BG 50 - 2013 Water Treatment For Closed Heating and Cooling Systems
BG 50 - 2013 Water Treatment For Closed Heating and Cooling Systems
BG 50 - 2013 Water Treatment For Closed Heating and Cooling Systems
southbank
On
06/03/2018
KUhYfHfYUhaYbhZcf7`cgYX
<YUh]b[UbX7cc`]b[GmghYag
:Y^iZYWnGZ\^cVaY7gdlc
5^c]bhjYbhifYk]h\"""
7<*%$'%&(
Licensed copy from CIS: southbank, Southbank University, 06/03/2018, Uncontrolled Copy.
1
ACKNOWLEDGEMENTS
The steering group was chaired by Alan Edwards representing the Water
Management Society, and the editor for the publication was Reginald Brown
Licensed copy from CIS: southbank, Southbank University, 06/03/2018, Uncontrolled Copy.
of BSRIA. Design and production was carried out by Joanna Smith of BSRIA.
BSRIA wishes to thank all the members of the steering group for their
contributions:
Every opportunity was taken to incorporate the views of the steering group,
however final editorial control of the publication rested with BSRIA.
The guidance given in this publication is correct to the best of BSRIA’s knowledge. However BSRIA
cannot guarantee that it is free of errors. Material in this publication does not constitute any warranty,
endorsement or guarantee by BSRIA. Risk associated with the use of material from this publication is
assumed entirely by the user.
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or
transmitted in any form or by any means electronic or mechanical including photocopying, recording or
otherwise without prior written permission of the publisher.
© BSRIA October 2013 ISBN 978-0-86022-724-3 Printed by Charlesworth Press
In particular the guide will help facilities managers and others to engage in
constructive discussion with water treatment professionals and choose the
most appropriate water treatment programme for their systems.
The guide partially replaces BSRIA AG 2/93 Water treatment for building
services systems in respect of closed system applications. The guidance is
consistent with BSRIA BG 29/2012 Pre-commission cleaning of pipework
systems, BS 8552:2012 Sampling and monitoring of water from building
services closed systems. Code of practice and the European Biocidal products
Regulation (528/2012, commonly known as BPR).
1 INTRODUCTION 1
3 CORROSION PROCESSES 21
3.1 Chemical corrosion processes 21
3.2 Microbially influenced corrosion (MIC) 31
7 REGULATIONS 78
7.1 Health and safety 78
7.2 Other regulations 79
GLOSSARY 101
1 INTRODUCTION
The scope of this guide is water treatment for the control of corrosion
and maintenance of water quality in closed heating and cooling systems in
buildings other than individual dwellings. This includes low temperature
hot water heating systems, heat pump and chilled water systems and
condenser water circuits. It is also relevant to community heating and
Licensed copy from CIS: southbank, Southbank University, 06/03/2018, Uncontrolled Copy.
The scope does not include the specific requirements for water treatment
for medium and high temperature heating systems, for which reference
should be made to BS 2486[3].
This scope does not include water treatment for open systems such as
cooling towers and steam boilers or for domestic hot and cold water
services.
Various technical issues are discussed in detail in the appendices and there
is a glossary and bibliography at the end of this guide.
There are many factors in the design of closed heating and cooling systems
that can influence corrosion. It is impossible to completely eliminate the
corrosion of ordinary metals in such systems, but it is possible to control
the corrosion rate to tolerable levels.
s choice of materials.
s flow rates and control strategy.
s minimising dissolved oxygen.
s filling, flushing and cleaning prior to use.
s chemical and physical water treatment.
s monitoring and maintenance.
2.1 CHOICE OF A wide range of well-understood materials are used in closed water
MATERIALS
systems. These include low carbon steel, stainless steel, galvanised steel, cast
iron, aluminium, copper and copper alloys, elastomers and plastics.
Metals are used for distribution pipework and equipment including heat
exchangers, pumps, valves, radiators and other heat emitters. Elastomers
are used as seals including “O-rings” in valves and fittings. Plastics are
used for pipework (PVC, ABS, HDPE etc.) and individual components of
fittings and equipment (acetal, nylon, PTFE etc.).
Steel, copper alloys and aluminium are suitable for closed heating and
cooling systems as the corrosion rate should be limited by the low
availability of dissolved oxygen in the water and the appropriate use of
corrosion inhibitors. However, there are other factors that may influence
corrosion. For example:
s Mild steel, stainless steels and copper may be prone to microbially
influenced corrosion (MIC).
s Heating and cooling systems contain different metals that when
joined together may induce galvanic corrosion in the presence of
dissolved oxygen.
s Brasses may be subject to dezincification.
s Aluminium and stainless steels are prone to pitting corrosion in high
chloride environments.
Aluminium Some boiler heat exchangers Good overall corrosion resistance Exposure to high pH causes
and radiators in oxygenated waters of neutral or rapid loss of metal and
slightly alkaline pH. Should not be formation of aluminium
exposed to pH greater than 8.5 hydroxide sludge. Susceptible
to pitting corrosion at
moderate chloride or sulfate
concentrations
Copper and copper alloys Copper tube, brass valves and Good overall corrosion resistance in Copper ions entering the water
fittings water of neutral or moderately alkaline can result in pitting corrosion of
pH. steel and aluminium. Brass can
be subject to stress corrosion
In oxygenated water copper is subject cracking when exposed to
to attack from turbulent erosion, flux ammonia.
residues and under-deposit corrosion.
Mild steel and cast iron Steel pipe, boiler heat Low concentrations of dissolved Formation of insoluble iron
exchangers, circulating pumps oxygen result in uniform corrosion and oxides as suspended solids
the production of magnetite sludge. increases wear in pumps and
High concentrations of dissolved the risk of under-deposit
oxygen result in pitting attack under corrosion in low flow areas
tubercles. where sedimentation occurs.
Galvanised steel Some piping systems Internally galvanised pipes and fittings Formation of zinc hydroxide as
should not be used in heating systems suspended solids.
(see Section 3.1.2)
Stainless steel (SS) Plate heat exchangers, Very good resistance to general
pump casings, minor parts. corrosion but may be susceptible to
Occasionally pipework. pitting, crevice corrosion and stress
corrosion cracking at high chloride or
sulfate concentrations.
Plastic Plastic pipe including underfloor Resistant to corrosion but may be Oxygen permeation through
heating. Minor parts. subject to physical degradation for plastic pipe. Pressure resistance
example by sunlight. decreases with temperature.
Rubber Flexible hose liners (EPDM), Resistant to corrosion but may be Amenable to the formation of
O-rings and seals. subject to gradual chemical and biofilm.
physical degradation leading to loss of
flexibility and cracking.
with flow velocity but this is less important than what happens at very low
or very high flow velocity.
If the water velocity is too low then settling of solids may occur. This is
mainly an issue in small bore pipework and terminal units, such as fan coils
and radiators, at the extremities of the building. Accumulation of deposits
increases the likelihood of under-deposit corrosion as well as biofouling
and MIC.
2.2.2 Circulation
It is essential to avoid prolonged stagnation in heating and cooling systems.
Stagnation will allow the sedimentation of suspended solids and promote
the formation of biofilms, increasing the risk of microbially influenced
corrosion. Also, most inhibitors work more effectively under flowing
rather than stagnant water conditions.
The system control strategy should therefore ensure that circulation pumps
and control valves are periodically operated to reduce the risk of stagnation
and ensure full distribution of all water treatment chemicals.
2.3 MINIMISING O2 to OH−) is the primary reaction that drives anodic dissolution and
DISSOLVED OXYGEN
therefore corrosion. Control of dissolved oxygen is therefore a key aspect
of controlling corrosion.
Barrier plastic pipework (for PE-X and PB) became available in the late
1980s. This barrier is either a plastic film on the inner surface of the
pipe that reduces oxygen diffusion or a concentric aluminium layer in
the middle of the pipe wall (composite pipe) that prevents it. In order to
maintain a continuous barrier throughout the system it is important that
the pipe is used with the fittings recommended by the manufacturer.
The use of non-barrier plastic pipework for heating systems is still allowed
in BS 7291[5]. If it is used then it is crucial to maintain the correct level of
a corrosion inhibitor to control corrosion.
The fill water also contains dissolved air (mostly oxygen and nitrogen)
that will be evolved from solution if the water is heated. Automatic air
vents allow gases evolved during the initial operation of heating systems, or
created by subsequent chemical or biological processes, to be vented from
high points of the system. Methods to accelerate deaeration of system
water are described in Section 5.2.
These steps should ensure that the maximum design pressure of the
heating system will not be exceeded during heating up and negative
pressure will not develop in any part of the system during cooling down.
Actual system pressure should be checked during commissioning and the
pressurisation settings adjusted upwards if necessary.
2.4 DESIGN FOR Most closed heating and cooling systems rely on chemical water treatment
WATER TREATMENT
for the control of corrosion. This section describes the system features
necessary to implement a chemical water treatment programme. The
chemicals that may be employed are discussed in Section 4.
- Ultraviolet disinfection
- Reverse osmosis (provides a barrier to bacteria)
- Automated biocide dosing
Water softening
Where the available water is particularly hard, a softening plant may be
temporarily installed to fill the system with reduced hardness water. It is
not recommended to install a permanent softening plant solely for fill
water as that will be underused and may become a source of bacterial
contamination.
The fill water should not be fully soft (complete removal of calcium) as
such waters are non-scale forming and, in theory, can be more corrosive
than non-softened waters, particularly for copper. This risk can be offset
by appropriate corrosion inhibitors e.g. azoles for copper protection.
Softening is not normally required for make-up water for closed systems
as there should be minimal make-up during normal operation and the
consequent addition of scale formers should be insignificant compared to
the volume of the system. Some water treatment practitioners do however
favour the use of blended softened water for both filling and topping
up where it is already available on site (usually for hot and cold water
services).
Mains water is not sterile but contains a wide range of bacteria that are
harmless to people but may become implicated in corrosion processes.
Low pressure membrane filtration is increasingly being used to provide a
Licensed copy from CIS: southbank, Southbank University, 06/03/2018, Uncontrolled Copy.
physical barrier to bacteria and fungi entering the system from the water
supply. This is claimed to reduce the need for biocides for subsequent
microbiological control.
Strainers
Strainers should be fitted in accordance with design codes to protect
sensitive equipment and heat exchangers. Strainers may also be fitted
where secondary circuits are fed from the primary circuit. The appropriate
strainer size and media must be selected according to the design flow rates
and maximum allowable pressure drops. Importantly, strainers must be
isolable and easily accessed for inspection and routine maintenance.
Various filtration media and bespoke filter units can remove suspended
solids and some microorganisms. Particular guidance on filtration
technologies can be found in Section 5.1.
For small systems a dosing pot is used for maintenance treatments. This
is a flow-through container, plumbed in parallel with part of the circuit.
It is fitted with valves so that it can be isolated, drained and filled with
chemical at atmospheric pressure, then reconnected to the circuit (see
Figure 1).
Tundish
Vent
Inlet
Outlet
Serial
number
plate
Drain
It is important that the dosing pot should remain open to the system
with continuous through-flow so that it does not become a dead leg and
encourage the growth of bacteria. One manufacturer now combines the
function of dosing pot and strainer.
s Pump sets
s Strainers and filters
The majority of samples needed to assess water quality in the system can
be taken from suitable drain points (see Section 6.3.3).
Filters and plate heat exchangers should be fitted with differential pressure
gauges to detect signs of blockage or fouling.
Licensed copy from CIS: southbank, Southbank University, 06/03/2018, Uncontrolled Copy.
Although external corrosion is not a water treatment issue there are some
failures where it may not be immediately obvious whether the problem
lies inside or outside the pipe. Stress corrosion cracking (SCC) particularly
affects brass fittings and valves on chilled water pipework when exposed
to ammonia or other aggressive chemical species. These can be leached
from certain types of fibre and rigid foam insulation when moistened by
condensation on the outer surface of the pipe. Where there is any doubt
as to the risk of SCC on chilled water pipework, it is recommended
to terminate and seal the suspect insulation before it reaches the brass
component. Neoprene insulation can then be used to individually insulate
the brass component but should extend to at least 300 mm either side of it.
2.5 PRE-COMMISSION The installation of pipework systems results in surfaces that may be
FLUSHING AND
CLEANING
oxidised or contaminated with dirt and debris. The objective of pre-
commission cleaning is to remove these contaminants and bacteria that
may have colonised the system after filling and pressure testing. If this
is not done then the system is at increased risk of operational problems
during commissioning and corrosion problems thereafter.
2.6 REMEDIAL 2.6.1 Why remedial flushing and cleaning may be necessary
FLUSHING AND If water quality is being properly managed then the system may never
CLEANING
need to be re-flushed. However there are circumstances where the system
condition and water quality have deteriorated to the extent that no
amount of chemical additions will correct the evident problems.
Some scenarios that can cause the water quality to deteriorate are:
s Persistent ingress of oxygen into the systems resulting in corrosion
of components
s Stagnant/low flow water conditions, resulting in microbial growth
or poor surface passivation
s Reduced system operation and/or building dilapidation
s Poor management or failure of the water treatment regime
s Inappropriate water treatment chemicals
s External contamination
s High rates of leakage and makeup resulting in loss of inhibitors
14 WATER TREATMENT FOR CLOSED HEATING AND COOLING SYSTEMS
© BSRIA BG 50/2013
SYSTEM DESIGN AND OPERATION 2
Dynamic flushing can be carried out using the mains water supply and
back flushing small circuits and terminal devices (fan coils, AHU, etc.) to
drain. In some circumstances flushing can be considerably aided by the
prior use of mild dispersants and polymers to aid the suspension and hence
removal of settled solids.
For the avoidance of doubt, the cleaning contractor and client should
review the guidelines in BG 29 and agree realistic criteria by which to
assess the success of the clean prior to commencing the work. In addition
to water quality guidelines modified from BG 29, those criteria may
include a relative improvement against current system water quality and the
physical condition of representative pipework surfaces before and after the
clean.
Planning considerations
s Condition of the installation - how bad is the problem and what is
the minimum intervention that will correct it?
s Costs of cleaning compared to partial or complete replacement of
the installation.
Licensed copy from CIS: southbank, Southbank University, 06/03/2018, Uncontrolled Copy.
Temporary pumps can be used for flushing and cleaning most of the
isolated sections but system pumps may be used for the main plant areas.
Specific provisions for the safe use of temporary pumps are discussed in
Appendix A.
The cleaning specialist must be aware of the existing system chemistry and
products in use. The replacement water treatment chemicals (inhibitors
and biocides) must be fully compatible with those in use and be approved
by the water treatment specialist as being compatible with their water
treatment regime and the system materials.
possible
s Locating a good water supply with adequate pressure and as close to
the works as possible.
s Checking mains or boosted water supply pressures.
s Ensuring that the water connection and pumps can provide an
adequate flow rate without losing effective pressure
s Locating or cutting in to pipework for flushing connections and
drains
s Providing power supplies if temporary flushing pumps are to be
utilised
s Confirming temporary pump size and power requirements if these
are to be utilised
s Agreeing the site-specific methodology and water quality results
required to re-integrate the cleaned pipework with the operational
system
s Agreeing the risk assessment and precautionary measures to be
implemented
Various type and grades of filter medium are used depending on particle
sizes to be removed.
reduce the solids concentration in the circulating water but has numerous
advantages:
s the filter housing is relatively small and inexpensive
s the connecting pipework is also small and easy to retrofit
s blockage of the filter will not impact on the main system
performance
s the filter can be left in situ after the flushing process for long term
maintenance operation but must be regularly checked
Licensed copy from CIS: southbank, Southbank University, 06/03/2018, Uncontrolled Copy.
Certain mild acid products can be utilised where there are deposits of
certain compositions that cannot be removed with neutral formulations.
The system water should be tested for iron and pH levels during the
chemical cleaning process to determine the efficacy of the product and the
exhaustion rate so as to determine the need for further chemical additions.
At the end of the cleaning process, the cleaning chemicals are usually
flushed from the system which is then re-treated with inhibitors and
biocides.
3 CORROSION PROCESSES
In this guide corrosion is more simply defined as the loss of metal from a
component due to the electrochemical reaction with its environment. In
closed systems this includes loss of metal from pipes and components due
to surface oxidation as well as pitting, dezincification and stress corrosion.
The driving force for the corrosion process is the energy released by the
oxidation of the metal at the anode.
In general corrosion of a single material, anodic and cathodic areas are not
fixed but evolve all over the surface of the material. In pitting corrosion of
a single material, the anodic reaction becomes fixed in a particular location
surrounded by cathodic sites (Figure 2). In this case M++ is the metal ion
released by the pitting process. Metal cations may react with the hydroxyl
ion formed at the cathode, ultimately to form an insoluble material, which
may hinder further corrosion, for example iron oxides in the case of steel
corrosion.
AQUEOUS
ELECTROLYTE
Licensed copy from CIS: southbank, Southbank University, 06/03/2018, Uncontrolled Copy.
O2 2OH− M++
H2O
CATHODE
2e¯ ANODE
Conductive path
METAL
In instances where the anode is small and localised the corrosion may be
locally intense resulting in pitting and eventual perforation. These factors
are explained below.
Dissolved Oxygen
The concentration of dissolved oxygen is by far the most important factor
controlling the rate of corrosion of metals in closed systems.
The rate of corrosion of active metals in near neutral (neither acid nor
alkaline) solutions is proportional to the concentration of dissolved oxygen,
and minimising this provides one method of controlling the corrosion
rate. However, a reduced oxygen concentration may not necessarily be an
Licensed copy from CIS: southbank, Southbank University, 06/03/2018, Uncontrolled Copy.
advantage for metals protected by a passive film, e.g. stainless steel, since the
ability to maintain the film will be governed by the availability of sufficient
cathodic current.
Temperature
Changes in temperature can modify the mechanism and rate of corrosion
reactions.
The further apart the metals are on this list, the greater will be the
reactivity between them and therefore the greater the speed at which the
anodic site will corrode.
Table 4: Galvanic series of some commercial metals and alloys
The actual ordering of metals in the series may vary according
to the chemical environment but the following can be taken as
indicative for a closed heating or cooling system.
AQUEOUS
ELECTROLYTE
M++
O2 2OH -
H2O
CATHODE 2e - ANODE
Conductive path
METAL 1 METAL 2
pH
The pH (hydrogen ion concentration) of system water significantly affects
the rate and degree to which metals corrode and the fate of the metal ions
released into solution. Most metal will corrode more rapidly in acidic
solutions (less than pH 7). Water treatment programmes for steel pipework
systems are typically designed to operate between pH 8 and pH 11.
Carbon dioxide
Dissolved carbon dioxide contributes to corrosion by reducing the pH of
the water and increasing its capacity to corrode metals.
Chlorides
Chlorides are potentially aggressive as they interfere with the development
of protective films and also allow passive films to be broken down more
Licensed copy from CIS: southbank, Southbank University, 06/03/2018, Uncontrolled Copy.
readily. The danger of having partial passivation is that the corrosive attack
is concentrated at active sites leading to pitting corrosion.
For other materials, including those that have a naturally formed protective
oxide film such as aluminium and stainless steel alloys, certain grades may
have reduced susceptibility to chloride attack and should be chosen where
this is potentially an issue (see Section 3.1.2).
Sulfates
High concentrations of sulfates may also increase corrosion rates but are
not as aggressive as chlorides at the same concentration. However, sulfate
ions can be metabolised by various sulfate reducing bacteria (SRBs)
causing pitting corrosion in anaerobic conditions under biofilm and
deposits (see Section 3.2).
Bacteria
There are many other bacteria (aerobic and anaerobic) that can result in
corrosion, either directly or indirectly, as discussed in Section 3.2.
Flow velocity
The general corrosion rate in a pipe gradually increases with flow velocity.
At a high flow velocity, particularly in the presence of entrained gases
or solids, turbulent erosion may occur. This causes uneven attack on
pipework surfaces after flow discontinuities. Turbulent erosion mainly
affects the softer metals such as copper and brass, particularly in domestic
water systems, but is relatively uncommon in closed systems.
Surface condition
Dirty surfaces, such as those contaminated with grease or scale are more
susceptible to localised corrosion than clean surfaces. One explanation
is that isolated areas of contamination on an otherwise clean surface can
initiate differential oxygen corrosion. Dirty surfaces also encourage the
growth of biofilm and MIC.
26 WATER TREATMENT FOR CLOSED HEATING AND COOLING SYSTEMS
© BSRIA BG 50/2013
CORROSION PROCESSES 3
Stress
Stresses in certain metals and alloys can cause stress-corrosion cracking
(SCC) when they are exposed to specific corrosive environments. The
factors required to produce this effect are a susceptible alloy/environment
combination, tensile stress (either applied or residual from the metal
forming processes) and exposure to an aggressive species. For example
ammonia causes SCC of brass and chloride causes SCC of stainless steel. A
valve that has suffered from SCC is shown in figure 4.
Licensed copy from CIS: southbank, Southbank University, 06/03/2018, Uncontrolled Copy.
Other factors
Other factors that increase heterogeneity and therefore encourage the
initiation of corrosion cells and should be avoided where possible include:
s Discontinuities in the natural or applied protective surface coating
(including inhibitor films)
s Local differences in oxygen concentration caused by accumulation
of deposits on surfaces and in crevices
s Differences in metallurgy due to welding
s The proximity of dissimilar metals
Contact with copper and copper alloys, and to a lesser extent, iron and iron
alloys, will induce galvanic corrosion in all environments where dissolved
oxygen is present. Aluminium is intentionally used a sacrificial anode in
some situations to protect more vulnerable materials.
Cast iron
Typical applications of cast iron include boiler sections (heat exchangers),
pump housings, large valves and pipe fittings (malleable iron). Corrosion
rates for cast iron in closed heating and cooling systems are similar to those
for mild steel and the same programmes of water treatment apply.
In common with copper, brasses are relatively soft and can suffer attack
by erosion, impingement or cavitation. Cavitation in heating and
cooling systems is most frequently encountered on valve seats where
the valve has been operated in an almost closed position. This risk is
exacerbated in water with high suspended solids or debris. An example is
shown in figure 5.
Stainless steel
The term “stainless steel” covers a wide of alloys incorporating
iron, chromium and nickel. These can be grouped by metallurgical
characteristics as martensitic, ferritic and austenitic. Austenitic grades have
the highest corrosion resistance and ductility and are most frequently used
in closed systems. Examples of the use of stainless steel in closed systems
include valve stems, pump shafts and impellers, strainers, parts of fittings,
expansion joints, plate heat exchangers and buffer vessels. Stainless steel
is occasionally used for pipe sections and associated fittings but less so in
closed systems than domestic water systems.
sludge that restricts flow and may lead to blockages or increased risk of
MIC. This is commonly found in the base of steel radiators and the cast
iron heat exchangers of older boilers.
Steel corrosion can occur even in the absence of oxygen, if the water
contains sulfate reducing bacteria (see Section 3.2.1).
Zinc
Zinc is used as a protective coating on some steel pipes and fittings,
Licensed copy from CIS: southbank, Southbank University, 06/03/2018, Uncontrolled Copy.
mainly for cold water services. Internally coated pipes and fittings are
NOT suitable for hot water or heating systems as the corrosion rate in
oxygenated water increases dramatically above 55°C and a reversal of
potential occurs above 60°C. The zinc then becomes cathodic to steel,
stimulating attack which can result in localised corrosion (pitting) and
subsequent perforation.
3.2 MICROBIALLY Bacteria are single celled microorganisms that often aggregate into
INFLUENCED colonies. The typical cell size is 1 μm to 10 μm. The population of
CORROSION (MIC)
microorganisms can be diverse and variable depending on the degree
of sensitivity to the oxidation-reduction potential of their environment.
Bacteria can be classed into the following categories depending on how
much oxygen they require for respiration:
s Aerobes (grow in the presence of oxygen), e.g. Pseudomonas,
Aeromonas, Flavobacter.
s Facultative anaerobes (able to grow with or without oxygen) e.g.
Klebsiella, E.coli.
s Anaerobes (grow in the absence of oxygen) e.g. Sulfate reducing
bacteria (SRB).
All natural sources of water (including tap water) contain many different
types of bacteria, some of which may multiply and lead to problems
within a pipework system if they encounter suitable conditions for growth.
Bacteria can circulate freely in the system water as “planktonic” bacteria or
adhere to the pipe walls as “sessile” bacteria.
Closed systems, if left filled and untreated, can quickly develop a biofilm
layer on pipe surfaces. A biofilm is a microbial mass of aquatic bacteria
and other microorganisms together with trapped particles and dead
bacteria cells, bound together by an exopolymer. This is an extracellular
polysaccharide exudate produced by slime forming bacteria such as
pseudomonads, constituting up to 90% of the biofilm. It protects the
sessile bacteria from hostile conditions including exposure to biocides. A
consortium of bacteria is therefore able to develop within the biofilm on
the pipe wall where both aerobic and anaerobic species can flourish. This is
the starting point for microbially influenced corrosion.
There are three ways in which bacteria are able to cause or influence
corrosion:
a. directly, by obscuring the surface, resulting in a differential aeration
cell
b. directly, by producing metabolic by-products which are in themselves
aggressive towards metal surfaces
c. indirectly, by acting on the treatment chemicals in a way that renders
them less effective
O2
O2
Aerated Water
O2
O2
O2 O2 O2
BIOFILM
Licensed copy from CIS: southbank, Southbank University, 06/03/2018, Uncontrolled Copy.
O2 O2
O2 O2 O2 O2
O2 O2 Aerobic O2
O2 O2 O2
BIO
O2
FILM
O2 O2
FILM
O2 O2 O2 O2 O2
BIO
O2 Anaerobic O2 O2
O2 O2
O2 O2
O2
OH– OH– O2 OH– OH–
M+ M+
M+
Cathode e– e– Cathode
–
e e–
Anode METAL
Corrosion due to SRB: The absence of oxygen under the biofilm allows
the growth of anaerobic organisms such as SRB which are one of the
most frequent causes of MIC. SRB reduce sulfate from the fill water to
hydrogen sulfide which reacts with the metal to produce metal sulfides
as corrosion products. The involvement of SRB in corrosion failures
is inferred from the evolution of hydrogen sulfide when the corrosion
deposit is acidified. Figure 7 shows two examples of SRB attack on pipe
surfaces under the microscope (at low magnification).
4.1 CORROSION The purpose of water treatment in a closed heating or cooling system is to
INHIBITION
ensure that the system maintains its efficiency and achieves or even extends
its life expectancy. In practice the focus tends to be on protecting the
metal components of the system from corrosion processes that may lead to
the formation of suspended solids and pitting, though the adverse effects of
Licensed copy from CIS: southbank, Southbank University, 06/03/2018, Uncontrolled Copy.
Note that some inhibitors, such as nitrite, can promote pitting corrosion
when present below a critical concentration. It is very important to
Chemical spot tests and performance tests should be available so that the
efficiency of the water treatment can be measured in the field.
Cathodic inhibitors are generally less effective than the anodic type
and may form visible films on the cathode surface. Whilst there is no
critical lower concentration, excessively high concentrations could cause
precipitation, increasing the risk of under-deposit corrosion.
36 WATER TREATMENT FOR CLOSED HEATING AND COOLING SYSTEMS
© BSRIA BG 50/2013
CHEMICAL WATER TREATMENT 4
pitting can ensue. Too little nitrite can be worse than none at all. Table
6 suggests the critical concentrations of chloride and sulfate for pitting of
steel in nitrite inhibitor based on information from Corrosion and Corrosion
Control[18].
Table 6: Critical concentrations for pitting of steel in nitrite inhibitor
Nitrite inhibitor Chloride Sulfate
NO2- mg/l Cl- mg/l SO42- mg/l
33 127 14
Licensed copy from CIS: southbank, Southbank University, 06/03/2018, Uncontrolled Copy.
67 278 37
Give that nitrite concentrations will normally be held above 300 mg/l and
mains water chloride and sulfate concentrations should be well below 100
mg/l this issue is unlikely to be a major concern in most systems filled
from the mains. However chloride and sulfate can be much higher in
borehole water. Table 8 of BG 29[1] suggests that water containing up to
250 mg/l sulfate or chloride should be acceptable for filling the system.
Also bear mind that chloride and sulfate can accumulate in the system in
the longer term as the breakdown product of some biocides.
Nitrate – The nitrate anion (NO3-) may be included with other inhibitors
for the protection and aluminium components and solder. In particular
the addition of nitrate can overcome the detrimental effect of nitrite on
aluminium.
heat flux.
Silicates are not used as stand-alone corrosion inhibitors for low carbon
steel protection but may be added to the water treatment programme for
control of aluminium corrosion and/or to augment the performance of
other inhibitors.
Organic film formers – These are organic molecules that react with
metal surfaces in contact with the water in which they are dissolved to
form a protective barrier.
Sulfites are still used for steam boiler plant and high temperature heating
systems but rarely in low temperature systems as they could promote the
growth of SRB by providing a source of oxidised sulfur and anaerobic
conditions. This is not an issue in high temperature systems as the bacteria
are eliminated by thermal disinfection.
DEHA is used for controlling ferrous metal corrosion in both high and
low temperature systems, particularly those that require the water to
maintain a low conductivity. In addition to being an oxygen scavenger and
pH buffer, DEHA acts as a passivator, converting haematite to magnetite.
the nitrite concentration is low then the molybdate should also be tested
so that the remedial dosing can be adjusted to bring both components up
to the recommended concentration. In some situations it will only be
necessary to add nitrite.
All biocides (see Section 4.2.2) must be compatible with the components
of the corrosion inhibition programme so that neither reduces the
effectiveness of the other.
4.2 BACTERIA AND In closed systems the primary concern is biofouling, though fungal growth
BIOFOULING
INHIBITION
can sometimes be significant. The bacteria that cause most problems in
closed heating and cooling systems are:
s Sulfate reducing bacteria (SRB)
s Nitrite reducing bacteria
s Pseudomonads
The anoxic conditions under the biofilm also provide ideal conditions
for the growth of anaerobic bacteria, such as the SRB that accelerate
corrosion and pit formation. SRB accelerate corrosion by reducing sulfate
to hydrogen sulfide that reacts to form insoluble sulfides and cathodic
depolarisation (removal of hydrogen from the cathode). Other bacteria
can also create acidic environments (with sulfuric acid, hydrochloric acid
etc.) under the biofilm, resulting in corrosion.
Dirt and debris: Dirt and debris will absorb and reduce the effectiveness
of biocides and other water treatment chemicals and provide areas of local
stagnation. Dirt and debris particles may also become incorporated in the
biofilm and may become a source of nutrients for bacteria.
Different dose rates are required for a maintenance dose biocide (to
prevent microbiological growth and therefore produce a biostatic effect)
and a shock dose biocide (to kill high microbiological numbers present
and bring the system under control and therefore produce a biocidal
effect). The activity of antimicrobial agents is often quantified as a
minimum concentration that is required to inhibit the growth of the target
organisms (minimum inhibitory concentration) or as a concentration that
leaves no detectable survivors after a specified contact time (minimum
bactericidal concentration, generally taken as the minimum concentration
required to achieve 99.9 percent reduction in bacteria).
Biocides can be divided into two main groups: oxidising biocides and non-
oxidising biocides.
Oxidising biocides
Commonly used oxidising biocides include chlorine, bromine, chlorine
dioxide and hydrogen peroxide. Oxidising biocides kill bacteria but will
also react with any organic matter present in the system. Also, at the
concentration required for effective antimicrobial activity most oxidising
biocides will be corrosive. The use of oxidising biocides in closed heating
Licensed copy from CIS: southbank, Southbank University, 06/03/2018, Uncontrolled Copy.
Non-oxidising biocides
The following non-oxidising biocides are currently still permitted under
the Biocidal Products Regulation (BPR) for use in closed systems:
s Isothiazolinones
s DBNPA
s Bronopol
s Gluteraldehyde
s THPS
s Triazines
It is also possible that a particular biocide has limited impact in the system
due to degradation by high pH or temperature. After the initial dosing and
significant kill of bacteria, the biocide will be rapidly depleted to below its
effective concentration. Bacteria will then be released into the water from
the biofilm resulting in a sharp increase in the measured numbers. In this
case a biocide which has better pH and/or temperature stability should be
selected.
4.3 SCALE INHIBITION Calcium scale (limescale) is not usually considered an acute problem in
heating and cooling systems with minimal fresh water additions. However,
over the lifetime of a system, repeated draining and refilling of a system
can result in scale deposition that will significantly reduce heat transfer
Licensed copy from CIS: southbank, Southbank University, 06/03/2018, Uncontrolled Copy.
cleaned system. Strainers do not retain fine particles of metal oxides, scale
and precipitates that contribute to the suspended solids result in a normal
system.
The typical strainer is supplied with a 0.8 mm stainless steel mesh though
different sizes can be specified. It is counterproductive to specify a smaller
mesh than is actually needed as this will increase the pressure drop and the
risk of blockage of the strainer itself if not regularly inspected. A Y pattern
strainer is shown in figure 9.
Figure 9: Y pattern strainer
Drain
valve
5.1.4 Hydro-cyclones
The principle of the hydro-cyclone is that the centripetal forces generated
in a rapidly spinning water column cause particles to move to a region
where they can be separated from the main water flow, collected and
drained off. The typical form is an inverted cone where the water enters
tangentially at the top. Clean water is discharged on the vortex axis at the
top, and particles collected via a drain at the bottom (figure 11).
Although cyclones could be sized for the total system flow (particularly
in flushing applications), they are most often installed as side stream
devices, usually with a separate pump. Although not as effective as media
filters, there is no cost of consumables apart from the energy requirement
associated with the pumping.
Collector
Drain
valve
Side stream units are normally sized such that the whole water system
volume passes through the filter at least once over a 24 hour period. As
they are on a side-stream, clogging up the filter does not cause back-
pressure problems on the main system. Cartridge filters are periodically
removed and replaced with a new cartridge, the need for replacement
being determined by pressure drop or visual inspection.
The pore size of the filter media can be varied and reduced over time to
“polish” the system water.
Membrane
a te
Perme
ntrate
Conce
Permeate collection material
Membrane
Feed channel spacer
Outer wrap
The sole application of reverse osmosis for closed systems is the pre-
treatment of fill water, particularly to provide a physical barrier against the
ingress of bacteria.
5.2 DEAERATION Cold tap water used to fill systems is often more than 95% saturated with
dissolved gases including oxygen. The equilibrium concentration of
oxygen depends on temperature, pressure and other dissolved components
in the water but could be as high as 10 mg/l. In order to manage the
corrosion risk, the oxygen concentration should ideally be reduced to less
than 1 mg/l, and as quickly as possible.
Chilled water systems may never see a temperature higher than the
ambient in the building, so the dissolved oxygen can only be removed by
corrosion, microbiological processes, chemical oxygen scavengers (rarely
used) or the application of technologies such as vacuum deaeration.
Vacuum deaeration can also be used for heating system water. This and
other possibilities are described below.
the top of risers and at high points where air (and other gases generated in
the system) will naturally collect when released from solution.
Automatic
air vent
Stagnation
volume
Automatic
Branch air vent
Riser
Deaerator
and dirt trap
Drain
valve
for the volume of water temporarily removed from the system during the
deaeration cycle.
Vacuum
relief valve Vacuum
pump
L2
Deaeration
vessel
L1
Reinjection
Inlet pump
valve
Non-return
valve
Main Branch
In both these methods, the oxygen reacts with the anode, initially to form
hydroxyl ions which tend to elevate the pH of the system water. Also,
subsequent reactions of the metal ions may result in increased suspended
solids and scale.
Sacrificial anodes are rarely used within closed systems. The principle can
however be adopted where lengths of pipework are to be protected from
external corrosion. Due to the low open circuit potential differences
between steel and for example a magnesium strip, one anode can only
protect a limited length of pipe line. However, this low potential
difference (voltage) can be preferable to a higher impressed voltage as the
danger of over-protecting some portions of the installation is less.
5.4 OTHER NON- Closed heating and cooling systems are predominantly treated with
CHEMICAL
TREATMENTS
chemical inhibitors and biocides. However, in recent years a number of
well-authenticated non-chemical methods of scale inhibition, corrosion
inhibition and bacterial inhibition have been reported, mainly in cooling
towers, but also occasionally in closed systems.
The authors of this text would strongly advise the owner/operator of any
system considering using a non-chemical system to seek the following
evidence before relying on innovative solutions:
s Proof of current usage:
- Is there authentic case study data relevant to closed systems?
- Are there references from users, independent of the supplier?
- Are site visits to existing installations possible?
- Is the supplier open about installations that may not have
performed to expectations and the reasons why?
s Effect of installation of the proposed unit on the existing treatment:
- If the unit purports only to control bacteria is it compatible with
the current corrosion inhibitor programme?
s Measures that will need to be put in place before installation for
comparative performance evaluations including:
- Corrosion rate (various metals)
- Total bacterial counts
- Biofilm monitoring
56 WATER TREATMENT FOR CLOSED HEATING AND COOLING SYSTEMS
© BSRIA BG 50/2013
NON-CHEMICAL WATER TREATMENT 5
The following text describes some approaches that have been tried:
of fill-waters and cooling towers but may have a future role in closed
systems.
There are four main actors associated with the water treatment
programme:
s Client: the organisation that commissions the cleaning or water
treatment activity
s Cleaning specialist: a person or organisation appointed to carry out
pre-commission cleaning or remedial cleaning of a pipework system
and related activities
s Water treatment specialist: a person or organisation appointed
to maintain the water quality and manage the corrosion, scaling,
sedimentation & biofouling risk within a pipework system; and to
supply the water treatment products.
s System operators: Staff who control the system on a daily basis and
who may be responsible for interim monitoring tasks and in some
cases interim dosing of chemicals.
Water analysis alone cannot give the full picture of the condition
of the system and, since it is only done periodically, rarely picks up
sudden changes in the system condition e.g. the loss of inhibitor due to
unscheduled drain-down or leakage. However, there are opportunities for
the continuous monitoring of certain system parameters as explained in
Section 6.6.4.
WATER TREATMENT FOR CLOSED HEATING AND COOLING SYSTEMS 59
© BSRIA BG 50/2013
6 MANAGEMENT OF THE WATER TREATMENT PROGRAMME
6.2 WATER Sampling and analysis of the water circulating through the main plant
SAMPLING AND
ANALYSIS
is the primary method of assessing the efficacy of the water treatment
programme i.e. control of scale, suspended solids, corrosion and biofouling.
Other methods such as corrosion and biofouling coupons may be used
in a supporting role. Sampling, analysis, interpretation of results and the
recommendation of corrective actions should be carried out by persons
with suitable training, competence and experience.
If these remote location samples are taken from low flow areas including
terminal units then they may contain higher concentrations of solids and
bacteria than at the main plant. This effect should be considered in the
interpretation of results. Where the results are deemed unacceptable then
further investigation and specific remedial actions may be required for
example remedial flushing or operational changes.
Routine monitoring can be carried out utilising site test kits. These
are available for determination of most chemical and microbiological
parameters of importance to water treatment. The benefit of test kits for
routine monitoring of chemical parameters is that they provide rapid on
the spot results that can be acted upon without the delays associated with
analysis by external laboratories. However it is essential that the selected
test kit provides a suitable range and accuracy for the analysis and the
operator is aware of the limitations of the test method including possible
interferences.
All results should be recorded in the site/system water treatment log book.
Where results exceed action limits then predefined remedial actions should
Licensed copy from CIS: southbank, Southbank University, 06/03/2018, Uncontrolled Copy.
6.3 SAMPLING The detailed scope of sampling and analysis should be defined and
FOR WATER
CHEMISTRY
documented by the water treatment specialist in the sampling and analysis
plan. This scope should include key components of the water treatment
programme and various indicators of water quality (see Section 6.5).
Where the sample is destined for immediate on-site analysis then a clean
high density polyethylene bottle with a wide neck is suitable for collecting
the sample prior to chemical analyses.
When the sample arrives at the laboratory the chain of custody form
should be signed by the person receiving the sample, with time and date.
The laboratory will allocate a unique reference number to the sample (if
not already printed on the label) that will allow it to be tracked during
analysis and reporting.
Table 8 summarises which sample points are suitable for different samples.
[6]
Table 8: Selection of sampling points (from BS 8552 )
Type of sample Sampling Point
Full bore drain Reduced bore drain Pressure test point
point point
6.4 SAMPLING FOR Sampling is an important part of the analytical process and the manner
MICROBIOLOGY
Licensed copy from CIS: southbank, Southbank University, 06/03/2018, Uncontrolled Copy.
If using a binder point and tube, the needle and tube should be disinfected
before use by flushing the inside, and swabbing the outside, with propan-2-
ol solution. There is not usually any system dead leg but the binder probe
should be inserted and the sample tube briefly flushed to remove any
residual disinfectant before collecting the sample as described above in
step 3.
Note: It has been common practice when taking water samples for
microbiological analysis from open systems to leave a small airspace in the
sample bottle. However, given that the sample is being extracted from
a low oxygen environment in a closed system, BS 8558[7] states that the
sample bottle should be filled to the brim. This is to avoid increasing the
dissolved oxygen concentration during handling and is consistent with
BS EN ISO 5667-3[13].
When taking both chemical and microbiological samples from the same
sample point, the microbiological sample should be taken first.
24 hours of the sample being taken. The impact of the time between
sampling and analysis should be minimized by:
1. Filling sample containers to the brim (as described in Section 6.4.3)
2. Refrigerating samples to between 2°C and 8°C (except where
otherwise indicated in the analytical method). Cool boxes with ice
packs can be used for transportation.
3. Storing samples in the dark
Licensed copy from CIS: southbank, Southbank University, 06/03/2018, Uncontrolled Copy.
There are several reasons why the final result will always be an estimate:
1. The sample may not be representative of the number of planktonic
bacteria in the system. Occasionally a fragment of biofilm containing
hundreds of bacteria will end up in the sample and may distort the
result.
2. The number of bacteria in the sample could increase or decrease
during transportation and while waiting for the analysis to begin,
depending on how the sample is handled.
Table 9 lists the main microbiological tests and the time required to obtain
a result. These tests are further explained in the following sections.
6.4.6 Pseudomonads
Pseudomonads are “pseudomonas–like” bacteria. At present there is no
standard method specifically for the analysis of pseudomonads in closed
systems. BS 8552[6] states that a suitable reference method is BS EN ISO
13720[14], using a pseudomonas selective agar base with CFC selective
supplement for “pseudomonas species”. The incubation period is 48 hours
at a temperature of 30°C.
Note that the results are usually expressed as cfu per 100 ml for
consistency with guidelines in BG 29[1]. Results provided “per ml” should
therefore be multiplied by 100 for comparison with guidelines.
The next step is to incubate the plate for the specified incubation
temperature and time: 22°C for 72 hours, 30°C for 72 hours or 37°C
for 48 hours depending on the application and objectives of the analysis.
Following incubation, the plates are counted and the result expressed as
cfu/ml.
Note that since the result of the TVC test is sensitive to the incubation
temperature, results obtained at different incubation temperatures cannot
be directly compared or included in the same trend analysis.
TVC results can also be obtained using test kits, in which case the
manufacturer’s instructions should be followed. Note that the results from
laboratory analysis and test kits are likely to differ (though they should be
self-consistent) and should not be combined for the purpose of assessing
trends.
If NRB are present the media turns pink and bubbles of ammonia gas
are produced. The time it takes for these reactions to take place gives an
indication of the number of bacteria present. A positive reaction after
1 day of incubation indicates heavy contamination (> 106 cfu/ml) and
a positive reaction after 5 days indicates low level contamination (10 -
100 cfu/ml). However, for practical purposes this should probably be
considered as a presence/absence test.
WATER TREATMENT FOR CLOSED HEATING AND COOLING SYSTEMS 67
© BSRIA BG 50/2013
6 MANAGEMENT OF THE WATER TREATMENT PROGRAMME
The shortcoming of this method is that the generation of the pink colour
is due to an increase in the alkalinity of the media due to the production
of ammonia by the NRB. If the sample is alkaline in the first place, the
media will change to pink regardless to the presence of NRB. Conversely
if the sample is acidic the media will turn yellow, and even if NRB are
present they may not be able to generate enough ammonia to change
the colour of the indicator and therefore a false negative result may be
reported.
Licensed copy from CIS: southbank, Southbank University, 06/03/2018, Uncontrolled Copy.
Test kit methods rely on the fact that SRB reduce sulfates to produce
hydrogen sulfide gas, which in turn results in a blackening of the culture
media.
the system.
6.5 WATER QUALITY The possible range of analysis likely to be carried out on site on samples
ANALYSIS AND
GUIDELINES
from closed systems together with guideline control limits, where
applicable, are detailed in Table 10 below. Notes are provided below
the table. The essential analysis and specific control limits for the system
and water treatment programme in use must be specified by the water
treatment specialist.
Cont...
No increasing trend
Zinc Limit as specified 21
No increasing trend
Aluminium Limit as specified 22
No increasing trend
Other Sulfate >90% of fill water sulfate 23
No decreasing trend
Chloride Limit as specified 24
limit of the range may indicate that the wrong water treatment chemical or
wrong dosage has been added to the system.
4. Conductivity and TDS. The relationship between conductivity and TDS
varies according to the chemistry of the system so any estimate of TDS based
on conductivity reading should be treated with caution. Ideally the specified
range should be expressed as conductivity as this will be the easiest to measure
on site. A sudden drop in conductivity could be indicative of water loss from
the system. For TDS determination the sample should be evaporated at
Licensed copy from CIS: southbank, Southbank University, 06/03/2018, Uncontrolled Copy.
105°C. The laboratory should be made aware of the presence of glycol as this
can interfere with the results.
5. Suspended solids. This is the key indicator of water quality. Suspended
solids should normally be less than 30 mg/l in the circulating water and a
well-controlled system may consistently achieve less than 10 mg/l. A high
suspended solids result may indicate poor control of corrosion rates and should
be considered together with the results for corrodible metals.
6. Settled solids (as defined in BG 29[1] and BS 8552[6]).The result will
indicate the degree of sedimentation of suspended solids at the sample location
since the last discharge of water from that sample point (for sampling or
maintenance). BG 29 suggests that the limit for settled solids in pipework
at the extremes of the system should be no more than double the suspended
solids limit (i.e. 60 mg/l) and less than three times for terminal units (i.e.90
mg/l). If the sample point has been used within the last 3 weeks and the
system is well controlled there should be no significant increase over the
suspended solids result. In that case the limit for either should be less than
150% of the suspended solids limit (i.e.45 mg/l).
7. Nitrite is the principal corrosion inhibitor in many water treatment packages
and it is essential to maintain the concentration in the range recommended by
the water treatment specialist. A low concentration of nitrite could actually
increase the corrosion rate. A rapid loss of nitrite may indicate the presence of
nitrite reducing bacteria. This should be confirmed with the NRB test.
8. Nitrate may be included as a component of the water treatment package (to
synergise with nitrite) but can also be formed by oxidation of the nitrite.
9. Molybdate is a common inhibitor in many water treatment packages.
Molybdate will gradually be lost through precipitation and over-dosing can
result in an increase in suspended solids.
10. Boron can be present in the water treatment package as borate.
11. Phosphonate may be included in the water treatment package as a scale
inhibitor. Loss of concentration is not critical.
12. Organic corrosion and scale inhibitors can be difficult and/or expensive to
monitor. The water treatment specialist will provide advice on what is feasible
and the associated guidelines.
13. Silicate may be present at trace levels in the water supply and as a film
forming inhibitor in the water treatment package for high pH water treatment
programmes.
14. Orthophosphate may be included in the water treatment package as a
corrosion inhibitor.
15. Total alkalinity (also known as methyl orange alkalinity from the use of
methyl orange indicator in the analytical titration) is used together with pH to
calculate the carbonate concentration in the sample.
16. Calcium hardness is a measured of the scale forming potential of the water.
17. Total hardness is the sum calcium and magnesium hardness of the water
expressed as mg/l CaCO3.
18. Total iron. The result is used to comment on the source of suspended and
Licensed copy from CIS: southbank, Southbank University, 06/03/2018, Uncontrolled Copy.
settled solids.
19. Dissolved iron is used as a primary indicator of corrosion control in systems
containing steel. A limit of 3 mg/l or less may be set for typical nitrite/
molybdate regimes (see BG 29[1])but may be much higher for some proprietary
products. Care must be taken in the interpretation of dissolved iron results in
high pH systems, and where there is only a small amount of steel, as a low
result may not mean that the system is safe.
20. Copper (dissolved or total). New systems with fresh copper surfaces are
vulnerable to cupro-solvency and high concentrations of dissolved copper could
result in pitting corrosion of steel and aluminium.
21. Zinc (dissolved or total). Zinc plated surfaces should not be used in heating
systems as the plating will be rapidly corroded. If zinc is found in other
circumstances it could be indicative of dezincification.
22. Aluminium (dissolved or total) is an indicator of corrosion control in systems
with aluminium components.
23. Sulfate is present in the fill/make-up water. The concentration of sulfate
in the system water should remain above 90% of that for the fill water. A
downward trend in sulfate could indicate the presence of active SRB.
24. Chloride is present from the fill water and the degradation of biocides. A high
concentration of chloride will increase the risk of pitting and stress corrosion.
There is no generally accepted “safe” level of chloride.
25. Ammonia can be produced by the action of bacteria on nitrite, nitrate and
organic water treatment components. High concentrations of ammonia are
detrimental to copper and copper alloys. Some practitioners recommend
remedial action if ammonia concentrations exceed 30 to 40 mg/l. However,
there is no published evidence to justify this recommendation in terms of an
increased risk of SCC.
26. Dissolved oxygen is required for most of the metallic corrosion processes
in closed systems. Cold tap water is often nearly saturated with dissolved
oxygen. Since corrosion processes will tend to reduce the concentration of
dissolved oxygen in the system water, the trend of results should be decreasing.
A persistently high concentration (>2 mg/l) in circulating water may be
indicative of oxygen continuing to enter the system e.g. though inadequate
system pressurisation (see section 2.3) or through plastic pipe. Very low
concentrations of oxygen relative to the circulating water in samples taken from
terminal units may indicate stagnation and/or local corrosion.
27. Total viable count (TVC) is a measure of the concentration of aerobic bacteria
in the water.These bacteria may not be implicated in corrosion but high levels
BG 29[1] states that the limit for pseudomonads in system water at handover
should be less than 10,000 cfu/100ml (100 cfu/ml) and no increasing
trend. This is based on the geometric mean of the samples as explained in BS
8558[7]. Opinions vary about the significance of high pseudomonad counts
in older systems with some practitioners arguing that the limits should be the
same as for TVC at 30°C and that 100 cfu/ml would certainly be no cause
for concern.Various data from actual sites suggest that pseudomonas counts
are typically around 10% of TVC counts in a “dirty” system (one operating
around the TVC limit) but only 1% of TVC in a clean system, hence the
criteria in BG 29.The water treatment specialist should decide on a suitable
control limit for pseudomonads based on his knowledge of the system and
operational requirements.
29. Sulfate reducing bacteria (SRB) are anaerobic bacteria that are a significant
cause of under-deposit pitting corrosion in pipework systems. As with other
bacteria, there is no relationship between the concentration of bacteria in
the water and in the biofilm. There are also difficulties in the sampling
and analysis as SRB may become dormant when exposed to oxygen in the
sample bottle and there are at least three different methods of analysis that
may respond differently to different SRB (see Section 6.4.9). A positive
result should be treated as an indication of the presence of SRB but a “non-
detectable” result does not mean the absence of SRB.
30. Nitrite reducing bacteria (NRB) reduce nitrite (or nitrate) inhibitor to
ammonia or nitrogen gas. NRB analysis is generally carried out to investigate
the reasons for rapid loss of nitrite. In most situations the major concern is
the loss of inhibitor, though a high concentration of ammonia is corrosive to
copper alloys. NRB include some pseudomonads when exposed to anaerobic
conditions.
Conclusions about the state of the system and any decisions about
remedial work should take account of all the available evidence. Often
the first step in dealing with water that falls outside the acceptable range
for a particular parameter should be to repeat the sampling to confirm the
result.
6.6 CORROSION Analysis of system water quality provides useful information about the
MONITORING
concentration and performance of corrosion inhibitors and biocides but
only gives a partial picture of the overall condition of the system and the
extent to which corrosion is taking place. Several additional techniques
and methods of corrosion monitoring can be applied to provide a more
complete picture of the health of the system.
1. System knowledge
2. Site testing of critical performance criteria
3. Documentation of observations and recommendations
alloys typically used to make heat exchangers. At least two coupons from
each metal of interest should be used to obtain mean corrosion rates.
Coupons can be assembled into bundles and placed in coupon chambers
or attached to coupon racks for insertion in the system.
different metals (e.g. steel and copper) may be bolted together to produce
a galvanic couple if required. It is important that clean gloves are used
when handling the coupons at any time to prevent grease and other
contaminants affecting the results.
The LPR method is based on the fact that polarising electrodes by less
than 20 mV produces a linear current response. The slope of the graph
of the polarisation voltage plotted against polarisation current is the
polarisation resistance, which is inversely proportional to corrosion rate.
A more accurate determination of corrosion rates can be obtained by the
instrument, using default “Tafel” slopes in the Stern-Geary equation. A
combination of the LPR technique and corrosion coupons will provide
a fairly accurate assessment of the corrosion rates of various metals in the
system and trends in corrosion rates over time.
This enables alarms to be set if corrosion rates exceed pre-set values due to
sudden changes in water quality.
There are a number of robust sensors available that can be used for in-line
monitoring of heating and cooling systems (Table 11). They will need to
Licensed copy from CIS: southbank, Southbank University, 06/03/2018, Uncontrolled Copy.
be calibrated before use but once installed they should not drift or give
noisy signals.
Table 11: Sensors for in-line monitoring of closed heating and cooling systems
Parameter Comment
Galvanic current The galvanic current flowing between steel and copper
gives a good indication of the level of corrosion
protection in system. Without inhibitors present, this
responds quickly to changes in dissolved oxygen.
Unfortunately this list of robust in-line sensors does not include pH and
ion selective electrodes as these need frequent calibration and cannot
withstand high temperatures. pH and ion selective electrodes can be
incorporated in automated sampling and analysis systems but these are
generally too expensive for most closed heating and cooling systems.
7 REGULATIONS
7.1 HEALTH AND The UK approach to health and safety is generally implemented through
SAFETY
the Health and Safety etc. Act 1974 (as amended) and the regulations
made under the act. Further information on these regulations and
practical guidance on safe working practice can be found at www.hse.gov.
uk. The following regulations (as amended) are particularly relevant to
Licensed copy from CIS: southbank, Southbank University, 06/03/2018, Uncontrolled Copy.
the regulations.
Step ladders are often used when taking samples in site. The safe use of
step ladders for sampling in ceiling voids always requires two persons.
7.2 OTHER Various regulations apply to water systems in general including the
REGULATIONS installation and operation of closed heating and cooling systems. The
applicable legislation for England is shown below. Different legislation
may apply in other parts of the UK but the practical requirements are
similar.
pressure.
[1]
Figure 16: Temporary pump arrangement (from BG 29 )
2
IV
1
IV
Licensed copy from CIS: southbank, Southbank University, 06/03/2018, Uncontrolled Copy.
8
3 4 T
IV STR NRV IV
OP DRV
7
IV
IV
1. Flexible pipe between the temporary pump and system is acceptable for short periods. However, if the
temporary pump is to be left in place for more than 1 month then connections should be hard piped. Flexible
hoses used for flushing purposes should be checked for damage before use and sterilised to avoid the risk of
bacterial contamination.
2. All flexible hose connections should be screwed. Quick release couplings or jubilee clips could present a hazard if
they work loose or are released under pressure.
3. A regulating valve with flow measurement device is required on the return connection from the system to
permit measurement and regulation of the flushing velocity. For this application, a variable orifice regulating valve
offers greater flexibility since it can be used to measure a wider range of flow rates.
4. A strainer on the pump inlet is required to protect the pump against circulating debris.
5. The entire temporary pump set should be mounted in a tank or bund so that drips or spillages do not cause
damage to under-floor services, structure or finishes.
6. A water supply will be required to replenish dirty water drained from the system. The smaller the supply available
the longer it will take to clean the system. To facilitate the process, flushing connections should be provided in the
cold water riser. A double check valve or a break tank with type A air gap will be required to prevent possible
back contamination of the boosted supply in compliance with the Water Regulations.
7. A drain connection will be required to discharge dirty water. A suitable drain point should be installed in the
main foul drainage system at a convenient location for this purpose. An effluent permit will be required and this
may need to include all chemicals proposed for use and those present in the system. Where a trapped waste
connection is provided solely for the purpose of facilitating the flushing process, this should be removed and
capped after completion.
8. A thermometer on the outlet from the pump will provide a check that circulating temperatures are below levels
at which bacteria could multiply.
Solution: The system was too badly affected for any on-line remediation
to be effective and the radiators were all replaced.
Paint blister
Corrosion site
Dislodged
tubercle
Note: the corrosion tubercle has been dislodged during the cutting of the sample
Corrosion
deposit
Solution: In this case the developer changed from plastic to steel pipe
to reduce oxygen ingress. Other similar projects use heat interface units
with plate heat exchangers so that any problems with water quality in the
distribution system do not spread into the completed apartments.
Figure 23: Corrosion and pitting in heat affected zone (cleaned sample)
Licensed copy from CIS: southbank, Southbank University, 06/03/2018, Uncontrolled Copy.
Solution: The affected areas were re-cleaned and pipe replaced as necessary.
Case study 4 – Rapid pitting corrosion of thin wall carbon steel tube
Manifestation: Pinhole leaks, poor water quality and sludge in the heating
systems soon after pre-commission cleaning.
Figure 24: Severe pitting on thin wall carbon steel tube (cleaned sample)
system pressures leading to large water losses, loss of inhibitors and gross
aeration.
Figure 25 shows the tube bundle of a large shell and tube condenser.
Several tubes had failed due to corrosion and there was considerable
corrosion debris collected in the bottom of the shell. Figure 26 shows
sections of 20 mm steel pipe with oxygen pitting corrosion.
Building: College
Solution: The affected valves were replaced and the insulation improved
to prevent condensation on the pipework and leaching of aggressive
species.
Manifestation: Brass control valves to fan coil units ‘letting by’ and
therefore giving poor temperature control and wasting of energy for
the air conditioning system. Figure 31 shows an example at 8 times
magnification.
Licensed copy from CIS: southbank, Southbank University, 06/03/2018, Uncontrolled Copy.
Solution: The affected valves were replaced. The system was flushed out
and inhibited with non-nitrite inhibitor to avoid ammonia formation.
The system static pressure was increased to reduce the risk of cavitation at
the top of the building. In these situations the control strategy and pump
settings should also be reviewed with the aim of reducing the differential
pressure across the control valve.
Solution: The main plant and risers were cleaned using system pumps,
followed by side stream filtration to maintain physical cleanliness of
recirculating water. Each floor was then individually cleaned, off-line,
using a temporary pump (one floor per weekend). Full building and
system operation was maintained through all working hours.
Building: Large office building with fan coil heating and cooling
Solution: A pilot scale cleaning rig was set up to assess cleaning strategies
for the distribution pipework as the scale was resistant to normal cleaning
chemicals. The system was eventually cleaned using ammonium citrate
followed by hydrogen peroxide to dissolve the scale. The fan coils were
replaced as a precautionary measure as the tube in these is much thinner
(0.3 mm) than distribution pipework.
APPENDIX C BIOCIDES
One of the main driving forces behind the current and future availability
of biocides in the water treatment industry is the European Biocidal
Products Regulation (528/2012, commonly known as BPR) which came
into force on the 1st September 2013, repealing the European Biocidal
Products Directive (98/8/EC, commonly known as BPD).
Licensed copy from CIS: southbank, Southbank University, 06/03/2018, Uncontrolled Copy.
Isothiazolinones
These biocidal products consist of a 3:1 ratio mixture of 5-chloro-2-
methyl-2H-isothiazol-3-one plus 2-methyl-2H-isothiazol-3-one (CMIT/
MIT) (abbreviated name).
O O
N CH3 N CH3
S S
Cl
CMIT MIT
DBNPA
2-2-Dibromo-3-nitrilopropionamide. Biocide with an active halogen
group.
O
N
Licensed copy from CIS: southbank, Southbank University, 06/03/2018, Uncontrolled Copy.
NH2
Br Br
Bronopol
2-Bromo-2-nitropropane-1,3-diol.
O¯
N+=O
Br
HO OH
Gluteraldehyde
CH2(CH2CHO)2
O O
Licensed copy from CIS: southbank, Southbank University, 06/03/2018, Uncontrolled Copy.
THPS
Tetrakis (hydroxymethyl) phosphonium sulfate
(P(CH2OH)4+)2 SO4
HO OH
OH O HO
P+ P+
O– S O–
HO OH
O
OH HO
Triazines
A number of triazine based biocides can be used within closed heating and
cooling systems, the predominant one being 1,3,5-tris(hydroxy-ethyl)-s-
hexahydrotriazine (HHT).
HO OH
Licensed copy from CIS: southbank, Southbank University, 06/03/2018, Uncontrolled Copy.
N N
OH
of water to release the biofilm. A sample of this water is then analysed for
TVC in the normal way.
Return
Flow meter
Control
valve
Flow
APPENDIX E ANTI-FREEZE
Glycol solutions are more corrosive than pure water and must be used in
combination with corrosion inhibitors. Also, the breakdown products are
acidic so pH should be monitored.
Glycols also provide a carbon source for bacteria growth and can be
broken down by bacteria, though high concentrations (>15% by volume)
are biocidal.
-2
-4
Freezing point °C
-6
Licensed copy from CIS: southbank, Southbank University, 06/03/2018, Uncontrolled Copy.
-8
-10
-12
-14
0 5 10 15 20 25 30
% by volume
-2
-4
Freezing point °C
-6
-8
-10
-12
-14
0 5 10 15 20 25 30
% by volume
GLOSSARY
REFERENCES
4. BS 7074-2:1989 Application, selection and installation of expansion vessels and ancillary equipment for sealed
water systems. Code of practice for low and medium temperature hot water heating systems
5. BS 7291-1:2010 Thermoplastics pipe and fitting systems for hot and cold water for domestic purposes and
heating installations in buildings. General requirements
6. BS 8552:2012 Sampling and monitoring of water from building services closed systems. Code of practice
7. BS 8558:2011 Guide to the design, installation, testing and maintenance of services supplying water for
domestic use within buildings and their curtilages. Complementary guidance to BS EN 806
8. BS EN 12502-1:2004 Protection of metallic materials against corrosion. Guidance on the assessment of
corrosion likelihood in water distribution and storage systems. General
9. BS EN 12502-2:2004 Protection of metallic materials against corrosion. Guidance on the assessment of
corrosion likelihood in water distribution and storage systems. Influencing factors for copper and copper alloys
10. BS EN 14868:2005 Protection of metallic materials against corrosion. Guidance on the assessment of corrosion
likelihood in closed water circulation systems
11. BS EN ISO 8044:2000 Corrosion of metals and alloys. Basic terms and definitions
12. BS EN ISO 6222:1999, BS 6068-4.5:1999 Water quality. Enumeration of culturable micro-organisms.
Colony count by inoculation in a nutrient agar culture medium
13. BS EN ISO 5667-3:2012 Water quality. Sampling. Preservation and handling of water samples
14. BS EN ISO 13720:2010 Meat and meat products. Enumeration of presumptive Pseudomonas spp.
15. BS EN ISO 19458:2006 Water quality. Sampling for microbiological analysis
16. ASTM G1 - 03(2011) Standard Practice for Preparing, Cleaning, and Evaluating Corrosion Test Specimens
17. ASHRAE Handbook. Fundamentals (SI) edition. 2009
18. Corrosion and Corrosion Control: An Introduction to Corrosion Science and Engineering, Fourth Edition
(2008). R Winston Revie, Herbert H Uhlig
BIBLIOGRAPHY
Fundamentals of Corrosion: Mechanisms, Causes and Preventative Methods (2010). Philip A Schweitzer.
Licensed copy from CIS: southbank, Southbank University, 06/03/2018, Uncontrolled Copy.
Fundamentals of Hydraulic Engineering Systems, Fourth edition (2009). Robert J. Houghtalen, Ned H.C.
Hwang, A.Osman Akan.
Industrial Biofouling: Detection, Prevention and Control (2000). James Walker, Susanne Surman, Jana Jass.
The corrosion of copper and its alloys: A practical guide for Engineers (2009). Roger Francis
Heat and mass transfer in building services design (1998). Keith Moss
NACE SP0169-2007 Control of external corrosion on underground or submerged metallic piping systems.
7HG>6ⳮ i]ZWj^ai
Zck^gdcbZciZmeZgih
6GF=5[]jYgmciWcbZ]XYbWY]bXYg][b UXXYXjU`iY]b
aUbiZUWhifY WcadYh]h]jYUXjUbhU[Y]baUf_Yh]b[
dfcZ]hUV`YWcbghfiWh]cb UbXYZZ]W]YbhVi]`X]b[g
IZhi^c\ IgdjWaZh]ddi^c\
BdYZaa^c\ >c[dgbVi^dc
GZhZVgX] IgV^c^c\
8dchjaiVcXn EjWa^XVi^dch
I/ ))%&()))+*+%%
;/ ))%&()))+*+'+ AYaVYfg\]d]gh\YZcibXUh]cbcZ6GF=5»g
:/ Whg^V5Whg^V#Xd#j`
L/ lll#Whg^V#Xd#j` YldYfh]gYUbX]bXYdYbXYbWY
DaY7gVX`cZaaAVcZLZhi!
7gVX`cZaa!7Zg`h]^gZ!
G<&',6=!J@
D[[^XZh^c7gVX`cZaa!7Z^_^c\!9jc[Zgba^cZ!
@jVaVAjbejg!DiiVlV!Hi=ZaZch!Hijii\Vgi
VcYIdjadjhZ#6hhdX^ViZh^c6gbV\]