SECTION 019113 - GENERAL COMMISSIONING REQUIREMENTS

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and
other Division 01 Specification Sections, apply to this Section.

B. OPR and BoD documentation are included by reference for information only.

1.2 SUMMARY

A. Section includes general requirements that apply to implementation of commissioning without regard to
specific systems, assemblies, or components.

B. Related Sections:

1. Division 01 Section "Facilities Exterior Enclosure Commissioning" for commissioning process


activities for building exterior enclosure, roof, and foundation systems, assemblies, equipment, and
components.
2. Division 01 Section "Interiors Commissioning" for commissioning process activities for building
interiors construction, stairways, and finish systems and assemblies.
3. Division 14 Section "Commissioning of Conveying Equipment" for commissioning process activities
for conveying systems, assemblies, equipment, and components.
4. Division 21 Section "Commissioning of Fire Suppression" for commissioning process activities for
fire-suppression systems, assemblies, equipment, and components.
5. Division 22 Section "Commissioning of Plumbing" for commissioning process activities for plumbing
systems, assemblies, equipment, and components.
6. Division 23 Section "Commissioning of HVAC" for commissioning process activities for HVAC&R
systems, assemblies, equipment, and components.
7. Division 25 Section "Commissioning of Integrated Automation" for commissioning process activities
for integrated automation systems, assemblies, equipment, and components.
8. Division 26 Section "Commissioning of Electrical Systems" for commissioning process activities for
electrical systems, assemblies, equipment, and components.
9. Division 27 Section "Commissioning of Communications" for commissioning process activities for
communications systems, assemblies, equipment, and components.
10. Division 28 Section "Commissioning of Electronic Safety and Security" for commissioning process
activities for electronic safety and security systems, assemblies, equipment, and components.

1.3 DEFINITIONS

A. BoD: Basis of Design. A document that records concepts, calculations, decisions, and product selections
used to meet the OPR and to satisfy applicable regulatory requirements, standards, and guidelines. The
document includes both narrative descriptions and lists of individual items that support the design process.

GENERAL COMMISSIONING REQUIREMENTS 019113 - 1


TA1056 MBI Sampang Agung Brewery Extension
B. Commissioning Plan: A document that outlines the organization, schedule, allocation of resources, and
documentation requirements of the commissioning process.

C. CxA: Commissioning Authority.

D. OPR: Owner's Project Requirements. A document that details the functional requirements of a project
and the expectations of how it will be used and operated. These include Project goals, measurable
performance criteria, cost considerations, benchmarks, success criteria, and supporting information.

E. Systems, Subsystems, Equipment, and Components: Where these terms are used together or separately,
they shall mean "as-built" systems, subsystems, equipment, and components.

1.4 COMMISSIONING TEAM

A. Members Appointed by Contractor(s): Individuals, each having the authority to act on behalf of the entity
he or she represents, explicitly organized to implement the commissioning process through coordinated
action. The commissioning team shall consist of, but not be limited to, representatives of Contractor,
including Project superintendent and subcontractors, installers, suppliers, and specialists deemed
appropriate by the CxA.

B. Members Appointed by Owner:

1. CxA: The designated person, company, or entity that plans, schedules, and coordinates the
commissioning team to implement the commissioning process. Owner will engage the CxA under
a separate contract.
2. Representatives of the facility user and operation and maintenance personnel.
3. Architect and engineering design professionals.

1.5 OWNER'S RESPONSIBILITIES

A. Provide the OPR documentation to the CxA and Contractor for information and use.

B. Assign operation and maintenance personnel and schedule them to participate in commissioning team
activities.

C. Provide the BoD documentation, prepared by Architect and approved by Owner, to the CxA and
Contractor for use in developing the commissioning plan, systems manual, and operation and
maintenance training plan.

1.6 CONTRACTOR'S RESPONSIBILITIES

A. Contractor shall assign representatives with expertise and authority to act on its behalf and shall schedule
them to participate in and perform commissioning process activities including, but not limited to, the
following:

1. Evaluate performance deficiencies identified in test reports and, in collaboration with entity
responsible for system and equipment installation, recommend corrective action.

GENERAL COMMISSIONING REQUIREMENTS 019113 - 2


TA1056 MBI Sampang Agung Brewery Extension
2. Cooperate with the CxA for resolution of issues recorded in the Issues Log.
3. Attend commissioning team meetings held on a variable basis.
4. Integrate and coordinate commissioning process activities with construction schedule.
5. Review and accept construction checklists provided by the CxA.
6. Complete electronic construction checklists as Work is completed and provide to the
Commissioning Authority on a weekly basis.
7. Review and accept commissioning process test procedures provided by the Commissioning
Authority.
8. Complete commissioning process test procedures.

1.7 CxA'S RESPONSIBILITIES

A. Organize and lead the commissioning team.

B. Provide commissioning plan.

C. Convene commissioning team meetings.

D. Provide Project-specific construction checklists and commissioning process test procedures.

E. Verify the execution of commissioning process activities using random sampling. The sampling rate may
vary from 1 to 100 percent. Verification will include, but is not limited to, equipment submittals,
construction checklists, training, operating and maintenance data, tests, and test reports to verify
compliance with the OPR. When a random sample does not meet the requirement, the CxA will report the
failure in the Issues Log.

F. Prepare and maintain the Issues Log.

G. Prepare and maintain completed construction checklist log.

H. Witness systems, assemblies, equipment, and component startup.

I. Compile test data, inspection reports, and certificates; include them in the systems manual and
commissioning process report.

PART 2 - PRODUCTS (Not Used)

PART 3 - EXECUTION (Not Used)

END OF SECTION 019113