PMJ002 0073
PMJ002 0073
PMJ002 0073
Purchaser review and comments shall not be assumed to indicate either responsibility or liability for
accuracy and completeness of this document or to alter any contractual terms and conditions.
Item Numbers
J-XM-080101 & J-XM-080201
Purchasers Disposition
Signature
CB1/2
/ X
\ x
X
NC
SUPPLI
ER
G1 G2
I
N.E.R. ; N.E.R.
750 AMPS 750 AMPS
! 10 SECS 10SECS
I 7,7 OHMS 7,7 OHMS
V _ _
N.E.R NEUTRAL
EARTHING
1 REMARKS:
2 1) THE REGULATION CAPABILITY OF THE MAIN A.C. GENERATION AND AVR SYSTEM UNDER STEADY STATE AND
3 TRANSIENT CONDITIONS SHALL BE CHOSEN FROM VOLTAGE REGULATION GRADES 2.13 (VR2.13), 2.23 (VR2.23), 2.33 '
4 (VR2.33) OR 3.11 (VR3.11) AS DEFINED IN BS 4999 PART 140. TRANSIENT PERFORMANCE IS DEFINED WITH RATED KVA
5 AT 0.8 POWER FACTOR REJECTED. THE LOWEST TOLERABLE REGULATION GRADE SHALL BE SELECTED TO OPTOMISE
6 EQUIPMENT COSTS AND FAULT LEVELS. SUPPLIER TO ADVISE FREQUENCY EXCURSIONS.
7
8
9
10
11
12
13
14
15
16