
Setting
d#
d##.#
d0
d0
d0
d1.0
d#.#
d0
d0
d8
Explanation
Settings
1-00
1-01
1-02
1-03
1-04
5-2
d50.0 to d400 Hz
Factory
NOTE
Setting
d60.0
d60.0
d220
d440
d1.0
d12
Pr.
1-05
1-06
1-07
1-08
1-09
1-10
1-11
1-12
1-13
1-14
1-15
1-16
1-17
1-18
Explanation
Settings
Factory
NOTE
Setting
d24
d1.0
d12.0
d24.0
d100
d0
d10.0
d10.0
d10.0
d10.0
d10.0
d6.0
d0
d0
d0
d0.0
2-00
Explanation
Settings
d0: Master Frequency input
determined by digital keypad.
(record the frequency of power
loss and it can do analog
overlap plus)
d1: Master Frequency determined
by analog signal DC 0V-10V
(external terminal AVI). (wont
record the frequency of power
loss and it cant do analog
overlap plus)
d2: Master Frequency determined
by analog signal DC 4mA 20mA (external terminal AVI).
(wont record the frequency of
power loss and it cant do
analog overlap plus)
d3: Master Frequency determined
by Potentiometer on the digital
keypad. (wont record the
frequency of power loss and it
can do analog overlap plus)
Factory
NOTE
Setting
d0
5-3
Pr.
2-00
2-01
2-02
2-03
2-04
2-05
2-06
Explanation
Settings
Factory
NOTE
Setting
d0
d0
d0
d10
d0
d0
d0
5-4
Pr.
3-00
Explanation
Analog Output Signal
Settings
d0: analog frequency meter
d1: analog current meter
Factory
NOTE
Setting
d0
d1 to d200%
d1.0 to d400 Hz
3-03
3-04
d0 to d999
d0 to d999
d0
d0
d0: No Function
d1
d8
3-05
3-06
d100
d1.0
Explanation
4-04
Settings
d 0.0 to d 100.0%
d0: Positive Bias
d1: Negative Bias
d1 to d200 %
Factory
NOTE
Setting
d0.0
d0
d100
d0
d0: No Function
d1: FWD/STOP, REV/STOP
d2: FWD/REV, RUN/STOP
d3: 3-wire Operation Control Mode
d4: E.F. External Fault Input (N.O.)
d5: E.F. External Fault Input (N.C.)
d6: Reset
d7: Multi-Step Speed Command 1
d8: Multi-Step Speed Command 2
d9: Multi-Step Speed Command 3
d1
5-5
Pr.
4-05
Explanation
Multi-Function Input Terminal 2 (M2)
Multi-Function Input Terminal 3 (M3)
4-06
4-08
4-09
Settings
d10: Jog Operation
d11: Accel/decel Inhibit
d12: First or Second
Acceleration/deceleration Time
Selection
d13: External base block (N.O.)
d14: External base block (N.C.)
d15: Up: Increment master
frequency
d16: Down: Decrement master
frequency
d17: Run PLC Program
d18: Pause PLC Program
d19: Counter Trigger Signal
d20: Counter Reset
d21: Select ACI / Deselect AVI
d22: PID Function Disabled
d23: JOG FWD
d24: JOG REV
d25: The source of master
frequency is AVI.
d26: The source of master
frequency is ACI.
d27: Press UP/DOWN key to switch
forward/reverse (N.O.) motion
d28: Press UP/DOWN key to switch
forward/reverse (N.C.) motion
d29: M0: 0: RUN 1: STOP, M1: no
function, Direction is controlled
by keypad
d0: Disable
d1: Enable
4-10
Up/Down Mode
4-11
Factory
NOTE
Setting
d6
d7
d8
d9
d0
d3
d1
Explanation
1st Step Speed Freq.
2nd Step Speed Freq.
Settings
d0.0 to d400 Hz
d0.0 to d400 Hz
Factory
NOTE
Setting
d0.0
d0.0
Pr.
Explanation
5-02
5-03
5-04
5-05
5-06
5-07
PLC Mode
5-08
5-09
5-10
5-11
5-12
5-13
5-14
5-15
5-16
Settings
d0.0 to d400 Hz
d0.0 to d400 Hz
d0.0 to d400 Hz
d0.0 to d400 Hz
d0.0 to d400 Hz
d0: Disable PLC Operation
d1: Execute one program cycle
d2: Continuously execute program
cycles
d3: Execute one program cycle step
by step
d4: Continuously execute one
program cycle step by step
d5: Disable PLC operation, but can
set direction of 1st speed to 7th
speed
d0 to d255 (0: FWD 1: REV)
d0 to d65500 Sec
d0 to d65500 Sec
d0 to d65500 Sec
d0 to d65500 Sec
d0 to d65500 Sec
d0 to d65500 Sec
d0 to d65500 Sec
d0 to d65500 Sec
Factory
NOTE
Setting
d0.0
d0.0
d0.0
d0.0
d0.0
d0
d0
d0
d0
d0
d0
d0
d0
d0
d0
Explanation
Over-Voltage Stall Prevention
Over-Voltage Stall Prevention Level
6-02
6-03
6-04
Settings
d0: Disable
d1: Enable
115V/230V series: d350 to d410V
460V series: d700 to d820V
d20 to d150%
d0: Disabled
d1: Enabled during constant speed
operation. After the over-torque
is detected, keep running until
OL1 or OL occurs.
d2: Enabled during constant speed
operation. After the over-torque
is detected, stop running.
d3: Enabled during running and
continues before Continuous
Output Time Limit (Pr.6-05) is
reached
d4: Enabled during running. After
the over-torque is detected, stop
running.
d30 to d200%
Factory
NOTE
Setting
d1
d390
d780
d130
d0
d150
5-7
Pr.
Explanation
Settings
Factory
NOTE
Setting
d0.1
6-05
6-06
d0 to d2
d2
d60
6-09
6-10
5-8
d0: No fault
d1: Over current (oc)
d2: Over voltage (ov)
d3: Over heat (oH)
d4: Over load (oL)
d5: Over load (oL1)
d6: External fault (EF)
d7: Reserved
d8: Reserved
d9: Excess current during
acceleration (ocA)
d10: Excess current during
deceleration (ocd)
d11: Excess current during steady
state (ocn)
d12: Ground fault (GF)
d13: Reserved
d14: Low voltage (Lv)
d15: CPU failure 1 (cF1)
d16: CPU failure 2 (cF2)
d17: Base block (b.b.)
d18: Overload (oL2)
d19: Auto acceleration/deceleration
failure (cFA)
d20: Software protection enable
(codE)
d21: Reserved
d22: CPU failure (cF3.1)
d23: CPU failure (cF3.2)
d24: CPU failure (cF3.3)
d25: CPU failure (cF3.4)
d26: CPU failure (cF3.5)
d27: CPU failure (cF3.6)
d28: CPU failure (cF3.7)
d29: Hardware protection failure
(HPF.1)
d30: Hardware protection failure
(HPF.2)
d31: Hardware protection failure
(HPF.3)
d32: Communication time-out
(CE10)
d33: Reserved
d34: Software error (SErr)
d35: Reserved
d36: PID error (Pld)
d37: Reserved
d38: Phase loss (PHL)
d0
d0
Explanation
Torque Compensation
Settings
d30 to d120%
Factory
NOTE
Setting
d85
d0 to d90%
d50
d0 to d10
d1
d0.0 to d10.0
d0.0
8-04
8-05
8-06
8-07
8-08
8-09
8-10
8-11
8-12
8-13
8-14
8-15
8-16
8-17
Explanation
DC Braking Voltage Level
DC Braking Time during Start-Up
DC Braking time during Stopping
Start-Point for DC Braking
Settings
d0 to d30%
d0.0 to d60.0 Sec
d0.0 to d60.0 Sec
d0.0 to d400 Hz
d0: Operation stops after
Momentary Power Loss
d1: Operation continues after
momentary power loss, speed
Momentary Power Loss Operation
search starts with the Master
Selection
Frequency reference value
d2: Operation continues after
momentary power loss, speed
search starts with the minimum
frequency
Maximum Allowable Power Loss Time d0.3 to d5.0 Sec
B.B. Time for Speed Search
d0.3 to d5.0 Sec
Current Limit for Speed Search
d30 to d200%
Skip Frequency 1 Upper Limit
d0.0 to d400 Hz
Skip Frequency 1 Lower Limit
d0.0 to d400 Hz
Skip Frequency 2 Upper Limit
d0.0 to d400 Hz
Skip Frequency 2 Lower Limit
d0.0 to d400 Hz
Skip Frequency 3 Upper Limit
d0.0 to d400 Hz
Skip Frequency 3 Lower Limit
d0.0 to d400 Hz
Auto Restart After Fault
d0 to d10
d0: Enable
AVR Function
d1: Disable
d2: Disable when deceleration
Software Braking Level
115V/230V series: d350 to d450V
460V series: d700 to d900V
DC Braking Lower Bound Limit
d0.0 to d400 Hz
Factory
NOTE
Setting
d0
d0.0
d0.0
d0.0
d0
d2.0
d0.5
d150
d0.0
d0.0
d0.0
d0.0
d0.0
d0.0
d0
d2
d380
d760
d0.0
5-9
Pr.
9-00
Explanation
Communication
Address
9-02
Transmission Fault
Treatment
9-04
Communication
Protocol
Settings
d1 to d254
Factory
NOTE
Setting
d1
d1
d1
d0
d0
d0
Explanation
Settings
Factory
NOTE
Setting
A-00
A-01
d0 to d999
A-02
d0 to d999
d100
A-03
d0 to d999
d100
A-04
d0 to d100
d0
A-05
d0 to d100%
A-06
d0 to d999
5-10
d0
d100
d100
d0
Pr.
Explanation
Settings
Factory
NOTE
Setting
A-07
d0 to d110%
d100
A-08
d0.0
A-09
A-10
A-11
A-12
A-13
Sleep Frequency
Wakeup Frequency
Sleep Period
PID User Defined
d0.0 to d400Hz
d0.0 to d400Hz
d0.0 to d650 seconds
d0.0 to d400
d0
d0.0
d0.0
d0.0
d0.0
5-11
Purpose
Restart freerunning motor
Functions
Before the free-running motor is
completely stopped, it can be restarted
without detection of motor speed. The
AC motor drive will auto search motor
speed and will accelerate when its
speed is the same as the motor speed.
Related
Parameters
8-06
8-07
Purpose
Functions
If the running direction of the freerunning motor is not steady, please
execute DC braking before start-up.
Related
Parameters
8-00
8-01
8-17
Multi-step Operation
Applications
Conveying machinery
Purpose
Functions
Related
Parameters
4-04~4-08
5-00~5-06
Purpose
Functions
Switching
acceleration and
deceleration times
by external signal
Related
Parameters
1-09~1-12
4-04~4-08
Operation Command
Applications
General application
5-12
Purpose
Selecting the
source of control
signal
Functions
Related
Parameters
2-01
4-04~4-08
Two-wire/three-wire
Applications
Purpose
Functions
FWD/STOP
M0 "Open": Stop, "Close": FWD Run
Related
Parameters
4-04~4-08
REV/STOP
M1 "Open": Stop, "Close":REV Run
GND
General application
To run, stop,
forward and
reverse by external
terminals
RUN/STOP
M1 "Open": FWD, "Close":REV
REV/FWD
GND
3-wire
STOP
RUN
M0 Run command, Runs when "close"
M2 Stop command, stops when "Open"
M1 REV/FWD Run selection
Frequency Hold
Applications
General application
Purpose
Functions
Acceleration/
Hold output frequency during
deceleration pause Acceleration/deceleration
Related
Parameters
4-04~4-08
Purpose
Functions
Related
Parameters
8-14
High-speed rotors
Purpose
Emergency stop
without brake
resistor
Functions
AC motor drive can use DC braking
for emergency stop when quick stop is
needed without brake resistor. When
used often, take motor cooling into
consideration.
Related
Parameters
8-00
8-02
8-03
5-13
Over-torque Setting
Applications
Purpose
To protect
machines and to
have continuous/
reliable operation
Functions
The over-torque detection level can be
set. Once OC stall, OV stall and overtorque occurs, the output frequency
will be adjusted automatically. It is
suitable for machines like fans and
pumps that require continuous
operation.
Related
Parameters
6-03~6-05
Purpose
Control the motor
speed within
upper/lower limit
Functions
When user cannot provide
upper/lower limit, gain or bias from
external signal, it can be set
individually in AC motor drive.
Related
Parameters
1-07
1-08
Purpose
To prevent
machine vibrations
Functions
The AC motor drive cannot run at
constant speed in the skip frequency
range. Three skip frequency ranges
can be set.
Related
Parameters
8-08~8-13
Purpose
Low noise
Functions
The carrier frequency can be
increased when required to reduce
motor noise.
Related
Parameters
2-03
Air conditioners
5-14
Purpose
For continuous
operation
Functions
When the frequency command is lost
by system malfunction, the AC motor
drive can still run. Suitable for
intelligent air conditioners.
Related
Parameters
2-05
General application
Purpose
Functions
Related
Parameters
3-05~3-06
General application
Purpose
Functions
Related
Parameters
3-05~3-06
Purpose
Functions
Related
Parameters
3-05~3-06
Over-torque Detection
Applications
Pumps, fans and
extruders
Purpose
To protect
machines and to
have continuous/
reliable operation
Functions
Related
Parameters
3-05~3-06
6-04
6-05
Functions
Related
Parameters
Purpose
3-05~3-06
5-15
General application
Purpose
Functions
Related
Parameters
3-05~3-06
3-04
3-10
Purpose
Functions
Related
Parameters
3-05~3-06
Purpose
For safety
Functions
When heat sink is overheated, it will
send a signal for external system or
control wiring.
Related
Parameters
3-05~3-06
General application
5-16
Purpose
Display running
status
Functions
The value of frequency, output
current/voltage can be read by
connecting a frequency meter or
voltage/current meter.
Related
Parameters
3-05
0-00
0-01
Settings
Read Only
Settings
Read Only
Factory setting: d#
Pr. 0-00 displays the identity code of the AC motor drive. The capacity, rated current, rated
voltage and the max. carrier frequency relate to the identity code. Users can use the following
table to check how the rated current, rated voltage and max. carrier frequency of the AC
motor drive correspond to the identity code.
Pr. 0-01 displays the rated current of the AC motor drive. By reading this parameter the user
can check if the AC motor drive is correct.
115V/230V Series
KW
0.2
0.4
0.75
HP
0.25
0.5
1.0
Pr.0-00
d0
d2
d4
Rated Output Current (A)
1.6
2.5
4.2
Max. Carrier Frequency
10kHz
460V Series
KW
0.4
0.75
1.5
HP
0.5
1.0
2.0
Pr.0-00
d3
d5
d7
Rated Output Current (A)
1.5
2.5
4.2
Max. Carrier Frequency
10kHz
0-02
1.5
2.0
d6
7.5
2.2
3.0
d8
11.0
2.2
3.0
d9
5.5
Parameter Reset
Factory Setting: d0
Settings d9
d10
This setting allows the user to return all parameters to the factory default settings.
0-03
d1
d2
d3
5-17
d4
0-04
d2
d3
d4
d5
d6
0-05
Unit: 0. 1
d0.1 to d160
The coefficient K determines the multiplying factor for the user-defined unit.
The display value is calculated as follows:
Display value = (output frequency x K)
The display window is only capable of showing three digits, yet you could use Pr.0-05 to
create larger numbers. The display windows uses decimal points to signify numbers up to five
digits as illustrated in the following:
Display
99.9
A signal decimal point between the middle and the right-most numbers is a true
decimal point; it separates ones and tenths as in 30.5 (thirty and one-half).
999.
A single decimal point after the right-most numbers is not a true decimal point,
instead it indicates that a zero follows the right-most number. For example, the
number 1230 would be displayed as 123.
99.9.
Two decimal points (one between the middle and the right-most numbers, and
one after the right-most number) are not true decimal points; instead they indicate
that two zeros follow the right-most number. For example, the number 34500
would be displayed as 34.5..
0-06
5-18
Number Represented
999
Software Version
Settings
Read Only
Display
d #.#
Revision August 2006, SE08, SW V2.61
0-07
Password Input
Settings
Unit: 1
d0 to d999
Factory Setting: d0
Pr.0-07 and Pr.0-08 work together to provide data security for the AC drive. When Pr.0-08 is
set to a value other than 0, a password must be entered to alter the values of parameters.
The password is the number set in Pr.0-08, which ranges from 1 to 999. Pr.0-07 is where the
password is entered to allow parameter values to be altered.
Display states:
d0: no password / correct password has been input
d1: parameters are locked
0-08
Password Set
Unit: 1
Settings
d0 to d999
Display
Factory Setting: d0
5-19
0-07
0-08
Displays 0 when
entering correct
password into
Pr.0-07.
Correct Password
END
Incorrect Password
END
0-08
0-07
Displays 0 when
entering correct
password into
Pr.0-07.
0-09
Unit: 1
d0 to d63
Factory Setting: d8
This parameter is determined to save frequency, operation direction and parameter setting
after power off or not.
Setting method: input to this parameter after converting binary 6-bit to decimal. Refer to
following two tables for detail.
Bit 0 Reserved
0: save frequency
Bit 1
1: not save frequency
Bit 2 Reserved
0: save direction
Bit 3
1: not save direction
0: save parameters (except Pr.0-09 and Pr.0-02)
Bit 4
1: not save parameters
0: save Pr.0-09
Bit 5
1: not save Pr. 0-09
5-20
bit 5
bit4
Bit 3
0
0
1
0
0
1
1
0
0
1
1
0
1
1
bit 1
0
1
0
1
0
1
0
1
0
2
8 (factory setting)
10
16
18
24
26
0
1
0
1
0
1
0
1
32
34
40
42
48
50
56
58
When Pr. 0-09 is set to b5=0, Pr. 0-09 setting will be saved after power on again.
When Pr. 0-02 is set to d10, all parameters (includes Pr.0-09) will be set to factory setting.
5-21
Unit: 0.1
d50.0 to d400 Hz
This parameter determines the AC motor drives Maximum Output Frequency. All the AC
motor drive frequency command sources (analog inputs 0 to +10V and 4 to 20mA) are scaled
to correspond to the output frequency range.
1-01
Unit: 0.1
d10.0 to d400 Hz
This value should be set according to the rated frequency of the motor as indicated on the
motor nameplate. Maximum Voltage Frequency determines the v/f curve ratio. For example, if
the drive is rated for 460 VAC output and the Maximum Voltage Frequency is set to 60Hz, the
drive will maintain a constant ratio of 7.66 V/Hz (460V/60Hz=7.66V/Hz). This parameter value
must be equal to or greater than the Mid-Point Frequency (Pr.1-03).
1-02
d4.0 to d510V
Unit: 0.1
Factory Setting: 220.0
Factory Setting: 440.0
This parameter determines the Maximum Output Voltage of the AC motor drive. The
Maximum Output Voltage setting must be smaller than or equal to the rated voltage of the
motor as indicated on the motor nameplate. This parameter value must be equal to or greater
than the Mid-Point Voltage (Pr.1-04).
1-03
Unit: 0.1
This parameter sets the Mid-Point Frequency of the V/f curve. With this setting, the V/f ratio
between Minimum Frequency and Mid-Point frequency can be determined. This parameter
must be equal to or greater than Minimum Output Frequency (Pr.1-05) and equal to or less
than Maximum Voltage Frequency (Pr.1-01).
1-04
Unit: 0.1
5-22
d4.0 to d510V
This parameter sets the Mid-Point Voltage of any V/f curve. With this setting, the V/f ratio
between Minimum Frequency and Mid-Point Frequency can be determined. This parameter
must be equal to or greater than Minimum Output Voltage (Pr.1-06) and equal to or less than
Maximum Output Voltage (Pr.1-02).
1-05
Unit: 0.1
d1.0 to d60.0Hz
This parameter sets the Minimum Output Frequency of the AC drive. This parameter must be
equal to or less than Mid-Point Frequency (Pr.1-03).
1-06
Unit: 0.1
460V series
d4.0 to d510V
This parameter sets Minimum Output Voltage of the AC drive. This parameter must be equal
to or less than Mid-Point Voltage (Pr.1-04).
Voltage
Pr.1-02
Pr.1-04
Pr.1-06
0
Freq.
Pr.1-03
Pr.1-05
Pr.1-00
Pr.1-01
1-07
d1 to d110%
Unit: 1
Factory Setting: d100
This parameter must be equal to or greater than the Output Frequency Lower Limit (Pr.1-08).
The Maximum Output Frequency (Pr.1-00) is regarded as 100%.
Output Frequency Upper Limit value = (Pr.1-00 * Pr.1-07)/100.
1-08
Unit: 1
d0 to d100%
Factory Setting: d0
5-23
If the Upper Limit of Output Frequency is 50Hz and the Maximum Output Frequency is 60Hz,
the Maximum Output Frequency will be limited to 50Hz.
If the Lower Limit of Output Frequency is 10Hz, and the Minimum Output Frequency (Pr.1-05)
is set at 1.0Hz, then any Command Frequency between 1-10Hz will generate a 10Hz output
from the drive.
This parameter must be equal to or less than the Upper Limit of Output Frequency (Pr.1-07).
1-09
1-10
Unit: 0.1
1-11
Unit: 0.1
1-12
Unit: 0.1
Settings
Unit: 0.1
d0.1 to d600Sec
Pr.1-9- This parameter is used to determine the time required for the AC drive to ramp from 0
Hz to its Maximum Output Frequency (Pr.1-00). The rate is linear unless S-Curve is
Enabled.
Pr.1-10. This parameter is used to determine the time required for the AC drive to decelerate
from the Maximum Output Frequency (Pr.1-00) down to 0 Hz. The rate is linear unless SCurve is Enabled.
The acceleration/deceleration time 2 determines the time for the AC drive to
acceleration/deceleration from 0Hz to Maximum Output Frequency (Pr.1-00)
(acceleration/deceleration time 1 is the default). A Multi-Function Input terminal must be
programmed to select acceleration/deceleration time 2 and the terminals must be closed to
select acceleration/deceleration time 2. See Pr.4-04 to Pr.4-8In the diagram shown below, the acceleration/deceleration time of the AC drive is the time
between 0 Hz to Maximum Output Frequency (Pr.1-00). Suppose the Maximum Output
Frequency is 60 Hz, start-up frequency (Pr.1-05) is 1.0 Hz, and acceleration/deceleration time
is 10 seconds. The actual time for the AC drive to accelerate from start-up to 60 Hz is 9.83
seconds and the deceleration time is also 9.83 seconds.
1-13
1-14
Jog Frequency
Settings
5-24
d0.1 to d600Sec
d1.0 to d400Hz
Unit: 0.1Sec
Factory Setting: d10.0
Unit: 0.1Hz
Factory Setting: d6.0
Revision August 2006, SE08, SW V2.61
The JOG function can be selected using Multi-function Input terminals (Pr.4-04 to Pr.4-08) if
programmed for Jog (d10). When the Jog terminal is closed, the AC drive will accelerate
from Minimum Output Frequency (Pr.1-05) to Jog Frequency (Pr.1-14). When the Jog
terminal open, the AC drive will decelerate from Jog Frequency to zero. The
acceleration/deceleration time is decided by the Jog acceleration/deceleration time (Pr.1-13).
During operation, the AC drive cannot perform Jog command. And during Jog operation,
other operation commands cannot be accepted, except command of FORWARD, REVERSE
and STOP keys on the digital keypad.
Frequency
Max.
Output
freq.
Pr.1-00
Jog
Freq.
Pr.1-14
Time
Pr. 1-13
Pr. 1-13
Acceleration Time
Deceleration Time
Jog operation
command
1-15
ON
OFF
Auto-Acceleration / Deceleration
Factory Setting: d0
Settings
d0
Linear Accel/Decel
d1
d2
d3
d4
d5
5-25
1-16
1-17
Acceleration S-Curve
Deceleration S-Curve
Settings
d0 to d7
Factory Setting: d0
These two parameters allow you to configure whether the acceleration and/or deceleration
ramps are linear or S-shaped. The S-curve is enabled when set at d1-d7. Setting d1 offers
the quickest S-curve and d7 offers the longest and smoothest S-curve. The AC drive will not
follow the acceleration/deceleration time in Pr.1-09 to Pr.1-12. To Disable the S-curve, set
Pr.1-16 and Pr.1-17 to d0.
From the diagram shown below, the original setting acceleration/deceleration time will be for
reference when the function of the S-curve is enabled. The actual acceleration/deceleration
time will be determined based on the S-curve selected (d1 to d7).
2
1
3
1
3
1 2
Disable S curve
3 4
Enable S curve
Acceleration/deceleration Characteristics
1-18
d0.0 to d600
Unit: 0.1Sec
Factory Setting: d0.0
When Pr.1-18 is set to d0.0 Jog decelerating time determined by the setting of Pr.1-13 0.1 to
600 sec, Jog decelerating time can be set independently, separates from Pr.1-13.
When Pr.1-18 is set to 0.0, Pr.1-13 determines both Jog acceleration and deceleration time.
When Pr.1-18 is set between 0.1 to 600 seconds, which will determine Jog Decelerating Time
and Pr.1-13 will only determine Jog Accelerating Time.
5-26
d0
d1
d2
d3
d4
d5
When setting analog overlap plus, it needs to set Pr. 2-06 to select AVI or ACI.
5-27
2-01
d0
d1
d2
d3
d4
When the AC drive is controlled by an external source, please refer to parameter group 4 for
detailed explanations on related parameter settings.
2-02
Stop Method
Factory Setting: d0
Settings
d0
d1
The parameter determines how the motor is stopped when the AC motor drive receives a
valid stop command or detects External Fault.
Ramp:
Coast:
the AC motor drive stops the output instantly upon command, and the motor
free runs until it comes to a complete standstill.
The motor stop method is usually determined by the characteristics of the motor load and
how frequently it is stopped.
(1)
(2)
5-28
Frequency
output
frequency
Frequency
output
frequency
motor
speed
motor
speed
Time
operation
command
stops according to
decel eration time
STOP
RUN
Time
free run to stop
operation
command
RUN
STOP
2-03
Unit: 1
Power
Setting Range
Factory Setting
This parameter determines the PWM carrier frequency of the AC motor drive.
Carrier
Frequency
Acoustic
Noise
3kHz
Significant
10kHz
Minimal
Electromagnetic
Noise or leakage
current
Minimal
Significant
Heat
Dissipation
Current
Wave
Minimal
Minimal
Significant
Significant
From the table, we see that the PWM carrier frequency has a significant influence on the
electromagnetic noise, AC motor drive heat dissipation, and motor acoustic noise.
2-04
d0
d1
The parameter determines whether the AC drive can operate in the reverse direction.
5-29
2-05
d0
Decelerate to 0 Hz
d1
d2
d0
Disable
d1
d2
This parameter is used to determinate that the analog signal to overlap is 0~10V (AVI) or
4~20mA (ACI).
To make sure the short PIN of J1 on the panel is correct position before setting this parameter.
5-30
d0
d1
This parameter sets the function of the AFM output 0~+10VDC (ACM is common).
The voltage output type for this analog signal is PWM. It needs to read value by the movable
coil meter and is not suitable for A/D signal conversion.
3-01
Unit: 1
d1 to d200%
The parameter sets the voltage range of the analog output signal at terminals AFM, that
corresponds with either the output frequency or the output current of the VFD.
AFM
GND
AFM
GND
The analog output voltage is directly proportional to the output frequency of the AC drive. With
the factory setting of 100%, the Maximum Output Frequency (Pr.1-00) of the AC drive
corresponds to +10VDC analog voltage output. (The actual voltage is about +10VDC, and
can be adjusted by Pr.3-01).
The analog output voltage is directly proportional to the output current of the AC drive. With
the factory setting of 100%, the 2.5 times rated current of the AC drive corresponds to
+10VDC analog voltage output. (The actual voltage is about +10VDC, and can be adjusted by
Pr. 3-01)
NOTE
Voltmeter specification: The sourcing capability of the output is limited to 0.21mA. Sourcing voltage:
10V. Output resistance: 47k.
If the meter reads full scale at a voltage less than 10 volts, then Pr.3-01 should be set by
the following formula: Pr.3-01 = ((meter full scale voltage)/10) 100%
For example: When using the meter with full scale of 5 volts, adjust Pr.3-01 to 50%.
5-31
3-02
Unit: 0.1
d1.0 to d400 Hz
Freq.
Max. Output Detection range
Freq.
+
- 2Hz
Desired Freq.
Pr.3-02
Preset Freq.
Attained
indication
Pr.3-05 to 3-06
Desired Freq.
Attained
Indication
Pr.3-05 to 3-06
Detection range
+
- 4Hz
Detection
range
-2Hz
Time
OFF
OFF
ON
OFF
ON
OFF
Unit: 1
d0 to d999
Factory Setting: d0
The parameter determines the upper limit value of the internal counter. The internal counter
can be triggered by the external terminal (Pr.4-4 to Pr.4-8, d19). Upon completion of counting,
the specified output terminal will be activated. (Pr.3-05, Pr.3-06, d14).
3-04
d0 to d999
Unit: 1
Factory Setting: d0
When the counter value is counted up from 1 to the setting value of this parameter, the
corresponding multi-function output terminal which set to d15 as Preliminary Counter Value
Attained will be closed. The application can be that closing the multi-function output terminal
makes the AC drive operate at low speed until stop before the counting value is going to be
attained.
The timing diagram is shown below:
5-32
Display
(Pr.0-04=d1)
2ms
TRG
Counter Trigger Signal
Multi-function Input Terminal
2ms
The width of trigger signal
should not be less than
2ms(<250 Hz)
3-05
3-06
Factory Setting: d1
Factory Setting: d8
Settings d0 to d18
Setting
Function
d0
No Function
d1
AC Drive Operational
Description
d2
d3
Zero Speed
d4
d5
Base-Block (B.B.) Indication the output will be activated when the output of the AC
d6
Low-Voltage Indication
d7
Fault Indication
d9
Desired Frequency Attained the output will be activated when the desired frequency
(Pr.3-02)is attained.
5-33
Setting
d10
Function
PLC Program Running
Description
the output will be activated when the PLC program is
running.
d11
d12
the output will be activated for 0.5 sec. when each multi-
Completed
the output will be activated for 0.5 sec. when the PLC
program cycle has completed.
d13
d14
d15
Attained
Preliminary Counter Value
Attained
d16
d17
d18
5-34
4-01
d0.0 to d100.0%
Unit: 0. 1
Factory Setting: d0.0
4-02
Positive Bias
d1
Negative Bias
4-03
d0
d1 to d200%
Unit: 1
Factory Setting: d100
d0
d1
Pr.4-00 to Pr.4-03 are used when the source of frequency command is the analog signal (0 to
+10V DC or 4 to 20 mA DC). Refer to the following examples.
Example 1:
The following is the most common method. Set parameter 2-00 to d1 (0 to +10V signal) or d2 (4 to
20mA current signal).
Example 2:
In this example with the potentiometer set to 0V the Output Frequency is 10 Hz. The mid-point of
the potentiometer becomes 40 Hz. Once the Maximum Output Frequency is reached any further
increase of the potentiometer will not increase output frequency.
5-35
Example 3:
The example also shows the popular method. The whole scale of the potentiometer can be used as
desired. In addition to signals of 0 to 10V and4 to 20mA, the popular voltage signals also include
signals of 0 to 5V, 20 to 4mA or that under 10V. Regarding the setting, please refer to the following
examples.
Example 4:
This example shows a potentiometer range of 0 to 5 Volts.
Example 5:
In this example a 1 volt negative bias is used. In a noise environment, it is advantageous to use
negative bias to provide a noise margin (1V in this example).
5-36
Example 6:
In this example, a negative bias is used to provide a noise margin. Also a potentiometer frequency
gain is used to allow the Maximum Output Frequency to be reached.
Max.
Output Pr.1-00
Freq.
60Hz
Gain adjustment
27
Factory Settings
Pr.1-00=60Hz--Max. output Freq.
Pr.4-00=10%--Potentiometer bias freq.
Pr.4-01=1 -- Bias polarity
Pr.4-02=111% -- Pot. freq. gain
Pr.4-03=0 -- Forward motion only
Calculation of gain
Pr.4-02=( 10V )X100%=111%
9V
0Hz
Negative
0V 1V
bias 6Hz
10V
It's 0Hz0
within
this
range.
Hz
54
10V
0V
Potentiometer Scale
Example 7:
In this example, the potentiometer is programmed to run a motor is both forward and reverse
direction. A motor will be idle when the potentiometer position is at mid-point of its scale. Using
Pr.4-03 will disable the external FWD and REV controls.
Max.
Output Pr.1-00
Freq.
60Hz
FWD
30Hz
0Hz
0V
5V
30Hz
REV
0
Factory Settings
Pr.1-00=60Hz--Max. output Freq.
Pr.4-00=30Hz--Potentiometer bias freq.
10V Pr.4-01=1 -- bias polarity
Pr.4-02=200% -- pot. freq. gain
Pr.4-03=1 -- pot. REV motion enable
60Hz
FWD.
REV.
60
0V
Hz
60
10V
Potentiometer Scale
Example 8:
In this example, the option of anti-slope is shown. Anti-slope is used in an application where control
of pressure, temperature, or flow is needed. Under a high pressure or flow situation, a sensor will
generate a large signal such as 20 mA or 10V. With anti-slope enable, the large signal will slow or
stop the AC drive.
5-37
Max.
Output Pr.1-00
Freq.
60Hz
30
Factory Settings
anti-slope
0Hz
0V
4mA
4-04
60
0V
4mA
Hz
0
10V
20mA
Potentiometer Scale
10V
20mA
d0 to d29
4-05
4-06
4-07
4-08
Factory Setting: d1
Factory Setting: d6
Factory Setting: d7
Factory Setting: d8
Factory Setting: d9
Parameters & Functions table:
Value
Function
d0 No Function
d1
d2
Value
Function
d15 Up: Increment master frequency
d4
d5
d6
External Reset
d7
d8
d9
d3
d10
d11
d12
d13
d14
5-38
Jog operation
Acceleration/Deceleration Speed
Inhibit
First or Second Acceleration or
Deceleration Time Selection
External Base Block (N.O.)
(Normally Open Contact Input)
External Base Block (N.C.)
(Normally Close Contact Input)
d21
Explanations:
d0 Parameter Disable:
Enter value (d0) to disable any Multi-Function Input Terminal: M1 (Pr.4-04), M2 (Pr.4-05), M3 (Pr.406), M4 (Pr.4-07) or M5 (Pr.4-08).
NOTE
The purpose of this function is to provide isolation for unused Multi-Function Input Terminals. Any
unused terminals should be programmed to d0 to insure they have no effect on drive operation.
d1 Two wire operation: Restricted to Pr.4-04 and external terminals M0, M1.
FWD/STOP
M0 "Open": Stop, "Close": FWD Run
REV/STOP
M1 "Open": Stop, "Close":REV Run
GND
d2 Two wire operation: Restrict to Pr. 4-04 and external terminals M0, M1.
RUN/STOP
M1 "Open": FWD, "Close":REV
REV/FWD
GND
NOTE
Multi-function Input Terminal M0 does not have its own parameter designation. M0 must be used in
conjunction with M1 to operate two and three wire control.
d3 Three Wire Control: Restricted to Pr.4-04 control terminals M0, M1, M2.
STOP
RUN
M0 Run command, Runs when "close"
M2 Stop command, stops when "Open"
M1 REV/FWD Run selection
5-39
NOTE
When value d3 is selected for Pr. 4-04, this will over ride any value entered in Pr.4-05, since Pr.4-05
must be used for three wire control as shown above.
d4, d5 External Faults:
Parameter values d4, d5 programs Multi-Function Input Terminals: M1 (Pr. 4-04), M2 (Pr. 4-05), M3
(Pr. 4-06), M4 (Pr. 4-07) or M5 (Pr. 4-08) to be External Fault (E.F.) inputs.
E.F.(N.O.)
Mx "Close": Operation available.
setting by d4
E.F(N.C.)
Mx "Open":Operation available.
setting by d5
GND
NOTE
When an External Fault input signal is received, the AC drive will stop all output and display E.F.
on Digital Keypad, the motor will free run. Normal operation can resume after the External Fault is
cleared and the AC drive is reset.
d6 External Reset:
Parameter value d6 programs a Multi-Function Input Terminal: M1 (Pr.4-04), M2 (Pr.4-05), M3 (Pr.406), M4 (Pr.4-07) or M5 (Pr.4-08) to be an External Reset.
RESET
Mx "Close": Operation available
setting by d6
GND
NOTE
the External Reset has the same function as the Reset key on the Digital keypad. After external fault
such as O.H., O.C. and O.V. are clear, this input can be used to reset the drive.
d7, d8, d9 Multi-Step Speed Command:
Parameter values d7, d8, d9 programs any three of the following Multi-Function Input Terminals: M1
(Pr.4-04), M2 (Pr.4-05), M3 (Pr.4-06), M4 (Pr.4-07) or M5 (Pr.4-08) for multi-step speed command
function.
5-40
D7 Multi-step 1
Mx "Close": Operation available
D8 Multi-step 2
D9 Multi-step 3
GND
These three inputs select the multi-step speeds defined by Pr.5-00 to Pr.5-06 as shown in the
following diagram. Pr.5-07 to Pr.5-16 can also control output speed by programming the AC drives
internal PLC function.
Freq. Pr.5-00
Pr.5-04
Step 1
Step 5
Pr.5-05
Pr.5-01
Step 6
Pr.5-03
Step 2
Step 4
Pr.5-02
Pr.5-06
Step 3
Step 7
Time
Master Freq.
Mx1-GND
ON
Mx2-GND
ON
ON
ON ON
ON
ON ON
ON ON ON ON
Mx3-GND
Operation
Command
ON
OFF
NOTE
Jog operation programmed by d10 can only be initiated while the motor is stopped. (Refer to Pr.1-13,
Pr.1-14.)
d11 Acceleration/Deceleration Speed Inhibit:
Parameter value d11 programs Multi-Function Input Terminal: M1 (Pr.4-04), M2 (Pr.4-05), M3 (Pr.406), M4 (Pr.4-07) or M5 (Pr.4-08) for Acceleration/deceleration Inhibit. When the command is
received, acceleration and deceleration is stopped and the AC drive maintains a constant speed.
Revision August 2006, SE08, SW V2.61
5-41
Master Frequency
Deceleration
inhibit
Acceleration
inhibit
Acceleration
inhibit
Deceleration
inhibit
Mx-GND
ON
Operation
command
ON
ON
OFF
ON
Mx set d12
GND
Frequency
Master
Pr.
Frequency 1-09
Pr.
1-10
Pr.
1-11
Pr.
Pr.
1-12 1-09
Pr.
1-12
2nd
Deceleration
1st
Acceleration/
Deceleration
Mx-GND
operation
command
2nd
Acceleration/
Deceleration
1st
Acceleration
Time
ON
ON
ON
ON
ON
OFF
5-42
B.B.(N.O.)
Mx "Close": Operation available.
setting by d13
B.B.(N.C.)
Mx "Open":Operation available.
setting by d14
GND
NOTE
When a Base-Block signal is received, the AC drive will stop all output and the motor will free run.
When base block control is deactivated, the AC drive will start its speed search function and
synchronize with the motor speed, and then accelerate to Master Frequency.
External
base-block
signal
Pr.8-04=d1
Speed search starts with the
reference value
Output
frequency
Output
voltage
Speed synchronization
detection
Pr.8-06
Min. base-block time
Speed search operation
UP
setting by d15
DOWN
setting by d16
5-43
PLC operation
Mx "Close": Run PLC.
setting by d17
Mx "Close":Pause PLC.
setting by d18
GND
NOTE
Pr.5-00 to Pr.5-16 define the PLC program.
d19 Counter Trigger:
Parameter value d19 programs Multi-Function Input Terminal: M1 (Pr.4-04), M2 (Pr.4-05), M3 (Pr.406), M4 (Pr.4-07) or M5 (Pr.4-08) to increase the AC drives internal counter. When an input is
received, the counter is increased by 1.
Trigger
GND
NOTE
The Counter Trigger input can be connected to an external Pulse Signal Generator to count a
processing step or unit of material. See the diagram below.
5-44
Reset counter
Mx "close": reset counter.
d20 reset the counter
value.
GND
and
will be disabled.
and
will be disabled.
5-45
M1 No Function
GND
4-09
d0
Disable
d1
Enable
When enabled, the AC drive will not start when powered up with run commands applied. To
start in Line Start Lockout mode, the AC drive must see the run command go from stop to run
after power up. When Line Start Lockout is disable (also known as Auto-Start), the drive will
start when powered-up with run commands applied.
4-10
Up/Down Mode
Factory Setting: d0
Settings
4-11
d0
d1
d2
d3
Constant speed
Unit: 5
d0 to d1000 Hz/sec
Factory Setting: d1
This parameter is used to set the acceleration/deceleration speed mode when multi-function
terminal is set to up/down frequency. (Pr. 4-04 ~ Pr.4-08, function d15, d16)
5-46
Unit: 0.01
5-01
Unit: 0.01
5-02
Unit: 0.01
5-03
Unit: 0.01
5-04
Unit: 0.01
5-05
Unit: 0.01
5-06
d0.0 to d400 Hz
Unit: 0.01
Factory Setting: 0.00
The Multi-Function Input Terminals (refer to Pr.4-04 to 4-08) are used to select one of the AC
drive Multi-Step speeds. The speeds (frequencies) are determined by Pr.5-00 to 5-06 shown
above.
5-07
PLC Mode
Factory Setting: d0
Settings
d0
d1
d2
d3
d4
d5
Disable PLC operation, but can set direction of 1st speed to 7th
speed
This parameter selects the mode of PLC operation for the AC drive. The PLC program can
be used in lieu of any External Controls, Relays or Switches. The AC drive will change
speeds and directions according to the users desired programming.
When this parameter is set to d5 and it is running by external multi-speed, the high priority of
the operation direction is Pr. 5-08.
Example 1 (Pr.5-07 = d1): Execute one cycle of the PLC program. Its relative parameter settings
are:
1.
Pr.5-00 to 5-06: 1st to 7th step speed (sets the frequency of each step speed).
2.
Pr.4-04 to 4-08: Multi-Function Input Terminals (set one multi-function terminal as d17- PLC
auto-operation).
3.
Pr.3-05 to 3-06: Multi-Function Output Terminals (set a Multi-Function Terminal as d10-PLC
operation indication, d11-one cycle in PLC auto mode or d12-PLC operation fulfillment
attainment).
4.
Pr.5-07: PLC mode.
5.
Pr.5-08: Direction of operation for Master Frequency and1st to 7th step speed.
6.
Pr.5-09 to 5-16: operation time setting of Master Frequency and1st to 7th step speed.
Revision August 2006, SE08, SW V2.61
5-47
Pr.5-03
60Hz
Pr.5-04
50Hz
Pr.5-02
40Hz
Pr.5-05
30Hz
Pr.5-01
20Hz
15Hz
Master 10Hz
Freq.
5Hz
0Hz
5-09=10 Sec
5-10=10 Sec
5-11=12 Sec
5-12=15 Sec
5-13=15 Sec
5-14=8 Sec
5-15=17 Sec
5-16=17 Sec
Pr.5-06
Pr.5-00
Time
(Sec)
5-09
5-10
5-12
5-11
5-14
5-13
5-16
5-15
Program operation
command
Program operation
output indication
Program step
complete
Program operation
completed
NOTE
The above diagram shows one complete PLC cycle. To restart the cycle, turn the PLC program off
and then back on.
60Hz
5-04
50Hz
5-02
40Hz
30Hz
5-01
20Hz
15Hz
10Hz
5Hz
0Hz
Program step
complete
5-09
Master freq.=5Hz
5-00=10 Hz 4-07=d17
5-01=20 Hz 3-05=d11
5-02=40 Hz 3-06=d12
5-03=60 Hz 5-07=d2
5-04=50 Hz 5-08=d0
5-05=30 Hz
5-06=15 Hz
5-05
5-09=10 Sec
5-10=10 Sec
5-11=12 Sec
5-12=15 Sec
5-13=15 Sec
5-14=8 Sec
5-15=17 Sec
5-16=17 Sec
5-00
5-06
5-00
Time
(Sec)
5-10
5-11
5-12
5-13
5-14
5-15
5-16
5-09
5-10
Program operation
completed
5-48
Master freq.=5Hz
5-00=10 Hz 4-07=d17
5-01=20 Hz 3-05=d11
5-02=40 Hz 3-06=d12
5-04 5-03=60 Hz 5-07=d3
5-04=50 Hz 5-08=d0
5-05=30 Hz
5-06=15 Hz
5-03
60Hz
50Hz
40Hz
5-09=10 Sec
5-10=10 Sec
5-11=12 Sec
5-12 =15 Sec
5-13=15 Sec
5-14=8 Sec
5-15=17 Sec
5-16=17 Sec
5-05
30Hz
20Hz
5-06
15Hz
10Hz
5Hz
0Hz
5-13
5-09
Program step
complete
t
5-14
5-15
5-16
Time
(Sec)
Program operation
completed
Example 4 (Pr. 5-07 =d4) Continuously execute PLC cycles step by step:
In this explanation, the PLC program runs continuously step by step. Also shown are examples of
steps in the Reverse direction.
Frequency
Master freq.=5Hz
5-00=10 Hz 4-07=d17
5-01=20 Hz 3-05=d10
5-02=40 Hz 3-06=d11
5-03=60 Hz 5-07=d4
5-04=50 Hz 5-08=d68
5-05=30 Hz
5-06=15 Hz
60Hz
50Hz
40Hz
5-09=10 Sec
5-10=10 Sec
5-11=12 Sec
5-12 =15 Sec
5-13=15 Sec
5-14=8 Sec
5-15=17 Sec
5-16=17 Sec
FWD
15Hz
10Hz
Time
(Sec)
0Hz
5-09 t
REV
20Hz
30Hz
5-49
60Hz
50Hz
40Hz
5-09=10 Sec
5-10=10 Sec
5-11=12 Sec
5-12 =15 Sec
5-13=15 Sec
5-14=8 Sec
5-15=17 Sec
5-16=17 Sec
FWD
15Hz
10Hz
Time
(Sec)
0Hz
5-09
REV
20Hz
30Hz
* The calculation of time for Pr.5-11, Pr.5-12, Pr.5-15 and Pr.5-16 should be carefully planned.
5-08
Unit: 1
d0 to d255
Factory Setting: d0
This parameter controls the direction of motion for the Multi-Step Speed Pr.5-00 to Pr.5-06
and the Master Frequency. The original direction of Master Frequency will become invalid.
NOTE
The equivalent 8-bit number is used to program the forward/reverse motion for each of the 8 speed
steps (including Master Frequency). The binary notation for the 8-bit number must be translated into
decimal notation and then be entered.
0=Forward
1=Reverse
Weights
Bit
0
Director of Master Frequency during PLC
Direction of 1st speed for Pr.5-00
Direction of 2nd speed for Pr.5-01
Direction of 3rd speed for Pr.5-02
Direction of 4th speed for Pr.5-03
Direction of 5th speed for Pr.5-04
Direction of 6th speed for Pr.5-05
Direction of 7 th speed for Pr.5-06
5-50
Weights
Bit
Direction 0
0=Forward
1=Reverse
WD
Direction of 1st speed for Pr.5-00 =FWD
Direction of 2nd speed for Pr.5-01 =REV
Direction of 3rd speed for Pr.5-02 = FWD
Direction of 4th speed for Pr.5-03 = F WD
Direction of 5 th speed for Pr.5-04 = FWD
Direction of 6 th speed for Pr.5-05 = REV
Direction of 7th speed for Pr.5-06 = FWD
7
The setting value = bit7 x 2 +bit6 x 2 +bit5 x 2 +bit4 x 2 +bit3 x 23+bit2 x 22+bit1 x 21+bit0 x 20
= 0 x 27+1 x 26+0 x 25+0 x 24+0 x 23+1 x 22+0 x 21+0 x 20
= 0+64+0+0+0+4+0+0
= 68
Setting Pr.5-08 as d68.
5-09
Unit: 1
5-10
Unit: 1
5-11
Unit: 1
5-12
Unit: 1
5-13
Unit: 1
5-14
Unit: 1
5-15
Unit: 1
5-16
d0 to d65500
Unit: 1
Factory Setting: d0
NOTE
If a parameter is set to d0 (0 Sec), the corresponding step will be skipped. This is commonly used
to reduce number of program steps.
5-51
Unit: 0.1
Factory Setting: d1
Settings d0
Disable
d1
Enable
During deceleration, the motor DC bus voltage may exceed its Maximum Allowable Value due
to motor regeneration. When this function is enabled, the AC drive will stop decelerating.
Maintaining a constant output frequency when it happens. The AC drive will only resume
deceleration when the voltage drops below preset value.
NOTE
With a moderate inertial load, the over-voltage during deceleration wont happen, and the drive will
stop in programmed time. The AC drive will automatically extend the deceleration time with high
inertial loads. If deceleration time is critical for the application, then dynamic braking resistors should
be used.
6-01
Unit: 1
During deceleration, the DC bus voltage may exceed its maximum allowable value due to
motor regeneration. When this function is enabled, the AC drive will stop decelerating.
Maintaining a constant output frequency when it happens. The AC drive will resume
deceleration when the voltage drops below preset value.
With a moderate inertial load, the over-voltage during deceleration wont happen, and the
drive will stop in programmed time. The AC drive will automatically extend the deceleration
time with high inertial loads. If deceleration time is critical for the application, then dynamic
braking resistors should be used.
5-52
DC bus voltage
Over-voltage
detection
level Pr.6-01
Band=20V
time
Output
Freq.
time
Over-voltage Stall Prevention
6-02
Unit: 1
d20 to d150%
Output current
Over-current
detection
level
Pr.6-02
ON Band=5%
OFF
time
Output
frequency
time
Over-current Stall Prevention Level
5-53
6-03
6-04
d0
d1
d2
d3
d4
Unit: 1
d30 to d200%
6-05
Unit: 0.1
If a Multi-Function Output Terminal is set as Over-Torque Detection Indication and the output
current exceeds the Over-Torque Detection Level (Pr.6-04, Factory Setting: 150%), the OverTorque Detection Time (Pr.6-05, Factory setting: 0.1) and the setting of multi-function terminal
is Over-Torque Detection Indication, the contact will be close.
6-06
Operation disabled
6-07
d30 to d600Sec
Unit: 1
Factory Setting: d60
The parameter determines the time required activating the I2t electronic thermal protection
function. The graph below shows I2t curves for 150% output power for 1 minute.
5-54
5
60Hz or more
4
50Hz
3
10Hz
5Hz
20 40 60
6-08
6-09
6-10
Load
factor (%)
Factory Setting: d0
Readings
d0
No fault
d1
Over-current (oc)
d2
Over-voltage (ov)
d3
Overheat (oH)
d4
Overload (oL)
d5
Overload1 (oL1)
d6
d7
Reserved
d8
Reserved
d9
d10
d11
d12
d13
Reserved
d14
d15
d16
d17
d18
Overload (oL2)
d19
5-55
d20
d21
Reserved
d22
d23
d24
d25
d26
d27
d28
d29
d30
d31
d32
d33
Reserved
d34
d35
Reserved
d36
d37
Reserved
d38
Pr.6-08 to 6-10 store records of the three most recent faults that had occurred. Use the reset
key to reset the drive when the fault no longer exits.
5-56
d30 to d120%
Unit: 1
Factory Setting: d85
This parameter will limit the AC drive output current in order to prevent the motor from
overheating.
7-01
d0 to d90%
Unit: 1
Factory Setting: d50
The rated current of the AC drive is regarded as 100%. Motor setting of no-load current will
effect the slip compensation. The setting value must be less than motor rated current setting
Pr.7-00
7-02
Torque Compensation
Settings
d0 to d10
Unit: 0.1
Factory Setting: d1
This parameter may be set so that the AC drive will increase its voltage output during start-up
to obtain a higher initial starting torque.
7-03
Slip Compensation
Settings
d0.0 to d10.0
Unit: 0.01
Factory Setting: d0.0
While driving an asynchronous motor, load on the AC drive will increase, causing an increase
in slip. This parameter may be used to compensate the nominal slip within a range of 0 to 10.
When the output current of the AC drive is greater than the motor no-load current (Pr.7-01),
the AC drive will adjust its output frequency according to this parameter.
5-57
Unit: 1
d0 to d30%
Factory Setting: d0
This parameter determines the level of DC Braking Voltage Level output to the motor during
start-up and stopping. When setting DC Braking Voltage, the Maximum Output Voltage (Pr.102) is regarded as 100%. It is recommended to start with a low DC Braking Voltage Level and
then increase until proper holding torque has been attained.
8-01
Unit: 0.1
This parameter determines the duration of time that the DC Braking Current will be applied to
the motor during the AC drive start-up.
8-02
Unit: 0.1
This parameter determines the duration of time that the DC braking voltage will be applied to
the motor during stopping. If stopping with DC Braking is desired, then Pr.2-02 must be set to
RAMP stop (d0).
8-03
Unit: 0.1
d0.0 to d400Hz
This parameter determines the frequency when DC Braking will begin during deceleration.
Output Frequency
Start-Point for
DC Braking
Time during
Stopping
01-05
Minimum Output
Frequency
Operation
Command
08-03
Time
08-01
ON
OFF
08-02
DC Braking Voltage %
5-58
DC Braking during Start-up is used for loads that may move before AC drive starts, such as
fans and pumps. These loads may also be moving in the wrong direction. Under such
circumstances, DC Braking can be executed to hold the load in position before applying a
forward motion.
DC Braking during stopping is used to decrease stopping time and also to hold a stopped
load in position. For high inertial loads, a dynamic braking resistor may be needed for quick
decelerations.
8-04
8-05
d0
d1
d2
d0.3 to d5.0Sec
Unit: 0.1
Factory Setting: d2.0
During a power loss, if the power loss time is less than the time defined by this parameter, the
AC drive will resume operation. If the Maximum Allowable Power Loss Time is exceeded, the
AC drive output is then turned off.
8-06
d0.3 to d5.0Sec
Unit: 0.1
Factory Setting: d0.5
When a momentary power loss is detected, the AC drive turns off for a specified time interval
determined by Pr.8-06 before resuming operation. This time interval is called Base-Block.
This parameter should be set to a value where the residual output voltage is nearly zero,
before the drive resumes operation.
This parameter also determines the searching time when performing external Base-Block and
fault reset.
8-07
d30 to d200
Unit: 1
Factory Setting: d150
5-59
Following a power failure, the AC drive will start its speed search operation, only if the output
current is greater than the value determined by Pr.8-07. When the output current is less than
that of Pr.8-07, the AC drive output frequency is at a speed synchronization point. The drive
will start to accelerate or decelerate back to the operating frequency at which it was running
prior to the power failure.
Power
Input
Maximum Allowable
Power Loss Time
08-05
Speed Search
08-04=d1
Output
Frequency
Speed
Synchronization
Detection
08-05
Output
Voltage
08-06
Baseblock Time
Maximum
Allowable Power
08-04=d2
Speed search starts with
Min. Output Frequency
08-06
Baseblock Time
8-08
Unit: 0.1
8-09
Unit: 0.1
8-10
Unit: 0.1
8-11
Unit: 0.1
8-12
Unit: 0.1
8-13
Unit: 0.1
Settings
d0.0 to d400Hz
These parameters determine Skip frequency. It will cause the AC drive to skip operation at
these frequency ranges with continuous frequency output.
Pr.8-9, Pr.8-11, Pr.8-13 are for Lower Bound setting, and the settings should follow as Pr.8-9
Pr.8-11Pr.8-13.
8-14
d0 to d10
Unit: 1
Factory Setting: d0
After fault occurs (allowable faults: over-current OC, over-voltage OV), the AC drive can be
reset/restarted automatically up to 10 times. Setting this parameter to 0 will disable the
reset/restart operation after any fault has occurred. When enabled, the AC drive will restart
with speed search, which starts at the Master Frequency.
5-60
8-15
d0
d1
d2
AVR function automatically regulates the AC drive output voltage to the Maximum Output
Voltage (Pr.1-02). For instance, if Pr.1-02 is set at 200 VAC and the input voltage is at 200V
to 264VAC, then the Maximum Output Voltage will automatically be reduced to a maximum of
200 VAC.
Without AVR function, the Maximum Output Voltage may vary between 180V to 264VAC, due
to the input voltage varying between 180V to 264 VAC.
Selecting program value d2 enables the AVR function and also disables the AVR function
during deceleration. This offers a quicker deceleration.
8-16
Unit: 1
During deceleration, the DC-bus voltage will increase due to motor regeneration. When DC
bus voltage level exceeds the Software Braking Level, the DC brake output pins (B1, B2) will
be activated.
8-17
d0.0 to d400 Hz
Unit: 0.1
Factory Setting: d0.0
The setting frequency is lower than Pr.8-17, the DC Braking will not be activated when stops.
5-61
Communication Address
Settings
d1 to d254
Factory Setting: d1
Computer
d1
S1
9-01
d3
d2
S1
S1
Transmission Speed
Factory Setting: d1
Settings
d0
d1
d2
d3
Users can set parameters and control the operation of the AC drive via the RS-485 serial
interface of a personal computer. This parameter is used to set the transmission speed
between the computer and AC drive.
9-02
5-62
d0
d1
d2
d3
9-03
Time-out Detection
Factory Setting: d0
Settings
d0
Disable
d1
1 sec
d2
2 sec
:
d20
20 sec
If this function is enabled, the timer will start counting once the first valid Modbus
communication signal is received after power-up or reset. The timer will reset to 0 after each
valid Modbus communication message is received. If the watchdog timer reaches the value
set in Pr. 9-03, the drive will stop its output and display the message "CE10" on the digital
keypad. This fault can reset by an external terminal, keypad or a Modbus communication
reset command.
9-04
Communication Protocol
Factory Setting: d0
Settings
d0
d1
d2
d3
d4
d5
d6
d7
d8
1. Computer Control
1: +EV
2: GND
3: SG4: SG+
6
There is a built-in RS-485 serial interface, marked (RJ-11 Jack) on the control terminal
block, for VFD-S Series. The pins are defined above. Each VFD-S AC drive has a preassigned communication address specified by Pr. 9-00. The computer then controls
each AC drive according to its communication address.
VFD-S can be setup to communicate on Modbus networks using one of the following
modes: ASCII (American Standard Code for Information Interchange) or RTU (Remote
5-63
Terminal Unit). Users can select the desired mode along with the serial port
communication protocol in Pr. 9-04.
Code Description:
ASCII mode:
Each 8-bit data is the combination of two ASCII characters. For example, a 1-byte data:
64 Hex, shown as 64 in ASCII, consists of 6 (36Hex) and 4 (34Hex).
Character
0
1
2
3
4
5
6
ASCII code
30H
31H
32H
33H
34H
35H
36H
Character
ASCII code
8
38H
9
39H
A
41H
B
42H
C
43H
D
44H
E
45H
7
37H
F
46H
RTU mode:
Each 8-bit data is the combination of two 4-bit hexadecimal characters. For example, 64
Hex.
2. Data Format
2.1 10-bit character frame (For 7-bit character):
( 7.N.2)
Start
bit
Stop
bit
Stop
bit
7-bit character
10-bit character frame
( 7.E.1)
Start
bit
Even Stop
parity bit
7-bit character
10-bit character frame
( 7.O.1)
Start
bit
Odd
Stop
parity bit
7-bit character
10-bit character frame
2.2 11-bit character frame (For 8-bit character):
5-64
( 8.N.2 )
Start
bit
Stop Stop
bit
bit
Even Stop
parity bit
8-bit character
11-bit character frame
( 8.E.1 )
Start
bit
8-bit character
11-bit character frame
( 8.O.1 )
Start
bit
Odd
Stop
parity bit
8-bit character
11-bit character frame
3. Communication Protocol
3.1 Communication Data Frame:
ASCII mode:
STX
ADR 1
ADR 0
CMD1
CMD0
DATA (n-1)
.
DATA 0
LRC CHK 1
LRC CHK 0
END1
END0
RTU mode:
START
ADR
CMD
DATA (n-1)
.
DATA 0
CRC CHK
Low
CRC CHK
High
END
Contents of data:
n x 8-bit data, n<= 25
5-65
Number of data
(count by word)
LRC CHK 1
LRC CHK 0
END 1
END 0
5-66
Response message:
:
0
1
0
3
2
1
0
2
0
0
0
2
D
7
CR
LF
STX
ADR 1
ADR 0
CMD 1
CMD 0
Number of data
(Count by byte)
Content of starting
address
2102H
Content of address
2103H
LRC CHK 1
LRC CHK 0
END 1
END 0
:
0
1
0
3
0
4
1
7
7
0
0
0
0
0
7
1
CR
LF
RTU mode:
Command message:
ADR
CMD
Starting data
address
Number of data
(count by word)
CRC CHK Low
CRC CHK High
01H
03H
21H
02H
00H
02H
6FH
F7H
Response message:
ADR
CMD
Number of data
(count by byte)
Content of address
2102H
Content of address
2103H
CRC CHK Low
CRC CHK High
01H
03H
04H
17H
70H
00H
00H
FEH
5CH
Response message:
STX
:
ADR 1
0
ADR 0
1
CMD 1
0
CMD 0
6
0
1
Data address
0
0
1
7
Data content
7
0
LRC CHK 1
7
LRC CHK 0
1
END 1
CR
END 0
LF
RTU mode:
Command message:
ADR
CMD
Data address
Data content
CRC CHK Low
CRC CHK High
Response message:
01H
06H
01H
00H
17H
70H
86H
22H
ADR
CMD
Data address
Data content
CRC CHK Low
CRC CHK High
01H
06H
01H
00H
17H
70H
86H
22H
5-67
ASCII Mode:
Command message:
STX
ADR 1
ADR 0
CMD1
CMD0
Starting Data address
Number of data
(count by word)
Number of data
(count by byte)
Data content of
address 0500H
Data content of
address 0501H
LRC CHK 1
LRC CHK 0
END1
END0
Response message:
:
0
1
1
0
0
5
0
0
0
0
0
2
0
STX
ADR 1
ADR 0
CMD1
CMD0
Starting Data
address
LRC CHK 0
END1
END0
8
CR
LF
Number of data
(count by word)
4
1
7
7
0
0
3
E
8
7
2
CR
LF
RTU mode:
Command message:
ADR
LRC CHK 1
:
0
1
1
0
0
5
0
0
0
0
0
2
E
Response message:
01H
ADR
01H
CMD
10H
CMD
10H
05H
00H
00H
02H
04H
05H
00H
00H
02H
41H
04H
Number of data
(count by word)
Number of data
(count by Byte)
Data content of address 0500H
Data content of address 0501H
CRC CHK Low
CRC CHK High
17H
70H
03H
E8H
C8H
2EH
ASCII mode:
LRC (Longitudinal Redundancy Check) is calculated by summing up, module 256, the values of
the bytes from ADR1 to last data character then calculating the hexadecimal
representation of the 2s-complement negation of the sum.
For example, reading 1 word from address 0401H of the AC drive with address 01H
STX
ADR 1
ADR 0
CMD1
CMD0
Starting data address
:
0
1
0
3
0
4
0
1
0
0
0
1
F
6
CR
LF
Number of data
LRC CHK 1
LRC CHK 0
END1
END0
01H
CMD
03H
Starting address
21H
02H
00H
02H
6FH
F7H
Number of data
(count by word)
CRC CHK Low
CRC CHK High
5-69
Step 5: Repeat step 3 and 4 until eight shifts have been performed. When this is done, a
complete 8-bit byte will have been processed.
Step 6: Repeat step 2 to 5 for the next 8-bit byte of the command message. Continue doing this
until all bytes have been processed. The final contents of the CRC register are the
CRC value. When transmitting the CRC value in the message, the upper and lower
bytes of the CRC value must be swapped, i.e. the lower order byte will be transmitted
first.
The following is an example of CRC generation using C language. The function takes two
arguments:
Unsigned char* data
5-70
Address
ggnnH
Functions
gg means parameter group, nn means parameter number, for
example, the address of Pr 4-01 is 0401H. Referencing to
chapter 5 for the function of each parameter. When reading
parameter by command code 03H, only one parameter can be
read at one time.
Content
Command
Address
2000H
Bit 0-1
Bit 2-3
Bit 4-5
2001H
2002H
Status
monitor
Read only
2100H
Bit 6-15
Freq. command
Bit 0
Bit 1
Bit 2-15
Functions
00: No function
01: Stop
10: Run
11: Jog + Run
Not used
00: No function
01: FWD
10: REV
11: Change direction
Not used
1: EF (external fault) on
1: Reset
Not used
Error code:
0: No errors occurred
1: Over-current (oc)
2: Over-voltage (ov)
3: Overheat (oH)
5: Overload1 (oL1)
6: External fault (EF)
7: Not used
8: Not used
9: Current exceeds 2 times rated current during acceleration
(ocA)
10: Current exceeds 2 times rated current during deceleration
(ocd)
11: Current exceeds 2 times rated current during steady state
operation (ocn)
12: Ground Fault (GF)
13: Reserved
14: Low voltage (Lv)
15: CPU failure 1 (cF1)
16: CPU failure 2 (cF2)
17: Base block
18: Overload (oL2)
19: Auto acceleration/deceleration failure (cFA)
20: Software protection enable (codE)
21: Reserved
22: CPU failure (cF3.1)
23: CPU failure (cF3.2)
24: CPU failure (cF3.3)
25: CPU failure (cF3.4)
26: CPU failure (cF3.5)
27: CPU failure (cF3.6)
28: CPU failure (cF3.7)
29: Hardware protection failure (HPF.1)
30: Hardware protection failure (HPF.2)
31: Hardware protection failure (HPF.3)
32: CE 10
33: Reserved
34: Software error (SErr)
5-71
Content
Address
2101H
Functions
35: Reserved
36: PID error (Pld)
37: Reserved
38: Phase loss (PHL)
Status of AC Drive
Bit 0-1
Bit 2
Bit 3-4
2102H
2103H
2104H
2105H
2106H
2107H
2108H
2109H
210AH
Bit 5-7
Bit 8
Bit 9
Bit 10
Bit 11
1: Parameters have been locked
Bit 12-15 Not Used
Frequency command F (XXX.XX)
Output Frequency H (XXX.XX)
Output Current A (XXX.XX)
DC-BUS Voltage U (XXX.XX)
Output Voltage E (XXX.XX)
Step number of Multi-Step Speed Operation
Step number of PLC operation
Time of PLC Operation
Counter Value
5-72
Example of an exception response of command code 06H and exception code 02H:
ASCII mode:
STX
ADR 1
ADR 0
CMD1
CMD0
Exception code
LRC CHK 1
LRC CHK 0
END1
END0
RTU mode:
ADR
CMD
Exception code
CRC CHK Low
CRC CHK High
:
0
1
8
6
0
2
7
7
CR
LF
01H
86H
02H
C3H
A1H
Meaning
eserved
AC drive busy:
The time interval between commands is too short. Please keep an
interval of 10ms at least after the return of a command. If no command
returned, please keep a 10ms interval at least for the same reason.
Reserved
Reserved
Check Sum Error: Check if the Check Sum is correct.
Watchdog Timer: The timer will reset to 0 after each valid Modbus
communication message is received.
Frame Error: Check if the Baud rate complies with the data format.
The command message is too short.
Command message length is out of range.
The command messages include the data that does not belong to 0 to
9, A to F except starting and end character (only for Modbus ASCII
mode).
5-73
/* interrupt enable */
/* interrupt as data in */
outportb(PORT+LCR,(inportb(PORT+LCR) | 0x80));
/* the BRDL/BRDH can be access as LCR.b7==1 */
outportb(PORT+BRDL,12);
outportb(PORT+BRDH,0x00);
outportb(PORT+LCR,0x06);
i=0;
while(!kbhit()){
if(inportb(PORT+LSR) & 0x01){ /* b0==1, read data ready */
rdat[i++]=inportb(PORT+RDR); /* read data form RDR */
}
5-74
}
Revision August 2006, SE08, SW V2.61
d0
Disable
d1
d2
d3
d4
Select an input terminal to serve as the PID feedback location. Please verify the feedback
location is different from the Frequency Set Point location and J1 for selecting ACI or AVI
must be in the correct position. (Refer to Pr. 2-00 for detail)
Negative feedback = Positive target value detection value.
Positive feedback = Negative target value + detection value.
A-01
To adjust feedback detective gain value. It is used to adjust target value error.
A-02
Unit: 1
Factory Setting: d100
This parameter is used to determinate error gain. If I = 0 and D = 0, doing proportional gain
operation.
A-03
Unit: 1
d0 to d999
d0
Disable
When this parameter is defined to gain is 1 and error value is fixed, integral value is equal to
error value as the setting of integral time is attained.
A-04
d0 to d100
d0
Unit: 1
Factory Setting: d0
Disable
5-75
When this parameter is set to gain =1, PID output is Derivative time. At this time, error value
error value of the preceding item= additional respond speed and it is easy to have over
compensation situation.
A-05
Unit: 1
d0 to d100%
This parameter determines the Upper Bound for Integral Control while operating in the PID
feedback loop. (Limit = 1-00A-05 %). During a fast Integration response, it is possible for
the frequency to spike beyond a reasonable point. This parameter will limit this frequency
spike.
A-06
Unit: 2 msec
d0 to d999
Factory Setting: d0
Primary Delay Filter Time will slow down oscillation of the system.
A setting of d0 disables this function.
A-07
d0 to d110%
Unit: 1
Factory Setting: d100
This parameter determines the limit of the PID output frequency. If this parameter is set to
110%, then the maximum output frequency while in the PID operation will be (110% x Pr.0100) 66Hz.
A-08
Unit: 0.1
Factory Setting: d0.0
This parameter defines the detection time for the loss of a feedback analog signal. The drive
will follow the operating procedure programmed in Pr.A-09 if the feedback signal is lost for
more than the time set in Pr. A-08.
A setting of 0.0 disables this function.
A-09
5-76
d0
d1
This parameter selects the operation of the drive upon a loss of PID feedback signal.
A-10
Sleep Frequency
Settings
A-11
Wakeup Frequency
Settings
A-12
Unit: 0.1
d0.0 to d400Hz
Unit: 0.1
d0.0 to d400Hz
Sleep Period
Settings
Unit: 0.1
These parameters determine sleep functions of the AC drive. If the command frequency falls
below the sleep frequency, for the specified time in Pr. A-12, then the drive will shut off the
output and wait until the command frequency rises above Pr. A-11. Please see the below
diagram.
Actual running
output frequency
Frequency Command
A-11
Wakeup Frequency
A-10
Sleep Frequency
Sleep Period
0Hz
A-12
Sleep Function
A-13
d0.0 to d400
Unit: 0.1
Factory Setting: d0.0
When parameter A-13 is set to 0, what F and H display is the actual value of setting
frequency and output frequency. When this parameter is not set to 0, the display value of F
and H = actual value A-13/1-00. To set frequency with panel, communication, VR, AVI or
ACI need to set according to the display value. For example, when 1-00=60.0Hz, if A-13 is set
to 30.0 Hz, it means when the actual value of frequency is 30.00 Hz, the display value will be
15.0 Hz . If you want to let drive run at 10.0Hz, the frequency command must be 5.0 Hz. But
5-77
the setting frequency of parameters, such as Max. operation frequency, 1st speed and etc.,
they are still needed to set with actual value.
Target
Value
P
A-02
A-03
Integration's
Upper
Bound
Frequency
A-05
+ +
+
PID Frequency
Output
Command
Limit
A-07
One-Time
Delay
A-06
Frequency
Command
A-04
Detection
Value
Gain
A-01
Output Value
A-00
If the input range of sensor is 0~SI_max, output range is SO_min~SO_max and then
SI_max
Input
Per output
is SO_max-SO_min , set drive input to sensor output
Set input range of drive is D_range= 10V(0~10V) or 16mA (4~20mA) that correspond to 0~1-00Hz
and then
Output
Per input
1-00
will be D_range
Display value of F, H
Actual value
According to the display value of F and H = actual value A-13/1-00, and then
=A-13/1-00. If you want the result to be display value = sensor output and actual value = drive output,
SI_max
A-01
X
100
A-13 SO_max-SO_min
=
1-00
1-00
D_range
and then
A-13 =
SI_max
A-01
X
X D_range
SO_max-SO_min
100
Example:
Sensor: 0~6 psi input corresponds to 0~5V output drive AVI: 0~10V input corresponds to 0~60Hz, A01=100
100
A-13 = 6 X
X 10 = 12
5-0 100
5-78
NOTE
Wait 5 seconds after a fault has been cleared before performing reset via keypad of input terminal.
Fault Descriptions
Corrective Actions
1.
2.
3.
Over current
Abnormal increase in current.
4.
5.
6.
7.
1.
Over voltage
The DC bus voltage has
exceeded its maximum
allowable value.
2.
3.
4.
6-1
Fault
Name
Fault Descriptions
Overheating
Heat sink temperature too high
Low voltage
The AC motor drive detects
that the DC bus voltage has
fallen below its minimum
value.
Overload
The AC motor drive detects
excessive drive output current.
NOTE: The AC motor drive
can withstand up to 150% of
the rated current for a
maximum of 60 seconds.
Overload 1
Internal electronic overload trip
Overload 2
Motor overload.
GFF hardware error
CC (current clamp)
OC hardware error
Corrective Actions
1. Ensure that the ambient temperature falls within
the specified temperature range.
2. Make sure that the ventilation holes are not
obstructed.
3. Remove any foreign objects from the heatsinks
and check for possible dirty heat sink fins.
4. Check the fan and clean it.
5. Provide enough spacing for adequate
ventilation. (See chapter 2)
1. Check whether the input voltage falls within the
AC motor drive rated input voltage range.
2. Check for abnormal load in motor.
3. Check for correct wiring of input power to R-S-T
(for 3-phase models) without phase loss.
1.
2.
3.
1.
2.
3.
4.
Over-current during
acceleration
3.
4.
1.
Over-current during
deceleration
6-2
2.
3.
Fault
Name
Fault Descriptions
Corrective Actions
1.
Over-current during
constant speed operation
2.
3.
1.
External Fault
2.
Internal EEPROM can not be
programmed.
Internal EEPROM can not be
programmed.
Drives internal circuitry
abnormal.
OH error
OV error
LV error
Current detection error
Ground fault
6-3
Fault
Name
Fault Descriptions
Corrective Actions
1.
Communication Error
6.2 Reset
There are three methods to reset the AC motor drive after solving the fault:
STOP/RESET
1.
Press
2.
Set external terminal to RESET (set one of Pr.4-04~Pr.4-08 to 06) and then set to be
key on keypad.
ON.
3.
NOTE
Make sure that RUN command or signal is OFF before executing RESET to prevent damage or
personal injury due to immediate operation.
6-4
Chapter 7 Troubleshooting
ocd
OC
Over-current
during acceleration
Over-current
during deceleration
Over current
Yes
No Reduce torque
compensation
No
No
Yes
Check if load is too large
No
No
No
No Suitable torque
compensation
Yes
Yes
Reduce torque
compensation
No
Check if
Check if
acceleration time No deceleration time
is too short by
is too short by
load inertia.
load inertia.
Yes
Yes
Yes
No
Reduce load or increase
the power of AC motor
drive
Increase accel/decel
time
Check braking
method. Please
contact DELTA
7-1
GFF
Ground fault
No
Yes
Remove ground fault
No
Reduce voltage to
be within spec.
Is voltage within
specification
Yes
Yes
No
No
Yes
Increase
deceleration
time
No
Yes
Increase
acceleration
time
Yes
Yes
No
Reduce moment
of inertia
No
No
Use braking unit or DC braking
No
Yes
Need to check control method. Please contact DELTA.
7-2
No
Check if there is any malfunction Yes
component or disconnection in
power supply circuit
No
No
Check if voltage is
within specification
Yes
Check if there is heavy load
with high start current in the
same power system
Yes
No
No
Check if Lv occurs when
breaker and magnetic
contactor is ON
No
Yes
Suitable power
transformer capacity
Yes
No
Yes
Control circuit has malfunction or
misoperation due to noise. Please
contact DELTA.
7-3
No
Yes
Is load too large
Yes
Reduce load
No
If cooling fan functions normally
No
Yes
Check if cooling fan is jammed
Yes
Remove obstruction
No
Check if surrounding temperature
is within specification
No
Yes
Adjust surrounding temperature
to specification
7.6 Overload
OL
OL1/ OL2
No
Modify setting
Yes
Is load too large
No
Yes
Reduce load or increase the power of AC motor drive
7-4
No
No
Display normal?
Yes
AC motor drive works normally
No
Correct wiring
Yes
Check if the screws of terminals are tightened
No
Yes
Check if the input voltage of R, S, T is unbalanced
Yes
No
7-5
Check if non-fuse
No
breaker and magnetic
contactor are ON
No
Yes
Yes
Input "RUN"
command
by keypad
Yes
No
If jumper or DC
No
reactor is connected
between +1 and +2/B1
Use jumper
or DC reactor
Yes
Yes
No
Check if input
voltage is normal
No
It can run when
no faults occur
Set them to ON
Press UP key to
set frequency
Yes
Yes
Check if motor
connection
is correct
No
Connect correctly
7-6
Yes
Yes
No
If the setting of
Pr.05-17toPr.05-31
Yes is too high
No
Yes
If finished with
executing
Pr.05-15
No
Yes
Is it in PLC mode
No
No
Yes
If the setting of
Pr.05-00 to Pr.05-14
are the same
No
No
No
Correct
wiring
Check if frequency for
each step is different
No
Yes
Change defective
potentiometer
Yes
Change frequencysetting
No Check if accel./decel.
time is set correctly
Yes
Please set suitable
accel./decel. time by
load inertia
7-7
No
Yes
Check if the inertia
Yes
of the motor and load
is too high
No
Thicken or shorten the
wiring between the
motor or AC motor drive
Yes
Reduce load or
increase the capacity
of AC motor drive
Yes
No
Increase torque compensation
No
Yes
Run in low speed continuously
Yes
No
Is load too large
Yes
No
Check if output voltage of U, V, W Yes
is balanced
No
Maybe AC motor drive has malfunction or misoperation
due to noise. Please contact DELTA.
7-8
Add surge suppressor on the relays and contacts to suppress switching surges.
2.
Shorten the wiring length of the control circuit or serial communication and keep them
separated from the power circuit wiring.
3.
Comply with the wiring regulations by using shielded wires and isolation amplifiers for
long wire length.
4.
The grounding terminal should comply with the local regulations and be grounded
independently, i.e. not to have common ground with electric welding machines and other
power equipment.
5.
Connect a noise filter at the mains input terminal of the AC motor drive to filter noise from
the power circuit. VFD-S can have a built-in filter as option.
To prevent vibration, the use of anti-vibration dampers is the last choice. Vibrations must
be within the specification. Vibration causes mechanical stress and it should not occur
frequently, continuously or repeatedly to prevent damaging to the AC motor drive.
2.
Store the AC motor drive in a clean and dry location, free from corrosive fumes/dust to
prevent corroded contacts. It also may cause short by low insulation in a humid location.
The solution is to use both paint and dust-proof. For particular occasion, use the
enclosure with whole-seal structure.
3.
The ambient temperature should be within the specification. Too high or too low
temperature will affect the lifetime and reliability. For semiconductor components, damage
will occur once any specification is out of range. Therefore, it is necessary to periodically
check air quality and the cooling fan and provide extra cooling of necessary. In addition,
the microcomputer may not work in extremely low temperatures, making cabinet heating
necessary.
7-9
4.
2.
Use a reactor or rectifier at the power input terminal of the AC motor drive or decrease
high harmonic by multiple circuit.
3.
If phase lead capacitors are used (never on the AC motor drive output!!), use serial
reactors to prevent capacitors damage from high harmonics.
serial reactor
Use a motor with independent ventilation (forced external cooling) or increase the motor
rated power.
7-10
2.
3.
Daily Inspection:
Basic check-up items to detect if there were any abnormalities during operation are:
1.
2.
3.
4.
5.
6.
Periodic Inspection:
Before the check-up, always turn off the AC input power and remove the cover. Wait at least 10
minutes after all display lamps have gone out, and then confirm that the capacitors have fully
discharged by measuring the voltage between
DANGER!
1. Disconnect AC power before processing!
2. Only qualified personnel shall install, wire and maintain AC motor drives. Please take off any metal
objects, such as watches and rings, before operation. And only insulated tools are allowed.
3. Never reassemble internal components or wiring.
4. Prevent electric shocks.
8-1
Periodical Maintenance
Ambient environment
Check Items
Maintenance
Period
Daily
Visual inspection
Half One
Year Year
Voltage
Maintenance
Period
Check Items
Half One
Year Year
Keypad
Maintenance
Period
Check Items
Visual inspection
Visual inspection
Half One
Year Year
Mechanical parts
Maintenance
Period
Check Items
8-2
Half One
Year Year
Maintenance
Period
Check Items
Visual inspection
Visual inspection
Visual inspection
Half One
Year Year
Main circuit
Maintenance
Period
Check Items
If machine or insulator is
deformed, cracked, damaged or
with changed color change due
to overheating or ageing
Visual inspection
NOTE: Please ignore the color
change of copper plate
Visual inspection
Half One
Year Year
Half One
Year Year
Visual inspection
Visual inspection
Visual inspection
8-3
Visual inspection
Static capacity
Half One
Year Year
Half One
Year Year
Half One
Year Year
8-4
Visual inspection
Half One
Year Year
Visual inspection
Visual inspection
Half One
Year Year
Change fan
Half One
Year Year
Half One
Year Year
Visual inspection
8-5
8-6
Appendix A Specifications
Output Rating
Voltage Class
Model Number VFD-XXXS
Max. Applicable Motor Output (kW)
Max. Applicable Motor Output (HP)
Rated Output Capacity (KVA)
Rated Output Current (A)
Maximum Output Voltage (V)
Rated Frequency (Hz)
Input Rating
Control
Characteristics
Rated Voltage/Frequency
Voltage/Freq. Tolerance
Control System
Output Frequency Resolution
Torque Characteristics
Overload Endurance
Accel/Decel Time
V/F Pattern
Stall Prevention Level
Keypad
Operating Characteristics
115V Class
230V Class
460V Class
002 004 007 002 004 007 015 022 004 007 015
0.2 0.4 0.75 0.2 0.4 0.75 1.5 2.2 0.4 0.75 1.5
0.25 0.5 1.0 0.25 0.5 1.0 2.0 3.0 0.5 1.0 2.0
0.6 1.0 1.6 0.6 1.0 1.6 2.9 4.2 1.2 2.0 3.3
1.6 2.5 4.2 1.6 2.5 4.2 7.5 11.0 1.5 2.5 4.2
3-phase
Proportional to
3-phase Proportional to Input Voltage
Twice the Input
Voltage
1.0 to 400 Hz
Single phase
Single/3-phase model drive
3-phase
4.9/ 6.5/ 9.7/ 15.7/ 24/
6
9
18
1.7 2.9 5.1
1.9 2.7 5.1 9.0
15
Frequency
Setting
Operation
Setting Signal
External
Signal
Keypad
-- --
1.6
3.0
5.1
8.4
--
022
2.2
3.0
4.4
5.5
6.9
-- --
External
Signal
Other Function
Enviroment
A-2
Installation Location
Pollution Degree
Altitude 1,000 m or below, keep from corrosive gasses, liquid and dust
2
Ambient Temperature
Storage Temperature
Ambient Humidity
Vibration
Appendix B Accessories
B.1 All Brake Resistors & Brake Units Used in AC Motor Drives
Note: Please only use DELTA resistors and recommended values. Other resistors and values will
void Deltas warranty. Please contact your nearest Delta representative for use of special resistors.
The brake unit should be at least 10 cm away from AC motor drive to avoid possible interference.
460V
Series
115V/230V
Series
Voltage
Refer to the Brake unit Module User Manual for further details.
Applicable
Motor
Resistor
Full Load
value spec
Torque
for each AC
Nm
Motor Drive
hp
kW
1/4
0.2
0.110
1/2
0.4
0.216
80W 200
0.75
0.427
80W 200
1.5
0.849
300W 100
2.2
1.262
1/2
0.4
0.216
0.75
1.5
2.2
80W 200
120
BR080W200 1
220
120
BR080W200 1
125
80
BR300W100 1
125
55
300W 70
BR300W70 1
125
35
80W 750
BR080W750 1
230
470
0.427
80W 750
BR080W750 1
125
260
0.849
300W 400
BR300W400 1
125
190
1.262
300W 250
BR300W250 1
125
145
BR080W200 1
NOTE
1.
Please select the brake unit and/or brake resistor according to the table.
2.
If damage to the drive or other equipment is due to the fact that the brake resistors and
the braking modules in use are not provided by Delta, the warranty will be void.
3.
Take into consideration the safety of the environment when installing the brake resistors.
4.
If the minimum resistance value is to be utilized, consult local dealers for the calculation of
the power in Watt.
5.
Please select thermal relay trip contact to prevent resistor over load. Use the contact to
switch power off to the AC motor drive!
6.
When using more than 2 brake units, equivalent resistor value of parallel brake unit cant
be less than the value in the column Minimum Equivalent Resistor Value for Each AC
Drive (the right-most column in the table).
7.
Please read the wiring information in the user manual of the brake unit thoroughly prior to
Model no.
BR080W200
L1
L2
140
125
20
5.3
60
160
215
200
30
5.3
60
750
265
250
30
5.3
60
930
BR080W750
BR300W70
BR300W100
BR300W250
BR300W400
BR400W150
BR400W040
B-2
EMI Filter
RF007S21AA
VFD015S21D/U, VFD022S21D/U
RF022S21BA
VFD004S43A/B, VFD007S43A/B
RF007S43AA
VFD002S11A/B, VFD004S11A/B
12DKT1W3S
08TDT1W4S
VFD007S11A/B
22DRT1W3S
Installation
All electrical equipment, including AC motor drives, will generate high-frequency/low-frequency noise
and will interfere with peripheral equipment by radiation or conduction when in operation. By using
an EMI filter with correct installation, much interference can be eliminated. It is recommended to use
DELTA EMI filter to have the best interference elimination performance.
We assure that it can comply with following rules when AC motor drive and EMI filter are installed
and wired according to user manual:
EN61000-6-4
EN61800-3: 1996 + A11: 2000
EN55011 (1991) Class A Group 1 (1st Environment, restricted distribution)
General precaution
1.
2.
EMI filter and AC motor drive should be installed on the same metal plate.
Please install AC motor drive on footprint EMI filter or install EMI filter as close as possible
to the AC motor drive.
3.
4.
5.
The cover of EMI filter and AC motor drive or grounding should be fixed on the metal plate
and the contact area should be as large as possible.
B-3
1.
2.
3.
Remove any paint on metal saddle for good ground contact with the plate and shielding.
Remove any paint on metal saddle for good ground contact with
the plate and shielding.
saddle
B-4
1000V
1300V
1600V
66 ft (20m)
328 ft (100m)
1312 ft (400m)
1312 ft (400m)
1312 ft (400m)
1312 ft (400m)
1000V
1300V
1600V
66 ft (20m)
165 ft (50m)
165 ft (50m)
328 ft (100m)
328 ft (100m)
328 ft (100m)
NOTE
When a thermal O/L relay protected by motor is used between AC motor drive and motor, it may
malfunction (especially for 460V series), even if the length of motor cable is only 165 ft (50m) or less.
To prevent it, please use AC reactor and/or lower the carrier frequency (Pr. 02-03 PWM carrier
frequency).
NOTE
Never connect phase lead capacitors or surge absorbers to the output terminals of the AC motor
drive.
B-5
If the length is too long, the stray capacitance between cables will increase and may
cause leakage current. It will activate the protection of over current, increase leakage
current or not insure the correction of current display. The worst case is that AC motor
drive may damage.
If more than one motor is connected to the AC motor drive, the total wiring length is the
sum of the wiring length from AC motor drive to each motor.
B.2.1 Dimensions
Dimensions are in millimeter and (inch)
Order P/N: RF007S21AA/ RF007S43AA
50
(1.97)
27
(1.06)
85
(3.35)
60
(2.36)
200
(7.87)
15
(0.52)
B-6
24
(0.94)
200 213
(7.87)(8.39)
4.5
(0.18)
50
(1.97)
27
(1.06)
100
(3.94)
74
(2.91)
228
(8.98)
15
(0.59)
24
(0.94)
228 241
(8.98) (9.49)
5.5
(0.22)
B-7
POWER-IN
B-8
POWER-IN
POWER-IN
B-9
B.3 AC Reactor
B.3.1 AC Input Reactor Recommended Value
230V, 50/60Hz, 1-Phase
kW
B-10
HP
Fundamental
Amps
Inductance (mH)
Max. continuous
Amps
3~5% impedance
6.5
0.2
1/4
0.4
1/2
7.5
0.75
12
1.5
1.5
12
18
1.25
2.2
18
27
0.8
kW
HP
Inductance (mH)
Fundamental
Amps
Max.
continuous
Amps
3% impedance
5% impedance
3
6
20
9
32
12
0.4
0.75
1/2
1
2
4
1.5
6.5
2.2
12
7.5
kW
HP
Fundamental
Amps
Max.
continuous
Amps
3% impedance
5% impedance
0.2
1/4
12
9
0.4
1/2
6.5
0.75
12
1.5
12
1.5
2.2
12
18
1.25
2.5
Fundamental
Amps
Max.
continuous
Amps
3% impedance
5% impedance
kW
HP
Inductance (mH)
0.4
1/2
20
32
0.75
12
1.5
6.5
2.2
12
7.5
Application 1
Question
B-11
B-12
Correct wiring
M1
reactor
AC motor drive
motor
AC motor drive
motor
AC motor drive
motor
M2
Mn
Application 2
Silicon rectifier and AC motor drive are
connected to the same power.
Question
Switching spikes will be generated when the
silicon rectifier switches on/off. These spikes
may damage the mains circuit.
Correct wiring
silicon rectifier
power
reactor
DC
AC motor drive
reactor
motor
B-13
Application 3
Used to improve the input power factor, to
reduce harmonics and provide protection from
AC line disturbances. (surges, switching
spikes, short interruptions, etc.). The AC line
reactor should be installed when the power
supply capacity is 500kVA or more and
exceeds 6 times the inverter capacity, or the
mains wiring distance 10m.
Question
When the mains power capacity is too large,
line impedance will be small and the charge
current will be too high. This may damage AC
motor drive due to higher rectifier
temperature.
Correct wiring
large-capacity
power
reactor
small-capacity
AC motor drive
motor
B-14
Input voltage
kW
HP
0.2
1/4
DC Amps
2
Inductance (mh)
20.00
MTE CAT. NO
2RB003
230Vac
0.4
1/2
15.00
4RB003
50/60Hz
0.75
7.50
9RB003
3-Phase
1.5
12
4.00
12RB003
2.2
18
2.75
18RB003
0.2
1/4
50.00
--
230Vac
0.4
1/2
25.00
--
50/60Hz
0.75
12.00
--
1-Phase
1.5
12
8.00
--
2.2
18
6.00
--
460V DC Choke
Input voltage
460Vac
50/60Hz
3-Phase
kW
HP
DC Amps
Inductance (mh)
0.4
1/2
50.00
2RB004
0.75
25.00
4RB004
1.5
11.50
9RB004
2.2
11.50
9RB004
MTE CAT. NO
B-15
Motor
460V
Series
115V/230VSeri
es
Qty.
HP
kW
1/4
0.2
1/2
0.4
0.75
1.5
2.2
1/4
1/2
1
2
3
0.2
0.4
0.75
1.5
2.2
0.5 - 5.5
1
3.5 - 5.5
0.5 - 5.5
Wiring Method
Please wind each wire 4 times around the core. The reactor must be put at inverter output as close
as possible.
Power
Supply
B-16
R/L1
U/T1
S/L2
V/T2
T/L3
W/T3
MOTOR
Models
VFD002S11A/B
VFD002S21A/B/E
VFD002S23A/B
VFD004S11A/B
VFD004S21A/B/E
VFD004S23A/B
VFD004S43A/B/E
VFD007S21A/B/E
VFD007S23A/B
VFD007S43A/B/E
VFD015S23D
Screw Size
M4*22
M4*22
M4*22
M4*12
M4*12
M4*12
M4*12
M4*12
M4*12
M4*12
M4*12
B-17
4 16 15 14 13 11
M1 M3
RC-01
Terminal
block
(Wiring
connections)
VFD-S
I/O
Block
VFD-S Programming
Pr. 2-00 and Pr. 2-01 set to d01
Pr. 4-04 set to d02 (M0, M1 set at RUN/STOP and FWD/REV)
Pr. 4-05 set to d06 (M2 set for reset)
Pr. 4-06 set to d10 (M3 set for jog operation)
B-18
15.5(0.61)
29.7(1.17)
25.2(1.0)
73.0(2.87)
22.0(0
.87)
)
1.1
.0(
67.8(2.67)
28
22.
0(0
.87
)
B-19
For 1-phase drives, the current rating of the breaker shall be 4 times maximum input
current rating.
2.
For 3-phase drives, the current rating of the breaker shall be 4 times maximum output
current rating.
3-phase
Recommended
Model
Recommended
Model
VFD002S11A/B
15
VFD002S23A
VFD002S21A/B/E
10
VFD004S23A
VFD004S11A/B
20
VFD004S43A/B/E
5
5
10
VFD004S21A/B/E
15
VFD007S23A
VFD007S11A/B
30
VFD007S43A/B/E
5
20
VFD007S21A/B/E
20
VFD015S23D
VFD015S21D/E
30
VFD015S43D/E/U
VFD022S21D/E/U
50
VFD022S23D
10
30
VFD022S43D/E/U
15
I (input)(A)
I (output)(A)
VFD002S11A/B
VFD002S21A/B/E
VFD002S23A
VFD004S11A/B
VFD004S21A/B/E
VFD004S23A
VFD004S43A/B/E
VFD007S11A/B
VFD007S21A/B/E
VFD007S23A
VFD007S43A/B/E
VFD015S21D/E
VFD015S23D
VFD015S43D/E/U
VFD022S21D/E/U
VFD022S23D
VFD022S43D/E/U
6
4,9
2.4
9
6.5
3.0
1.9
18
9.7
5.1
3.2
15.7
9.0
4.3
24
15
7.1
1.6
1.6
1.6
2.5
2.5
2.5
1.5
4.2
4.2
4.2
2.5
7.5
7.5
4.2
11.0
11.0
5.5
B-20
I (A)
15
10
5
20
15
5
5
30
20
10
5
30
20
10
50
30
15
Line Fuse
Bussmann P/N
JJN-15
JJN-10
JJN-6
JJN-20
JJN-15
JJN-6
JJN-5
JJN-30
JJN-20
JJN-10
JJN-5
JJN-30
JJN-20
JJN-10
JJN-50
JJN-30
JJN-15
Speed and
torque
characteristics
Time
ratings
Overload
capacity
Starting
torque
The starting capacity should be less than 1.5x rated capacity of AC motor drive
The starting capacity is
kN
GD 2 N
TL +
1.5 the _ capacity _ of _ AC _ motor _ drive ( kVA)
973 cos
375 t A
2.1 The starting capacity should be less than the rated capacity of the AC motor drive
Acceleration time 60 seconds
kN
cos
[n
ns
(ks 1) 1.5 the _ capacity _ of _ AC _ motor _ drive(kVA)
nT
kN
cos
[n
ns
(ks 1) the _ capacity _ of _ AC _ motor _ drive(kVA)
nT
2.2 The current should be less than the rated current of the AC motor drive(A)
Acceleration time 60 seconds
C-2
Error! Reference source not found. Error! Reference source not found.|VFD-S Series
k PM
cos
The motor capacity should be less than the capacity of AC motor drive
PM
cos
VM
IM
k
PC1
kS
nT
nS
TL
tA
: Motor speed
GD 2
C-3
A.
B.
When a special motor is used or more than one motor is driven in parallel with a single
AC Motor Drive, select the AC Motor Drive current 1.25x(Sum of the motor rated
currents).
C.
The starting and accel./decel. characteristics of a motor are limited by the rated current
and the overload protection of the AC Motor Drive. Compared to running the motor
D.O.L. (Direct On-Line), a lower starting torque output with AC Motor Drive can be
expected. If higher starting torque is required (such as for elevators, mixers, tooling
machines, etc.) use an AC Motor Drive of higher capacity or increase the capacities for
both the motor and the AC Motor Drive.
D.
When an error occurs on the drive, a protective circuit will be activated and the AC Motor
Drive output is turned off and the motor will coast to stop. For an emergency stop, an
external mechanical brake is needed to quickly stop the motor.
A.
The AC Motor Drive can be driven at an output frequency up to 400Hz (less for some
models). Setting errors may create a dangerous situation. For safety, the use of the
upper limit frequency function is strongly recommended.
B.
High DC braking operating voltages and long operation time (at low frequencies) may
cause overheating of the motor. In that case, forced external motor cooling is
recommended.
C.
Motor accel./decel. time is determined by motor rated torque, load torque, and load
inertia.
C-4
Error! Reference source not found. Error! Reference source not found.|VFD-S Series
D.
When using the AC Motor Drive to control a standard 3-phase induction motor, take the
following precautions:
A.
B.
The motor losses are greater than for an inverter duty motor.
Avoid running the motor at low speed for a long time. Under this condition, the motor
temperature may rise above the motor rating due to limited airflow produced by the
motors fan. Consider external forced motor cooling.
C.
When the standard motor operates at low speed for long time, the output load must be
decreased.
D.
Load duty-cycle
25%
40% 60%
100
torque(%)
82
70
60
50
continuous
3 6
20
Frequency (Hz)
60
C-5
E.
If 100% continuous torque is required at low speed, it may be necessary to use a special
inverter duty motor.
F.
Motor dynamic balance and rotor endurance should be considered if the operating speed
exceeds the rated speed (60Hz) of a standard motor.
G.
Motor torque characteristics vary when an AC Motor Drive instead of commercial power
supply drives the motor. Check the load torque characteristics of the machine to be
connected.
H.
Because of the high carrier frequency PWM control of the VFD series, pay attention to
the following motor vibration problems:
Resonant mechanical vibration: anti-vibration (damping) rubbers should be
used to mount equipment that runs at varying speed.
Motor imbalance: special care is required for operation at 50 or 60 Hz and
higher frequency.
To avoid resonances, use the Skip frequencies.
I.
The motor fan will be very noisy when the motor speed exceeds 50 or 60Hz.
Special motors:
A.
B.
Submersible motor:
The rated current is higher than that of a standard motor. Please check before operation
and choose the capacity of the AC motor drive carefully. With long motor cable between
AC motor drive and motor, available motor torque is reduced.
C.
C-6
Error! Reference source not found. Error! Reference source not found.|VFD-S Series
D.
E.
Synchronous motor:
The rated current and starting current are higher than for standard motors. Please check
before operation and choose the capacity of the AC motor drive carefully. When the AC
motor drive operates more than one motor, please pay attention to starting and changing
the motor.
Pay attention to reduced lubrication when operating gear reduction motors, gearboxes,
belts and chains, etc. over longer periods at low speeds. At high speeds of 50/60Hz and
above, lifetime reducing noises and vibrations may occur.
Motor torque
C-7
AC motor drive
Motor
180
60 seconds
155
140
100
80
55
38
03 20
03 20
50
120
Frequency (Hz)
Base freq.: 50Hz
V/F for 220V/50Hz
C-8
180
150
torque (%)
torque (%)
45
35
55
38
60
120
Frequency (Hz)
Base freq.: 60Hz
V/F for 220V/60Hz
60 seconds
100
85
68
100
0 3 20
60
120
Frequency (Hz)
Base freq.: 60Hz
V/F for 220V/60Hz
140
130
60 seconds
155
torque (%)
torque (%)
180
60 seconds
100
80
45
35
0 3 20 50
120
Frequency (Hz)
Base freq.: 50Hz
V/F for 220V/50Hz
Appendix D CE
D-2