Error when loading the project into an HMI Panel with Firmware adaption
Why does loading the configuration with Firmware adaption into a SIMATIC HMI-Panel fail?
Behavior
Description
Procedure depending on the type of error message
1. Missing Panel Image
2. Error during transmission
Behavior
An error-free compiled configuration cannot be loaded onto the HMI control Panel (Basic, Comfort, Mobile or Unified Panel).
Description
A project for an HMI control Panel is translated without errors. A message appears in the "Load preview" that the configured Panel Image version differs from the version
installed on the HMI control Panel:
"Components with a different version are installed on the target device."
"A more recent compatible Runtime exists on the target device." or "An older incompatible firmware image exists on the target device."
Fig. 01
Fig. 02
Cause
Before loading Panel, a corresponding "Panel Image" must be installed on the Engineering PC. As of TIA Portal V16, the Firmware Images of the HMI Panels are
supplied separately from the TIA Portal installation and are no longer installed automatically. The Setups for the "WinCC Panel Images" are therefore provided
separately from V16 onwards.
Procedure
Fig. 03
Cause
One of the messages listed above appears if there is a discrepancy between the installed Image version on the Panel, the Panel version set in the TIA Portal
project and the installed version of the Panel Image on the Engineering PC.
Procedure
As of TIA Portal V16, you must install the updates for the Panel Images separately from the Engineering system updates,
as the setup for the Panel Images has been separated from the TIA Portal setup.
Note on Unified
For WinCC Unified Comfort Panels, the Image version (main version + update) must also be set in the project.
Fig. 04
If an Image version does not match the version set in the TIA project, the installed Image version on the HMI Control Panel and the installed version of the Images
on the Engineering PC, a communication error occurs and loading is aborted.
To ensure that the project can be transferred without communication errors, the appropriate update for the Panel Images must be installed. You can download the
update from the following link:
Image Downloads for HMI Operator Panels
Additional Keywords
Download, Upload, Update, Transfer, Error, Abort, Connection
Security information
In order to protect technical infrastructures, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic,
state-of-the-art IT security concept. Siemens’ products and solutions constitute one element of such a concept. For more information about cyber security, please visit
https://www.siemens.com/cybersecurity#Ouraspiration.
© Siemens AG 2009-2024 - Imprint Privacy policy Cookie policy Terms of use Digital ID