Edwards E2M28 To E2M30 Instruction Manual
Edwards E2M28 To E2M30 Instruction Manual
Edwards E2M28 To E2M30 Instruction Manual
Issue D
Instruction Manual
IEC 34 Parts 1, 5, 8†, 11* General Requirements for Rotating Electrical Machines.
C22.2 No77-1988# Motors with Inherent Overheating Protection.
C22.2 No 100-92# Motors and Generators.
†
3-phase pumps only.
*
1-phase pumps only.
#
1-phase pumps only. Canadian Standard Association.
23/9/96 Crawley
Dr. A. P. Troup, Director of Technology Date and Place
This product has been manufactured under a quality system registered to ISO9001
CONTENTS
1 INTRODUCTION 1
1.1 Scope of this manual 1
1.2 Description 3
1.3 Gas-ballast 3
2 TECHNICAL DATA 4
2.1 Operating and storage conditions 4
2.2 Performance 4
2.3 Mechanical data 5
2.3.1 General 5
2.4 Electrical data; single-phase motors 5
2.5 Electrical data; three-phase motors 5
2.6 Lubrication data 5
3 INSTALLATION 8
3.1 Safety 8
3.2 System design 9
3.3 Unpack and inspect 9
3.4 Locate the pump 10
3.5 Fill the pump with oil 10
3.6 Electrical installation: single-phase motors 11
3.7 Electrical installation: three-phase motors 13
3.7.1 Connect the pump to your electrical supply 13
3.7.2 Check the direction of rotation 15
3.8 Inlet connection 16
3.9 Outlet connection 17
3.10 Gas ballast inlet connection 17
3.11 Leak test the system 17
4 OPERATION 18
4.1 Gas-ballast control 18
4.2 Start-up procedure 18
4.3 To achieve ultimate vacuum 19
4.4 To pump condensable vapours 19
4.5 To decontaminate the oil 20
4.6 Unattended operation 20
4.7 Shut-down 20
5 MAINTENANCE 21
5.1 Safety information 21
5.2 Maintenance plan 22
PTS219515 Issue A
Tables
Table Title Page
Associated publications
Publication title Publication number
WARNING
Warnings are given where failure to observe the instruction could result in injury or death
to people.
CAUTION
Cautions are given where failure to observe the instruction could result in damage to the
equipment, associated equipment and process.
The units used throughout this manual conform to the SI international system of units of
measurement.
The E2M28 and E2M30 pumps are two-stage, direct drive, sliding vane pumps. The pump is
oil-sealed and designed for reliable, long-term operation in both laboratory and industrial
environments. The pump is a free-standing unit. The drive is provided through a flexible
coupling by a single-phase or three-phase (four pole) motor.
The motors are totally enclosed and are cooled by the motor-cooling fan which directs air along
the motor fins.
The single-phase motors have a thermal overload device. When the motor is too hot, the thermal
overload device switches off the pump. The thermal overload device has an automatic reset;
when the motor cools down, the device resets and the motor will restart. The single phase motors
have an on/off switch.
An oil pressure system lubricates the pump shaft bearing surfaces and rotor sealing faces. The
pump has an oil distribution valve which prevents discharge of oil to the pump interior
(suckback) after the pump stops. The pumping chambers are air-tight, so this arrangement
prevents air suckback unless the gas-ballast valve is open. For protection in this case, refer to
Section 1.3.
You can inspect the level and condition of oil in the oil box reservoir through the oil sight-glass
(12). An oil filler-plug (1) is fitted to the top of the oil box. The pump has two oil drain-plugs
(11 and 14) to allow either gravity oil drain or pressure oil drain.
The pump has inlet-port (6), outlet nozzle (2) and gas-ballast control (3). The pump is mounted
on an aluminium alloy baseplate (10) on rubber pads. Details of suitable vibration isolators and
other recommended accessories are given in Section 7.
1.3 Gas-ballast
To pump high vapour loads, gas-ballast is delivered into the pump to prevent condensation of
the vapour carried by the pumped gases.
Air (or another gas) can be introduced into the low vacuum stage through the gas-ballast control.
The gas-ballast control is a multi-turn valve which you can adjust, as required, between closed
and fully open.
2.2 Performance
Note: Where total pressures are shown in the technical data tables, measurements were taken using
an untrapped total pressure capacitance diaphragm gauge on a header, as specified by Pneurop
standards.
E2M28 E2M30
Maximum displacement
50 Hz electrical supply 32.2 m3h-1 19 cfm
60 Hz electrical supply 38.9 m3h-1 23 cfm
Maximum speed - Pneurop
50 Hz electrical supply 27.5 m3h-1 16.2 cfm
60 Hz electrical supply 33.0 m3h-1 19.4 cfm
Motor rotational speed
50 Hz electrical supply 1440 r min-1 1440 r min -1
60 Hz electrical supply 1720 r min-1 1720 r min -1
Ultimate vacuum
without gas-ballast (partial pressure) 1 x 10-4 mbar 7 x 10-5 torr
(1 x 10-2 Pa)
without gas-ballast (total pressure) 1 x 10-3 mbar 7 x 10-4 torr
(1 x 10-1 Pa)
with full gas-ballast (partial pressure) 2 x 10-1 mbar 1.5 x 10-1 torr
(2 x 101 Pa)
Maximum water vapour inlet pressure 30 mbar 22.5 torr
(3 x 103 Pa)
Maximum water vapour pumping rate 0.7 kgh-1 0.7 kgh-1
Maximum permitted outlet pressure 0.5 bar gauge, 0.5 bar gauge,
(at full pump throughput) 1.5 bar absolute, 1.5 bar absolute,
1.5 x 105 Pa 1.5 x 105 Pa
Note: An Edwards Health and Safety Data Sheet for the following oil is available on request.
* To operate the pump when the ambient temperature is outside the range specified in Section
2.1, or to optimise the pump performance when you process condensible vapours, you may
need a different oil.
A373-15-903
220-240 50 4.8 33 15 3 11 - 251
or
230-240 60 5.0 33 15 3 11 - 251
A374-15-903
A373-15-981
115 60 11.0 71 40 4 12 597 251
or
230 60 5.5 36 20 5 12 597 251
A374-15-981
Electrical Dimension
Voltage Frequency Full load Start Recommended supply in
(V) (Hz) current (A) current (A) fuse rating (A) connection Figure 2 (mm)
Figure
A B
3.1 Safety
WARNING
The E2M28 and E2M30 pump are not recommended for pumping hazardous substances.
WARNING
If you use a hydrocarbon oil in this pump, you must not use the pump to process oxygen
in concentrations greater than 25% in volume. If you do, there is a risk of fire or explosion
in the oil-box of the pump.
You must ensure that the E2M28 or E2M30 pump is suitable for your application, If you have
any doubts as to the suitability of the E2M28 or E2M30 pump for your application, refer to the
Edwards guidelines on vacuum pump and vacuum system safety (see the Associated
Publication at the end of the contents list at the front of this manual).
Obey the safety instructions listed below when you install the pump, especially when you
connect the pump into an existing system. Details of specific safety precautions are given at the
appropriate point in the instructions.
• The installation of your E2M28 or E2M30 pump must be performed by a suitably trained
and supervised technician.
• Wear the appropriate safety-clothing when you come into contact with contaminated
components.
• Vent and purge your vacuum system before you start installation work.
• Ensure that the installation technician is familiar with the safety procedures which relate to
the pump-oil and the products processed by the pumping system. Take suitable precautions
to avoid the inhalation of oil mist and excessive skin contact with pump-oil, as prolonged
exposure can be harmful.
• Disconnect the other components in the pumping system from the electrical supply so that
they cannot be operated accidentally.
• Use a suitable inlet-valve to isolate the pump from your vacuum system if you need to allow
the pump to warm up before you pump condensable vapours or if you need to maintain
vacuum when the pump is switched off.
• Avoid high levels of heat input to the pump from the process gases, otherwise the pump
may overheat and seize, and cause the motor thermal overload device to open.
• If you use the pump in a high ambient temperature and have a high gas throughput, the
temperature of the pump-body may exceed 70 oC and you must fit suitable guards to prevent
contact with hot surfaces.
• Make sure that the exhaust pipeline cannot become blocked. If you have an outlet-isolation
valve, make sure that you cannot operate the pump with the valve closed.
• Provide for a purge of inert gas when you shut down the pumping system, to dilute
dangerous gases to safe concentrations. A suitable gas-ballast control valve for introduction
of purge gas into the pump is available as an accessory (see Section 7.3.5).
Check that your package contains the items listed in Table 3. If any of these items are missing,
notify your supplier within 3 days.
If the pump is not to be used immediately, replace the protective covers. Store the pump in
suitable conditions, as described in Section 6.
WARNING
The pump can be either free-standing on its baseplate or fixed by bolts through the four fixing
holes in the baseplate; or used with vibration isolators. For the location of fixing holes in the
baseplate, refer to Figure 2. Provide a firm, level platform for the pump. Locate the pump so
that the oil-level sight-glass is visible and the oil filler-plug, oil drain-plugs and gas-ballast
control are accessible.
If your pump will be located inside an enclosure, make sure that there is adequate ventilation at
both ends of the pump, so that the ambient temperature around the pump does not exceed 40 oC.
There must be a minimum space of 25 mm between the pump and the enclosure walls.
2. Pour oil into the pump until the oil-level reaches the MAX mark on the bezel at the top of
the oil sight-glass (12). If the oil-level goes above the MAX mark, remove the oil drain-plug
(11) and drain the excess oil from the pump.
3. After a few minutes, recheck the oil-level. If the oil-level is now below the MAX mark, pour
more oil into the pump.
4. Refit the oil filler-plug. Tighten the plug firmly by hand. Do not overtighten.
WARNING
Ensure that the electrical installation of the E2M28 or E2M30 conforms with your local and
national safety requirements. It must be connected to a suitably fused and protected
electrical supply and a suitable earth point.
CAUTION
If your pump-motor can be used with more than one voltage range, you must ensure that
the motor is configured for your electrical supply voltage and frequency. If you do not,
you may damage the motor.
Note: The pump will restart automatically when the electrical supply is restored after an interruption
and when the pump cools after it has overheated. If you do not want the pump to restart
automatically, use electrical control equipment which must be reset manually.
Ensure that your electrical supply voltage corresponds with the voltage specified on the motor
data plate. Table 1 gives the figure reference of the correct electrical supply connection diagram
and details the recommended fuse rating.
The diameter of the outer sheath of the electrical supply cable must be within the range 7 mm
to 10.5 mm. The cable must conform in size and colour coding with your local and national
electrical installation regulations.
1. Remove the cover from the motor terminal box (Figure 1, item 8).
2. Remove the cable-gland from the inside of the terminal-box and fit the cable-gland to the
cable leadthrough hole in the side of the terminal-box.
6. Select the correct size of receptacle connectors for your cable wires: use the red connectors
for wire sizes 0.75 mm2 to 1.5 mm2 or the blue connectors for wire sizes 1. 5 mm2 to 2.5 mm2.
8. Connect the electrical supply cable to the appropriate terminals as shown in Figures 3 to 5.
9. Tighten the dome shaped nut on the cable-gland until the outer sheath of the cable is firmly
gripped. Do not overtighten.
BN Brown
OR Orange
VT Violet
WH White
BN Brown
OR Orange
VT Violet
WH White
Figure 5 - Electrical supply connection, single-phase motors, 200 V 50 Hz, 200-210 V 60 Hz,
or 230 V 60 Hz
WARNING
Ensure that the electrical installation of the pump conforms with your local and national
safety requirements. It must be connected to a suitably fused and protected electrical
supply and a suitable earth point.
CAUTION
If your pump-motor can be used with more than one voltage range, you must ensure that
the motor is configured for your electrical supply voltage and frequency. If you do not,
you may damage the motor.
If you do not want the pump to restart automatically, use electrical control equipment which
We recommend that you connect the electrical supply to the motor through a starter or circuit
breaker which has thermal over-current protection which can be adjusted to suit the full load
current ratings shown in Table 2. The fuse ratings in Table 2 are provided for guidance only.
The supplier of your thermal over-current protection device may specify different values to
ensure correct operation of the fuse and the over-current protection device. Ensure that the fuse
you use is suitable for the starting currents given in Table 2. Table 2 also gives the figure reference
of the correct electrical supply connection diagram for your motor.
The diameter of the outer sheath of the electrical cable must be in the range 10-14 mm. The cable
must conform in size and colour coding with your local and national electrical installation
regulations.
2. Remove the cable-gland from the inside of the terminal-box and fit the cable-gland to the
cable leadthrough hole in the side of the terminal-box.
3. Refer to the electrical supply connection diagram for your pump, (Figure 6 or 7). Make sure
that the metal links are connected as shown; if they are not, move the links to the position
shown.
4. Pass the electrical supply cable through the cable-gland and connect to the appropriate
terminals, as shown in Figures 6 and 7.
5. Tighten the cable gland until the outer sheath of the cable is firmly gripped. Do not
overtighten.
6. Ensure that the gasket seal for the terminal box cover is correctly positioned, then refit the
cover to the terminal-box and secure with the screws.
CAUTION
Ensure that the pump-motor rotates in the correct direction. If it does not, the pump and
your vacuum system can become pressurised.
• Connect to the NW25 flange supplied: use the NW25 centring ring and ’O’ ring supplied.
• Remove the NW25 flange and connect to the 1 inch BSP threaded hole.
• Use an NW25 to 28 mm bore tube adaptor available as an optional accessory, see Section 7.
Take note of the following information when you connect the pump to your vacuum system.
Refer to Section 7 for details of the accessories mentioned below.
• For optimum pumping speeds, ensure that the pipeline connected to the inlet-port is as short
as possible and has an internal diameter not less than the inlet-port diameter.
• Support the vacuum pipelines to prevent loading of the coupling-joints.
• If necessary, incorporate flexible bellows in your system pipelines to reduce the transmission
of vibration and to prevent loading of coupling-joints. If you use flexible bellows, you must
ensure that you use bellows which have a maximum pressure rating which is greater than
the highest pressure that can be generated in your system. We recommend that you use
Edwards flexible bellows.
• Use a suitable inlet catchpot if you pump condensable vapours or if you use the pump for
very dusty applications.
• Ensure that sealing surfaces are clean and scratch-free.
WARNING
Connect the pump outlet to a suitable treatment plant to prevent the discharge of
dangerous gases and vapours to the surrounding atmosphere. Use a catchpot to prevent
the drainage of contaminated condensate back into the pump.
To connect the pump to your outlet accessories or to your exhaust treatment plant, you can:
Take note of the following information before you connect to the pump outlet:
• The exhaust system must be configured so that the maximum pressure at the pump outlet
does not exceed 0.5 bar gauge (1.5 bar absolute, 1.5 x 105 Pa) at full pump throughput.
• In the following circumstances, we recommend that you fit an oil mist filter to the pump
outlet:
• if you use the pump with the gas-ballast control open
• if you operate the pump with an inlet pressure greater than 10 mbar for extended
periods or
• if you frequently pump down from atmospheric pressure.
The mist filter will trap the oil exhausted from the pump: you can re-use the oil if it is not
contaminated.
If you want to use a different gas for the gas ballast supply, or if you want to connect a valve to
the gas ballast inlet, remove the filters (as described in Section 5.6) and connect your gas supply
or valve to the 1/4 inch BSP threaded hole.
Turn the gas-ballast control 6 turns anti-clockwise to open it fully. Use the gas-ballast control
open:
When you operate the pump with the gas-ballast control open, there will be an increased rate of
oil loss from the pump.
WARNING
Do not block the pump outlet or allow the outlet pressure to rise above 1.5 bar absolute.
If you do, the oil box may fracture: this may cause injury to people nearby.
If the oil is contaminated, or if the pump temperature is below 13 oC, or if the electrical supply
voltage is more than 10% below the lowest voltage specified for the pump, the pump may operate
at a reduced speed for a few minutes. On single-phase pumps, if the pump continues to operate
at reduced speed, the motor thermal overload device will open and stop the pump. When the
motor has cooled, the thermal overload device will reset automatically and the pump will restart.
1. Check that the pump oil-level is between the MAX and MIN marks on the bezel of the
oil-level sight-glass; if it is not, refer to Section 5.3.
2. Turn the gas-ballast control to the required position (refer to Section 4.1).
4. Check that the oil-level in the sight-glass drops slightly (3 to 5 mm) after start-up. This shows
that the pump has primed with oil.
• Your pressure measurement technique or gauge head is unsuitable or the gauge head is
faulty.
• You have used an oil other than the recommended oil, and the vapour pressure of the oil is
higher than the specified ultimate vacuum of the pump.
2. Turn the gas-ballast control fully anti-clockwise (fully open) and operate the pump for at
least 1 hour (or overnight) to thoroughly purge the oil of contaminants.
4. Open the vacuum system isolation-valve and pump down to ultimate vacuum.
2. Turn the gas-ballast control anti-clockwise to fully open and operate the pump for 30
minutes to warm the oil; this will help to prevent vapour condensation in the pump.
3. Open the vacuum system isolation-valve and continue to operate the pump with the
gas-ballast control open.
After you have pumped condensable vapours, you can (if necessary) decontaminate the oil; use
the procedure in Section 4.5.
1. Look at the condition of the oil in the oil sight-glass (Figure 1, item 12). If the oil is cloudy
or discoloured, continue with the procedure at Step 2 below.
Single-phase motors are cooled by internal fans. These motors have a thermal overload device.
When the motor is too hot, the thermal overload device switches off the pump. The thermal
overload device has an automatic reset; when the motor cools down, the device resets and the
motor will restart. When you check the pump, make sure that the pump is not going through a
repetitive cycle of thermal overload failures and automatic resets. If necessary reduce the
thermal load from the pumped gases, to prevent overheating of the pump.
4.7 Shut-down
Note: If the gas-ballast control is open and the pump is switched off for any reason, the pump drive
shaft may rotate in the reverse direction, causing a system pressure rise. To prevent this, use
a gas-ballast control valve (refer to Section 7.3.5).
We recommend, as described in the procedure below, that you decontaminate the oil before you
shut down the pump; this will prevent damage to the pump by the contaminates in the oil.
WARNING
Obey the safety instruction given below and take note of appropriate precautions. If you
do not, you can cause injury to people and damage to equipment.
• Ensure that maintenance is done by a suitably trained and supervised technician. Obey your
local and national safety requirements.
• Ensure that the maintenance technician is familiar with the safety procedures which relate
to the pump-oil and the products processed by the pumping-system.
• Allow the pump to cool to a safe temperature before you start maintenance work.
• Isolate the pump and other components in the pumping system from the electrical supply
so that they can not be operated accidentally.
• After maintenance is completed, recheck the pump rotation direction if the electrical supply
has been disconnected.
• Do not reuse ’O’ rings and seals if they are damaged.
• The pump and its fluid will be contaminated with the process chemicals that have been
pumped during operation. Ensure that the pump is decontaminated before maintenance
and that you take adequate precautions to protect people from the effects of dangerous
substances if contamination has occurred.
• Do not touch or inhale the thermal breakdown products of fluorinated materials which may
be present if the pump has been heated to 260 oC and above. These breakdown products
are very dangerous. Fluorinated materials in the pump may include oils, greases and seals.
The pump may have overheated if it was misused, if it malfunctioned or if it was in a fire.
Edwards Health and Safety Data sheets for fluorinated materials used in the pump are
available on request: contact your supplier or Edwards.
• Leak-test the system after maintenance work is complete if you have connected or
disconnected any vacuum or exhaust joints; seal any leaks found.
More frequent maintenance may be required if the pump is used to process corrosive or abrasive
gases and vapours; in these circumstances, we recommend that you replace the pump seals every
year. If necessary, adjust the maintenance plan according to your experience.
When you maintain the pump, use Edwards spares and maintenance kits; these contain all of
the components necessary to complete maintenance operations successfully. The Item Numbers
of the spares and kits are given in Section 7.
Examine the condition of any external accessories, filters or traps (if fitted). Refer to the
instructions supplied with these accessories for maintenance procedure.
1. Check that the oil-level in the oil sight-glass (12) is between the MAX and MIN level marks
on the bezel of the sight-glass.
2. If the oil-level is near to or below the MIN level mark, remove the oil filler-plug (1) and pour
more oil into the reservoir until the oil reaches the MAX level mark. If the oil-level goes
above the MAX mark, remove the oil drain-plug (11) and drain the excess oil from the pump.
Refit the oil filler-plug.
3. If the oil is contaminated, drain and refill the pump with clean oil as described in Section 5.4.
The pressure drain method is the fastest method, but requires you to operate the pump: we
recommend that you use an oil drain extension tube (available as an optional accessory, see
Section 7).
2. Isolate the pump from your electrical supply and disconnect it from your vacuum system.
4. Place a suitable block under the pump-motor to tilt the pump and place a suitable container
under the oil drain-plug (gravity drain) (11). Remove the oil drain-plug and allow the oil
to drain into the container.
5. If the oil is dirty or contaminated, replace the oil-filler plug and pour clean oil into the pump.
Reconnect the pump to the electrical supply and operate the pump for about 5 to 10 minutes.
Disconnect the pump from the electrical supply, remove the oil filler-plug and allow the oil
to drain out of the pump. Repeat this step until the oil reservoir is clean.
1. Inlet adaptor
2. ’O’ ring
3. Circlip
4. Inlet-filter
6. Refit the oil drain-plug, remove the block and reconnect the pump to your vacuum system.
8. Allow a few minutes for the oil to drain into the pump. If necessary, add more oil. Refit the
oil filler-plug.
4. Screw the oil drain extension accessory (or another suitable tube) into the 1/8 inch BSP
threaded hole. Connect a flexible hose from the tube to a suitable container to collect the
drained oil.
5. Switch on the pump and fully open the gas-ballast control (3). Partially restrict the pump
outlet while the oil drains from the pump (this causes a positive pressure in the oil box and
forces the oil out through the pressure drain tube).
6. As soon as the oil has drained, remove the partial restriction from the pump outlet. Switch
off the pump.
7. If the oil is dirty or contaminated, pour clean oil into the pump. Operate the pump for about
5 to 10 minutes. Drain the oil from the pump as described in steps 5 and 6 above. Repeat
8. Remove the drain hose and extension tube. Replace the oil drain-plug.
9. Fill a suitable container with clean oil, remove the oil filler-plug (1) and pour the oil into the
filler hole until the oil-level reaches the MAX level mark on the bezel of the oil sight-glass
(12).
10. Allow a few minutes for the oil to drain into the pump. If necessary, add more oil. Refit the
oil filler-plug.
1. Unscrew the inlet adaptor (1) and remove the ’O’ ring (2), circlip (3) and inlet-filter (4).
2. Wash the filter in a suitable cleaning solution. Allow the filter to dry.
Refer to Figure 9.
2. Remove the protective wire mesh (2) and filter elements (1).
3. Wash the wire mesh and filter in a suitable cleaning solution. Allow the wire mesh and filter
to dry before replacing them in the pump.
4. Replace the wire mesh (2) and filter element (1) in the adpator plate housing and retain with
the retainer circlip (3).
1. Filter element
2. Wire mesh
3. Retainer circlip
2. Use a dry cloth and a brush to remove dirt and deposits from the fan-cover.
5.11.5 The vacuum is not maintained after the pump is switched off
• The gas-ballast control is open.
• ’O’ ring(s) are damaged or missing.
• The shaft seals have deteriorated.
6.1 Storage
CAUTION
Observe the storage temperature limits stated in Section 2. Storage below -30 oC will
permanently damage the pump seals.
Note: If you will store a new pump in conditions of high humidity, remove the pump from its
cardboard packaging box; dispose of the box (refer to Section 6.2).
3. Purge your vacuum system and the pump with dry nitrogen and disconnect the pump from
your vacuum system.
5. Place and secure protective covers over the inlet and outlet-ports.
6. Store the pump in cool, dry conditions until required for use. When required, prepare and
install the pump as described in Section 3. If the pump has been stored for more than a year,
before you install the pump you must clean and overhaul it as described in the instructions
supplied with the clean and overhaul kit.
6.2 Disposal
Dispose of the pump, the oil and any components removed from the pump in a safe manner in
accordance with all local and national safety and environmental requirements.
• Components which have come into contact with the pump fluid.
• Components which have been contaminated with dangerous process substances.
7.1 Introduction
Edwards products, spares and accessories are available from Edwards companies in Belgium,
Brazil, Canada, France, Germany, Hong Kong, Italy, Japan, Korea, Switzerland, United
Kingdom, U.S.A and a worldwide network of distributors. The majority of these centres employ
Service Engineers who have undergone comprehensive Edwards training courses.
Order spare parts and accessories from your nearest Edwards company or distributor. When
you order, state for each part required:
7.2 Spares
The following maintenance kits contain all of the parts you will need to maintain your pump.
The maintenance kits also include instructions for the use of the kits. Use the Clean and Overhaul
Kit for routine maintenance operations. Use the Blade Kit together with the Clean and Overhaul
Kit when you must renew the blade assembly in the rotary pump.
7.3 Accessories
A range of accessories is available for the E2M28 and E2M30 pumps; refer to Figure 10.
Figure 12 - Single-phase motor electrical circuit diagram, for pumps A373-15-981, A374-15-981, A373-15-904 and A374-15-904
r dr
o ai
d n
u ex
c te
t ns
I io
B
t n
e 50
m 0-
N 02
u -0
m 00
b
e
r
7.
O 3.
10
P
u
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
NW m
p in- 25 to
let 28
adap- m m
tor bore
tube
adap
tor,
supp
lied
with
con
nect
High Voltage
Low Voltage
A
i o n
har
dwa
r e .
Atta
B
c h
A
this
adap
tor to
t h e
NW
2 5
pump-inlet to connect 28mm bore plastic or rubber tube.
Figure 10 - Accessories
pumps A373-15-903 and A374-
Figure 11 - Single-phase motor
electrical circuit diagram, for
15-903