Measuring Instrument
Measuring Instrument
Measuring Instrument
Function
Effects of electric current on
the instruments.
The electrical instruments may, in a broad sense, be classified
according to the manufacturing standards into absolute instruments and
secondary instruments.
Indicating instruments: These instruments, as shown in Figs, indicate the value of voltage, current
power etc. directly on a graduated dial. Ammeters, voltmeters and wattmeter’s belong to this class.
Integrating instruments: These instruments measure the total amount, either the quantity
of electricity or the electrical energy, supplied to a circuit over a period of time. Ampere hour
meters and energy meters belong to this class. Fig shows the Kilowatt hour/energy meter.
Magnetic effect
Heating effect
Chemical effect
Electrostatic effect
Electromagnetic induction effect
The following three forces are essential requirements of
an indicating instrument for its satisfactory operation. They
are-
Deflecting force
Controlling force
Damping force.
This causes the moving system of the instrument to move
from its 'zero' position, when the instrument is connected to
the supply. To obtain this force in an instrument, different
effects of electric current, such as magnetic effect, heating
effect, chemical effect etc. are employed.
How this deflecting force is developed in an instrument will
be explained later while explaining the individual type of
instruments.
This force is essential to control the movement of the moving system and to
ensure that the magnitude of the deflection of the pointer is always the same
for a given value of the quantity to be measured. As such, the controlling
force always acts opposite to the deflecting force, and also brings the pointer
to zero position when the instrument is disconnected from the supply.
The controlling force could be produced by any one of the following ways.
Gravity control & Spring control
Gravity control: In this method, small Spring control: The most common
adjustable weights are attached to the arrangement of spring control utilises two
opposite extension of the pointer . These phosphor-bronze or beryllium-copper spiral
weights are attracted by the earth's hair-springs , the inner ends of which are
gravitational pull, and thereby, produce the attached to the spindle. The outer end of the
required controlling force (torque). The spring is fixed, whereas that of one is attached
instruments with gravity control are to be to the end of a lever pivoted , thereby enabling
used in the vertical position only. the zero adjustment to be easily effected when
needed.
Gravity control Spring control
This force is necessary to bring the moving system to rest in its final
deflected position quickly. Without such damping, the combination
of the inertia of the moving system and the controlling force makes
the pointer (moving system) to oscillate about its final deflected
position for some time before coming to rest, resulting in a waste of
time in taking the reading.
Under damping.
Over damping.
Critical damping.
The damping torque is proportional to the speed of rotation of
the moving system, that is
Driving system
This coil is known as “pressure or voltage” coil and is connected across
the supply mains. This voltage coil has many turns and is arranged to be
as highly inductive as possible. In other words, the voltage coil produces
a high ratio of inductance to resistance.
An adjustable copper shading rings are provided on the central limb of
the shunt magnet to make the phase angle displacement
between magnetic field set up by shunt magnet and supply voltage is
approximately 90 degree.
The copper shading bands are also called the power factor
compensator or compensating loop. The series electromagnet is
energized by a coil, known as “current” coil which is connected in
series with the load so that it carry the load current. The flux
produced by this magnet is proportional to, and in phase with the load
current.
Overview of Single Phase Induction Type Energy Meter
Moving system
The moving system essentially consists of a light rotating aluminium
disk mounted on a vertical spindle or shaft. The shaft that supports the
aluminium disk is connected by a gear arrangement to the clock
mechanism on the front of the meter to provide information that
consumed energy by the load.
The time varying (sinusoidal) fluxes produced by shunt and series
magnet induce eddy currents in the aluminium disc
The number of rotations of the disk is therefore proportional to the
energy consumed by the load in a certain time interval and is
commonly measured in kilowatt-hours (Kwh)
Overview of Single Phase Induction Type Energy Meter
Braking system
Damping of the disk is provided by a small permanent magnet,
located diametrically opposite to the a.c magnets. The disk passes
between the magnet gaps. The movement of rotating disc through the
magnetic field crossing the air gap sets up eddy currents in the disc
that reacts with the magnetic field and exerts a braking torque.
By changing the position of the brake magnet or diverting some of the
flux there form, the speed of the rotating disc can be controlled.
nnn
Working of Single phase induction type Energy Meter
The basic working of Single phase induction type Energy
Meter is only focused on two mechanisms:
i. Mechanism of rotation of an aluminum disc which is
made to rotate at a speed proportional to the power.
ii. Mechanism of counting and displaying the amount of
energy transferred
Working of Single phase induction type Energy Meter
Mechanism of rotation of an aluminum disc
The metallic disc is acted upon by two coils. One coil is
connected 0r arranged in such a way that it produces a
magnetic flux in proportion to the voltage and the other
produces a magnetic flux in proportion to the current. The
field of the voltage coil is delayed by 90 degrees using a lag
coil.
A permanent magnet exerts an opposing force proportional
to the speed of rotation of the disc – this acts as a brake
which causes the disc to stop spinning when power stops
being drawn rather than allowing it to spin faster and faster.
This causes the disc to rotate at a speed proportional to the
power being used
Working of Single phase induction type Energy Meter
THEN
A tachometer (revolution-counter,
Tach, rev-counter, RPM gauge) is an
instrument measuring the rotation
speed of a shaft or disk, as in a motor
or other machine.The device usually
displays the revolutions per minute
(RPM) on a calibrated analogue dial,
but digital displays are increasingly
common.
A multimeter is used to measure voltage
(ac/dc), current or
resistance,capacitor,frequency, electronics
componets, depending upon the function
selected.
A voltmeter is used to measure voltage
across a component or circuit
An ammeter is used to measure current
through a circuit
An ohmmeter is used to measure
resistance
A clamp meter (clamp-on ammeter)
is a type of ammeter which measures
electrical current without the need to
disconnect the wiring through which the
current is flowing.
Clamp meters are also known as tong
testers.
Modern ammeter designs are of digital
type,and use an analog to digital converter
to measure the unknown current which is
shown on a digital display
A handy inexpensive item to add to a tool
box is the one dollar neon tester. It is useful
to identify polarity in DC and identify the
ungrounded conductor in AC circuits.
For DC there is a polarity indicator. In AC
simply hold one end of the tester between
your fingers and touch the other end of the
tester to the conductor to be measured. A
slight glow will be present if you are on the
ungrounded conductor.
Another type of neon tester is the receptacle
outlet tester, a very useful tool for every
electrician. This item, when plugged into an
outlet, will give you detailed indication of
how the receptacle is wired.
A light meter is a device used to
measure the amount of light.
In photography, a light meter is often
used to determine the proper
exposure for a photograph.
Typically a light meter will include a
computer, either digital or analog,
which allows the photographer to
determine which shutte speed and f-
number should be selected for an
optimum exposure, given a certain
lighting situation and film speed.
Oscilloscopes
Oscilloscopes are used to observe the change of an electrical signal
over time, such that voltage and time describe a shape which is
continuously graphed against a calibrated scale. The observed
waveform can be analyzed for such properties as amplitude,
frequency, rise time, time interval, distortion and others
The main purpose of an oscilloscope is to graph an electrical signal as
it varies over time. Most scopes produce a two-dimensional graph with
time on the x-axis and voltage on the y-axis.
Window-type Bar-type
Current Transformers
Function of CT:
The principal function of a CT is to produce a proportional current at a
level of magnitude, which is suitable for the operation of low-range
measuring or protective devices such as indicating or recording instruments
and relays.
The primary and secondary currents are expressed as a ratio such as 100/5
or 1000/5 .
With a 100/5 ratio CT, 100A flowing in the primary winding will result in
5A flowing in the secondary winding, provided that the correct rated
burden is connected to the secondary winding.
Current Transformers Stepping:
These are used with low range ammeters to measure current in high voltage
alternating circuits where it is not practical to connect instrument and
meters directly to lines.
They are step-up transformers (voltage ratio) because when we step-up
the voltage the current decreases.
The current is a step-down in a known ratio called the current ratio .
Connections of Current Transformers
Single-Ratio Multi-Ratio CT
Current Transformers
Working (Measurement):
If a current transformer has primary to secondary current ratio of 100:5 then
it steps up the voltage 20 times and step down the current 1/20 times of its
actual value.
If we know the current ratio and the reading of an a.c. ammeter, the primary current can be calculated as:
Primary Current = CT ratio × ammeter reading
Why CT secondary should never be open ?:
Ammeter resistance is very low ,the current transformer normally works as a
short-circuited instrument.
If for any reason the ammeter is taken out of secondary winding then the
secondary winding must be short-circuited with the help of a short-circuit
switch.
If this is not done, then a high m.m.f. (Ampere-turns IT) will set up a high flux
in the magnetic core and it will produce excessive core loss which produce
heat and high voltage across the secondary terminals .
The high voltage can damage any electronic components in secondary side.
Hence the secondary of any current transformer should never be left open.
Current Transformers
.
100
___ = 100:5 or 20:1
5
Potential Transformers
What is a Potential Transformer (PT) or (VT)
A PT or sometimes called VT is a step-down transformer having many primary turns but few
secondary turns.
In a step-down transformer the voltage decreases and the current increases, thus voltage can be easily
measured by using a low-range voltmeter instrument.
The voltage is stepped-down in a known ratio called the voltage ratio.
Construction and working of P.T.:
Construction
A potential transformer has many primary winding turns but few number of secondary winding turns
that makes it a step-down transformer.
A Voltmeter is connected to the secondary winding is usually a voltmeter of 150 V.
Working (Measurement):
Primary terminals are connected in parallel across the line to which the voltage is to be measured.
The voltmeter reading gives the transformed value of the voltage across the secondary terminals.
The deflection of the voltmeter when divided by the transformed ratio gives the actual voltage across
the primary winding as:
The Line voltage = deflection / transformation-Ratio
Where transformation ratio = V2/V1
Potential Transformers
Precaution for P.T.
Since the secondary of a p.t. is connected to relays, their ratings are
usually 40 to 100 Watts.
For safety purpose the secondary should be completely insulated from
the high voltage primary and should be in addition grounded.
Types of P.T. :
Some types of p.t. are:
Shell type
Dry type
Oil type
Rating Type
1. Below 5000 v Shell type
2. 5000-13800 v Dry type and oil type
3. Above 13800 v only oil type
Basic important rules for Instrument Transformers
Rule # 1
Never open circuit a current transformer secondary
while the primary is energized
CTs are intended to be proportional current devices.
Very high voltages can result from open circuiting the
secondary circuit of an energized CT. Even very small
primary currents can cause damage
Rule # 2
Never short circuit the secondary of an energized VT
VTs are intended to be used as proportional voltage
devices. Damaging current will result from short
circuiting the secondary circuit of an energized VT
Basic important rules for Instrument Transformers
Rule # 3
CT secondary leads must be added to the CT burden
Electronic relays usually represent very little burden to the CT
secondary circuit. In many cases the major burden is caused
by the CT secondary leads.
Rule # 4
Never use a 60 Hz rated VT on a 50 Hz System
60 Hz VTs may saturate at lower frequencies and exceed
temperature limitations. VT failure is likely…severe equipment
damage is possible.
Measurement Errors
Practically all measurements of continuums involve
errors. Understanding the nature and source of these
errors can help in reducing their impact.
Error: It is the deviation of the measured (or indicated) value
from the true (or expected) value of a quantity. In other words,
error is the difference between the measured value and the true
value of the unknown quantity.
The types of errors include:
1. Systematic errors and
2. Random errors.
Systematic errors
Systematic error are deterministic; they may be predicted and
hence eventually removed from data.
Systematic errors may be traced by a careful examination of
the measurement path: from measurement object, via the
measurement system to the observer.
Another way to reveal a systematic error is to use the
repetition method of measurements.
NB: Systematic errors may change with time, so it is
important that sufficient reference data be collected to allow
the systematic errors to be quantified
Random errors
Systematic error are deterministic; they may be predicted
and hence eventually removed from data.
Random error vary unpredictably for every successive
measurement of the same physical quantity, made with
the same equipment under the same conditions.
We cannot correct random errors, since we have no
insight into their cause and since they result in random
(non-predictable) variations in the measurement result.
When dealing with random errors we can only speak of
the probability of an error of a given magnitude.
NB: Random errors are described in probabilistic terms,
while systematic errors are described in deterministic
terms. Unfortunately, this deterministic character makes
it more difficult to detect systematic errors.
Purpose of Calibration
Purpose of Calibration refers to the act of evaluating and adjusting
the precision and accuracy of measurement equipment.
Calibration is a comparison between a known measurement (the
standard) and the measurement using your instrument and
Instrument calibration is one of the primary processes used to
maintain instrument accuracy. Calibration is the process of
configuring an instrument to provide a result for a sample within an
acceptable range
There are three main reasons for having instruments calibrated: To
ensure readings from an instrument are consistent with other
measurement.
To determine the accuracy of the instrument readings. To establish
the reliability of the instrument i.e. that it can be trusted
Purpose of Calibration
The calibration is the procedure for determining the correct values of
measurand by comparison with standard ones. The standard of device
with which comparison is made is called a standard instrument. The
instrument which is unknown & is to be calibrated is called
test instrument. Thus in calibration, test instrument is
compared with standard instrument.
Types of calibration methodologies:
There are two methodologies for obtaining the comparison between test
instrument & standard instrument. These methodologies are
i. Direct comparisons
ii. Indirect comparisons
Purpose of Calibration
Direct comparisons:
In a direct comparison, a source or generator applies a known input to
the meter under test. The ratio of what meter is indicating & the known
generator values gives the meter’ s error.
In such case the meter is the test instrument while the generator is the
standard instrument.
The deviation of meter from the standard value is compared with the
allowable performance limit.
Purpose of Calibration
Indirect comparisons:
In the indirect comparison, the test instrument is compared with the
response
standard instrument of same type i .e., if test instrument is meter,
standard
instrument is also meter, if test instrument is generator; the standard
instrument is also generator & so on.
If the test instrument is a meter then the same input is applied to the test
meter as well a standard meter. In case of generator calibration, the
output of the generator tester as well as standard, or set to same nominal
levels. Then the transfer meter is used which measures the outputs of
both standard and test generator.
Performance characteristics of an instrument
i. Static characteristics
ii. Dynamic characteristics
Static characteristics
The set of criteria defined for the instruments, which are used to measure the
quantities which are slowly varying with time or mostly constant, i.e., do not
vary with time, is called ‘static characteristics’.
The various static characteristics are:
i) Accuracy
ii) Precision
iii) Sensitivity
iv) Linearity
v) Reproducibility
vi) Repeatability
Performance characteristics of an instrument
vii) Resolution
viii) Threshold
x) Stability
xi) Tolerance
xii) Range or span
Accuracy:
It is the degree of closeness with which the reading approaches the true
value of the quantity to be measured.
Precision:
It is the measure of reproducibility i.e., given a fixed value of a quantity
precision is a measure of the degree of agreement within a group of
measurements.
Performance characteristics of an instrument
Sensitivity:
The sensitivity denotes the smallest change in the measured variable to
which the instrument responds. It is defined as the ratio of the changes in
the output of an instrument to a change in the value of the quantity to be
measured.
Linearity:
The linearity is defined as the ability to reproduce the input
characteristics symmetrically & linearly.
Reproducibility:
It is the degree of closeness with which a given value may be repeatedly
measured. It is specified in terms of scale readings over a given period of
time.
Performance characteristics of an instrument
Resolution:
If the input is slowly increased from some arbitrary input value, it will
again be found that output does not change at all until a certain
increment is exceeded.
Threshold:
If the instrument input is increased very gradually from zero there will
be some minimum value below which no output change can be detected.
This minimum value defines the threshold of the instrument.
Stability:
It is the ability of an instrument to retain its performance throughout is
specified operating life.
Performance characteristics of an instrument
Tolerance:
The maximum allowable error in the measurement is specified in
terms of some value which is called Tolerance.
Range or span:
The minimum & maximum values of a quantity for which an instrument
is designed to measure is called its range or span.
Performance characteristics of an instrument
Dynamic characteristics
The set of criteria defined for the instruments, which are changes rapidly
with time, is called ‘dynamic characteristics’.
The various dynamic characteristics are:
i. Speed of response
ii. Measuring lag
iii. Fidelity
iv. Dynamic error
Speed of response:
It is defined as the rapidity with which a measurement system responds
to changes in the measured quantity.
Performance characteristics of an instrument
Measuring lag:
It is the retardation or delay in the response of a measurement system to
changes in the measured quantity.
Fidelity:
It is defined as the degree to which a measurement system indicates
changes in the measured quantity without dynamic error.
Dynamic error:
It is the difference between the true value of the quantity changing with
time & the value indicated by the measurement system if no static error
is assumed. It is also called measurement error.