DRC 40 Spec
DRC 40 Spec
DRC 40 Spec
Bauar t gepruft
Sicherheit
LPS
egel ma ge
od o s
be wac g
www.tuv.com
ID 2000000000
■ Features ■ Applications
Universal AC input / Full range Security system
Protections: Short circuit / Overload / Over voltage Emergency lighting system
Battery low protection / Battery reverse polarity protection Alarm system
by fuse DC UPS system
Can be installed on DIN rail TS-35/7.5 or 15 •Central monitoring system
Alarm signal for AC OK and Battery low Access systems
(via TTL open collector, optional via relay)
Cooling by free air convection
Pass LPS
LED indicator for power on
100% full load burn-in test ■ GTIN CODE
MW Search: https://www.meanwell.com/serviceGTIN.aspx
3 years warranty
■ Description
DRC-40 is a 40W AC/DC DIN rail type security power supply series. In addition to the primary output, there
is a charger output with a smaller rated current, enabling the backup power supply application the security
access systems require. DRC-40 accepts the universal input between 90VAC and 264VAC, and supplies
13.8VDC and 27.6VDC at output, respectively. With the efficiency up to 87%, it can operate with air
convection cooling under -30 ℃ through 70 ℃ . In addition to the key protection features such as overload
protection, over voltage protection, battery low cut off, and battery reverse polarity protection (by fuse),
the alarm signal for AC OK and battery low signaling is provided, via TTL open collector output for the
standard model ( via relay contact output as the optional model), to facilitate the system design.
■ Model Encoding
DRC - 40 A
Output voltage
Output wattage
Series name
SPECIFICATION
MODEL DRC-40A DRC-40B
OUTPUT NUMBER CH1 CH2 CH1 CH2
DC VOLTAGE 13.8V 13.8V 27.6V 27.6V
RATED CURRENT 1.9A 1A 0.95A 0.5A
CURRENT RANGE 0 ~ 2.9A -------- 0 ~ 1.45A --------
RATED POWER 40.02W 40.02W
RIPPLE & NOISE (max.) Note.2 120mVp-p -------- 200mVp-p --------
OUTPUT
VOLTAGE ADJ. RANGE CH1:12 ~ 15V CH1:24 ~ 30V
VOLTAGE TOLERANCE Note.3 ±1.0% -------- ±1.0% --------
LINE REGULATION ±0.5% -------- ±0.5% --------
LOAD REGULATION ±0.5% -------- ±0.5% --------
SETUP, RISE TIME Note.4 400ms, 50ms/230VAC 800ms, 50ms/115VAC at full load
HOLD UP TIME (Typ.) 50ms/230VAC 10ms/115VAC at full load
VOLTAGE RANGE 90 ~ 264VAC 127 ~ 370VDC [DC input operation possible by connecting AC/L(+), AC/N(-)]
FREQUENCY RANGE 47 ~ 63Hz
INPUT EFFICIENCY (Typ.) 86% 87%
AC CURRENT (Typ.) 0.8A/115VAC 0.6A/230VAC
INRUSH CURRENT (Typ.) COLD START 30A/115VAC 60A/230VAC
105 ~ 150% rated output power
OVERLOAD
Protection type : Hiccup mode, recovers automatically after fault condition is removed
PROTECTION CH1:14.49 ~ 18.63V CH1:28.98 ~ 37.26V
OVER VOLTAGE
Protection type : Shut down o/p voltage, re-power on to recover
BATTERY CUT OFF 10±0.5V 20±1V
AC OK Open collector output, CONTACT : AC OK ; CUT OFF : AC Fail ; max. rating : 50V/30mA
FUNCTION Open collector output, CUT OFF : Battery ; CONTACT : Battery Low ; max. rating : 50V/30mA
BATTERY LOW
Battery low voltage : < 11V Battery low voltage : < 22V
WORKING TEMP. -30 ~ +70℃ (Refer to "Derating Curve")
WORKING HUMIDITY 20 ~ 90% RH non-condensing
ENVIRONMENT STORAGE TEMP., HUMIDITY -40 ~ +85℃, 10 ~ 95% RH
TEMP. COEFFICIENT ±0.03%/℃ (0 ~ 55℃) on CH1 output
VIBRATION 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
SAFETY STANDARDS UL62368-1, TUV BS EN/EN62368-1, EAC TP TC 004, AS/NZS 60950.1 approved
Block Diagram
AC OK
ALARM
Bat. Low
CIRCUIT
DETECTION Bat. -
CIRCUIT
PWM
O.L.P. Battery Charger
CONTROL
&
O.V.P. Back up Control
100
100
90
80
230VAC 80
Input only
60 70
LOAD (%)
LOAD (%)
60
40
50
20
40
-30 -20 0 15 30 40 50 55 60 70 (VERTICAL) 90 100 125 135 145 155 165 175 180 200 230 264
Suggested Application
1.Backup connection for AC interruption
(1) Please refer to Fig1.1 for suggested connection.
The power supply charges the battery and provides energy to the load at the same time when AC mains is OK.
The battery starts to supply power to the load when AC mains fails.
A : 12V
B : 24V Load
Battery
+ - + -
Bat+ Bat- V+ V-
DC OK
+
+V ADJ
The signal is "Low" when the voltage of battery is under A:11V, B:22V. Low (0.3V max. at 30mA)
Battery Low
The signal is "High" when the voltage of battery is above A:11V, B:22V. High or open (External applied voltage 50V max.)
AC OK (Battery low)
PIN6(PIN8)
R
V
PIN5(PIN7)
Fig 2.2 Internal circuit of AC OK (Battery Low), via TTL open collector
Mechanical Specification
Case No.962A Unit:mm
40
100
3.81×7
8 7 6 5 4 3 2 1
TB2
DC OK
+
+V ADJ
90
TB1
3 2 1
7.5 7.5
Installation Instruction
Back View
Installation Manual
Please refer to : http://www.meanwell.com/manual.html