POWEROIL TO 1020 - 60 U is an Uninhibited Transformer Oil meeting IEC 60296 - 2012 – 02 Edition 4.0 Standard
Table – 2 - General Specifications. It also meets the ASTM D 1275 B Test requirement for Corrosive Sulphur.

Sr No Characteristics Unit Test Method Guaranteed Data

Min Max
1 Appearance Visual inspection of oil Clear free from sediment
sample in transmitted light and suspended matter
under a thickness of 10 cm
at ambient temperature
o
2 Density at 20 C g /ml ISO 3675 or IEC 12185 0.895
o 2
3 Kinematic Viscosity at 40 C mm / sec ISO 3104 12
o
at - 30 C 1800
o
4 Flash Point, PMCC C ISO 2719 135
o
5 Pour Point C ISO 3016 - 40
o
6 Inter Facial Tension at 25 C mN / m EN 14210 or ASTM D 971 No General Requirement
( Where it is used as
general requirement ) 40 min
7 Acidity mg KOH/ gm IEC 62021-1or IEC 62021-2 0.01
8 Water Content,Bulk/ Drum,IBC mg / kg IEC 60814 30 / 40
9 Breakdown Voltage IEC 60156
As Delivered / After Treatment kV 30 / 70
10 Dielectric Dissipation Factor IEC 60247 or IEC 61620 0.005
(Tan δ )at 90 C & 40 to 60 Hz
o

11 Corrosive Sulphur
o
Silver Strip, 100 C, 18 Hrs DIN 51353 Not Corrosive
o
Copper Strip , 150 C, 48 Hrs ASTM D 1275 B Not Corrosive
12 Potentially Corrosive Sulphur IEC 62535 Not Corrosive
13 DBDS mg / kg IEC 62697-1(in preparation) Not Detectable (< 5 mg/kg )
14 Total Sulphur Content % IP 373 or ISO 14596 No General Requirement
15 Inhibitors of IEC 60666 % IEC 60666 ( U ) Uninhibited Oil
( Anti Oxidant additives ) Not Detectable (< 0.01 % )
16 Metal Passivator additives of mg / kg IEC 60666 Not Detectable (< 5 mg/kg )
IEC 60666
17 Other Additives Does not contain
any additives
18 Oxidation Stability at IEC 61125 Method C
o
120 C, 164 Hrs
Total Acidity mg KOH /gm 1.9.4 of IEC 61125 : 1992 1.2
Sludge % 1.9.1 of IEC 61125 : 1992 0.8
o
DDF at 90 C 1.9.6 of IEC 61125 0.500
Amendment 1 ( 2004 ) +
IEC 60247
19 Gassing Tendency μ L / min IEC 60628 : 1985 Method A No General Requirement
20 PCA Content % IP 346 3
21 PCB Content mg / kg IEC 61619 Not Detectable ( < 2mg /kg)
22 2 – Furfural and related mg / kg IEC 61198 Not Detectable
compounds content (< 0.05 mg/kg ) for each
individual compound
23 Stray Gassing See 6.22 of IEC 60296 No General Requirement
24 ECT See 6.14 of IEC 60296 No General Requirement
25 Particle Content IEC 60970 No General Requirement

(Version # 6 January , 2018)

Disclaimer: APAR makes no warrantees, representation or conditions of any kind expressed or implied for use with respect to these products. Final determination of suitability
of the products for the application contemplated by the user is solely their responsibility.
Apar Industries Ltd., Apar House, Corporate Park, Sion-Trombay Road, Chembur, Mumbai – 400 071. Product Data Sheet
Tel: 91-22-2526 3400 / 6780 0400 | Fax: 91-22-2524 6326 | website: www.apar.com