MVTT 14

Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

Type MVTT 14 and MVTT 15: Static Digital Time delay relays

Features
1000/1 setting range Time settings easily selected by means of thumbwheel switches Provide time delayed pick-up, or drop-off Compact construction Non-volatile trip indication (MVTT 14 only)

Application
This range of static time delay relays is particularly suitable for use in protection and control schemes and industrial process plant. The relays can perform with consistent accuracy over a large number of operations, with little or no maintenance over long periods. Furthermore, the static circuits have been designed to perform with complete reliability in the electrically hostile environments often encountered in electrical power stations and substations and also over a very wide range of ambient temperature.

Type variations
Model for time delayed operation on Pick-up Drop-off MVTT 14 MVTT 15

Auxiliary supplies: Five dc supply ranges are available Timing ranges: Five standard timing ranges are available

Figure 1 Type MVTT 14 relay removed from case

MVTT 14/15
506

Description
Type MVTT 14 with timedelayed pick-up
As shown in Figure 2, the MVTT 14 relay is initiated by an external contact which connects the dc supply to relay terminal 13. The dc supply is permanently connected to relay terminals 21 and 14. The closure of the external contact causes the counter to be reset immediately and starts the CMOS oscillator which generates a square wave output to the binary coded decimal counter. The required time delay is preset by adjusting the three binary coded decimal thumbwheel switches. Each thumbwheel switch output to the associated counter provides a successive decade setting of between 0 and 9. When the comparator detects that the accumulated count has reached the set count determined by the thumbwheel settings, then the output element is energised and the internal oscillator inhibited. The relay resets instantaneously when the external contact is reopened.

Type MVTT 15 with time delayed drop-off


As shown in Figure 3 the MVTT 15 versions have similar circuits to the MVTT 14. The dc supply is continuously applied to the relay. Closing the external initiating contact causes the relay output element to pick-up instantaneously. The drop-off time delay is initiated by opening this contact which starts the CMOS oscillator. The output element remains in the energised state until the comparator detects that the accumulated count has reached the set count, determined by the thumbwheel settings. At this instant the output element is de-energised, thus removing the dc to the dc regulator circuit by opening the internal hold-on contact (RL 6-1).

Power supplies
Relays designed for power supplies of 220/250V dc are supplied with an external assembly for connection in series with the dc auxiliary supply to the relay.

Inhibit oscillator Counter reset circuits


21 13 14

RL1

5 1 3

+ Vx in Case earth
1 3 5 7 9 11 13 2 4 6 8 10 12 14

Close to start timer

RL2 RL1 RL2 RL3 RL4 OP

11 7 9

Output contacts

Power supply circuits

Oscillator

Binary coded decimal counter

Comparator

Output circuits

0v

R ext(2) See Note 4

9 9 9
See Note 2 secs Binary coded decimal switches Notes 1 (a) (b) (c) CT shorting links make before (b) & (c) disconnect Short terminals break before (c) Long terminals

Reset

RL5 1 RL3
12 8 10

RL4

6 2 4

Output contacts

21

22

3 Connections are applicable for 24/27, 30/34, 48/54 7 110/125V 4 Rext(2) is required for MVTT14 to meet ES1484 class 2. (Not applicable to 24/27V version)

Module terminal block viewed from rear

Figure 2

Application diagram: digital time delay relay type MVTT 14 (dc version)

507

MVTT 14/15

2 Earthing connections as shown are typical only

Open to start timer

21 22

Inhibit reset circuit RL61

Inhibit oscillator

Reset counter RL1 Binary coded decimal counter


RL1 RL2 RL3 RL4 RL6

5 1 3

Vxin

13 14

0V R ext(2) See Note 4

Power supply circuits

Oscillator

Comparator

RL2

11 7 9

Output contacts

Case earth
1 3 5 7 9 11 13 2 4 6 8 10 12 14

9 9
Case earth

Output circuits RL3


12 8 10

9
secs Binary coded decimal switches

RL4

6 2 4

Output contacts

21

22

Notes 1 (a) (b) (c)

CT shorting links make before (b) & (c) disconnect Short terminals break before (c) Long terminals

2 Earthing connections as shown are typical only 3 Connections are applicable for 24/27, 30/34, 48/54 7 110/125V 4 Rext(2) is required for MVTT15 to meet ES1484 class 1. (Not applicable to 24/27V version)

Module terminal block viewed from rear

Figure 3

Application diagram: digital time delay relay type MVTT 15 (dc version)

Close to start timer V start + _ 0V Case earth


1 3 5 7 9 11 13 2 4 6 8 10 12 14

Inhibit oscillator Counter reset circuit


13 21 14

RL1

5 1 3

Vx in

HN0079

Vx out

Power supply circuits

Oscillator

Binary coded decimal counter

Comparator

Output circuits OP

RL1 RL2 RL3 RL4 Reset RL5 1

RL2

11 7 9

Output contacts

9 9 9
Case earth See Note 2 secs Binary coded decimal switches Notes 1 (a) (b) CT shorting links make before (b) & (c) disconnect Short terminals break before (c) Long terminals

RL3

12 8 10

RL4

6 2 4

Output contacts

MVTT 14/15
508

21

22

Module terminal block viewed from rear

(c)

2 Earthing connections as shown are typical only

Figure 4

Application diagram: digital time delay relay type MVTT 14 220V (dc version)

Figure 5

Application diagram: digital time delay relay, type MVTT 15 220V (dc version)

Standard setting ranges

Technical Data
Voltage rating
Rating (Vx) 24/27 30/34 48/54 110/125 220/250 Operating range Vdc 19 to 32 24 to 37.5 38 to 60 87 to 150 175 to 300

1ms to 1s in 1ms steps 10ms to 10s in 10ms steps 0.1s to 100s in 0.1s steps 1s to 1000s in 1s steps 10s to 10000s in 10s steps

Accuracy
2% of setting or +20ms -0ms, whichever is the greater Consistency 0.5% or 5ms, whichever is the greater

Burdens
DC Burden (mA) Rated Voltage Vx 24 30 48 110 220 Output Elements MVTT 14 15 25 25 10 65 Unoperated MVTT 15 15 25 25 10 65 Output Elements MVTT 14 120 125 85 40 65 Operated MVTT 15 110 120 75 35 65

Disengaging time Resetting time

<10ms <20ms

Contacts

MVTT 15 Output element : Miniature relay Contacts: 4 change-over

509

MVTT 14/15

MVTT 14 Output element : Miniature relay Contacts: 4 change-over

Contact ratings
Make and carry for 0.2s ac 7500VA with maxima of 30A or 300V 5A 5A 1250VA with maxima of 5A and 300V 50W (resistive) 25W (inductive) L/R =0.04s with maxima of 5A or 300V

Electrical environment
DC supply interruption IEC 255-11:1979 The unit will withstand a 10ms interruption in the auxiliary supply, under normal operating conditions, without de-energising. AC ripple on dc supply IEC 255-11:1979 The unit will withstand 12% ac ripple on the dc supply. High frequency disturbance IEC 255-22-1:1988 Class III 2.5kV peak between independent circuits and between independent circuits and case earth 1.0kV peak across terminals of the same circuit (except metallic contacts). Under the conditions created by this test an additional tolerance of 3% is allowed. Electrostatic discharge IEC 255-22-2:1989 Class II 4kV discharge in air with cover in place IEC 801-2:1991 Level 2 4kV point contact discharge with cover removed Fast transient disturbance IEC 255-22-4:1992 Class IV 4kV, 2.5 kHz applied directly to auxiliary supply IEC 801-4:1988 Level 4 4kV, 2.5 kHz applied directly to all inputs Surge immunity IEC 1000-4-5:1995 Level 3 2kV peak 1.2/50s between all groups and case earth 2kV peak, 1.2/50s between terminals of each group EMC compliance 89/336/EEC Compliance to the European Commission Directive on EMC is claimed via the Technical Construction File route EN 50081-2:1994 EN 50082-2:1995 Generic Standards were used to establish conformity

Product safety
73/23/EEC Compliance with the European Commission low voltage directive EN 61010-1:1993/A2:1995 EN 60950:1992/A3:1995 Compliance is demonstrated by reference to generic safety standards

Make and carry continuously ac dc Break ac dc

Atmospheric environment
Temperature IEC 255-6:1988 Storage and transit -25 to +70C Operating -25C to 55C IEC 68-2-1:1990 IEC 68-2-2:1974 Cold Dry heat

Durability
Loaded contact 10,000 operations minimum Unloaded contact 100,000 operations minimum

Under the conditions created by this test an additional tolerance of 3% is allowed. Humidity IEC 68-2-3:1969 56 days at 93% RH and 40C Under the conditions created by this test an additional tolerance of 3% is allowed. Enclosure Protection IEC 529:1989 IP50 (dust protected)

Operation indicator
A non-volatile, hand-reset led trip indicator is supplied as standard on the MVTT 14 (delay on pick-up) only.

High voltage withstand


Dielectric withstand IEC 255-5:1977 2kV rms for 1 minute between all terminals and case earth. 2kV rms for 1 minute between all terminals of independent circuits, with terminals on each independent circuit connected together. 1kV rms for 1 minute across normally open contacts. High voltage impulse IEC 255-5:1977 Three positive and three negative impulses of 5kV peak, 1.2/50ms, 0.5J between all terminals of the same circuit (except output contacts), independent circuits, and all terminals connected together and case earth.

Mechanical environment
Vibration IEC 255-21-2:1988 Response Class 2 Endurance Class 2 Shock and bump IEC 255-21:1988 Shock response Class 2 Shock withstand Class 1 Bump Class 1 Seismic IEC 255-21:1993 Class 2

MVTT 14/15
510

Environmental withstand
Temperature IEC 6821/IEC 6822 Storage and transport 25C to +70C Operating 25C to +55C Humidity IEC 6823 56 days (at 93% RH and 40C) Enclosure protection IEC529 IP50 (dust protected) Vibration IEC 255211 0.5g between 10 and 300Hz
177 157 max. 32 45

4 holes 4.4

13 24

168

159

Push button projection 10 max

48 Panel cut-out: Flush mounting fixing details 212 25 min.

Reset

Cases
MVTT 14 and MVTT 15 relays are housed in size 2 cases as shown in Figure 6

51

Flush mounting

All dimensions in mm

Figure 6

Case outline size 2

Information Required with Order


Relay type Voltage rating Timing range required

511

MVTT 14/15

You might also like