EME 109 Lab 3 PDF
EME 109 Lab 3 PDF
EME 109 Lab 3 PDF
Conditioning/Psychrometric Experiment
Austin Jones
In this lab, our goal was to demonstrate the characteristics of an air conditioner system as
well as the principles of psychrometrics. Specifically, we analyzed the P.A. Hilton Air
Conditioning Laboratory Unit under different operating conditions (see table 3 in appendix),
which is equipped with a pre-heater, after-heater, and boiler. Case 1 was the basic air conditioner
operation. Case 2 applied a heat load by turning on pre-heater. Case 3 had the pre-heater turned
off, but the after-heater and boiler switched on. Various measuring instruments were used to get
properties of the air and refrigerant such as a thermocouple, thermometers, flow meter,
Before starting, we recorded the ambient temperature, pressure and relative humidity of
the lab environment. Then we used the measuring instruments to record data for each of the
cases after reaching steady state. The data was then analyzed in various manners shown in the
following section.
Results and Discussion:
The 4 different states were plotted on the PH diagram for the R-134a cycle (see figure 1).
Case 1 is shown in red, 2 is shown in blue, and 3 is shown in green. State 1 was plotted by the
point corresponding to pressure and temperature 1 (t3 and p3). The pressures were converted to
MPa in order to use the chart. State 3 was plotted from the corresponding temperature and
pressure at state 3 (t3 and p3). The transition between states 3-4 was assumed isenthalpic, so the
temperature at state four was found by the measuring the temperature at 4 (t4). State 2 was
plotted at the same pressure as 3 and found by using temperature at 2 (t2) because the process
(see figure 2). Case 1 is shown in red, 2 is shown in blue, and 3 is shown in green. These plots
were easily drawn by marking points for each dry and wet bulb temperatures.
To get the mass flow rates, we used the specific volume of air at station D and the
inclined manometer reading for each case. The following equation was used to determine mass
flow rates:
√
z
m = .0504 v , where
m=mass flow rate [kg/s] z=manometer reading [mmH20]
v=specific volume [m3/kg]
The values of the mass flow rate for each case are presented in table 4 in the appendix.
To obtain the heat transfer of the pre-heater coils, the mass flow was used, as well as the
The results from case 2 yield a heat transfer rate of 0.4169 kW.
P = V2/R
In our case, the preheater power ratings were 926.4 and 920.51 W. Adding these, we get a total
power of 1.846 kW. Our heat transfer rate is much smaller, most likely due to losses in the system.
Two different approaches were used to estimate mass transfer from steam generator. The
first method applies energy and mass balances to the boiler. By assuming all electrical energy
entering boiler was used to convert water to steam and that there was no heat loss, the balance
P = Δhvap × mboiler
P is the input power of 4.35 kW, Δhvap is the heat of vaporization of water which is 2256 kJ/kg,
and mboiler is the mass flow rate of the water leaving the boiler as steam. By sloving for mboiler, the
flow rate was multiplied by the difference in absolute humidities of states A3 and B3:
Using this equation, the value turned out to be 0.1128 g/s. The discrepancy in these two methods
is probably due to the fact that a few of the cancellations in the energy balance are false. There
was most likely a significant amount of heat loss in the boiler, and some steam may have escaped
To find the condensate flow rate in case 3, we divided the amount of condensate collected
by the time taken to collect the condensate. Our experiment yielded a flow rate of 0.326 g/s, and
volumetric flow rate of 0.326 ml/sec. The condensate flow rate is calculated by multiplying the
mass flow rate by the difference in absolute humidity between states C and B:
Our experiment yields a value of 0.0752 g/s. The large difference between the two values is most likely
due to reading off of the psychrometric chart. Also, some of the condensate may have been picked up and
put back into the air flow.
P compressor =
(m x isentropic work ) / 0.80
The isentropic work was determined using the PH diagram, and is the difference in enthalpies
between states 1 and 2s, where 2s is a state with entropy equal to state 1 and equal pressures
between 2 and 3.
Actual compressor work was determined by multiplying mass flow rate by difference in
enthalpies between 1 and 2 for each case. Heat loss is the difference between compressor power
and compressor work.
The results for the COPR for each case are presented in table 6 in the appendix.
One way to improve the experimental design of this experiment, would be to use better
instruments. Many of the instruments used have low resolution and are hard to get a good
Discussion
enthalpy of vaporization, and good thermal conductivity, low boiling/freezing points, and low
specific heat. High enthalpy of vaporization allows for maximum heat absorbed in evaporation.
compressor. A refrigerant can be modeled as an ideal gas, and if the pressure is greater than
Our goal in this experiment was to analyze the P.A. Hilton Air Conditioning Laboratory
Unit. We were concerned mainly with the refrigerant cycle, psychrometrics of the air flow, mass
transfer rates, heat transfer, power, and coefficient of performance. We observed the air
conditioner in three different operating conditions, and data points were plotted on PH chart and
psychrometric chart for each case. Mass flow rates were also calculated for each operating
condition. We assumed a compressor efficiency of 80 % for this unit, and compressor power was
compared to compressor work in order to obtain heat loss, which ranged from 0.376kW to
0.386kW. The coefficient of performance was also computed for each case and ranged from
6.016 to 6.128. A typical COPR for AC cycles is around 4.0, which suggests that the P.A. Hilton
is among one of the higher performing units. Some of the calculations seemed to be far from
Pre-heater 0 2 kW 0
After-heater 0 0 1 kW
Boiler 0 0 3 kW
Case
Mass Flow Rate m [kg/s]
1 0.0383
2 0.0379
3 0.0376
Table 5: Compressor Power Inputs, compressor work, and compressor heat loss