Copeland Digital Compressor Controller en Us 160802

Download as pdf or txt
Download as pdf or txt
You are on page 1of 12

AE8-1328 R5

AE8-1328 R5 March 2011

Copeland® Digital Compressor Controller

Introduction • For systems that need an accurate suction


The Digital Compressor Controller is the electronics pressure reading, the Digital Compressor
interface between the Copeland Scroll Digital ™ Controller is able to smooth out the pressure
compressor or the Copeland Discus Digital™ compressor swings associated with loading and unloading
and the system controller. The Digital Compressor the compressor. A pressure transducer input is
Controller is designed only for single phase Copeland “filtered” by using the unloader control algorithm
Scroll Digital compressors and three phase Copeland to output a smooth suction pressure signal.
Scroll Digital and Discus Digital compressors. (Reference
• For systems that include a compressor vapor
Emerson Climate Technologies AE21-1319, AE4-1357
injection solenoid valve, the compressor controller
and AE21-1355 for details on the digital compressor.)
energizes this valve whenever the compressor
The system controller supplied by the OEM measures
is running.
temperature, pressure or humidity to calculate the
needed compressor capacity and communicates that
capacity to the Digital Compressor Controller via an Specifications Width: 2.0”
analog signal. (51 mm)

The Digital Compressor Controller provides control,


protection and diagnostics for the digital compressor
system. The type of compressor and the application
determine the version of Digital Compressor Controller Height:
that can be used. See Tables 1, 2 3 and 4 for part 4.0”
number details. (102 mm)
• The Digital Compressor Controller “modulates”
or cycles the unloader solenoid in an on/off
pattern according to the capacity demand signal
from the system controller.
• The compressor contactor coil is controlled
based on the capacity demand from the system
controller and the presence of any compressor
trip or lock out conditions. Depth: 6.0” (153 mm)
• The compressor is protected against high Operating Temperature: -40°F to 150°F
discharge temperature by a discharge temperature (-40°C to 65°C)
thermistor. If the maximum temperature limit is
exceeded, the Digital Compressor Controller will Storage Temperature: -60°F* to 175°F
protect the compressor by turning it off. (-49°C* to 80°C)
• Seven ALERT codes are displayed indicating Supply Voltage: 19-28VAC, 48-62Hz
an abnormal system or compressor condition.
Depending on the severity of the code, the Supply Power: 2 VA maximum
Digital Compressor Controller will shut down the UL Requirements: For power supply:
compressor or run the compressor in a limited use only with Class 2
capacity. circuits, File #SA32917
• After each compressor shut down event, in some Enclosure Protection IP20, NEMA1
digital controller module versions a two minute
anti-short cycle delay timer is active preventing
the compressor from restarting. This is indicated *MIL-STD-810F, Method 502.4, 4.5.2
by a flashing green light. See Table 1 for versions
with this feature.

© 2010 Emerson Climate Technologies 1


Printed in the U.S.A.
AE8-1328 R5

Installation
Four #10 self tapping sheet metal screws, at least
½” length, are required for installation. The maximum
mounting screw torque is 20 in.lbs. Locate the
Digital Compressor Controller inside the electrical
enclosure near the compressor contactor (wire
routing for compressor power wiring will be easier
in this position). The maximum wire terminal screw
torque is 7 in. lbs. The Digital Compressor Controller
will operate in any mounting orientation where the
green POWER LED is at the top. Mount the Digital
Compressor Controller so all LEDs are visible from
a comfortable viewing position.

A service panel label (Form 052-2401-00) describing


the terminals and ALERT flash codes is included with
each Digital Compressor Controller. This label should
be in a visible location for the technician when he is
troubleshooting the system. See Figure 5. Figure 1
Digital Compressor Controller 543-0024-00, -01
Compressor Wiring
(See Figure 3)
The Digital Compressor Controller senses compressor
motor current for diagnostics and protection. The
compressor motor leads must be run through the
holes in the plastic housing for a current transformer
to sense motor current.

Single Phase Compressors: the compressor’s run


(R), common (C) and start (S) wires must be routed
through the holes in the Digital Compressor Controller
module marked “R,” “C” and “S.” The run capacitor may
be located on either side of the Digital Compressor
Controller module.

Three Phase Compressors: the compressor’s T1, T2


and T3 wires must be routed through the holes in the
Digital Compressor Controller module marked “T1,” Figure 2
“T2” and “T3.” The Digital Compressor Controller
Digital Compressor Controller 543-0086-01
module is phase insensitive and will not detect reverse
phasing of the compressor.
Low Voltage Terminals
NOTE!
24COM Module Common
Do not bundle low voltage wires with compressor
24VAC Module Power
power or high voltage wires.
C1 Demand Input – { Recommend
C2 Demand Input + Shielded Cable
NOTE!
P1 Pressure Common
Attach cable ties through loops on side of the
P2 Pressure Input
housing for wire strain relief.
P3 Pressure Power 5VDC
P4 Pressure Shield
P5 Pressure Output –
P6 Pressure Output +
T1 Discharge Temp Sensor
T2 Discharge Temp Sensor

© 2010 Emerson Climate Technologies 2


Printed in the U.S.A.
AE8-1328 R5

High Voltage Terminals recommended. For best signal resolution, the smallest
A1 Alarm Relay Out acceptable pressure transducer range for the refrigerant
A2 Alarm Relay Out should be used. The Digital Compressor Controller
M1 Contactor provides a precision source 5VDC for the pressure
M2 Contactor transducer to accurately measure the pressure. This
L1 Control Voltage 5VDC source is capable of sourcing a maximum of
L2 Control Voltage 10mA
U1 Digital Unloader Solenoid
U2 Digital Unloader Solenoid (P5, P6) System Pressure Output
V1 Vapor Injection Solenoid
If a pressure transducer is connected to the System
V2 Vapor Injection Solenoid
Pressure Input terminals, the System Pressure Output
provides an analog output of the filtered suction
NOTE!
pressure. The Digital Compressor Controller “filters”
To avoid damaging the Digital Compressor Controller do
this suction pressure by using the unloader capacity
not connect wires to terminals C3, C4, T3, T4, T5 or T6.
algorithm to smooth the pressure fluctuations measured
by the suction pressure transducer. The output of
(24VAC, 24COM) Digital Compressor
0 – 5VDC corresponds to the range of the pressure
Controller Power
transducer connected to the System Pressure Input
The power supply for the Digital Compressor Controller terminals. This output is capable of sourcing a maximum
is 19-28VAC, 48-62Hz. The maximum load is 2 VA. The of 10mA.
24VAC phasing for the Digital Compressor Controller
must match the system controller to avoid a transformer (T1, T2) Discharge Temperature Input
short circuit condition because the two controllers have
their commons connected together. Twenty-four volt The Discharge Temperature Input is a thermistor input.
power to the module must be on anytime the unit is on There is no polarity requirement for the thermistor.
and should not be interrupted by any control. Center For thermistor signal wiring, short wire runs are
tap transformers are not to be used. recommended. For 3D Discus Digital and Scroll Digital,
the cut out temperature is 268°F (131°C) and the cut
(C1, C2) System Controller Demand in or reset temperature is 250°F (121°C). For the 4D
Discus Digital, the cut out temperature is 310°F (154°C)
Controller Demand is an analog input signal from and the cut-in temperature is 267°F (130°C). See Table
the system controller to the Compressor Controller, 4 for thermistor temperature/resistance values.
proportional to the capacity required from the compressor.
Controller Demand is a 1-5VDC input where 1.0VDC is (A1, A2) Alarm Relay
0% capacity and 5.0VDC is 100% capacity. When the
signal falls below 10% capacity (1.25VDC on decreasing The Alarm Relay output is a normally open, dry contact
demand) the Digital Compressor Controller will shut relay output. The maximum operating voltage for this
down the compressor. When the signal rises above relay is 250VAC or 30VDC and the maximum load is 3 A.
10% capacity (1.44VDC on increasing demand) and During an alarm condition, the relay contacts close until
the anti-short cycle timer inherent in some controllers the alarm condition ceases or power is turned off.
(see Table 1) has timed out, the Digital Compressor
Controller will start the compressor again. See Figure (M1, M2) Compressor Contactor
4 for a graphical representation. The maximum input
voltage for C1, C2 is 5.3 VDC. The compressor contactor output is a triac output. The
maximum continuous contactor coil load is 0.5A
NOTE! and the peak inrush current is 6A. The maximum
During normal unit operation the voltage to C2 must coil operating voltage is 24 - 250VAC. This output is
be above 0.5 volts. The voltage to C2 should never be incompatible with DC coil voltages. The compressor
completely interrupted while the unit is on. contactor is energized when there are no ALERT
conditions and the demand signal is greater than
(P1, P2, P3, P4) System Pressure Input 1.44VDC.
If a pressure transducer is used with the Compressor (L1, L2) Control Power
Controller, the System Pressure Input is a measurement
of the system suction pressure. For pressure transducer NOTE!
signal wiring, short wire runs and shielded wiring are Control Power supplied to Digital Compressor Controller

© 2010 Emerson Climate Technologies 3


Printed in the U.S.A.
AE8-1328 R5

must be the same voltage as the compressor contactor Compressor Running


coil, unloader solenoid and vapor injection solenoid.
The loaded/unloaded cycle always equals either 20
The Control Power requirement is a single phase, 19- seconds or 15 seconds depending on the controller
250VAC, 48-62Hz source. The control power must be module. The loaded sequence always precedes the
isolated with a transformer from the mains power unloaded sequence. Capacity modulation is achieved by
supply. The maximum load on the control power energizing and de-energizing the solenoid valve. When
circuit is 1.5A based on a motor contactor, unloader the solenoid valve is de-energized, the compressor
solenoid and vapor injection solenoid connected to the capacity is 100%. When the solenoid valve is energized,
Compressor Controller. the compressor capacity is zero. Therefore, the capacity
achieved is the time average capacity, which is a
(U1, U2) Unloader Solenoid variable from 10 – 100%.

The Unloader Solenoid output is a triac output. The Example of 20 second cycle: If the solenoid is de-
maximum continuous solenoid load is 0.5A and the peak energized (compressor loaded) for four seconds,
inrush current is 6A. The maximum solenoid operating then energized (compressor unloaded) for sixteen
voltage is 250VAC. This output is incompatible with DC seconds, the resulting capacity will be 20% of full load
solenoid voltages. The unloader solenoid is energized capacity. See Table 2. Example of 15 second cycle: If
in an on/off pattern to deliver the capacity requested by the solenoid is de-energized (compressor loaded) for
the demand signal. three seconds, then energized (compressor unloaded)
for twelve seconds, the resulting capacity will be 20%
(V1, V2) Vapor Injection Solenoid of full load capacity. See Table 3.
The Vapor Injection Solenoid output is a triac output. Digital Compressor Controller LEDs
The maximum continuous solenoid load is 0.5A. The
maximum solenoid operating voltage is 250VAC and the POWER LED (green) – indicates voltage is present at
peak inrush current is 6A. This output is incompatible the 24VAC power terminals. When the anti-short cycle
with DC solenoid voltages. The vapor injection solenoid timer is active, the green LED will flash.
is energized whenever the compressor contactor is
energized. UNLOADER LED (yellow) – indicates the unloader
solenoid status. This LED is on when the unloader
Compressor Start And Shut Down solenoid is energized.
The Digital Compressor Controller always unloads ALERT LED (red) – communicates an abnormal system
the compressor for 0.1 seconds at each startup. After condition through a unique flash code. The ALERT LED
this brief unloading period, the unloader solenoid will will flash a number of times consecutively, pause and
be deenergized and the compressor will run loaded then repeat the process. The number of consecutive
according to the level of the Demand input signal. flashes, defined as the Flash Code, correlates to a
Each time the compressor shuts down, the Digital particular abnormal condition.
Compressor Controller will run the compressor unloaded
for 0.5 seconds. Energizing the unloader solenoid for Flash Code Troubleshooting
this period of time will allow the discharge and suction
pressures to equalize, minimizing scroll reverse rotation. While each ALERT code is active, the alarm relay
contacts (A1 and A2) are closed. The ALERT code will
remain active and the alarm relay contacts closed until
the reset conditions have been met or 24VAC power has
been cycled off and on. All Flash Codes except Code
6 and 8 result in the compressor contactor, unloader
solenoid and vapor injection solenoid being deenergized.
Flash codes 3, 4, 5, and 9 activate the two minute anti-
cycle timer. Flash code 2 activates the 30 minute timer.

All LEDs flashing at the same rate indicates 24VAC


supply is too low for operation. All LEDs on solid at
the same time indicates Digital Compressor Controller
failure.

© 2010 Emerson Climate Technologies 4


Printed in the U.S.A.
AE8-1328 R5

Whenever power is cycled off and on, the current Flash The Digital Compressor Controller will deenergize
Code and all internal counters are reset. the compressor contactor and vapor injection
solenoid. The alarm relay contacts will close.
Flash Code 1 - Reserved for future use
If a low pressure cut-out device is used, the
Flash Code 2 - High Discharge Temperature compressor could short-cycle depending on the cut-
The discharge temperature thermistor has measured in and cut-out pressures and system configuration.
a temperature above 268°F (130°C) or the thermistor This could be interpreted as a Locked Rotor fault
is short circuited (jumpered out). by the Digital Controller and the compressor will
get locked out.
The Digital Compressor Controller will deenergize
the compressor contactor and vapor injection This code results in a lockout and can only be reset
solenoid. The alarm relay contacts will close. by cycling the 24VAC power off and on.

The compressor will be allowed to restart after a 30 Flash Code 5 - Demand Signal Loss
minute delay and after the thermistor temperature The demand signal input has dropped below 0.5VDC.
is below 250°F (120°C). The flash code and alarm The demand input signal wire may be disconnected
relay contacts will be reset after the compressor has or the system controller providing the signal may
run for 60 uninterrupted minutes without any other not be powered.
ALERTs.
The Digital Compressor Controller will deenergize
If five high discharge temperature ALERTs have the compressor contactor and vapor injection
occurred within four hours, the Digital Compressor solenoid. The alarm relay contacts will close.
Controller will lock out the compressor. The lockout
can only be reset by cycling the 24VAC power off Once the system controller demand signal input has
and on. risen above 0.5VDC, the ALERT code and alarm
relay output will reset. If the demand signal is above
Flash Code 3 - Compressor Protector Trip 1.44VDC and the anti-short cycle timer has timed
The demand signal from the system controller is out, the compressor will restart. There is no lockout
greater than 1.44VDC and there is no compressor feature for this ALERT.
current detected. This could be due to the
compressor’s internal overload protector being Flash Code 6 - Discharge Thermistor Fault
open, fuse or breaker open, power disconnected to The Digital Compressor Controller is not receiving
compressor contactor, compressor power wiring not a signal from the discharge temperature thermistor.
run through Digital Compressor Controller current The thermistor may be missing, disconnected or a
transformer port or a compressor contactor failure. wire is broken.

The Digital Compressor Controller will deenergize The alarm relay contacts will close and the Digital
the compressor contactor and vapor injection Compressor Controller will not increase the capacity
solenoid. The alarm relay contacts will close. of the compressor beyond 50% loading.

The Digital Compressor Controller will wait for This ALERT code and alarm relay output are reset
the anti-short cycle timer to time out and if the by reconnecting the thermistor.
system controller demand signal is still greater than
1.44VDC, energize the compressor contactor again. Flash Code 7 - Unloader Solenoid Fault
If compressor current is detected on the restart, the Reserved for future use
ALERT code and alarm relay output will reset. The
Digital Compressor Controller will attempt to restart Flash Code 8 - Compressor Contactor Fault
compressor as long as the system controller demand Compressor current is detected when the system
is above 1.44VDC. There is no lockout feature for controller demand signal is below 1.44VDC. The
this ALERT. compressor contactor may have welded contacts
or the contacts may be mechanically jammed. The
Flash Code 4 - Locked Rotor compressor will continue to run in this condition since
A locked rotor condition in the compressor is the Digital Compressor Controller cannot open the
sensed by the Digital Compressor Controller on four compressor contactor.
consecutive start ups within a 20 second period.

© 2010 Emerson Climate Technologies 5


Printed in the U.S.A.
AE8-1328 R5

The Digital Compressor Controller will energize Input Tests


the compressor contactor and vapor injection
solenoid. The alarm relay contacts will close. The Thermistor Input – disconnect the discharge temperature
unloader solenoid will remain energized causing the sensor wires from terminals T1 and T2. If functioning
compressor to run unloaded as long as the system normally, the Digital Compressor Controller should display
controller demand signal is less than 1.44VDC. If the a Code 6 unless a previous ALERT code was present.
system controller demand is greater than 1.44VDC,
the unloader solenoid will deenergize causing the Demand Input – disconnect the System Controller
compressor to run loaded. Demand signal wires from C1 and C2. If functioning
normally, the Digital Compressor Controller should
The ALERT code and alarm relay output are reset display a Code 5 unless a previous ALERT code was
when current is no longer detected while system present.
controller demand signal is below 1.44VDC.
Output Tests
Flash Code 9 - Low 24VAC Supply
Supply voltage to the Digital Compressor Controller Contactor Output – while the Digital Compressor
has dropped below 18.5VAC. Controller is powered off (no supply voltage to 24VAC
and 24COM), disconnect the System Controller Demand
The Digital Compressor Controller will deenergize signal wire from C1 and C2. Add a jumper wire from P3
the compressor contactor, unloader solenoid and to C2 and a second jumper wire from P1 to C1. Reapply
vapor injection solenoid. The alarm relay contacts power to 24VAC and 24COM. If functioning normally,
may close if the voltage is high enough for the alarm a voltmeter should read the same voltage across M1
relay to pull in. and M2 as is measured across L1 and L2, unless an
The ALERT code and alarm relay output are reset ALERT code is present.
when the supply voltage to the Digital Compressor
Controller rises above 19.5VAC. Unloader Output – while Digital Compressor Controller is
modulating the unloader solenoid, a voltmeter should read
the same voltage across U1 and U2 as is measured across
OEM Testing L1 and L2 whenever the yellow “Unloader “LED is lit.
The Digital Compressor Controller can remain in
circuit during factory hi-pot testing. The maximum Demand Cooling with Copeland Digital Compressor
hi-pot test voltage that should be applied between Controller
ground and the 24VAC Low Voltage Inputs and The digital compressor controller has its own discharge
Outputs is 600VAC. The maximum hi-pot test temperature protection. However, for applications requiring
voltage that should be applied between the High Demand Cooling, the Demand Cooling module should
Voltage Control and High Voltage Outputs is have primary control of the temperature protection.
2500VAC. The normal leakage current should be To ensure the Demand Cooling system functions
less than 200 microamps. appropriately, jumper the T1 and T2 inputs on the Digital
Compressor Controller, with a 5kOhm, 1 Watt resistor.
Testing the Installed Digital Compressor Controller
For more information regarding Copeland Demand
Once installed, the Digital Compressor Controller can
be tested to verify it is working properly. In each test, Cooling, refer to AE4-1327, Economized Vapor Injection
24VAC must be supplied to 24VAC and 24COM. For the (EVI) Compressors, and/or AE4-1287, Copeland Discus
output test, 24-250VAC must be supplied to L1 and L2. Demand Cooling.

© 2010 Emerson Climate Technologies 6


Printed in the U.S.A.
AE8-1328 R5

Figure 3
Compressor Controller Wiring Diagram

24VAC
** 24COM
CONTROLLER
POWER 24VAC V2
***
OPTIONAL
1-5VDC DEMAND VAPOR
SIGNAL FROM COMMON C1 INJECTION
+5VDC V1
SYSTEM SOLENOID
C2
CONTROLLER SIGNAL
C3 DIGITAL
U2 UNLOADER
C4 SOLENOID
OPTIONAL P1 U1
COMMON
SUCTION
PRESSURE
TRANSDUCER
SIGNAL
+5VDC
P2
P3 M2
*
SUPPLY CONTACTOR
INPUT
COIL
OPTIONAL P4 M1
0-5VDC COMMON P5
SUCTION
PRESSURE +5VDC P6 L2 CONTROL
OUTPUT VOLTAGE
T1
L1 24-250VAC
T2
DISCHARGE T3
TEMPERATURE A1
ALARM
THERMISTOR T4 RELAY
OR 5kOhm, 1W RESISTOR T5 OUTPUT
A2
(for Demand Cooling Applications)
T6

COMPRESSOR POWER
WIRE T1/C

Note: The L1, M1, U1, and V1 are connected together inside the module.
Note: For 110V control circuits, it is suggest to connect the incoming control power (110V) to L2 and
connect the unpowered wire (Neutral) to L1. This wiring method is to prevent having 110V at the coils
when the module relays are not closed.

© 2010 Emerson Climate Technologies 7


Printed in the U.S.A.
AE8-1328 R5

Table 1
Digital Compressor Controllers
“Duty Cycle Time 2-Minute Anti Short
Part No. Application
(sec)” Cycle Timer Delay
543-0024-00 20 Yes Refrigeration - Scroll
543-0024-01 15 Yes Air Conditioning - Scroll
543-0086-01 20 No Refrigeration - Scroll & Discus® (3D)
543-0088-00 20 No Refrigeration - Discus® (4D)

Table 2
Digital Compressor Controller Differences

Digital Compressor Controller Part Number


Features
543-0024-00 543-0024-01 543-0086-01 543-0088-00
>268F, Lockout >268F, Lockout
High Discharge Temperature on 5th on 5th
>268F, No Lockout >310F, No Lockout

Protector Trip 2min Off Time 2min Off Time 6sec Off Time 6sec Off Time

Lockout on Lockout on No Lockout, No Lockout,


Locked Rotor Detection Detection 30min Offtime 30min Offtime

Demand Signal Loss Demand < 0.5V Demand < 0.5V Demand < 0.5V Demand < 0.5V

Limit Capacity Limit Capacity


Discharge Thermistor Fault To 50% To 50%
No Capacity Limit No Capacity Limit

Detection In Detection In
Welded Contactor Detection In 2Secs Detection In 2Secs
30Secs 30Secs
Supply voltage Supply voltage Supply voltage Supply voltage
Low Voltage < 19VAC < 19VAC < 19VAC < 19VAC

Anti-Short Cycling Time 2min OFFtime 2min OFFtime 6secs OFFtime 6secs OFFtime

Modulation Range 10% To 100% 10% To 100% 10% To 100% 50% To 100%

Duty Cycle Time 20secs 15secs 20secs 20secs

Table 3
20 Second Cycle Controller: 543-0024-00 20; 543-0086-01
% Digital
Demand Signal
Loaded % Unloaded% Time Loaded Time Unloaded Compressor
(VDC)
Capacity
1.00 Off Off Off Off 0%
1.44 10% 90% 2 seconds 18 seconds 10%
3.00 50% 50% 10 seconds 10 seconds 50%
4.20 80% 20% 16 seconds 4 seconds 80%
5.00 100% 0% 20 seconds 0 seconds 100%

© 2010 Emerson Climate Technologies 8


Printed in the U.S.A.
AE8-1328 R5

Table 4
15 Second Cycle Controller: 543-0024-01

Demand Signal % Digital Compressor


Loaded % Unloaded% Time Loaded Time Unloaded
(VDC) Capacity
1.00 Off Off Off Off 0%
1.44 10% 90% 1.5 seconds 13.5 seconds 10%
3.00 50% 50% 7.5 seconds 7.5 seconds 50%
4.20 80% 20% 12 seconds 3 seconds 80%
5.00 100% 0% 15 seconds 0 seconds 100%

Table 5
20 Second Cycle Controller: 543-0088-00

Demand Signal % Digital Compressor


Loaded % Unloaded% Time Loaded Time Unloaded
(VDC) Capacity
1 Off Off Off Off 0%
2.9 0% 100% 0 seconds 20 seconds 50%
3.42 25% 75% 5 seconds 15 seconds 63%
3.95 50% 50% 10 seconds 10 seconds 75%
5 100% 0% 20 seconds 0 seconds 100%
* Note! Only one bank of a 4D Discus Digital modulates. Therefore, unless the compressor is completely off (1.00 V
or less to Digital Compressor Controller) at least 50% capacity will be provided by the 4D compressor at all times.

© 2010 Emerson Climate Technologies 9


Printed in the U.S.A.
AE8-1328 R5

Table 6
Thermistor Temperature/Resistance Values

Deg C Deg F Resistance (kOhms) Deg C Deg F Resistance (kOhms)


-40 -40 2889.60 70 158 15.07
-35 -31 2087.22 75 167 12.73
-30 -22 1522.20 80 176 10.79
-25 -13 1121.44 85 185 9.20
-20 -4 834.72 90 194 7.87
-15 5 627.28 95 203 6.77
-10 14 475.74 100 212 5.85
-5 23 363.99 105 221 5.09
0 32 280.82 110 230 4.45
5 41 218.41 115 239 3.87
10 50 171.17 120 248 3.35
15 59 135.14 125 257 2.92
20 68 107.44 130 266 2.58
25 77 86.00 135 275 2.28
30 86 69.28 140 284 2.02
35 95 56.16 145 293 1.80
40 104 45.81 150 302 1.59
45 113 37.58 155 311 1.39
50 122 30.99 160 320 1.25
55 131 25.68 165 329 1.12
60 140 21.40 170 338 1.01
65 149 17.91 175 347 0.92
180 356 0.83

© 2010 Emerson Climate Technologies 10


Printed in the U.S.A.
AE8-1328 R5

Figure 4
Demand Signal Vs. Modulation Graph
(P/N 543-0024-00, 543-0024-01, & 543-0086-01)

Figure 5
Demand Signal vs. Modulation Graph (P/N 543-0088-00)
100%
5.00
90%

80%
3.95
Unloader Modulation

70%

60%

50% Compressor
Off 2.90
40%

30%

20%

10%

0%
0.0 0.4 0.8 1.2 1.6 2.0 2.4 2.8 3.2 3.6 4.0 4.4 4.8 5.2
Demand Signal (VDC)

© 2010 Emerson Climate Technologies 11


Printed in the U.S.A.
AE8-1328 R5

Figure 6
Service Panel Label (Form 052-2401-00) For Controller Part No. 543-0024-00 and 543-0024-01

Copeland Scroll Digital™ Compressor Controller


Low Voltage Terminals LED Descriptions Troubleshooting ALERT Flash Codes
24 COM Module Power Green LED - 24VAC Power Code 1 Reserved for future use
24 VAC Module Power Yellow LED - Unloader Solenoid On
Code 2 High Discharge Temperature
C1 Demand Input - Red LED - ALERT Flash Code
Discharge thermistor above trip set point or thermistor short circuited.
C2 Demand Input +
Resets after 30 minutes and motor cools down.
P1 Pressure Common • Flashing Green LED indicates anti-short
If 5 events occur within 4 hours, the compressor is locked out.
P2 Pressure Input cycle timer active
P3 Pressure Power 5VDC Code 3 Compressor Protector Trip
P4 Pressure Shield • All LEDs flashing at same rate indicates No compressor current is detected when compressor should be running.
P5 Pressure Output - 24VAC supply too low for operation Resets when compressor current is detected.
P6 Pressure Output + Code 4 Locked Rotor
T1 Discharge Temp Sensor • All LEDs solid at same time indicates Locked rotor condition is detected. Compressor is locked out.
T2 Discharge Temp Sensor controller failure
Code 5 Demand Signal Loss
High Voltage Terminals • Reset ALERT code or lockout by Demand input signal is below 0.5VDC. Resets after demand input signal rises
A1 Alarm Relay Out removing 24VAC supply to module above 1.0VDC.
A2 Alarm Relay Out Code 6 Discharge Thermistor Fault
L1 Control Voltage N • All ALERTs close alarm relay contacts Thermistor is not connected. Reset by reconnecting thermistor.
L2 Control Voltage L
M1 Contactor • All ALERTs deenergize contactor and Code 7 Reserved for future use
M2 Contactor solenoids except Code 6 Code 8 Compressor Contactor Fault
U1 Unloader Solenoid Compressor current is detected when compressor should be off. Resets when
U2 Unloader Solenoid • Compressor always unloads for 0.1 second at current is no longer detected.
V1 Vapor Injection Solenoid startup
V2 Vapor Injection Solenoid Code 9 Low 24VAC Supply
• Compressor only starts when Demand signal Supply voltage to module has dropped below 18.5VAC. Resets after voltage rise
All high voltage terminals input is above 1.45 VDC and no ALERTs are above 19.5VAC.
rated 24-250 VAC present

For More Information:


EmersonClimate.com Emerson and Copeland are trademarks of Emerson Electric Co. or one of its affiliated companies.
Online Product Information (OPI) Part Number
© 2003 Emerson Climate Technologies, Inc. All rights reserved.
AE Bulletin AE8-1328 052-2401-00 Rev. 0

Figure 7
Service Panel Label (Form 052-2402-00) For Controller Part No. 543-0086-01 and 543-0088-00

Copeland™ 4D Digital Compressor Controller

© 2010 Emerson Climate Technologies 12


Printed in the U.S.A.

You might also like