100 Series (5-15kVA)

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

5 - 15 kVA

100 SERIES
UNINTERRUPTIBLE POWER SUPPLIES

Tescom 100 series are, True online,


1 phase in / 1 phase out

Double conversion UPS Systems,


manufactured with the state of the art,
PWM and IGBT technology, producing
microprocessor controlled pure
sinewave output to critical loads.

GENERAL SPECIFICATIONS
• Output isolation transformer • T-MON remote monitoring soſtware

• Up to 91% efficiency • Parallel operation

• Static by-pass • Manufactured according to EC Directive; EN62040

• LCD front panel • 10 years spare parts support

• 64 events memory • 2 years warranty

• RS232 and relay contacts

• Custom input and output voltage ranges

• SNMP compatible communication


5 - 15 kVA
TECHNICAL SPECIFICATIONS

MODELMODEL 105XA 107XA 110 115


Power (kVA) 5 7 10 15
INPUT
Voltage 220/230 VAC P + N + G ± 15%
By-pass voltage 220/230 VAC P + N ± 10%
Frequency 50Hz / 60Hz ± 5%
OUTPUT
Power (kW) 3,25 4,55 7 10,5
Power factor 0.65 0.7
Voltage 220/230 VAC P+ N ± 1%
Frequency 50Hz (60Hz on request)
Frequency tolerance Line synchronized: ± 2% , free running: ± 0,2%
Efficiency (at 100% load) up to 90% up to 91%
Crest factor 3:1
Overload protection 100%-125% load: 10 min., 125%-150% load: 1 min., > 150% load: by pass
Short circuit protection Electronic short circuit protection
VoltageTHD < 3%
BATTERIES
Type Sealed Lead Acid - Maintenance Free
Number of batteries 16 18 20
Float charging voltage 216 VDC 243 VDC 270 VDC
End of discharge voltage 160 VDC 180 VDC 200 VDC
Battery cabinet Internal External
Battery ambient temperature 25ºC
Battery protection Automatic circuit breaker
Battery test Optional
GENERAL
Standards EN 62040-1, EN 62040-2
Serial communication Dry contacts & RS232
Soſtware T-Mon UPS Management Soſtware (3 clients, +1 server management std.)
Temperature range 0ºC - 40ºC
Ventilation Forced air cooling
Relative humidity < 90% (non-condensing)
Protection degree IP20
Altitude < 2000m
Acoustic noise < 45 dBA
Weight without batteries (kg) 60 75 82 107
Dimensions (mm) HxWxD 595x265x600 645x265x670 720x265x740 775x300x800
OPSTIONS
Different input / output voltage Please ask
Input transformer Galvanic isolation transformer at the input (in external cabinet)
6kVA & 7kVA Previous, output PF:0.7 versions (4200W - 4900W) available on request
MBS Maintenance Bypass Switch for complete isolation
Adaptors SNMP, MODBUS, Remote Mon. Panel, RS485
Parallel operation N+1 (up to 4 units)

You might also like