SYSTEM PROTECTION
I. FUSE COORDINATION
I.1. GENERAL I.1.1. The purpose of protective coordination is to provide isolation of a fault as close to the fault as possible so that a minimum of customers will be affected. The workhorse of the JEA protection scheme is the fuse. By following the fuse tables given in this section, the fuse closest to a fault will melt first providing proper coordination and fault isolation. I.1.2. The fuse tables are divided into three major groups: I.1.2.1. GROUP A Lateral Fusing This shows the required fuses for the fusing of laterals and sub-laterals. Tables for overhead and underground laterals behind substation breakers and reclosers are given for each system voltage. I.1.2.2. GROUP B: Equipment Protection Fusing This provides the fuse sizes for the protection of transformers and capacitors. I.1.2.3. GROUP C: Fuse Coordination This has various tables for coordinating one type of fuse link behind another type of fuse link. I.1.3. In order to maintain a properly functioning fuse coordination system, the fuse tables presented in this section must be followed in both system design and maintenance. I.1.4. If an installed fuse will not hold the connected load and a larger fuse is installed, the party installing the larger size fuse shall notify the USC System Analysis Process of (1) the location, (2) the old fuse size, and (3) the new fuse size. I.1.5. If a fuse is replaced with a different size fuse because the required size was not available, the party installing the different size fuse shall notify the Systems Operation Control Center so the proper size fuse can be reinstalled.
SYSTEM PROTECTION
VI. 3. - Page 1 of 14
II.2.
SYSTEM PROTECTION
VI. 3. - Page 2 of 14
UNDERGROUND LATERAL FUSING (E-LINK) 26.4 kV System Behind Station Breaker TAP OFF MAIN LINE 150E 1ST SUB-LATERAL FUSE 100E 2ND SUB-LATERAL FUSE 50E
SYSTEM PROTECTION
VI. 3. - Page 3 of 14
RECLOSER NUMBER
R-1 R-2 R-3 R-4 R-5 R-6 R-7 R-8 R-9 R-10 R-11 R-12 R-13 R-14 R-15 R-16 R-17 R-18 R-19 R-20 R-21 R-22 R-23 R-24 R-25 R-26 R-27 R-28 R-29 R-30 R-31 R-32 R-33 R-34 R-35 R-36 R-37 R-38 R-39 R-40 R-41 R-42 R-43 R-44 R-45
CONDUCTOR 4 CU.
80T 80T
80T 80T 80T 80T 80T 80T 80T 80T 80T 80T 80T 80T 80T 80T 80T 80T 80T 80T 80T 80T 80T 80T 50T 50T 50T 25T 65T 65T 30T 25T 25T 25T
65T 65T 65T 65T 65T 65T 65T 65T 65T 65T 65T 65T 65T 65T 65T 65T 65T 65T 65T 65T 65T 65T 50T 50T 50T 25T 65T 65T 30T 25T 25T 25T
100T 100T 100T 80T 80T 80T 100T 80T 100T 100T 80T 100T 100T 80T 80T 80T 100T 100T 100T 100T 100T 100T 50T 50T 50T 25T 65T 65T 30T 25T 25T 25T
SYSTEM PROTECTION
VI. 3. - Page 4 of 14
RECLOSER NUMBER
R-1 R-2 R-3 R-4 R-5 R-6 R-7 R-8 R-9 R-10 R-11 R-12 R-13 R-14 R-15 R-16 R-17 R-18 R-19 R-20 R-21 R-22 R-23 R-24 R-25 R-26 R-27 R-28 R-29 R-30 R-31 R-32 R-33 R-34 R-35 R-36 R-37 R-38 R-39 R-40 R-41 R-42 R-43 R-44 R-45
1ST SUBLATERAL
50E 50E
2ND SUBLATERAL
25E 25E
100E 100E 100E 50E 50E 50E 100E 50E 100E 100E 50E 100E 100E 50E 50E 50E 100E 100E 100E 100E 100E 100E 25E 25E 25E 20E 50E 50E 25E 20E 20E 20E
50E 50E 50E 25E 25E 25E 50E 25E 50E 50E 25E 50E 50E 25E 25E 25E 50E 50E 50E 50E 50E 50E 15E 15E 15E 15E 25E 25E 15E 15E 15E 15E
SYSTEM PROTECTION
VI. 3. - Page 5 of 14
IV.
15T 25T
TRANSFORMER KVA 1-PHASE OH/UG 5 10 15 25 37.5 50 75 100 167 250 KVA 3 PHASE PADS 75 150 225 300 500 750 1000 1500 2500 3750
(1) FUSE LINKS Overhead applies to pole mounted transformers as well as padmounted transformers not equipped with BAY-O-NET fuses that are fused at the cable pole. See Group A General Comments on underground laterals.
SYSTEM PROTECTION
VI. 3. - Page 6 of 14
TRANSFORMER KVA FULL KVA 3 PHASE LOAD 1 PHASE PADS AMPS 5 .66 10 1.31 15 1.97 25 3.28 37.5 4.92 50 150 6.56 75 225 9.84 100 300 13.12 167 500 21.92 250 750 32.80 333 1000 43.70 500 1500 65.60
(1) FUSE LINKS Overhead applies to pole mounted transformers as well as padmounted transformers not equipped with BAY-O-NET fuses that are fused at the cable pole. See Group A general comments on underground laterals. TABLE 4: TRANSFORMER FUSING -- 2.4/4.16kV
TRANSFORMER FULL KVA LOAD 1 PHASE AMPS 3 1.25 5 2.08 7.5 3.13 10 4.17 15 6.25 25 10.42 37.5 15.60 50 20.80 75 31.30 100 41.70 167 69.60 250 104.00 333 139.00 500 208.00 FUSE LINKS - OVERHEAD JEA ITEM ID FUS OH 022 FUS OH 023 FUS OH 024 FUS OH 025 FUS OH 027 FUS OH 028 FUS OH 029 FUS OH 030 FUS OH 031 FUS OH 032 FUS OH 033 FUS OH 034 FUS OH 035 FUS OH 036 CHANCE TYPE 1.6 SF 2.1 SF 3.1 SF 4.2 SF 7.0 SF 10.4 SF 14 SF 21 SF 32 SF 46 SF 100 MS 125 MS 150 MS 200 MS KEARNEY TYPE 2-1/2 X 3-1/2 X 4X 5-1/2 X 10 X 15 X 25 KS 30 KS 50 KS 65 KS 100 KS 125 KS 150 KS 200 KS COOPER TYPE -----25 S 30 S 50 S 65 S 100 S 125 S 150 S 200 S
SYSTEM PROTECTION
VI. 3. - Page 7 of 14
100T 80 50 50
80T 65 40 40
65T 50 30 30
30T 25 12 12
25T 20 12 12
20T 15 10 10
150E 100 65 80
100E 50 30 40
80E 50 25 30
30E 20 12 12
25E 15 10 10
20E 15 10 8
SYSTEM PROTECTION
VI. 3. - Page 8 of 14
UVF4
DIMENSIONS: h 55 W 43 F 56-3/4 D 59-3/4 ITEM FUSAS001 LOCPA001 QTY 1 2 DESCRIPTION FUSE ASSEMBLY, PADMOUNT THREE PHASE IN / OUT PADLOCK, BRASS 1-3/4 IN. SHANK OPENING
SYSTEM PROTECTION
VI. 3. - Page 9 of 14
UVF5 * _
QTY 1 1 1 1
NOTES: 1. All automatic reset fault indicators have a 32 second inrush restraint time delay and a 7.5 min. reset time delay. 2. Fault indicators are to be installed as follows: a. Preferred: Install fault indicator below the terminator stress cone and above the concentric neutral basket. Fault indicator core must be under the drain wire. b. Alternate: Install fault indicator over the concentric neutral basket where the neutrals are bent back and bound.
SYSTEM PROTECTION
VI. 3. - Page 10 of 14
ELBOW ARRESTOR
NOTE: Plate UVF6 for 26.4 kV, UWF6 for 13.2 kV, and URF6 for 4.16 kV ITEM ARREL--BUSWI001 COBCO028 QTY 1 1 5 DESCRIPTION ARRESTOR, ELBOW, METAL OXIDE VARRISTER BUSHING, PLUG INSERT 25KV LOADBREAKER 200 AMP CONDUCTOR, BARE CU, #4AWG SOL SOFT DRAW
SYSTEM PROTECTION
VI. 3. - Page 11 of 14
UVF7
QTY 2 3 2 1
DESCRIPTION ARRESTER, ELBOW METAL OXIDE VARRISTER CONDUCTOR, BARE CU, #4AWG SOL SOFT DRAW CONNECTOR, SPLIT BOLT 2 - 1/0 CU RECEPTACLE, FEED THRU 25KV LOADBREAK
SYSTEM PROTECTION
VI. 3. - Page 12 of 14
UVF8
ITEM ARREL001 BOLMS017 CLATG001 CLAHL001 COBCO029 ENCOD004 LOCPA001 RECPA004 WASSF003
QTY 6 4 5 6 20 1 1 6 4
DESCRIPTION ARRESTER, ELBOW METAL OXIDE VARRISTER BOLT, MACHINE SQ. HEAD 5/8 X 8 IN. CONNECTOR, TRANSFORMER TANK GROUND CLAMP, HOTLINE #6 SOL. - 1/0 STR. CONDUCTOR, BARE CU, #2AWG SOL HARD DRAW ENCLOSURE, THREE PHASE JUNCTION/ ARRESTER PADLOCK, ALL BRASS 1 - 3/4 IN SHANK OPENING RECEPTACLE, FEED THRU 25KV LOADBREAKER WASHER, SQ. FLAT FOR 5/8 OR 3/4 IN. BOLT
SYSTEM PROTECTION
VI. 3. - Page 13 of 14
UVF9
NOTES: 1. Enclosure comes equipped with two (2) parking stand mounting plates and one (1) universal junction module mounting plate. 2. Itemize the accessories you wish to mount in the enclosure. EXAMPLES: FEED-THRU BUSHING I.RECPA004 3 POINT JUNCTION MODULE I.JUNL0XXX 4 POINT JUNCTION MODULE I.JUNL0XXX 3. Use pad plate UPD1 * ITEM ENCOD007 LOCPA001 ANCSD001 RECPA004 QTY 1 1 4 1 DESCRIPTION ENCLOSURE, SINGLE PHASE JUNCTION PADLOCK, ALL BRASS 1 - 3/4 IN SHANK OPENING ANCHOR, CONCRETE BUSHING, FEED-THRU
SYSTEM PROTECTION
VI. 3. - Page 14 of 14