Test Report: Digital Grid Smart Infrastructure Division

Download as pdf or txt
Download as pdf or txt
You are on page 1of 12

Digital Grid

Smart Infrastructure Division


Report no. 518/TTS/1/1 Page 1/12

Test Report
Report no.: 518/TTS/1/1

Subject: Type Test Summary


Date: 2019-11-11

Place: SIEMENS, SI DG SPD R&D


Hamilton Laboratory
Hebburn

Client: Siemens AG,


Humboldtstr. 59
D-90459 Nuremberg, Germany

Object: REYROLLE 5 Protection Relays

Type: REYROLLE 5 Devices

Manufacturer: SIEMENS AG
EM DG PRO MF GOA

Test Program
Details the results of the environmental and functional type tests for the Reyrolle 5 Overcurrent protection
relays, and the Reyrolle 5 Transformer protection relays, which have IEC 61850 communication capability.

The relays used in the hardware and functional tests were selected from the range of hardware variations
available to the Reyrolle 5 series and the functional tests applied to prove the Reyrolle 5 with IEC 61850
communication capability.

All tests were carried out within testing facilities within Siemens and demonstrate that the relays performed
within the claims of the Performance Specification and in compliance with the relevant Standards.

Summary and Test Result


The tests were passed successfully and the specified requirements were met.
Digitally signed by Coyle Shaunna
DN: serialNumber=Z0035X8C,
givenName=Shaunna, sn=Coyle,
o=Siemens, cn=Coyle Shaunna
Date: 2019.11.11 12:46:24 Z
Prepared by: Miss Shaunna Coyle __________________ _____________________
Test Engineer Signature Date
Siemens SI DG SPD R&D 4 Digitally signed by
Maxwell Andrew
Date: 2019.11.11
Reviewed by: Mr. Andrew Maxwell __________________12:59:08 Z _____________________
Engineer Signature Date
Siemens SI DG SPD R&D 4 Digitally signed by
Kell Graeme
Date: 2019.11.11
Approved by: Mr. Graeme Kell 13:15:20 Z
__________________ _____________________
T&C Manager Signature Date
Siemens SI DG SPD R&D 4

This report consists of 12 pages

Restricted Smart Infrastructure Division


SI DG, SA&P
Template:Type_Test_Summary Version :V1.00
Copyright: 2019 Publication or reproduction of the contents of this report in any other form than a complete copy to the letter is not allowed without our written consent.
Digital Grid
Smart Infrastructure Division
Report no. 518/TTS/1/1 REYROLLE 5
Page 2/12
Type Test Summary

Report Index:
Item Description
1 First Issue

Table of Contents
1 Introduction .............................................................................................................................................. 3
2 Software / Firmware References ............................................................................................................. 3
3 MLFB Structure – Reyrolle 511 (Overcurrent) ....................................................................................... 4
4 MLFB Structure – Reyrolle 54 (Transformer) ........................................................................................ 5
5 Environmental Tests ................................................................................................................................ 6
6 Functional Tests ....................................................................................................................................... 8

Restricted Smart Infrastructure Division


SI DG, SA&P
Template:Type_Test_Summary Version :V1.00
Copyright: 2019 Publication or reproduction of the contents of this report in any other form than a complete copy to the letter is not allowed without our written consent.
Digital Grid
Smart Infrastructure Division
Report no. 518/TTS/1/1 REYROLLE 5
Page 3/12
Type Test Summary

1 Introduction
This report identifies the environmental type tests that were applied to relays representing the range of
hardware builds on the Reyrolle 5 platform with IEC 61850 communication capability and the functional type
tests that were applied to the Reyrolle 5 Overcurrent relays and Transformer relays.

The relay operational and functional claims made in the Technical Documentation are mainly based on IEC
Product Standards. Where Product Standards are not available, reference may be made to either the IEC
Generic Standards or other current Standards such as EATS.

The Technical Documentation for the Devices consists of the following set of documents:
1. Introduction
2. Basic Structure of the Device Functionality
3. Device Functionality
4. Application Function Templates
5. Protection and Automation Functions
6. Supervision Functions
7. Control Functions
8. Instruments and Meters
9. Functional Tests
10. Technical Data

The Technical Documentation for the Hardware consists of the following documents:
1. Introduction
2. Devices and Front Fascia Panels
3. Electronic Modules
4. Working with the Device
5. Technical Data
6. Ordering Information

The requirements of the quoted standards are generally similar to those of other standards authorities
throughout the world and form a basis for demonstrating relay compliance with the claims of the Performance
Specification.

Also included in this report are the production software references and the product reference codes which are
termed the MLFB structure.

2 Software / Firmware References


The production software references are applicable for versions up to and including:

REYROLLE 5 Non-Directional Overcurrent 7SR5110 v02.00


REYROLLE 5 Directional Overcurrent 7SR5111 v02.00
REYROLLE 5 Two Winding Transformer 7SR542 v02.00
REYROLLE 5 Three Winding Transformer 7SR543 v02.00

Restricted Smart Infrastructure Division


SI DG, SA&P
Template:Type_Test_Summary Version :V1.00
Copyright: 2019 Publication or reproduction of the contents of this report in any other form than a complete copy to the letter is not allowed without our written consent.
Digital Grid
Smart Infrastructure Division
Report no. 518/TTS/1/1 REYROLLE 5
Page 4/12
Type Test Summary

3 MLFB Structure – Reyrolle 511 (Overcurrent)


REYROLLE
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
ORDER-No.: n a a n n n n - n a a n n - n a a n -

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
ORDER-No.: 7 S R 5 1 1 n - n A A n n - 0 A A 0 -
| | | |
Overcurrent: I/O Configurations 7 8 | |
4CT, 8BI, 6BO 0 - 1 | 1
4CT, 13BI, 8BO 0 - 2 | 1
4CT, 38BI, 18BO 0 - 7 | 6
| | | |
Directional Overcurrent: I/O Configurations 7 8 | |
4CT, 4VT, 9BI, 8BO 1 - 1 | 1
4CT, 4VT, 14BI, 10BO 1 - 2 | 6
4CT, 4VT, 39BI, 20BO 1 - 7 | 6
| |
CPU/ Data Comms 11 |
Standard: 1 x USB (front) , RS485 (rear) ports, plus:- |
2 x RJ45 ports 1 |
2 x Optical LC ports 2 |
|
Case & Fascia 12
Size 6 case 1
Size 12 case 6

Export Data CT inputs: 1 A / 5 A, 50 Hz / 60 Hz


HS: 8536900 VT inputs: 40 V to 160 V, 50 Hz / 60 Hz
ECCN: EAR99 PSU: DC 24 V to DC 250 V, AC 100 V to AC 230 V
AL: N BI: DC 24 V / DC 110 V / DC 220 V
IEC 61850 ethernet, Modbus RTU, IEC 60870-5-103, DNP 3.0

Issue 15/07/19

Restricted Smart Infrastructure Division


SI DG, SA&P
Template:Type_Test_Summary Version :V1.00
Copyright: 2019 Publication or reproduction of the contents of this report in any other form than a complete copy to the letter is not allowed without our written consent.
Digital Grid
Smart Infrastructure Division
Report no. 518/TTS/1/1 REYROLLE 5
Page 5/12
Type Test Summary

4 MLFB Structure – Reyrolle 54 (Transformer)


REYROLLE
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
ORDER-No.: n a a n n n n - n a a n n - n a a n -

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
ORDER-No.: 7 S R 5 4 n n - n A A n 6 - 0 A A 0 -
| | | |
2 Wdg. Transformer: I/O Configurations 6 7 8 |
8CT, 16BI, 8BO 2 0 - 2 |
8CT, 4VT, 12BI, 8BO 2 1 - 1 |
8CT, 4VT, 37BI, 18BO 2 1 - 6 |
| | | |
3 Wdg. Transformer: I/O Configurations 6 7 8 |
12CT, 24BI, 10BO 3 0 - 3 |
12CT, 4VT, 35BI, 16BO 3 1 - 5 |
|
CPU/ Data Comms 11
Standard: 1 x USB (front) , RS485 (rear) ports, plus:-
2 x RJ45 ports 1
2 x Optical LC ports 2

Case & Fascia 12


Size 12 Case 6

Export Data CT inputs: 1 A / 5 A, 50 Hz / 60 Hz


HS: 8536900 VT inputs: 40 V to 160 V, 50 Hz / 60 Hz
ECCN: EAR99 PSU: DC 24 V to DC 250 V, AC 100 V to AC 230 V
AL: N BI: DC 24 V / DC 110 V / DC 220 V
IEC 61850 ethernet, Modbus RTU, IEC 60870-5-103, DNP 3.0

Issue 15/07/19

Restricted Smart Infrastructure Division


SI DG, SA&P
Template:Type_Test_Summary Version :V1.00
Copyright: 2019 Publication or reproduction of the contents of this report in any other form than a complete copy to the letter is not allowed without our written consent.
Digital Grid
Smart Infrastructure Division
Report no. 518/TTS/1/1 REYROLLE 5
Page 6/12
Type Test Summary

5 Environmental Tests
Test
Standard Test Description Severity
Result
IEC 60255-27
Operate : 96hrs @ -10°C.
IEC 60255-1 Temperature cold heat Pass
Storeage : 96hrs @ -25°C.
IEC 60068-2-1
IEC 60255-27
Operate : 96hrs @ +55°C.
IEC 60255-1 Temperature dry heat Pass
Storeage : 96hrs @ +70°C.
IEC 60068-2-2
IEC 60255-1 +20°C(ambient), -25°C, +70°C,
Cyclic temperature Pass
IEC 60068-2-14 -25°C, +70°C, +20°C(ambient).
IEC 60255-27
Relative humidity -
IEC 60255-1 56 days @ +40°C 93% r.h. Pass
steady state
IEC 60068-2-78
IEC 60255-27
+25°C 97%rh, +40°C 93%rh,
IEC 60255-1 Relative humidity - cyclic Pass
6 cycles of 24hr duration.
IEC 60068-2-30
IP54 – Front Panel
IEC 60255-27
Enclosure IP4X – Rear Metal Box Pass
BS EN 60529
IP2X – Rear Wiring Terminal Access
IEC 60255-27 Vibration tests
Class 1, 0.5gn operational, 1gn endurance. Pass
IEC 60255-21-1 (sinusoidal)

IEC 60255-27
Shock and bump tests Class 1, 5gn operational, 10gn and 15gn withstand. Pass
IEC 60255-21-2

IEC 60255-27
Seismic tests Class 1, 1gn horizontal and 0.5gn vertical. Pass
IEC 60255-21-3
Aux supply - Reverse
IEC 60255-27 Single wide voltage range PSU. Pass
polarity and slow ramp
Aux supply - A.C. and
IEC 60255-26 Single wide voltage range PSU, 50ms withstand at
d.c. Voltage Pass
IEC 61000-4-11 minimum voltage.
interruptions
IEC 60255-26 Aux supply - A.C. and Single wide voltage range PSU, 50ms withstand at
Pass
IEC 61000-4-29 d.c. Voltage dips minimum voltage.
IEC 60255-26 A.C. component in d.c.
Single wide voltage range PSU, 15%. Pass
IEC 61000-4-17 (ripple)
Gradual shutdown/start-
IEC 60255-26 up (for d.c. power Single wide voltage range PSU. Pass
supply)
IEC 60255-27 Aux supply - Burden Single wide voltage range PSU. Pass
IEC 60255-1 Aux supply - Inrush Single wide voltage range PSU. Pass
DC supply voltage - high ES 1 & 2, Binary inputs pick-up, drop-off, operate time,
EATS 48-4 burden trip relays - switched non-operate current, capacitive discharge, Pass
capacitive discharge. thermal withstand.
IEC 60255-27 Thermal requirements - 4xIn continuous, transducer burden, relay dc burden,
Pass
EATS 48-5 CT inputs. transducer thermal withstand.
IEC 60255-27 Thermal requirements - 300V continuous, transducer burden, relay dc burden,
Pass
EATS 48-5 VT inputs. transducer thermal withstand.

2.5KVrms, 50Hz, 1min common mode, 1KVrms,


IEC 60255-27 Insulation - dielectric. Pass
contacts.
Insulation - impulse
IEC 60255-27 5KVpk, 1.2/50µs. Pass
voltage.
Restricted Smart Infrastructure Division
SI DG, SA&P
Template:Type_Test_Summary Version :V1.00
Copyright: 2019 Publication or reproduction of the contents of this report in any other form than a complete copy to the letter is not allowed without our written consent.
Digital Grid
Smart Infrastructure Division
Report no. 518/TTS/1/1 REYROLLE 5
Page 7/12
Type Test Summary

Test
Standard Test Description Severity
Result
Insulation - dc
IEC 60255-27 >100MΩ @ 500Vdc. Pass
resistance.
IEC 60255-26 1MHz - Slow Damped 2.5kVpk common mode & 1kVpk differential mode,
1MHz exponentially decaying. Pass
IEC 61000-4-18 Oscillatory
IEC 60255-26
Electro Static Discharge Class 4 ±15KV air discharge. Pass
IEC 61000-4-2
Radiated e/m field 10V/m, 80% modulated.
IEC 61000-4-3 disturbance (RFI), Sweeps 80MHz - 1000MHz, 1400MHz - 2700MHz Pass
inc. Radio telephones. Spot 80, 160, 380, 450, 900, 1850, 2150 MHz.
Fast transient/burst
IEC 60255-26
immunity (Electrical Zone A, 4kV, 5kHz, General, 2kV, 5kHz, Comms. Pass
IEC 61000-4-4
Withstand Tests).
Analog Inputs Line to Earth – 4kV.
Case, Aux Power & I/O Line to Earth – 4kV.
IEC 60255-26 RS485 Comms port Line to Earth – 4kV.
Surge Immunity Pass
IEC 61000-4-5 RJ45 Ethernet port Line to Earth – 4kV.
Analog Inputs Line to Line – 2kV.
Case, Aux Power & I/O Line to Line – 2kV.
10Vrms 80% modulated.
IEC 60255-26 Conducted RFI Sweep 0.15MHz - 80MHz. Pass
IEC 61000-4-6 Immunity. Spot 27, 68 MHz.
IEC 60255-26 Power frequency
Level 5, 100A/m Continuous, 1000A/m Pulsed. Pass
IEC 61000-4-8 magnetic field immunity.
Power frequency Zone A, Binary outputs at 300V common and 150V
IEC 60255-26 Pass
interface - general. differential modes.
IEC 60255-26 0.15 - 0.5 MHz 79 µVdB or 66µVdB Ave.,
Conducted Emissions Pass
CISPR 22 0.50 - 30 MHz 73 µVdB Quasipeak or 60µVdB Ave.
30 – 230MHz 50 µVdB Quasipeak @ 3m
230 – 1000MHz 57 µVdB Quasipeak @ 3m
IEC 60255-26
1 – 3GHz 56 µVdB Average @ 3m
CISPR 11 Radiated Emissions Pass
76 µVdB Quasipeak @ 3m
CISPR 22
3 – 6GHz 60 µVdB Average @ 3m
80 µVdB Quasipeak @ 3m
Mechanical Endurance
Loaded Contact ≥10000 cycles
Making ≥1000 cycles
Breaking ≥1000 cycles
IEC 60255-27
Contact performance Limited Making Capacity ≥1000W @ L/R = 40ms Pass
IEC 60255-1
Contact Current
Continuous ≥5A
Short Term ≥30A, 200ms
Limited Breaking Capacity ≥30W @ L/R = 40ms

Restricted Smart Infrastructure Division


SI DG, SA&P
Template:Type_Test_Summary Version :V1.00
Copyright: 2019 Publication or reproduction of the contents of this report in any other form than a complete copy to the letter is not allowed without our written consent.
Digital Grid
Smart Infrastructure Division
Report no. 518/TTS/1/1 REYROLLE 5
Page 8/12
Type Test Summary

6 Functional Tests

2-Winding Transformer

3-Winding Transformer
Directional OC
Overcurrent

Test Result
IEC
Description
Function

Load Blinder
21LB Used to block tripping during sustained heavy load periods in X X Pass
distribution networks
Over Fluxing (DTL)
The flux in the transformer core is directly proportional to the
applied voltage and inversely proportional to the frequency. An
increase in transformer terminal voltage or a decrease in frequency
24DT X X Pass
will result in an increase in the flux. Over-excitation results in excess
flux, which causes transformer heating and increases exciting
current, noise and vibration.
DTL elements.
Over Fluxing (IDMTL)
The flux in the transformer core is directly proportional to the
applied voltage and inversely proportional to the frequency. An
increase in transformer terminal voltage or a decrease in frequency
24IT X X Pass
will result in an increase in the flux. Over-excitation results in excess
flux, which causes transformer heating and increases exciting
current, noise and vibration.
IDMTL elements
Under Voltage
Used to indicate that voltage has decreased to below an acceptable
27 level or ceased to flow, or a low voltage situation exists. For this X X X Pass
reason simple Definite Time Lag (DTL) elements may be used.
Identical DTL elements.
Vx Under Voltage
27Vx X X X Pass
DTL element, configured as an Under Voltage function
Directional Power Voltage Protection: Power
32 32 Power is derived from three phase voltages and currents and is X Pass
generally applied as a reverse element to detect that the motor has
stopped acting as a generator.
Undercurrent
37 Used to indicate that current has ceased to flow or that a low load X X X X Pass
situation exists. For this reason simple Definite Time Lag (DTL)
elements may be used.
Undercurrent – Measured E/F
37G Used to indicate that current has ceased to flow or that a low load X X X X Pass
situation exists. For this reason simple Definite Time Lag (DTL)
elements may be used.
Broken Conductor / Open Circuit
46BC X X X X Pass
Allows the detection of a broken conductor.
Instantaneous Negative Phase Sequence Overcurrent
46DT Measures the quantity of unbalanced current in the three phase X X X X Pass
system.
Time Delayed Negative Phase Sequence Overcurrent
46IT Measures the quantity of unbalanced current in the three phase X X X X Pass
system.
Restricted Smart Infrastructure Division
SI DG, SA&P
Template:Type_Test_Summary Version :V1.00
Copyright: 2019 Publication or reproduction of the contents of this report in any other form than a complete copy to the letter is not allowed without our written consent.
Digital Grid
Smart Infrastructure Division
Report no. 518/TTS/1/1 REYROLLE 5
Page 9/12
Type Test Summary

2-Winding Transformer

3-Winding Transformer
Directional OC
Overcurrent

Test Result
IEC
Description
Function

Negative Phase Sequence Voltage


47 Allows the detection of unbalance between phases by negative X X X Pass
phase sequence voltage.
Thermal Overload
49 X X X X Pass
Provides the thermal overload protection for static plant.
Instantaneous Phase Fault Overcurrent
50 Allows individually settable instantaneous phase fault overcurrent X X X X Pass
elements with individually mapped binary outputs.
Arc Flash Detection (Includes 50GAFD)
50AFD Optical detection of arcing faults results in fast clearance of the X X Pass
fault.
CB Fail
50BF X X X X Pass
Allows the detection of a CB failure.
Instantaneous Measured Earth Fault Overcurrent
50G Allows individually settable instantaneous measured earth fault X X X X Pass
overcurrent elements with individually mapped binary outputs.
Instantaneous Sensitive Earth Fault Overcurrent
50GS Allows the use of individually settable instantaneous sensitive earth X X Pass
fault overcurrent elements with individually mapped binary outputs.
Instantaneous Calculated Earth Fault Overcurrent
50N The 50N function has the facility to allow the use of individually X X X X Pass
settable instantaneous derived earth fault overcurrent elements,
with individually mappable binary outputs.
Switch Onto Fault
50SOTF If a fault appears on the line during the Close Pulse. This prevents a X X Pass
CB being repeatedly closed onto a faulted line.
Switch Onto Fault
50GSOTF If a fault appears on the line during the Close Pulse. This prevents a X X Pass
CB being repeatedly closed onto a faulted line.
Time Delayed Phase Fault Overcurrent
51 Allows the use of individually settable time delayed phase fault X X X X Pass
overcurrent elements with individually mapped binary outputs.
Cold Load Pickup
Allows a group of settings to be dedicated to be Cold Load settings.
These Cold Load settings are active during energisation of the
protected section of the power system and generally have more
robust settings than the nominal settings to allow higher currents to
51CL flow during line charging. After stabilisation of the power system the X X X X Pass
relay settings are transferred to the nominal settings. The relay
monitors the protected section of the power system, detects the
opening of the associated circuit breaker and transfers the active
setting to the Cold Load settings, in preparation for closing of the
circuit breaker.

Restricted Smart Infrastructure Division


SI DG, SA&P
Template:Type_Test_Summary Version :V1.00
Copyright: 2019 Publication or reproduction of the contents of this report in any other form than a complete copy to the letter is not allowed without our written consent.
Digital Grid
Smart Infrastructure Division
Report no. 518/TTS/1/1 REYROLLE 5
Page 10/12
Type Test Summary

2-Winding Transformer

3-Winding Transformer
Directional OC
Overcurrent

Test Result
IEC
Description
Function

Time Delayed Measured Earth Fault Overcurrent


51G Allows the use of individually settable time delayed measured earth X X X X Pass
fault overcurrent elements with individually mapped binary outputs.
Sensitive Earth Fault
51GS Allows the use of individually settable instantaneous sensitive earth X X Pass
fault overcurrent elements with individually mapped binary outputs.
Time Delayed Calculated Earth Fault Overcurrent

51N The 51N function has the facility to allow the use of individually X X X X Pass
settable time delayed derived earth fault overcurrent elements, with
individually mappable binary outputs.
Voltage Dependant Overcurrent
Used to increase the sensitivity of the Phase Fault current
51V characteristic. This is achieved by reducing the pick up level of the X X Pass
over current protection when the system voltage drops below a
settable level. The increase in current sensitivity is a pre-selected
menu option.
Power Factor
55 Low / High Power Factor Protection. Can be blocked if all phase X Pass
voltages fall below setting.
Over Voltage
59 Used to indicate that voltage has increased to above an acceptable X X X Pass
level. For this reason simple Definite Time Lag (DTL) elements may
be used.
Neutral Voltage Displacement (DTL)
59NDT DTL Over-voltage element X X X Pass
Vx = directly measured from Auxiliary VT
Vn = calculated from Phase VTs
Neutral Voltage Displacement (IDMTL)
59NIT Over-voltage element configurable as DTL or IDMTL X X X Pass
Vx = directly measured from Auxiliary VT
Vn = calculated from Phase VTs
Vx Over Voltage
59Vx X X X Pass
DTL element, configured as an Over Voltage function
CT Supervision (current only)
60CTS-I Allows the detection of a CT failure when only current monitoring is X X X X Pass
available.
CT Supervision (voltage reference)
60CTS-V Allows the detection of a CT failure when current and voltage X Pass
monitoring are available.
VT Supervision
60VTS X X X Pass
Allows the detection of a 1, 2 or 3 phase VT failures.
Directional Instantaneous Phase Fault Overcurrent
67 The directional element produces forward and reverse outputs X Pass
which can then be used as controls to each phase fault
instantaneous over-current elements.
Restricted Smart Infrastructure Division
SI DG, SA&P
Template:Type_Test_Summary Version :V1.00
Copyright: 2019 Publication or reproduction of the contents of this report in any other form than a complete copy to the letter is not allowed without our written consent.
Digital Grid
Smart Infrastructure Division
Report no. 518/TTS/1/1 REYROLLE 5
Page 11/12
Type Test Summary

2-Winding Transformer

3-Winding Transformer
Directional OC
Overcurrent

Test Result
IEC
Description
Function

Directional Instantaneous Measured Earth Fault


67G The directional element produces forward and reverse outputs X Pass
which can then be used as controls to each measured earth fault
instantaneous over-current elements.
Directional Instantaneous Sensitive Earth Fault
67GS The directional element produces forward and reverse outputs X Pass
which can then be used as controls to each sensitive earth fault
instantaneous over-current elements.
Directional Instantaneous Calculated Earth Fault
67N The directional element produces forward and reverse outputs X Pass
which can then be used as controls to each derived earth fault
instantaneous over-current elements.
Close Circuit Supervision
74CCS Provides circuit supervision elements and monitors the close circuit X X X X Pass
wiring.
Trip Circuit Supervision
74TCS Provides circuit supervision elements and monitors the trip circuit X X X X Pass
wiring.
Vector Shift
78VS Detects a vector shift in all three phase system voltages over a half- X Pass
cycle window. The function is used to detect islanding or loss of
connection between a generator and the main utility supply.
Autoreclose
79 X X Pass
Multishot Delayed Autoreclose with configurable sequences.
Under / Over Frequency
81 Identical DTL elements, each configurable as Under or Over X X X Pass
Frequency function. Inhibited by low voltage detection.
2nd harmonic / Inrush Detector
81HB2 Used to block the operation of selected elements during transformer X X X X Pass
magnetising inrush conditions.
5th harmonic / Inrush Detector
81HB5 Used to block the operation of selected elements during transformer X X Pass
magnetising inrush conditions.
Rate Of Change Of Frequency
The ROCOF measurements are done on all three phases
81R simultaneously and the final tripping decision is determined from the X Pass
phase voltage with highest magnitude. The adjustment will be done
in Hz per second [Hz/s].
DTL elements with an Inhibit input and a Trip output.
High Impedance REF
The single phase current input is derived from the residual output of
87GH line/neutral CTs connected in parallel. An external stabilising X X X X Pass
resistor must be connected in series with this input to ensure that
this element provides a high impedance path.
Biased Differential
87T-BD X X Pass
Transformer differential element
Restricted Smart Infrastructure Division
SI DG, SA&P
Template:Type_Test_Summary Version :V1.00
Copyright: 2019 Publication or reproduction of the contents of this report in any other form than a complete copy to the letter is not allowed without our written consent.
Digital Grid
Smart Infrastructure Division
Report no. 518/TTS/1/1 REYROLLE 5
Page 12/12
Type Test Summary

2-Winding Transformer

3-Winding Transformer
Directional OC
Overcurrent

Test Result
IEC
Description
Function

Differential Highset
87T-HS X X Pass
Transformer highest element
Circuit Breaker Control
Control
X X X X Pass
& Logic Configurable settings for the Circuit Breakers.
CT/VT Config (52)
- X X X X Pass
Phase rotation and Phase Connections allocation.
Demand Metering
- X X X X Pass
Statistical analysis of metering over a given time period.
CB Counters (52)
- Displays the number of trips and opens issued by the device. X X X X Pass
Contains CB Total Trip Counter and CB Delta Trip counter
- CB Position Monitoring (52) X X X X Pass
The position of CB can be monitored.
- Measurands - Instruments and Meters X X X X Pass
Metering values produced by the relay.
DNP3
- X X X X Pass
Functional check of elements.
Modbus
- X X X X Pass
Functional check of elements.
IEC60870-5-103
- X X X X Pass
Functional check of elements.
IEC61850
- X X X X Pass
Functional check of elements.

Restricted Smart Infrastructure Division


SI DG, SA&P
Template:Type_Test_Summary Version :V1.00
Copyright: 2019 Publication or reproduction of the contents of this report in any other form than a complete copy to the letter is not allowed without our written consent.