Standard For Insulation Co Ordination 3058912
Standard For Insulation Co Ordination 3058912
Standard For Insulation Co Ordination 3058912
If this standard is a printed version, to ensure compliance, reference must be made to the Energy
Queensland internet site to obtain the latest version.
pprover
Approver Carmelo Noel
sset Standards
General Manager Asset
Energy Queensland
Abstract: The aim of this document is to establish guidelines for insulation co-ordination within
Energy Queensland. This document describes the functional requirements for substation insulation
co-ordination and the integration of insulation co-ordination systems into a substation. This is to
ensure the safety of personnel, the general public and network assets.
2 References ...........
........................................................................................................................... 1
4.3.1 .............................................................................................................. 9
General ................
4.3.3 insulation...............................................................................9
Non-self-restoring insulation 9
4.3.4 Insulation behaviour at power frequency voltage and temporary overvoltages ...9
. 9
5.1.1 ................................................................................................ 11
Surge arresters ............
5.1.2 Application
pplication of surge arresters
arresters........................................................................... 11
5.1.6 Additional
dditional considerations ................................................................................. 12
5.1.7 impedance.................................................................................... 12
Pole footing impedance
5.1.8 ................................................................................ 12
Reducing lightning surges ..
5.1.9 lines................................................................... 12
Insulator design for overhead lines
6 Insulation co-ordination.......................................................................................................
co-ordination 13
6.3.2 ...................................................................................... 16
Design considerations ....
6.3.3 ................................................................................................. 16
Design outputs .......
Annex
nnex A 17
Informative 17
Types of overvoltages
overvoltages............................................................................................................... 17
Annex
nnex B 21
Informative 21
Annex C 22
Informative 22
Annex D 23
Table 4-1 - Substation equipment insulation ratings as outlined in the Substation Standard for
(STNW3015)................................................................................ 6
Substation Primary Plant Rating (STNW3015)
Table of Figures
Figure 4-1 - Classes and shapes of overvoltages, standard voltage shapes and standard withstand
................................................................................................. 7
voltages tests (IEC 60071.1, 2019) ..
Figure 4-2 - Overvoltage representation of magnitudes and durations. (Volker Hinrichsen, 2020) .. 8
1 Overview
Ergon Energy and Energex have adopted a set of standard rated withstand voltages, minimum
clearances, and a specified outage rate for direct lighting strike shielding. Therefore, insulation co-
ordination studies are shortened to the task of reducing overvoltage stresses on equipment by
providing adequate surge protection by selection and positioning of surge arresters.
The aim is to minimise equipment damage and network outages due to overvoltages so far as
reasonably practicable.
This document does not cover specific aspects of insulation co-ordination such as lightning strike
shielding and selection of surge arresters. They are covered in other documents and application
guides.
2 References
The following documents and standards were used in the development of this joint EQL standard.
Surge arresters. Part 4: Metal-oxide surge arresters without gaps for a.c. systems (Australian
Standard)
Volker Hinrichsen, Metal-Oxide Surge Arresters in High-Voltage Power Systems Fundamentals Ed.
3.0 Siemens viewed August 2020, https://assets.siemens-
energy.com/siemens/assets/api/uuid:2ded5619-b9b1-4a28-ae11-d0742992f5da/e50001-g630-
h197-x-4a00-ableiterhandbuch-teil-1-a4.pdf
3.1 Definitions
For the purposes of this standard, the following definitions apply.
Continuous voltage Considered having constant r.m.s value, continuously applied to any pair of
terminals of an insulation [(IEC 60071.1, 2019), modified].
Earth fault factor (k) At a given location of a three-phase system, and for a given system
configuration, the ratio of the highest RMS phase-to-earth power-frequency
voltage on a healthy phase during a fault to earth affecting one or more
phases at any point on the system to the RMS phase-to-earth power-
External insulation The distances in atmospheric air, and the surfaces in contact with atmospheric
air of solid insulation of the equipment which are subject to dielectric stresses
and to the effects of atmospheric and other external conditions, such as
pollution, humidity, vermin, etc. (IEC 60071.1, 2019).
Highest voltage for equipment (Um) The highest r.m.s. value of phase-to-phase voltage for which
the equipment is designed in respect of its insulation as well as other
characteristics which relate to this voltage [(IEC 60071.1, 2019), modified].
Highest voltage of a system (Us) The highest value of operating voltage which occurs under
normal operating conditions at any time and at any point in the system [(IEC
60071.1, 2019),modified].
Impedance earthed (neutral) system A system where the neutral point is connected through an
impedance (resistor/reactor) to reduce the prospective earth fault current. For
a line-ground fault, the unfaulted phases may rise above normal operating
voltages. The ratio between the upstream positive and zero sequence
impedance and the neutral impedance will affect the earth fault factor.
Insulation co-ordination Selection of the dielectric strength of equipment in relation to the operating
voltages and overvoltages which can appear on the system for which the
equipment is intended, and taking into account the service environment and
the characteristics of the available preventing and protective devices.
The "dielectric strength" of the equipment is meant here as its rated insulation
level or its standard insulation level (IEC 60071.1, 2019).
Insulation failure Failure of insulation is the most common cause of problems in electrical
equipment. The purpose of insulation is to prevent the flow of electric current
between points of different potential in an electrical system.
Internal insulation The internal solid, liquid, or gaseous parts of the insulation of equipment which
are protected from the effects of atmospheric and other external conditions
(IEC 60071.1, 2019).
Lightning impulse protection level (Upl) Maximum permissible peak voltage value on the terminals
of a protective device subjected to lightning impulses under specific conditions
(IEC 60071.1, 2019).
Lightning impulse withstand voltage (LIWV) or basic insulation level (BIL): The electrical
strength of insulation expressed in crest value of a standard lightning impulse
under standard atmospheric conditions. The standard lightning impulse is an
impulse voltage having the front time 1.2 μs and a time to half value of 50 μs
(1.2x50 μs).
Nominal Voltage of a System (Un): A suitable approximate value of voltage used to designate the
identity of a system (IEC 60071.1, 2019).
Non self-restoring insulation Insulation which loses its insulating properties, or does not recover
them completely, after a disruptive discharge (IEC 60071.1, 2019).
Rated insulation level: A set of standard withstand voltages which characterise the dielectric
strength of the insulation.
Rated withstand voltage The value of the test voltage, applied in a standard withstand voltage
test that proves that the insulation complies with one or more required
withstand voltages.
Representative overvoltages (Urp) Overvoltage assumed to produce the same dielectric effect on
the insulation as the overvoltage of a given class occurring in service due to
various origins (IEC 60071.1, 2019).
Required withstand voltage (Urw) The test voltage that the insulation must withstand in a
standard withstand test to ensure that the insulation will meet the performance
criterion when subjected to a given class of overvoltages in actual service
conditions and for the whole service duration. The required withstand voltage
has the shape of the co-ordination withstand voltage, and is specified with
reference to all the conditions of the standard withstand test selected to verify
it (IEC 60071.1, 2019).
Self-restoring insulation Insulation which completely recovers its insulating properties within a short
time interval after a disruptive discharge (IEC 60071.1, 2019).
Service reliability The ability of a power system to meet its supply function under stated
conditions for a specified period of time.
Short-duration power frequency withstand voltage (PFWV) also referred to as ACWV The
electrical strength of insulation expressed in r.m.s value of a standard short-
duration power frequency voltage under standard atmospheric conditions. The
standard short-duration power frequency voltage is a sinusoidal voltage with
frequency between 48 Hz and 62 Hz, and duration of 60 s.
Standard rated withstand voltage (Uw) Standard value of the rated withstand voltage as specified
in this document (IEC 60071.1, 2019).
Statistical LIWV/BIL (or SIWV/BSL) The crest value of a standard lightning (or switching) impulse
for which the insulation exhibits a 90% probability of withstand (or a 10%
probability of failure) under specified conditions applicable to self-restoring
insulation.
Switching impulse protective level (Ups) Maximum permissible peak voltage value on the terminals
of a protective device subjected to switching impulses under specific
conditions (IEC 60071.1, 2019).
Switching impulse withstand voltage (SIWV) or basic switching impulse insulation level (BSL): The
electrical strength of insulation expressed in crest value of a standard
switching impulse.
The standard lightning impulse An impulse voltage having a front time of 1.2 µs and a time to half
value of 50 µs.
The standard short duration power frequency voltageA sinusoidal voltage having a frequency
between 48 Hz and 62 Hz, and duration of 60 s.
The standard switching impulse An impulse voltage having a time to peak of 250 µs and a time to
half value of 2500 µs.
Transient overvoltage Short duration overvoltage of few milliseconds or less, oscillatory or non-
oscillatory, usually highly damped (IEC 60071.1, 2019).
Withstand voltage Value of the test voltage to be applied under specified conditions in a
withstand voltage test, during which a specified number of disruptive
discharges is tolerated [(IEC 60071.1, 2019), modified].
3.2 Abbreviations
The following acronyms appear in this standard.
AS Australian Standard
BIL Basic Insulation Level
CFO Critical Flashover
EQL Energy Queensland Limited
FFO Fast-front overvoltages
IEC International Electrotechnical Commission
k Earth fault factor
kc Co-ordination factor
ks Safety factor
Kt Atmospheric correction factor
LIWV Lightning Impulse Withstand Voltage also referred to as Basic Insulation
Level (BIL)
OV Overvoltage
p.u. Per unit
PSCAD/EMTP Power System Computer Aided Design / Electromagnetic Transients
Program
SIWV Switching impulse withstand voltage
SFO Slow-front overvoltages
Table 4-1 - Substation equipment insulation ratings as outlined in the Substation Standard for
Substation Primary Plant Rating (STNW3015)
kV kVp
95
11 12 28
(75)
150
22 24 50
(125)
200
33 36 70
(170)
275 650
132 145
(230) (550)
460 1050
220 245
(395) (950)
Figure 4-1 - Classes and shapes of overvoltages, standard voltage shapes and standard withstand
voltages tests (IEC 60071.1, 2019)
It is conventional to express overvoltages as a ratio in terms of per unit (p.u.) of the peak value of
overvoltages to the peak value of phase-to-earth of the highest voltage for system and or
equipment.
ℎ . . = √2 × .
√3.
The relative magnitude and duration of overvoltages are illustrated in Figure 4-2
Figure 4-2 - Overvoltage representation of magnitudes and durations. (Volker Hinrichsen, 2020)
Table 4-2 - System temporary overvoltage characteristics below outlines the typical magnitudes of
temporary overvoltages in p.u. and typical fault times. Further information is provided in 0.
Magnitude of Overvoltage
Temporary Overvoltage Cause (p.u.) Fault time
Fault Overvoltage (Effectively earthed) 1.3 Less than 1 second
Fault Overvoltage (Impedance earthed) 1.3 - 1.73 Less than 3 seconds
Load Rejection (Moderately extended) < 1.2 Up to 7 minutes
Load Rejection (Extended system) 1.5 A few seconds
Load Rejection (Resonance &
3 Until cleared
Ferroresonance)
Transformer Energisation 1.5 to 2.0 May last for seconds
Longitudinal Overvoltage A few seconds to several
2.0
(synchronisation) minutes
Slow Front Overvoltage (Line
2.8 to 3.0 -
Energisation Ph-E )
Slow Front Overvoltage (Line 1.55 x Line Energisation Ph-E
-
Energisation Ph-Ph ) Fault level
Slow Front Overvoltage (Fault initiation 2(k-1)
-
max.) k = earth fault factor
Slow Front Overvoltage (Fault clearing
2.0 -
max.)
Slow Front Overvoltage (Switching of < 2.0 (Ph-Ph)
-
capacitive or inductive current) < 3.0 (Ph-E)
2.0 (Without restrike)
Switching (Lightning Type) -
3.0 (With restrike)
on the surface of the insulation also become important. For metal enclosed gas-insulated systems,
the effect of the internal pressure, temperature, local inhomogeneities and impurity play an
important role.
Rain, fog, dew formation together with pollution can drastically reduce insulation strength.
Self-restoring insulation
For self-restoring insulation, the probability of flashover may be described by an insulation strength
characteristic curve. This curve has two basic parameters, the Critical Flashover (CFO),
corresponding to the 50% probability of flashover for single impulse application, and a normalised
The main type of surge arrester currently employed within the EQL networks is the metal-oxide
surge arresters without gaps, type SM or higher (IEC 60099-4, 2014), although gapped silicon-
carbide arresters may still exist in older installations.
See (RED 364) Sect 3.3-3.6 and (STNW3028) for more information.
6 Insulation co-ordination
6.1 General
Insulation co-ordination within substations is required to achieve acceptable service reliability by
minimising the risk of insulation failure to major plant and equipment. This is achieved by a
combination of the following:
Surge arresters are installed at locations in accordance with Table 5-1 - Surge arrester
locations.
The selection of surge arresters and selection of pollution level has been in accordance
with Selection of Surge Arresters (STNW3033). The response to power frequency of
external insulation of equipment becomes important when contamination is present.
The external insulation must be designed for contamination severity.
Equipment LIWV values are selected in accordance with Table 4-1 - Substation
equipment insulation ratings.
Substation sites are protected from direct lightning strikes by adequate shielding in
accordance with Substation Direct Lightning Strike Shielding Standard (STNW3032).
Sites meet minimum overhead earth wire shielding distance of the overhead lines
entering or leaving major substations and associated feeder structure footing
resistances according to section 8.5.5 of Standard for Sub-transmission Overhead Line
Design (STNW3355).
Equipment clearances shall maintain electrical safety and maintenance requirements.
The minimum air clearance requirements shall be as per the Clearances in Air Standard
(RED 1909 STNW3013).
Defining the rated insulation level of the equipment. Lightning impulse and short duration power
frequency withstand voltage for the range I voltages (Um up to 245 kV) is required (IEC 60071.1).
Switching studies may be required at lower voltages in special applications (e.g. non-standard
configurations) using the methods outlined in the Insulation Co-ordination Application Guidelines
(IEC 60071.2) and/or simulation studies. PSCAD / EMTP software shall be used where computer
modelling is required.
Substation sites should be protected from direct lightning strikes by adequate shielding in
accordance with Substation Direct Lightning Strike Shielding Standard (STNW3032).
The general procedure can be summarised by the following steps for insulation co-ordination:
The requirements for equipment insulation are already predetermined via a set of withstand
voltages, as outlined in clause 4.1The process of insulation co-ordination is reduced to the
selection and suitable placement of adequate overvoltage protective devices to limit voltage
stresses on equipment insulation.
The detailed procedure for the calculation of overvoltages in 6.3.2 is outlined in Annex G of the
Insulation Co-ordination Application Guidelines (IEC 60071.2). The Computational Guide to
Insulation Co-Ordination and Modelling of Electric Networks (IEC 60071-4) gives examples of the
insulation co-ordination procedure if using PSCAD / EMTP.
The continuous power-frequency withstand voltage of the insulation can be defined as the highest
equipment voltage, Um.
Fault overvoltages
Load rejection overvoltages
Transformer energisation overvoltages
Longitudinal overvoltage during synchronisation
Earth faults produce temporary power-frequency phase-earth overvoltages on the healthy phases.
The temporary overvoltage between phases or across longitudinal insulation normally does not
occur.
The amplitude of the temporary overvoltages depends on system earthing. In effectively earthed
systems, the TOV is about 1.3 p.u. and the duration, considering backup protection, is generally <
1 s.
In impedance earthed systems, the TOV is about 1.73 p.u. or greater the duration is generally less
than 10 s with earth fault clearing or undefined in systems without fault clearing. The amplitude of
fault overvoltages depends on the earth fault factor of the system. Calculation of earth fault factor
is given in (STNW3033) Selection of Surge Arresters.
Temporary overvoltages caused by load rejection are a function of the load rejected, system
topology after rejection and the characteristics of the sources. In a system with relatively short lines
for full load rejection, the temporary overvoltage is < 1.2 p.u. and the duration of the overvoltage
may be up to several minutes.
In a system with long lines, the temporary overvoltage may be 1.5 p.u. or more, the duration of the
overvoltage may be in the order of a few seconds.
Resonance and ferroresonance should also be considered as part of load rejection overvoltages.
Temporary overvoltages arise from the interaction between capacitive elements (lines, cables,
capacitors) and inductive elements having non-linear magnetising characteristics (transformers,
shunt reactors). These types of overvoltages can have a magnitude of 3.0 p.u. and last until the
condition is cleared.
The temporary overvoltages resulting from transformer energisation typically have a magnitude in
the range of 1.5 to 2.0 p.u. and may last for seconds.
Longitudinal overvoltages may occur during synchronisation of generators to the network, due to
phase opposition. (Martinez-Velasco & Molina, 2015) The magnitude of the overvoltage is 2 p.u.
and may last from a few seconds to several minutes.
Slow-front overvoltages (SFO) typically have a duration of tens to thousands of microseconds and
tail durations in the same order of magnitude, with an oscillatory nature. The representative voltage
shape of the SFO is the standard switching impulse, 250/2500 µs, as seen in Figure 4-1.
In the earlier defined ranges for Um, in range I switching overvoltages generally do not constitute a
serious problem and therefore insulation co-ordination is primarily based upon the lightning
overvoltage in overhead line systems.
In range II, however, overvoltages due to closing and re-closing of single-phase or three-phase are
of great importance in the selection of system insulation.
Line switching overvoltages may be reduced through the use of the following:
Phase-to-phase switching overvoltages are typically 1.55 times the phase-to-earth switching
overvoltages. The use of surge arresters will limit the overvoltage to approximately twice the SPL
of the arrester.
Longitudinal switching overvoltages, in synchronised systems, have the same polarity as the
operating voltage. Thus, longitudinal insulation is exposed to a lower overvoltage than the phase-to
earth overvoltages. In non-synchronous systems longitudinal insulation can be subject to opposing
polarities at each end, with different overvoltage levels. One terminal will be subject to energisation
overvoltages while the other terminal is subject to the peak of the operating voltage, with each
terminal having opposite polarities (IEEE 1313.2, R2005).
Within the previously defined ranges in clause 4.1, range I and sometimes range II, high switching
overvoltages can arise at the initiation of an earth fault or load rejection. Conservative estimates of
maximum levels are:
In range II, overvoltages due to restrikes or re-ignitions of the arc of a switching device during
interruption of capacitive current such as unload of lines, cables or capacitor banks can produce
extremely high overvoltages.
The energisation of capacitor banks produces overvoltages at the capacitor location, line
terminations, transformer & remote capacitor banks and at the cables.
The phase-to-earth energisation transient at the switched capacitor location should be less than
2.0 p.u. while phase-to-phase should be less than 3.0 p.u. (Martinez-Velasco & Molina)
The phase-to-phase transient at the line terminations can be 4.0 p.u. or in some cases higher due
to travelling wave reflection.
The higher phase-to-phase overvoltages are mostly associated with floating capacitor banks.
The chopping of inductive current produces high overvoltages due to the transformation of
magnetic energy to capacitive energy and should therefore also be considered.
Slow-front lightning OV originate from lightning strike to a phase conductor of long lines (>100 km)
when the lightning current is sufficiently small to cause flashover and sufficient distance from the
considered location. As the time to half-value rarely exceeds 200 μ and amplitude is not critical for
the insulation, slow-front lightning OV, therefore, are usually neglected.
Fast Front Overvoltages (FFO) have time to crest/peak typically within the range of 0.1 to 20 µs.
The standard voltage shape of the FFO is shown in Figure 4-1. This is represented as the standard
lightning impulse 1.2/50 µs.
Shielding failure
Backflash
Induced voltage
Switching
Shielding failure is usually as a result of lightning strikes to the phase conductors. For shielding
failures, the voltage on the struck phase is random.
A.14. Backflash
Backflash is due to lightning strikes to the line shielding system, such as an overhead earth wire
which flashes over to the phase conductors. The incoming surges caused by the backflash are
more severe than those caused by shielding failures.
Backflash usually occurs on a phase with power frequency voltage that is opposite in polarity to the
surge voltage. The maximum longitudinal overvoltage is the difference between the lightning
overvoltage on one terminal and the power frequency voltage of the opposite polarity on the other
terminal of the switching device.
Voltages are induced in overhead lines when lightning strikes to ground are in close proximity to a
line, thus inducing an overvoltage in the phase conductors. For strikes close to the substations,
lightning overvoltages between phases have approximately the same magnitude as those for
phase-to-earth.
Lightning type overvoltages, caused by switching, are a result of the connection or disconnection of
nearby equipment. This produces voltage surges with similar wave shapes of shorter duration to
the standard lightning surge, as seen in Figure 4-1. Generally, these short duration and fast-rising
surges are oscillatory. Therefore, the insulation strength for this wave shape is closer to that of the
standard lightning impulse than that of the standard switching impulse.
This Standard identifies the minimum insulation co-ordination requirements for the design and
construction of major substations.
Insulation Co-ordination
3. Equipment minimum insulation level requirements are met as per Table 4-1 Yes/No/NA
4. Electrical clearance requirements are met (RED 1909 STNW3013, 2018) Yes/No/NA
6. Surge arrester selection minimum requirements are met (STNW3033, 2008) Yes/No/NA
8. Surge arrester location requirements are met as per Table 5-1 Yes/No/NA
Overhead earth wire requirements for incoming overhead lines are met
9. Yes/No/NA
(STNW3355, 2018)
Where a detailed insulation co-ordination study is required, it is recommended that the insulation
co-ordination report be structured as per the following:
These standards have been revised, redesignated and withdrawn over the years to align with
international standards. This Annex has been added to detail these changes.
Australian Standards
(AS 2067, 2016) Calls upon (AS 1824.1, 1995) (AS 1824.2, 1985).
Revision history
June 2023 2 John Lansley Update format ECM audit. Moved legislation to Section 2.