Transformer Fan Details

Download as pdf or txt
Download as pdf or txt
You are on page 1of 38

Fans for Transformer Cooling

s
Valid as of 12/2005

Product Brochure 2CT2 2005

12/2005

Introduction

SIVENT Fans for Transformer Cooling

1 2 3 4 5 6 7 8 9

Quick Selection

2CT2 44

2CT2 56

2CT2 63

2CT2 73

2CT2 80

2CT2 10

Annex

The products listed in this product brochure are manufactured in compliance with a TV-certified quality management system in accordance with DIN EN ISO 9001 (certificate registration number 12 100 16950). The TV certificate is acknowledged in all IQ Net countries. TV stands for German Technical Control Board.

12/2005

1
Introduction General Information
Sivent fans are used for all power transformer cooling applications, e.g. in transformer substations or power plants, to dissipate the heat losses over external radiators or oil coolers. Our long-standing experience in the development of blade wheel and housing geometries guarantees minimum noise emission. The fans comply with the market requirements in large-scale transformer engineering and assure fail-safe operation in all climatic zones.

Advantages of Sivent Axial Fans


Sivent axial fans offer the following advantages:

Long service life Special corrosion protection Individual color selection Operating characteristics matched to the
power supply companys requirements

Outdoor-suitable housing made of hot-galvanized


sheet-steel and featuring an additional coating

Symbols for Fan Data


P F[Hz] U[V] I[A] P1[W] N[1/min] VFl[m/h] PST[Pa] LWal[dB] - number of poles - Frequency - nominal Voltage - operating current during free blow-out - power consumption during free blow-out - Speed - Volume flow during free blow-out - maximum static pressure; VFL is than reduced - A - Sound power level of a fan

Regulations of electrical voltages

built according to international IEC standard voltages 400/460 volts +6% / -10% )
Some countries still hold on to the old voltages 380 volts +/- 10% (342 volts up to 418 volts) resp. 415 volts +/- 10 % (374 volts up to 457 volts). In these extreme cases the machine function could be affected. A corresponding transformer or a special motor has to be used.

12/2005

1/1

SIVENT Fans for Transformer Cooling


Quick Selection

Selection and ordering data all data refer to 400 V, 50 Hz (-/+ 5% voltage tolerance) in acc. with EN60034-1
Max. Max. static volume flow pressure 3 in Pa in m /h Volume flow up to 7000 m 3/h 2304 9 2664 12 3600 22 4320 32 5742 28 6372 70 Volume flow up to 14000 m 3/h 8240 51 9398 43 10477 42 11702 42 12583 39 13648 65 Volume flow up to 22000 m 3/h 15224 39 15527 59 17404 64 19007 88 19200 62 21605 98 Volume flow up to 26000 m 3/h 23834 95 25433 157 Volume flow up to 32000 m 3/h 28440 96 31667 67 Volume flow up to 51000 m 3/h 35860 153 40462 110 43350 160 51022 174 A-Sound power level free-blowing in db(A) 53 57 65 69 76 79 76 68 69 69 70 76 72 77 77 81 78 82 83 87 90 83 95 90 95 95 No. of poles p 12 10 8 6 8 4 8 12 12 12 12 10 12 10 10 8 10 8 8 6 10 12 8 10 8 8 Frequency in f 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 440 440 440 440 560 440 630 730 730 730 730 800 800 730 800 730 800 800 800 730 1000 1000 1000 1000 1000 1000 2CT2 445-1EA23 2CT2 443-1EA23 2CT2 448-1EA23 2CT2 446-1EA23 2CT2 568-1EA23 2CT2 444-1EA23 2CT2 638-1EA13 2CT2 735-2EA13 2CT2 735-3EA13 2CT2 735-4EA13 2CT2 735-5EA13 2CT2 803-2EA13 2CT2 805-5EA13 2CT2 733-5EA13 2CT2 803-4EA13 2CT2 738-5EA13 2CT2 803-5EA13 2CT2 808-4EA13 2CT2 808-5EA13 2CT2 736-5EA13 2CT2 103-1EB13 2CT2 105-3EB13 2CT2 108-1EB13 2CT2 103-3EB13 2CT2 108-2EB13 2CT2 108-3EB13 Size Type Refererence Page 3/2 3/2 3/2 3/2 4/2 3/2 5/2 6/2 6/2 6/2 6/2 7/2 7/2 6/2 7/2 7/2 7/2 7/2 7/2 6/2 8/2 8/2 8/2 8/2 8/2 8/2

Data on power, volume flow and noise in accordance with the technical terms of delivery DIN24166 Accuracy class 2. Characteristic curve measuring in accordance with ISO 5801.

Available upon request: - Special voltages - Motor protection: temperature monitors (bimetal) or PTC resistor - Further ambient conditions, e.g. -40C - Further installation positions, e.g. vertical - Air flow direction blowing via motor as of size 560 - Individually factory-adjustable operating points as of size 730 mm - Higher static pressure up to 290 Pa - Pressure- and/or suction-side protection grid as of size 560 - Further motor pole configurations from 4- to 24-pole - Blade wheels in the following materials: polyamide, aluminum/cast, aluminum/sheet

12/2005

2/1

SIVENT Fans for Transformer Cooling


Quick Selection Selection and ordering data all data refer to 460 V, 60 Hz (-/+ 5% voltage tolerance) in acc. with EN60034-1
Max. volume flow in m3/h Volume flow up 2243 2776 4000 4655 6281 6316 Volume flow up 9023 9469 11124 12441 13773 Volume flow up 14992 16472 17213 21005 Volume flow up 23171 25206 34128 39760 48556 Max. static pressure in Pa 7000 m3/h 9 13 27 36 66 34 14000 m 3/h 69 68 60 59 58 22000 m 3/h 54 95 50 93 49000 m 3/h 90 133 138 102 158 A-Sound power level free-blowing in db(A) 35 41 50 54 62 77 86 79 73 73 74 75 80 75 81 82 86 94 89 94

No. of poles p 12 10 8 6 4 8 6 8 12 12 12 12 10 12 10 10 8 10 12 10

Frequency f 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60

Size

Type

Refererence Page

to

440 440 440 440 440 560 560 630 730 730 730 730 800 800 800 800 800 1000 1000 1000

2CT2 445-1EA23 2CT2 443-1EA23 2CT2 448-1EA23 2CT2 446-1EA23 2CT2 444-1EA23 2CT2 568-1EA83 2CT2 566-1EA83 2CT2 638-1EA83 2CT2 735-2EA83 2CT2 735-3EA83 2CT2 735-4EA83 2CT2 735-5EA83 2CT2 803-2EA83 2CT2 805-5EA83 2CT2 803-4EA83 2CT2 803-5EA83 2CT2 808-5EA83 2CT2 103-1EB83 2CT2 105-3EB83 2CT2 103-3EB83

3/3 3/3 3/3 3/3 3/3 4/3 4/3 5/3 6/3 6/3 6/3 6/3 7/3 7/3 7/3 7/3 7/3 8/3 8/3 8/3

to

to

to

Data on power, volume flow and noise in accordance with the technical terms of delivery DIN24166 Accuracy class 2. Characteristic curve measuring in accordance with ISO 5801.

Available upon request: - Special voltages - Motor protection: temperature monitors (bimetal) or PTC resistor - Further ambient conditions, e.g. -40C - Further installation positions, e.g. vertical - Air flow direction blowing via motor as of size 560 - Individually factory-adjustable operating points as of size 730 mm - Higher static pressure up to 290 Pa - Pressure- and/or suction-side protection grid as of size 560 - Further motor pole configurations from 4- to 24-pole - Blade wheels in the following materials: polyamide, aluminum/cast, aluminum/sheet

12/2005

2/2

12/2005

SIVENT Fans for Transformer Cooling


2CT2 44 Application Area

Fan 2CT2 44

Technical delivery Installation Impeller

DIN 24166, accuracy class 2 Suitable for outdoor installation 1)Polypropylene (black, UV-resistant, fail-safe also with intensive solar radiation (1200 W/m2)) 2) Aluminum cast fix Q 6,3 in acc. with ISO 1940 Part 1 From -20C to +50 C Sheet-steel with integrally molded inlet nozzle, hot-galvanized Suction- and pressure-side stainless steel protection grids 440 mm 2300 - 6400 m/h 9 - 70 Pa 4/6/8/10/12-pole From 0.05 to 0.43 kW IP55 as in DIN VDE 0470-1 F as in VDE 0530 50Hz: 220-290VD / 380-500VY/ 60Hz 208-290VD/360-500VY Inside the motor terminal box (refer to dimension drawing) Horizontal and vertical motor shaft (blowing direction) Housing: hot-galvanized with triple coating RAL7033 105m, (cement gray) CHING coating HV43 Motor: RAL 9005 (black) After ISO 12944 C3/L Approx. 20 kg 4years

Wing angle Balance quality Average air flow temperature Housing Protection grid Diameter (blade wheel Volume flow (max.) Static pressure (max.) Number of poles Motor output Degree of protection Isolations class of winding Varying-voltage winding Electrical connection Installation positions Color + layer thickness

Corrosion protection Weight Maintenance period

SIVENT Fans for Transformer Cooling


2CT2 44, 400 V Y, 50 Hz Characteristic curves, incl. protection grid (suction- and pressure-side)
80

70

4-pole

60 static pressure in Pa

50

40
6-pole

30
8-pole

20
10-pole

10
12-pole

0 0 1000 2000 3000 4000 flow rate in m/h 5000 6000 7000

0,25 impeller power demand in kW

0,2

0,15

0,1

0,05

0 0 1000 2000 3000 4000 5000 6000 7000 flow rate in m /h

Selection and Ordering Data


operating current during free blow -out in A pow er consumption during free blow -out in W Volume flow during free blow -out in m3/h Sound pressure level in 1 m, lateral free blow -out in dB(A)

No. of poles in p

Speed in 1/min

maximum static pressure in Pa

A-Sound pow er level free blow -out in dB(A)

Fan type

Motor size 63, 400 V Y, 50 Hz

4 6 8 10 12

0.72 0.32 0.21 0.11 0.11

430 160 90 55 51

1140 770 645 475 410

6372 4320 3600 2664 2304

70 32 22 12 9

63 53 48 40 36

79 69 65 57 53

2CT2 444-1EA23 2CT2 446-1EA23 2CT2 448-1EA23 2CT2 443-1EA23 2CT2 445-1EA23

12/2005

3/2

SIVENT Fans for Transformer Cooling


2CT2 44, 460 V Y, 60 Hz Characteristic curves, incl. protection grid (suction- and pressure-side)
80
4-pole

70

60 static pressure in Pa

50
6-pole

40

30

8-pole

20

10-pole

10
12-pole

0 0 1000 2000 3000 4000 flow rate in m/h 5000 6000 7000

0,25 impeller power demand in kW

0,2

0,15

0,1

0,05

0 0 1000 2000 3000 4000 5000 6000 7000 flow rate in m /h

Selection and Ordering Data


operating current during free blow -out in A pow er consumption during free blow -out in W Volume flow during free blow -out in m/h Sound pressure level in 1 m, lateral free blow -out in dB(A)

No. of poles in p

Speed in 1/min

maximum static pressure in Pa

A-Sound pow er level free blow -out in dB(A)

Fan type

Motor size 63, 460 V Y, 60 Hz

4 6 8 10 12

0,86 0,38 0,24 0,12 0,11

580 220 120 73 58

1130 830 715 495 400

6281 4655 4000 2776 2243

66 36 27 13 9

62 54 50 41 35

79 71 66 58 52

2CT2 444-1EA23 2CT2 446-1EA23 2CT2 448-1EA23 2CT2 443-1EA23 2CT2 445-1EA23

12/2005

3/3

SIVENT Fans for Transformer Cooling


Dimension Drawings 2CT2 44

3
Rating Plate

Standard housing, circular

12/2005

3/4

SIVENT Fans for Transformer Cooling


2CT2 56 Application Area

Fan 2CT2 56

Technical Data
Technical delivery Installation Impeller DIN 24166, accuracy class 2 Suitable for outdoor installation 1)Polypropylene (black, UV-resistant, fail-safe also with intensive solar radiation (1200 W/m2)) 2) Aluminum cast Q 6,3 in 1940 Part 1 1 Q6,3 in acc. acc.with withISO ISO 1940 Part From -20C to +50 C Sheet-steel with integrally molded inlet nozzle, hot-galvanized Suction- and pressure-side stainless steel protection grids 560 mm 5500 m/h 33Pa 8-pole Up to 0,3 kW IP55 as in DIN VDE 0470-1 F as in VDE 0530 50Hz: 220-290VD / 380-500VY/ 60Hz: 440-480VY Inside the motor terminal box (refer to dimension drawing) Horizontal and vertical motor shaft (blowing direction) Housing: hot-galvanized with triple coating RAL7033 105mm (cement gray) CHING coating HV43 Motor: RAL 9005 (black) After ISO 12944 C3/L Approx. 40kg 4years

Balance quality Average air flow temperature Housing Protection grid Diameter (blade wheel Volume flow (max.) Static pressure (max.) Number of poles Motor output Degree of protection Isolations class of winding Varying-voltage winding Electrical connection Installation positions Color + layer thickness

Corrosion protection Weight Maintenance period

12/2005

4/1

SIVENT Fans for Transformer Cooling


2CT2 56, 400 V Y, 50 Hz Characteristic curves without protection grid (suction- and pressure side)

Pressure loss per protection grid PLGrid= 4.41 * (V/3600) (m/h)

4
static pressure in Pa

30

25 8-pole 20

15

10

0 0 1000 2000 3000 4000 5000 6000 7000

flow rate in m/h

impeller power demand in kW

0,09 0,08 0,07 0,06 0,05 0,04 0,03 0,02 0,01 0 0 1000 2000 3000 4000 5000 6000 7000

flow rate in m/h

Selection and Ordering Data


No. of poles in p operating current during free blow -out in A pow er consumption during free blow -out in W Volume flow during free blow -out in m/h maximum static pressure in Pa Sound pressure level in 1 m, lateral free blow -out in dB(A) A-Sound pow er level free blow -out in dB(A)

Speed in 1/min

Fan type

Motor size 80, 400 V Y, 50 Hz

0,75

200

700

5742

28

66

76

2CT2 568-1EA13

12/2005

4/2

SIVENT Fans for Transformer Cooling


2CT2 56, 460 V Y, 60 Hz Characteristic curves without protection grid (suction- and pressure side)

Pressure loss per protection grid PLGrid= 4.41 * (V/3600) (m/h)

80 70 6-pole 60
static pressure in Pa

50 40 8-pole 30 20 10 0 0 2000 4000 6000 8000 10000

flow rate in m/h

impeller power demand in kW

0,35 0,3 0,25 0,2 0,15 0,1 0,05 0 0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000

flow rate in m/h

Selection and Ordering Data


No. of poles in p operating current during free blow -out in A pow er consumption during free blow -out in W Volume flow during free blow -out in m/h maximum static pressure in Pa Sound pressure level in 1 m, lateral free blow -out in dB(A) A-Sound pow er level free blow -out in dB(A)

Speed in 1/min

Fan type

Motor size 80, 460 V Y, 60 Hz

6 8

1,2 0,51

550 230

1100 770

9023 6316

69 34

76 67

86 77

2CT2 566-1EA83 2CT2 568-1EA83

Motor size 71, 460 V Y, 60 Hz

12/2005

4/3

SIVENT Fans for Transformer Cooling


Dimension Drawings 2CT2 56

Rating Plate

Protection Schutzgitter Grid

560 590

610

700

12/2005

4/4

SIVENT Fans for Transformer Cooling


2CT2 63 Application Area

Fan 2CT2 63

Technical Data
Technical delivery Installation Impeller DIN 24166, accuracy class 2 Suitable for outdoor installation 1)Polypropylene (black, UV-resistant, fail-safe also with intensive solar radiation (1200 W/m2)) 2) Aluminum cast Q6,3 6,3in inacc. acc.with withISO ISO1940 1940Part Part11 Q From -20C to +50 C Sheet-steel with integrally molded inlet nozzle, hot-galvanized Suction- and pressure-side stainless steel protection grids 630 mm 8100 m/h 51Pa 8-pole Up to 0,3 kW IP55 as in DIN VDE 0470-1 F as in VDE 0530 50Hz: 220-290VD / 380-500VY/60Hz: 440-480VY Inside the motor terminal box (refer to dimension drawing) Horizontal and vertical motor shaft (blowing direction) Housing: hot-galvanized with triple coating RAL7033 105mm (cement gray) CHING coating HV43 Motor: RAL 9005 (black) After ISO 12944 C3/L Approx. 60kg 4years

Balance quality Average air flow temperature Housing Protection grid Diameter (blade wheel Volume flow (max.) Static pressure (max.) Number of poles Motor output Degree of protection Isolations class of winding Varying-voltage winding Electrical connection Installation positions Color + layer thickness

Corrosion protection Weight Maintenance period

12/2005

5/1

SIVENT Fans for Transformer Cooling


2CT2 63, 400 V Y, 50 Hz Characteristic curves without protection grid (suction- and pressure side)

Pressure loss per protection grid PLGrid= 3.92 * (V/3600) (m/h)

60
8-pole

50 static pressure in Pa

40

30

20

10

0 0 1000 2000 3000 4000 5000 6000 7000 8000 9000 flow rate in m/h
0,16 0,14 0,12 0,1 0,08 0,06 0,04 0,02 0 0 1000 2000 3000 4000 5000 6000 7000 8000 9000

impeller power demand in kW

flow rate in m/h

Selection and Ordering Data


No. of poles in p operating current during free blow -out in A pow er consumption during free blow -out in W Speed in 1/min Volume flow during free blow -out in m/h maximum static pressure in Pa Sound pressure level in 1 m, lateral free blow -out in dB(A) A-Sound pow er level free blow -out in dB(A) Fan type

Motor size 80, 400 V Y, 50 Hz

0,68

310

720

8214

51

66

76

2CT2 638-1EA13

12/2005

5/2

SIVENT Fans for Transformer Cooling


2CT2 63, 460 V Y, 60 Hz Characteristic curves without protection grid (suction- and pressure side)

Pressure loss per protection grid PLGrid= 3.92 * (V/3600) (m/h)

80
8-pole

70 60 static pressure in Pa 50 40 30 20 10 0 0 2000 4000 6000 8000 10000 flow rate in m/h
0,25

impeller power demand in kW

0,2

0,15

0,1

0,05

0 0 2000 4000 6000 8000 10000

flow rate in m/h

Selection and Ordering Data


No. of poles in p operating current during free blow -out in A pow er consumption during free blow -out in W Speed in 1/min Volume flow during free blow -out in m/h maximum static pressure in Pa Sound pressure level in 1 m, lateral free blow -out in dB(A) A-Sound pow er level free blow -out in dB(A) Fan type

Motor size 80, 460 V Y, 60 Hz

440

830

9469

68

69

79

2CT2 638-1EA83

12/2005

5/3

SIVENT Fans for Transformer Cooling


Dimension Drawings 2CT2 63

Rating Plate

Protection Grid Schutzgitter

11/2005

5/4

SIVENT Fans for Transformer Cooling


2CT2 73 Application Area

6
Fan 2CT2 73

Technical Data
Technical delivery Installation Impeller Balance quality Average air flow temperature Housing Protection grid Diameter (blade wheel Volume flow (max.) Static pressure (max.) Number of poles Motor output Degree of protection Isolations class of winding Varying-voltage winding Electrical connection Installation positions Color + layer thickness DIN 24166, accuracy class 2 Suitable for outdoor installation Aluminum cast, seawater-resistant, hot-galvanized hub Q 6,3 in acc. with ISO 1940 Part 1 From -20C to +50 C Sheet-steel with integrally molded inlet nozzle, hot-galvanized Suction- and pressure-side stainless steel protection grids 730 mm 9000-25500 m/h 40-160Pa 6/12-pole From 0.12 to 1.67 kW IP55 as in DIN VDE 0470-1 F as in VDE 0530 50Hz: 220-290VD / 380-500VY/ 60Hz: 440-480VY Inside the motor terminal box (refer to dimension drawing) Horizontal and vertical motor shaft (blowing direction) Housing: hot-galvanized with triple coating RAL7033 105mm (cement gray) CHING coating HV43 Motor: RAL 9005 (black) After ISO 12944 C3/L Approx. 67kg 4years

Corrosion protection Weight Maintenance period

11/2005

6/1

SIVENT Fans for Transformer Cooling


2CT2 73, 400 V Y, 50 Hz Characteristic curves without protection grid (suction- and pressure side)

Pressure loss per protection grid PLGrid= 0.7 * (V/3600) (m/h)

180 160 140


static pressure in Pa

35 6-pole Motor size 112

120 100 80 60 40 20 0 0 5000 10000 15000


flow rate in m/h
1,8

35 12-pole Motor size 100 30 12-pole Motor size 100 35 10-pole Motor size 100 25 12-pole Motor size 100

35 8-pole Motor size 100

20 12-pole Motor size 100

20000

25000

30000

impeller power demand in kW

1,6 1,4 1,2 1 0,8 0,6 0,4 0,2 0 0 5000 10000 15000 flow rate in m /h 20000 25000 30000

Selection and Ordering Data


operating pow er consumption current during during free blow -out free blow -out in A in W Volume flow during free blow -out in m3/h Sound pressure level A -Sound pow er level in 2 m, free blow -out free blow -out (free-blow ing) in dB(A) in dB(A)

No. of poles in p

Blade angle

Speed in 1/min

maximum static pressure in Pa

Fan type

Motor size 112, 400 V Y, 50 Hz

6 8 10 12 12 12 12

35 35 35 35 30 25 20

4,3 2,3 2,9 1,5 1,5 1,5 1,4

2140 1100 780 410 350 320 290

950 710 580 470 480 480 490

25433 19007 15527 12583 11702 10477 9398

157 88 59 39 42 42 43

71 65 61 54 53 53 52

87 81 77 70 69 69 68

2CT2 736-5EA13 2CT2 738-5EA13 2CT2 733-5EA13 2CT2 735-5EA13 2CT2 735-4EA13 2CT2 735-3EA13 2CT2 735-2EA13

Motor size 100, 400 V Y, 50 Hz

12/2005

6/2

SIVENT Fans for Transformer Cooling


2CT2 73, 460 V Y, 60 Hz Characteristic curves without protection grid (suction- and pressure side)

Pressure loss per protection grid PLGrid= 0.7 * (V/3600) (m/h)

70 25 12-pole 30 12-pole Motor size 100 Motor size 100 35 12-pole Motor size 100 50
static pressure in Pa

60

20 12-pole Motor size 100

40

30

20

10

0 0 2000 4000 6000 8000 10000 12000 14000 16000

flow rate in m/h


0,4 impeller power demand in kW 0,35 0,3 0,25 0,2 0,15 0,1 0,05 0 0 2000 4000 6000 8000 10000 12000 14000 16000 flow rate in m /h

Selection and Ordering Data


operating pow er consumption current during during free blow -out free blow -out in A in W Volume flow during free blow -out in m/h Sound pressure level A-Sound pow er level in 2 m, free blow -out free blow -out in dB(A) in dB(A)

No. of poles in p

Blade angle

Speed in 1/min

maximum static pressure in Pa

Fan type

Motor size 100, 460 V Y, 60 Hz

12 12 12 12

20 25 30 35

1,5 1,5 1,6 1,7

440 510 600 700

580 570 565 560

11124 12441 13773 14992

60 59 58 54

57 57 58 59

73 73 74 75

2CT2 735-2EA83 2CT2 735-3EA83 2CT2 735-4EA83 2CT2 735-5EA83

12/2005

6/3

SIVENT Fans for Transformer Cooling


Dimension Drawings 2CT2 73

Frderrichtung

Air Flow Direction Drehrichtung Rotation

12/2005

6/4

SIVENT Fans for Transformer Cooling


2CT2 80 Application Area

Fan 2CT2 80

7
DIN 24166, accuracy class 2 Suitable for outdoor installation Aluminum cast, seawater-resistant, hot-galvanized hub Q 6,3 in acc. with ISO 1940 Part 1 From -20C to +50 C Sheet-steel with integrally molded inlet nozzle, hot-galvanized Suction- and pressure-side stainless steel protection grids 800 mm 15000-24000 m/h 40-100Pa 8/10/12-pole From 0.29 to 1.11 kW IP55 as in DIN VDE 0470-1 F as in VDE 0530 50Hz: 220-290VD / 380-500VY/ 60Hz: 440-480VY Inside the motor terminal box (refer to dimension drawing) Horizontal and vertical motor shaft (blowing direction) Housing: hot-galvanized with triple coating RAL7033 105mm (cement gray) CHING coating HV43 Motor: RAL 9005 (black) After ISO 12944 C3/L Approx. 76kg 4years

Technical Data
Technical delivery Installation Impeller Balance quality Average air flow temperature Housing Protection grid Diameter (blade wheel Volume flow (max.) Static pressure (max.) Number of poles Motor output Degree of protection Isolations class of winding Varying-voltage winding Electrical connection Installation positions Color + layer thickness

Corrosion protection Weight Maintenance period

12/2005

7/1

SIVENT Fans for Transformer Cooling


2CT2 80, 400 V Y, 50 Hz Characteristic curves without protection grid (suction- and pressure side)

Pressure loss per protection grid PLGrid= 0.48 * (V/3600) (m/h)

120

100 35 8-pole
30 8-pole

static pressure in Pa

80
30 10-pole 20 10-pole

35 10-pole

60

40

35 12-pole

20

0 0
1,4 1,2 1 0,8 0,6 0,4 0,2 0 0 5000 10000 15000 20000 25000 30000

5000

10000

15000 20000 flow rate in m/h

25000

30000

impeller power demand in kW

flow rate in m/h

Selection and Ordering Data

No. of poles in p

Blade angle

operating current during free blow -out in A

pow er consumption during free blow -out in W

Speed in 1/min

Volume flow during free blow -out in m/h

maximum static pressure in Pa

Sound pressure level A -Sound pow er level in 2 m, free blow -out free blow -out in dB(A) in dB(A)

Fan type

Motor size 112, 400 V Y, 50 Hz

8 8 10 10 10 12

35 30 35 30 20 35

3,2 2,6 3,0 2,7 2,7 1,7

1500 1300 1100 900 690 565

720 720 580 580 580 460

23834 21605 19200 17404 13648 15224

95 98 62 64 65 39

67 66 62 61 60 56

83 82 78 77 76 72

2CT2 808-5EA13 2CT2 808-4EA13 2CT2 803-5EA13 2CT2 803-4EA13 2CT2 803-2EA13 2CT2 805-5EA13

Motor size 100, 400 V Y, 50 Hz

12/2005

7/2

SIVENT Fans for Transformer Cooling


2CT2 80, 460 V Y, 60 Hz Characteristic curves without protection grid (suction- and pressure side)

Pressure loss per protection grid PLGrid= 0.48 * (V/3600) (m/h)

140 30 8-pole 120 30 10-pole 100 static pressure in Pa 20 10-pole 80 35 10-pole

60 35 12-pole 40

20

0 0 5000 10000 15000 flow rate in m/h 20000 25000 30000

1,6

impeller power demand in kW

1,4 1,2 1 0,8 0,6 0,4 0,2 0 0 5000 10000 15000 20000 25000 30000

flow rate in m/h

Selection and Ordering Data


operating current during free blow -out in A pow er consumption during free blow -out in W Volume flow during free blow -out in m/h maximum static pressure in Pa Sound pressure level A-Sound pow er level in 2 m, free blow -out free blow -out in dB(A) in dB(A)

No. of poles in p

Blade angle

Speed in 1/min

Fan type

Motor size 112, 460 V Y, 60 Hz

8 10 10 10 12

30 35 30 20 35

3,85 3,3 3,3 2,7 1,8

2000 1530 1240 950 820

840 700 700 700 520

25206 23171 21005 16472 17213

133 90 93 95 50

70 66 65 64 59

86 82 81 80 75

2CT2 808-5EA83 2CT2 803-5EA83 2CT2 803-4EA83 2CT2 803-2EA83 2CT2 805-5EA83

Motor size 100, 460 V Y, 60 Hz

12/2005

7/2

SIVENT Fans for Transformer Cooling


Dimension Drawings 2CT2 80

12/2005

7/4

SIVENT Fans for Transformer Cooling


2CT2 10 Application Area

Fan 2CT2 10

Technical Data
Technical delivery Installation Impeller Balance quality Average air flow temperature Housing Protection grid Diameter (blade wheel Volume flow (max.) Static pressure (max.) Number of poles Motor output Degree of protection Isolations class of winding Varying-voltage winding Electrical connection Installation positions Color + layer thickness DIN 24166, accuracy class 2 Suitable for outdoor installation Aluminum cast, seawater-resistant, hot-galvanized hub Q 6,3 in acc. with ISO 1940 Part 1 From -20 to +50 c C From -20C to +50 Sheet-steel with integrally molded inlet nozzle, hot-galvanized Suction- and pressure-side stainless steel protection grids 1000mm 28000-51000 m/h 95-175 Pa 8/10/12-pole From 0.65 to 2.75kW IP55 as in DIN VDE 0470-1 F as in VDE 0530 50Hz: 220-290VD / 380-500VY/ 60Hz: 440-480VY Inside the motor terminal box (refer to dimension drawing) Horizontal and vertical motor shaft (blowing direction) Housing: hot-galvanized with triple coating RAL7033 105mm (cement gray) CHING coating HV43 Motor: RAL 9005 (black) After ISO 12944 C3/L Approx. 130kg 4years

Corrosion protection Weight Maintenance period

12/2005

8/1

SIVENT Fans for Transformer Cooling


2CT2 10, 400 V Y, 50 Hz Characteristic curves without protection grid (suction- and pressure side)

Pressure loss per protection grid PLGrid= 0.36 * (V/3600) (m/h)

200 180
21 8-pole

27 8-pole

160
15 8-pole

140 static pressure in Pa 120 100 80


27 12-pole

27 10-pole 15 10-pole

60 40

20 0 0 10000 20000 30000 40000 flow rate in m/h 50000 60000

3,000 impeller power demand in kW 2,500 2,000 1,500 1,000 0,500 0,000 0 10000 20000 30000 flow rate in m/h 40000 50000 60000

Selection and Ordering Data

No. of poles in p

Blade angle

operating current during free blow -out in A

pow er consumption during free blow -out in W

Speed in 1/min

Volume flow during free blow -out in m/h

maximum static pressure in Pa

Sound pressure level in 2 m, free blow -out in dB(A)

A-Sound pow er level free blow -out in dB(A)

Fan type

Motor size 132, 400 V Y, 50 Hz

8 8 8 10 10 12

27 21 15 27 15 27

7,4 6,5 5,6 4,7 3,7 2,80

3500 2940 2990 2000 1500 1300

725 725 725 575 575 450

51022 43350 35860 40462 28440 31667

174 160 153 110 100 67

79 79 79 74 74 67

95 95 95 90 90 83

2CT2 108-3EB13 2CT2 108-2EB13 2CT2 108-1EB13 2CT2 103-3EB13 2CT2 103-1EB13 2CT2 105-3EB13

12/2005

8/2

SIVENT Fans for Transformer Cooling


2CT2 10, 460 V Y, 60 Hz Characteristic curves without protection grid (suction- and pressure side)

Pressure loss per protection grid PLGrid= 0.36 * (V/3600) (m/h)

180
27 10-pole

160
15 10-pole

140 120 100


27 12-pole

static pressure in Pa

80 60 40 20 0 0 10000 20000 30000 40000 flow rate in m/h 50000 60000

2,500 impeller power demand in kW 2,000 1,500 1,000 0,500 0,000 0 10000 20000 30000 flow rate in m/h 40000 50000 60000

Selection and Ordering Data

No. of poles in p

Blade angle

operating current during free blow -out in A

pow er consumption during free blow -out in W

Speed in 1/min

Volume flow during free blow -out in m/h

maximum static pressure in Pa

Sound pressure level in 2 m, free blow -out in dB(A)

A-Sound pow er level free blow -out in dB(A)

Fan type

Motor size 132, 460 V Y, 60 Hz

10 10 12

27 15 27

6,5 4,7 4,2

3457 2578 2600

690 690 565

48556 34128 39760

158 138 102

78 78 73

94 94 89

2CT2 103-3EB83 2CT2 103-1EB83 2CT2 105-3EB83

12/2005

8/3

SIVENT Fans for Transformer Cooling


Dimension Drawings 2CT2 10

12/2005

8/4

Annex
Ordering Notes Ordering Information
General information Our logistics service offers quality from ordering, down to delivery in terms of delivery service, communications and environmental protection. For this purpose, we rely on an optimization of logistical procedures on the basis of a customer-oriented infrastructure and DP-based order processing. Personal support, deliveries on schedule and transportation throughout Germany are our top priorities. Furthermore, the DIN-ISO-9001 certification as well as consistent quality assurance form indispensable prerequisites. Our DP-based order processing system is fast, cost-favorable and fault-free. If you want to benefit from these advantages, please contact us. Packings, packing units Our device and shipping packings offer protection against dust and mechanical damage during transportation and thus assure our devices impeccable delivery condition. The selection and design of our packings are based on aspects of environmental compatibility, reusability (e.g. crumpled paper instead of styrofoam chips as transportation protection in shipping packings up to 32 kg) and, particularly, waste minimization. With our multipackings and reusable packings, we offer you differentiated packing types, which are both environmentally compatible and customized to your needs. Your advantages at a glance: Reduced ordering expenditures Cost reductions thanks to sorted packings: low or no disposal costs Time and personnel savings thanks to reduced unpacking times On-schedule just in time deliveries directly to the assembly line facilitate stock reduction: cost savings thanks to reduced storage areas Fast assembly thanks to set delivery Standardized Euronorm boxes, module-compliant with Europallets, are suitable for most conveyor systems Active contribution to environmental protection Unless stated otherwise in the selection and ordering data of this catalog, our devices are delivered in individual single packings. For small parts/accessories, we offer cost-favorable packing units as standard packings, which contain more than one device, e.g. 5, 10, 50 or 100 items. It is imperative to order whole-numbered multiples of these quantities to assure an impeccable quality of the devices and a smooth order execution. The devices are delivered in a neutral white cardboard box. A label states warning notes, the CE mark as well as the open recycling arrow symbol and device descriptions in German and English. In addition to the order number (MLFB) and the packing quantity, also the order number of the operating instructions (Instr. Order No.), which you can order from your local Siemens branch (for Siemens contact partners, visit: http://www.siemens.de/automation/partner), is stated. Furthermore, the device order numbers are scannable for most devices via the EAN barcode for simplified order and storage logistics. Multipackings and reusable packings Set delivery (reusable, not sorted) An order-related, non-sorted delivery of larger quantities of unpacked devices in ENBs can be ordered upon agreement. For the stipulation of delivery modalities or set deliveries and further forms of delivery in ENBs/RTCs, such as container deliveries or return deliveries, please contact your local Siemens branch (for Siemens contact partners, visit: http://www.siemens.de/automation/partner), which will conclude a respective agreement with you. ENB = Euronorm box RTC = Reusable transport containers

Orders of special versions When ordering products which deviate from the catalog-listed designs, the order number stated in the catalog must be supplemented by Z; the desired characteristics are to be additionally stated in the form of alphanumeric short specifications or in plain text.

Minimum quantity orders With minimum orders, the costs for order processing exceed the order value. For such cases, we recommend to combine your demands to a larger order. Should this not be possible, we ask for your understanding that we have to charge a processing surcharge of 20.-- for orders with a net product value of less than 250.-- for a proportional coverage of our order processing and invoicing costs.

12/2005

9/1

Annex
Conditions of Sale and Delivery
Conditions of sale and delivery Via this catalog, you can purchase the products described herein (hardware and software) from the Siemens Aktiengesellschaft in accordance with the conditions stipulated below. Please observe that the scope, quality and conditions for deliveries and services, including software, supplied by Siemens branches/regional subsidiaries with their corporate domicile outside Germany shall exclusively be subject to the corresponding general terms and conditions of the respective Siemens branches/regional subsidiaries with their corporate domicile outside Germany. The following conditions shall exclusively apply to orders placed with the Siemens Aktiengesellschaft. For customers having their domicile in Germany The general conditions of payment as well as the general conditions of delivery for products and services of the electrical industry shall apply. The general conditions for the surrender of software for automation and drive technology to licensees having their domicile in Germany shall apply to software products. For customers having their domicile outside Germany The general conditions of payment as well as the general conditions of delivery of Siemens, Automation and Drives, for customers having their domicile outside Germany shall apply. The general conditions for the surrender of software products for Automation and Drives to licensees having their domicile outside Germany shall apply to software products. ECCN Export regulations The products listed in this catalog/this price list may be subject to European and/or US export regulations. Therefore, all exports subject to authorization require approval by the responsible authorities. For the products listed in this catalog/this price list, the following export regulations are to be observed in accordance with the currently applicable regulations: AL Number of the German export list Products with identification other than N are subject to export authorization. With software products, generally also the export identifications of the respective data carriers must be observed. Products identified with AL unequal N are subject to a European or German export authorization for exports outside the EU. Number of the US export list (Export Control Classification Number). Products with identification other than N are subject to a re-export authorization to certain countries. With software products, generally also the export identifications of the respective data carriers must be observed. Products identified with ECCN unequal N are subject to a US re-export authorization. An authorization obligation may also be given for products without identification or with identification AL: N or ECCN: N, amongst others, by the products final destination or intended purpose. The export identification codes AL and ECCN stated on the order confirmations, delivery notes and invoices shall be authoritative. Subject to changes and errors.

General information Prices are valid in (Euro) ex place of delivery, excluding packing. The turnover tax (value added tax) is not included in the prices. Its respectively valid rate will be charged separately in accordance with the legal regulations. The prices for products containing silver and/or copper may be subject to surcharges if the respective quotation limit values are exceeded. We reserve price changes and will charge the prices respectively valid at the time of delivery. Dimensions are stated in mm, illustrations are non-binding. Unless stated otherwise on individual pages of this catalog/this price list, all data, particularly the stated values, dimensions and weights, are subject to changes. You can obtain the detailed terms and conditions of the Siemens AG free of charge from your local Siemens branch via order number: 6ZB5310-0KR30-0BA0 Terms and conditions for customers having their domicile in the Federal Republic of Germany 6ZB5310-0KS53-0BA0 Terms and conditions for customers having their domicile outside the Federal Republic of Germany These documents can also be downloaded from the A&D Mall at: http://www.siemens.de/automation/mall (Germany: A&D Mall online help system)

12/2005

9/2

12/2005

The information contained in this product brochure includes descriptions or performance characteristics which may not always comply with the described form in specific application cases or which may be subject to change due to an advancement of the products. The desired performance characteristics shall only be binding if they are expressly agreed upon within the scope of contractual conclusion. Subject to delivery options and technical changes.

Siemens Aktiengesellschaft Automation and Drives Low-Voltage Controls and Distribution P.O. Box 4848 90327 NUREMBERG FEDERAL REPUBLIC OF GERMANY www.siemens.com/lowvoltage

Technical delivery Installation Impeller Balance quality Average air flow temperature Housing Protection grid Diameter (blade wheel Volume flow (max.) Static pressure (max.) Number of poles Motor output Degree of protection Isolations class of winding Varying-voltage winding Electrical connection Installation positions Color + layer thickness

DIN 24166, accuracy class 2 Suitable for outdoor installation Aluminum cast, seawater-resistant, hot-galvanized hub Q 6,3 in acc. with ISO 1940 Part 1 From -20C to +50 C Sheet-steel with integrally molded inlet nozzle Suction- and pressure-side stainless steel protection grids 1000mm 28000-51000 m/h 95-175 Pa 8/10/12-pole From 0.65 to 2.75kW IP55 as in DIN VDE 0470-1 F as in VDE 0530 50 Hz: 220-290VD / 380-500VY Inside the motor terminal box (refer to dimension drawing) Horizontal and vertical motor shaft (blowing direction) Housing: hot-galvanized with triple coating RAL7033 105mm (cement gray) CHING coating HV43 Motor: RAL 9005 (black) After ISO 12944 C3/L Approx. 130kg 4years

Corrosion protection Weight Maintenance period

You might also like