53 - SOP For Cable Laying Termination in Switchyard
53 - SOP For Cable Laying Termination in Switchyard
53 - SOP For Cable Laying Termination in Switchyard
: RP-PRJ(SOL)-SOP-53
SOP for CABLE LAYING, GLANDING & Ver no.: 1.1
TERMINATION IN Switchyard Eff. Dt.:01-03-2023
Approval Date: 03-03-2023
SOP
For
REVISION HISTORY
PURPOSE- To Ensure that Cable Laying, Glanding & Termination Work in Switchyard will be executed safely
in accordance with the approved drawings and technical specification and that all quality /control activities
are conducted in systematic manner, works to be inspected and conformance is verified and documented.
SCOPE: Excavation, Material Lifting, Cable Pulling, Testing, Lugs Crimping, Cable Glanding, Cable
Termination, Heat shrinkable sleeves placing, Ferruling, cable tagging, Torquing/Marking etc.
RESPONSIBILITY: Project Manager/Site In-Charge, Switchyard Section In-Charge & AC Contractors
Reference Document:
Site EHS Plan,
Field Quality Plan,
Approved Drawing,
Technical Specification
Doc.No.: RP-PRJ(SOL)-SOP-53
SOP for CABLE LAYING, GLANDING & Ver no.: 1.1
TERMINATION IN Switchyard Eff. Dt.:01-03-2023
Approval Date: 03-03-2023
3) Cable Trench
Excavator For Excavation and backfilling of cable
trench
4) Measuring
Tape For measurement purpose
10) Cable Lifting For Lifting of cable drum and smooth laying
Jack with Shaft of cable without damage.
11) Cable Roller For the free movement of the cable without
damage
• Cable Drum of required length and size according to cable schedule shall be shifted
to the location with the help of Farana
• Cable Drum shall be lifted to the required height to get clearance from the ground
level while rolling with the help of jocks
• Packing of drum shall be remove and care shall be taken to avoid the cable damage
• Cable drum shall be tested for its IR values and continuity with the help of megger
• Drum shall be rolled in the direction which is mentioned on the drum
• Cable should not be dragged on rough surface and rocky area
• During cutting of the length required (with reference to cable schedule) one-meter
extra length shall be kept.
Cable must be covered with the end cap from both the ends & should kept at
certain height.
• After completion of the laying and cutting, Cable identification tags shall be
provided at both the ends and at turnings
• Clamping at required intervals shall be provided.
Glanding
• Required quantum and diameter of holes shall be made on the Gland plate of each
panels
• Gland shall be fixed to the cable with the help of cable armoring and gland plate of the
panels
• Core end Insulation of required length shall be removed which can fit to lug length
• Crimping shall be done minimum in two stages and sleeves shall be provided.
• Fix the lugs to the contact terminals firmly with the help of Washers, nut& bolts.
Doc.No.: RP-PRJ(SOL)-SOP-53
SOP for CABLE LAYING, GLANDING & Ver no.: 1.1
TERMINATION IN Switchyard Eff. Dt.:01-03-2023
Approval Date: 03-03-2023
Notes:
• All the Equipment’s must be calibrated by NABL approved lab, calibration certificate must
be submitted before starting of work
• Cable bending radius should be minimum 15D (IS:1255 to be refer for detailing)
• All the spare holes should be closed with cable-grommet/ Rubber Patch
• All the joints should be sealed with silicon only, use of putty and POP is not allowed.
• Size of fasteners should be appropriate as at least 5mm bolt projection must be available
outside of nut.
• Torque marking by permanent marker should be done for each fastener.
• Cable should be kept straight between termination point and gland below the gland as well
to eliminate chances of stress on termination. Sleeves shrinking should be done carefully,
it should not be burnt.
• Sleeves should be used as per standard color coding i.e., Red & Black for DC cable and
Red, Yellow & Blue for AC.
• Armor earthing should be done at one end of cable.
• Min. gap between power and control/communication cable should be maintained.
• SS / Metal cable tie should be used for dressing of cable only.
Doc.No.: RP-PRJ(SOL)-SOP-53
SOP for CABLE LAYING, GLANDING & Ver no.: 1.1
TERMINATION IN Switchyard Eff. Dt.:01-03-2023
Approval Date: 03-03-2023
• Tre-foil clamp with extra soft cushion must be used for AC single core cable.
• Only laser embossed aluminum cable tags should be used for identification, use of ferules
not allowed.
• Spare or leftover cable in the drum should be sealed with packing to avoid moisture entry.
• Required gap between cables must be provided.
• All the termination must be neat and clean.
• Any cable should not be passed through sharp edges.
• All the dressing of cable should be well supported and secured.
• All the metal parts must be free from rust
2. Environmental All workers shall educate on good environmental management practices and
well-disciplined to environment. The garbage bin shall be provided at the working area and
Supervisor shall ensure its must be collected regularly and disposed-off at the approved dump
site. Safety team shall ensure that no open burning of construction or domestic wastes is
practiced.
All workers shall ensure that all tools and equipment machinery are in good condition to avoid
any oil leakage that could harm to environment