LT PN GTP - BD

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 6

GAURANTEED TECHNICAL PARTICULARS OF LT PANEL

1 PANELS CONSTRUCTION FEATURES


Name of Panel Manufacturer
Country of Origin
Reference Standard (IEC)
System Voltage/Frequency/No. of phases
Designed for ambient temperature

The max. Temp. in any part of the equipment at specified rating shall not exceed

Temp. rise of busbar over 50 deg.C


Form of the Separation for panels (Main PCC & Other MCC)
Cable Entry
Degree of Protection for Inner Enclosure
Type of PANEL
Minimum Thickness of CRCA MS Sheet
Colour Shade
Thickness of Paint Shade (in microns)
Back doors of the panels shall be double door leaf type where the panels have
more than 400 mm width.
Panels Earthing
Use of Bakelite/Hylam is not acceptable. vendor to Confirm
Internal Wiring
Panel Type
Minimum Thickness of CRCA MS Sheet
Colour Shade
Thickness of Paint Shade (in microns)
2 MAIN LT PANEL
2.1 Transformer Incomer (2 Nos.)
Switchgear Rating/No of Poles
EDO/MDO Breaker
Short Circuit current rating withstand capacity for 1 sec.(ICS) in kA
Short Circuit current rating withstand capacity for 1 sec.(ICU) in kA
Spring Return Switch
Make

Model No of ACB

Model no of microprocessor based with adjustable O/L, S/C & inbuilt earth Fault
Release
Communication Facility Available or not
(E) Electrical interlock shall prevent the closing
of an incomer if its adjoining outgoing feeder is being
fed from another incomer through the bus-coupler.
The electrical interlocks should prevent the closing of two
incomer breakers and the connecting bus-coupler
500VA,433V/433 V,Delta/Star Trafo
32A TP MPCB (To Control Ckt)
32A TP MPCB (U/V, O/V,P/S,PL Protection relay)
32A TP MPCB (R, Y,B)
16A DP MCB ( 1 Nos.)
16A 4P MCB (3 Nos.)
250A,4P, MCCB for SPD
2.3 Meters
Energy Analyser
Make
Model No
Accuracy Class
Communication Port
IOT BASED MFM Required for ENERGY AUDIT MFG to Confirm
2.4 BUS-COUPLER
Switchgear Rating/No of Poles
EDO/MDO Breaker
Short Circuit current rating withstand capacity for 1 sec.(ICS) in kA
Short Circuit current rating withstand capacity for 1 sec.(ICU) in kA
Spring Return Switch
Make

Model No of ACB

Model no of microprocessor based with adjustable O/L, S/C & inbuilt earth Fault
Release
Communication Facility Available or not
(E) Electrical interlock shall prevent the closing
of an incomer if its adjoining outgoing feeder is being
fed from another incomer through the bus-coupler.
The electrical interlocks should prevent the closing of two
incomer breakers and the connecting bus-coupler
2.7 Main Busbar
Ampere rating
Material
Area of Cross-Section for phase
Area of Cross-Section for Neutral
Area of Cross-Section for Earthing
Fault Withstand Capacity kA for 1sec.
Black Matt Painted
Phase Identification
2.8 Main LT Panel Outgoings
2.8.1 Switchgear Rating for MCCBs (Outgoings)
No of Poles
Short Circuit current rating withstand capacity for 1 sec.(ICS) in kA
Make
Model No of MCCB
Communication Facility Available or not
2.8.2 Switchgear Rating for MCCBs (Outgoings)
No of Poles
Short Circuit current rating withstand capacity for 1 sec.(ICS) in kA
Make
Model No of MCCB
Communication Facility Available or not
2.9 CT
2.9.1 Make
CT Ratio-1
Type
Model No
Rated burden
Accuracy class
Insulation Class
2.9.2 Make
CT Ratio-2
Type
Model No
Rated burden
Accuracy class
Insulation Class
2.9.3 Make
CT Ratio-3
Type
Model No
Rated burden
Accuracy class
Insulation Class
2.10 SPD with View Glass
Rating
Class
Make
Model No
2.11 Outer Enclosure
2.12 Power Backup
230VAC Control Supply
30min Power Pack 24V DC for Closing Coil,Trip Coil Circuit,Ann.Window & Digital
meter
Auto Mains Failure Switch
2.13 Other Accessories as per SLD
VENDOR EVALUATION NO.
TECHNICAL PARTICULARS OF LT PANEL
STANDARD TECH PARAMETERS To be Provided by Vendor
VENDOR TO SPECIFY
VENDOR TO SPECIFY
IS 8623/IEC 60439
415 ± 10%/50 ± 5%/3 Phase, 4 Wire
50 °C

Temp. Rise 45 °C over an ambient of 40°C

40°C
Form-3B
Bottom For I/C & O/G
IP 54 for PANEL ENCLOSURE
Out Door Type panel having Canopy of IP55
CRCA Sheet - 2 mm
RAL 7035 or Per IS 5
80 Microns

MFG TO CONFIRM

VENDOR TO SPECIFY
VENDOR TO SPECIFY
FRLS, 1100V Grade cable
VENDOR TO SPECIFY
VENDOR TO SPECIFY
VENDOR TO SPECIFY
VENDOR TO SPECIFY

3200A 4P ACB
EDO
50kA
50kA
Required
ABB/L&T/Schneider/Siemens/C&S
ABB-Emax2/L&T-MTX2.5G/Schneider-ET6G/
Siemens-ETU45B/C&S LSIG

VEDNOR TO SPECIFY

VEDNOR TO SPECIFY

ATTAINABLE

Required
Required
Required
Required
Required
Required
Required

MFM METER
Secure /L&T
VEDNOR TO SPECIFY
CL: 0.5S
With RS485
YES

3200A FP ACB
EDO
50kA
50kA
Required
ABB/L&T/Schneider/Siemens/C&S
ABB-Emax2/L&T-U
Power/Schneider-NW/Siemens-3WL/C&S
AA/AAA
ABB-Emax2/L&T-MTX2.5G/Schneider-ET6G/
Siemens-ETU45B/C&S LSIG
VEDNOR TO SPECIFY

ATTAINABLE

3200A
Aluminum
100% Aluminum Bus Bar
100% Aluminum Bus Bar
50*6
50kA
VENDOR TO SPECIFY (AS PER IS8623)
PVC Sleeves colur coded

4P 630Amp (17 Nos.)


25kA
ABB/L&T/Schneider/Siemens/C&S
Vendor to SPECIFY
VEDNOR TO SPECIFY
4P 100Amp (2 nos)
25kA
ABB/L&T/Schneider/Siemens/C&S
Vendor to SPECIFY
VEDNOR TO SPECIFY

Kalpa/Newtek/Rishab
3200/5
Metering
VENDOR TO SPECIFY
5VA
CL 0.5s
INSULATION CLASS F
Kalpa/Newtek/Rishab
3200/5
To APFCR
VENDOR TO SPECIFY
5VA
CL 1
INSULATION CLASS F
Kalpa/Newtek/Rishab
3200/5
Protection
VENDOR TO SPECIFY
5VA
CL PS
INSULATION CLASS F

100KA
CL-1,B
VENDOR TO SPECIFY
VENDOR TO SPECIFY
VENDOR TO SPECIFY

Required

Required

Required
As per SLD

You might also like