8-TON TUHYE0963AN41AN

Job Name:
System Reference: Date:
208/230V OUTDOOR VRF HEAT PUMP SYSTEM UNIT OPTION
Standard Model TUHYE0963AN41AN
ACCESSORIES
Big Foot Stand for details see Big Foot Stands submittals
Header Kit for details see Pipe Accessories Submittal
Joint Kit for details see Pipe Accessories Submittal
Low Ambient Kit for details see Low Ambient Kit Submittal
Panel Heater Kit for details see Panel Heater Kit Submittal
Snow/Hail Guards Kit for details see Snow/Hail Guards Kit Submittal

Specifications System
Unit Type TUHYE0963AN41AN
Cooling Capacity (Nominal) BTU/H 96,000
Heating Capacity (Nominal) BTU/H 108,000
Cooling ºF [ºC] 23~126 [-5.0~52.0]
Guaranteed Operating Range
Heating ºF [ºC] -13~60 [-25.0~15.5]
Extended Operating Range Heating ºF [ºC] -27.4~60 [-33.0~15.5]
71-5/8 x 48-7/8 x 29-3/16
External Dimensions (H x W x D) In. [mm]
[1,818 x 1,240 x 740]
Net Weight Lbs. [kg] 622 [282]
Pre-coated galvanized steel sheet (+powder coating for -BS type) [MUNSELL 3Y
External Finish
7.8/1.1 or similar]
Electrical Power Requirements Voltage, Phase, Hertz, Power Tolerance 208/230V, 3-phase, 60 Hz, ±10%
Minimum Circuit Ampacity A 44.0/40.0
Maximum Overcurrent Protection A 70/60
Recommended Fuse Size A 45/40
Recommended Minimum Wire Size AWG [mm] 6/8 [13.3/8.4]
SCCR kA 5
Liquid (High Pressure) In. [mm] 3/8 [9.52] Brazed (Pipe Size Dependent on Piping Length)
Refrigerant Piping Diameter
Gas (Low Pressure) In. [mm] 7/8 [22.2] Brazed
Max. Total Refrigerant Line Length Ft. 3,280 [1,000]
Max. Refrigerant Line Length (Between ODU & IDU) Ft. 541 [165]
Max. Control Wiring Length Ft. 1,640 [500]
Total Capacity 50.0~130.0% of outdoor unit capacity
Indoor Unit Connectable
Model/Quantity P04~P96/1.0~24.0
Sound Pressure Levels dB(A) 56.0/58.5
Sound Power Levels dB(A) 75.0/77.5
Type x Quantity Propeller fan x 2
Fan Motor Output kW 0.46+0.46
FAN4 Airflow Rate CFM 6,700
Selectable;
External Static Pressure In. WG 0.00, 0.12, 0.24, 0.32, In. WG;
factory set to 0 In. WG
Compressor Operating Range 15.0% to 100.0%
Compressor Type x Quantity Inverter scroll hermetic compressor x 1
Refrigerant Type x Original Charge R410A x 21.0 lbs + 9.0 oz [9.8 kg]
High Pressure Protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Protection Devices
Inverter Circuit (Comp./Fan) Over-current protection
EER 11.9/12.3
AHRI Ratings (Ducted/Non-ducted) IEER 23.5/26.5
COP 4.04/4.39

NOTES:
Nominal cooling conditions (Test conditions are based on AHRI 1230-2023) 1
Harsh weather environments may demand performance enhancing equipment. Ask your Mitsubishi
Indoor: 80°FD.B./67°FW.B. (26.7°CD.B./19.4°CW.B.), Outdoor: 95°FD.B. (35°CD.B.) Electric representative for more details about your region
Nominal heating conditions (Test conditions are based on AHRI 1230-2023) 2
For details on extended cooling operation range down to -10° F DB, see Low Ambient Kit Submittal
Indoor: 70°FD.B. (21.1°CD.B.), Outdoor: 47°FD.B./43°FW.B. (8.3°CD.B./6.1°CW.B.) 3
When applying product below -4°F, consult your design engineer for cold climate application best
practices, including the use of a backup source for heating
4
Unit will continue to operate in extended operating range, but capacity is not guaranteed

Specifications are subject to change without notice. © 2024 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
OUTDOOR UNIT: TUHYE0963AN41AN – DIMENSIONS
PUHY-EP96, 120, 144T/YNU-A1 Unit: mm (in.)

FORM# TUHYE0963AN41AN - 202405 Variable Refrigerant Flow (VRF) Multi-Split AC and HP


AHRI Standard 1230

Specifications are subject to change without notice. © 2024 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.