Ceiling Diffusers
Ceiling Diffusers
Ceiling Diffusers
WE SHAPE
AIR
PRODUCT BULLETIN
PRODUCTS CATALOGUE
www.betag.com
index
MULTI PATTERN CEILING DIFFUSERS
1 TO 4
5 TO 7
PERFORMANCE DATA
8 TO 22
CEILING DIFFUSERS
MULTI PATTERN CEILING DIFFUSERS
A - 13
A + 146mm
38mm
46mm
30O
33mm
TYPE: 4RAD
A + 146mm
A-8
84mm
30O
33mm
TYPE: 4SAD
>> Flush mounted with different pattern arrangements. Availbale in both square and rectangular shapes.
>> Core is availbale in one way, two way, three way and four way discharge.
>> Core is fixed to the frame by the action of spring loaded pins, it is easily removable to allow for maximum flexibility
in installation, maintenance, damper adjustment and pattern exchange.
CEILING DIFFUSERS
MULTI PATTERN CEILING DIFFUSERS
>> Stainless steel clips are fixed at the frame corners to assure maximum tightness and rigidity for the diffuser
construction.
>> Insulating gasket is fixed on request around the back of the frame to prevent infiltration between the frame and
the ceiling
>> Available with easily removable opposed blade damper, attached to the frame by means of stainless steel (S)
shape clips to ensure tight attachment with maximum flexibility.
>> The ceiling diffuser may be used as a supply air diffuser or as a return air diffuser according to the application
designed for. Both types can be supplied with a damper to control the static pressure loss and the air volume flow
rate.
Available types of finishings:
Standard Sizes:
150 * 150
225 * 150
375 * 300
225 * 225
300 * I5O
450 * 300
300 * 300
375 * 150
525 * 300
375 * 375
450 * 150
600 * 300
450 * 450
525 * I5O
450 * 375
525 * 525
300 * 225
525 * 375
600 * 600
375 * 225
600 * 375
450 * 225
525 * 450
525 * 225
600 * 450
CEILING DIFFUSERS
MULTI PATTERN CEILING DIFFUSERS
SQUARE
RECTANGULAR
1-WAY
1-WAY
2-WAY
2-WAY
3-WAY
3-WAY
CEILING DIFFUSERS
MULTI PATTERN CEILING DIFFUSERS
PATTERN ARRANGEMENT
2 WAY
3 WAY
4 WAY
1 RAD AXA
2 RAD AXA
3 RAD AXA
A
4 RAD AXA
RECTANGULAR
SQAURE
1 WAY
1 RAD AXB
2 RAD AXB
3 RAD AXB
4 RAD AXB
ORDERING SYSTEM
TYPE
PATTERN
SIZE
FINISH
RAL: Powder coated finish as per RAIL codes.
Anodized: Anodized aluminium finish.
Example:
PERFORATED DIFFUSERS
KD-6
KD-6
St
RAL
9010
AxA
A+6
Installation of KD-6
KD-6/5 Ceiling installation with screws
A1x A1
Ax A
27
KD-6/5
KD-6/6
Ordering key:
KD-6A/5-J2 Size600
A
(mm)
300
400
500
600
625
300
400
500
600
625
A1
(mm)
298
398
498
598
623
H
(mm)
84
99
114
127
173
d
(mm)
148
198
248
298
298
Discharge directions
KD-6A,
KD-6B,
KD-6C,
KD-6D,
KD-6E,
J2 Registers J2
5 Installation with screws on
6 the outer frame
Installation via special grider
A Inlet direction
B
C
D
E
KD-6
J2
40
size
300
400
500
600
625
141
194
244
294
294
PERFORATED DIFFUSERS
KD-6
Diagram for determining the size and temperature of the air jet flow of the square diffusers KD-6
Effective discharge velocity vef (m/s)
625
0.2
0.1
0.05
6
7
600
8
0.04
500
10
2000
400
0.03
1500
1000
800
300
600
500
400
300
200
0.6
0.3
0.2
0.4
0.5
3
0.75
2
1.0
0.6
Example:
L=C+E
C
VL (m/s)
Q (m3/h)
tZ ( C)
tL ( C)
b0.2
Given data:
Air flow volume:
Air jet velocity:
Temperature difference:
Q = 600 m /h, L = 2 m
VL = 0.3 m/s
tZ = 5OC
Solution:
From the diagram select the diffuser KD-6 size 400.
VL = 0.2 m/s
L (m)
2
Throw distance L (m)
0.1
VL (m/s)
tL ( C)
PERFORATED DIFFUSERS
KD-6
2.0
14
13
je t
Air
12
oic
vel
11
L
ty V
500
um
e
/s)
(m
1.0
0.8
0.6
0.7
0.5
0.4
0.3
0.8
(m
10
Vo
l
1.5
200
7
100
6
5
50
4
3
2
20
1
0.1
0.2
0.3
0.4
Vertical velocity vh(m/s)
0.5
0.7
0.7
1.0
2.0
Distance from ceiling (m)
Dtz(OC)
temperature quotient:
Pressure drop diagram
25%
Opened
50%
55
100%
50
50
Regulation set-up
45
40
35
40
30
35
20
pcel
(A
)
30
30
LW
A(
dB
10
25
Pressure drop
pcel (Pa)
45
40
1.5
5.0
50
4.0
VL
100
3.0
CEILING DIFFUSERS
PERFORMANCE DATA
The following tables include the results of tests conducted on three square ceiling diffusers. The test results
include noise criteria (NC), static pressure versus airflow, throw and Ak. The diffusers were selected and
supplied by Beta in 1991. The extrapolations and interpolations were made to cover a full range of sizes and
parameters according to ETL Testing Laboratories Inc. who made the tests.
TEST METHOD >>
The air diffusers were tested in accordance with the Air Diffusion Council test code for grilles, registers and
diffusers No. ADC 1062:GRD-84. The test was conducted in ETL Testing Laboratories Inc.
The diffusers were installed in the ADC facility and supplied with measured volume of air. The static pressure
was measured (1-1.5) duct diameter upstream of the diffuser inlet.
Acoustical data was obtained employing a Bruel and Kjaep digital frequency analyzer and analyzed by
computer. Sound power levels were plotted on a graph of Noise Criteria Curves which are in the ADC codes.
NOTES :
0.035
0.046
0.052
0.058
0.070
0.070
0.081
300 X 150
225 X 225
375 X 150
450 X150
300 X 225
525 X 150
0.023
150 X 150
225 X 150
An
SIZE
0.031
0.026
0.026
0.020
0.020
0.018
0.014
0.009
Ak
1.270
29
0.508
1.2-1.8-3.3
<15
44
0.508
1.5-2.1-3.9
<15
59
0.508
1.8-2.7-4.5
<15
66
0.508
1.8-2.7-4.8
<15
74
0.616
1.8-2.7-4.8
<15
88
0.616
2.1-3.3-5.7
<15
88
0.616
2.1-3.3-5.7
<15
103
0.616
2.1-3.3-6.0
<15
1.016
24
0.330
0.9-1.2-2.4
<15
35
0.330
1.2-1.8-3.3
<15
47
0.330
1.5-2.1-4.2
<15
53
0.330
1.5-2.1-4.2
<15
59
0.395
1.5-2.1-4.2
<15
71
0.395
1.8-2.7-4.5
<15
71
0.395
1.8-2.7-4.5
<15
83
0.395
1.8-2.7-4.8
<15
Vn
SAD,RAD
L/S
Pt
Th
NC
L/S
Pt
Th
NC
L/S
Pt
Th
NC
L/S
Pt
Th
NC
L/S
Pt
Th
NC
L/S
Pt
Th
NC
L/S
Pt
Th
NC
L/S
Pt
Th
NC
CEILING DIFFUSERS
35
0.711
1.2-2.1-3.6
<15
53
0.711
1.8-2.4-4.2
<15
71
0.737
2.1-3.0-4.8
<15
80
0.737
2.1-3.3-5.4
<15
88
0.914
2.1-3.3-5.7
<15
106
0.914
2.4-3.6-6.0
<15
106
0.914
2.4-3.6-6.0
<15
124
0.914
3.0-3.9-6.9
<15
1.524
41
0.991
1.5-2.4-3.9
<15
62
0.991
2.1-3.0-4.8
<15
83
1.013
2.4-3.3-5.4
<15
93
1.016
2.4-3.6-6.0
<15
103
1.205
2.7-3.9-6.3
<15
124
1.205
3.0-4.2-6.6
<15
124
1.205
3.0-4.2-6.6
<15
145
1.205
3.3-4.5-7.5
<15
1.778
47
1.295
1.8-2.7-4.2
<15
71
1.295
2.4-3.3-5.1
<15
94
1.321
2.7-3.6-5.7
<15
106
1.321
3.0-4.2-6.3
16
118
1.651
3.3-4.5-6.9
15
142
1.651
3.6-4.8-7.5
16
142
1.651
3.6-4.8-7.5
16
165
1.651
3.6-4.8-8.1
16
2.032
59
2.007
2.1-3.3-4.8
19
88
2.032
3.0-3.9-6.0
20
118
2.057
3.3-4.2-6.6
21
133
2.057
3.3-4.8-6.9
22
147
2.515
3.9-5.1-7.5
22
177
2.515
4.2-5.4-8.1
23
177
2.515
4.2-5.4-8.1
23
206
2.515
4.2-5.4-8.7
23
2.540
71
3.658
2.7-3.6-5.1
24
106
3.568
3.6-4.5-6.6
26
142
3.658
3.9-4.8-7.2
27
159
2.972
4.2-5.4-7.8
28
177
3.658
4.5--5.7-8.1
28
212
3.658
4.8-6.0-9.0
29
212
3.658
4.8-6.0-9.0
29
248
3.658
5.1-6.0-9.3
29
3.048
4.064
83
94
3.962
5.029
3.0-3.9-5.4 3.3-4.2-5.7
29
33
124
142
4.978
6.502
4.2-5.1-7.2 4.5-5.4-7.5
30
34
165
189
4.978
6.502
4.5-5.4-7.8 5.1-6.0-8.4
31
35
186
213
4.064
5.283
4.8-6.0-8.4 5.1-6.3-9.3
33
37
206
236
4.978
6.502
5.1-6.3-8.7 6.0-7.2-9.9
32
36
248
283
4.978
6.502
.5.4-6.9-9.9 6.3-7.8-11.1
33
37
248
283
4.978
6.502
5.4-6.9-9.9 6.3-7.8-11.1
33
37
289
330
4.978
6.502
5.7-6.9-0.2 6.3-7.8-11.1
33
37
3.556
*SI UNITS
CEILING DIFFUSERS
PERFORMANCE DATA-SUPPLY/SAD,RAD
0.093
0.093
0.105
0.116
0.122
0.139
0.139
600x150
450x225
375x300
525x225
600x225
450x300
0.087
375x225
300x300
An
SIZE
0.052
0.052
0.045
0.043
0.039
0.033
0.033
0.033
Ak
Vn
L/S
Pt
Th
NC
L/S
Pt
Th
NC
L/S
Pt
Th
NC
L/S
Pt
Th
NC
L/S
Pt
Th
NC
L/S
Pt
Th
NC
L/S
Pt
Th
NC
L/S
Pt
Th
NC
1.016
89
0.395
1.8-2.7-4.5
<15
94
0.356
1.8-2.7-5.4
<15
94
0.395
1.7-2.8-5.5
<15
106
0.395
2.4-3.3-6.0
<15
118
0.395
2.4-3.3-6.6
<15
124
0.395
2.4-3.0-6.0
<15
142
0.395
2.4-3.0-6.0
<15
142
0.395
2.4-3.0-6.0
<15
CEILING DIFFUSERS
1.270
111
0.616
2.4-3.0-5.7
15
118
0.533
2.1-3.3-6.3
<15
118
0.616
2.7-3.6-6.6
<15
133
0.616
2.7-3.6-6.9
<15
147
0.616
2.7-3.9-6.9
<15
155
0.616
2.7-3.6-6.6
<15
177
0.616
2.7-4.2-6.9
<15
177
0.616
2.7-3.9-6.6
<15
SAD,RAD
1.524
133
0.914
2.7-3.9-6.9
17
142
0.787
2.7-3.9-7.2
<15
142
0.914
3.0-4.2-7.5
<15
159
0.914
3.0-4.2-7.5
<15
177
0.914
3.0-4.5-7.5
<15
186
0.914
3.0-4.8-7.5
<15
212
0.914
3.3-5.1-7.5
<15
212
0.914
3.3-4.8-7.2
<15
1.778
155
1.205
3.3-4.5-7.2
20
165
1.067
3.3-4.8-7.8
16
165
1.205
3.6-4.8-8.1
<15
186
1.205
3.6-5.1-7.8
15
206
1.205
3.6-5.4-8.1
15
217
1.205
3.6-5.7-8.1
15
248
1.205
3.9-5.7-8.1
15
248
1.205
3.6-5.4-7.8
15
2.032
177
1.651
3.6-5.1-7.8
24
189
1.397
3.6-5.4-8.1
19
189
1.651
3.9-5.7-8.4
17
212
1.651
4.2-6.0-9.0
18
236
1.651
4.5-6.3-9.0
19
248
1.651
4.2-6.0-8.7
18
283
1.651
4.5-6.0-8.7
19
283
1.651
4.2-5.7-8.4
20
2.540
3.048
266
221
3.658
2.515
7.2-5.7-8.7 5.1-6.3-9.6
34
30
283
236
3.150
2.159
4.5-6.3-9.0 5.4-7.2-9.9
32
25
283
236
3.658
2.515
4.8-6.6-9.3 5.7-7.5-10.2
30
24
319
265
3.658
2.515
5.1-6.9-9.6 6.0-7.5-10.5
31
25
354
295
3.658
2.515
5.4-6.9-9.9 6.3-7.8- 10.5
32
26
372
310
3.658
2.515
5.1-6.6-9.3 6.0-7.5-9.9
31
25
425
354
3.658
2.515
5.4-6.9-9.3 6.3-7.5-10.2
32
26
425
354
3.658
2.515
5.1-6.6-9.0 6.0-7.2-9.9
33
27
3.556
310
4.978
5.7-6.9-10.5
38
330
4.242
6.3-7.8-10.8
36
330
4.978
6.6-8.1-11.1
34
372
4.978
6.6-8.1-11.1
35
413
4.978
6.9-8.4-11.1
36
434
4.978
6.9-8.4-11.1
35
496
4.978
6.9-8.7-11.1
36
496
4.978
6.9-8.4-10.8
37
*SI UNITS
4.064
354
6.502
6.6-7.8-11.4
42
378
5.563
6.9-8.1-11.4
40
378
6.502
7.2-8.4-11.7
38
425
6.502
7.2-8.7-12
39
472
6.502
7.5-9.3-12.6
40
496
6.502
7.2-9.0-12.9
39
566
6.502
7.5-9.0-12.9
40
566
6.502
7.2-8.7-12.3
41
CEILING DIFFUSERS
PERFORMANCE DATA-SUPPLY/SAD,RAD
11
0.163
0.174
0.186
0.203
0.209
0.232
0.244
450x375
600x300
525x375
450x450
600x375
525x450
0.145
375x375
525x300
An
SIZE
0.084
0.073
0.074
0.068
0.064
0.060
0.054
Ak
Vn
L/S
Pt
Th
NC
L/S
Pt
Th
NC
L/S
Pt
Th
NC
L/S
Pt
Th
NC
L/S
Pt
Th
NC
L/S
Pt
Th
NC
LS
Pt
Th
NC
L/S
Pt
Th
NC
1.270
184
0.559
3.0-4.2-8.1
<15
206
0.616
3.0-4.5-8.4
<15
221
0.616
3.0-4.8-8.7
<15
236
0.616
3.3-4.8-8.7
<15
258
0.616
3.3-5.1-8.7
<15
265
0.584
3.3-5.1-9.6
18
295
0.616
3.6-5.4-9.9
<15
310
0.616
3.6-5.4-9.9
<15
SAD,RAD
1.016
148
0.356
2.4-3.6-6.9
<15
165
0.395
2.4-3.6-7.5
<15
177
0.395
2.4-3.3-7.2
<15
189
0.395
2.4-3.3-7.2
<15
207
0.395
2.7-3.9-7.8
<15
212
0.381
2.7-4.2-8.1
<15
236
0.395
2.7-4.5-8.7
<15
248
0.395
2.4-4.2-7.8
<15
CEILING DIFFUSERS
1.524
221
0.813
3.6-5.1-9.0
17
248
0.914
3.6-5.4-9.3
<15
265
0.914
3.9-5.7-9.3
<15
283
0.914
3.9-6.0-9.3
<15
310
0.914
3.9-6.3-9.3
<15
319
0.838
4.2-6.0-10.5
22
354
0.914
4.2-6.3-10.8
<15
372
0.914
4.2-6.0-10.5
<15
1.778
258
1.092
3.9-5.7-9.9
23
289
1.205
4.5-6.6-9.6
15
310
1.205
4.5-6.9-9.9
17
330
1.205
4.5-6.9-9.9
17
361
1.205
4.8-7.2-10.5
17
372
1.143
4.8-6.9-11.7
27
413
1.205
5.4-7.8-11.7
18
434
1.205
5.4-8.1-12.0
18
2.032
295
1.422
4.8-6.9-10.2
28
330
1.651
5.1-7.5-10.5
20
354
1.651
5.1-7.2-10.2
21
378
1.651
5.7-7.8-11.4
21
413
1.651
6.0-8.1-12.0
21
425
1.473
5.7-8.1-12.3
34
472
1.651
6.0-8.7-12.6
22
496
1.651
5.7-8.4-12.6
22
*SI UNITS
2.540
3.048
3.556
4.064
369
443
516
590
2.210
3.200
4.369
5.715
5.7-8.1-11.4 6.9-9.0-12.9 7.8-9.6-13.8
8.4-10.2-15
35
41
45
49
413
496
578
661
2.515
3.658
4.978
6.502
6.3-8.4-12.3 7.5-9.3-13.2 8.1-9.9-14.4 9.0-10.8-15.6
27
33
37
41
442
531
619
708
2.515
3.658
4.978
6.502
6.6-8.7-12.6 7.5-9.3-13.5 8.4-10.2-15
9.3-11.1-16.2
28
34
38
42
472
566
661
755
2.515
3.658
4.978
6.502
6.9-8.7-12.9 7.8-9.6-14.1 8.4-10.5-15.3 9.0-11.4-16.8
28
34
38
42
516
620
723
826
2.515
3.658
4.978
6.502
7.2-9.0-13.2 7.8-9.9-14.4 8.4-10.8-15.9 9.2-11.7-17.7
28
34
38
42
531
637
743
849
2.311
3.353
4.521
5.969
6.6-9.6-13.5 8.1-10.5-15.3 9.3-11.4-16.2 12.3-16.2-17.7
39
44
48
53
590
708
826
944
2.515
3.658
4.978
6.502
7.2-9.9-14.1 9.0-11.1-15.9 12.0-15.6-17.1 12.9-16.5-18.3
29
35
39
43
619
743
867
991
2.515
3.658
4.978
6.502
6.9-9.3-13.5 8.7-10.8-15.0 12.0-15.3-17.1 13.5-16.8-18.9
29
36
39
43
CEILING DIFFUSERS
PERFORMANCE DATA-SUPPLY/SAD,RAD
12
0.325
0.372
600x525
600x600
L/S
Ak
An
Vn
Pt
Th
NC
0.130
0.117
0.099
0.101
Ak
283
0.395
3.3-4.8-9.3
<15
289
0.381
3.3-4.6-9.3
16
330
0.395
3.3-5.1-9.9
<15
378
0.381
3.6-5.7-10.8
18
L/S
Pt
Th
NC
L/S
Pt
Th
NC
L/S
Pt
Th
NC
L/S
Pt
Th
NC
1.524
* Supply.
* Damper is fully open.
1.778
496
1.205
5.7-8.1-13.5
19
506
1.168
5.7-8.1-13.5
31
578
1.205
6.3-9.0-13.5
18
661
1.194
6.3-9.3-15.6
34
*SI UNITS
3.556
2.032
2.540
3.048
4.064
708
849
991
1133
566
1.651
3.658
6.502
2.515
4.978
6.6-9.6-14.1 8.4-11.1-15.6 9.9-12.6-17.7 11.4-13.8-18.3 12.3-14.7-20.4
30
44
40
36
23
1012
1156
578
867
723
2.413
3.454
4.724
6.121
1.524
6.6-9.6-14.1 7.8-11.1-15.9 9.6-12.3-17.7 10.8-13.2-18.9 11.7-14.1-20.7
42
47
55
37
51
826
661
991
1321
1156
4.978
3.658
1.651
6.502
2.515
6.9-10.2-14.7 8.7-11.7-16.8 10.5-12.6-18.0 11.4-13.5-19.8 12.3-14.7-21.6
24
37
31
45
41
755
1510
944
1321
1133
1.549
2.413
6.223
3.505
4.775
7.5-11.1-16.2 9.0-12.9-18.0 11.1-14.1-20.1 12.3-15.3-21.6 13.5-16.2-23.7
45
40
57
50
53
NOTES
425
354
0.914
0.616
3.9-6.0-10.8 4.8-7.2-12.3
<15
<15
434
361
0.864
0.610
3.9-6.0-11.1 4.8-7.2-12.3
25
20
413
496
0.616
0.914
4.2-6.6-11.7 5.4-7.8-12.6
<15
15
566
472
0.610
0.889
4.5-6.9-12.9 5.4-8.1-14.1
23
29
1.270
SAD,RAD
CONDITIONS
1.016
Vn
0.285
525x525
SYMBOLS
0.279
600x450
SIZE
An
CEILING DIFFUSERS
CEILING DIFFUSERS
PERFORMANCE DATA-SUPPLY/SAD,RAD
An
0.023
0.035
0.046
0.052
0.058
0.070
0.070
0.081
0.087
0.093
0.093
0.105
0.116
0.122
0.139
0.139
0.145
SIZE
150 x 150
225 x 150
300 x 150
225 x 225
375 x 150
450 x 150
300 x 225
525 x 150
375 x 225
300 x 300
600 x 150
450 x 225
375 x 300
525 x 225
600 x 225
450 x 300
375 x 375
L/S
Ps
NC
L/S
Ps
NC
L/S
Ps
NC
L/S
Ps
NC
L/S
Ps
NC
L/S
Ps
NC
L/S
Ps
NC
L/S
Ps
NC
L/S
Ps
NC
L/S
Ps
NC
L/S
Ps
NC
L/S
Ps
NC
L/S
Ps
NC
L/S
Ps
NC
L/S
Ps
NC
L/S
Ps
NC
L/S
Ps
NC
Vn
3
71
4.572
31
106
5.588
33
142
5.588
34
159
5.588
36
177
5.764
36
212
6.098
37
212
6.098
37
248
6.096
38
266
6.096
38
283
6.096
39
283
6.096
39
319
6.096
40
354
6.096
40
372
6.096
41
425
6.096
42
425
6.096
42
442
6.096
42
2.5
59
3.302
25
88
3.810
28
118
3.810
29
132
3.810
30
147
3.986
31
177
4.320
32
177
4.320
32
206
4.318
33
221
4.318
33
236
4.318
33
236
4.318
33
265
4.318
34
295
4.318
34
310
4.318
35
354
4.318
36
354
4.318
36
368
4.318
36
2
47
2.032
17
71
2.540
19
94
2.540
21
106
2.540
22
118
2.626
23
142
2.793
24
142
2.793
24
165
2.794
25
177
2.794
26
189
2.794
26
189
2.794
26
212
2.794
27
236
2.794
27
248
2.794
27
283
2.794
28
283
2.794
28
294
2.794
28
1.5
35
1.270
<15
53
1.524
<15
71
1.524
<15
79
1.524
<15
88
1.524
<15
106
1.524
15
106
1.524
15
124
1.524
16
133
1.524
16
142
1.524
16
142
1.524
16
159
1.524
17
177
1.524
17
186
1.524
18
212
1.524
19
212
1.524
19
221
1.524
19
SAD,RAD
CEILING DIFFUSERS
3.6
83
6.350
36
124
7.620
38
165
7.620
40
185
7.620
41
206
7.881
42
248
8.383
43
248
8.382
43
289
8.382
44
310
8.382
45
330
8.382
45
330
8.382
45
372
8.382
46
413
8.382
46
434
8.382
46
495
8.382
47
495
8.382
47
515
8.382
52
4.1
94
8.128
41
142
9.906
44
189
9.906
45
211
9.906
46
236
10.253
46
283
10.922
47
283
10.922
47
330
10.922
48
354
10.922
48
378
10.922
49
378
10.922
49
425
10.922
50
472
10.922
50
496
10.922
51
566
10.922
52
566
10.922
52
589
10.922
*SI UNITS
CEILING DIFFUSERS
PERFORMANCE DATA-RETURN/SAD,RAD
SAD,RAD
0.279
0.285
0.325
0.372
600 x 450
525 x 525
600 x 525
600 x 600
2.5
413
4.318
37
442
4.318
37
472
4.318
37
516
4.318
38
531
4.318
38
590
4.318
39
619
4.318
39
708
4.318
40
722
4.318
40
826
4.318
41
944
4.318
42
* Return
* Damper is fully open.
* Noise Criteria is based on (10dB) room attenuation.
0.244
525 x 450
2
330
2.794
29
354
2.794
29
378
2.794
30
413
2.794
31
425
2.794
31
472
2.794
32
495
2.794
32
566
2.794
33
578
2.794
33
661
2.794
34
755
2.794
34
CONDITIONS
0.232
600 x 375
L/S
Ps
NC
L/S
Ps
NC
L/S
Ps
NC
L/S
Ps
NC
L/S
Ps
NC
L/S
Ps
NC
L/S
Ps
NC
L/S
Ps
NC
L/S
Ps
NC
L/S
Ps
NC
L/S
Ps
NC
L/S
*An
*Vn
*Ps
*NC
0.209
450 x 450
1.5
248
1.524
20
265
1.524
20
283
1.524
21
310
1.524
21
319
1.524
21
354
1.524
22
372
1.524
22
425
1.524
23
433
1.524
23
495
1.524
24
566
1.524
24
Vn
SYMBOLS
0.203
525 x 375
0.174
450 x 375
0.186
0.163
525 x 300
600 x 300
An
SIZE
CEILING DIFFUSERS
3
495
6.096
42
531
6.096
43
566
6.096
43
620
6.096
44
637
6.096
44
708
6.096
45
743
6.096
45
849
6.096
46
866
6.096
46
991
6.096
47
1133
6.096
48
4.1
661
10.922
53
708
10.922
53
755
10.922
53
826
10.922
54
849
10.922
54
944
10.922
55
991
10.922
55
1133
10.922
56
1155
10.922
56
1321
10.922
57
1510
10.922
58
3.6
578
8.382
48
619
8.382
49
661
8.382
49
723
8.382
50
743
8.382
50
826
8.382
51
867
8.382
51
991
8.382
52
1011
8.382
52
1156
8.382
53
1321
8.382
53
CEILING DIFFUSERS
PERFORMANCE DATA-RETURN/SAD,RAD
0.146
0.192
0.375
0.500
0.563
0.625
9x6
12 x 6
9x9
15 x 6
0.210
0.096
0.250
6x6
Ak
An
SIZE
50
CFM
4-6-11
3-4-8
<15
75
Th
NC
CFM
<15
<15
100
NC
CFM
110
0.016
5-8-14
<15
NC
125
CFM
Pt
<15
Th
6-9-16
5-7-14
Th
NC
<15
6-9-16
0.024
156
<15
0.020
0.013
Pt
<15
<15
NC
CFM
140
6-9-15
0.013
5-7-14
Pt
Th
0.020
125
5-7-13
0.013
4-6-11
Pt
Th
0.020
93
<15
0.020
63
250
0.013
Pt
200
Vn
<15
7-11-19
0.036
188
<15
7-11-18
0.029
170
<15
7-10-16
0.029
150
<15
6-8-14
0.028
112
<15
4-7-12
0.028
75
300
SAD,RAD
CEILING DIFFUSERS
0.065
11-15-23
15
<15
250
219
0.047
16
<15
9-13-21
10-14-21
8-12-20
225
195
0.052
<15
<15
0.040
0.052
9-12-19
200
175
0.040
<15
<15
8-11-18
0.051
8-11-17
150
131
0.039
<15
7-10-16
6-9-14
<15
0.051
100
400
5-8-13
0.039
88
350
22
13-17-25
0.099
312
22
11-16-23
0.081
280
21
11-14-22
0.081
250
20
10-13-20
0.080
187
19
7-11-16
0.079
125
500
28
15-19-27
0.144
375
28
14-18-26
0.117
335
27
13-16-24
0.144
300
26
12-15-22
0.144
225
24
9-12-17
0.144
150
600
32
17-21-29
0.196
438
33
16-20-28
0.160
395
31
15-18-26
0.196
350
30
14-17-24
0.196
262
29
10-13-18
0.156
175
700
*IMPERIAL UNITS
36
20-24-33
0.256
500
37
17-21-31
0.208
450
35
17-20-28
0.256
400
34
15-18-25
0.256
300
33
11-14-19
0.198
200
800
CEILING DIFFUSERS
PERFORMANCE DATA-SUPPLY/SAD,RAD
0.330
0.875
0.938
1.000
21 x 6
15 x 9
12 x 12
0.353
0.284
0.750
12 x 9
0.284
Ak
0.750
An
18 x 6
SIZE
150
CFM
7-11-19
6-9-15
<15
150
Th
NC
CFM
<15
<15
175
NC
CFM
<15
<15
188
NC
CFM
0.014
6-9-18
<15
Pt
NC
200
Th
15
<15
NC
CFM
<15
7-11-21
0.021
250
8-10-19
0.016
6-9-15
Pt
Th
0.024
235
7-11-20
0.016
6-9-16
Pt
Th
0.024
218
7-11-19
0.016
6-9-15
Pt
Th
0.024
188
<15
0.024
188
250
0.016
Pt
200
Vn
<15
9-13-24
0.031
300
17
9-13-23
0.036
281
<15
10-13-23
0.036
262
<15
8-12-20
0.036
225
<15
8-12-20
0.036
225
300
SAD,RAD
CEILING DIFFUSERS
16
11-16-26
0.042
350
20
11-15-24
0.047
328
<15
11-15-25
0.047
306
<15
10-14-22
19
12-18-27
0.055
400
24
12-17-26
0.065
375
16
12-16-27
0.065
350
16
12-16-25
0.065
300
263
0.047
16
12-16-25
0.065
300
400
<15
10-14-22
0.047
263
350
25
15-21-30
0.085
500
30
14-19-29
0.099
469
23
14-18-29
0.099
437
23
14-18-27
0.099
375
23
14-18-27
0.099
375
500
32
18-24-33
0.124
600
34
17-21-32
0.144
563
29
17-20-31
0.144
525
29
16-20-30
0.144
450
29
16-20-30
0.144
450
600
36
21-26-36
0.167
700
38
19-23-35
0.196
657
33
19-23-34
0.196
612
33
18-23-33
0.196
525
33
18-23-33
0.196
525
700
*IMPERIAL UNITS
40
23-27-38
0.219
800
42
22-26-38
0.256
750
37
21-26-37
0.256
700
37
21-26-37
0.256
600
37
21-26-37
0.256
600
800
CEILING DIFFUSERS
PERFORMANCE DATA-SUPPLY/SAD,RAD
17
0.577
0.644
1.563
1.750
1.875
2.000
15 x 15
21 x 12
18 x 15
24 x 12
0.688
0.555
1.500
18 x 12
Ak
An
SIZE
305
CFM
9-13-22
8-10-20
<15
310
Th
NC
CFM
<15
<15
350
NC
CFM
<15
<15
375
NC
CFM
0.016
8-11-24
<15
Pt
NC
400
Th
<15
<15
NC
CFM
<15
11-16-29
0.024
500
10-16-29
0.016
8-11-24
Pt
Th
0.024
468
10-15-28
0.016
8-12-25
Pt
Th
0.024
438
10-14-27
0.014
8-12-23
Pt
Th
0.022
390
<15
0.024
380
250
0.016
Pt
200
Vn
<15
13-20-31
0.036
600
<15
13-19-31
0.036
562
<15
12-18-31
0.036
525
17
12.17-30
0.032
470
<15
11-16-24
0.036
458
300
SAD,RAD
CEIING DIFFUSERS
CEILING
DIFFUSERS
0.065
19-26-38
21
0.047
15-23-33
17
21
800
17
17-24-34
0.065
750
20
17-25-35
0.065
700
28
16-23-34
0.056
625
20
14-19-28
0.065
600
400
700
15-23-33
0.047
656
15
15-22-32
0.047
613
23
13-19-33
0.043
545
15
12-18-26
0.047
530
350
28
23-29-43
0.099
1000
28
22-29-42
0.099
937
27
21-28-41
0.099
875
35
19-27-38
0.087
780
27
17-22-30
0.099
750
500
34
26-32-47
0.144
1200
34
25-31-45
0.144
1125
33
25-31-44
0.144
1050
41
23-30-43
0.126
940
33
20-24-33
0.144
900
600
38
28-35-51
0.196
1400
38
28-34-50
0.196
1312
37
27-33-48
0.196
1225
45
26-32-46
0.172
1090
37
23-28-36
0.196
1050
700
*IMPERIAL UNITS
42
30-38-56
0.256
1600
42
31-37-54
0.256
1500
41
30-36-52
0.256
1400
49
28-34-50
0.225
1250
41
24-29-41
0.256
1200
800
CEILING DIFFUSERS
PERFORMANCE DATA-SUPPLY/SAD,RAD
18
0.420
0.465
1.125
1.250
1.313
1.500
18 x 9
15 x 12
21 x 9
24 x 9
0.488
0.358
1.000
24 x 6
Ak
An
SIZE
200
CFM
9-12-22
7-10-19
<15
226
Th
NC
CFM
<15
<15
250
NC
CFM
<15
<15
262
NC
CFM
0.016
8-10-20
<15
Pt
NC
300
Th
<15
<15
NC
CFM
<15
9-14-23
0.024
375
9-12-22
0.016
8-10-20
Pt
Th
0.024
327
19-13-23
0.016
8-12-22
Pt
Th
0.024
313
9-12-23
0.016
8-11-20
Pt
Th
0.024
282
<15
0.024
250
250
0.016
Pt
200
Vn
<15
11-17-25
0.036
450
<15
10-16-25
0.036
393
<15
10-15-25
0.036
375
<15
10-14-25
0.036
337
<15
10-14-25
0.036
300
300
SAD,RAD
CEILING DIFFUSERS
15
13-19-27
0.047
525
15
12-19-27
0.047
458
15
12-18-27
0.047
438
15
12-17-26
0.047
393
<15
12-16-27
0.047
350
350
19
15-20-29
0.065
600
18
14-20-29
0.065
524
19
15-21-30
0.065
500
18
14-20-30
0.065
450
17
13-19-28
0.065
400
400
26
18-23-31
0.099
750
25
17-22-31
0.099
655
26
18-23-33
0.099
625
25
17-24-32
0.099
562
24
16-22-31
0.099
500
500
32
21-25-34
0.144
900
31
20-25-33
0.144
786
32
21-26-35
0.144
750
31
20-25-35
0.144
675
30
19-25-34
0.144
600
600
36
23-29-37
0.196
1050
35
23-28-37
0.196
917
36
23-28-37
0.196
875
35
22-27-37
0.196
768
34
22-27-37
0.196
700
700
*IMPERIAL UNITS
40
25-30-43
0.256
1200
39
24-30-43
0.256
1050
40
25-31-42
0.256
1000
39
24-29-40
0.256
900
38
24-28-39
0.256
800
800
CEILING DIFFUSERS
PERFORMANCE DATA-SUPPLY/SAD,RAD
0.785
0.908
2.250
2.500
2.625
3.000
18 x 18
24 x 15
21 x 18
24 x 18
0.799
2.188
21 x 15
Ak
An
SIZE
<15
500
NC
CFM
0.023
<15
526
CFM
0.016
11-16-31
<15
NC
600
CFM
Pt
<15
Th
12-18-33
8-14-26
Th
NC
<15
13-20-36
0.024
750
<15
0.024
657
0.016
Pt
12-18-33
9-15-29
Th
NC
<15
0.024
625
18
11-17-32
0.016
Pt
0.015
9-12-27
Pt
450
Th
<15
<15
NC
CFM
560
11-17-29
0.016
9-10-26
0.024
546
Pt
436
CFM
250
Th
200
Vn
<15
16-24-41
0.036
900
<15
14-12-35
0.036
787
<15
14-12-36
0.036
750
22
14-20-35
0.033
675
<15
13-12-31
0.036
655
300
SAD,RAD
CEILING DIFFUSERS
19
19-27-45
0.047
1050
18
18-27-40
0.047
918
18
18-26-39
0.047
875
27
16-23-39
0.045
785
17
16-24-35
0.047
765
350
23
33-32-47
0.065
1200
22
19-28-42
0.065
1050
22
20-29-42
0.065
1000
34
19-27-41
0.058
900
21
20-27-40
0.065
875
400
30
28-37-52
0.099
1500
29
23-31-45
0.099
1310
29
24-33-47
0.099
1250
39
22-32-45
0.091
1125
28
24-30-44
0.099
1092
500
36
33-42-59
0.144
1800
36
29-36-50
0.144
1570
35
30-37-53
0.144
1500
44
27-35-51
0.132
1350
34
26-33-48
0.144
1312
600
40
38-46-61
0.196
2100
39
40-51-57
0.196
1830
39
40-52-57
0.196
1750
48
31-38--54
0.178
1575
38
28-36-53
0.196
1532
700
*IMPERIAL UNITS
44
41-49-68
0.256
2400
43
45-56-63
0.256
2090
43
43-55-61
0.256
2000
53
41-54-59
0.235
1800
42
31-39-59
0.256
1750
800
CEILING DIFFUSERS
PERFORMANCE DATA-SUPPLY/SAD,RAD
3.500
4.000
24 x 21
24 x 24
700
CFM
: Throw in feet.
: Noise Criteria
Th
NC
Pt
23
* Supply.
An
Vn
Ak
18
NC
15-23-43
0.024
1000
CONDITIONS
0.015
12-19-36
800
CFM
Pt
<15
Th
14-22-39
11-17-33
Th
NC
<15
0.024
875
0.016
Pt
16
20
13-20-37
11-16-31
Th
NC
765
0.024
610
0.015
Pt
CFM
1.400
1.256
1.065
CFM
SYMBOLS
3.063
21 x 21
1070
34
21-31-52
0.047
1400
18
21-30-45
0.047
1225
31
19-27-45
0.046
1225
40
25-37-54
0.061
1600
24
23-34-49
0.065
1400
37
22-32-47
0.060
1530
mentioned ones.
150fpm.
50
37-47-67
0.038
2400
37
35-42-60
0.144
2100
47
32-41-59
0.036
1835
53
41-51--72
0.188
2800
41
38-45-66
0.196
2450
51
36-44-63
0.186
2140
*IMPERIAL UNITS
* Drop
2450
57
45-54-79
0.245
3200
45
41-49-72
0.256
2800
55
39-47-69
0.241
: No correction required.
: No correction required.
: No correction required.
45
30-43-60
0.095
2000
31
29-39-56
0.099
1750
42
26-37-53
0.095
NOTES
29
18-27-47
0.035
1200
15
18-26-42
0.036
1050
25
16-24-41
0.034
920
SAD,RAD
CEILING DIFFUSERS
CEILING DIFFUSERS
PERFORMANCE DATA-SUPPLY/SAD,RAD
0.563
0.625
0.750
0.750
0.875
0.938
1.000
1.000
1.125
1.250
1.313
1.500
1.500
1.563
9x9
15 x 6
18 x 6
12 x 9
21 x 6
15 x 9
12 x 12
24 x 6
18 x 9
15 x 12
21 x 9
24 x 9
18 x 12
15 x 15
0.375
9x6
0.500
0.250
6x6
12 x 6
An
SIZE
300
75
0.050
<15
113
0.060
<15
150
0.060
<15
168
1.060
<15
188
0.060
<15
225
0.060
15
225
0.060
15
263
0.060
16
281
0.060
16
300
0.060
16
300
0.060
16
338
0.060
17
375
0.060
17
394
0.060
18
450
0.060
19
450
0.060
19
468
0.060
19
Vn
CFM
Ps
NC
CFM
Ps
NC
CFM
Ps
NC
CFM
Ps
NC
CFM
Ps
NC
CFM
Ps
NC
CFM
Ps
NC
CFM
Ps
NC
CFM
Ps
NC
CFM
Ps
NC
CFM
Ps
NC
CFM
Ps
NC
CFM
Ps
NC
CFM
Ps
NC
CFM
Ps
NC
CFM
Ps
NC
CFM
Ps
NC
CEILING DIFFUSERS
100
0.080
17
150
0.100
19
200
0.100
21
224
0.100
22
250
0.103
23
300
0.110
24
300
0.110
24
350
0.110
25
375
0.110
26
400
0.110
26
400
0.110
26
450
0.110
27
500
0.110
27
525
0.110
27
600
0.110
28
600
0.110
28
624
0.110
28
400
125
0.130
25
188
0.150
28
250
0.150
29
280
0.150
30
313
0.157
31
375
0.170
32
375
0.170
32
438
0.170
33
469
0.170
33
500
0.170
33
500
0.170
33
563
0170
34
625
0.170
34
657
0.170
35
750
0.170
36
750
0.170
36
780
0.170
36
500
SAD,RAD
150
0.180
31
225
0.220
33
300
0.220
34
336
0.220
36
375
0.227
36
450
0.240
37
450
0.240
37
525
0.240
38
563
0.240
38
600
0.240
39
600
0.240
39
675
0.240
40
750
0.240
40
788
0.240
41
900
0.240
42
900
0.240
42
936
0.240
42
600
175
0.250
36
263
0.300
38
350
0.300
40
392
0.300
41
438
0.310
42
525
0.330
43
525
0.330
43
613
0.330
44
657
0.330
45
700
0.330
45
700
0.330
45
788
0.330
46
875
0.330
46
919
0.330
46
1050
0.330
47
1050
0.330
47
1092
0.339
47
700
200
0.320
41
300
0.390
44
400
0.390
45
448
0.390
46
500
0.404
46
600
0.430
47
600
0.430
47
700
0.430
48
750
0.430
48
800
0.430
49
800
0.430
49
900
0.430
50
1000
0.430
50
1050
0.430
51
1200
0.430
52
1200
0.430
52
1248
0.430
52
800
CEILING DIFFUSERS
PERFORMANCE DATA-RETURN/SAD,RAD
3.000
3.063
3.500
4.000
24 x 18
21 x 21
24 x 21
24 x 24
1050
0.240
42
1125
0.240
43
1200
0.240
43
1313
0.240
44
1350
0.240
44
1500
0.240
45
1575
0.240
45
1800
0.240
46
1836
0.240
46
2100
0.240
47
2400
0.240
48
1225
0.330
48
1313
0.330
49
1400
0.330
49
1532
0.330
50
1575
0.330
50
1750
0.330
51
1838
0.330
51
2100
0.330
52
2142
0.330
52
2450
0.330
53
2800
0.330
53
700
1400
0.430
53
1500
0.430
53
1600
0.430
53
1750
0.430
54
1800
0.430
54
2000
0.430
55
2100
0.430
55
2400
0.430
56
2448
0.430
56
2800
0.430
57
3200
0.430
58
800
*IMPERIAL UNITS
CONDITIONS
2.625
21 x 18
875
0.170
37
938
0.170
37
1000
0.170
37
1094
0.170
38
1125
0.170
38
1250
0.170
39
1313
0.170
39
1500
0.170
40
1530
0.170
40
1750
0.170
40
2000
0.170
42
600
*Return
*Damper is fully open.
*Noise Criteria is based on (10dB) room attenuation
2.500
24 x 15
700
0.110
29
750
0.110
29
800
0.110
30
875
0.110
31
900
0.110
31
1000
0.110
32
1050
0.110
32
1200
0.110
33
1224
0.110
33
1400
0.110
34
1600
0.110
34
525
0.060
20
563
0.060
20
600
0.060
21
656
0.060
21
675
0.060
21
750
0.060
22
788
0.060
22
900
0.060
23
918
0.060
23
1050
0.060
24
1200
0.060
24
CFM
Ps
NC
CFM
Ps
NC
CFM
Ps
NC
CFM
Ps
NC
CFM
Ps
NC
CFM
Ps
NC
CFM
Ps
NC
CFM
Ps
NC
CFM
Ps
NC
CFM
Ps
NC
CFM
Ps
NC
500
SYMBOLS
2.250
18 x 18
400
300
Vn
SAD,RAD
*CFM:
*An:
*Vn:
*Ps:
*NC:
2.188
21 x 15
1.875
18 x 15
2.000
1.750
21 x 12
24 x 12
An
SIZE
CEILING DIFFUSERS
CEILING DIFFUSERS
PERFORMANCE DATA-RETURN/SAD,RAD