MVTT 14
MVTT 14
MVTT 14
Features
1000/1 setting range Time settings easily selected by means of thumbwheel switches Provide time delayed pick-up, or drop-off Compact construction Non-volatile trip indication (MVTT 14 only)
Application
This range of static time delay relays is particularly suitable for use in protection and control schemes and industrial process plant. The relays can perform with consistent accuracy over a large number of operations, with little or no maintenance over long periods. Furthermore, the static circuits have been designed to perform with complete reliability in the electrically hostile environments often encountered in electrical power stations and substations and also over a very wide range of ambient temperature.
Type variations
Model for time delayed operation on Pick-up Drop-off MVTT 14 MVTT 15
Auxiliary supplies: Five dc supply ranges are available Timing ranges: Five standard timing ranges are available
MVTT 14/15
506
Description
Type MVTT 14 with timedelayed pick-up
As shown in Figure 2, the MVTT 14 relay is initiated by an external contact which connects the dc supply to relay terminal 13. The dc supply is permanently connected to relay terminals 21 and 14. The closure of the external contact causes the counter to be reset immediately and starts the CMOS oscillator which generates a square wave output to the binary coded decimal counter. The required time delay is preset by adjusting the three binary coded decimal thumbwheel switches. Each thumbwheel switch output to the associated counter provides a successive decade setting of between 0 and 9. When the comparator detects that the accumulated count has reached the set count determined by the thumbwheel settings, then the output element is energised and the internal oscillator inhibited. The relay resets instantaneously when the external contact is reopened.
Power supplies
Relays designed for power supplies of 220/250V dc are supplied with an external assembly for connection in series with the dc auxiliary supply to the relay.
RL1
5 1 3
+ Vx in Case earth
1 3 5 7 9 11 13 2 4 6 8 10 12 14
11 7 9
Output contacts
Oscillator
Comparator
Output circuits
0v
9 9 9
See Note 2 secs Binary coded decimal switches Notes 1 (a) (b) (c) CT shorting links make before (b) & (c) disconnect Short terminals break before (c) Long terminals
Reset
RL5 1 RL3
12 8 10
RL4
6 2 4
Output contacts
21
22
3 Connections are applicable for 24/27, 30/34, 48/54 7 110/125V 4 Rext(2) is required for MVTT14 to meet ES1484 class 2. (Not applicable to 24/27V version)
Figure 2
Application diagram: digital time delay relay type MVTT 14 (dc version)
507
MVTT 14/15
21 22
Inhibit oscillator
5 1 3
Vxin
13 14
Oscillator
Comparator
RL2
11 7 9
Output contacts
Case earth
1 3 5 7 9 11 13 2 4 6 8 10 12 14
9 9
Case earth
9
secs Binary coded decimal switches
RL4
6 2 4
Output contacts
21
22
CT shorting links make before (b) & (c) disconnect Short terminals break before (c) Long terminals
2 Earthing connections as shown are typical only 3 Connections are applicable for 24/27, 30/34, 48/54 7 110/125V 4 Rext(2) is required for MVTT15 to meet ES1484 class 1. (Not applicable to 24/27V version)
Figure 3
Application diagram: digital time delay relay type MVTT 15 (dc version)
RL1
5 1 3
Vx in
HN0079
Vx out
Oscillator
Comparator
Output circuits OP
RL2
11 7 9
Output contacts
9 9 9
Case earth See Note 2 secs Binary coded decimal switches Notes 1 (a) (b) CT shorting links make before (b) & (c) disconnect Short terminals break before (c) Long terminals
RL3
12 8 10
RL4
6 2 4
Output contacts
MVTT 14/15
508
21
22
(c)
Figure 4
Application diagram: digital time delay relay type MVTT 14 220V (dc version)
Figure 5
Application diagram: digital time delay relay, type MVTT 15 220V (dc version)
Technical Data
Voltage rating
Rating (Vx) 24/27 30/34 48/54 110/125 220/250 Operating range Vdc 19 to 32 24 to 37.5 38 to 60 87 to 150 175 to 300
1ms to 1s in 1ms steps 10ms to 10s in 10ms steps 0.1s to 100s in 0.1s steps 1s to 1000s in 1s steps 10s to 10000s in 10s steps
Accuracy
2% of setting or +20ms -0ms, whichever is the greater Consistency 0.5% or 5ms, whichever is the greater
Burdens
DC Burden (mA) Rated Voltage Vx 24 30 48 110 220 Output Elements MVTT 14 15 25 25 10 65 Unoperated MVTT 15 15 25 25 10 65 Output Elements MVTT 14 120 125 85 40 65 Operated MVTT 15 110 120 75 35 65
<10ms <20ms
Contacts
509
MVTT 14/15
Contact ratings
Make and carry for 0.2s ac 7500VA with maxima of 30A or 300V 5A 5A 1250VA with maxima of 5A and 300V 50W (resistive) 25W (inductive) L/R =0.04s with maxima of 5A or 300V
Electrical environment
DC supply interruption IEC 255-11:1979 The unit will withstand a 10ms interruption in the auxiliary supply, under normal operating conditions, without de-energising. AC ripple on dc supply IEC 255-11:1979 The unit will withstand 12% ac ripple on the dc supply. High frequency disturbance IEC 255-22-1:1988 Class III 2.5kV peak between independent circuits and between independent circuits and case earth 1.0kV peak across terminals of the same circuit (except metallic contacts). Under the conditions created by this test an additional tolerance of 3% is allowed. Electrostatic discharge IEC 255-22-2:1989 Class II 4kV discharge in air with cover in place IEC 801-2:1991 Level 2 4kV point contact discharge with cover removed Fast transient disturbance IEC 255-22-4:1992 Class IV 4kV, 2.5 kHz applied directly to auxiliary supply IEC 801-4:1988 Level 4 4kV, 2.5 kHz applied directly to all inputs Surge immunity IEC 1000-4-5:1995 Level 3 2kV peak 1.2/50s between all groups and case earth 2kV peak, 1.2/50s between terminals of each group EMC compliance 89/336/EEC Compliance to the European Commission Directive on EMC is claimed via the Technical Construction File route EN 50081-2:1994 EN 50082-2:1995 Generic Standards were used to establish conformity
Product safety
73/23/EEC Compliance with the European Commission low voltage directive EN 61010-1:1993/A2:1995 EN 60950:1992/A3:1995 Compliance is demonstrated by reference to generic safety standards
Atmospheric environment
Temperature IEC 255-6:1988 Storage and transit -25 to +70C Operating -25C to 55C IEC 68-2-1:1990 IEC 68-2-2:1974 Cold Dry heat
Durability
Loaded contact 10,000 operations minimum Unloaded contact 100,000 operations minimum
Under the conditions created by this test an additional tolerance of 3% is allowed. Humidity IEC 68-2-3:1969 56 days at 93% RH and 40C Under the conditions created by this test an additional tolerance of 3% is allowed. Enclosure Protection IEC 529:1989 IP50 (dust protected)
Operation indicator
A non-volatile, hand-reset led trip indicator is supplied as standard on the MVTT 14 (delay on pick-up) only.
Mechanical environment
Vibration IEC 255-21-2:1988 Response Class 2 Endurance Class 2 Shock and bump IEC 255-21:1988 Shock response Class 2 Shock withstand Class 1 Bump Class 1 Seismic IEC 255-21:1993 Class 2
MVTT 14/15
510
Environmental withstand
Temperature IEC 6821/IEC 6822 Storage and transport 25C to +70C Operating 25C to +55C Humidity IEC 6823 56 days (at 93% RH and 40C) Enclosure protection IEC529 IP50 (dust protected) Vibration IEC 255211 0.5g between 10 and 300Hz
177 157 max. 32 45
4 holes 4.4
13 24
168
159
Reset
Cases
MVTT 14 and MVTT 15 relays are housed in size 2 cases as shown in Figure 6
51
Flush mounting
All dimensions in mm
Figure 6
511
MVTT 14/15