Regal Furnace Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 44

Oil Fired Furnace

Installation and Operation Instruction Manual

Keep these instructions with the furnace at all times for future reference
Boyertown Furnace Co. PO Box 100 Boyertown, PA 19512 610-369-1450
www.boyertownfurnace.com
6/1/05

Be Aware of Hazard Definitions


Danger Warning Caution Notice Denotes presence of a hazard which, if ignored, will result in severe personal injury, death or property damage Denotes presence of a hazard which, if ignored could result in severe personal injury, death or substantial property damage. Denotes the presence of a hazard, which if ignored, could result in minor personal injury or property damage Intended to bring attention to information, but not related to personal injury or property damage.

Danger This equipment must be installed, adjusted and started only by a qualified service agency an individual or agency, licensed and experienced with all codes and ordinances, and who is responsible for the installation and adjustment of the equipment. The installation must comply with all local codes and ordinances and with the latest revision of the National Fire Protection Standard for Oil Burning Equipment, NFPA 31. Read all instructions before proceeding. Follow all instructions completely. Failure to follow these instructions could result in equipment malfunction causing severe personal injury, death or substantial Warning property damage. Do not alter this furnace in any way. The manufacturer will not be liable for any damage resulting from changes made in the field to the furnace or its components or from improper installation. Failure to comply could result in severe personal injury, death, or substantial property damage. Your oil fired furnace is designed to burn No. 1 and No. 2 heating oil only. Never use gasoline or a mixture of gasoline and oil. Do not store gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. The area around the furnace should be kept free and clear of combustible materials. Never burn garbage or refuse in your furnace. Never try to ignite oil by tossing burning papers or other material into your furnace. Do not attempt to start the burner when excess oil has accumulated or the furnace is full of vapors. Do not use the furnace as a construction heater. Do not operate furnace if the heat exchanger is damaged. Toxic flue products could enter air stream. Do not jumper, attempt to bypass or override any of the safety limit controls. Do not use this furnace if any part has been under water. Immediately call a qualified service technician to inspect the furnace and replace any part of the furnace, control system or burner that has been under water. Do not operate furnace if temperature rise through the heat exchanger exceeds that which is listed on the Ratings Label (Typically75F). Do not operate furnace without return air properly sized or ducted. NOTICE Concealed Damage- If you discover damage to the burner, furnace or controls during unpacking, notify the carrier at once and file the appropriate claim. When calling or writing about the furnace please have the following information available: the furnace model number and serial number which is located on the upper portion of the front of the unit. Record the model and serial number for future reference in the space provided in this manual. 2

TABLE OF CONTENTS
Page No. Furnace Specifications ..4 Installation Clearances ..6
Standard Clearances Reduced Clearances

Duct Work ..9


Sizing Blower Specifications Filter Racks Multiple Furnace Installation

Venting ...12
Chimney Venting Chimney Relining Chimney Connector Power Venting Vent Dampers

Ventilation and Combustion Air .....15 Burner Installation ...16 Wiring ....18
Power Thermostat

Oil Tank and Piping .....24 Start Up ..25


Start Up Equipment Burner Adjustments

Operating and Maintenance 27


Cleaning the Furnace Oil Burner Blowers Belt Drive Blowers Direct Drive Vent System Fuel Oil System Filters

Parts Breakdown Lists ...30 Trouble Shooting Guide. .39 Warranty ..41 Installation and Service Check List ...42 Warranty Registration .43

4
LB115 LBD115 LB145 LBD160 HB85 105,000 86,000 0.65 80 A 0.65 80 A 0.85 80 A 0.85 80 A 1.10 80 B 1.10 80 B 1.00 80 B 0.75 80 A 1.00 80 B 0.65 80 A 86,000 114,000 114,000 155,000 155,000 145,000 112,000 145,000 84,000 105,000 140,000 140,000 189,000 189,000 175,000 140,000 175,000 105,000 175,000 140,000 0.90 80 A HBD115 HBD160 189,000 157,000 1.10 80 B 175,000 145,000 1.00 80 B 1.00 80 B 1.10 80 B 145,000 157,000 175,000 189,000 HB115 HB160 HSD140 140,000 115,000 0.85 80 A LBD145 LB160 HBD85 HBD145 HSD112 140,000 115,000 0.85 80 A HB145 HSD84 0.85 70 B 0.85 70 B 1.00 70 B 0.85 70 B 1.00 70 B 8" 83.9% 20x25 20x25 20x25 20x25 83.9% 82.9% 82.9% 78.8% 20x20 8" 8" 8" 6" 1.10 70 B 6" 79.3% 20x20 8" 78.5% 20x25 6" 80.7% 20x20 8" 8" 83.2% 1-16x20 1-20x20 1-20x20 1-20x20 1-16x20 1-16x20 16x20 20x20 16x20 82.9% 82.9% 81.4% 80.7% 81.4% 8" 6" 83.2% 1-16x20 1-20x20 8" 6" 6" 0.85 70 B 1.10 70 B 6" 80.0% 20x20 1.00 70 B 1.10 70 B 1.10 70 B 0.65 70 W 0.65 70 W 1.00 70 B 6" 80.0% 20x20 6" 82.6% 16x20 1/2 Hp 3/4 Hp 4sp 3/4 Hp 1 Hp 3spd 3/4 Hp 3-1/2" 1-1/2 42" 1711 1925 2119 1586 1433 N/R -----1605 -----1491 N/R N/R -----400 4 400 -----450 N/R 5 450 -----450 N/R 5 450 1969 2044 1896 -----1969 2044 1896 2251 42" 1925 2251 2119 1339 1292 1242 1177 1126 1104 1069 1020 2 1/2 225 1850 1723 1629 1438 1670 1547 1452 N/R 4 320 1761 4 1/2 375 1893 1982 1881 2176 2018 1-1/2 3-1/2" 3-1/2" 3-1/2" 2-1/2 39" 2150 1151 1402 1323 1875 -----2003 1862 1126 N/R -----5 -----350 350 485 485 485 485 -----5 3 N/R 1084 1862 1205 -----1700 2003 1292 1875 1273 2017 1484 1418 37" 3 3-1/2" 2 37" 2150 2017 1969 1 Hp 3spd 1/3 Hp 3/4 Hp 4sp 3-1/2" 2 37" 1713 1969 1598 1452 N/R -----1615 1498 N/R N/R -----4 435 435 1/2 Hp 3/4 Hp 3/4 Hp 3/4 Hp 4sp 1 Hp 3spd 3-1/2" 1-1/2 39" 1350 1305 1268 1215 1215 1175 1142 1082 3 385 1400 1 Hp 3spd 3/4 Hp 4sp 3/4 Hp 4sp 3 42 45 55 23 23 22 48 1/2 11 1/2 10 20 21 15 18 7/8 21 15 18 7/8 22 48 1/2 11 1/2 10 20 24 53 37 1/2 12 10 27 5/8 22 22 21 1/2 21 1/2 22 22 21 1/2 22 22 27 5/8 27 5/8 10 10 12 12 37 1/2 37 1/2 53 53 24 24 23 24 42 38 1/2 12 10 20 22 22 18 1/8 18 1/8 21 1/2 22 22 22 22 20 27 5/8 10 10 12 12 38 1/2 37 1/2 42 53 38 35 1/2 11 1/2 10 20 21 21 14 1/8 24 24 45 45 45 45 45 55 60 24 22 53 1/2 12 10 20 22 18 7/8 18 7/8 60 24 22 53 1/2 12 10 20 22 18 7/8 18 7/8 60 24 29 5/8 52 1/2 12 10 27 5/8 22 18 7/8 23 7/8 60 24 29 5/8 52 1/2 12 10 27 5/8 22 18 7/8 23 7/8 60 24 29 5/8 52 1/2 12 10 27 5/8 22 18 7/8 23 7/8 60 24 29 5/8 52 1/2 12 10 27 5/8 22 18 7/8 23 7/8 20 1/2 55 20 1/8 10 1/4 8 1/2 8 1/2 18 1/8 18 1/2 18 7/8 18 7/8 20 1/2 67 24 10 1/4 8 1/2 8 1/2 22 18 1/2 18 7/8 18 7/8 25 1/2 69 24 12 3/4 8 3/4 8 1/2 22 23 1/2 23 7/8 18 7/8

Hallmark Specifications CF85 105,000 86,000 0.65 80 A 0.65 60 W 0.65 70 W 6" 83.0% 2-14x20

Model

LB85

LBD85

BTU/Hr Input

105,000

105,000

BTU/Hr Output

88,000

88,000

Nozzle Beckett AFG @140PSI

0.65 80 A

0.65 80 A

Nozzle Riello 40 Series @ 160 PSI 0.65 60 W 0.65 60 W 0.85 60 W 0.85 60 W 1.00 60 W 1.00 60 W 1.10 60 W 1.10 60 W 0.65 60 W 0.65 60 W 0.85 60 W 0.85 60 W 1.00 60 W 1.00 60 W 1.10 60 W 1.10 60 W

Nozzle Carlin EZ-1 @ 140 PSI

0.65 70 W 0.65 70 W

Flue Size

6"

AFUE Seasonal Efficiency

82.6%

Filter Size (inches)

16x20

Blower Size

100-10BD 100-10DD 110-10BD 110-10DD 120-12BD 120-12DD 120-12BD 120-12DD 100-10BD 100-10DD 100-10BD 110-10DD 120-12BD 120-12DD 120-12BD 120-12DD 100-10DD 110-10DD 110-10DD 100-10DD 1 Hp 3sp 3/4 Hp 4sp

Blower Motor

1/3 Hp

3/4 Hp 4sp

Motor Pulley

3-1/2"

Turns on Motor Pulley

2-1/2

Belt Length

36"

CFM @ 0.2"WC

1105

1400 1328 1265 1203 1210 1123 N/R N/R

MED HI

MED LOW

LOW

CFM @ 0.5"WC

------

MED HI

MED LOW

LOW

Cooling Capacity (Tons)

------

Shipping Weight (lbs)

385

350

Dimensions (Inches) 57 23 22 32 1/2 10 10 20 20 3/4 21 20

Cabinet Height

42

Cabinet Width

23

Cabinet Depth

38

Center Line Flue to Floor

35 1/2

Center Line Flue to Side

11 1/2

Depth of Burner Housing

10

Warm Air Supply Depth

20

Warm Air Supply Width

Ho

21

Return Air Width

Hr

21

Return Air Depth

14 1/8

R e g a l S p e c ific a tio n s M odel R EH 1000 R EL 1000 REH 750 R EL750 1 7 5 ,0 0 0 8 5 ,0 0 0 B T U /H r In p u t 1 7 5 ,0 0 0 1 4 0 ,0 0 0 1 2 0 ,0 0 0 1 4 0 ,0 0 0 1 2 0 ,0 0 0 1 0 5 ,0 0 0 8 5 ,0 0 0 1 0 5 ,0 0 7 0 ,0 0 0 1 4 0 ,0 0 0 7 0 ,0 0 0 B T U /H r O u tp u t 1 4 0 ,0 0 0 1 1 5 ,0 0 0 9 5 ,0 0 0 1 1 5 ,0 0 0 9 5 ,0 0 0 8 5 ,0 0 0 8 5 ,0 0 0 .6 0 8 0 A 1 .2 5 8 0 B .6 0 8 0 A N o z z le B e c k e tt A F G @ 1 0 0 P S I 1 .2 5 8 0 B 1 .0 0 8 0 B .8 5 8 0 B 1 .0 0 8 0 B .8 5 8 0 B .7 5 8 0 B .7 5 8 0 B .5 0 6 0 A 1 .0 0 8 0 B N o z z le R ie llo 4 0 S e r ie s @ 1 5 0 P S .5 0 6 0 A 1 .0 0 8 0 B .8 5 8 0 B .6 5 6 0 A .8 5 8 0 B .6 5 6 0 A .6 0 6 0 A .6 0 6 0 A .6 0 7 0 A N o z z le C a r lin E Z - 1 @ 1 0 0 P S I .6 0 7 0 A 1 .0 0 6 0 S S 1 .2 5 6 0 S S .8 5 7 0 A 1 .0 0 6 0 S S 1 .2 5 6 0 S S .8 5 7 0 A .7 5 7 0 A .7 5 7 0 A 6" F lu e S iz e 6" 6" 6" 6" 6" 6" 6" 6" 6" 8 5 .9 % A F U E S e a s o n a l E ffic ie n c y 8 2 .3 % 8 5 .9 % 8 4 .2 % 8 5 .0 % 8 5 .0 % 8 5 .0 % 8 5 .0 % 8 5 .4 % 8 4 .4 % 16x25 F ilte r S iz e ( in c h e s ) 16x25 (2 )1 6 x 2 0 (2 )1 6 x 2 0 16x25 16x25 (2 )1 6 x 2 0 (2 )1 6 x 2 0 16x25 (2 )1 6 x 2 0 1 0 0 -1 0 T 1 0 0 -1 0 T B lo w e r S iz e 1 0 0 -1 0 T 1 0 0 -1 0 T 1 0 0 -1 0 T 1 0 0 -1 0 T 1 0 0 -1 0 T 1 0 0 -1 0 T 1 0 0 -1 0 T 1 0 0 -1 0 T B lo w e r M o to r 3 /4 H p 4 s p 3 /4 H p 4 s p 3 /4 H p 4 s p 3 /4 H p 4 s p 3 /4 H p 4 s p 3 /4 H p 4 s p 3 /4 H p 4 s p 3 /4 H p 4 s p 3 /4 H p 4 s p 3 /4 H p 4 s p 1903 H ig h 1745 C F M @ 0 .2 " W C 2283 1903 2466 2283 1745 2466 1903 1745 M e d H ig h 1711 1550 2130 1711 2150 2130 1550 2150 1711 1550 M ed Low 1547 1376 1901 1547 1839 1901 1376 1839 1547 1376 Low 1399 1250 N /R 1399 N /R 1717 1250 1600 1399 1250 H ig h C F M @ 0 .5 " W C 1661 1480 2007 1661 2072 2007 1480 2072 1661 1480 M e d H ig h 1485 1343 1832 1485 1859 1832 1343 1859 1485 1343 M ed Low 1355 1175 N /R 1355 N /R 1644 N /R 1610 1355 1175 Low 1227 1043 N /R 1227 N /R 1501 N /R N /R N /R N /R C o o lin g C a p a c ity ( T o n s ) 4 3 1 /2 5 4 5 5 3 1 /2 5 4 3 1 /2 S h ip p in g W e ig h t ( lb s ) 323 298 347 323 362 347 298 362 323 298 D im e n s io n s ( In c h e s ) C a b in e t H e ig h t A 40 5 3 5 /8 5 6 1 /2 40 46 5 6 1 /2 5 3 5 /8 46 40 5 3 5 /8 C a b in e t W id th B 2 0 1 /4 2 2 1 /4 2 5 1 /2 2 0 1 /4 2 5 1 /8 2 5 1 /2 2 2 1 /4 2 5 1 /8 2 0 1 /4 2 2 1 /4 C a b in e t D e p th C 4 7 1 /2 3 3 1 /8 38 4 7 1 /2 5 3 5 /8 38 3 3 1 /8 5 3 5 /8 4 7 1 /2 3 3 1 /8 C e n te r L in e F lu e to F lo o r D 3 1 1 /4 4 9 1 /8 5 2 5 /8 3 1 1 /4 3 8 1 /2 5 2 5 /8 4 9 1 /8 3 8 1 /2 3 1 1 /4 4 9 1 /8 C e n te r L in e F lu e to S id e E 1 0 1 /8 1 1 1 /8 1 2 3 /4 1 0 1 /8 2 1 1 /2 1 2 3 /4 1 1 1 /8 1 2 1 /2 1 0 1 /8 1 1 1 /8 W a r m A ir S u p p ly D e p th G 1 7 1 /2 1 9 3 /4 2 3 3 /8 1 7 1 /2 2 1 1 /2 2 3 3 /8 1 9 3 /4 2 1 1 /2 1 7 1 /2 1 9 3 /4 H o 1 8 1 /4 W a r m A ir S u p p ly W id th 1 8 1 /4 2 0 1 /2 2 3 3 /4 2 2 7 /8 2 3 3 /4 2 0 1 /2 2 2 7 /8 1 8 1 /4 2 0 1 /2 R e tu r n A ir W id th Hr 1 8 1 /4 15 15 1 8 1 /4 2 2 7 /8 15 15 2 2 7 /8 1 8 1 /4 15 R e tu r n A ir D e p th J 14 2 3 5 /8 2 3 5 /8 14 1 3 5 /8 2 3 5 /8 2 3 5 /8 1 3 5 /8 14 2 3 5 /8

Installation Clearances
WARNING Furnaces in rooms shall be installed with the clearances from combustible materials not less than indicated in Table 1. Combustible materials are those made of or surfaced with wood, compressed paper, plant fibers, plastics, or other material that will ignite and burn, whether flame proofed or not, or whether plastered or not. Place the furnace near the center of the supply and return ducts and as close to the chimney connector as possible. Provide a solid brick or 2 thick minimum concrete pad if the furnace mounting area is not level or if the floor can become flooded.

MODEL

Sides A

Table 1 Standard Installation Clearances Top Front Rear Flooring B C D

HB85 6 2 24 6 Combustible LB85 6 2 24 6 Noncombustible HB115 6 2 24 6 Combustible LB115 6 2 24 6 Noncombustible HB145 6 2 24 6 Combustible LB145 6 2 24 6 Noncombustible HB160 6 2 24 6 Combustible LB160 6 2 24 6 Noncombustible CF85 1 2 18 1 Noncombustible1 HSD84 6 2 24 6 Noncombustible HSD112 6 2 24 6 Noncombustible HSD140 6 2 24 6 Noncombustible REH600 2 2 Alcove-24 2 Combustible REL600 2 2 Alcove-24 2 Noncombustible REH750 2 2 Alcove-24 2 Combustible REL750 2 2 Alcove-24 2 Noncombustible REH850 2 2 Alcove-24 2 Combustible REL850 2 2 Alcove-24 2 Noncombustible REH1000 2 2 Alcove-24 2 Combustible REL1000 2 2 Alcove-24 2 Noncombustible REH1250 2 2 Alcove-24 2 Combustible REL1250 2 2 Alcove-24 2 Noncombustible Notes: 1. Optional combustible flooring base is available. 6

Chimney Connector E 18 18 18 18 18 18 18 18 9 18 18 18 18 18 18 18 18 18 18 18 18 18

Plenum Top & Sides 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

Lowboy furnaces not listed for combustible floor may be placed on combustible floors although not listed for such installation, provided the floor under the furnace is protected in accordance with the requirements of accepted building code practice and NFPA 31. The furnaces shall be permitted to be placed on combustible flooring protected by 4 hollow block placed with ends unsealed and joints matching in such a fashion as to permit free circulation of air from side to side through the masonry. The block must be covered with sheet metal not less than 24 gauge. Counter flow furnaces may be installed on combustible flooring with the use of an WARNING optional combustible floor base. Failure to properly install may result in fire, property damage or personal injury. Refer to drawing HE-191 for installation instructions.

Furnaces are permitted to be installed in rooms, but not alcoves or closets, with lesser clearances to combustible material, provided the combustible material is protected as described in Table 2 and NFPA 31. In no case shall the clearance be such as to interfere with the requirements for combustion air, draft regulators and accessibility. All clearances shall be measured from the outer surface of the combustible material to the nearest point on the surface of the appliance or chimney connector, disregarding any intervening protection applied to the combustible material. Spacers and ties are to be of noncombustible material. No spacer or tie shall be used directly opposite an appliance or chimney connector. With all clearance reduction systems using ventilated air space there shall be at least 1 clearance between the reduction systems using ventilated air space. Mineral wool batts, blanket or board shall have a minimum density of 8lb/ft3 and a minimum melting temperature of 15000F. Insulation material used as part of a clearance reduction system shall have a thermal conductivity of 1.0(Btu/In)/ (Ft2/Hr/0F).

Type of protection applied to and covering all surfaces within the distance specified as the required clearance with no protection 3 thick masonry wall without ventilated air space insulation board over 1 glass fiber or mineral wool batts 24 gauge sheet metal over 1 glass fiber or mineral wool batts reinforced with wire on rear face with ventilated air space 3 thick masonry wall with ventilated air space 24 gauge sheet metal with ventilated air space insulation board with ventilated air space 24 gauge sheet metal with ventilated air space over 24 gauge sheet metal with ventilated air space 1 glass fiber or mineral wool batts sandwiched between 2 sheets 24 gauge sheet metal with ventilated air space

Table 2 Allowable Clearances with Specified Protection Where the Specified Clearance with No Protection from the Appliance or Chimney Connector 18 Above Rear & Sides N/A 12 12 9 12 Above Rear & Sides N/A 9 9 6 9 Above N/A 6 Rear & Sides 6 5 Above N/A 4 6 Rear & Sides 5 3

N/A 9 9 9 6

6 6 6 6 6

N/A 6 6 6 6

6 4 4 4 4

N/A 5 5 5 5

6 3 3 3 3

N/A 3 3 3 3

6 2 3 3 3

If the furnace is to be installed in a residential garage, the furnace must be a minimum of 18 above the garage floor and located so it cannot be damaged by a moving vehicle.

Duct Work
NOTICE The duct system should follow the design standards of Air Conditioning Contractors of America (ACCA) or ASHRAE. The duct system should be sized for the maximum CFM capabilities of the furnace being installed. All trunk lines, take-offs, registers and grill free areas must be figured when determining the air handling capacity of a duct system. By utilizing the Tables 3 through 5, one can obtain the necessary duct system size. Use a supplier's catalog for proper sizing of outlet and return air registers to insure that the register will meet the CFM requirements of the run to which it is connected. Do not exceed the recommended flow rate. The pressure drop for each should not exceed 0.05 inch water column. The return air ducts should equal the warm air duct system in CFM capacities. Avoid locating a return air duct in rooms that may contain undue odors. Use only a return air filter mounted to or integral to the furnace. Do not add additonal filters unless the duct system is sized to allow for the additional pressure drop. An open return in a basement does not meet the requirements of return air. Instruct the homeowner not to block any returns. Always check the size of existing ducts, particularly if you are adding air conditioning. The pressure drop through the cooling evaporator coil reduces available air flow. If the ducts are too small the system may not work satisfactorily or be noisy on either heat or cooling. If the furnace is used in connection with summer air conditioning, the furnace should be installed parallel with or on the upstream side of the evaporator coil to avoid condensation in the furnace heat exchanger. The evaporator coil must be installed at least 6 above the heat exchanger for proper air flow. Distances less than 6 will result in decreased air flow. In all cases refer to the manufacturers data for static pressure losses to ensure the total system static pressure does not exceed 0.5 WC. If the cooling unit is installed with a parallel flow arrangement, dampers or other means used to control flow of air should be provided to prevent chilled air from entering the furnace. If such a damper is manually operated, it must be equipped with a means to prevent operation of either unit, unless the damper is in the full heat or cool position. NOTE: When a return register is located in the same room as the furnace, the register must be at least 20 feet away from the furnace. To obtain proper CFM on a belt drive unit installed with air conditioning, the motor and/or blower pulley may need to be changed. On a direct drive unit the blower motor speed may need to be changed depending upon the size of the air conditioning system installed and the static resistance of the duct system. See blower specifications for air conditioning CFM's at a .5 static. Determining Air Flow CFM The temperature rise through the furnace should not exceed 0 rated temperature rise as listed the on the Rating Label (Typically750F) and should be at least 55 F for comfort. The sensible heat temperature change for cooling would be approximately 300F. Actual temperature change will be approximately 200F due to the humidity in the air. To calculate the sensible heat change or temperature rise the following formula applies T = (Btuh Output)/(1.1 x CFM) To calculate the air flow when you know the temperature rise the following formula applies CFM = (Btuh Output)/ (1.1 x T) 9

An estimate of air flow can be achieved by the following rules of thumb: Heating: 1300 CFM per 100,000 Btuh output Cooling: 400 CFM per ton of air conditioning Determine the required air flow for the system based on both heating and cooling requirements. Use the larger of either for duct design. Table 3 lists the maximum recommended air velocities for ducts. Velocities greater than those as listed may result in objectionable air noise in the ducts. Table 3 Recommended Maximum Duct Velocities, Feet Per Minute (FPM) Main Ducts* Branch Ducts Application Supply Return Supply Return Apartments 900 700 600 600 Auditoriums 1200 1000 1000 800 Banks 2000 1500 1600 1200 Hotel Rooms 1500 1300 1200 1000 Libraries 2000 1500 1600 1200 Meeting Rooms 2000 1500 1600 1200 Offices 2000 1500 1600 1200 Residences 900 700 600 600 Restaurants 2000 1500 1600 1200 Retail Stores 2000 1500 1600 1200 *When sound control is critical use branch duct velocities Table 4 Duct Area Required at Listed Flow Conditions Area Area Area Area Area Area Sq. In. Sq. In. Sq. In. Sq. In. Sq. In. Sq. In. 2000FPM 1600FPM 1200FPM 1000FPM 800FPM 600FPM 50 12 100 24 18 14 12 150 36 27 22 18 14 200 48 36 29 24 18 14 250 60 45 36 30 23 18 300 72 54 43 36 27 22 400 96 72 58 48 36 29 500 120 90 72 60 45 36 750 180 135 108 90 68 54 1000 240 180 144 120 90 72 1250 300 225 180 150 113 90 1500 360 270 216 180 135 108 1750 420 315 252 210 158 126 2000 480 360 288 240 180 144 Note: For Systems not over 100 feet equivalent length. Do not apply this table to duct systems which exceed 100 equivalent feet in length. For longer systems refer to ACCA Manual D. Incorrectly sized ducts can result in unsafe or uncomfortable operation. CFM

10

Nominal Size Area in.2 Model HP

4 12.5 Speed

Table 5 Round Duct Equivalent Area 5 6 7 8 19.6 28.3 38.5 50.3 Table 6 Belt Drive Blower Specifications Volts Amps Shaft Blower Motor Size Model Pulley
115 115 115 115 115 115 115 115 6.1 9.2 10.4 10.4 6.1 9.2 10.4 10.4 1/2 1/2 5/8 5/8 1/2 1/2 5/8 5/8 100-10T 110-10 120-12T 120-12T 100-10T 100-10T 120-12T 120-12T 3-1/2 3-1/2 3-1/2 3-1/2 3-1/2 3-1/2 3-1/2 3-1/2

9 63.6 Turns Open


2-1/2 1-1/2 2 1 2-1/2 3 1-1/2 1

10 78.5 Blower Pulley


6 6 6 6 6 5 6 6

12 113.1 CFM Static Pressure


1105 0.2 1400 0.2 1969 0.2 1685 0.5 1151 0.2 1418 0.2 1925 0.2 1665 0.5

LB85 LB115 LB160 LB160C HB85 HB115 HB160 HB160C

1/3 1/2 3/4 3/4 1/3 1/2 3/4 3/4

1725 1725 1725 1725 1725 1725 1725 1725

Table 7 Direct Drive Blower Specifications


Model HP Speeds RPM Volts Full Load Amp. 9.2 9.2 11.0 9.2 9.2 11.0 9.2 9.2 9.2 11.0 9.2 9.2 9.2 9.2 Capacitor 370 volt mfd 15 15 50 15 15 50 15 15 15 15 15 15 15 15 Rotation Blower Model 100-10T 110-10R 120-12T 100-10T 110-10R 120-12T 100-10T 100-10T 110-10R 110-10R 100-10T 100-10T 100-10T 100-10T Blower Speed AC Hi Hi Hi Hi Hi Hi Hi Hi Hi Hi Hi Hi Hi Hi Blower Speed Change Med Low Med Hi Med Med Low Med Hi Med Med Hi Med Low Med Hi Med Med Low Med Hi Med Hi Med Hi Blower Speed Heat Low Med Low Low Low Med Low Low Med Low Low Low Low Low Med Low Low Med Low

LBD85 LBD115 LBD160 HBD85 HBD115 HBD160 CF85 HSD84 HSD112 HSD140 REL750 REL1000 REH750 REH1000

3/4 3/4 1 3/4 3/4 1 3/4 3/4 3/4 1 3/4 3/4 3/4 3/4

4 4 3 4 4 3 4 4 4 3 4 4 4 4

1075 1075 1075 1075 1075 1075 1075 1075 1075 1075 1075 1075 1075 1075

115 115 115 115 115 115 115 115 115 115 115 115 115 115

CCW CCW CCW CCW CCW CCW CCW CCW CCW CCW CCW CCW CCW CCW

11

Table 8 Direct Drive Blower Performance


0.2 In. W.C. Static Pressure High LBD-85 LBD-115 LBD-145/160 HBD-85 HBD-115 HBD-145/160 CF-85 HSD-84 HSD-112 HSD-140 REL-600 REL-750 REL-850 REL-1000 REL-1250 REH-600 REH-750 REH-850 REH-1000 REH-1250 1350 1713 2150 1484 1711 2251 1400 1339 1850 2176 1903 1903 1903 2466 2466 1745 1745 1745 2283 2283 Med. High 1305 1598 2017 1402 1586 2119 1328 1292 1723 2018 1711 1711 1711 2150 2150 1550 1550 1550 2130 2130 Med. Low 1268 1452 -----1323 1433 -----1265 1242 1629 -----1547 1547 1547 1839 1839 1376 1376 1376 1901 1901 Low 1215 N/R 1875 1273 N/R 1969 1203 1177 1438 1893 1399 1399 1399 1600 N/R 1250 1250 1250 1717 N/R High 1215 1615 2003 1292 1605 2044 1210 1126 1670 1982 1661 1661 1661 2072 2072 1480 1480 1480 2007 2007 0.5 In. W.C. Static Pressure Med. High 1175 1498 1862 1205 1491 1896 1123 1104 1547 1881 1485 1485 1485 1859 1859 1343 1343 1343 1832 1832 Med. Low 1142 N/R -----1126 N/R -----N/R 1059 1452 -----1355 1355 1355 1610 N/R 1175 1175 N/R 1644 N/R Low 1082 N/R N/R 1084 N/R N/R N/R 1020 N/R 1761 1227 1227 N/R N/R N/R 1043 N/R N/R 1501 N/R

MULTIPLE FURNACES IN COMMON DUCT WORK WARNING Multiple furnaces connected to common duct work, either supply, return, or both supply and return must be wired so that all furnace blower motors are energized at the same time. Failure to turn all blowers on at the same time can cause a reversal of air flow in those units where the blower motor is not operating. This reversal of air flow can cause premature blower, blower motor, wiring and or heat exchanger failure. Please consult the factory for specific wiring instructions for your application.

VENTING
WARNING Failure to follow all instructions can result in flue gas spillage and carbon monoxide emissions, causing severe personal injury or death. All chimneys must meet the requirements of NFPA 211 and NFPA 31 12

Chimney The furnace must be connected to an adequate chimney or an approved venting system in accordance with these instructions. An adequate chimney or venting system is one that is sealed and lined with the capability of producing a -.04" W.C. flue draft and having the capacity to handle the amount of flue gas that is introduced. A chimney with an internal construction of corrosion resistant tile, stainless steel, or some other material that will withstand flue gas temperatures up to 10000F is required. Masonry and metal chimneys shall be constructed in accordance with applicable building code requirements. Masonry chimneys shall be lined with an approved clay tile liner or a listed chimney lining system installed in accordance with manufacturers instructions and also meeting the requirements of NFPA-211 Standard for Chimneys, Fireplaces, Vents, and Solid Fuel-Burning Appliances. Metal chimneys also shall meet the requirements of NFPA-211. Factory built chimneys shall be listed and shall be installed in accordance with their listing and NFPA-211. Prior to installation of the furnace, the chimney or venting system shall be examined by the installer and determined to be in good condition. All joints of the chimney must be tightly sealed. The inside of the chimney should be free of all obstruction, such as loose brick, broken pieces of tile, or corroded metal. If chimney flues are divided or there are multiple flues within one chimney, make sure there are no openings in the partition separating the divided or individual flues. When a new appliance is connected to an existing chimney, that chimney shall be brought up to current requirements. Chimneys which are relined shall be done so with an approved liner that will resist corrosion, softening, or cracking from the flue gasses. All chimney clean-out doors and flue connections must fit tightly so they will seal to avoid air leakage. The inside area of the chimney liner should equal, at a minimum, the area of the vent pipe exiting the furnace. If more than one appliance is installed, the area of both appliances shall be used in determining the required inside area of the chimney. The flue gas exit of a chimney shall be at least 3 feet above the highest point where it passes through the roof of a building and at least 2 feet higher than any portion of a building within 10 feet of such chimney. The chimney height will also be determined by the height of the surrounding trees, buildings and terrain. When chimney downdraft conditions cause faulty operation that creates a hazard, corrective steps must be taken. When altering the surrounding obstructions is not possible, a chimney cap can be constructed on the top of the chimney to avoid downdrafts. The chimney cap should be pyramid shaped on the top with a perfectly flat surface immediately above the chimney outlet. The hood should be attached by four (4) iron supports. The four iron supports should be equal in height to the width of the chimney opening. Four plates, flaring down, can be added to help insure that the wind will pass straight over the chimney outlet. Chimney Relining A tile lined masonry chimney serving an oil fired furnace should comply with applicable building codes such as NFPA-211. An additional listed lining may be required to reduce transient low draft during startup and acid water condensation during cyclic operation. This is particularly true for high mass masonry chimneys serving oil fired furnaces of higher efficiency. For masonry chimneys, local experience can indicate how well construction has withstood the lower temperatures produced by higher efficiency furnaces. 13

Evidence of potential or existing chimney damage should be determined by visual inspection of the chimney and liner. Exterior indicators such as missing or loose mortar/bricks, white deposits on the brick or water stains on the interior building walls should be investigated further. The operational flue temperatures for furnaces range from 350F to 550F at the outlet of the furnace. These temperatures are further reduced before reaching the chimney due to heat loss through the vent connector and dilution from the draft regulator. The resulting flue gas temperatures may become low enough to form condensation on the chimney liner walls. To prevent condensation, it is necessary that the internal chimney wall temperature always be kept above the dew point of the flue gasses. If the chimney is a masonry type, it may have to be lined with a flue liner, if the temperature loss is too great for the furnace. A liner will act as an insulator and reduce the flue gas temperature loss. Insulation may be added around the liner for further temperature stability. Refer to NFPA-31 for recommended liner sizing tables as developed by the Oil Heat Vent Analysis Program. Chimney Connector The chimney connector pipe between the furnace and chimney shall be of equal diameter as the flue outlet of the furnace. Refer to furnace specifications in this manual for proper size flue pipe for your model furnace. Any reduction in size required for the chimney must be made at the chimney connector. The vent connector pipe must be made of 24 gauge (or thicker) corrosion-resistant steel. The vent connector pipe should be as short as possible and installed so that it has a continuous rise from the furnace to the chimney. Long horizontal vent runs can result in the possibility of condensation in the flue pipe or the chimney. All horizontal runs of vent connector pipe should be pitched upward a minimum of 1/4 inch per foot of run. The horizontal length of the vent pipe connector shall not exceed 10 feet. The chimney connector shall be installed so as to minimize the number of elbows and to avoid sharp turns or other construction features that would create excessive resistance to the flow of flue gasses. Tees may be used in a straight section in conjunction with a barometric draft regulator; however, they must not be used for a 90 turn. No device that will obstruct the free flow of flue gasses shall be installed in the chimney connector. This does not exclude the use of devices specifically designed for the use in chimney connectors such as automatic dampers. The vent pipe should be joined with metal screws and supported by straps. A thimble should be used to connect the vent connector pipe to the chimney so the pipe may be readily removed in case of inspection or replacement. No chimney connector shall pass through any floor or ceiling. The vent connector pipe must not pass through a combustible wall or partition unless they are guarded at the point of passage by a ventilated metal thimble not less than 12 inches larger in diameter than the connector, on metal or fireclay thimbles adequate protection is provided at the passageway. An acceptable passageway could be either an approved, ventilated metal thimble which is at least 12 inches larger in diameter than the vent connector pipe, or brick work which is at least 8 inches thick constructed into the wall and surrounding the vent connector Clearances from combustible materials or materials shall be in accordance with the clearances given in Tables 1 or 2. The vent connector pipe should extend only to (and not beyond) the inside wall of the chimney. A thimble should be used to connect the vent connector pipe to the chimney so that the vent connector pipe may be readily removed in case of inspection or replacement. Connection to the chimney must be made above the bottom of the chimney to avoid blockage. Vent piping should extend just into the chimney far enough to expel flue gasses. Inserting the vent piping too far into the chimney will cause undue obstruction. Use a thimble or a slip joint where vent pipe 14

enters the chimney to allow easy removal for cleaning. A draft regulator is required in the vent piping; it should be located at least 24 inches from the furnace if possible in either a horizontal or vertical section of the vent pipe. The draft regulator must be installed in the same room as the furnace and in such a manner that there is no difference in pressure between the air in the vicinity to the regulator and the combustion air supply. Ensure that the barometric damper is accessible for adjustment. With the burner operating, use a draft gauge to adjust the regulator to the proper setting (see instructions enclosed with draft gauge to adjust the regulator to the proper setting). When the burner air supply and draft are properly adjusted, the over-fire draft should be a negative .02" W.C. Two or more oil burning appliances each equipped with a safety control may be permitted to be connected to one common chimney if sufficient draft is available for the safe simultaneous removal of all products of combustion. If two or more openings are provided into one chimney, they shall be at different levels on the same story of the building, with the smaller appliance entering at the highest possible level consistent with clearances to combustible materials. Two or more connectors shall not be joined together unless the common connector, manifold and chimney are properly sized. Adequate draft must be available to safely remove all products of combustion simultaneously without leakage, or back flow. WARNING All LB series furnaces now have a flue separation plate located between the rear flue of the heat exchanger and the extension pipe in the blower compartment as indicated by the fluorescent orange sticker on the flue collar. The flue separation plate MUST BE REMOVED when these furnaces are installed IN REAR FLUE APPLICATIONS. The plate can be taken off by removing the lower left screw that attaches the extension pipe to the heat exchanger. Then loosen the other three screws until the plate can be moved freely downward and to the left. Reinsert the screw previously removed and tighten up all four screws. See figure for reference. Power Venting The furnace may be power vented through a side wall by using a listed power side wall Venter. The vent device must be able to produce a draft of -.02W.C. over the fire and be equipped with a post purge timer set to a minimum time of 5 minutes. The power vent must be installed in accordance with the recommendations of the manufacturer, all applicable building code requirements, and NFPA-31. Vent Dampers Do not install a thermal type vent damper on the furnace. Failure to comply could result in severe personal injury, death or substantial property damage. If a vent damper is required, use only a motorized damper, wired and installed following the vent damper manufacturers instructions.

Ventilation and Combustion Air


Appliances shall be installed in a location where the facilities for ventilation permit the satisfactory combustion of oil, proper venting and the maintenance of ambient temperature at safe limits under 15

normal conditions of use. The burner requires a generous amount of clean combustion air to operate safely. The furnace room must be well ventilated to allow sufficient make-up air to support combustion. Inadequate combustion air may result in erratic operation of the burner, noisy combustion or fuel odors in the air. NEVER BLOCK THE FURNACE FROM THE SUPPLY OF COMBUSTION AIR. Remember, your need for outside air will be greatly increased if you have a vented dryer in the basement or other venting fans in the home. Do not install an exhaust fan in the same room as the furnace. In unconfined spaces in buildings of conventional construction, infiltration is adequate to provide air for ventilation and combustion. If the unconfined space is within a building having insufficient air because of tight construction, the air required for combustion and ventilation shall be obtained from outdoors or from spaces freely communicating with the outdoors. In this situation, permanent openings having a total free opening area of not less than 1 square inch per 5000Btu/Hr of total input of all appliances must be provided. If the furnace is located in a confined space (A space whose volume is less than 50 cubic feet per 1000Btu/Hr of the combined input ratings of all appliances installed in that space) the confined space shall have two permanent openings, one 6 inches from the top of the space and one 6 inches from the bottom of the space. Each opening shall have a free area opening of not less than 1 square inch per 1000Btu/Hr of total input rating of all appliances in the enclosure freely communicating with interior areas having adequate infiltration with the outside. If adequate infiltration air is not available the confined space shall be fitted with two openings, one 6 inches from the top of the enclosure and one 6 inches from the bottom of the enclosure. Each opening shall have a free area of at least 1 square inch per 2000Btu/Hr of the total input of the appliances in the enclosure. In calculating free area, consideration must be given to the blocking effect of louvers, screens or grills protesting the opening. Screens used shall not be less than mesh and shall be readily accessible for cleaning.

Burner Installation
NOTICE Remove the oil burner from its shipping carton and inspect thoroughly. Verify that the correct burner combination and nozzle is installed in the burner as shipped. Read the oil burner manual included in the shipping carton and follow the instructions for preparing and installing the burner. Refer to Table 9, Table 10, or Table 11 for the burner specifications for your unit. On units which can be multi fired, a nozzle change may be required. Follow the oil burner manuals instructions for the proper installation of the nozzle. Verify that the electrode settings match the manufacturers recommended settings. Inspect the combustion chamber. Verify that it is in the correct position in the heat exchanger and is in good condition. The oil burner is to be bolted to the pouch plate using the burner mounting flange gasket and the nuts supplied. Make sure that the burner passes through the burner opening in the combustion chamber and does not protrude into the combustion chamber. Refer to the wiring section of this manual for the correct wiring connections to the furnace and to the oil burner manual for fuel piping. 16

Table 9 Beckett Burner Specifications


Furnace Model Burner Delavan Pump Air Air Head Tube Insertion Model Nozzle Press. Band1 Shutter1 Length LB/HB85 F-33 AFG 140 0 7 9 5-5/8 0.65X80A F-4 LB/HB115 140 0 8 9 5-5/8 AFG 0.85X80 A LB/HB145 F-4 AFG 140 0 10 9 5-5/8 1.00X80B F-4 LB/HB160 140 1 10 9 5-5/8 AFG 1.10X80B CF85 F-3 AFG 140 0 7 9 5-5/8 0.65X80 A F-43 HSD84 140 0 6 6-1/2 5-1/4 AF 0.65X80A HSD112 F-4 AF 0.75X80 A 140 0 4 6-1/2 5-1/4 F-6 HSD140 140 0 6-1/2 6-1/2 5-1/4 AF 0.90X80A 2 REL/REH600 F-3 AFG 100 0 4 6-1/2 5-1/2 0.60X80 A F-32 REL/REH750 100 0 6 6-1/2 5-1/2 AFG 0.75X80B 2 REL/REH850 F-3 AFG 0.85X80 B 100 0 9 6-1/2 5-1/2 F-62 REL/REH1000 100 0 5 AFG 9 7-3/4 1.00X80 B REL/REH1250 F-62 AFG 100 0 8.5 9 7-3/4 1.25X80B Notes: 1. Approximate air settings, see start up procedures for final adjustments. 2. With ceramic amulet and Stainless Air Tube. 3. Low Firing Rate Baffle installed. Static Plate 3-3/8 3-3/8 2-3/4 2-3/4 3-3/8 2-3/4 2-3/4 2-3/4 3-3/8 3-3/8 3-3/8 3-3/8 3-3/8

Table 10 Riello Burner Specifications


Furnace Model Burner Delavan Pump Air Turbulator Model Nozzle Press. Setting1 Setting LB/HB85 0.65X60W 40F3 160 4.50 0.5 LB/HB115 0.85X60 W 160 3.25 2.0 40F5 LB/HB145 1.00X60W 40F5 160 3.75 3.0 LB/HB160 1.10X60W 160 6.00 3.0 40F5 CF85 0.65X60W 40F3 160 4.50 0.5 REL/REH600 0.50X60A 150 2.75 3.0 40F3 REL/REH750 0.60X60A 40F3 150 4.0 3.0 REL/REH850 0.65X60A 150 5.25 3.0 40F3 REL/REH1000 0.85X80B 40F5 150 2.75 4.0 REL/REH1250 1.00X80 B 150 3.6 4.0 40F5 Notes: 1. Approximate air settings see start up procedures for final adjustments 2. Burner Amulet Required Tube Length 8-7/8 8-7/8 8-7/8 8-7/8 8-7/8 8 8 8 8-7/8 8-7/8 Insertion 5-3/4 5-3/4 5-3/4 5-3/4 5-3/4 5-1/4 2 5-1/4 2 5-1/4 2 7-1/2 2 7-1/2 2

Table 11 Carlin Burner Specifications


Burner Nozzle Pump Air Air Bar1 1 Model Press. Band LB/HB85 0.65X70W2 EZ-1 140 0.65 0.60-0.65 2 LB/HB115 0.85X70 B EZ-1 140 0.85 0.85-1.00 LB/HB145 1.00X70B2 EZ-1 140 1.00 0.85-1.00 2 LB/HB160 1.10X70 B EZ-1 140 1.10 1.10-1.25 CF85 0.65X70W2 EZ-1 140 0.65 0.60-0.65 2 REL/REH600 0.60X70 A EZ-1 100 0.60 0.60-0.65 REL/REH750 0.75X70A2 EZ-1 100 0.75 0.75 2 REL/REH850 0.85X70 A 100 0.85 0.85-1.00 EZ-1 3 REL/REH1000 1.00X60 SS EZ-1 100 1.00 0.85-1.00 REL/REH1250 1.25X60SS3 EZ-1 100 1.25 1.10-1.25 Notes: 1. Approximate air settings - see start up section for final adjustments 2. Delavan nozzle 3. Hago nozzle Furnace Model Tube Length 9 9 9 9 9 7 7 7 9 9 Insertion 5-3/4 5-3/4 5-3/4 5-3/4 5-3/4 5-1/2 5-1/2 5-1/2 8 8

17

Wiring
WARNING Electric shock hazard can cause severe personal injury or death if power source, including service switch for the furnace, is not disconnected before installing or servicing the unit. All wiring must conform to the National Electrical Code NFPA 70, latest edition and any additional state or local codes. All wiring must be N.E.C. Class 1. If original wiring as supplied with the furnace must be replaced, replace with type 105C wire or equivalent only. Power Supply wire for the furnace must be sized for the load requirement as listed on the furnace rating plate. Connect 120 VAC 60HZ single phase separate electrical line from the main house panel to the power leads in the junction box attached to the furnace as indicated in the electrical wiring diagrams. Provide a fused disconnect in the power line following all code requirements. Connect the burner to the factory wired burner harness as shown in the electrical diagrams. Provide electrical ground at the furnace as required by codes. Thermostat Locate the room thermostat on an interior wall in the natural circulating path of room air. Do not locate the thermostat so it is exposed to cold air infiltration, drafts from windows or doors, air currents from supply or return air registers, behind obstructions, in a closet or in a corner. Ensure the thermostat wont be exposed to heat from nearby fireplace, radio, television, lamp or rays from the sun. Do not mount thermostat on a wall over a supply or return duct, chimney or vent. Wire the thermostat to furnace and set the thermostat anticipator as shown on the oil burner primary control. Failure to properly adjust the heat anticipator could result in short cycling of the furnace or overheating the home.

18

19

20

21

22

23

Oil Tank and Piping


WARNING Installation of oil tanks must meet all local codes and ordinances. Refer to NFPA-31 for complete guidelines on oil tank installations internal to the building, outside above and below ground tanks. Oil tanks located inside the building shall not be in excess of 275 gallons individual capacity and shall not be located within 5 feet horizontally from any source of heat, either internal or external to the appliance being served or in a manner that the temperature of the oil in the tanks exceeds 25F above room temperature. Connect burner to oil supply using the correct size heavy wall copper tubing, wrought iron, steel or brass fittings in accordance with the literature attached to the pump. All lines must have shut off valves, a good pipe joint compound approved for use with oil on all pipe threads, no kinks, no sharp bends, and be properly tested for leaks. Use flare fittings only when assembling oil lines. Avoid use of fittings in inaccessible locations. Avoid running tubing against any type of heating unit and across ceiling or floor joists. Piping shall be supported and protected from physical damage and where necessary, protected against corrosion as per code. Piping systems shall be maintained liquid tight. A piping system that has leaks constitutes a hazard which must be repaired in an approved manner. All oil feed lines to burners must be air tight. The slightest air leak, caused by loose fittings, bad gaskets or any other reason, can cause a foaming oil stream which will cause any of the following conditions: a) Intermittent firing, causing safety shutdown. b) Poor starts. c) Smokey starts. d) Continual sooting of furnace and burner parts including the cad cell. e) Reduced firing rate, inefficient operation and erratic fire pattern. f) A dangerous combustion condition, allowing the combustion chamber to fill with a lean mixture (too much air in the oil stream) which could cause a delay in ignition of the fuel mixture until the danger point has been reached. This fuel unit when connected with a single pipe system is satisfactory only where the oil supply is on the same level or above the burner, permitting gravity flow of oil. When it is necessary to lift oil to the burner, a return line must be connected between the fuel unit and the tank. This requires the insertion of the "bypass" plug in the oil pump. The bypass plug and pump instructions are attached to the pump. Installation of a check valve in the suction line of a two pipe system is advisable under all circumstances. Be sure the check valve fittings are air tight. If lift exceeds 10 ft. a two-stage pump must be installed with a two pipe system. If any part of the fuel oil tank is above the burner, an anti-siphon device must be used to prevent the flow of oil in case of an oil line breakage. Suction vacuum must be held to acceptable limits. THE VACUUM TEST IS WORTH THE TIME REQUIRED TO MAKE IT. This problem becomes proportionately larger with underground tanks. Connect vacuum gauge to oil pump. Suction vacuum must not exceed 10 inches of mercury for single stage pumps and 15 inches for two stage pumps. It is preferable to stay below these limitations. When the suction line is tight and properly installed the pump will hold its vacuum for a minimum of 60 minutes after shutdown. Use an oil filter with the proper capacity to filter for all installations. Install the filter inside the building between the tank shutoff valve and the burner. The filter cartridge should be replaced at least once a year. The filter body should be thoroughly cleaned before installing a new cartridge. 24

Start-Up
WARNING Use number No. 2 fuel oil only. Do not attempt to start the burner if excess oil has accumulated. Do not use gasoline, crankcase draining or any oil containing gasoline. This equipment must be adjusted and started only by a qualified service agency an individual or agency, licensed and experienced with all codes and ordinances, and who is responsible for the installation and adjustment of the equipment. 1. Check that all safety devices are in place. 2. Check that thermostats are correctly connected and set. 3. Check that the inside of the furnace is free of any fuel residue or foreign materials and that the refractory chamber has not been damaged. 4. Check oil burner nozzle to ensure that the right size and type is installed and tight in the adapter. See preliminary settings for proper nozzle size and type. 5. Check electrode settings, as they may have been jarred out of position during transportation. See oil burner instructions for nozzle and electrode setting 6. Check air setting to ensure that it matches the preliminary air settings as found in Table 9, Table 10, or Table 11. 7. Check that the Burner mounting bolts are tight. 8. Lubricate burner motor and circulator motor if required. 9. Open all oil lines valves. 10. Set room thermostat to call for heat. 11. Turn service switch on. Burner should start. On one pipe fuel system only you may have to bleed the oil system. To bleed attach a clear plastic tube to the oil pump bleed port and allow oil to run until all the air is out of the oil suction line feeding the oil burner. If air is still evident in the bleed line you must check the oil lines, all fittings, filters and any other connections for tightness. See burner and fuel pump manufacturers recommendations for proper bleeding of the fuel system. CAUTION: DO NOT RUN THE PUMP DRY FOR MORE THAN FIVE MINUTES, AS IRREPAIRABLE DAMAGE MAY RESULT. 12. Turn OFF burner and install pressure gauge and vacuum gauge into the proper ports on the pump. See the burner manufacturers manual for location of ports. 13. Start burner again and check oil pressure. Adjust if necessary. See oil burner manufacturers instructions for pump adjustment. Start-up Equipment THE FOLLOWING PROPER COMBUSTION INSTRUMENTS ARE REQUIRED TO DETERMINE PROPER AIR ADJUSTMENTS AND DRAFT WHEN SETTING UP OR SERVICING THE OIL BURNER. DO NOT ATTEMPT TO START UP OR SERVICE THE FURNACE WITHOUT THE PROPER COMBUSTION INSTRUMENTS. 1. 2. 3. 4. 5. 6. Carbon-dioxide (C02) or Oxygen (02) Analyzer Draft gauge. Scale should read from +.10" W.C. to -.25" W.C. Oil Pressure Gauge 0-200 PSI Stack Thermometer Plenum Thermometer Smoke Test Gun 25

7. Vacuum Gauge 0-30 in. of Hg 8. Volt meter 9. Amp meter Burner Adjustments Allow the burner to operate for at least 10 minutes before making the following adjustments. The factory burner settings may not be suitable for specific job conditions. Do not attempt to make any adjustments or start the furnace without the proper equipment. 1. A 5/16 diameter hole will be required in the flue pipe between the furnace and the barometric damper as close to the furnace as possible. 2. Set the draft regulator (barometric damper) using a draft gauge to obtain a negative draft over-fire of -.01 to -.02 in. W.C. 3. Pump pressure Install a pump pressure gauge in the oil pump following the oil burner manufacturers recommendations. Adjust to obtain required pressure as necessary. 4. Combustion Set-up The air settings shown in Table 8 thru Table 10 are approximate. The burner must be adjusted during actual field installed conditions. Failure to do so will result in poor performance and nuisance service calls. After proper draft and oil pressure have been established: a. Begin to close the air band to create a slight trace of smoke as noted on the Bacharach or equivalent smoke tester scale. b. Take a flue gas sample and note the CO2 reading. It will be about 12% to 13.5% c. Open the air band to reduce the CO2 approximately 2%. The desired CO2 setting for all units should be 10% to 11% d. Check for 0 smoke. Head settings and/or air band may be altered to obtain the above results. Lock the air band and head setting screws in place. The above procedure will give a built in margin to ensure clean operation throughout the heating season. Should draft conditions vary, lint accumulate in the fan, heavier oil delivered, or other adverse conditions be encountered you will have a reasonable margin of built in protection before smoke generation begins. Flue Gas Temperature - The flue gas temperature will vary to some degree depending on BTU inputs, duct design and the air flow across the heat exchanger. The suggested minimum NET stack temperature is 350F, and the maximum stack temperature is 550F. The lower the stack temperature, the higher the efficiency; however, stack temperatures under 350F may cause condensation which in turn may cause metal corrosion. Temperature Rise - Supply air temperature minus return air temperature. The temperature rise across the furnace (operating at steady state conditions) should be approximately 75F. A higher temperature rise would slightly lower the efficiency. The supply air temperature should be measured in the supply air trunk-line approximately 12 inches down stream of the plenum. Do not exceed the maximum temperature rise as listed on the furnace nameplate. Check operation of the cad cell relay by removing cad cell wire from external terminal of primary safety control to ensure that it goes off on safety. Check blower motor amperage under both heating and air conditioning loads and ensure that the amperage is less than the full load nameplate amperage of the blower motor.

5.

6.

7. 8.

26

Operating and Maintenance Instructions


WARNING The furnace must be installed, adjusted and maintained only by a qualified service agency annually. Have your unit inspected, cleaned and adjusted at least once a year to assure proper operation. Do not tamper with the unit or controls. Incorrect operation of the unit could result in severe personal injury and property damage. Never attempt to use gasoline in the furnace. Never store gasoline or other combustible materials near the burner or appliance. The area around the furnace should be kept clear of all combustible materials. Never attempt to burn garbage or refuse in the furnace. Never attempt to light the furnace by throwing burning material into the furnace. Never attempt to use crankcase or waste oil or materials other than the approved fuel oils in this furnace. Never restrict the air inlet openings to the burner. Do not attempt to start the furnace when excess oil has accumulated in the chamber or the furnace is full of vapors. Cleaning WARNING Cleaning the heat exchanger must be done yearly by a qualified service technician.

It is important to inspect and clean the heat exchanger once annually or as necessary to remove any build up of soot. A layer of soot on the inside surface of the heat exchanger will result in reduced efficiency. HB, LB, HS, CF 1. 2. 3. 4. 5. 6. Turn off all power to the furnace. Remove the upper pouch plate and the flue pipe. Lower the combustion baffle Using a soft 2" flue brush, cleaning the upper half of each corrugation of any soot buildup. Inspect heat exchanger and combustion chamber. Place the combustion baffle back to its original position and proceed to clean the lower half with the flue brush. 7. Vacuum any loose debris. 8. Replace the upper pouch plate and flue pipe. Should any of the gaskets break or otherwise not be able to provide an adequate seal, the gasket should be replaced before reassembly. 9. Clean and readjust the oil burner as required. REH, REL 1. Turn off all power to the furnace. 2. Remove clean out caps and the flue pipe. 3. Remove the burner and burner mounting plate. Extreme care must be used when removing the burner mounting plate as the ceramic fiber combustion chamber is directly attached to the burner mounting plate. 4. With access to the inside of the heat exchanger through the cleanout openings, burner opening, and vent opening use a soft flue brush to remove any soot build up. 27

5. Vacuum any loose debris. Do not use a vacuum on the combustion chamber. 6. Inspect heat exchanger and combustion chamber. 7. Replace the burner mounting plate with chamber, burner, vent pipe and burner. Replace any of the gaskets which would not be able to provide an adequate seal. 8. Clean and readjust the oil burner as required. Oil Burner NOTICE Refer to the oil burner instruction manual provided with the burner for proper maintenance and service. Burner Components: If replacement of burner parts is necessary, always use parts recommended by the manufacturer. Specify part number and description when ordering. Electrode settings are important for reliable ignition of the oil. Check to be sure the settings are in accordance with the instructions provided in the burner manual. Nozzles: ANY NOZZLE REPLACEMENT SHOULD BE OF THE EXACT TYPE AS THE ORIGINAL SUPPLIED BY THE MANUFACTURER. Use extreme care in handling nozzles to avoid scratches or dirt that could cause leaks or affect the oil spray pattern. Perform the combustion checks as per the burner manual and the furnace manual. Blowers Belt Drive Clean and inspect blower wheel annually. Lubricate blower motor as per the motors recommendations. Proper belt tension and alignment has a great impact on the overall performance of the furnace. A "Rule of Thumb" for checking belt tension is as shown. When the belt is grasped as shown a total deflection of between 3/4" and 1 " should be easily attained. As with all "Rules of Thumb" a measure of judgment must be exercised by the service person. Too much deflection indicates the belt is not tight enough, which will result in slippage causing a loss of blower speed and belt failure. Too little deflection indicates the belt is too tight. This will result in noise from excessive vibration, shorter belt life and premature bearing failure. Excessive belt tension may also result in overloading the motor. A belt should be just tight enough to prevent slippage. Blowers - Direct Drive Clean inspect blower wheel annually. Lubricate blower motor as per the motors recommendations. Vent System Clean and inspect the flue pipe draft regulator and chimney annually as outlined in this manual. Fuel Oil System Check oil tank and piping for leaks annually, replacing the oil filter to avoid contamination of the fuel unit and nozzle.

28

Filters Air filters should be inspected and replaced if required monthly. The filters supplied with the furnace are disposable and need to be replaced with the exact type and size as supplied. Dirty or clogged air filters will impair the furnace performance and may cause the furnace to shut down or overheat. Do not add additional filters unless the duct system is sized to allow for the additional pressure drop.

29

Item No. 1 1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31

Qty 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 2 1 1 4 1 1 1 1 1 1 1 2 1 1 1 2 1

Description BECKETT BURNER RIELLO BURNER CARLIN BURNER POUCHPLATE COVER POUCHPLATE ASSEMBLY COMBUSTION CHAMBER KIT FLUE COLLAR FLUE GASKET FRONT PANEL FAN & LIMIT CONTROL FRONT AIR BAFFLE POUCHPLATE GASKET KIT BAFFLE ASSEMBLY KIT HEAT EXCHANGER KIT FLUE COVER REAR PANEL SIDE PANEL FILTER RACK CHANNEL BLOWER RUBBER PLUG BUMPERS BLOWER WHEEL BLOWER PULLEY V-BELT VARIABLE MOTOR PULLEY BLOWER MOTOR ADJ. BRACKET BELT DRIVE MOTOR MOTOR MOUNTING BRACKET BLOWER LEG BLOWER PARTITION BASE PAN DOOR SIDE AIR BAFFLE BLOWER ASSEMBLY COMPLETE

HB85 Part No. 540600B 540904 540906 505000 732638 711301K 740780 489020 504110 552323 504900 489000 730317K 730051K 740800 504130 504100 504160 710450 712125 710351 711100 710590 711251 711260 712450 740730 740762 504140 504150 504120 740521 730477

HB115 Part No. 540601B 540901 540907 505001 732638 711301K 740780 489020 504510 552323 504900 489000 730317K 730061K 740800 504530 504500 504560 710450 712125 710351 711050 710570 711251 711260 712460 740730 740762 504540 504550 504520 740522 730483

HB160 Part No. 540603B 540903 540909 505001 732638 711311K 740790 489021 504810 552323 504900 489000 730318K 730071K 740810 504830 504800 504860 710452 712125 710354 711100 710650 711252 711260 712489 740750 740762 504840 504850 504820 740523 730489

30

Item No. 1 1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32

Qty 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 2 1 1 4 1 1 1 4 1 2 1 1 1 1 1 2 1 1

Description BECKETT BURNER RIELLO BURNER CARLIN BURNER POUCHPLATE COVER POUCHPLATE ASSEMBLY COMBUSTION CHAMBER KIT FLUE COLLAR FLUE GASKET FRONT PANEL FAN CENTER RELAY FAN & LIMIT CONTROL FRONT AIR BAFFLE POUCHPLATE GASKET KIT HEAT EXCHANGER KIT REAR PANEL FLUE COVER SIDE PANEL FILTER RACK DIRECT DRIVE MOTOR BLOWER MOTOR MOUNTING LEG BLOWER MOTOR LEG BAND BLOWER PARTITION BLOWER WHEEL RUBBER PLUG BUMPERS BLOWER BLOWER LEG TERMINAL BOARD CAPACITOR CONDUIT TERMINAL,BRACKET BASE PAN DOOR SIDE AIR BAFFLE BAFFLE ASSEMBLY KIT BLOWER ASSEMBLY COMPLETE

HBD85 Part No. 540600B 540904 540906 505000 732638 711301K 740780 489020 504110 552250 552323 504900 489000 730051K 504130 740800 504100 504160 712491 710025 710026 504140 710356 712125 710401 740762 310285 712430 505003 504150 504120 740521 730317K 730478

HBD115 Part No. 540601B 540901 540907 505001 732638 711301K 740780 489020 504510 552250 552323 504900 489000 730061K 504530 740800 504500 504560 712491 710023 710026 504545 710358 712125 710402 740762 310285 712430 505003 504550 504520 740522 730317K 730484

HBD160 Part No. 540603B 540903 540909 505001 732638 711311K 740790 489021 504810 552250 552323 504900 489000 730071K 504830 740810 504800 504860 712492 710028 710027 504845 710359 712125 710403 740762 310285 712435 505003 504850 504820 740523 730318K 730493

31

Item No. 1 1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36

Qty 1 1 1 1 1 1 1 5 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 4 2 1 1 1 1 1 1 1 2 1 2 1 1 1

Description BECKETT BURNER RIELLO BURNER CARLIN BURNER POUCHPLATE COVER POUCHPLATE ASSEMBLY COMBUSTION CHAMBER FLUE COLLAR FLUE GASKET FRONT PANEL FAN & LIMIT CONTROL FRONT AIR BAFFLE POUCHPLATE GASKET KIT HEAT EXCHANGER KIT BLOWER PARTITION LB REAR AIR BAFFLE SEPARATION PLATE FLUE EXTENSION PIPE REAR PANEL FLUE COVER DOOR BLOWER MOTOR ADJ. BRACKET MOTOR MOUNTING BRACKET BLOWER WHEEL RUBBER GROMMETS BLOWER LEG BLOWER BLOWER PULLEY V-BELT VARIABLE MOTOR PULLEY BELT DRIVE MOTOR RIGHT SIDE PANEL BASE PAN SIDE AIR BAFFLE LEFT SIDE PANEL FILTER RACK CHANNEL BAFFLE ASSEMBLY KIT TOP CHANNEL BLOWER ASSEMBLY COMPLETE

LB85 Part No. 540600B 540904 540906 505000 732638 711301K 740780 489020 504020 552323 504900 489000 730051K 504060 504910 740763 732690 504030 740800 504040 711260 740730 710351 712100 740767 710450 711100 710561 711251 712450 504000 504070 740521 504010 504080 730317K 504050 730475

LB115 Part No. 540601B 540901 540907 505001 732638 711301K 740780 489020 504420 552323 504900 489000 730061K 504460 504910 740763 732691 504430 740800 504440 711260 740730 710352 712100 740768 710451 711100 710590 711251 712460 504400 504470 740522 504410 504480 730317K 504450 730481

LB160 Part No. 540603B 540903 540909 505001 732638 711311K 740790 489021 504720 552323 504900 489000 730071K 504760 504910 740764 732692 504730 740810 504740 711260 740750 710354 712100 740768 710452 711100 710570 711252 712489 504700 504770 740523 504710 504780 730318K 504450 730488

32

Item No. 1 1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37

Qty 1 1 1 1 1 1 1 5 1 1 1 1 1 1 1 1 1 1 1 1 1 1 4 2 1 1 1 1 4 1 1 1 1 2 1 2 1 1 1

Description BECKETT BURNER RIELLO BURNER CARLIN BURNER POUCHPLATE COVER POUCHPLATE ASSEMBLY FLUE COLLAR COMBUSTION CHAMBER KIT FLUE GASKET FRONT PANEL FAN & LIMIT CONTROL FAN CENTER RELAY FRONT AIR BAFFLE POUCHPLATE GASKET KIT HEAT EXCHANGER KIT BLOWER PARTITION LB REAR AIR BAFFLE SEPARATION PLATE FLUE EXTENSION PIPE REAR PANEL FLUE COVER DOOR BLOWER WHEEL RUBBER GROMMETS BLOWER LEG BLOWER CAPACITOR CONDUIT TERMINAL BRACKET ELECTRON TERMINAL BOARD BLOWER MOTOR MOUNTING LEG DIRECT DRIVE MOTOR BLOWER MOTOR LEG BAND RIGHT SIDE PANEL BASE PAN SIDE AIR BAFFLE LEFT SIDE PANEL FILTER RACK CHANNEL BAFFLE ASSEMBLY KIT TOP CHANNEL BLOWER ASSEMBLY COMPLETE

LBD85 Part No. 540600B 540904 540906 505000 732638 740780 711301K 489020 504020 552323 552250 504900 489000 730051K 504060 504910 740763 732690 504030 740800 504040 710356 712100 740767 710401 712430 505003 310285 710025 712491 710026 504000 504070 740521 504010 504080 730317K 504050 730476

LBD115 Part No. 540601B 540901 540907 505001 732638 740780 711301K 489020 504420 552323 552250 504900 489000 730061K 504460 504910 740763 732691 504430 740800 504440 710358 712100 740768 710402 712430 505003 310285 710023 712491 710026 504400 504470 740522 504410 504480 730317K 504450 730482

LBD160 Part No. 540603B 540903 540909 505001 732638 740790 711311K 489021 504720 552323 552250 504900 489000 730071K 504760 504910 740764 732692 504730 740810 504740 710359 712100 740768 710403 712435 505003 310285 710028 712492 710027 504700 504770 740523 504710 504780 730318K 504450 730494

33

Item No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 28 29

Qty 1 1 1 1 1 1 1 1 2 1 2 1 1 1 1 2 4 1 1 1 1 1 1 1 4 1 1 1 1 1

Description BECKETT BURNER POUCHPLATE ASSEMBLY COMBUSTION CHAMBER KIT FLUE COLLAR FAN & LIMIT CONTROL FAN CENTER RELAY FRONT PANEL FRONT DOOR SIDE PANEL POUCHPLATE GASKET KIT FLUE GASKET HEAT EXCHANGER KIT UPPER BACK FLUE COVER REAR DOOR BLOWER LEG RUBBER GROMMETS BLOWER BLOWER WHEEL ELECTRON TERMINAL BOARD CAPACITOR CONDUIT TERMINAL BRACKET FILTER RACK BLOWER MOTOR LEG BAND BLOWER MOTOR MOUNTING LEG DIRECT DRIVE MOTOR BAFFLE ASSEMBLY KIT BLOWER ASSEMBLY COMPLETE RIGHT HAND DISCHARGE BLOWER ASSEMBLY COMPLETE LEFT HAND DISCHARGE POUCHPLATE CHAMBER ASSEMBLY

HSD84 Part No. 540705 730400 730382K 740780 552320 552250 501190 501210 501170 481015K 489020 730120 501200 740800 501220 740760 712100 710401 710356 310285 712430 505003 504560 710026 710025 712491 730260K 730521 730526 730400

HSD112 Part No. 540706 730420 730384K 740780 552320 552250 501410 501430 501390 481015K 489020 730150 501420 740800 501440 740761 712100 710402 710358 310285 712430 505003 504560 710026 710023 712491 730280 730552 730556 730420

HSD140 Part No. 540707 730440 730386K 740790 552320 552250 501630 501650 501610 481015K 489021 730180 501640 740810 501660 740761 712100 710402 710358 310285 712435 505003 501669 710027 710028 712492 730300 730582 730586 730440

34

Item No. 1 1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30

Qty 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 4 1 1 1 1 2 1 1 1 1 2 1 1 1 1 1

Description BECKETT BURNER RIELLO BURNER CARLIN BURNER POUCHPLATE ASSEMBLY COMBUSTION CHAMBER KIT FLUE COLLAR FLUE GASKET FRONT PANEL FAN & LIMIT CONTROL FAN CENTER RELAY POUCHPLATE GASKET KIT HEAT EXCHANGER KIT BLOWER PARTITION TRANSFORMER FAN SWITCH LIMIT SWITCH BLOWER MOTOR MOUNTING LEG DIRECT DRIVE MOTOR BLOWER MOTOR LEG BAND CAPACITOR ELECTRON TERMINAL BOARD BLOWER LEG BLOWER BLOWER WHEEL FILTER RACK CHANNEL REAR PANEL SIDE PANEL BASE PAN DOOR BAFFLE ASSEMBLY KIT TOP CHANNEL BLOWER ASSEMBLY COMPLETE

CF85 Part No. 540600B 540904 540906 732637 711301K 740780 489020 504310 552322 552250 489000 730054 504340 540737 540734 540735 710025 712491 710026 712430 310285 504997 710401 710356 504370 504330 504300 504350 504320 730317K 504360 730479

35

Item No. 1 2 3 3 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31

Qty 1 1 1 1 1 1 2 2 1 1 2 1 1 1 1 1 1 1 4 1 1 2 1 1 1 1 1 1 1 1 2 1 1

Description FRONT PANEL FRONT DOOR BECKETT BURNER RIELLO BURNER CARLIN BURNER POUCHPLATE ASSEMBLY SIDE POUCHPLATE GASKETS UPPER/LOWER POUCHPLATE GASKETS COMBUSTION CHAMBER INNER FRONT PANEL CAPS FAN & LIMIT CONTROL HEAT EXCHANGER REAR PANEL REAR BAFFLE RIGHT SIDE PANEL BLOWER MOTOR BLOWER MOTOR LEG BAND BLOWER MOTOR LEGS BLOWER WHEEL BLOWER BLOWER LEGS ELECTRON TERMINAL BOARD CAPACITOR BLOWER PARTITION BASE PAN TOP PANEL JACKET COLLAR FAN CENTER RELAY LEFT SIDE PANEL JACKET SIDE BAFFLE BLOWER ASSEMBLY COMPLETE POUCH PLATE ASSEMBLY W/CHAMBER

REH750 Part No. 15353 15354 540605B 540850 540800 15739W 15601 15600 15610 15355 15738 552324 15810 15356 15360 15350 712491 710026 710025 710356 710401 15150 310285 712430 15357 15358 15352 15410 552250 15351 15359 15105 15739C

REH1000 Part No. 15453 15454 540607B 540855 540810 15766W 15603 15602 15611 15455 15738 552323 15830 15456 15360 15450 712491 710026 710025 710356 710401 15150 310285 712430 15457 15458 15452 15461 552250 15451 15459 15105 15766C

36

Item No. 1 2 2 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

Qty 1 1 1 1 1 2 2 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 4 1 1 1 1 4 2 1 1 1 1 1 1

Description FRONT PANEL BECKETT BURNER RIELLO BURNER CARLIN BURNER POUCHPLATE ASSEMBLY SIDE POUCHPLATE GASKETS UPPER/LOWER POUCHPLATE GASKETS COMBUSTION CHAMBER TOP PANEL JACKET COLLAR CAPS FAN & LIMIT CONTROL INNER FRONT PANEL HEAT EXCHANGER TOP CHANNEL BLOWER PARTITION BLOWER PARTITION BRACKET FILTER SUPPORT ASSEMBLY REAR PANEL REAR DOOR BLOWER MOTOR BLOWER MOTOR LEG BAND BLOWER MOTOR LEGS BLOWER CAPACITOR ELECTRON TERMINAL BOARD BLOWER WHEEL RUBBER GROMMETS BLOWER LEGS RIGHT SIDE PANEL BASE PAN FAN CENTER RELAY LEFT SIDE PANEL BLOWER ASSEMBLY COMPLETE POUCH PLATE ASSEMBLY W/CHAMBER

REL750 FF Part No. 15303 540605B 540850 540800 15739W 15601 15600 15610 15302 15410 15738 552323 15306 15805 15304 15307 15411 15412 15308 15305 712491 710026 710025 710401 712430 310285 710356 712100 740767 15300 15309 552250 15301 15100 15739C

REL1000 FF Part No. 15403 540607B 540855 540810 15766W 15603 15602 15611 15402 15410 15738 552323 15406 15825 15404 15407 15411 15412 15408 15405 712491 710026 710025 710401 712430 310285 710356 712100 740767 15400 15409 552250 15401 15105 15766C

37

Item No. 1 2 2 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34

Qty 1 1 1 1 1 2 2 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 4 1 1 1 1 4 2 1 1 1 1 1 1

Description FRONT PANEL BECKETT BURNER RIELLO BURNER CARLIN BURNER POUCHPLATE ASSEMBLY SIDE POUCHPLATE GASKETS UPPER/LOWER POUCHPLATE GASKETS COMBUSTION CHAMBER TOP PANEL CAPS FAN & LIMIT CONTROL INNER FRONT PANEL HEAT EXCHANGER TOP CHANNEL BLOWER PARTITION BLOWER PARTITION BRACKET EXTENSION PIPE W/FLANGE FILTER SUPPORT ASSEMBLY JACKET COLLAR REAR PANEL REAR DOOR BLOWER MOTOR BLOWER MOTOR LEG BAND BLOWER MOTOR LEGS BLOWER CAPACITOR ELECTRON TERMINAL BOARD BLOWER WHEEL RUBBER GROMMETS BLOWER LEGS RIGHT SIDE PANEL BASE PAN FAN CENTER RELAY LEFT SIDE PANEL BLOWER ASSEMBLY COMPLETE POUCH PLATE ASSEMBLY W/CHAMBER

REL750 RF Part No. 15303 540605B 540850 540800 15739W 15601 15600 15610 15302 15738 552323 15306 15807 15304 15307 15411 15732W 15412 15410 15308 15305 712491 710026 710025 710401 712430 310285 710356 712100 740767 15300 15309 552250 15301 15100 15739C

REL1000 RF Part No. 15403 540607B 540855 540810 15766W 15603 15602 15611 15402 15738 552323 15406 15827 15404 15407 15411 15760W 15412 15410 15408 15405 712491 710026 710025 710401 712430 310285 710356 712100 740767 15400 15409 552250 15401 15105 15766C

38

Troubleshooting Guide
WARNING This equipment must be serviced, adjusted and started only by a qualified service agency an individual or agency, licensed and experienced with all codes and ordinances, and is responsible for the installation and adjustment of the equipment. Burner Goes Off on Safety

No Oil T ank Full Yes Fill T ank

Bleed Oil Lines Oil flows Freely Yes

No

Fuel Supply Valves Open Yes

No

Open All Supply Valves

Air in Oil Lines No

Yes

Check All Fitting Connections

Oil Filter Clean Yes Pump Strainer Clean

No

Replace Oil Filter

No

Clean or Replace Strainer

Pump Pressure Per Set-up Label Yes

No

Adjust Pressure Per Set-up Label

No

Refer to Burner Manual

Spark Established Yes

No

Ignition Electrode Yes Shorted or Cracked Porcelain


No

Replace Electrodes

Refer to Burner Manual

Nozzle Clean and Matches Preliminary Settings Yes

No

Replace Nozzle

Air Settings Match Preliminary Settings Yes

No

Adjust Air Settings

Refer to Burner Manual for Control T rouble Shooting

39

Burner Will Not Start

T hermostat Set Above Room T emperature


Yes

No

Adjust T hermostat

120 Volts at Furnace


Yes

No

Check Supply Fuses and Disconnects

120 Volts at Burner Control


Yes

No

Fan and Limit Operational


Yes

No

Replace Fan and Limit

Check all Wiring

Burner Off on Safety


Yes

No

Refer to Burner Manual

Refer to Burner Manual

Blower Will Not Start

120 Volts at Blower


No

Yes

Yes Mot or on Overload No

Yes

Check System St at ic Pressure Adjust Motor Pulley Belt Drive Furnaces

Replace Mot or

120 Volts at Furnace


Yes

No

Check Supply Fuses and Disconnect s

Fan and Limit Operational


Yes

No

Replace Fan and Limit

Check all Wiring

40

Boyertown Furnace Limited Warranty


Boyertown Furnace Company, Inc. (Boyertown) hereby warrants to the original consumer purchaser (Purchaser) that all equipment manufactured for and bearing Boyertowns nameplate to be free from defects in workmanship or material for a period of years as indicated below under normal use and service at a firing rate of number (2) oil not exceeding that shown on its rating plate on all models of Boyertown Furnace. If any such equipment sold by Boyertown proves to be defective in workmanship and material and if such part is within the indicated months below from the date of original installation returned to our factory, transportation charges prepaid, said part will be replaced or repaired, free of charge, F.O.B. Factory. Purchasers remedy shall be limited to such repair or replacement and shall be purchasers exclusive remedy. The purchaser, by acceptance of this equipment, will assume all liability for the consequences of its use or misuse by the purchaser, his employees, and all other persons. All warranties are based upon the return of the defective part to the Factory for examination, and purchaser shall assume responsibility and liability for transportation and labor costs.

Boyertown shall not be liable for any consequential damages resulting from breach of this or any other warranty, express or implied. Some states do not allow the exclusion or limitations on relief such as incidental or consequential damages, so the above limitation or
exclusion may not apply to you. Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you.

Model Hallmark Regal

Warranty Period Years 5 1

Warranty Period Months 60 12

Heat Exchanger Residential Single Family Limited Warranty


In addition to the above limited warranty, Boyertown warrants to the original consumer purchaser at the original installation address in a single family dwelling a limited lifetime warranty and adjustment policy on the heat exchanger. In the event that any defect in material and workmanship is found to exist by Boyertown Furnace Company within twenty years (20) of the original installation, Boyertown Furnace Company will at its option, with the serial number and proof of purchase by the original consumer purchaser, furnish a replacement, or repair the heat exchanger. In the event that any defect in material and workmanship is found to exist by Boyertown Furnace Company after twenty (20) years of the original installation, Boyertown Furnace Company will at its option, with the serial number and proof of purchase by the original consumer purchaser, provide a new heat exchanger at fifty percent (50%) of the then current list price, or allow a credit in the amount of fifty percent (50%) of the then current list price of an equivalent heat exchanger toward the list price purchase of an equivalent manufactured Boyertown Furnace Company unit. Proof of purchase will be required of the original purchaser when the claim is made. The purchaser must pay all other costs of warranty services, including labor costs involved in diagnostic calls, or in removing, servicing, or replacing warranty parts and or freight charges.

Heat Exchanger Commercial Limited Warranty


In addition to the above limited warranty, Boyertown warrants to the original consumer purchaser at the original installation address, being other than a single family residence a ten (10) year warranty on the heat exchanger. In the event that any defect in material and workmanship is found to exist by Boyertown Furnace Company within ten years (10) of the original installation, Boyertown Furnace Company will at its option, with the serial number and proof of purchase by the original consumer purchaser, furnish a replacement, or repair the heat exchanger. Proof of purchase will be required of the original purchaser when the claim is made. The purchaser must pay all other costs of warranty services, including labor costs involved in diagnostic calls, or in removing, servicing, or replacing warranty parts and or freight charges.

Any Implied warranty relating to the heat exchanger covered by this warranty, including that of merchantability and fitness for a particular purpose shall be limited to the period of this limited warranty. Boyertown shall not be liable for any consequential damages resulting from breach of this or any other warranty, express or implied. Some states do not allow the exclusion or limitations on relief such as incidental or consequential damages, so the above limitation or
exclusion may not apply to you. Some states do not allow limitations on how long an implied warranty lasts, so the above may not apply to you.

Purchasers Responsibilities
In the event the original consumer purchaser believes there is a defect in material or workmanship, he shall, within thirty (30) days of the discovery of the defect, notify Boyertown in writing. Boyertown or its authorized representative at its option will inspect the furnace and its component parts to determine whether a defect exists and recommend repair or replacement if necessary under the terms of the warranty. If Boyertown determines that no such defect exists, purchaser may still pursue its remedies by commencing a civil action, but must do so within (1) year after the cause accrued. Some states do not allow this (1) year limitation, so it may not be applicable to you. This warranty will not be applicable if the furnace has been damaged as a result of being improperly serviced, or operated, including but not limited to the following: A) If the furnace is used or operated over its rated capacity, as shown on the rating plate, or installed for uses other than residential home heating or commercial heating as listed above. B) The furnace not being connected to an adequate sized supply and return air ducts according to industry standards and/or restrictions of air flow through the furnace and duct system. C) Furnace must be operated in an environment free from the effects of chlorinated hydrocarbons. D) Furnace not being operated during each heating season. E) Damages , defects or other losses that occur in anyway after the furnace or heat exchanger has been tampered with, or altered in any way, except as may be specifically directed in writing by Boyertown Furnace Company, and damages, defects or other losses arising from improper installation, adjustment or servicing of the furnace or heat exchanger. F) No warranty is given to any equipment which has not been installed by a qualified installer according to the regulations of the National Fire Protection Standard for Oil Burning Equipment, NFPA No. 31 and in complete accordance with all existing local codes, regulations, ordinances, and authorities having jurisdiction. A qualified installer is an individual or agency responsible for the installation and adjustment of oil burning equipment. The installer should be licensed and experienced to perform the installation of such equipment according to all codes and ordinances. G) This warranty does not cover expenses for the removal or reinstallation. The purchaser shall be responsible for the cost of removing and reinstalling the defective part including labor and material connected therewith. Upon request of Boyertown, it shall be the obligation of the purchaser to ship prepaid to Boyertown the defective part for inspection or repair. H) This warranty is applicable only to defects in material and workmanship and shall not cover failure of the furnace or any of its component parts due to any other reason including, but not limited to (1) lack of sufficient air flow, (2) floods, (3) fire, (4) acts of God, (5) negligent or improper installation, (6) corrosion of heat exchanger surfaces, (7) leaky gaskets, (8) improper maintenance of external and fire side surfaces.

41

Installation and Service Check List Furnace Model: _______________________ Installation Date: ______________________ Installer Name: ________________________ Furnace Installation Serial No.: ______________________ Phone No.: ______________________

Furnace level and in solid contact with floor? Furnace and burner wired per wiring diagram and National Electric Code? 120VAC wiring Type_____ Size _____ AWG Burner sealed to furnace? Mounting nuts tight? Space is large enough to provide required clearances? NFPA 31 Installation of Oil Burning Equipment followed? Local, state and national codes, laws, regulations and ordinances followed? Existing chimney and vent system inspected to NFPA 211 and in good condition? New vent pipe installed and properly sealed? Vent size checked against furnace manual and codes? Return and supply ducts checked for size based on furnace air flow and ACCA Manual D? All ducts sealed and insulated as required? Burner Model: __________________ Nozzle: _______GPH _______Deg. _______Type_______ Burner Pump Pressure: ______________ Fuel filter and fuel lines installed and inspected as per burner manual? Air bled from oil piping? Piping checked for leaks? Burner started, adjusted and tested per burner manual? Thermostat heat anticipator set per burner manual instructions? Temperature rise through the furnace checked 750F maximum and blower speed adjusted as required? Blower motor amperage does not exceed rated full load amperage? Clean air filter installed? Limit control tested for proper operation? Furnace observed going through several operational cycles for proper operation?

Vent System

Duct Work

Burner Operation

Furnace Operation

Post Installation
Reviewed owners information in this manual with owner or maintenance personnel and instructed to keep for future reference? Properly filled in and returned warranty registration card to Boyertown Furnace Co. Inserted burner manual instructions with furnace manual for future use?

42

Notes

__________________________________________ __________________________________________ __________________________________________ __________________________________________ __________________________________________ __________________________________________ __________________________________________ __________________________________________ __________________________________________ __________________________________________ __________________________________________ __________________________________________ __________________________________________ __________________________________________
--------------Cut and Return This Form or Register Online at www.boyertownfurnace.com----------------------

Warranty Registration
Boyertown Furnace Co. P.O. Box 100 Boyertown, PA 19512 Date Installed: ___________________________ Furnace Model: __________________________ Serial Number: ________________________ Name of Purchaser: _________________________________________________________________________ Purchasers Address: ________________________________________________________________________ ________________________________________________________________________ Dealers Name: _____________________________________________________________________________ Dealers Address: ___________________________________________________________________________ ___________________________________________________________________________