Accu 05 Ahu 03

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

SINGLE

ACCU-05-AHU-03(ver 1.9.1.14)

Project Model Selection Summary

Date: 16/05/2024

1. Units
Room Load(ton) Rated/Corrected Capa.(ton) Capacity Ratio(%)

System Name Model Name Type Remark


TC SC HC TC SC HC TC SC HC

ACCU-05-AHU-03-01 21.8 0.0 5.0 AK-W200LH00 Single Package 14.96/14.96 12.62/12.62 14.50/15.51 64.0 0.0 310.2 NA

ACCU-05-AHU-03-02 21.8 0.0 5.0 AK-W200LH00 Single Package 14.96/14.96 12.62/12.62 14.50/15.51 64.0 0.0 310.2 NA

2. Accessories
Model Name Quantity Description

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.

The result can be slightly different from Product Data Book due to simulation.

6
SINGLE
ACCU-05-AHU-03(ver 1.9.1.14)

System Model Selection

System Name: ACCU-05-AHU-03-01 Date: 16/05/2024


System No : 1/2

1. Design Conditions
Cooling Heating

DBT(°C) WBT(°C) RH(%) DBT(°C) WBT(°C) RH(%)

OAT 21.3 18.1 74.0 10.0 6.9 64.6

IAT 23.0 16.2 50.0 20.0 13.8 50.0

2. Requirements
Floor/Room name : ACCU/05 (1) 1 Percent of Mixing Air(OA) : 35 %
Total cooling load : 21.8 ton Heating load : 5.0 ton
Sensible cooling load : 0.0 ton Required air flow : 170 CMM

3. Product Information
Product type : Single Package Total cooling capacity : 14.96 ton
Product name : AK-W200LH00 Sensible cooling capacity : 12.62 ton
Hz : 50,60Hz Heating capacity : 14.50 ton
Refrigerant : R410A Air flow rate : 170 CMM
Type : HeatPump Pipe length : 0.0 m
Cooling input power : 15.26 kW Pipe elevation : 0.0 m
Heating input power : 14.86 kW Electric heater : None
Motor & Drive type : Standard & Standard ESP : 0.01 kgf/cm²
Filter : Exist
4. Simulation Results
Total cooling capacity (Gross/Net*) : 14.96 / 13.95 ton
Sensible cooling capacity (Gross/Net*) : 12.62 / 11.61 ton
Heating capacity : 18.06 ton
SHF 0.84
Cooling power : 15.26 kW
Heating power : 14.11 kW
Additional Refrigerant 0.00 kg

*Please refer to the Product Data Book for net capacity of AK-C03620, AK-C04820, and AK-C06020.

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.

The result can be slightly different from Product Data Book due to simulation.

7
SINGLE
ACCU-05-AHU-03(ver 1.9.1.14)

Model Selection - Psychrometric Chart

System Name: ACCU-05-AHU-03-01 Date: 16/05/2024


System No : 1/2

1. Psychrometric Air Condition(Cooling)


RA OA MA SA

DB(°C) 23.0 21.3 22.4 10.5

WB(°C) 16.2 18.1 16.9 11.5

RH(%) 50.0 74.0 57.9 111.8

2. Psychrometric Air Condition(Heating)


RA OA MA SA

DB(°C) 20.0 10.0 16.5 31.4

WB(°C) 13.8 6.9 11.6 17.2

RH(%) 50.0 64.7 55.3 22.6

8
SINGLE
ACCU-05-AHU-03(ver 1.9.1.14)

System Model Selection

System Name: ACCU-05-AHU-03-02 Date: 16/05/2024


System No : 2/2

1. Design Conditions
Cooling Heating

DBT(°C) WBT(°C) RH(%) DBT(°C) WBT(°C) RH(%)

OAT 21.3 18.1 74.0 10.0 6.9 64.6

IAT 23.0 16.2 50.0 20.0 13.8 50.0

2. Requirements
Floor/Room name : Percent of Mixing Air(OA) : 35 %
Total cooling load : 21.8 ton Heating load : 5.0 ton
Sensible cooling load : 0.0 ton Required air flow : 170 CMM

3. Product Information
Product type : Single Package Total cooling capacity : 14.96 ton
Product name : AK-W200LH00 Sensible cooling capacity : 12.62 ton
Hz : 50,60Hz Heating capacity : 14.50 ton
Refrigerant : R410A Air flow rate : 170 CMM
Type : HeatPump Pipe length : 0.0 m
Cooling input power : 15.26 kW Pipe elevation : 0.0 m
Heating input power : 14.86 kW Electric heater : None
Motor & Drive type : Standard & Standard ESP : 0.01 kgf/cm²
Filter : Exist
4. Simulation Results
Total cooling capacity (Gross/Net*) : 14.96 / 13.95 ton
Sensible cooling capacity (Gross/Net*) : 12.62 / 11.61 ton
Heating capacity : 18.06 ton
SHF 0.84
Cooling power : 15.26 kW
Heating power : 14.11 kW
Additional Refrigerant 0.00 kg

*Please refer to the Product Data Book for net capacity of AK-C03620, AK-C04820, and AK-C06020.

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.

The result can be slightly different from Product Data Book due to simulation.

9
SINGLE
ACCU-05-AHU-03(ver 1.9.1.14)

Model Selection - Psychrometric Chart

System Name: ACCU-05-AHU-03-02 Date: 16/05/2024


System No : 2/2

1. Psychrometric Air Condition(Cooling)


RA OA MA SA

DB(°C) 23.0 21.3 22.4 10.5

WB(°C) 16.2 18.1 16.9 11.5

RH(%) 50.0 74.0 57.9 111.8

2. Psychrometric Air Condition(Heating)


RA OA MA SA

DB(°C) 20.0 10.0 16.5 31.4

WB(°C) 13.8 6.9 11.6 17.2

RH(%) 50.0 64.7 55.3 22.6

10

You might also like