Busbar Protection - Busbar Differential: Best Practice and Recommendations
Busbar Protection - Busbar Differential: Best Practice and Recommendations
Busbar Protection - Busbar Differential: Best Practice and Recommendations
for Electricity
04 December 2019
Page I
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.entsoe.eu
European Network of
Transmission System Operators
for Electricity
Page II
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
11 CONCLUSIONS ..................................................................................................................... 49
12 BIBLIOGRAPHY .................................................................................................................... 50
Page III
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
DEFINITIONS
Busbar protection (BBP): Protection intended to detect and operate to clear faults on a busbar.
Circuit Breaker Failure (CBF) Protection: CBF protection is a backup protection in case the designated
Circuit Breakers failed to open and clear a fault; it will avoid circuit breaker redundancy
ABBREVIATIONS
87- Differential principle of protection (ANSI code)
AFP - Arc Fault Protection
AIS – Air Insulated Substation
AR – Auto Reclose
BBP – Busbar Protection
BBTR - Busbar Protection Trip Relays
BFP – Breaker Failure Protection
BP – Bay Protection
BTTRTR - Back Trip Receive Trip Relays
BU – Bay Unit
CB – Circuit Breaker
CBF – Circuit Breaker Failure
CT – Current Transformer
DAR – Delayed Auto Reclose
DBI – “Don’t Believe It”, INVALID (1, 1 or 0, 0 for Double Points Status of CBs or Disconnectors)
DC – Direct Current
FAT – Factory Acceptance Test
GIS – Gas Insulated Substation
HVDC – High Voltage Direct Current
ICTR - Interlocked Current Trip Relay
IED –Intelligent Electronic Device
MSCDN - Mechanically Switched Capacitor with Damping Network
OHL – Overhead Line
RES – Renewable Energy Source
S/S – Substation
SGT – Super Grid Transformer, Power Transformer
SVC – Static VAR Compensator (for reactive-power control)
TSO – Transmission System Operator
VT – Voltage Transformer
Page IV
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
EXECUTIVE SUMMARY
This document has been developed by ENTSO-E and it is intended to present the fundamentals of the
busbar protection and all stages of its engineering (design, settings, commissioning and maintenance).
The report is based on responses received from European TSOs to a questionnaire on busbar
protection. It presents the statistical findings of these responses and exploits the experience of TSOs in
busbar protection.
The overall engineering and the management of busbar protection is of great importance to electrical
utilities as busbar faults are of great importance to the safety and the stability of the transmission
system. Busbar protection may simultaneously trip a number of bus segments or even an entire busbar
of a substation and the fast elimination of busbar faults is critical to ensure that the transmission
system does not suffer from severe shocks. The failure of protection operating or any unwanted
tripping may also lead to severe consequences in a transmission system. Although busbar protection is
quite expensive and complicated, its features may save equipment and even people’s lives.
A busbar protection system should dynamically replicate the bus topology and contain design flexibility
to protect all existing bus arrangements. In general, the main requirements for busbar protection
include security, dependability, speed, sensitivity and selectivity. All these requirements are
interrelated; therefore, it is not possible to satisfy one without affecting the other. The design solution
should meet the requirements that correspond to the importance of the substation within the
network and the layout of the substation.
The dominating protection principle of busbar protection is the differential principle. The main types of
differential current protection relays are low-impedance and high-impedance differential protection.
Low-impedance differential principle is mostly used, although, the high-impedance differential
principle is still used by some system operators. Both types of differential current protection relays
have advantages and disadvantages. The low-impedance deferential protection relays are frequently
numeric and more flexible which allows to protect substations with complex schemes. Low-impedance
deferential protection relays can stay in operation even during the reconstruction of substations when
usually some temporary operation is needed. On the other hand, high-impedance relays can be more
easily extended because there is no need to add new analogue inputs. They also need less mounting
space and are less expensive. In addition, the hardware for low-impedance differential relays can be
shared with breaker failure protection, so costs of these relays can be easily reduced. Each end user
should evaluate the advantages and disadvantages and choose the best solution based on the
intended application and installation.
Other busbar arrangements, reliability principles and tripping criteria which support the functionality
of busbar protection (check zone logic, the directional principle, the saturation detection, voltage and
current release criterion and built in circuit breaker failure) must be considered in the design and
configuration of the breaker failure protection. Centralized or decentralized types are equivalently
used depending on the local conditions. Aspects like the number of bays; integrated protection
functions; distance between central unit and bay units; EMC problems; maintenance; function testing
and design should also be considered. The redundancy level should be a function of the critical clearing
time and if this is less than typical remote backup clearing times then busbar protection must installed.
High penetration of power electronics at the connection interface and the existence of GIS or AIS
substations should also be considered in the design and management of busbar protection.
Concerning planning great concern is devoted to the location of installation of busbar protection and
there are a variety of tactics. Most companies try to install busbar protection as much as possible to
Page V
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
avoid the clearance of the busbar faults by the second zone of the distance relays. However, double
busbar protection is not the rule and its policy is managed and/or executed by the companies.
Under normal conditions, a switchgear cannot be switched off completely to check the busbar
protection, making asset management issues critical for the BBP protection. As busbar protection is a
system of the entire busbar, a suitable test strategy must be defined. A general recommendation of
how to test a busbar protection is difficult to provide as it depends on the type of protection system,
on the topology and on the risk or consequence of a false trip.
If the busbar protection must be replaced, the protection system usually must be switched off for a
certain time. A parallel operation of the existing and the new busbar protection is very complex and
involves many provisional steps (risks of false tripping). For this reason, the necessary deactivation of
the busbar protection must be kept as short as possible. During the time when no busbar protection is
in operation, the activation of a reverse zone in the distance protection can provisionally replace the
busbar protection.
Components of the protection system (bay unit or central unit) may fail as with other protection
devices. For this reason, it is advisable to have spares in case of failure, the spares must also be
checked periodically. If applicable, spares for several substations can be stored centrally.
As a rule, the network operator provides a detailed technical specification for busbar protection. In
addition to the protection-relevant requirements, the specification also contains additional
requirements such as for the communication interface (e.g. IEC61850 Edition2) or quality management
(ISO9001).
The life cycle of busbar protection systems is approximately 20 years and the number and rate of
failures of hardware components is identical to that of numerical protection devices.
Page VI
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
LIST OF FIGURES
FIGURE 1: DIFFERENTIAL (OBJECT ORIENTED) PROTECTION PRINCIPLE .................................................................... 3
FIGURE 2: SIMPLE CURRENT DIFFERENTIAL SCHEME WITH PARALLELED CTS ........................................................... 4
FIGURE 3: CROSS-SECTION OF AN AIR INSULATED SWITCHGEAR UNIT WITHIN OPTICAL SENSORS ......................... 6
FIGURE 4: SYSTEM DIAGRAM OF A GENERIC ARC GUARD INCLUDES BOTH OPTICAL AND CURRENT DETECTORS ... 7
FIGURE 5: DOUBLE BUSBAR WITH TRANSFER BUS .................................................................................................... 9
FIGURE 6: MESH BUSBAR SCHEME AND BBP AT MESH SCHEME ............................................................................... 9
FIGURE 7: ONE AND A HALF BREAKER SCHEME ....................................................................................................... 10
FIGURE 8: PROTECTION SCHEME OF BUSBAR PROTECTION OF A SUBSTATION WITH THE CONFIGURATION OF
1 ½ BREAKER ......................................................................................................................................... 10
FIGURE 9: UNDER-VOLTAGE RELEASE CRITERION ................................................................................................... 12
FIGURE 10: NEUTRAL OVER-VOLTAGE RELEASE CRITERION .................................................................................... 13
FIGURE 11: FAULT IN THE DEAD ZONE ..................................................................................................................... 15
FIGURE 12: FAST BUT NOT SELECTIVE PROTECTION OF BUS COUPLERS AND SWITCHED BUSBARS ....................... 16
FIGURE 13: SELECTIVE BUT DELAYED PROTECTION OF BUS COUPLERS AND SWITCHED BUSBARS ........................ 16
FIGURE 14: BREAKER FAILURE PROTECTION ............................................................................................................ 18
FIGURE 15: BBP TRIPPING CHARACTERISTIC ............................................................................................................ 21
FIGURE 16: THE SITUATION JUST BEFORE THE BUSBAR FAULT ............................................................................... 26
FIGURE 17: CHART - SUBSTATION DESIGN CONFIGURATION ................................................................................. 28
FIGURE 18: DO YOU HAVE DIFFERENTIAL BBP PROTECTIONS AT ALL SUBSTATIONS (S/S)? .................................... 29
FIGURE 19: VOLTAGE LEVEL LACKING BBP? ............................................................................................................. 29
FIGURE 20: CRITERION NOT HAVING BBP IN S/S ..................................................................................................... 30
FIGURE 21: DIFFERENCES IN BBP AT S/S FEEDING RES VS. THOSE FEEDING CONVENTIONAL GENERATING
PLANTS? ................................................................................................................................................ 31
FIGURE 22: BUSBAR PROTECTION CONFIGURATION ............................................................................................... 31
FIGURE 23: POWER SUPPLY TYPE FOR SINGLE BUSBAR PROTECTION ..................................................................... 32
FIGURE 24: BUSBAR PROTECTION OPERATING PRINCIPLES .................................................................................... 34
FIGURE 25: ADDITIONAL TRIPPING CRITERIA FOR BBP DIFFERENTIAL .................................................................... 34
FIGURE 26: A FAULT IN A BAY BETWEEN A CIRCUIT BREAKER AND A CURRENT TRANSFORMER ELIMINATED
BY? ........................................................................................................................................................ 36
FIGURE 27: BUS COUPLER SPLITTING POLICY .......................................................................................................... 36
FIGURE 28: CIRCUIT BREAKER FAILURE PROTECTION (BFP) OPERATING PRINCIPLES ............................................. 38
FIGURE 29: BBP PARAMETRIZATION/SETTINGS RESOURCES ................................................................................... 38
FIGURE 30: CRITERIA FOR SETTING OF THE MINIMUM DIFFERENTIAL CURRENT OF BUSBAR PROTECTION .......... 39
FIGURE 31: THE CRITERION OF STARTING SIGNAL FOR BFP .................................................................................... 40
FIGURE 32: THE CRITERION FOR SETTING OF THE MINIMUM CURRENT FOR BREAKER FAILURE DETECTION,
PHASE OR THREE PHASE DETECTION? .................................................................................................. 40
FIGURE 33: MAINTENANCE OF BBP – HOW IS IT IMPLEMENTED? .......................................................................... 42
FIGURE 34: BBP MAINTENANCE STRATEGY/HOW OFTEN IS THE DEVICE TESTED? ................................................. 43
FIGURE 35: EXPECTED LIFETIME FOR NUMERICAL BBP IN YEARS ............................................................................ 46
FIGURE 36: NUMBER OF BUSBAR FAULTS - YEARS TO BUSBAR FAULT. FAULTY TRIPS ARE NOT INCLUDED ........... 47
FIGURE 37: NUMBER OF UNWANTED TRIPS FROM BUSBAR PROTECTIONS ........................................................... 48
Page VII
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
1 INTRODUCTION
Busbar faults are directly related and interlinked with the safety and the stability of the transmission
systems. Their fast elimination assures the successful withstanding of the transmission system to
severe shocks [3]. Busbar protection may simultaneously trip a number of bus segments or even an
entire busbar of a substation which may then lead to the loss of important assets. If generation or big
loads are connected to the busbar the energy balance of the system may be suddenly endangered.
Consequently, the failure to tripping or any unwanted tripping may lead to severe consequences on
the power system.
This document has been developed by ENTSO-E and it is intended to present the fundamentals of the
busbar protection and all stages of its engineering (design, settings, commissioning and
maintenance). The report is based on responses received from European TSOs to a questionnaire on
busbar protection. It presents the statistical findings of these responses and exploits the experience
of TSOs in busbar protection.
Chapter 2 presents a brief description of the principles of function of the busbar protection.
Chapter 3 documents the various configurations and architectures of busbar protections.
Chapter 4 analyses the protection of specific components of the buses (Eg. busbar couplers,
segments between components, etc.) with the objective of covering all of the elements involved and
even optimal overlapping regarding their protection.
Chapter 5 is exclusively devoted to a very important protection, usually interlinked with busbar
differential protection, the circuit breaker failure protection.
Chapter 6 gives guidance concerning the setting and the parameterisation of the busbar differential
protection.
Chapter 7 covers issues in relation to the asset management of the busbar differential protection, Eg.
principles in relation to testing, maintenance, lifecycle and refurbishment.
Chapter 8 makes reference to Standards (CENELEC, IEC, ENTSO-E / EU regulations etc) concerning
busbar (differential) protection as well as to brochures of related international organizations like
CIGRE, IEEE etc.
Chapter 9 discusses a case concerning maloperation of busbar protection and the “lessons learned”.
Chapter 10 includes the statistical appraisal / presentation of the responses of the TSOs to the
distributed survey about busbar protections.
Finally, Chapter 11 summarizes the conclusions and recommendations.
The report is accompanied by a related reference / bibliography list (Chapter 12) with books, papers,
presentations, brochures etc. concerning busbar differential protection.
Page 1
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.entsoe.eu
European Network of
Transmission System Operators
for Electricity
protections served as the main protection for busbar faults. As a result of increased network short-
circuit capacity, dedicated differential relays for busbar protections have been applied to minimize
the tripping time of the protection and to limit the damage caused by high fault currents. Today,
busbar protection systems are used [7]. and even double busbar protections may be applied.
The generic transmission systems’ key issues i.e. reliability, operability, maintainability and cost need
to be addressed when designing a substation and selecting a busbar configuration and consequently
a busbar protection scheme. At EHV/HV levels, solutions that provide a high degree of reliability can
be justified. A busbar protection system should dynamically replicate the bus topology. It should also
contain sufficient design flexibility to protect all existing bus arrangements. In general, the main
requirements for busbar protection include:
• Security - probability of an unnecessary protection operation for through faults (“Out-of-
Zone” faults) is low.
• Dependability - probability that the protection will not operate for a fault on the bus (“In-
Zone faults”) is low.
• Speed – high-speed operation is required to limit equipment damage, and to preserve
system transient stability.
• Sensitivity – the ability to detect and clear high resistance faults.
• Selectivity – the ability to isolate only the faulty bus section.
All these requirements are interrelated; therefore, it is not possible to satisfy one without affecting
the other. The design solution should meet the requirements that correspond to the Importance of
the substation within the network and the layout of the substation.
The dominated protection principle of busbar protection is the differential principle. The
fundamental general principle of differential protection of a “single object” is illustrated in FIGURE 1
bellow. In the place of “object” a generator, a transformer, a bus arrangement, a reactor, a line or a
cable etc. can be considered. Of course the differential protection of each one of this type of
components has additional specific peculiarities, but the fundamental principle is the same.
The affection of the measured and compared currents flowing “into” the protected object due to a
fault is presented.
Page 2
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
Page 3
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
source to the bus must be equal to the sum of all currents that flow from the bus to the load. If this is
not satisfied, an internal fault (“In-Zone” fault) has occurred. However, in actual applications, bus
differential relays could unintentionally operate when there is no fault on the protected bus. This
might happen when faults in the power system cause high currents to flow through the protected
bus causing saturation of some iron-cored CTs that provide information to the relay about the
magnitude of the primary currents. Saturated CTs will provide false information, reporting smaller
current magnitudes than there actually are. As a result, the relay will derive “differential” current
that actually does not exist. To avoid unnecessary operation, manufacturers use different algorithms
to achieve relay stability during CT saturation.
Kirchoff’s current law states that the vectorial sum of all currents at a node or bus is equal to zero.
This principle is applied to bus protection in power system networks. Current transformers (CTs) are
installed to monitor all currents entering and leaving a bus through the normal circuits connected to
the bus. A bus differential protection scheme, regardless of the type of relay used, simply compares
the current entering the bus with the current leaving the bus. Any difference in the current entering
and leaving the bus, above some predetermined threshold, is an indication of a bus fault that must
be isolated quickly. Bus differential relays perform this function by detecting the differential current
and tripping all breakers directly associated with the bus to isolate the fault. Unlike transformer
differential relay schemes, the bus differential relay does not need to provide magnitude or phase
angle compensation because of transformer winding ratios and connections. Likewise, bus
differential schemes do not have to contend with magnetizing inrush currents that require
transformer bus differential relay schemes to employ harmonic blocking, restraint, or other
waveform recognition techniques. On the surface, bus differential schemes should be very simple to
apply. A simple bus differential scheme can be implemented by paralleling CTs from all circuit
breakers on the bus, in which case the sum of the current on each phase for all normal through-load
and external through-fault conditions is zero, as shown in FIGURE 2. The first complication arises
because all paralleled CTs must have the same ratio to ensure that all secondary currents are
compared on the same base as the primary currents.
Page 4
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
The relay in this simple bus differential scheme could use a simple, instantaneous overcurrent
element set with a very sensitive pickup, because ideally no current flows to the relay under normal
through-load and through-fault conditions. This, of course, assumes that all paralleled CTs not only
have the same ratio but that they also perform identically under all conditions, including external
faults with heavy through current and asymmetrically offset waveforms caused by high source X/R
ratios. The reality is that all conventional iron-core current transformers, regardless of ratio and
accuracy class, are susceptible to saturation, during which time their secondary output current fails
to accurately represent the primary current flowing in the bus. This causes a difference current that
the differential relay may interpret as an internal fault. Bus differential relays, regardless of the
design, must differentiate between true internal bus faults and false differential currents caused by
CT saturation for a fault outside the bus differential zone of protection
Page 5
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
open, but the current through the CT has not gone to zero. The logic sends a transfer trip to the
breaker at the remote end to interrupt the last source of fault current. The other possibility is to send
a teleprotection signal to distance relays on the remote end immediately when BBP operates. It will
accelerate the operation of the distance relays.
An open or shorted CT in a low-impedance scheme produces a differential current, which is
proportional to the load current on the circuit with the faulty CT. With low-impedance relays, the
setting can eliminate differential current under normal load condition, so a current threshold can be
set sensitively to detect an opened or shorted CT. This threshold can be used to alarm, disable the
BBP or trip the bus. A more sophisticated method can detect the change in differential and restraint
current. The loss of a CT output current results in an increase in differential current and a decrease in
restraint current.
The additional tripping criteria are described in a chapter hereafter.
Conventional current based protection techniques are at times challenged by the nature of arcing
faults and can result in slow protection clearance times. Slow protection clearance times increase the
Page 6
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
risk to nearby personnel and increase the degree of damage to plant and equipment. By employing
an optical detection technique, Arc Fault Protection (AFP) results in fast clearance of arcing faults.
The AFP can detect arc-flash events and send a trip signal from 2 up 4 ms if using high speed output
contacts or 15 ms for relay contacts.
Although detecting light is perhaps the easiest and fastest detection method, many systems detect
two and sometimes a combination of three or more parameters (i.e. light, current and sound). The
most efficient, cost effective, and therefore the most commonly used method combines the
detection of light and current.
Arc Flash Detection System
The primary components of an arc flash detection system (light and current detector) are the arc
monitor unit, control unit, optical detector, current detector and current transformer. The control
unit receives signals from both a high-sensitivity light detector and the upstream current
transformer, enabling it to determine whether to trigger the circuit breaker. Clearly, this signalling
process must be both fast and reliable to minimize danger and damage. Fiber optics, with its inherent
speed and EMI immunity, makes it a perfect medium for an arc flash detection system.
FIGURE 4: System diagram of a generic arc guard includes both optical and current detectors
The optical detector unit includes an optical emitter and receiver, an optical sensor in the form of a
bare fiber loop, and fiber optic cable. The optical sensor collects the flash light and transfers it via
fiber optic cable to the fiber optic receiver, which converts the optical signal to an electrical signal
that informs the control system when an arc flash is occurring.
There are two types of optical sensors commonly used in such systems: the point sensor and the loop
sensor. The point sensor approach uses a light sensor and an optical receiver to detect light in a given
area, while the loop sensor uses a loop of bare fiber positioned strategically throughout the
equipment.
The unavailability of a differential busbar protection in a substation can be critical for the grid
regarding the stability of the nearby power plant units. Operating reliability is also required in case of
short circuit in the substation : it is forbidden to lose an entire substation in case of malfunction of
the busbar protection.
Page 7
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
It is therefore necessary to monitor in real time the proper functioning of the busbar protection. It is
required to verify that the acquisition of the input quantities is correct and that the internal
components of the protection are functional.
The main busbar protection fault supervision functions are mostly the following: faulty current
measurement detection, faulty disconnector position detection and internal component failure
detection.
For the reliable operation of busbar protection this supervision functions are continuously running
and protect the busbar protection from false tripping. These supervision features are presented now.
First of all, current measurement supervision monitors in real time the following currents computed
by the protection: the differential currents, the zone differential currents and the check zone
differential current.
When a faulty current is detected, the actions can be:
• Alarm (possibly delayed),
• Full Busbar Protection blocking (full blocking or only for the phase concerned by the faulty
differential current),
• Partially (Zone) Busbar Protection blocking (only for the zone concerned by the faulty
differential current and only for the phase concerned).
Likewise, disconnector position supervision monitor in real time the faulty disconnector position
replica and the wrong disconnector position detection (mistaken position).
Internal components failure supervision is also required as for any protection. This supervision
monitor the following points: components failure (watchdog), link between bay failure (for
decentralized arrangement), power supply failure…
When a faulty disconnector position or an internal component failure is detected, the actions can be
the same: alarm (possibly delayed) or full (partially) busbar protection blocking
BUSBAR SPLITTING
A busbar differential protection is characterized by its protecting zones, which refer to bus segments
being isolated by circuit breakers in case of busbar faults. Purpose is to isolate –after a fault- only the
busbar part feeding the fault. When more than one protection zone at the busbar protection is
applied, a busbar splitting strategy is used.
The positions of the CT are structuring to get the optimal splitting strategy. Indeed, in case of a
busbar fault, the busbar protection performs the tripping of the CB only for the corresponding busbar
section (the busbar section is boarded by CT with regard to measurement and by CB with regard to
tripping).
The CBs and disconnector positions are also needed to apply the correct differential current
computation and busbar splitting operation in case of fault. It is indeed useful to use several
measuring zone to obtain the best selectivity.
Several busbar switching schemes are available and there are many variants of each scheme [2]
Page 8
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
Some examples:
Double Busbar with Transfer Bus
Page 9
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
Page 10
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
DISTANCE PROTECTION
Distance protection relays are mostly used for busbar protection backup (or during maintenance of
the busbar differential protection).
Different choices are possible to use distance protection:
- Use of zone 2 of distance protection from the opposite end of the overhead lines or
underground cables,
- Use of reverse zone (oriented towards the busbar) for the transformers distance protection
or overhead lines distance protection,
- Use of distance protection to trip coupling circuit breaker (with blocking scheme between
distance protection for the ring substation topology)
During maintenance period of busbar differential protection, it can be needed to modify distance
protection settings (X-reaches, R-reaches or grading times).
These setting modifications are sometimes needed to ensure the stability of the generator in the
area or to ensure the integrity of GIS busbar in case of fault during busbar differential protection
maintenance.
Page 11
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
Page 12
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
Page 13
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
from the zone relay and a separate tripping path. This preference is naturally met when using a
standalone BF relay.
Integrating the BF function in multiple zone relays allows biasing the scheme for more security or
more dependability compared with standalone BF protection, depending on the specific architecture
selected and willingness to accept extra inter-relay signalling and associated complexity.
DECENTRALIZED ARRANGEMENT
In the past, before numerical de-centralized busbar protection was available, busbar protections
were constructed centrally. All process data, such as CT currents, isolator positions and tripping
channels had to be wired back towards the central position of the busbar protection panel.
Considerable interconnection (such as start circuit breaker failure protection, block autoreclosure,
etc.) between the other protection panels had to be made. In those conventional arrangements,
many cables had to be used, the engineering, commissioning and maintenance was quite time
consuming and costly.
A vertical comparison of centralized vs. decentralized is shown in TABLE 1.
Page 14
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
Page 15
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
the busbar differential protection. In the case of current transformers arranged on the line
side, the fault must be disconnected by the circuit breaker at the opposite end.
87
87
FIGURE 12: Fast but not selective protection of bus couplers and switched busbars
87 87
87
FIGURE 13: Selective but delayed protection of bus couplers and switched busbars
There are two other possible ways how to protect these bays.
The first one is selective but the switching of the fault is delayed. It can be used if we prefer
selectivity to speed.
If there is a fault between CTs, only the CB in the bus coupler or bus section is tripped. After that
these two CTs are with different zones of the BBP, so only the faulted bus can be switched off. A
small delay about 100ms is necessary in this case to let CB in the bus coupler or bus section to open
and the BBP to change configuration of the S/S. The state of the CB must be signalized to the BBP.
The second one is cheaper and easier but is both unselective and delayed. It can be used if there is
not problem with stability and power outage. It is described in the chapter 4.1.1 (dead zone) in
detail.
Page 16
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
Page 17
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
normally in testing procedures. For feeders with weak infeed it is common to use the circuit breaker
auxiliary open contact 52a instead of current base confirmation.
The time delay is established according to stability network demands and is an important factor
when coordinating with remote back-up protections.
Different consequences can result from the output of this scheme: a re-trip function, a back-up trip
function and intertripping.
The FIGURE 14 scheme uses the inputs (CT, wiring, relay input circuitry, and firmware) to issue the
trip and to determine if the breaker actually failed. This combined with multiple operational copies of
the BF function can potentially erode security of the BF protection. Some multi-input relays reduce
this concern to a degree by allowing different CT, wiring, and relay inputs for the BF function, as
shown in the next picture.
Page 18
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
However a consequence of this is that if one of the distributed units or the central unit of the
numerical protection fails the entire busbar protection for one or more busbar sections is lost. The
result is that a substantial number of circuit may have to be taken out of service until a repair is
completed.
Two options are possible as contingency arrangement to allow the busbar sections to remain in
service:
1) Provision of a second central unit and associated fibre optic connections so that in the event
of failure of the first unit the busbar protection can be manually connected to the second
unit to enable it to remain in service.
2) Adjust the protection arrangement on the infeeding circuits (feeders) to provide limited
protection for the busbars to allow them to remain in operational service.
The option 2 contingency plan can be implemented by using feeder distance protection fast
discriminative reverse Zone 3. The reverse Zone 3 can be selectable via Group settings, when used to
provide busbar contingency plan, it shoul trip not only the local circuit breaker/s of the feeders but
also other circuit breakers of connected bays to the busbar(s) (such as Transformers and other shunt
plants etc.) by a separate cross tripping scheme. The time setting for the reverse Zone 3 should be
properly graded with the all the distance protections of the feeders connected to the busbar to
ensure that a busbar fault is cleared as quickly as possible but not tripped by the faults within Zone 1
of the feeder protections.
Page 19
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
appropriate safety or operational Codes / guidelines or they are according to the utility’s specific
policy.
Direct tripping from busbar protection trip relay shall be selected as follows:
(i) Where the remote end of a two-ended feeder is connected to a double busbar substation
(ii) Where the remote end of a three-ended feeder is connected to a double busbar substation
and fault clearance from the remote substation in CB Fail time is unacceptable from a system
operation perspective.
(iii) Where the local substation is indoors with CTs on the line side only i.e. possibility of a 'Small
zone' fault indoors except where (viii) and (ix) apply.
(iv) Where the outgoing feeder is a transformer feeder with LV-side circuit breaker connected to
LV-level kV at the remote end
(v) Where the local SGT LV circuit breaker is connected to LV-side kV at the local end i.e. for the
LV circuit breaker of a HV/LV kV SGT.
(vi) In all those cases where the additional time delay associated with CB Fail protection would
adversely affect the transient stability of generators or where continued energisation from
the remote end only is unacceptable,
(vii) There is no requirement to affect direct tripping from bus sections or couplers.
Selective tripping of the remote ends of feeders shall be selected where:
(viii) The feeder is a ‘teed’ feeder, including feeders whose remote termination is a double busbar
or a mesh corner to which is also connected an interconnecting transformer.
(ix) The feeder's remote termination is a mesh corner with or without a connection to a supply
transformer.
(x) However, if the delayed tripping of the remote ends in (viii) to (ix) will cause instability
problems, direct tripping should be adopted.
As mentioned in chapter 2.1, BBP is based on the principle of Kirchhoff’s Current Law, which states
that in the case of unfaulty operations all currents flowing into and out of the object must be zero
[4]. The BBP protection calculates the sum of all currents flowing into and out of the busbar. The
differential current 𝑰𝑫𝒊𝒇𝒇 is equal to the phasor sum of all feeder currents, belong to particular
section – 𝑰𝑫𝒊𝒇𝒇 = |𝑰̅𝟏 + ̅𝑰𝟐 + ̅𝑰𝟑 + ⋯ + ̅𝑰𝑵 |. The restraint current 𝑰𝑹𝒆𝒔 corresponds to the arithmetic
sum of all feeder currents (sum of their absolute values) belong to particular section - 𝑰𝑹𝒆𝒔 = |𝑰̅𝟏 | +
|𝑰̅𝟐 | + |𝑰̅𝟑 | + ⋯ + |𝑰̅𝑵 |. The tripping characteristic of numerical low impedance biased BBP is shown
in the FIGURE 15 [6].
The tripping characteristic is determined by the two settable parameters – differential current limit
𝑰𝑩 and stabilizing factor 𝒌. BBP operates when two criteria are met – 𝑰𝑫𝒊𝒇𝒇 > 𝑰𝑩 and 𝑰𝑫𝒊𝒇𝒇 >
𝒌 × 𝑰𝑹𝒆𝒔 .
Page 20
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
- The current threshold 𝑰𝑩 must be 20% lower than minimum calculated short circuit and
should be 25-30% greater than maximum operational current, commonly nominal current of
CT with the highest primary current
𝟏, 𝟐𝟓 × 𝑰𝑴𝒂𝒙𝑪𝑻 < 𝑰𝑩 < 𝟎, 𝟖 × 𝑰𝑴𝒊𝒏𝑺𝑪 .
Sometimes, in the case of a single phase to earth fault, 80% of the minimum calculated short
circuit may be lower than 125% of the maximum operational current (mostly when
considering energizing a substation by one transmission or distribution line). The setting
must be then done appropriately to this situation. Some vendors offer controllable (by binary
input) sensitive setting of the current threshold – 𝑰𝑩−𝑺𝒆𝒏𝒔 , some offer separate setting for
neutral current – 𝑰𝑵𝑩 , which would be suitable for this situation.
- The stabilizing factor 𝒌 must provide stability against external faults (faults outside protected
zone) and, on the other hand, should be sensitive to detect busbar faults. In the case of a
busbar fault, when each feeder either feed the fault or doesn’t flow any current through, the
operating current is equal to the restraint current. The operating current lies on the fault
characteristic with stabilizing factor 𝒌 = 𝟏 i.e. 𝑰𝑶𝒑 = 𝑰𝑹𝒆𝒔 . As a fault resistance on the
substation used to be low and short circuit current is high, compare to the operational
current, this the most likely situation, that can happen in transmission and distribution
system. To determine the value of 𝒌 the saturation time of CTs should be taken into account.
This factor can be calculated according following equation [6]
𝑲𝑩 𝑰𝑴𝒂𝒙𝑺𝑪 𝑰𝑴𝒂𝒙𝑺𝑪
𝒌> 𝑓𝑜𝑟 𝑲𝑩 ≥ 𝟐 𝑤ℎ𝑖𝑙𝑒 𝑲𝑩 = =
(𝟒 × √𝑲𝑩 − 𝟏) 𝑰𝑺𝒂𝒕𝑪𝑻 𝑰𝑵𝑪𝑻 × 𝒏′
Where 𝑰𝑴𝒂𝒙𝑺𝑪 is the maximum continuous short circuit, 𝑰𝑺𝒂𝒕 is the saturation current of a
particular CT, 𝑰𝑵𝑪𝑻 is the nominal current of the CT and 𝒏′ is the effective overcurrent factor
of that CT. Since the 𝑲𝑩 factor in transmission and distribution system is usually lower than
2, and very often lower than 1, the setting, with safety margin, 𝒌 = 𝟎, 𝟔 is sufficient. The
practice is set the stabilizing factor between 0,6 and 0,8 – 𝒌 ∈ 〈𝟎, 𝟔 − 𝟎, 𝟖〉.
k=1
k set =0,1 - 0,9
I Op
Tripping area
IB
I Restr
Page 21
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
The same rules should be applied also on check zone’s setting. Some vendor’s BBP doesn’t allow
separate setting of the check zone and it is the same as particular (bus) zones
The time delay of BBP should be set to zero
Page 22
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
Page 23
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
CERTIFICATION
As a general rule, the network operator provides a detailed technical specification for busbar
protection. In addition to the protection-relevant requirements, the specification also contains
additional requirements such as for the communication interface (e.g. IEC61850 Edition2) or quality
management (ISO9001).
The vendor must prove compliance with the requirements by means of tests or certificates. The
tests can be carried out either in the manufacturer's laboratory or in the network operator's own
laboratory.
COMMISSIONING
As a rule, all functions of the busbar protection together with the process (from the auxiliary contacts
of the isolators, trips to the circuit-breakers, current transformers and signalisation of the
alarms/events) are tested during the commissioning by protection specialists (own or from the
manufacturer). Since the busbar protection is not in operation, the complete protection functions
can be tested. Whether a test with primary current must be carried out is decided on a case-by-case
basis. It is essential that the stability control of the differential function (with operating current or
with primary feed-in) is carried out.
LIFE CYCLE
The life cycle of busbar protection systems is approximately 20 years as for numerical protection
devices. The number and rate of failures of hardware components is identical to that of numerical
protection devices.
Page 24
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
respect to a variety of bus arrangements are discussed; specific application guidelines are provided.
Breaker failure protection is discussed as pertaining to bus protection. Means of securing bus
protection schemes against corrupted relay input signals are also included.
IEEE Std C37.119-2016 - Guide for Breaker Failure Protection of Power Circuit Breakers
This guide compiles information on the application considerations for breaker failure protection.
The reasons for local backup protection are described. Breaker failure schemes are discussed.
Issues relating to the settings of current detectors and timers are discussed for various applications.
ENTSO-E 181010 SOC TOP 09.2 - Best protection practices for HV and EHAV AC Transmission Systems
of ENTSO-E Electrical Grids
This document describes the best practices for protection schemes with considerations of security
of supply and safety of personnel and equipment. The focus is on the protection application of
equipment, at mainly extra high voltage (EHV) AC, i.e. 400 kV, or high voltage (HV) AC, i.e. less than
or equal to 220 kV, and in some special cases other voltage levels as well.
CIGRE 2010 Technical Brochure – Modern Techniques for Protecting Busbars in HV Networks, ISBN
978-2-85873-119-0
This Technical Brochure is intended to assist the relay application engineer in the correct selection
and application of busbar protection. It provides relevant information about their performance,
operation, testing, and maintenance. Two main designs used for HV busbar protection today are
high impedance and low impedance differential protection systems. Features of modern low
impedance differential protection are described in details.
CEPS’S EVENT
On 7.10.2014 in a double bus substation 400kV a BBP did not operate during a busbar fault. It was
not caused by the BBP itself but by special conditions before the fault.
The BBP contains a current measurement blocking function that is described in the chapter 2.4. In
case that the BBP measures only a small differential current it is suspected that the measurement of
the relay is not correct. If the situation takes longer than 5s the function of the relay is selectively
blocked – tripping in zones with the spurious measurement is blocked.
The fault occurred during an on-load busbar changeover. It means the bus coupler was switched on
and all bays were changing to a one bus. In changed bays, one bus disconnector was gradually
switched on and the second one switched off.
In one bay, there was a drawbar of one phase of the disconnector Q1 broken. It meant that the
motor was working but the contact in one phase did not move. Therefore, the disconnector Q1 was
closed only in two phases, but signalization to the control system and to the BBP was that it was
connected in all three phases.
Page 25
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
Page 26
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
10 TSO’S QUESTIONNAIRE
A questionnaire was addressed for filling in by TSOs represented within or being corresponding with
Protection Equipment subgroup, in order to gather information about busbar protection, about the
adopted practice and the problems faced.
The TABLE 2 shows –in alphabetic order- the TSOs of ENTSO-E that responded to the questionnaire
(24 companies responded, coming from all ENTSO-E regions).
Hereafter the main findings from the received responses are cited.
Page 27
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
20 20
20
16
No. of TSO
15
11 11 11
10
10
0
1. Single busbar 2. Double busbar 3. Double busbar 4. Triple busbar 5. Breaker-and-a- 6. Double busbar 7. Ring busbar or 8. Other
with single breaker with transfer bus- half with double Mesh Corner configuration
(bus-section) coupler breakers (bus-
sections)
Page 28
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
FIGURE 18: Do you have Differential BBP protections at all Substations (S/S)?
The main reason of not having BBP is the configuration of older-design substations with an
electromechanical relay or according each TSO’s requirements, depends mainly on technical and
economical evaluation: substation have few feeding lines, importance for transmission system,
critical fault clearing time, lower power consumption or quality requirements (FIGURE 20). In giving
time the prevailing tendency is to install BBP in all new or reconstructed substations.
Page 29
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
Page 30
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
FIGURE 21: Differences in BBP at S/S feeding RES vs. those feeding conventional generating plants?
Page 31
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
Page 32
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
One power supply use 17 TSO. Redundant power supplies use 13 TSO. Both, one and redundant
power supply use 6 TSO. About 45 % of the TSO’ use one power supply, 30 % of them use redundant
PS and about 25 % use both type.
Page 33
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
Page 34
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
It’s used to increase stability of BBP, The check zone calculates the diff. current and restrain
current for the all s/s (all bays, except bus-coupler) without taking into account the position of
the BB disconnectors. A trip order is issued only in case a fault is detected simultaneously in
both the BBP zone and in the check. It is also used in smaller 110kV substations
- Current directional
Currents in all bays must have the same direction – into the protected zone. Generally it’s not
common upon responders.
- Phase under-voltage release criterion (U<)
It is not used among responders.
- Voltage sequence components release criterion (U1<, U2>,3Uo>)
It is not used among responders.
- Neutral over voltage release criterion (3Uo>)
It is not used among responders.
- Neutral over current release criterion (3Io>)
It is not used among responders.
- Overcurrent release of the trip command
It is not used among responders.
- External release of the trip command
It is not used among responders.
- Other
Check Zone + Discrimination Zone -Two independent algorithms (e.g. angler differential +
current differential), dead zone function
Page 35
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
FIGURE 26: A fault in a bay between a circuit breaker and a current transformer eliminated by?
Page 36
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
A bus coupler distance protection zone reach is calculated by estimating shortest line reactance
reach with additional margin (0,72 x shortest line). Time delay is between 150 ms and 300 ms with
consideration of other protection time delays (line distance protection zone 2, BFP, line distance
reversal zone). The similar setting selection principles apply to overcurrent protection relays.
Protection must trip before line distance remote end protection and/or before reversal line distance
protection zone.
Also, there are some cases without additional time delays in bus coupler protection to consider.
Page 37
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
Page 38
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
FIGURE 30: Criteria for Setting Of The Minimum Differential Current Of Busbar Protection
Page 39
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
FIGURE 32: The criterion for setting of the minimum current for breaker failure detection, phase or
three phase detection?
The BFP tripping time is crucial factor for transmission system operation stability and must fulfil
critical clearing time conditions. The setting for the time delay varies among TSO’s from 120 ms to
300 ms. The time delay is calculated by evaluating protection response time, CB contact tripping
time, action time of auxiliary relays, safety time margin and selectivity in relation with the fault
clearance time by the main protection.
Page 40
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
The current circuit (differential current) supervision function is part of BBP. Current circuit
supervision picks up if differential current exceeds setting value for a set time. Settings values are
determined by maximum CT primary current or by certain level of operational current. Function can
block BBP entirely or alarm about current circuit malfunction due to incorrectly connected CT, open
wire or CT defects.
The stabilization factor (k-factor) for BB zones determines the stabilization in case of external faults.
A higher stabilization factor has a positive influence on the stabilization for external errors, while the
sensitivity to internal faults diminishes.
BB auto-reclosure solution is initiated only for one time when BBP trips faulty busbar section and if
BFP permits to do it. BB auto-reclosure is initiated by one of the dedicated CB’s, after successful
busbar auto-reclosure remaining busbar CB are connected automatically.
Special solution BFP applicable to reduce short circuit clearing time in S/S with connected extra-large
units (app. 1GW). Aim is to speed up reaction of BFP when failure of CB occurs during clearing
multiphase short circuit on line. For detection such short circuit additional zone must be set (shorter
to zone 1) in line distance protection. Activation signal of this zone is sent to BFP. If this zone is still
active after time of proper reaction on short circuit in base protection zone, re-trip is omitted and
BFP is operating according to scheme.
Page 41
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
Page 42
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
10.8.3 Q.8.3 BBP MAINTENANCE STRATEGY/HOW OFTEN IS THE DEVICE TESTED AND WHAT
IS TESTED?
Page 43
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
10.8.6 Q.8.6 ADDITIONAL BAY PROTECTION (BP) RELATED FUNCTION ON BAY UNITS (BU)
The “district” options / combinations are:
- Overall protection sytem (BBP+BP in same devices).
- Distance protection on BU
- Overcurrent on BU
- Autoreclosing (AR)?
- Disturbance protection (starting?)
The majority of TSOs use the BU for BBP only.
Five TSOs use BU for BBP and BFP only. Some of the TSOs have additional bay protection in already
running BBP.
Four exceptions occur:
• BU contains BBP, BFP and Pole discordance function
• Two TSOs use overcurrent protection on BU. One only for 110 kV overhead lines.
• One TSO use Distance Protection on BU in a few S/S.
10.8.7 Q.8.7 IS THERE A CERTIFICATION PROCESS FOR THE BBP? (TENDER REQUIREMENT)
Nearly all TSOs have a certification process. The certification processes are very different, but tree
different strategies seam to occur:
• Tender specification: All requirements are detailed described including technical data,
manufacturer quality management system, list of clients/users, etc.
• Type test in laboratory owned by TSO (Done by either TSO itself or the vendor).
• Type approval process for protection relays and functional requirements.
Page 44
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
10.8.10 Q.8.10 WHAT TESTS ARE PERFORMED DURING COMMISSIONING? ARE THE DONE
WHEN THE SUBSTATION IS IN OPERATION OR WHEN IT IS OUT OF SERVICE?
The answers to this question are quite different and therefore some tendencies are summarized.
For new substations the tests of BBP during commissioning are done when the S/S are out of service.
In case of commissioning of BBP in existing substation 7 TSO have stated that S/S is out of service
during commissioning of BBP. One TSO states that this is the best case. If not the bays are out of
service one after one other.
Different tendencies are:
• Due to extensive FAT (Q8.8) performed test are related to the interfaces: CBs, isolators
positions, CTs, telealarms going to the SCADA system, local alarms.
• Full test concerning both functional test and tests to the interfaces. Following test are usually
performed: power control, control of setting, control of protection functions and
characteristics bye test equipment, control of analogue and binary inputs, control of binary
output, control of signalization, tripping test, signalization of CBs and disconnectors, polarity
check of CTs by a primary power source.
A commissioning test includes some of or all of the following statements:
• Power control
• Control of settings
• Control of protection functions and characteristics by test equipment
• Test of breaker failure scheme on each bay
• Control of analogue and binary inputs
• Control of signalizations
• Tripping test
• Signalizations of CBs and disconnectors
Page 45
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
10.8.11 Q.8.11 DO YOU DO PRIMARY CURRENT INJECTION TESTS? IF YES THEN HOW? BY AN
OPERATION CURRENT OR BY A TEST EQUIPMENT?
It is remarkable that for the first commissioning for a new S/S or a new bay more than the half of the
TSO uses primary current injection tests done by test equipment before energizing. Some TSO use
primary current injection by a test equipment only for advanced protection schemes but mostly as a
part of standard commissioning.
10.8.12 Q.8.12 WHAT IS EXPECTED LIFETIME FOR DIFFERENT TECHNOLOGIES/WHAT ARE THE
FAILURE RATES OF THE EQUIPMENT/MAIN FAILURE MODES FOR DIFFERENT TYPE OF
BUSBAR PROTECTIONS? PLEASE GIVE SOME FIGURES IN CASE THEY ARE AVAILABLE.
Page 46
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
10.8.13 Q8.13. STATISTICS ABOUT NUMBER OF BUSBAR FAULT (PER SUBSTATION AND PER
YEAR)/ NUMBER OF UNWANTED TRIPS/AVAILABILITY
Please note that answers not are given in an uniform format:
• Some TSOs report numbers of substation for each voltage level others “x substations with
highest voltage 110 kV and y substations with highest voltage 400 kV” . In Question 4.1 TSOs
are asked for substation design issues but only for system 220 kV-400 kV. The problem is to
distinguish on this when statistics are made.
• Some TSOs use unit “number of busbar fault per substation” others “number of busbar fault
per substation”.
• Some TSOs have answered number of busbar faults per year and per substation, others
number of unwanted trips and others have answered both questions. It seems to some TSOs
only have statistics on unwanted trips.
In Figure 36 is shown years to busbar faults. Faulty trips (over-reaction) from busbar protection are
not included in this figure.
Figure 36: Number of busbar faults - Years to Busbar Fault. Faulty trips are not included
Page 47
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
Page 48
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
11 CONCLUSIONS
BBP is one of the most important protection devices which is installed on substations. It is the most
critical protection system due to its big impact for the system. The most important key factors
related with the correct function of BBP is the large amount of the affected elements that trip and
the necessity of the instantaneous tripping of the bus faults.
HV and EHV (220 kV and above) bars must be equipped with busbar protection phase segregated.
BBP realizes fast and selective tripping. Although BBP is quite expensive and complicated device, its
features may save equipment and even peoples live. Using BBP and CBF is also a necessity to assure
system stability.
The redundancy level should be a function to the critical clearing time: If this is less than typical
remote backup clearing times then busbar protection must installed.
The BBP protection should not trip for external faults. Check zone logic that covers the whole busbar
arrangement is recommended. Other reliability principles that support the functionality of BBP are:
the directional principle, the saturation detection, voltage and current release criterion, etc.
The protection should only trip the bar faulted section (selectivity). The protection should include
dynamic bus replica mechanism. When bad arrangement is detected the protection should alarm and
block.
Low impedance differential protection systems are preferred.
Centralized or decentralized types are equivalently used depending on the local conditions. The pros
and cons were given as they frame the design decision.
Local back-up protection (breaker failure protection) needed for busbar protection. When the busbar
protection is unavailable, if the critical clearing time of the substation is small, local back-up with
reverse zones of the line protection should be used.
Concerning planning great concern is devoted to the places of installation of BBP. There is a variety of
tactics. Most companies try to install as much as possible BBP and to avoid the clearance of the
busbar faults by the second zone of the distance relays.
Double busbar protection is not the rule. Setting procedure is managed and/or executed by the
companies. Commissioning and maintenance is made in a manner not to jeopardise the security of
the system.
High penetration of power electronics at the connection interface and the existence of GIS or AIS
substations are taken into consideration to the even more detailed and sound management of the
BBP.
Page 49
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu
European Network of
Transmission System Operators
for Electricity
12 BIBLIOGRAPHY
[1] Bogdan Kasztenny, Michael J. Thompson (2010). Breaker Failure Protection – Standalone or
Integrated With Zone Protection Relays? 37th Annual Western Protective Relay Conference,
(p. 13). USA.
[2] Caitlin Martin, Steven Chase, Thanh-Xuan Nguyen, Dereje Jada Hawaz, Jeff Pope, and Casper
Labuschagne (2013, rev. 2015). Bus Protection Considerations for Various Bus Types. 40th
Annual Western Protective Relay Conference, October 2013, (p. 10). USA.
[3] ENTSO-E. (2018). Best Protection Practices for EHV AC Transmission System. Brussels: ENTSO-E
site.
[4] Ken Behrendt, David Costello, and Stanley E. Zocholl (2008, 2010, 2013, 2016). Considerations
for Using High-Impedance or Low-Impedance Relays for Bus Differential Protection. 35th
Annual Western Protective Relay Conference,, (p. 18). USA.
[5] Lubomir Sevov, Bogdan Kaszten,Ed Taylor (2006). Commissioning and Testing Complex Busbar
Protection Schemes - Experience at Pacific Gas & Electric. 60th Annual Georgia Tech Protective
Relaying Conference, (p. 18). Atlanta, Georgia.
[6] Ziegler, G. (2005). Numerical Differential Protection. Erlangen: Publicis Kommunikations
Agentur GmbH.
[7] CIGRE No 431 Technical Brochure (2010). Modern Techniques for Protecting Busbars in HV
Networks.
[8] Armando Guzman, Casper Labuschagne & Bai-Lin Qin. (2015). Reliable busbar and breaker
failure protection with advanced zone selection. Schweitzer Engineering Laboratories, Inc.
Pullman, WA USA.
[9] Bogdan Kasztenny, Lubo Sevov & Gustavo Brunello. (2001). Digital low-impedance bus
differential protection-review of principles and approaches. College Station, TX.
[10] Steven Chase, Thanh-Xuan Nguyen, Dereje Jada Hawaz, Jeff Pope, and Casper Labuschagne.
Bus protection considerations for various bus types. Schweitzer Engineering Laboratories, Inc.
40th Annual Western Protective Relay Conference, October 2013
[11] R.Pellizzonni, L.Funes, R.Delorenzi, E.Dufur, P.D'Amore, I.Steinbrecher, E.Fernandez, E.Shiavino
(2010). Virtual busbar protection implemented with IEDs IEC 61850 from different vendors in a
132/33/13.2 kV SUBSTATION. CIGRE Paris, (p. 10).
[12] Zhang, R. (2018). User Experience and Current Practice with IEC 61850 Process Bus. CIGRE
2018 (p. 12). Paris: CIGRE.
[13] ΙΕΕΕ Std C37.234/2009 - Guide for Protective Relay Applications to Power System Buses
Page 50
ENTSO-E • Avenue de Cortenbergh, 100 • 1000 Brussels • Belgium • Tel +32 2 741 09 50 • Fax + 32 2 741 09 51• [email protected] • www.ENTSO-E.eu