Power Systems (Q-Bank-Ch3-Fault Analysis
Power Systems (Q-Bank-Ch3-Fault Analysis
Power Systems (Q-Bank-Ch3-Fault Analysis
1. The P.U reactance becomes ____________, if the capacity and voltages are doubled
3. In which of the following faults, all the sequence voltages are equal?
4. A short circuit fault on the alternator is given as IR1 = j8.5 p.u, IR2 = -j8.5 p.u & IR0 = 0, then
the fault is
5. The equivalent positive, negative and zero sequence reactance’s at fault point ‘F’ is
6. If a symmetrical fault occurs on a power system, the percentage reactance of the system
on 2500 base kVA is 25% if the full load current corresponding to base kVA is 20A. If the
base kVA is changed to 5000kVA, then the short circuit current becomes
(a) Doubles (b) Half of the original
(c) Remains same (d) None of these
7. A synchronous machine is directly connected to the load. The internal voltage of the
synchronous machine is 1.2 p.u, load voltage is 1.0 p.u and the synchronous reactance is 1.5
pu. The maximum real power transferred is __________________ p.u.
8. The per unit impedance of two synchronous machines is 0.242. If the base voltage is
increased by 1.1 times, then per unit impedance will be ___________.
(a) 27, 9
(b) 9, 27
(c) 27, 72
(d) 72, 27
10. Which of the following is true about the sequence reactance of transformer?
(a) Negative and positive sequence reactance’s are equal to the leakage reactance
(b) Negative sequence reactance is larger than positive sequence reactance
(c) Negative sequence reactance is smaller than positive sequence reactance
(d) None of the above.
11. A 3-phase transformer having zero-sequence impedance of Z0 has the zero sequence
network as shown in the figure. The connections of its windings are
(a) star-star
(b) delta-delta
(c) star-delta
(d) delta-star with neutral grounded
(1) Short circuit current is generally calculated as symmetrical sinusoidal A.C. component and
it is expressed in R.M.S value.
(2) The severity of offset current is double at zero cross over point
(a) 1 only (b) 2 only
(c) Both (d) None
13. In which transformer the per unit reactance is same in both sides (primary and
secondary) referred
14. The direct axis reactance Xd of a synchronous generator is given as 0.4 pu based on
generator’s name plate rating of 10kV, 75MVA, the base of calculation is 11kV, 100 MVA.
The pu value of Xd of new base is ____________.
15. For the system shown in the diagram given below, the line to ground fault on the line
side of the transformer is equivalent to
16. When a line to ground fault occurs, the current in a faulted phase is 100 A. The zero
sequence current in this case will ___________________ A.
17. In a power system severe over voltages are developed in a grounded fault when
18. The single diagram of a certain power network is shown below. At the same instant of
time the following faults are taking place at in given options. The maximum short circuit
current is calculated by consider the fault at
19. The single line diagram of power system is shown below. The zero sequence impedance
diagram will be
20. A 132 kV sub-station is having short circuit capacity of 4800 MVA in case of double line
fault at the bus. The negative sequence driving point reactance is
(a) 4.37 kA
(b) 46.65 kA
(c) 17.5 kA
(d) 29.15 kA
22. A 3-phase 3-wire overhead transmission having a self-reactance of j0.5 PU and mutual
reactance at j0.1 PU. The positive sequence voltage of phase a is 1.530o PU. The sequence
current of phase b of abc phase sequence is
23. The reactance of a generator designed ‘X’ is given as 0.25PU based on the generator’s
nameplate rating of 18kV, 500MVA. If the base for calculations is changed to 20kV, 100MVA.
The generator reactance ‘X’ on new base will be
(a) 1.025PU (b) 0.05PU
(c) 0.0405PU (d) 0.25PU
24. The positive, negative and zero sequence currents of a star connected load for phase R
are given as
IR1 = (10) A ; IR2 = (5 + j15) A ; IR0 = (5 j15) A
The neutral current will be
(a) Zero (b) (15 + j24)A
(c) (15 –j24) (d) (15 – j24)A
25. An alternator having positive, negative and zero sequence reactance 0.2, 0.2 and 0.1 p.u
respectively. The ratio between double line to three phase short circuit fault current will be
26. Three phase fault current at the terminals of alternator will be reduced by
(a) by maintaining large air gap length between rotor & stator
(b) by maintaining smaller air gap length between rotor & stator
(c) by connecting series capacitor between alternator & bus
(d) by placing shunt reactor bank at alternator terminals
27. An alternator of 100 MVA, 18 kV has subtransient and steady state reactances
x11
d
0.1 p.u., x1d 0.25 p.u. and x d 1.0 p.u.. What is maximum dc component in fault current
for 3- short circuit occurs at terminals.
28. A line to ground fault occurs on the terminals of an alternator, sequence voltages and
sequence currents during this fault are Va0 = 0.3 pu, Va2 = 0.4 pu, Va1 = 0.7 pu, Ia0 = Ia1 =Ia2
= j2.0 p.u. If zero sequence impedance is j0.05 p.u then what will be neutral to ground
impedance placed approximately
29. Four alternators are connected in parallel, each alternator of 11 kV, 10 MVA, 0.5 p.u
reactance. What is the current carried by CB if fault occurs at location ‘p’.
(d)–j8 p.u
(a) LG (b) LL
(c) LLG (d) LLL
31. A 30 MVA, 3 phase 11 kV, 50 Hz alternator having the neutral solidly grounded is
operating at no load. It has a positive sequence reactance of 2.5 ohms and the negative and
zero sequence reactance are 80% and 30% of the positive sequence value respectively then
the current through ground is ____________ kA for LLG fault.
32. 10kVA, 400V/200V single phase transformer with 10% reactance draws a steady state
current of _____________ A.
33. Two identical generators are connected by a transmission line as shown below. The
positive sequence reactance of the generator is 0.25 p.u. The zero sequence reactance is
0.08 p.u. The neutral grounding reactance is 0.05 p.u. The positive sequence reactance of
transmission line is 0.1 p.u. A single line to ground fault is taking place at bus 1. The voltage
of neutral w.r.t ground in p.u of generator one is _________.
(a) 0.14
(b) 0.16
(c) 0.89
(d) 0.24
34. The zero sequence circuit of the three phase transformer shown in figure is
35. A single phase load of 100 KVA connected across line bc of a 3-phase supply of 3.3 kV.
The negative sequence component of line current is
(a) j12.24 A (b) j17.5 A
(c) j16.4 A (d) j18.2 A
36. A 3-phase, 50 Hz generator is rated at 500 MVA, 20 KV with X′′d = 0.2j pu. It supplies
pure resistive load of 400 MW at 20 kV. The load is connected directly across the terminals of
the generator. If all the three phases of the load are short circuited simultaneously, then the
initial symmetrical rms current in the generator in per unit on a base of 500 MVA, 20 kV is
(a) 2.24 pu (b) 4.23 pu
(c) 3.43 pu (d) 5.06 pu
37. A 10 MVA, 13.8 kV alternator has positive, negative and zero sequence reactance’s of
30%, 40% and 5% respectively. The value of resistance that must be placed in the generator
neutral so that the fault current for a line to ground fault of zero fault impedance will not
exceed the rated line current is
(a) 16.12 (b) 18.43
(c) 17.16 (d) 20.24
38. When a fault occurs in a power system the following sequence currents are recorded.
IZero = –j1.246 pu ; IPositive = j 2.046 pu ; INegative = –j 0.8 pu. The fault is
(a) line to ground (b) line to line
(c) line to line to ground (d) three-phase
39. The estimated short circuit MVA at the bus bars of a generating station A is 1500 MVA
and of another station B is 1200 MVA. The generated voltage at each station is 33 KV. If
these stations are inter connected through a line having a reactance of 1 Ω and negligible
resistance, the possible short circuit MVA on station A is
40. A 11 kV, 10 MVA alternator has 10% sub-transient reactance, transient reactance and
80% synchronous reactance XS. It is connected to a load through a circuit breaker and a
transformer. If under no load conditions a 3-phase fault occurs between the transformer and
the circuit breaker, then the maximum d.c. component of the short circuit current is
41. The following figure shows a synchronous generator whose neutral is grounded through
a reactance Xn. The generator has balanced emfs and sequence reactances X1, X2 and X0.
The value of neutral grounding reactance for which the LG fault current is less than the three
phase fault current is
1
(a) Xn X X0
3 1
1
(b) Xn X1 X 0
3
1
(c) Xn X1 X 0
3
1
(d) Xn X1 2X 0
3
42. Consider the power system shown in figure. An SLG fault occurs at Bus-2 at the far end
of the line. Consider the numerical data:
Gen-G: 3-phase, 50 MVA, 33 kV
X1 = X2 = 0.2 p.u; X0 = 0.1 p.u.
33 kV line: X1 = X2 = 10 ohms; Xo = 20 ohms
Determine the fault current magnitude, if the generator neutral is solidly grounded and fault
impedance is 0.1 p.u. on 50MVA, 33 kV.
(a) 812.1 A
(b) 843.16 A
(c) 921.61 A
(d) 994.83 A
43. The below given figure is a single line diagram of a 3-phase power system. Data for this
system is as follows:
G and M are generator and synchronous motor respectively, both rated 2500 kVA, 600 volts
with X” = X2 = 10% and X0 = 5%.
T1 and T2 are transformers each rated 2500 kVA, 600 V delta and 4160 V star, with leakage
reactance of 6%.
The transmission line reactance are X1 = X2 = 15% and X0 = 50% on a base of 2500 kVA,
4.16kV.
A double-line to ground fault occurs on line ‘b’ and ‘c’ at point P in the system. Assuming
that synchronous motor is operating at rated voltage and neglecting pre-fault current. The
zero sequence current after the fault is _____________.
44. In the circuit shown one conductor of a three-phase line is open. The current flowing to
the connected load through line ‘a’ is 10 A. With the current in line ‘a’ as reference and
assuming that line ‘C’ is open. The negative sequence current component in line ‘a’ will be:
(a) 5.7730o
(b) 4.7145o
(c) 4.9225o
(d) 7.2112o
Solutions
1. Ans: (d)
MVA
Solution: XP.U X
KV
2
2MVA XP.U
X 'P.U X
4 KV 2
2
2. Ans: (a)
Solution: Due to resistance and reactance in the line the power factor of fault current is
lagging. If resistance of line is neglected then power factor is zero power factor lagging.
3. Ans: (b)
Solution: For LLG fault all positive, negative, zero sequence voltages are equal.
4. Ans: (d)
Solution: In LL fault IR1 = IR2 : IR0 = 0
5. Ans: (a)
Solution: For positive and negative sequence reactance
0.2
x1 x2 0.067
3
6. Ans: (c)
Solution: The short circuit current is independent of base kVA, therefore the short circuit
current remains the same.
7. Ans: 0.8
EV 1.0 1.2
Solution: The maximum real power transfer 0.8 p.u.
XS 1.5
8. Ans: 0.20
Kv
2 2
1 1
Solution: Z p.u.. New Z p.u.. Old 0.242 0.200
Kv 1.1
2
2
9. Ans: (a)
Solution: x0 xs 2xm .................. (i)
x1 xs xm .................. (ii)
Solving (i) & (ii), we have xs 27 and xm 9
16. Ans: 33 to 34
I
Solution: Iao f 33.33 A
3
kV
2
BaseMVA BaseMVA
SCMVA=
BaseMVA BaseMVA X1 X 2
X1 X 2 X1 X2 BaseMVA
kV kV kV
2 2 2
132
2
X1 X 2 3.63
4800
2X1 3.63 X1 X 2
3.63
X1 1.815
2
0.15
IF(G) (p.u.) 10.667 4.0 p.u.
0.25 0.15
100M
IF(G) 4 17.54 KA
3 13.2K
j0.5
ICB j8 j6 p.u
j0.5
j0.5
3
X 2 0.8X1 2
For LLG fault,
11K
Ea1 3
Ia1 2085.35A
X1 X 2 || X 0 2.5 0.545
IR1 X 2 2085.35 2
Ia0 A
X2 X0 2 0.75
Ia0 1.516 kA
In If 3IaO 4.549 kA
X0eq
0.08 3 0.05 0.08 3 0.05 3 0.1 0.16 p.u.
0.08 3 0.05 0.08 3 0.05 3 0.1
( zero seq of line =3 times positive sequence of line )
1.0
If IR0 2.2 p.u
0.145 0.145 0.16
0.53
IR0(G ) 2.2 1.6 p.u
1
0.53 0.23
Vn 3 IR0G1 Xn 3 1.6 0.05 0.24 p.u
2.904
Rn 0.968 pu 0.968 19.044
3
R n 18.43
When a fault occurs on power station A (point F1), the total percentage reactance from
generator neutral upto fault point F1, is the parallel combination of (8.33 % + 9.18 %) and
6.67 %
17.51 6.67
i.e. Total % reactance upto fault point F1, 4.83%
17.51 6.67
100 100
Short circuit MVA = Base MVA 100 2070
% Reactance 4.83
X"d 1.21
10MVA
11000
I"d 5248.63A
3 1.21
E
Id.c(max) 2 " 2 5249 7.4 kA
Xd
Base voltage = 33 KV
332
Base impedance = 21.78
50
50 103
Base current 874.79 A
3 33
Line sequence reactance in p.u.
10
X1 X 2 j0.46 p.u.
21.78
20
X0 j0.918 p.u.
21.78
X1.total X 2.total 0.2 0.46 0.66 p.u.
X 0.total j1.018 p.u.
Total sequence reactance upto the fault location:
3Eph 31
If.SLG 1.1372 p.u. 994.83 A
X1.total X 2.total X 0.total 3X f 0.66 0.66 1.018 3 0.1
0.16 0.31
Z1 Z 2 j j0.106
0.16 0.31
0.56 0.06
Z0 j j0.054
0.56 0.06
Z0 Z2 0.106 0.054
So that j0.036
Z0 Z2 0.160
Referring to Fig.(d)
Ea 1 1
Ia1 j7.05 p.u.
Z0 Z2 j 0.106 0.036 j0.142
Z1
Z0 Z2
Z 2 j0.106
Ia0
Z0 Z2
Ia1
j0.160
j7.05 j4.67 p.u.
2. Ans: (c)
Solution: In absence of ground connection at generator no current can flow into the ground
at the fault. The current in LL & LLG fault will be same in this case.
3. Ans: (b)
Solution: Maximum possible sub-transient current
Ic Ia0 Ia1 2 Ia2
Ic j2.5 11200 j5.75 12400 j3.25 8.64925.69 0 A
4. Ans: (c)
400M
Solution: Xp.u. LV 0.121 0.1 p.u.
22K
2
5. Ans: (b)
6. Ans: (c)
Solution: Equivalent reactance seen from the fault point
XPU
j0.1 j0.2 j0.08 j0.1 j0.08 j0.12214
j0.1 j0.2 j0.08 j0.08 j0.1
1 1
Fault level current = j8.187
X(PU) j0.12214
7. Ans: (d)
ER1
Solution: sub transient current for symmetrical fault If IR
X1
1.0 1.0
X1 0.2
If 5
X 2 X1 0.2
X 0 0.2 0.2 0.04
For L-G fault
ER1 1.0 10
IR1 2.27
X1 X 2 X 0 3Xn 0.2 0.2 0.04 0 0.44
8. Ans: (c)
ER1 1.0
Solution: For 3 phase fault IF IR IR1 => X1p.u 0.2 p.u.
X1p.u 5
X 2p.u 0.2 p.u.
9. Ans: (c)
Solution: Base MVA 150
150
X G New 0.2 0.3
100
Equivalent Reactance = 0.3 0.1 0.15 0.55pu
150
SC MVA = 272.72MVA
0.55
1
If 7.452( 75)p.u.
.02484 .049585 j .01 .08 j
If 7.452 6 44.72
Solution: The earth fault is assumed to occur on the red phase. Taking red phase as the
reference, its phase e.m.f.
11 1000
ER 6351 V
3
%X Base KV
2
Z=
Base MVA 100
10 11
2
X1 0.605
20 100
5 11
2
X2 0.3025
20 100
30 11
2
X0 1.815
20 100
3ER 3 6351
If
X1 X2 X0 j0.605 j0.3025 j1.815
I f j6998 A
If 6998 A
So that X=
5 11000 / 3 0.605
100 524.86
Let X' be the (external) reactance per phase to be
connected in series with the alternator.
ISC 8 I 8 524.86 4200 A
E
ISC X ' 0.90
0.605 X '
Base MVA
SCMVA
X p.u.
1
X system 0.125 pu
8
400
Operating voltage at motor bus before fault 0.909 pu
440
Short circuit current fed to fault at motor bus,
1 0.909
Isc 2 20.8
0.125 0.258 0.1
1M
Base current, I base
1.312kA
3 440
Short circuit current,
ISC 20.8 1.312 27.29 kA
15. Ans: 16 to 17
Solution: For a base of 25,000 KVA, 13.8 kV in the generator circuit, the base for the motor is
5000 KVA, 6.9 kV. The subtransient reactance of each motor is
25000
X"d 0.2 1 p.u.
5000
The voltage at the motors is 6.9 kV when a 3- fault occur at point ‘P’
j
Z Th j0.15 j0.10 || j0.125 p.u.
4
1.0
I"f j8 p.u.
j0.125
25000
The base current in the 6.9 kV circuit is 2091.85 A
3 6.9
I"f 8 2091.85 16.735 kA