FL500 UV/IR

FLAME DETECTOR
Rugged stainless Self-check feature
steel enclosure

IR detector

UV detector

Three LED status indicators


Custom ID tag
for alarm, fault, and normal
attachment
operating conditions

UV/IR TECHNOLOGY SAFETY INTEGRITY SELF-CHECK


A UV/IR flame detector combines an ultraviolet (UV) sensor Every two minutes, a built in self-check known as Continuous
for quick response and an infrared (IR) sensor that monitors Optical Path Monitoring (COPM) performs an optical and electrical
radiation emitted by a flame. This combination offers increased check to ensure the optical path is clear and the electronic circuitry
immunity, operates at faster speeds and is suited for both is operational.
indoor and outdoor use.

IMPROVED DESIGN RELIABLE TESTING ANYTIME, ANYWHERE


Stainless steel housing, three LED status indicators, reduced The FL500 can be tested with our exclusive TL105 Test Lamp,
footprint, and simplified wiring make the FL500 easy to install which simulates the flickering of a fire. This allows the detector
and maintain. to be tested under simulated fire conditions without the associated
risk of an open flame.

FM PERFORMANCE APPROVED DETECTION


The FL500 UV/IR Flame Detector has seven fuel sources
performance approved by Factory Mutual (FM)—heptane,
hydrogen, methane, methanol, propane, ethane, and butane.
FL500 UV/IR FLAME DETECTOR
SYSTEM SPECIFICATIONS ELECTRICAL SPECIFICATIONS
Wave Lengths 185 to 260 nm (UV) Input Power 20-36 VDC
4.35 microns (IR) 200 mA max. current
Field of View Up to 130° max. conical (3 W max. power consumption)
Fuel Distance (ft.) Response Time (s) Typical Current 80 to 150 mA
n-Heptane 90 6.0 Analog Output Source or Sink
n-Heptane 60 < 3.0 Analog Signal 0-20 mA
Methanol 40 12.0
Methane 80 < 10.0 Fault Mode 0-0.2 mA**
Propane 60 < 7.0 COPM Self-Check Fault 2 mA, ± 0.2 mA***
Butane 55 < 6.0 Ready Signal 4 mA, ± 0.2 mA
Ethane 60 < 3.0
IR Signal 8 mA, ± 0.2 mA
Accessories test lamp
UV Signal 12 mA, ± 0.2 mA
Classification Class I, Div 1, Groups A*, B, C, D;
Class II, Div 1, Groups E, F, G; Alarm Low 16 mA, ± 0.2 mA
Class III, Type 6P Alarm High 20 mA, ± 0.2 mA
Ex db IIC T5 Gb; Relay Contact Rating 5 A 250 VAC,
Ex tb IIIC T100°C Db 5 A @ 30 VDC resistive (North America),
II 2 G D 5 A @ 30 V RMS/42.4 V peak,
IP66/IP67 5 A @30 VDC resistive (Europe)
Warranty Three Years Dip Switch Selectable Options
Approvals CSA, FM, ATEX, IECEx, CE Marking Sensitivity High, Medium, Low
Compliance to CPR through EN 54-10 Time Delay Alarm High 2, 4, 8, or 10 seconds
HART 7 registered Alarm Low & Alarm High Relays Latching/Non-Latching
SIL 3 suitable Energized/De-Energized
RS-485 Output Modbus RTU, suitable for linking up to 128
units or up to 247 units with repeaters.
ENVIRONMENTAL SPECIFICATIONS BAUD Rate 2400, 4800, 9600, or 19200 BPS

Operating Temperature Range -67°F to +185°F HART Fully HART 7 FieldComm compliant
(-55°C to +85°C) EMC Complies with EN 50130-4, EN 61000-6-4
Storage Temperature Range -40°F to +185°F Cable Requirements Screened or screened and armored to
(-40°C to +85°C) BS5308 Part 2, Type 2, or equivalent.
Operating Humidity Range 0% to 95% RH, non-condensing Status Indicator 3 LEDs with status, fault,
and alarm conditions
Faults Monitored Memory checksum, reset line shorted,
optics blockage, internal voltages,
MECHANICAL SPECIFICATIONS and low supply voltage
Housing 316 Stainless Steel, powder coated
* Applicable to FM approval only
Diameter 4.5” (114 mm) ** Under HART, current values can be either 3.5 mA or 1.25 mA, depending on user selection
*** Under HART, current values can be either 3.5 mA or 2.0 mA, depending on user selection
Length 5.5” (140 mm)
Weight 9 lb. (4.0 kg)
Mounting Stainless steel mounting bracket
Cable Entry 2 x 3/4” NPT or 2 x 25 mm
Standard Configuration FL500-5-5-1-2-1-1-1-1
1.25 mA HART, source current, relays,
Modbus, high sensitivity, 4 sec. delay,
3/4” NPT, mounting bracket

Note: This Bulletin contains only a general description of the products shown. While product uses and performance capabilities are generally MSA operates in over 40 countries
described, the products shall not, under any circumstances, be used by untrained or unqualified individuals. The products shall not be used until
the product instructions/user manual, which contains detailed information concerning the proper use and care of the products, including any worldwide. To find an MSA office near you,
warnings or cautions, have been thoroughly read and understood. Specifications are subject to change without prior notice. please visit MSAsafety.com/offices.

1466-18-MC / 05.2021
© MSA 2021
MSAsafety.com/detection