Compilance Sheet - DQGAM C1760D5E C1760D5

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 6

QUESTION

General description and characteristics of engine- generating sets, standards with


which components comply, site rating and overload capability, overall efficiency, and
fuel and lubricant consumption at 100%, 75%, 50% and 25% of rated load.

Description and operating criteria of engine; type, model, manufacturer, fuel and
lubricating oil types and specific consumption, starting conditions and starting periods
from cold to full-load pick-up, governor and response characteristics due to sudden
load changes, super-charger, fuel injection system, cooling system and radiator, air
filters, fuel filters, oil filters and pumps.

Dimensioned outline plan and elevation drawings of engine generator set and other
components specified, weights and forces, mounting methods, vibration protection
etc.

Control instruments, protection, alarms, cut-outs, indicating lamps, indicating


instruments and all other devices or components.

10. Time-current characteristic curves for generator protective device.


11. Synchronization system where specified for two or more sets are in parallel,
including technical data, instruments, governor and voltage regulation, with
characteristic curves etc.

Manufacturer Seismic Qualification Certification: Submit certification that [day


tank,]engine generatorset, batteries, battery racks, accessories, and components will
withstand seismic forces defined in Section 260548 "Vibration and Seismic Controls
for Electrical Systems." Include the following:
1. Basis for Certification: Indicate whether withstand certification is based on actual
test of assembled components or on calculation.
a. The term "withstand" means "the unit will remain in place without separation of
any parts from the device when subjected to the seismic forces specified and the unit
will be fully operational after the seismic event."
2. Dimensioned Outline Drawings of Equipment Unit: Identify center of gravity and
locate and describe mounting and anchorage provisions.

Local Representative: Provide evidence that proposed equipment manufacturer has a


locally established and authorized organization which can be called upon for
professional advice and maintenance as may be required, and which can immediately
supply spare parts to support day to day and emergency maintenance requirements.
Failure to satisfy Engineer may disqualify a manufacturer.
B. Standards: Equipment
A. Spare Parts: Provide list of manufacturer’s recommended spare parts for
1000hours operation of
the plant. Provide list of manufacturer's spare parts for 2000 hours operation
together with current prices..
B. Tools and Instruments: Provide list of tools and instruments required for normal
routine
inspection, testing, operation and general maintenance, as recommended by the
manufacturer.

A. Performance Class: Diesel generator set shall be class G3 (15% voltage drop / free
drop at 100% loading) to ISO 8528-1.
F. Load Shedding: An automatic microprocessor based load shedding system shall be
provided for load connection / disconnection according to load priorities and
generator power availability as described on the drawings.

2.7.D. Power Monitoring system: Control and electrical Data Acquisition system shall
be provided by generators supplier including but not limited to the following: an
industrial computer system along with HMI screen that monitors and controls all data
related to generators operation, Automatic Transfer switches and synchronization
panel.

E. This system shall be provided with a software licensed to gather and analyze real-
time data. Allow for trending, graphic display, alarm tracking, recording and reporting
of data.

G. Provide Controls to enable to change priority of the loads via color touch screen
Operator Interface Panel (Terminal) which shall comprise a microprocessor-based,
password protected, video touch-screen panel allowing facility operators the ability to
change set points and time
delays.

2.5.D.9. Class H for stator and class H for rotor & exciter, with class F temperature
rise,
2.7.J.i Low Day-tank Level: Trouble alarm indication.

2.8.A.1. Construction of Sound Proof enclosure: Galvanized steel ?


AUTOXPERT COMMENTS

Comply and you can find those informations in the data sheet
of the Gesnets already Shared

Comply and you can find those informations in the data sheet
of the Gesnets already Shared. Engine can run on cold start
and takes sudden load and full load pickup. QSK50 & QSK60
are equipped with ECM while KTA50 is hydromechanical
engine. Oher information are included in our quotation and
datasheets provided

Comply, Check Shared Documents :C1760D5 - Outline


Drawinngs - A072N984_Outline_DS47138696,C1760D5E -
A068D968 - Outline Drawings, DQGAM - Outline Drawings -
A055G670

Comply, Check Shared Documents:C1760D5 - Wiring


Drawings - A072P527, C1760D5E - A050T378 - Wiring
Drawings, DQGAM - Wiring Drawings - A028U330

Comply, Check Shared Documents C1760D5 - Alternator Data


Sheet - ESA062L870 , DQGAM, C1760D5E - Alternator Data
Sheet - ads-333

Comply and you can find the seismic certification informations


in the data sheet of the Gesnets already Shared

You can find the Cummins Authorized Distributor Document


to prove the same clause.
Comply, We have included them with the today's submission.
Tools for C1760D5 will be sent later

Comply

do not Comply, A PLC is needed from your end to manage


required customer's sequence of operation.

Our Gensets are equipped with HMI to Monintor data and


adjust the parameters and logg data using inpower application
to register variables and statuses.

Out of our scope. It is related to BMS.

PCC can bi configured to take those data but again this is


related to PLC and BMS to be included within your offer.

PCC provide a wide range of free configuration digital and


analog inputs to receive signal from sensors and get the
needed input source.
PCC is equipped is equipped with load shedding system.
How many steps of load shedding?

can we extract data from PCC, such as :Load, Frequency,


voltage, etc… in other words, does it register data

can we connect a signal from day tank (via a level sensor) to


PCC to get an alarm. Does it contain inputs that can be used?