ASHRAE 154 - Ventilation For Commercial Cooking Operations - Unlocked
ASHRAE 154 - Ventilation For Commercial Cooking Operations - Unlocked
ASHRAE 154 - Ventilation For Commercial Cooking Operations - Unlocked
Ventilation for
Commercial Cooking
Operations
Approved by ASHRAE on July 31, 2016, and by the American National Standards Institute on August 1, 2016.
This Standard is under continuous maintenance by a Standing Standard Project Committee (SSPC) for which the Standards
Committee has established a documented program for regular publication of addenda or revisions, including procedures for
timely, documented, consensus action on requests for change to any part of the Standard. The change submittal form,
instructions, and deadlines may be obtained in electronic form from the ASHRAE website (www.ashrae.org) or in paper
form from the Senior Manager of Standards. The latest edition of an ASHRAE Standard may be purchased from the
ASHRAE website (www.ashrae.org) or from ASHRAE Customer Service, 1791 Tullie Circle, NE, Atlanta, GA 30329-2305.
E-mail: [email protected]. Fax: 678-539-2129. Telephone: 404-636-8400 (worldwide), or toll free 1-800-527-4723 (for
orders in US and Canada). For reprint permission, go to www.ashrae.org/permissions.
* Denotes members of voting status when the document was approved for publication
SPECIAL NOTE
This American National Standard (ANS) is a national voluntary consensus Standard developed under the auspices of ASHRAE. Consensus is defined
by the American National Standards Institute (ANSI), of which ASHRAE is a member and which has approved this Standard as an ANS, as
“substantial agreement reached by directly and materially affected interest categories. This signifies the concurrence of more than a simple majority,
but not necessarily unanimity. Consensus requires that all views and objections be considered, and that an effort be made toward their resolution.”
Compliance with this Standard is voluntary until and unless a legal jurisdiction makes compliance mandatory through legislation.
ASHRAE obtains consensus through participation of its national and international members, associated societies, and public review.
ASHRAE Standards are prepared by a Project Committee appointed specifically for the purpose of writing the Standard. The Project
Committee Chair and Vice-Chair must be members of ASHRAE; while other committee members may or may not be ASHRAE members, all
must be technically qualified in the subject area of the Standard. Every effort is made to balance the concerned interests on all Project Committees.
The Senior Manager of Standards of ASHRAE should be contacted for
a. interpretation of the contents of this Standard,
b. participation in the next review of the Standard,
c. offering constructive criticism for improving the Standard, or
d. permission to reprint portions of the Standard.
DISCLAIMER
ASHRAE uses its best efforts to promulgate Standards and Guidelines for the benefit of the public in light of available information and accepted
industry practices. However, ASHRAE does not guarantee, certify, or assure the safety or performance of any products, components, or systems
tested, installed, or operated in accordance with ASHRAE’s Standards or Guidelines or that any tests conducted under its Standards or Guidelines
will be nonhazardous or free from risk.
CONTENTS
ANSI/ASHRAE Standard 154-2016,
Ventilation for Commercial Cooking Operations
SECTION PAGE
Foreword .....................................................................................................................................................................2
1 Purpose.............................................................................................................................................................2
2 Scope ................................................................................................................................................................2
3 Definitions .........................................................................................................................................................2
4 Exhaust Hoods..................................................................................................................................................5
5 Exhaust Systems ............................................................................................................................................10
6 Replacement Air..............................................................................................................................................11
7 System Controls..............................................................................................................................................12
8 Administration and Compliance ......................................................................................................................12
9 References......................................................................................................................................................12
Informative Annex A: Examples of Air Balancing ..................................................................................................14
Informative Annex B: Alternative Airflow Calculation Method ...............................................................................17
Informative Annex C: Hood Energy Savings Calculation ......................................................................................19
Informative Annex D: Using ASHRAE Standard 154 to Determine Hood Overhangs and Exhaust Airflows........21
Informative Annex E: Informative Bibliography .....................................................................................................23
NOTE
Approved addenda, errata, or interpretations for this standard can be downloaded free of charge from the ASHRAE
website at www.ashrae.org/technology.
© 2016 ASHRAE
1791 Tullie Circle NE · Atlanta, GA 30329 · www.ashrae.org · All rights reserved.
ASHRAE is a registered trademark of the American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.
ANSI is a registered trademark of the American National Standards Institute.
--``,,,`,,`,`,,,,,```,,,``````-`-`,,`,,`,`,,`---
© ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution,
or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.
(This foreword is not part of this standard. It is merely based on the temperature of the cooking surface. The follow-
informative and does not contain requirements necessary ing appliance duty classifications are used in this standard:
for conformance to the standard. It has not been pro- a. light: a cooking process requiring an exhaust airflow
cessed according to the ANSI requirements for a standard rate of less than 200 cfm/ft (310 L/s/m) for capture,
and may contain material that has not been subject to containment, and removal of the cooking effluent and
public review or a consensus process. Unresolved objec- products of combustion.
tors on informative material are not offered the right to b. medium: a cooking process requiring an exhaust
appeal at ASHRAE or ANSI.) airflow rate of 200 to 300 cfm/ft (310 to 460 L/s/m) for
capture, containment, and removal of the cooking
FOREWORD
effluent and products of combustion.
First published in 2003, ASHRAE Standard 154 has been c. heavy: a cooking process requiring an exhaust airflow
thoroughly revised in this edition to make it code enforceable rate of 300 to 400 cfm/ft (460 to 620 L/s/m) for
and to provide the most complete design guidance available capture, containment, and removal of the cooking
on commercial kitchen ventilation components and systems. effluent and products of combustion.
In revising this standard, the project committee has drawn d. extra-heavy: a cooking process requiring an exhaust
upon recent laboratory research that was sponsored in part airflow rate greater than 400 cfm/ft (620 L/s/m) for
by ASHRAE and assembled by the ASHRAE Technical Com- capture, containment, and removal of the cooking
mittee on kitchen ventilation, TC 5.10. It has also relied upon effluent and products of combustion.
the significant field experiences of the manufacturers, design- approved: acceptable to the authority having jurisdiction.
ers, and users of kitchen ventilation systems. The standard is
intended to serve as a template for standardization, harmoni- back-wall supply: see replacement air, makeup air (dedicated
zation, and ongoing revision of related model and adopted replacement air), back-wall.
codes and to bring consistency to design requirements and baffle filter: see grease removal device.
applications of commercial kitchen ventilation systems. capture area: the area within an exhaust hood that contains
This revision of Standard 154-2011 addresses recent cooking effluent until it is exhausted.
advancements in commercial kitchen ventilation (CKV)
research, CKV system components, and cooking appliances capture and containment (C&C): an exhaust hood’s ability
and continues the advancement of Standard 154 as the lead- to capture and contain the cooking effluent and heat generated
ing CKV code-language design document. during cooking operations.
cartridge filter: see grease removal device.
1. PURPOSE
centrifugal fan: see exhaust fan.
The purpose of this standard is to provide design criteria for certified: see listed.
acceptable performance in commercial cooking ventilation
systems. compensating hood: see replacement air, makeup air (dedi-
cated replacement air), internal.
2. SCOPE commercial cooking appliance: an appliance specifically
2.1 This standard covers designed to be used in a food-service-establishment kitchen,
--``,,,`,,`,`,,,,,```,,,``````-`-`,,`,,`,`,,`---
exfiltration: leakage or flow of indoor air out of the building accumulation of combustible condensation, thus reducing the
or space through openings in the building or space envelope, possibility of fire within the duct system.
whether intentional or unintentional. The driving force for grease laden: containing grease particles and/or grease vapor.
exfiltration is a positive pressure in the building or space rela-
tive to the exterior of the building envelope. grease removal device: a device designed and installed in a
Type I hood to remove grease vapor and/or particles from the
exhaust fan: a fan used to exhaust cooking effluent collected airstream. As used in this standard, the term refers to devices
by a hood. Also referred to as a power roof ventilator. The that are certified to UL Standard 1046, Grease Filters for
majority of these fans have a centrifugal fan wheel. Fans used Exhaust Ducts 4, or to UL Standard 710, Exhaust Hoods for
in Type I hood applications must include provisions for han- Commercial Cooking Equipment 5, as part of the hood.
dling grease and access for cleaning. Devices include but are not limited to the following:
a. in-line exhaust fan or tubular centrifugal fan: a fan a. baffle filter: a filter typically having a series of verti-
designed for mounting indoors or outdoors in a cal baffles designed to capture grease and drain to a
section of duct between the hood and the point of grease trough. Filters are removable for cleaning and
discharge. Air enters the fan axially and discharges maintenance of the hood.
linear to the entrance. b. cartridge filter: a filter having a horizontal slot open-
b. roof exhaust fan or power roof ventilator: a fan ing with a series of internal deflectors designed to
designed for curb mounting on a roof and that capture grease and drain to a grease trough. Filters are
discharges downward toward the roof, vertically up removable for cleaning and maintenance of the hood.
away from the roof, or horizontally away from the c. fixed or stationary extractor: a device typically
building. Fans that discharge downward may be used having horizontal slot openings with a series of inter-
only for Type II hood applications. nal deflectors designed to capture grease and drain to
c. up-blast exhaust fan: a fan designed for curb-mount- a grease trough. Extractors are not removable from the
ing on a roof or for wall mounting. Air enters the fan hood and typically have access doors for cleaning and
axially but discharges radially from the centrifugal maintenance of the hood.
impeller and turns 90 degrees to exit the fan vertically d. multistage extractor or filter: these devices consist of
where roof-mounted and horizontally where wall- a series of two or more grease removal devices located
mounted. in the hood.
d. side-wall exhaust fan: a fan design similar to an up- e. removable extractor: any style of grease removal
blast exhaust fan but designed to mount outdoors on device that is removable from the hood.
the side wall of a building. The mounting arrangement f. water wash: a version of the fixed extractor that has a
and internal construction may be specific to side system of built-in nozzles for cleaning the grease
discharge orientation. The fan discharges horizontally removal device.
away from the building.
greasetight: designed to prevent the leakage of grease under
e. utility-set exhaust fan: a fan typically designed with normal operating conditions.
a single-inlet, a scroll housing, and a backward-
inclined or an airfoil centrifugal impeller. It can hood: a device designed to capture and contain cooking efflu-
provide a higher static efficiency capability than a ent, including grease, smoke, steam, heat, and vapor, until it is
typical power roof ventilator. Air enters the impeller exhausted through a duct or recirculating system. Hoods are
axially and leaves it in a substantially radial direction. categorized as Type I or Type II.
These can be mounted indoors or outdoors in-line Type I hood: a hood used for collecting and removing
having additional duct between the fan outlet and the convective heat, grease particulate, condensible vapor,
point of discharge. and smoke. This category includes listed grease filters,
baffles, or extractors for removing the grease and a fire-
exhaust fire (actuated) damper: a damper arranged to auto-
suppression system. Type I hoods are installed over
matically close to restrict the passage of fire airflow into the
cooking appliances, such as ranges, fryers, griddles,
exhaust duct.
broilers, and ovens, that produce smoke or grease-laden
fire resistance rating: the time rating of a material or assem- vapors. For Type I hoods, the following types of hoods
bly indicating its ability to withstand exposure to a fire. are commonly available.
fire suppression system: an automatic fire suppression sys- a. wall-mounted canopy hood: a wall canopy exhaust
tem that is specifically designed to protect Type I hood sys- hood is mounted against a wall above a single appli-
tems and, where required, the cooking appliances served by ance or a line of appliances, or it may be freestanding
the hood system(s). with a vertical back panel extending from the rear of
the appliance(s) to the hood. It typically overhangs the
front-face supply: see replacement air, makeup air (dedi-
front and sides of the appliance(s) on all open sides of
cated replacement air), front-face.
the hood. The wall acts as a back panel, forcing
grease duct: a duct system for the conveyance of cooking replacement air to be drawn across the front and/or
effluent. The system is designed and installed to reduce the side(s) of the cooking appliance, thus increasing the
--``,,,`,,`,`,,,,,```,,,``````-`-`,,`,,`,`,,`---
effectiveness of the hood to capture and contain efflu- interlock, indirect: the indirect connection between equip-
ent generated by the cooking operations. Mounting ment through an external controller; for example, a timeclock,
height varies. building automation system, heat sensor, etc.
b. single-island canopy hood: a single-island canopy internal discharge makeup air: see replacement air, makeup
hood is placed over a single appliance or line of appli- air (dedicated replacement air), internal.
ances. It is open on all sides and overhangs the front,
rear, and sides of the appliance(s). A single-island labeled: equipment or materials to which a label, symbol, or
canopy is more susceptible to cross drafts and requires other identifying mark of an organization, acceptable to the
greater exhaust airflow than an equivalent-sized wall- authority having jurisdiction, has been attached. This organi-
mounted canopy to capture and contain effluent gener- zation is concerned with product evaluation and maintains
ated by the cooking operations. Mounting height periodic inspection of the production of labeled equipment or
varies. materials. By labeling the equipment or materials, the manu-
c. double-island canopy hood: a double-island canopy facturer indicates compliance with appropriate standards or
hood is placed over back-to-back appliances or lines performance in a specified manner.
of appliances. It is open on all sides and overhangs the liquid-tight: constructed and performing so as not to permit
front and the sides of the appliance(s). It may have a the leakage of any liquid at any temperature.
wall panel between the backs of the appliances.
Mounting height varies. listed: equipment or materials included in a list published by
d. backshelf hood: also referred to as a noncanopy hood, an organization acceptable to the authority having jurisdic-
low-proximity hood, or sidewall hood (where wall tion. This organization is concerned with product evaluation
mounted). Its front lower lip is low over the appli- and performs periodic inspections of production of listed
ance(s) and is typically set back from the front of the equipment or materials. The list states either that the equip-
appliance(s), which means there may be no front over- ment or material meets appropriate standards or that it has
hang of appliance(s). It is always closed to the rear of been tested and found suitable for use in a specified manner.
the appliances by a panel where freestanding or by a makeup air: see replacement air, makeup air (dedicated
panel or wall when wall mounted, and its height above replacement air).
--``,,,`,,`,`,,,,,```,,,``````-`-`,,`,,`,`,,`---
makeup air (dedicated replacement air): air deliberately room that originated as outdoor air may be considered
brought into the building from the outdoors and supplied transfer air.
to the vicinity of an exhaust hood to replace the air and infiltration: leakage or flow of outdoor air into the build-
cooking effluent being exhausted. Makeup air is gener- ing or space through openings in the building or space
ally filtered and fan-forced, and it may be heated or envelope, whether intentional or unintentional. The driving
cooled depending on the requirements of the application. force for infiltration is a negative pressure in a space or
Makeup air may be delivered through outlets integral to building relative to the exterior of the building envelope.
the exhaust hood (compensating hoods) or through out-
setback: the horizontal distance that the top horizontal cook-
lets in the same room. Following are systems commonly
ing surface of an appliance extends beyond the front edge of a
used to supply makeup air.
backshelf or pass-over hood.
a. air curtain: air that is introduced vertically downward
short-circuit makeup air: see replacement air, makeup air
through a slot, louvers, or holes along the front edge
(dedicated replacement air), internal.
of the hood or around the perimeter of the hood. This
design has also been referred to as down-discharge. side panel: a panel that is attached to the lower edge of the
b. back-wall: air that is introduced behind and/or below end wall of a hood effectively extending the side of the hood
the cooking equipment. A makeup air plenum is down closer to the cooking appliance.
installed between the back of the hood and the wall. smoke bomb: a device that combusts to produce a large vol-
The full-length plenum typically extends down the ume of smoke, greater than 400 cfm (189 L/s).
wall to approximately 6 in. (150 mm) below the cook-
smoke candle or smoke puffer: a device that is ignited and
ing surface or 2 to 3 ft (600 to 900 mm) above the floor.
combusts to produce smoke or uses a chemical interaction
The air supplied by this system mostly enters the
(such as titanium tetrahydrochloride [TiCL4] with humid air) to
kitchen space rather than remain contained in the
produce smoke or that emits a silica powder to produce smoke.
cooking zone.
c. front-face: air that is introduced either horizontally or solid-fuel cooking appliance: an appliance that combusts a
at a slight downward angle from horizontal from the solid fuel such as wood, charcoal, or coal to provide all or part
front of the hood plenum. of the heat for the cooking process.
d. internal: typically in this design, untempered makeup solid-fuel flavoring cooking appliance: an appliance that
air is introduced directly into the hood cavity. This uses an energy source other than solid fuel to provide all of
design has also been referred to as short-circuit. the heat for the cooking process and also combusts solid fuel
e. perimeter: makeup air is discharged vertically down- solely for the purpose of imparting flavor to the food being
ward from a plenum above and outside of the front and cooked.
sides of the hood.
supply air: see replacement air, supply air.
supply air: air entering a space from an air-conditioning,
heating, or ventilating system for the purpose of comfort transfer air: see replacement air, supply air.
conditioning. Supply air is generally filtered, fan-forced, tubular centrifugal fan: see exhaust fan, tubular centrifugal
and heated, cooled, humidified, or dehumidified as nec- fan.
essary to maintain specified temperature and humidity
conditions. Only the quantity of outdoor air within the 4. EXHAUST HOODS
supply airflow is used as replacement air. Following are 4.1 Hood Requirements
systems commonly used for delivering supply air.
4.1.1 Type I hoods shall be listed in accordance with UL
a. louvered ceiling diffusers: ceiling-installed, aspirat- Standard 710 5, UL Standard 710B 3, or UL Standard 710C 6
ing, two-, three-, or four-way diffusers. Air should not and shall be installed in accordance with their listing require-
be directed toward the hood. ments. Type II hoods shall meet the requirements of Sections
b. perforated diffusers: a ceiling-installed diffuser with 4.2 through 4.8. Type I hoods shall meet the requirements of
a perforated face. Air should not be directed toward Section 4.2 and Sections 4.5 through 4.8. Where a Type II
the hoods. hood is required, a Type II or listed Type I hood shall be pro-
c. linear slot diffusers: ceiling-installed diffusers, typi- vided.
cally placed around the perimeter of rooms. These have 4.1.1.1 Recirculating systems and recirculating hoods
a higher discharge velocity than a louvered ceiling. shall be listed in accordance with UL Standard 710B 3.
d. displacement diffusers: floor-, wall-, and ceiling-
4.1.2 A performance test of an installed Type I hood shall
mounted diffusers with perforated face areas provid-
be carried out as specified in Section 4.7.
ing laminar low-velocity flow from the face.
transfer air: air transferred from one room to another 4.2 Where Required
through openings in the room envelope, whether it is 4.2.1 Table 1 specifies the Type I hood requirements by
transferred intentionally or not. The driving force for appliance description. Table 2 specifies the appliance duty
transfer air is generally a small pressure differential classification as it relates to the Type II hood requirements.
between the rooms, although one or more fans may be Exception: Equipment that is listed in Table 2 and the addi-
used. Only that portion of air transferred from another tional heat and moisture loads generated by unhooded
--``,,,`,,`,`,,,,,```,,,``````-`-`,,`,,`,`,,`---
electric appliances are included in the sensible and 4.3.3.1 Canopy Type Hood. The vertical distance
latent cooling load calculations to determine the between the front lower edge of the hood and the cooking sur-
required capacity of the HVAC system. face shall not exceed 48 in. (1219 mm). The vertical distance
4.2.2 Type II hoods shall be installed in accordance with the between the front lower edge of the hood and the finished
overhangs shown in Table 3 and the net exhaust airflow rates floor shall not be less than 78 in. (1981 mm). The inside hood
shown in Table 4, based on the maximum appliance duty level height shall be at least 24 in. (610 mm).
shown in Table 2 for the appliances underneath the hood. Type 4.3.3.2 Eyebrow Type Hood. The front lower edge of
II hoods may also be installed where cooking or dishwashing the hood shall be at least 78 in. (1981 mm) above the finished
appliances produce heat, steam, or products of combustion and floor.
do not produce grease in excess of 3.1 × 10–7 lb/ft3 (5 mg/m3) 4.3.3.3 Backshelf/Pass-Over Type Hood. The vertical
when measured at an exhaust airflow of 500 cfm (236 L/s). distance between the front lower edge of the hood and the
Informative Note: The 3.1 × 10–7 lb/ft3 (5 mg/m3) grease cooking surface shall be a maximum of 24 in. (610 mm)
concentration when measured at 500 cfm (236 L/s) of exhaust above the cooking surface.
air is equivalent to 9.3 × 10–3 lb/h (4.21 × 10–3 kg/h) of grease 4.4 Type II Hood Airflow Rates
generated by the cooking process.
4.4.1 The net exhaust flow rate (see definition in Section 3)
4.2.3 A Type I hood shall be provided where a cooking for Type II hoods shall comply with Table 4. The duty level
operation within a commercial or institutional food service for the hood shall be the duty level of the appliance that has
facility produces smoke or grease-laden vapors. Appliances the highest (heaviest) duty level of all the appliances that are
that produce greater than 3.1 × 10–7 lb/ft3 (5 mg/m3) of grease installed underneath the hood according to Table 2.
(when measured at 500 cfm [236 L/s] exhaust airflow) shall
Exception: Type II hoods that are shown by the perfor-
require a Type I hood. Type I hoods shall be installed in
mance test in Section 4.7 to provide equivalent capture
accordance with the overhangs shown in Table 3.
and containment at lower airflow rates.
Exceptions:
4.5 Internal Discharge Makeup
1. Cooking appliances not used for commercial pur-
4.5.1 Where a Type I or Type II hood has internal discharge
poses and installed within dwelling units.
makeup air, the makeup airflow shall not exceed 10% of the
2. Appliances listed in Table 2 that produce less than
exhaust airflow. The exhaust airflow required to meet this
3.1 × 10–7 lb/ft3 (5 mg/m3) of grease (when mea-
standard shall be the net exhaust from the hood, calculated as
sured at 500 cfm [236 L/s] exhaust airflow).
follows:
Informative Note: The 3.1 × 10–7 lb/ft3 (5 mg/m3) grease
concentration when measured at 500 cfm (236 L/s) of exhaust ENET = EHOOD – MAID
air is equivalent to 9.3 × 10–3 lb/h (4.21 × 10–3 kg/h) of grease
generated by the cooking process. where
4.2.4 Solid-Fuel Cooking Appliances. Exhaust hood sys- ENET = net hood exhaust, cfm (L/s)
tems, including hoods, ducts, and exhaust fans, serving one or EHOOD = total hood exhaust, cfm (L/s)
more solid-fuel cooking appliances shall be independent of MAID = makeup air, internal discharge, cfm (L/s)
all other exhaust systems.
4.6 Type I Hood Grease Extraction
Exception: Cooking processes that only use solid fuel for
flavoring are exempt from this requirement. 4.6.1 Type I hoods shall be provided with a grease removal
device in accordance with their listing.
4.3 Type II Hood Sizing
4.6.2 For grease removal devices that report grease removal
4.3.1 Type II hood overhangs and setbacks shall comply efficiency, the efficiency data shall be reported as determined
with Table 3 on all open sides, measured in the horizontal by ASTM F2519 7.
plane from the inside edge of the hood to the edge of the top
horizontal surface of the appliance. The vertical distance 4.7 Hood Performance Test
between the front lower lip of the hood and appliance cooking 4.7.1 Type II Hood Performance Test. A performance test
surface shall not exceed 4 ft (1219 mm). shall be conducted upon the completion of—and before final
Exception: A side overhang is not required where full side approval of—installation of a ventilation system serving com-
panels or panels angled from the front lip of the hood to mercial cooking appliances. The test shall verify the rate of
exhaust airflow required by Section 4.2. The permit holder
the front of the appliance at cooking-surface height are
shall furnish the necessary test equipment and devices required
installed (see Figure 1).
to perform the tests.
4.3.2 The spaces between appliances, the backs of appli- 4.7.2 Type I Hood Capture and Containment Test. The
ances, and the spaces from the appliances to walls or end pan- permit holder shall verify the capture and containment perfor-
els shall be included in overall hood dimensions. In the case mance of Type I hoods. A field test shall be conducted with
of island hoods, appliance flues shall be included in the cook- all appliances under the hood at operating temperatures, all
ing surface dimensions. the hoods operating at design airflows, and with all sources of
4.3.3 Hoods shall be mounted above the cooking surface as replacement air operating at design airflows for the restau-
follows: rant. Capture and containment shall be verified visually by
--``,,,`,,`,`,,,,,```,,,``````-`-`,,`,,`,`,,`---
Type I Hoodsa
Extra-Heavy
Appliance Description Size Light Duty Medium Duty Heavy Duty Duty
Braising pan/tilting skillet, electric All •
Oven, baking, electric and gas All •
Oven, rotisserie, electric and gas All •
Oven, combination, electric and gas All •
Oven, convection, full-size, electric and gas All •
Oven, convection, half-size, electric and gas (protein cooking) All •
Oven, conveyor, electric All •
Oven, deck, electric and gas All •
Oven, duck, electric and gas All •
Oven, revolving rack, electric and gas All •
Oven, rapid cook, electric All •
Oven, roasting, electric and gas All •
Oven, rotisserie, electric and gas All •
Oven, stone hearth, gas All •
Range, cook-top, induction All •
Range, discrete element, electric (with or without oven) All •
Salamander, electric and gas All •
Braising pan/tilting skillet, gas All •
Broiler, chain conveyor, electric All •
Broiler, electric, underfired All •
Fryer, doughnut, electric and gas All •
Fryer, kettle, electric and gas All •
Fryer, open deep-fat, electric and gas All •
Fryer, pressure, electric and gas All •
Griddle, double-sided, electric and gas All •
Griddle, flat, electric and gas All •
Oven, conveyor, gas All •
Range, open burner, gas (with or without oven) All •
Range, hot top, electric and gas All •
Smoker, electric and gas All •
Broiler, chain conveyor, gas All •
Broiler, electric and gas, over-fired (upright) All •
Broiler, gas, underfired All •
Grill, plancha, electric and gas All •
Oven, tandoor, gas All •
Range, wok, gas and electric All •
Oven, stone hearth, wood-fired or wood for flavoring All •
Solid fuel cooking appliances combusting a solid fuel (such as All •
wood, charcoal, or coal) to provide all or part of the heat for the
cooking process b
a. Where recirculating systems or recirculating hoods are used, the additional heat and moisture loads generated by such appliances shall be accounted for in the sensible and latent
loads for the HVAC system.
b. Solid-fuel flavoring cooking appliances shall comply with Table 1 as if they do not combust solid fuel.
--``,,,`,,`,`,,,,
Type II Hoodsb
Appliance Description Size Hood Not Requireda Light Duty Medium Duty
Cabinet, holding, electric All •
Cabinet, proofing, electric All •
Cheese-melter, electric All •
Coffee maker, electric All •
Cooktop, induction, electric All •
Dishwasher, door-type rack, hot water sanitizing, heat recovery and vapor
reduction, electric All •
Dishwasher, door-type rack, chemical sanitizing, heat recovery and vapor
reduction, electric All •
Dishwasher, door-type dump and fill, hot water sanitizing, electric All •
Dishwasher, door-type dump and fill, chemical sanitizing, electric All •
Dishwasher, pot and pan, hot water sanitizing, heat recovery and vapor
reduction, electric All •
Dishwasher, powered sink, electric All •
Dishwasher, under-counter, chemical sanitizing, electric All •
Dishwasher, under-counter, electric All •
Dishwasher, undercounter, hot water sanitizing, heat recovery and vapor
reduction, electric All •
Drawer warmer, 2 drawer, electric All •
Egg cooker, electric All •
Espresso machine, electric All •
Grill, panini, electric All •
Hot dog cooker, electric All •
Hot plate, countertop, electric All •
Ovens, microwave, electric All •
Popcorn machine, electric All •
Rethermalizer, electric All •
Rice cooker, electric All •
Steam table, electric All •
Steamers, bun, electric All •
Steamer, compartment atmospheric, countertop, electric All •
Steamer, compartment pressurized, countertop, electric All •
Table, hot food, electric All •
Toaster, electric All •
--``,,,`,,`,`,,,,,```,,,``````-`-`,,`,,`,`,,`---
Type II Hoodsb
Appliance Description Size Hood Not Requireda Light Duty Medium Duty
Type of Hood End Overhang, in. (mm) Front Overhang, in. (mm) Rear Overhang, in. (mm)
observing smoke or steam produced by actual cooking opera- material, interior installation (including fire-rated enclosures
tion or by simulating cooking using devices such as smoke and the clearance between the duct and interior surface of the
candles or smoke puffers. Smoke bombs shall not be used. enclosures), exterior installation, and exhaust system termina-
Informative Note: Smoke bombs typically create new tion on the roof or at a wall, refer to NFPA 96 9, the Interna-
effluent from a point source and do not necessarily show tional Mechanical Code 10, or local codes.
whether the cooking effluent is being captured. Actual cook- 5.1.7 Ducts with field-applied insulation listed in accor-
ing at the normal production rate is the most reliable method dance with ASTM E 2336, Standard Test Methods for Fire
of generating smoke. Resistive Grease Duct Enclosure Systems 11, and factory-built
4.8 Hood Clearance to Combustibles ducts with integral insulation listed in accordance with UL
4.8.1 Type I hoods shall be installed with a minimum 18 in. 2221, Tests of Fire Resistive Grease Duct Enclosure
(457 mm) clearance to combustibles from any hood surface. Assemblies 12, are acceptable, where included in NFPA 96 9,
Exception: Type I hoods that are listed to reduced clear- the International Mechanical Code 10, or the Uniform
ances in accordance with Standard UL710 5 or Standard Mechanical Code 13 for use as an alternative to a duct and
UL 710B 3 shall be installed at a minimum clearance to fire-resistance-rated shaft enclosure around the duct.
combustibles in accordance with their listings. 5.2 Duct Leakage Testing
5. EXHAUST SYSTEMS 5.2.1 Prior to the use or concealment of any portion of a
grease duct system, a leakage test shall be performed to deter-
5.1 Duct Systems mine that all welded joints and seams are liquid tight. The
5.1.1 Ducts serving Type I hoods shall be constructed of leakage test shall consist of a light test, water pressure test, or
carbon steel of a minimum 16 gage thickness or stainless steel an approved equivalent test. The permit holder shall be
of a minimum 18 gage thickness. All seams, joints, and pene- responsible for providing the necessary equipment and for
trations shall have a liquid-tight continuous external or inter- performing the test.
nal weld. Internal welds shall be flush with the duct walls and
5.2.1.1 Light Test. The light test shall be performed by
accessible for inspection.
passing a lamp having a power rating of not less than 100 W
Exception: Factory-built ducts listed in accordance with through the entire section of ductwork to be tested. The lamp
UL 1978 8. shall be open so as to emit light equally in all directions per-
5.1.2 Ducts shall be constructed and installed so that grease pendicular to the duct walls. No light from the duct interior
cannot collect in any portion thereof, and ducts shall slope not shall be visible through any exterior surface.
less than one-fourth unit vertical in 12 units horizontal (2% 5.2.1.2 Water Test. The water test shall be performed by
slope) toward the hood or toward an approved grease reser- use of a pressure washer operating at a minimum of 1500 psi
voir. Where horizontal ducts exceed 75 ft (22.8 m) in length, (10.34 kPa), simulating cleaning operations. The water shall
the slope shall not be less than one unit vertical in 12 units be applied directly to all areas to be tested. No water applied
horizontal (8.3% slope).
to the duct interior shall be visible on any exterior surface in
Exception: Listed factory-built ducts constructed of a any volume during the test.
round cross section shall be permitted to be installed at
a reduced slope as allowed by their listing and the man- 5.3 Airflow Performance
ufacturer’s installation instructions. 5.3.1 The velocity in the duct shall be at least 500 fpm
5.1.3 Ducts shall not pass through firewalls unless enclosed (2.54 m/s).
in accordance with the applicable codes and standards. Informative Note: This standard does not limit the air-
5.1.4 Ducts shall lead to the exterior of the building. flow velocity by specifying a maximum velocity, but due to
typical spatial and cost constraints, general design duct veloc-
5.1.5 A separate grease duct system shall be provided for
ities between 1500 and 1800 fpm (7.62 and 9.14 m/s) are
each Type I hood. A separate grease duct system is not
often used when designing for maximum airflows. Duct
required where all of the following conditions are met:
velocities greater than 2500 fpm (12.70 m/s) can cause
a. All interconnected hoods are located within the same story. unwanted duct pressure and noise levels.
b. All interconnected hoods are located within the same 5.3.2 Lower exhaust airflow than that required for full-load
room or in adjoining rooms. cooking conditions is permitted during no-load cooking con-
c. Interconnecting ducts do not penetrate fire barriers. ditions, where engineered controls or listed multispeed or
d. The grease duct system does not serve solid fuel-fired variable-speed controls automatically operate the exhaust sys-
appliance(s). tem to maintain capture and removal of cooking effluents.
5.1.6 Ducts shall be installed without forming dips or traps 5.4 Fans
that might collect grease, except where unavoidable. In such 5.4.1 Fans shall be of sufficient capacity to provide the
situations, the duct section having a dip or trap shall be pro- required airflow against the system’s resistance. Expected air
vided with drain access for regular cleanout. temperatures, altitude, windage, and system effects shall be
Informative Note: For other duct construction and instal- taken into account when determining fan capacity. Fan air
lation details, such as welded duct connections, access open- performance shall be tested and certified according to AMCA
ings for inspection and maintenance, clearance to combustible Standard 210 14.
--``,,,`,,`,`,,,,,```,,,``````-`-`,,`,,`,`,,`---
Informative Note: Belt-drive fans and adjustable-drive 5.6.2 Exhaust airstreams for Type I hoods shall be located a
sheaves provide a means of adjusting the fan speed for final minimum of 40 in. (1016 mm) above the finished roof surface
system balancing. A variable-speed controller allows a and be directed away from roof and building surfaces.
broader range of speed adjustability. 5.6.3 Additional protection for roofing material at the
5.4.2 Exhaust fans (up-blast, in-line, or utility-set fans) exhaust discharge of a Type I hood shall be provided to pre-
serving Type I hoods shall be capable of handling hot, grease- vent material degradation or failure.
laden air and flare-up conditions. Fans shall be designed to 5.7 Operation and Maintenance
contain and properly drain grease removed from the air- 5.7.1 Appliance Interlock
stream. The fan housing or scroll that contains the grease
shall be fully welded so that it is liquid tight. The fan impeller 5.7.1.1 The exhaust fan serving a Type I hood shall have
shall be a self-cleaning design. automatic controls that will activate the fan when any appli-
ance that requires such Type I hood is turned on, or a means
Exception: Fans that are listed to UL 705, Standard for of interlock shall be provided that will prevent operation of
Power Ventilators 15, and UL 762, Outline of Investiga- such appliances when the exhaust fan is not turned on.
tion for Power Roof Ventilators for Restaurant Exhaust
5.7.1.2 Where one or more temperature or energy sensors
Applications 16.
are used to activate a Type I hood exhaust fan, the fan shall
5.4.3 Up-blast fans shall be hinged with tip-over restraints activate not more than 15-minutes after the first appliance
and have a flexible weatherproof electrical cable to permit served by that hood has been turned on. A method of interlock
inspection and cleaning. Utility-set exhaust fans shall be pro- between an exhaust hood system and appliances equipped
vided with access panels for inspection and cleaning. with standing pilot burners shall not cause the pilot burners to
be extinguished. A method of interlock between an exhaust
5.4.4 Access shall be provided for cleaning the fan wheel. hood system and cooking appliances shall not involve or
The access opening shall be a minimum of 3 × 5 in. (76 × depend on any component of a fire extinguishing system.
127 mm) or have a circular diameter of at least 4 in. (102
mm) on the curvature of the outer fan housing. Fan drive 5.7.2 The entire exhaust system shall be inspected at regu-
assemblies shall be separated from the airstream. Covers lar intervals for grease buildup by a properly trained, quali-
shall be provided with motor weather protection for outdoor fied, and certified company or person(s) acceptable to the
installation and belt guards for indoor applications. authority having jurisdiction.
5.7.2.1 The schedule of inspection for grease buildup in
5.4.5 The ductwork extending to up-blast fans shall extend the exhaust system and cleaning of the exhaust system shall
a minimum of 18 in. (457 mm) above the roof surface. comply with NFPA 96 9.
5.5 Other Equipment 5.7.2.2 Upon inspection, if the exhaust system is found to
5.5.1 Thermal recovery units, air pollution control devices, be contaminated with grease deposits, the contaminated por-
or other devices can be used in the exhaust systems when spe- tions of the exhaust system shall be thoroughly cleaned by a
cifically approved for such use except where prohibited. properly trained, qualified, and certified company or per-
Refer to Section 514.2 of the International Mechanical son(s) acceptable to the authority having jurisdiction.
Code 10, for prohibited applications. 5.7.3 Inspection and maintenance of thermal recovery
units, air pollution control devices, or other devices shall be
5.5.2 Clearance, installation, and fire-extinguishing system conducted by properly trained and qualified persons at a fre-
requirements shall comply with applicable codes and standards. quency specified in the manufacturer’s instructions or equip-
5.5.3 Pollution control units not equipped with electrostatic ment listing.
precipitators shall be listed in accordance with the applicable
requirements of UL710 5 and UL1978 8. Pollution control 6. REPLACEMENT AIR
units equipped with electrostatic precipitators shall be listed 6.1 Air Introduction
in accordance with UL86717 and the applicable requirements
6.1.1 The terminal velocity of air introduced from devices
of UL710 5 and UL1978 8.
in the kitchen shall not exceed 50 fpm (0.25 m/s) at the lowest
5.6 Exhaust Discharge edges of the hood.
Informative Notes:
5.6.1 Exhaust systems shall be designed to prevent re-
1. Using perforated ceiling or perimeter diffusers
entrainment into building intakes. Prevailing winds and veloc-
ities shall be considered when locating intake and exhaust generally results in a lower terminal velocity at the
openings. The minimum horizontal distance between dis- lower edge of the hood than directional ceiling
charge and intake shall be 10 ft (3 m). Where this horizontal diffusers.
distance is not achievable, the exhaust shall discharge a mini- 2. Best practice is to bring conditioned air into the
mum of 2 ft (0.6 m) above any outdoor air. Exhaust discharge kitchen away from the hood and distribute it
shall not impinge on overhangs, parapets, other equipment, or throughout the kitchen to improve worker produc-
higher parts of buildings. tivity and comfort as well as to lower hood exhaust
rates.
Informative Note: Refer to ASHRAE Handbook—
Fundamentals 18, Chapter 16, for airflow patterns around 6.1.2 Transfer air from dining or other areas that passes
buildings. through openings such as windows or walkways shall be
--``,,,`,,`,`,,,,,```,,,``````-`-`,,`,,`,`,,`---
sized for air velocities not to exceed 75 fpm (0.381 m/s) based shopping mall, the food-service facility shall be maintained
on the free area of the opening. Openings provided for trans- under a negative pressure with respect to outdoors and the
fer air shall remain open during system operation. adjacent spaces.
Informative Note: Such openings should be arranged to Exceptions:
avoid creating drafts on personnel. Consideration should be
1. Where the separation between the food service facil-
given to minimizing air velocity when openings are used as
ity and the adjacent interior room is sealed substan-
pass-through openings for prepared food.
tially airtight to prevent odor migration.
6.2 Air Balance 2. In shopping malls and other occupancies where a
6.2.1 Design plans for a facility with a commercial kitchen food-service facility is open to another tenancy or to
ventilation system shall include a table or diagram indicating the mall common area, the food-service facility shall
the design outdoor air balance (see Informative Annex A, be permitted to be under a negative pressure with
Section A1). The design outdoor air balance shall indicate all respect to the non-food-service occupancy.
exhaust and replacement air for the facility, plus the net exfil- 6.3.3 The pressure in any room in which a draft-hood
tration if applicable. The total replacement air airflow rate vented appliance, such as a gas water heater, is located shall
shall equal the total exhaust airflow rate plus the net exfiltra- be maintained not less than 0.02 in. of water (5.0 Pa) below
tion. It is permissible to supply replacement air to the kitchen outdoor ambient pressure.
space by using transfer air from areas other than the kitchen.
--``,,,`,,`,`,,,,,```,,,``````-`-`,,`,,`,`,,`---
Informative Note: Although individual replacement air 7. SYSTEM CONTROLS
sources are not required to be 100% outdoor air, sufficient
outdoor air must be introduced into the system to compensate 7.1 Operating Controls
for each exhaust and exfiltration component. For example, for 7.1.1 Replacement air systems shall be interlocked to
100 cfm (47 L/s) transfer air from room A to room B to qual- ensure operation upon activation of the exhaust system.
ify as replacement air, at least 100 cfm (47 L/s) outdoor air 7.1.2 Demand-Control Ventilation
must be provided to room A (e.g., as outdoor air to an envi- 7.1.2.1 The exhaust flow rate is permitted to be reduced
ronmental air system serving room A, infiltration to room A, during partial load cooking and when there is no cooking
or transfer air from another room). through the means of demand-control ventilation.
6.2.2 Operation of systems where airflows can vary 7.1.2.2 Exhaust rates shall maintain capture and contain-
(including but not limited to HVAC systems incorporating ment of appliance flue gases and cooking effluent during full-
variable air volume, systems with outdoor air economizer load, partial, or idle operating conditions.
control, or exhaust systems with variable airflow) shall be
controlled to comply with the requirements of this standard 7.1.2.3 During periods of reduced exhaust airflow, replace-
over the full range of anticipated airflows. Additional air bal- ment air shall be automatically controlled to maintain the build-
ance diagrams or tables shall be provided as necessary to ing pressure differentials in accordance with Section 6.3.
indicate compliance over the full range of anticipated airflow. Informative Note: Replacement air units may have mini-
mum airflow requirements for safe or effective operation of
6.2.3 Where the design air balance relies on transfer air
heating and/or cooling/dehumidification functions. Demand-
from a source beyond the facility’s control (e.g., air drawn
control ventilation systems’ minimum airflow settings must
into an individual tenant’s facility from the common areas of
not be set lower than the replacement air systems minimum
a shopping mall), this source shall be identified.
operating airflow.
6.3 Pressure Differentials 7.1.2.4 Demand-control ventilation systems shall be part
6.3.1 The commercial kitchen ventilation system shall be of a listed hood, shall be listed for the purpose, or shall be
designed to establish pressure differentials to control odor engineered.
migration and to control dust, dirt, and insects in accordance
with the criteria in the following subsections. 8. ADMINISTRATION AND COMPLIANCE
6.3.1.1 The kitchen of a food-service facility shall be 8.1 Equivalency. Nothing in this standard is intended to pre-
maintained under a negative pressure with respect to dining vent the use of systems, methods, or devices of equivalent or
areas and adjacent nonfood areas. The maximum negative superior quality, strength, fire resistance, effectiveness, dura-
pressure shall not exceed 0.02 in. of water (5.0 Pa). bility, and safety over those prescribed by this standard.
6.3.1.2 A freestanding food-service facility (i.e., a food- 8.1.1 Technical documentation shall be submitted to the
service facility that entirely occupies a single building) shall be authority having jurisdiction to demonstrate equivalency.
maintained under a positive pressure with respect to outdoors. 8.1.2 The system, method, or device shall be approved for
Exception: Where migration of food odors to adjacent the intended purpose.
interior rooms within the same tenancy would not be
objectionable. Display cooking under a hood located 9. REFERENCES
in the dining area is not considered a kitchen. 1. Fisher, D., R. Swierczyna, and P. Sobiski. 2008. Revised
6.3.2 Where a food-service facility shares a wall with an Heat Gain and Capture and Containment Exhaust
adjacent non-food-service facility, such as a retail center or a Rates from Typical Commercial Cooking Appliances.
Final Report Research Project 1362 (RP-1362). tions. Quincy, MA: National Fire Protection Associa-
ASHRAE, Atlanta, GA. tion.
2. UL. 2010. UL 197, Standard for Commercial Electric 10. ICC. 2012. International Mechanical Code. Washington,
Cooking Appliances, Tenth Edition. Northbrook, IL: D.C.: International Code Council.
Underwriters Laboratories, Inc. 11. ASTM. 2014. ASTM E2336, Standard Test Method for
3. UL. 2011. UL 710B, Standard for Recirculating Systems, Fire Resistive Grease Duct Enclosure Systems. West
Second Edition. Northbrook, IL: Underwriters Labo- Conshohocken, PA: ASTM International.
ratories, Inc. 12. UL. 2010. UL 2221, Tests of Fire Resistive Grease Duct
4. UL. 2010. UL 1046, Grease Filters for Exhaust Ducts, Enclosure Assemblies, Second Edition. Northbrook,
Fourth Edition. Northbrook, IL: Underwriters Labora- IL: Underwriters Laboratories Inc.
tories, Inc. 13. IAPMO. 2012. Uniform Mechanical Code. Ontario, CA:
International Association of Plumbing and Mechanical
5. UL. 2012. UL 710, Exhaust Hoods for Commercial
Officials.
Cooking Equipment, Sixth Edition. Northbrook, IL:
14. ASHRAE. 2007. ANSI/ASHRAE 51 (ANSI/AMCA
Underwriters Laboratories, Inc.
210), Laboratory Methods of Testing Fans for Aerody-
6. UL. 2006. UL 710C, Ultraviolet Radiation Systems for namic Performance Rating. Atlanta: ASHRAE
Use in the Ventilation Control of Commercial Cooking (Arlington Heights, IL: Air Movement and Control
Operations, Issue Number 3. Northbrook, IL: Under- Association).
writers Laboratories, Inc. 15. UL. 1994. UL 705, Power Ventilators. Northbrook, IL:
7. ASTM. 2011. ASTM F2519-05 (2011), Standard Test Underwriters Laboratories, Inc.
Method for Grease Particle Capture Efficiency of 16. UL. 2013. UL 762, Outline of Investigation for Power
Commercial Kitchen Filters and Extractors. West Roof Ventilators for Restaurant Exhaust Applications.
Conshohocken, PAASTM International. Northbrook, IL: Underwriters Laboratories, Inc.
8. UL. 2010. UL 1978, Grease Ducts. Northbrook, IL: 17. UL. 2011. UL 867, Electrostatic Air Cleaners, Fifth Edi-
Underwriters Laboratories, Inc. tion. Northbrook, IL: Underwriters Laboratories Inc.
9. NFPA. 2014. NFPA 96, Standard for Ventilation Control 18. ASHRAE. 2013. ASHRAE Handbook—Fundamentals.
and Fire Protection of Commercial Cooking Opera- Atlanta: ASHRAE.
--``,,,`,,`,`,,,,,```,,,``````-`-`,,`,,`,`,,`---
(This annex is not part of this standard. It is merely infor- hood or through ceiling diffusers. Additionally, the kitchen
mative and does not contain requirements necessary for may have an HVAC system to condition part of the supply air.
conformance to the standard. It has not been processed Table A-1 shows an air balance for a conventional system,
according to the ANSI requirements for a standard and and Figure A-1 depicts the system graphically.
may contain material that has not been subject to public
review or a consensus process. Unresolved objectors on A2. BEST PRACTICE AIR BALANCING
informative material are not offered the right to appeal at
ASHRAE or ANSI.) Best practice has changed over the years from using makeup
air systems in the kitchen to completely conditioning both the
INFORMATIVE ANNEX A dining and kitchen spaces. For conditioning the kitchen space,
EXAMPLES OF AIR BALANCING either a traditional rooftop unit or a 100% outdoor unit may
be used. This approach provides many benefits, including
This annex provides examples of the air balancing required in
increased occupant comfort and reduced moisture and humid-
Section 6.2.1. The first example shows what is used in a con-
ity throughout the facility, which can be a cause of mold and
ventional restaurant. The second example shows a best-prac-
mildew growth, although energy use may increase. The air
tice design that eliminates the makeup air altogether in the
balance is presented in Table A-2 and is depicted graphically
restaurant. This standard also addresses the need for appropri-
in Figure A-2.
ate pressure differentials in a commercial kitchen, whether it
is a conventional design or a best-practices design.
A3. PRESSURE DIFFERENTIALS
A1. CONVENTIONAL AIR BALANCING
For both the conventional system and best-practice systems, it
In a conventional restaurant, air may be supplied to both the is important that the kitchen be designed to have a slightly
kitchen and dining spaces through many means. Makeup air negative pressure and that the overall building be designed to
has typically been introduced into the kitchen space at the be slightly positive in pressure.
--``,,,`,,`,`,,,,,```,,,``````
--``,,,`,,`,`,,,,,```,,,``````-`-`,,`,,`,`,,`---
TOTAL 3400 3200
Net = 3400 – 3200 = 200 exfiltration
The units for this table can be either cfm or L/s because the airflow in and airflow out may be expressed in either units as long as they are consistent.
--``,,,`,,`,`,,,,,```,,,``````-`-`,,`,,`,`,,`---
(This annex is not part of this standard. It is merely infor- QK = convective heat from appliance, W
mative and does not contain requirements necessary for
conformance to the standard. It has not been processed z = distance between appliance and hood, ft (m)
according to the ANSI requirements for a standard and dh = hydraulic diameter of the appliance surface, ft (m)
may contain material that has not been subject to public (See Equation B-3)
review or a consensus process. Unresolved objectors on
informative material are not offered the right to appeal at r = reduction factor for hood location
ASHRAE or ANSI.)
= simultaneous factor, set to 1
INFORMATIVE ANNEX B The hydraulic diameter calculation is shown in Equation
ALTERNATIVE AIRFLOW CALCULATION METHOD B-3 and takes the length and width of the appliance surface
This annex presents an alternate airflow calculation method to into account.
determine the airflows for specific appliances. This is a modi-
fied version of VDI Standard 2052 (see Informative Annex E, 2LB
d h = ---------------------- (B-3)
“Bibliography”), which is a European standard for calculating L+B
exhaust airflow for commercial kitchen hoods based on the
process loads they must handle. The modifications include where
adding a hood effectiveness (Eh). Because this standard is
L = appliance length, ft (m)
looking at a worst-case scenario in terms of capture and con-
tainment of effluent from appliances, the simultaneous factor B = appliance width, ft (m)
and the fraction of input energy to nameplate energy have
been adjusted. The convective heat from the appliances is calculated
using Equation B-4. The values of Qs can be obtained from
B1. EXHAUST AIRFLOW CALCULATION VDI Standard 2052.
The overall kitchen exhaust (shown in Equation B-1) is calcu- Q K = E r P Qs (B-4)
lated by summing the thermal plumes from each appliance
underneath the hood. This value is then multiplied by a flush- where
out factor that accounts for how the air is introduced (set to
1.35 for ceiling diffusers) and divided by hood effectiveness. Er = fraction of input energy to nameplate rating
For the purpose of unlisted canopy-style hoods, this value is (assumed to be 50% in VDI Standard 2052), set to
set to 0.7. For unlisted backshelf-style hoods with a setback, a 1.0
hood effectiveness should be set to 0.5 as shown in Table B-1.
An approved method for determining hood effectiveness for P = input power of the appliance, kW
listed hoods has not yet been developed. Qs = fraction of input energy converted to direct
(convective) heat energy, W
1
V e = V th a ------ + V h (B-1)
E h B3. AIRFLOW CALCULATION EXAMPLE
where This example will calculate the exhaust airflow for a hood
--``,,,`,,`,`,,,,,```,,,``````-`-`,,`,,`,`,,`---
Ve = ventilation exhaust, m3/h that has two appliances under a generic canopy exhaust hood
located at a wall that has a hanging height of 1.98 m above
Vth = thermal plume, m3/h
finished floor. The appliances specifications are shown in
a = flushout factor, set to 1.35 Table B-3.
Eh = hood effectiveness, set to 0.7 The hydraulic diameter for each appliance is calculated
Vh = internal (short-circuit) makeup air using Equation B-3 and the convective energy is calculated
using Equation B-4, and the results are shown in Table B-4:
B2. THERMAL PLUME CALCULATION The thermal plume airflows are then calculated for each
appliance using Equation B-2, and the results are shown in
The thermal plume from appliances is calculated by Equation
Table B-5.
B-2 and takes into account the convection heat rising from the
appliance, the surface area of the appliance, and the height The final step is to calculate the hood exhaust airflows
difference between the appliance surface and bottom of the using Equation B-1 with a hood effectiveness of 0.7 and a
hood. The reduction factor also takes into account whether flushout factor of 1.35. The resulting hood exhaust airflow is
the hood is a wall or island application (see Table B-2). 1842 cfm (3130 m3/h). The airflows come out to approxi-
mately 451 L/s/m (291 cfm/ft), which is close to the current
V th = k Q K1 3 z + 1.7 d h 5 3 r (B-2) IMC value of 465 L/s/m (300 cfm/ft) for wall canopy hoods.
If the bottom of the hood were installed at 6.98 ft (2.13 m)
where above the finished floor, note that the resulting hood airflow is
k = 18 m4/3W–1/3h–1, constant 2037 cfm (3461 m3/h) or 322 cfm/ft (498.7 L/s/m).
Canopy 0.7
Backshelf 0.5
TABLE B-4 Hydraulic Diameter for Each Appliance Calculated using Equation B-3
Appliance dh QK, W
TABLE B-5 Thermal Plume Airflows Calculated for Each Appliance Using Equation B-2
Griddle 1167
TOTAL 1623
--``,,,`,,`,`,,,,,```,,,``````-`-`,,`,,`,`,,`---
I-P Units
SI Units
P A1 = 0.000157 V 1 p 1
V DCKV 3
P F 1 = P A1 f P M DCKV = P M Design -----------------
-
V Design
P M 1 = 1 + DL P F 1 E M E D
P M DCKV = P M Design – P M DCKV t
P A2 = 0.000157 V 2 p 2
The HVAC energy savings need to take into account the --``,,,`,,`,`,,,,,```,,,``````-`-`,,`,,`,`,,`---
P F 2 = P A2 f local weather for the specific site being analyzed when com-
paring listed and unlisted exhaust hoods as well as DCKV
P M 2 = 1 + DL P F 2 E M E D systems. Several public domain programs are available to cal-
culate the energy from HVAC systems. Commercial software
P M = 0.746 P M 1 – P M 2 t is also available for performing energy simulations.
Power required at input to motor, DCKV average exhaust rate PM, DCKV hp kW
Average reduced exhaust rate with DCKV system installed VDCKV cfm m3/s
Energy savings with DCKV system installed PM, DCKV kWh kWh
Time of operation t h h
--``,,,`,,`,`,,,,,```,,,``````-`-
(This annex is not part of this standard. It is merely infor- (add standoffs for gas and/or water piping if required) to the
mative and does not contain requirements necessary for minimum front overhang as shown in Table D-2. After the
conformance to the standard. It has not been processed hood size is determined, the exhaust airflow needs to be cal-
according to the ANSI requirements for a standard and culated as shown in Step 4.
may contain material that has not been subject to public
Step 4: Determine the Minimum Exhaust Airflow
review or a consensus process. Unresolved objectors on
informative material are not offered the right to appeal at The minimum exhaust airflows are a function of both the
ASHRAE or ANSI.) hood type (which has already been defined as a wall canopy
hood) and the minimum duty levels for the appliances operat-
INFORMATIVE ANNEX D ing underneath the hood. From Table 1 of this standard, the
USING ASHRAE STANDARD 154 TO DETERMINE duty level for the convection oven is light-duty, while for the
HOOD OVERHANGS AND EXHAUST AIRFLOWS braising pan and gas range it is medium-duty. Therefore, the
This annex provides an example of how to use ASHRAE maximum duty-level for the appliances underneath the hood
Standard 154 to determine the overhangs for the hoods. This is medium-duty. The airflow for this appliance configuration
example also shows how to calculate the heat gain to the would need to be specified by manufacturers.
space from unhooded appliances. The steps involved include Another item that is needed for design engineers to size the
specifying the appliance layout underneath the hood, specify- HVAC system is an estimation of how much load is being added
ing the hood length and depth, and calculating the exhaust air- to the kitchen space from the hooded and unhooded appliances.
flow required for the hood and appliances. Steps 5 and 6 show how to perform these calculations.
D1. APPLIANCES UNDERNEATH THE HOOD Step 5: Determine the Heat Gain to Space from
Hooded Equipment
Assume that the cooking operation has the following appli-
If it is desired, the heat gain to space from the equipment
ances.
underneath the hood can be estimated. ASHRAE Handbook—
a. Electric convection oven: 38 in. (965 mm) L × 41 in. Fundamentals, Chapter 31, Table 5, lists heat gain values for
(1041 mm) D × 57 in. (1448 mm) H with a nameplate rat- several common appliances. Table D-3 shows the appliance
ing of 10.4 kW name, its description in Table 5, and the heat gain to space for
b. Electric braising pan: 30 gal (114 L) capacity, which is 38 that appliance. Note that in Table 5 the heat gain is split into
in. (965 mm) L × 42 in. (1067 mm) D × 39 in. (991 mm) three separate components: sensible-radiant heat gain, sensi-
H, with a nameplate rating of 12.0 kW ble-convective heat gain, and sensible-latent heat gain. The
c. Stainless preparation table: 32 in. (813 mm) L × 26 in. sensible-radiant heat gain is the radiation from the appliance
(660 mm) D × 32 in. (813 mm) H surface to the room. The sensible-convective heat gain is the
d. 4-burner gas range: 34 in. (864 mm) L × 38 in. (965 mm) dry heat that makes up the thermal plume from the appliance
D × 36 in. (914 mm) H that is captured by the hood, and the latent-convective heat
gain is the moisture portion of the thermal plenum captured
D2. UNHOODED APPLIANCE DESCRIPTIONS by the hood. For hooded appliances, it is assumed that all of
the convective plume is captured and only the sensible-radiant
a. Three (3) coffee makers: Nameplate rating of 1140 W
heat gain impacts the heat load to the space.
b. Conveyor-rack dishwasher: 24 in. (610 mm) L × 25 in.
For the gas range, the heat gain should be adjusted, as the
(625 mm) D × 34 in. (864 mm) H with a nameplate rating
value in ASHRAE Handbook—Fundamentals only accounts
of 7.8 kW
for three burners on. If the heat gain is prorated to account for
To determine the overall hood size, the minimum length four burners on (e.g., multiply the heat gain by a factor of 4/3),
and width need to be calculated as shown in Steps 1 through 3 the resulting heat gain to space from the four-burner range
below. would be approximately 9500 Btu/h. Adding the heat gain
from the appliances together, the resulting heat gain to space is
Step 1: Determine Minimum End and Front Overhangs
estimated to be 11,000 Btu/h.
Table 3 of this standard contains the minimum side and front
hood overhangs based on the style of hood used over the appli- Step 6: Determine the Heat Gain to Space from
ances. For this example, we will select a wall canopy hood. Unhooded Equipment
From Table 3, the minimum side overhangs are 6 in. (152 mm),
For the unhooded appliances, all of the heat generated by the
and the minimum front overhang is 12 in. (305 mm).
appliance is added to the space load. It should be noted from
Step 2: Determine Minimum Hood Length Table 2 of this standard that a hood is recommended for use
To determine the minimum overall hood length, the length (or over a rack conveyor dishwasher; however, the user can be
width) of the individual appliances underneath the hood are exempted from having a hood if the heat load is accounted for
added together along with the hood overhang on each end of and managed by the building HVAC system. From ASHRAE
the hood as shown in Table D-1. Handbook—Fundamentals, Chapter 31, Tables 5A and 5E,
the sensible-radiant, sensible-convective, and latent-convec-
Step 3: Determine the Overall Hood Depth tive heat gains are added together to get the total heat gain to
To determine the minimum overall hood depth, add the maxi- space. Table D-4 shows the lookup values from Tables 5A
mum appliance depth for the equipment underneath the hood and 5E for the unhooded appliances in this example.
--``,,,`,,`,`,,,,,```,,,``````-`-`,,`,,`,`,,`---
--``,,,`,,`,`,,,,,```,,,``````-`-`,,`,,`,`,,`---
Right End overhang 6 (152)
TOTAL 54 (1372)
Four-burner gas range Rangetop: 3 burners on/oven off 7100 (2081) 9500 (2784)
3 Coffee makers Coffee brewer 200 (59) 300 (88) 700 (205) 1200 (352)
Rack conveyor Dishwasher 0 (0) 4750 (1392) 16,970 (4974) 21,720 (6336)
dishwasher (conveyor type,
hot-water
sanitizing,
standby)
(This annex is not part of this standard. It is merely infor- Ventilation/Appliance Systems. West Conshohocken, PA:
mative and does not contain requirements necessary for ASTM International.
conformance to the standard. It has not been processed ASTM. 2012. ASTM F1704-12, Standard Test Method for
according to the ANSI requirements for a standard and Capture and Containment Performance of Commercial
may contain material that has not been subject to public Kitchen Exhaust Ventilation Systems. West Consho-
review or a consensus process. Unresolved objectors on hocken, PA: ASTM International.
informative material are not offered the right to appeal at CEC. 2002. PIER Report, Makeup Air Effect On Commercial
ASHRAE or ANSI.) Kitchen Exhaust System Performance, Publication P500-
03-007F. Sacramento, CA: California Energy Commission.
INFORMATIVE ANNEX E EERE. 2010. Energy Plus, Version 6.0.0, Energy Efficiency
INFORMATIVE BIBLIOGRAPHY and Renewable Energy. Germantown, MD: U.S. Depart-
ment of Energy.
ASHRAE. 2013. ASHRAE Handbook—Fundamentals.
LBNL. 1993. DOE-2, Version 2.1E. Berkeley, CA: Lawrence
Atlanta: ASHRAE.
Berkeley National Laboratory.
ASHRAE. 2015. ASHRAE Handbook—HVAC Applications. NFPA. 2013. NFPA17A-2013, Standard for Wet Chemical
Atlanta: ASHRAE. Extinguishing Systems. Quincy, MA: National Fire Pro-
ASHRAE. 2016. ASHRAE Handbook—HVAC Systems and tection Association.
Equipment. Atlanta: ASHRAE. Trane. 2010. Trace 700. Piscataway, NJ: Trane.
ASTM. 2009. ASTM F2474-09, Standard Test Method for VDI. 2006. VDI Standard 2052, Ventilation Equipment for
Heat Gain to Space Performance of Commercial Kitchen Kitchens. Duesseldorf: Verein Deutscher Ingenieure.
--``,,,`,,`,`,,,,,```,,,``````-`-`,,`,,`,`,,`---
--``,,,`,,`,`,,,,,```,,,``````-`-`,,`,,`,`,,`---
© ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution,
or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.
NOTICE
This standard is maintained under continuous maintenance procedures by a Standing Standard Project Committee (SSPC) for
which the Standards Committee has established a documented program for regular publication of addenda or revisions, includ-
ing procedures for timely, documented, consensus action on requests for change to any part of the standard. SSPC consider-
ation will be given to proposed changes within 13 months of receipt by the Senior Manager of Standards (SMOS).
Proposed changes must be submitted to the SMOS in the latest published format available from the SMOS. However, the
SMOS may accept proposed changes in an earlier published format if the SM`OS concludes that the differences are immaterial
to the proposed change submittal. If the SMOS concludes that a current form must be utilized, the proposer may be given up to
20 additional days to resubmit the proposed changes in the current format.
An electronic version of each change, which must comply with the instructions in the Notice and the Form, is the preferred
form of submittal to ASHRAE Headquarters at the address shown below. The electronic format facilitates both paper-based
and computer-based processing. Submittal in paper form is acceptable. The following instructions apply to change proposals
submitted in electronic form.
Use the appropriate file format for your word processor and save the file in either a recent version of Microsoft Word (pre-
ferred) or another commonly used word-processing program. Please save each change proposal file with a different name (for
example, “prop01.doc,” “prop02.doc,” etc.). If supplemental background documents to support changes submitted are
included, it is preferred that they also be in electronic form as word-processed or scanned documents.
For files submitted attached to an e-mail, ASHRAE will accept an electronic signature (as a picture; *.tif, or *.wpg) on the
change submittal form as equivalent to the signature required on the change submittal form to convey non-
exclusive copyright.
The form and instructions for electronic submittal may be obtained from the Standards section of ASHRAE’s Home
Page, www.ashrae.org, or by contacting a Standards Secretary via phone (404-636-8400), fax (404-321-5478), e-mail
([email protected]), or mail (1791 Tullie Circle, NE, Atlanta, GA 30329-2305).
--``,,,`,,`,`,,,,,```,,,``````-`-`,,`,,`,`,,`---
© ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution,
or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.
NOTE: Use a separate form for each comment. Submittals (Microsoft Word preferred) may be attached to e-mail (preferred),
or submitted in paper by mail or fax to ASHRAE, Senior Manager of Standards, 1791 Tullie Circle, NE, Atlanta, GA 30329-
2305. E-mail: [email protected]. Fax: +1-404-321-5478.
1. Submitter:
Affiliation:
I hereby grant ASHRAE the non-exclusive royalty rights, including non-exclusive rights in copyright, in my proposals. I
understand that I acquire no rights in publication of the standard in which my proposals in this or other analogous form is used.
I hereby attest that I have the authority and am empowered to grant this copyright release.
5. Proposed change:
7. Will the proposed change increase the cost of engineering or construction? If yes, provide a brief explanation as
to why the increase is justified.
Rev. 1-7-2013
© ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution,
or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.
POLICY STATEMENT DEFINING ASHRAE’S CONCERN
FOR THE ENVIRONMENTAL IMPACT OF ITS ACTIVITIES
ASHRAE is concerned with the impact of its members’ activities on both the indoor and outdoor environment.
ASHRAE’s members will strive to minimize any possible deleterious effect on the indoor and outdoor environment of
the systems and components in their responsibility while maximizing the beneficial effects these systems provide,
consistent with accepted Standards and the practical state of the art.
ASHRAE’s short-range goal is to ensure that the systems and components within its scope do not impact the
indoor and outdoor environment to a greater extent than specified by the Standards and Guidelines as established by
itself and other responsible bodies.
As an ongoing goal, ASHRAE will, through its Standards Committee and extensive Technical Committee structure,
continue to generate up-to-date Standards and Guidelines where appropriate and adopt, recommend, and promote
those new and revised Standards developed by other responsible organizations.
Through its Handbook, appropriate chapters will contain up-to-date Standards and design considerations as the
material is systematically revised.
ASHRAE will take the lead with respect to dissemination of environmental information of its primary interest and
will seek out and disseminate information from other responsible organizations that is pertinent, as guides to updating
Standards and Guidelines.
The effects of the design and selection of equipment and systems will be considered within the scope of the
--``,,,`,,`,`,,,,,```,,,``````-`-`,,`,,`,`,,`---
system’s intended use and expected misuse. The disposal of hazardous materials, if any, will also be considered.
ASHRAE’s primary concern for environmental impact will be at the site where equipment within ASHRAE’s scope
operates. However, energy source selection and the possible environmental impact due to the energy source and
energy transportation will be considered where possible. Recommendations concerning energy source selection
should be made by its members.
ASHRAE · 1791 Tullie Circle NE · Atlanta, GA 30329 · www.ashrae.org
About ASHRAE
ASHRAE, founded in 1894, is a global society advancing human well-being through sustainable technology for the
built environment. The Society and its members focus on building systems, energy efficiency, indoor air quality,
refrigeration, and sustainability. Through research, Standards writing, publishing, certification and continuing
education, ASHRAE shapes tomorrow’s built environment today.
To stay current with this and other ASHRAE Standards and Guidelines, visit www.ashrae.org/standards.
To ensure that you have all of the approved addenda, errata, and interpretations for this
Standard, visit www.ashrae.org/standards to download them free of charge.
Addenda, errata, and interpretations for ASHRAE Standards and Guidelines are no
longer distributed with copies of the Standards and Guidelines. ASHRAE provides
these addenda, errata, and interpretations only in electronic form to promote
more sustainable use of resources.