Use and Maintenance Manual: Doc. No
Use and Maintenance Manual: Doc. No
Use and Maintenance Manual: Doc. No
PROGETTO: -
Co-Job: P08408
Date: April 2023
Sinergia SpA
Via Serio 29 – 24021 Albino BG - Italy
Tel. +39 035 0527200 Fax. + 39 035 0526085 www.sinergia-it.com
Use & Maintenance Manual i
INDEX
INDEX
INDEX i
LIST OF FIGURES v
LIST OF TABLES vii
1 PREFACE 1
2 GENERAL INFORMATION 3
2.1 MANUFACTURER 3
2.2 WARRANTY 3
2.2.1 Controversies 4
2.3 NOTES ABOUT THE PRESENT MANUAL 4
2.3.1 Characters and symbols 4
2.3.2 Target group 5
3 PRODUCT DESCRIPTION 7
3.1 TECHNICAL DATA 8
3.1.1 Skid baseplate 8
3.1.2 Dryer vessels 8
3.1.3 Cooler and condensate separator 10
3.1.4 Local control panel 13
3.1.5 Pilot air 13
3.1.6 Valves 14
3.2 CONDITIONS OF GUARANTEED PERFORMANCE 14
3.3 NOISE LEVEL 15
3.4 INTRINSIC RISKS 15
4 OPERATING PRINCIPLES 17
4.1 ADSORPTION 17
4.2 REGENERATION 20
4.2.1 Dehumidification 20
4.2.2 Depressurization 20
4.2.3 Stripping 20
4.2.4 Pressurization 21
4.2.5 Cooling 21
ii Use & Maintenance Manual
Dryer DHRD6000
LIST OF FIGURES
LIST OF TABLES
Table 2.1 Special meaning of characters and symbols used in the Manual 5
Table 3.1: Technical features of dryer vessels. 9
Table 3.2: Technical features of the cooler and condensate separator. 12
Table 4.1: Position of the actuated valves during the adsorbing phase in the column AT002 and regeneration
phase in the column AT001. 21
Table 4.2: Position of the actuated valves during the adsorbing phase in the column AT001 and regeneration
phase in the column AT002. 22
Table 6.1: Safety symbols used in the present manual. 32
Table 15.1: Main potential anomalies. 65
Table 15.2: Continuation of Table 15.1 66
Table 15.3: Continuation of Table 15.1 67
Table 16.1: Maintenance schedule prescribed by Sinergia for the main components of the dryer. 70
Table 17.1: Recyclable materials of assembled components. 78
Use & Maintenance Manual 1
PREFACE
1 PREFACE
The present Use and Maintenance Manual edited by Sinergia SpA is an important tool for a better
understanding of the dryer functionality, correct application and maintenance in compliance with its end use.
This Manual must be always available at the dryer location and permanently well kept on the plant to which it
is associated.
The personnel in charge of installation, use, maintenance and repair of plant components must consult this
Manual before the start of any activity, and scrupulously follow all the included instructions in order to avoid
any danger, damage to equipment and injuries to personnel.
This Manual does not take into account local regulations that, in any case, have to be strictly observed by the
personnel.
NOTE:
The Customer must be sure that the staff in charge of any activity on the dryer reads and
understands all the instructions.
Use & Maintenance Manual 3
GENERAL INFORMATION
2 GENERAL INFORMATION
2.1Manufacturer
2.2Warranty
The package warranty is twelve (12) months from the start-up or eighteen (18) months from the delivery,
whichever occurs first.
General conditions
SINERGIA S.p.A. warrants that the goods are new, never used, of good quality, free from defects of materials,
manufacturing or processing, and that they comply with the specifications, drawings and all provisions
specified in the agreement, as well as suitable for the agreed purpose.
All the supplied equipment is under the warranty of Sinergia S.p.A. Upon expiration of these terms the warranty
becomes null and void. For all the parts replaced, modified or repaired, the warranty period will be extended
for another 12 months from the date the repair, replacement or modification are completed.
In case of any claim regarding this warranty, the Buyer is to send a written request to the address of the Service
Department of Sinergia S.p.A (e-mail address: [email protected]), quoting the serial number of the
machine or the delivery note of the goods; if the components are under warranty and regular defects or flaws
are detected, Sinergia S.p.A. will repair or replace them with another part, at its own discretion and expense.
The warranty expires automatically if the Buyer fails to comply with the instructions in the User Manual provided
by Sinergia S.p.A. and in particular, with the instructions on storage, installation, maintenance, including the
obligation to use original spare parts. The warranty expires automatically when any operation of any kind is
carried out on the goods, by technicians not sent by or not authorized in writing by Sinergia S.p.A.
The warranty does not cover damages due to corrosion, erosion, normal wear and tear, errors in use,
overloading, performance and stresses beyond the limits indicated in the related manual, use different from
what has been agreed with the Buyer, recognized force majeure, faulty repairs, tampering and any operation
performed on the goods that does not fall within the agreed technical conditions.
4 Use & Maintenance Manual
Dryer DHRD6000
If the warranty for any reason whatsoever is not applicable, the intervention of Sinergia S.p.A., if required, will
be at the Buyer’s charge.
If the Buyer detects a non-conformity after the delivery and during the warranty validity, the Buyer shall notify
it to Sinergia S.p.A. promptly; the Buyer shall retain from carrying out any action on the equipment without the
explicit authorization of Sinergia S.p.A.
Sinergia S.p.A. shall be held liable for any damages directly caused by the malfunction of its machines only to
the limit of the value of the purchase order. It shall not be held liable in any way for any indirect or consequential
damages.
Warranty on performance
Sinergia S.p.A. ensures that the performance of the goods supplied complies with the terms stated in the order
and subsequent amendments approved in writing by both parties, if any.
If during the warranty period, the goods supplied do not retain the characteristics and performance required,
except for normal wear and tear, incorrect exercise and operation beyond the contract limits of the machinery,
Sinergia S.p.A. shall timely replace, repair, change or modify the goods supplied in order to restore their correct
operation.
Warranty on machines
During the warranty period, Sinergia S.p.A. agrees to execute promptly, at its own expense, all the operations
needed to disassemble, verify parts that are considered defective, repair and provide new components, if
necessary.
If it is necessary to intervene on the acquired equipment, the Buyer shall provide to Sinergia S.p.A., at its own
expense, the support in the form of both personnel and tools for the site activities.
NOTE:
Warranty is valid only if original spare parts are used and maintenance is carried out by technicians of
Sinergia S.p.A. or under the supervision and authorization of Sinergia S.p.A.
2.2.1 Controversies
Any disputes that might arise shall be under the jurisdiction of the court of Bergamo (Italy). Any issues not
explicitly clarified in these general warranty terms shall be solved as per the Italian Civil Code.
The present manual includes information about the assembled heatless dryer and its components designed
and constructed by Sinergia. Concerning the equipment supplied by external providers, it is fundamental to
refer to their associated manuals.
Table 2.1 Special meaning of characters and symbols used in the Manual
Character/Symbol Definition
NOTE:
It provides an advice to perform an operation as safe and
……………………………………………………
efficient as possible or an important remark
3 PRODUCT DESCRIPTION
3.1Technical data
The heat of compression desiccant air dryer (DHRD6000) is a hot regenerated dryer, which takes
advantage of the hot air coming from the compressor to regenerate the adsorbing material. The air for the
adsorption phase needs to be cooled. To this aim, the skid is equipped with a cooler followed by a separator
for condensate elimination.
For a detailed description of the dryer operating principle, see Section 4. In the following, the technical features
of the skid components are illustrated.
Furthermore, a post filter is loosed supplied, equipped with a drain valve and a differential pressure indicator.
NOTE:
In the following, the tags of the components will be indicated as in the P&IDs (APPENDIX B), with green
color. The General Arrangement (APPENDIX A) reports the general configuration of the complete dryer,
while the following tables illustrate the relevant features of the unit elements.
Corrosion allowances mm 1
The vessels have a cylindrical shape; the shell is 1750 mm long, with an external diameter of 1086 mm and
thickness of 6 mm. The shell has a head to both the extremities for a total vessel length of ~2616 mm. The
vertical overall dimension of the tank is ~2830 mm.
➢ flanged connection for desiccant material loading (N3), with blind flange;
➢ flanged connection for desiccant material unloading (N4), with blind flange;
➢ nozzle for pressure indicator (N5);
➢ nozzle for pressure transmitter (N6);
➢ nozzle for service (N7);
➢ lifting lugs;
➢ supporting legs;
➢ name plate (NP).
• shell;
• tube bundle;
• tube sheets;
• baffles.
The shell has a circular cross section with an external diameter of 323.8 mm and thickness of 9.53 mm. Its
overall longitudinal dimension is 1697 mm.
The tube layout pattern is triangular (30°) and the tube pitch (center-center distance of adjoining tubes) is
equal to 13 mm (minimum tube pitch of 1.25 times the tube outside diameter (O.D.)).
The tube bundles are secured at the inlet and outlet sides to the tube sheets.
Single segmental baffles are used to support the tubes and to enable a desirable velocity to be maintained
for the shell side fluid. They are responsible for obstructing and redirecting the flow of fluid in the shell side. In
fact, they direct the air through the shell so that it does not take a short cut through the shell side leaving
ineffective low air volumes. The baffles are fixed to the tube bundle (at 235 mm each other, except the lateral
ones which are 395 mm far-between) in order that the bundle is removable for maintenance. Furthermore, the
baffles are normal to the shell wall and force the steam to flow at right angles to the axis of the tubes. The
increased turbulence results in greater heat transfer. Moreover, the baffles help in keeping the tubes from
sagging and increase the strength of the tubes by preventing their failure by flow-induced vibration.
Downstream the cooler there is a condensate separator SEP001 where the condensate is separated from
the air stream.
The separator is designed taking advantage of the coalescing phenomena. The separator vessel includes a
demister to enhance the removal of liquid droplets entrained in vapor stream. This device assists the separator
vessel by increasing the gas liquid separation efficiency. In fact, an empty drum relies on high residence time
for separating liquid from vapor and requires high size. By using a demister pad, the degree of separation can
be achieved using smaller vessel dimension.
The separator is installed horizontally. The vessel has a cylindrical shape with an external diameter of 323.8
mm, thickness of 7.14 mm and a head at the opposite side with respect to the inlet flanged connection. The
demister is 150 mm long and it has a diameter of 303 mm, so that it intercepts all the inlet air. A stainless-steel
thread constitutes the wire mesh de-misting pad.
The accumulated condensate is removed through an automatic draining system.
The main features of the cooler and condensate separator are:
• design and reference codes are EN13445 and PED 2014/68/UE;
• main construction materials:
o shell: SA106 Gr.B;
o pipes: SA106 Gr.B;
o flanges and fittings: SA105;
o plates / baffles: SA240 Gr.TP 304;
o head / cap: SA2340Gr. WPB;
o demister: SA240 Gr. TP316L.
• receiving fluid for cooler: water at the shell side, air at tube side;
• receiving fluid for condensate separator: wet air;
12 Use & Maintenance Manual
Dryer DHRD6000
Unit of Value
Feature
measure Shell side Tube side
Min. admissible temperature MDMT @ the max pressure °C 2 @ 5 bar(g) -10 @ 10 bar(g)
Corrosion allowance mm 1 1
Referring to Figure 3.3, the cooler and the condensate separator are equipped with:
➢ a series of 349 parallel tubes installed inside the casing (tube bundle) for the passage of air to be
cooled;
➢ flanged connections for air inlet (N1);
➢ flanged connections for air outlet (N2);
➢ flanged connections for cooling water inlet (N3);
➢ flanged connections for cooling water outlet (N4);
➢ cooler drain/service nozzle (N7); the drain valve HV001 is normally closed;
➢ separator drain nozzle (N5) connected through the drain valve HV016 to the automatic and manual
condensate drains:
o automatic drain connected by the intercepting valve HV002 to the automatic valve XV015;
o manual drain connected by the intercepting valve HV015 to the drain valve HV003.
➢ service nozzles (N6).
Use & Maintenance Manual 13
PRODUCT DESCRIPTION
To perform, the cooler needs 14.499 lt/hr of cooling water at a maximum pressure of 5 barg and maximum
temperature of 35°C.
NOTE:
Actuated pneumatic valves require a pressure of 6.5 barg for proper operation.
14 Use & Maintenance Manual
Dryer DHRD6000
3.1.6 Valves
➢ Actuated valves:
The dryer is equipped with actuated valves to automatically manage the drying phases. These valves
are all double effect except the discharging valve XV012, stripping valve XV011 and cooling valve
XV013, which are single effect valves.
Note that the actuated single effect valves are coupled with a solenoid valve named as the actuated
valves, but with prefix XY instead of XV. The double effect actuated valves are coupled with two
solenoid valves named as the actuated valve, but with prefix XY instead of XV and suffix A or B.
➢ Automatic valve XV015 to automatically drain the condensate from the separator through the
automatic condensate drain.
➢ Drain valves:
o manual (normally open) valve HV002 to intercept the automatic drain;
o manual (normally closed) valve HV015 to intercept the manual drain valve HV003;
o manual drain valve HV001 to drain cooling water from the cooler;
o manual ball (normally closed) valve HV012 to drain/depressurize the lower points of the plant;
o manual (normally closed) valves HV012/HV013/HV014 to discharge drain from piping;
➢ hand control valve HCV001 to regulate the dried air outlet flow;
➢ hand valve HV006 to isolate pilot air;
➢ safety valves on each vessel (PSV001/002);
➢ check valve (CV001) to allow the correct direction of the air flow during the various drying phases;
➢ instrument isolation valves.
Sinergia guarantees the dryer performance under the following working conditions:
• inlet flow: 4993 Nm3/h;
• inlet pressure: 8.5 bar(g);
• inlet temperature: 130 °C.
Under previous conditions, the following values of main parameters are guaranteed:
• noise limit: 85 dB(A) @ 1m;
• outlet pressure: 8 bar(g);
• outlet flow: 4993 Nm3/h;
• dew point: -40 °C @ 8 barg.
Use & Maintenance Manual 15
PRODUCT DESCRIPTION
The machinery has been designed with all the available devices aimed to reduce as much as possible
produced noises and vibrations. Sinergia SpA makes its best effort to reduce the environmental pollution,
including acoustic impact due to its products, also thanks to the management system, certified ISO 14001.
The maximum measured level of continuous acoustic pressure pondered A at 1 m of distance from the dryer
is equal to 85 dB(A).
3.4Intrinsic risks
The machinery design and construction doesn’t take into account some aspects, whose in-observance could
cause both material damages and personnel injuries.
• Accidental loads:
the dryer is not designed against following accidental loads, which could compromise the safety:
o further loads located above the dryer;
o snow;
o rain;
o wind;
o seismic hazard.
• Fire:
the dryer is equipped with a safety valve installed on each vessel, which could discharge overpressure
due to temperature increase. It is not equipped with further firefighting.
• Accidental impacts:
the dryer is not protected against accidental impacts, that must be taken into account depending on
the installation area.
The Client must provide to remove the associated risks at the installation site.
Use & Maintenance Manual 17
OPERATING PRINCIPLES
4 OPERATING PRINCIPLES
The operating principles of the heatless dryer are illustrated below, following the fundamental phases of
exercise. See the P&ID (APPENDIX B) for details of equipment position mentioned in the following paragraphs
by green characters.
The adsorption and regenerating phases occur simultaneously in the two columns. While the “on line” tower is
adsorbing, the “off line” tower is regenerating. At the phase’s end, they automatically switch to complete the
column cycle.
The hot air coming from the compressor is directly used to regenerate the adsorbing material. Consequently,
it is delivered at the top side of the column, which is regenerating (AT001 or AT002) and crosses the adsorption
material bed (activated alumina). This phase is called dehumidification (or heating) and it is described in
Section 4.2.1.
After the dehumidification, while the adsorbing process is going on in one column, the depressurization,
stripping, pressurization and cooling phases follow one other in the regenerating column. Note that, during
the depressurization, stripping, pressurization and cooling phases the air used for the adsorption is that coming
from the compressor and cooled by the cooler AC001.
The process and the air path during these phases are described in the Sections 4.2.2 - 4.2.5.
At the end of the adsorption / regeneration phase, the column phases automatically exchange. Note that the
phase duration is defined, as described in Section 4.5.
In the following, the process description assumes the column AT002 in adsorption and the column AT001 in
regeneration.
4.1Adsorption
During the adsorption process, the inlet air enters in the “on line” tower from the bottom and flows up through
the desiccant bed, so that the moisture content adheres to the desiccant surface. Due to the system upset, the
condensate is kept away from the desiccant and remains at the bottom of the tower from where it can be easily
exhausted during the regeneration cycle.
18 Use & Maintenance Manual
Dryer DHRD6000
The air required for the adsorption phase needs to be cooled. To this aim, the air is conveyed from the bottom
connection of the regenerating column to the cooler AC001, able to reduce the inlet temperature thanks to
cooling water, which shall be supplied at the temperature of 25 °C. At this point, the condensate included in
the air is partially separated thanks to the condensate separator SEP001 installed downstream the cooler
and it is drained by the drain valve HV002.
In the following, the cooled air is delivered to the bottom of the column in adsorption. As it flows up through
this “on line” tower, its moisture content adheres to the desiccant surface and it is retained within the required
dew point value (see Section 3.2). Dry compressed air is then released from the top of the column to the outlet
line. The outlet air temperature is controlled by the temperature transmitter (TT004).
Figure 4.1 shows the path of compressed air from the inlet point to the outlet one during the adsorption phase
of column AT002 (the left one) and the regeneration phases of the column AT001 (the right one). The position
of the actuated valves is specified in Table 4.1.
Note that the inlet temperature is controlled by the temperature transmitter TT001. If the temperature is too
low (100 °C) for the dryer efficiency an alarm shall trigger (at Client’s charge).
The temperature before and after the cooler is monitored respectively by the temperature transmitters TT002
and TT003. If the air is not sufficiently cooled namely, the temperature monitored by the temperature
transmitter TT003 exceeds 46 °C an alarm shall trigger ((at Client’s charge)).
The pressure of the dried air downstream each column is monitored by the pressure transmitters PT001/002.
If the pressure is too low, namely below 4 bar(g), the dryer cannot operate; consequently, an alarm shall trigger
((at Client’s charge)).
At the outlet, the dried air temperature is monitored by the temperature transmitter TT004. A maximum
temperature of 70 °C is allowed, on the contrary an alarm shall trigger ((at Client’s charge)).
Use & Maintenance Manual 19
OPERATING PRINCIPLES
IA
LEGEND:
Wet hot air
Wet cool air
Dried air
Figure 4.1: Air path during the adsorption phase of the tower AT002 and the dehumidification phase of the tower
AT001. The valve position is specified in Table 4.1.
20 Use & Maintenance Manual
Dryer DHRD6000
4.2Regeneration
Regeneration (purging or “off-line” cycle), is the process by which moisture accumulated during the “on line”
cycle (adsorption) is stripped away.
The regenerating phases are described below.
4.2.1 Dehumidification
During the dehumidification, the hot air coming from the compressor is delivered to the column that is in
regeneration phase (AT001), particularly it enters into the column from the top side. As the air flows gently
through the regenerating bed, from the top to the bottom of the tower, it attracts the moisture accumulated on
the surface of the desiccant during the adsorption phase. At the column outlet, the air is cooled prior to be
conveyed to the column in adsorption. The cooler operation is described in Section 4.3.
The path of compressed air from the inlet point to the outlet one during the dehumidification phase of the
column AT001 (the right one) and the simultaneous adsorption phase in the column AT002 (the left one) is
shown in Figure 4.1. The position of the actuated valves is specified in Table 4.1.
4.2.2 Depressurization
During this phase, the hot air coming from the compressor is directly delivered to the cooler AC001 in order to
be used for the adsorption in the column AT002. Simultaneously, the column AT001 is depressurized, namely
the pressure inside the tank is discharged into the atmosphere through the valve XV012 and the silencers
AM001/002, dragging outside part of the moisture entrapped into the adsorbing material.
The air path during the depressurization phase of the column AT001 (the right one) and the simultaneous
adsorption phase in the column AT002 (the left one) is shown in Figure 4.1. The position of the actuated valves
is specified in Table 4.1.
Expansion phase ends when the vessel pressure equals the atmospheric one.
4.2.3 Stripping
To improve the regeneration of the desiccant material, and thus the dryer efficiency, the depressurization is
followed by the stripping phase. A percentage of dried air (purge air) is removed from the dried outlet flow and
delivered to the regenerating tower to remove the last little bit of moisture entrapped into the regenerating bed.
This allows the achievement of low dew point values.
A percentage of purge air (see Section 3.2) is delivered through the stripping valve XV011 to the top of the
column in regeneration (AT001).
The moisture evaporates tanks to the dried air stream, and it is discharged to the atmosphere through the
valve XV012 and the silencers AM001/002.
The air path from the dryer inlet through the cooler AC001, the condensate separator SEP001 and the
adsorbing tower AT002 is the same as during the depressurization phase of column AT001. The air path during
the stripping phase of the column AT001 and the simultaneous adsorption phase in the column AT002 is
shown in Figure 4.3. The position of the actuated valves is specified in Table 4.1.
Use & Maintenance Manual 21
OPERATING PRINCIPLES
4.2.4 Pressurization
After the stripping phase, the column in regeneration (AT001) is bringing back to the working pressure to avoid
pressure oscillations on the network when it is switched to the adsorption phase. To this aim, the actuated
discharge valve (XV012) closes themselves off. The air path during the pressurization in the column AT001 is
the same shown in Figure 4.3, with the valve XV012 closed. The position of the actuated valves is specified in
Table 4.1.
When the pressure reaches the working value (monitored by the pressure transmitter PT001), the regenerated
column is ready to be cooled and to start a new adsorption cycle.
4.2.5 Cooling
At the end of the stripping and the pressurization phases the cooling cycle valves open. The cooling phase
reduces the temperature of the adsorbing material prior to the column shift. This process, combined with the
stripping phase, provides extremely low dew points and temperature fluctuation during the tower shift.
During this phase, a percentage of dried air (purge air) is removed from the dried outlet flow and delivered to
the regenerating tower (AT001) through the cooling valve XV013; particularly it crosses the tower from the
bottom to the top. The cooling air pressure is monitored by the pressure transmitter PT004.
The air path during the cooling in the column AT001 is shown in Figure 4.4, while the position of the actuated
valves is specified in Table 4.1.
Table 4.1: Position of the actuated valves during the adsorbing phase in the column AT002 and regeneration
phase in the column AT001.
22 Use & Maintenance Manual
Dryer DHRD6000
At the end of the cooling phase, the column AT001 that was in the regenerating process is automatically
switched to adsorption and vice versa.
For completeness, the position of the actuated valves during the adsorption phase of column AT001 and the
regeneration phase of the column AT002 is specified in Table 4.2.
Table 4.2: Position of the actuated valves during the adsorbing phase in the column AT001 and regeneration
phase in the column AT002.
Use & Maintenance Manual 23
OPERATING PRINCIPLES
LEGEND:
IA
Wet hot air
Wet cool air
Dried air
Figure 4.2: Air path during the adsorption phase of the tower AT002 and the depressurization phase of the tower
AT001. The valve position is specified in Table 4.1.
24 Use & Maintenance Manual
Dryer DHRD6000
LEGEND: IA
Wet hot air
Wet cool air
Dried air
Figure 4.3: Air path during the adsorption phase of the tower AT002 and the stripping phase of the tower AT001.
The valve position is specified in Table 4.1.
Use & Maintenance Manual 25
OPERATING PRINCIPLES
IA
LEGEND:
Wet hot air
Wet cool air
Dried air
Figure 4.4: Air path during the adsorption phase of the tower AT002 and the cooling phase of the tower AT001.
The valve position is specified in Table 4.1.
26 Use & Maintenance Manual
Dryer DHRD6000
4.3Cooler operation
The plant includes the cooler described in Section 3.1.3. Its aim is to cool the inlet air using cooling water. The
inlet and outlet temperature of both air (tube side) and water (shell side) are specified in the Table 3.2.
The hot inlet air enters into the cooler by the flanged connection N1 and it is delivered to the tube bundle
through the tube sheet. At the same time, the cooling water enters into the cooler shell through the flanged
connection N3, which is installed on the shell at the opposite extremity with respect to N1 in order to have the
countercurrent flow of the fluids.
The two fluids enter into close contact through the tube bundle and the baffles. In fact, while the air flows into
the tube bundle, the water runs countercurrent into the shell, over the outside surfaces of the tubes, adsorbing
a part of the air heat content. Consequently, the air cools, reaching the desired outlet temperature. The cooled
air is delivered to the plant through the outlet flanged connection N2, while the heated water flows off to the
water discharge through the flanged connection N4, installed on the opposite side of the shell.
The cold air enters into the condensate separator, installed downstream, through the flanged connection N1.
The demister installed at the separator vessel inlet intercept all the flowing air.
This device works by coalescing smaller liquid droplets by obstructing its path. Obstruction of path causes
increased collisions among the liquid droplets. Most of these droplets stick together and constitute bigger
droplets that are too heavy to rise with the gas stream. Thus, the bigger liquid droplets (and other foreign
particles) drop down in bottom of the shell. The gravity facilitates this process. The obstruction in the path does
not affect the gas stream, which escapes through the air outlet (N2). The air flux delivers the condensate
particles along the bottom side of the shell to the drain manhole from where they are drained. The opening
and closure times of the solenoid valve are managed from control system.
4.5Phase duration
The desiccant material quantity has been designed to have a minimum regeneration cycle period.
The dryer operates in “fixed time mode”, namely the duration of the various drying phases is fix. The
manufacturer suggests to set a total cycle period of 480 minutes:
• adsorption: 240’;
• dehumidification and depressurization: 90’;
• stripping: 90’;
• pressurization and cooling: 60’.
The moisture loading is affected by inlet temperature, pressure, relative humidity and flow. These conditions
vary throughout the day and rarely combine perfectly to produce maximum moisture loads. An inlet
temperature drop can significantly reduce the moisture load. Dryers are sized for “worst case scenario”
operation, with the fixed time control mode to accommodate maximum moisture loads, but since a fixed
duration cycle does not compensate for fluctuating loads, energy is wasted by regenerating more often than
necessary.
Use & Maintenance Manual 27
OPERATING PRINCIPLES
The dew point control mode is designed to adjust the energy use necessary to actual moisture load. Dew
point control eliminates the unnecessary use of energy by delaying regeneration until the total design moisture
load is achieved. Under dew point control, adsorption and regeneration cycles switch based on the dew point
value. Particularly, at the end of the regeneration phase, if the dew point value is still good, the dryer stays in
standby. When the dew point becomes worse, namely higher than the set point, the regeneration phase starts.
Use & Maintenance Manual 29
CONTROL SYSTEM
5 CONTROL SYSTEM
6 STAFF SAFETY
The dryer is designed and constructed in compliance with the most recent safety regulations. Nevertheless,
the personnel in charge of any activity on/with the machinery have to pay attention and comply with the safety
instructions prescribed in the present manual.
DANGER!
Danger due to incorrect behaviour!
Minor or relevant components damage and personnel injuries could be due to:
• not-observance of safety instructions;
• activity carry out by non-qualified personnel;
• machinery not use within design specifications;
• product modifications not authorized by the Manufacturer;
• incorrect maintenance.
Personnel must wear proper Personal Protective Equipment (PPE) depending on the performing activity. In
the manual, referring to the described activity, proper PPE are suggested. However, standard safety
regulations must be obeyed.
From a safety point of view, the unit must be daily inspected, to ensure that operating conditions are safe and
eventually intervene to reestablish the dangerous ones.
6.1Safety symbols
Symbols used in the present manual to indicate potential hazards and prescription of Personal Protective
Equipment (PPE) are listed and illustrated in Table 6.1. This table indicates also the activities during which
personnel must obey obligatory instructions and must pay attention to potential hazards.
32 Use & Maintenance Manual
Dryer DHRD6000
On the equipment, hazard or relevant parts are indicated by proper symbols. They indicate:
• electrical supply on the control panel;
• earth lugs on the baseplate;
• lifting eyebolts at baseplate corners;
• hot surfaces of columns and piping upstream the cooler.
The safety symbols located on the skid are indicated in the General arrangement drawing (APPENDIX A).
Clear misuse is the use of dryer components as climbing aid. Pipes, valves and other elements are not
designed to that aim; they could fracture or became damaged.
6.4Safety devices
The machinery has been designed with particular attention to safety. In fact, it is equipped with:
➢ safety valve installed on each dryer column (PSV001/002) set to 10 barg and with discharge in air
environment;
➢ couple of silencers (AM001/002) to discharge regenerating air;
➢ insulating coating 30 mm thick of columns (AT001/002) against surface hot temperature.
6.5Residual risks
Although risks have been reduced as far as possible with accurate design and construction, some residual
risks persist.
• Discharge of air under pressure:
o the unit is equipped with pressure safety valves installed on the columns against the risk of blast
due to too high overpressure. However, risks of safety valve discharge persist, although they
are directed in safe areas, at a height of about 3 m.
o although two silencers (AM001/002) are installed, during the depressurization phase the
discharge of air under pressure generates a strong and sudden noise (see Section 3.3).
• Sliding:
spilled desiccant agent beads on the floor during desiccant material emptying and filling could cause
sliding.
• Burn:
due to the high temperature of the compressed inlet air, the vessel and piping external surface could
reach burning temperatures (> 65 °C). Although the vessels are insulated by stone wool, some parts,
i.e. the upper and lower part of the vessels (heads), the lining clamping screws and/or nozzles or
flanged connections could stick out from the isolation. Connecting piping upstream the cooler could
also reach burning temperatures; these surfaces are indicated on the skid by proper pictograms.
Further residual risks which characterize the various life phases of the machinery are listed in the associated
following sections by “danger advises”.
NOTE:
The machine is designed to always guarantee a free path for the air passage between skid inlet and outlet,
to avoid risks resulting from overpressure. In case of emergency stop or blackout the valves remain in
position.
It is responsibility of the user to ensure correct installation of valves, shut-off devices and safety devices
upstream and downstream the skid, in order to avoid risks deriving from overpressures.
34 Use & Maintenance Manual
Dryer DHRD6000
In case of restart after a prolonged shutdown or shutdown for maintenance activities, the user has the
responsibility to verify the position and status of the shut-off valves / devices installed upstream and
downstream of the skid.
During normal operation, personnel is allowed staying on the panel side at the floor level.
In case of maintenance activities that require elevated positions, the operator cannot use any components as
support. A proper ladder or gangway must be adopted.
WARNING!
Prior to start any maintenance activity, wait 60 minutes from the machine shutdown in order
to let it cool down.
Attention must be paid to the discharges of safety valves. They are located at elevated position (about 3 m),
but during inspections or maintenance activities of the highest parts of the dryer, personnel must never stay in
front of them, except if the dryer is not under pressure.
Furthermore, pay attention to air discharge from the silencers during depressurization; pressurized air
violently ejected could cause severe injuries to eyes and/or skin, while strong and sudden noise could cause
damages to the auditory apparatus.
Use & Maintenance Manual 35
LIFTING AND TRANSPORT
7.1Loading/unloading
The package must be moved by a crane with sufficient payload, using a suitable lifting beam.
Details for lifting, namely hoisting scheme and weight (~8000 kg) indicated in the General Arrangement
drawings (APPENDIX A).
DANGER!
Danger due to improper lifting/handling!
• Lifting/handling and loading/unloading must be performed by qualified and
authorized technicians. Incorrect activity can cause material damages and
personnel injuries.
• Use proper lifting equipment in regular state and with sufficient payload.
• Ensure that the lifting / tie down points are used whenever the skid is lifted or
transported. Incorrect lifting could cause material damages and personnel
injuries.
• Keep the skid always in upright position to not compromise the efficiency.
• Do not work on or walk under the units while they are suspended.
7.2Transport
WARNING!
Danger due to incorrect transport!
• Transport must be performed by qualified and authorized technicians. Incorrect
activity can cause material damages and personnel injuries.
• Accurately ensure and safeguard the units.
• Do not place further loads over the packages: they could cause material damages.
The packages are not designed for mechanical loads.
• Keep the units always in upright position, except the air receivers, which are
packaged and transported in horizontal position.
• Obey safety precaution. In-observance can cause material and/or personnel
damages.
NOTE:
Sinergia declines any responsibility for damages caused by not correct transportation beyond the scope
of supply.
In case the packing and/or the units have been damaged during transportation, both the hauler and the
manufacturer must be urgently contacted, and a written report of damages must be sent to the Manufacturer.
WARNING!
Danger due to damaged components!
Do not put in operation a damaged unit: damaged components could cause working
anomalies and/or other damages.
Use & Maintenance Manual 37
PACKAGING
8 PACKAGING
Sinergia supplies a seaworthy package sufficient to withstand, for land/sea and outside storage for twelve (12)
months, handling during loading/unloading, sea and inland transport, outdoor storage, exposure to high
humidity, extreme temperature, salt, precipitation.
The type of packaging provided is a ISPM15 fumigated and marked wooden box coupled with sac barrier,
coex cover and dehydrating salts included.
Therefore, equipment and materials are protected against both mechanical damages (shocks, rupture,
breakage, loss) and corrosion (rain, salty atmosphere, sand, etc.).
Dimensions, weights, volumes and main handling information as stackability and storage class are indicated
in the packing list.
NOTE:
• •Never superimpose the boxes one over the other one.
• •NEVER place heavy packages on other packages and ensure to not exceed the load capacity of the
supporting floor.
Use & Maintenance Manual 39
STORAGE
9 STORAGE
In case it is necessary to store the supplied units, in any case the storage place should satisfy the following
general conditions:
• during the guaranteed period (12 months) of the supplied packaging, it can be stored outdoor; after this
period, follow the prescription of “long term storage” below;
• flat surface isolated from the ground (by a concrete cover to avoid moisture) and external vibrations;
• safe zone.
NOTE:
• •Required activities to guarantee unit protection during storage as indicated below shall be performed
by specialized packers and a report including pictures and operation description shall be issued;
otherwise, packing warranty decays.
• NEVER place heavy packages on other packages and ensure to not exceed the load capacity of the
supporting floor.
In case of temporary storage (less than 12 months from packing), the main concern is protection from weather
agents.
a) Before the installation, components must be preserved in their original packaging. During storage it is
important to check monthly:
• condition of dehydrating material through the humidity indicator installed on barrier bags. If packing
humidity indicator indicates high humidity, replacement of dehydrating material inside the packing is
required. To this aim specialized packers must:
alternatively, if the previous step cannot be performed because the original packing is damaged or
not specialized technicians are available, apply a new specific long term storage packing, as for
instance:
- sack-coupled barrier (film composed by layers of high density polyethylene, aluminum foil and
polyester or Valeron film). To protect the machinery against moisture, it must be vacuum-
sealed, namely the barrier bag has to be hermetically sealed, so that it comes in the package
by creating a vacuum that reduces the volume of contained air. With the aim of absorbing
moisture in the air at the time of closing, a correct quantity of new desiccant bags of dehydrating
salts have to be included (hanged up at the upper parts of the skids) in the package. Then, the
unis shall be protected by a wooden box.
- Vapor Corrosion Inhibitors (VCI) packaging. Adopting this method, an invisible layer of
protection against corrosion is due to the volatile active substances that evaporates from the
support material and condenses on the free surface of the metal in a molecular layer. This type
of protection can be adopted alone or integrated with other packaging. Then, the unis shall be
protected by a wooden box.
if the specific long-term packing cannot be performed, hang up enough sachets of dehydrating salt
as previously detailed. Then, protect the units with a lorry tarpaulin accurately wrapped and store
indoor for a maximum period of six months. Ensure minimum temperature of +2 °C to avoid ice
formation;
ensure the units against potential accidental impacts by protections and information signs;
issue a report including pictures and job description.
b) In the case of temporary storage of the skids during the plant life, due to the disconnection from the
external plant, after shutdown and depressurization, it is fundamental to:
accurately clean and dry all the components and equipment, included internal surfaces of piping,
tanks and any shell subjected to pressure under operation;
drain accumulated condensate from all condensate drains, clean and dry drainage systems;
ensure that everything is in good condition and not damaged; in contrary case, substitute or repair
following the Manufacturer’s prescriptions;
plug all flanged and threaded opening with bolted plugs or blind flanges with gaskets;
concerning the single supplied components follow the storage prescriptions listed below and
suggested by the relative Manufacturers in the associated Manuals;
Use & Maintenance Manual 41
STORAGE
place a suitable quantity of vapour corrosion emitters (VCI) inside the Local Control panels and tape
openings to minimize air infiltration;
During long-term storage, it is fundamental also the prevention of external and internal surfaces of components
from corrosion that could be caused by condensation of air moisture due to changes of ambient temperature
from day to night and due to season succession. To this aim, anti-corrosion and anti-rust protections must
be adopted in addition to the prescriptions for the temporary storage.
a) In the case of required long storage of the skids before the installation (namely, in the case the skids are
still packaged so as they were packed in the Sinergia’s factory) it is necessary to:
follow the first six steps for the short-term storage;
accurately unpack, cut the sac-barrier, remove the original dehydrating sachets;
inspect the skids to ensure component integrity and not corrosion evidence;
fill the skids of nitrogen.
Prior to fill the plant:
- ensure closure of the drain (HV002/003/012) valves;
- close all open connections with blind flanges or threaded plugs with gaskets, except the filing
ones.
- install pressure gauges at the filling connections to monitor the nitrogen pressure.
To fill:
- suck trapped air and fill with nitrogen; the oxygen content must be less than 2% of the volume
measured at the flushing outlet and the nitrogen pressure of 0.3÷0.35 barg.
WARNING!
When filling with nitrogen is required, ensure that the operation is carried out safely for both
the personnel and the components to be filled. This implies, but it is not limited to:
- ensure that the area is adequately ventilated, in order to avoid risk of suffocation in
case of nitrogen leakages;
- check for leakages all the plugged connections;
- limit the potential overpressure risks, employing a suitable pressure regulator (or an
equivalent device) between the package to be filled and the nitrogen supply (depending on
the pressure of the nitrogen supply).
42 Use & Maintenance Manual
Dryer DHRD6000
- concerning the single components installed on the skids, follow the long-term storage
prescriptions listed below and suggested by the relative Manufacturers in the associated
Manuals;
replace the dehydrating salts inside the packing and re-close the packing or apply a new packing,
following the indications provided for short terms storage at point a. Note that the dehydrating salt
status conditions shall be checked every month and replaced every twelve (12) months (since last
salt replacement);
if the specific long-term packing cannot be performed, hang up enough sachets of dehydrating salt
as previously detailed. Then, protect the units with a lorry tarpaulin accurately wrapped and store
indoor for a maximum period of six months;
never seal wood or other high moisture cellulose products in a barrier bag;
exposure of finished and unfinished surfaces to hygroscopic materials or materials that contain
moisture must be avoided unless proper precautions are taken;
check monthly the dryer nitrogen filling pressure (0.3-0.35 bar(g)) on the dedicated pressure gauge
accessible through a dedicated opening in the wooden crate; If nitrogen pressure is lower than 0.3
barg, it is necessary to refill the plant. Consider the safety prescriptions listed in Temporary storage,
point a);ensure the packaging against potential punctures (e.g. by wooden braces);
ensure the packaging against potential accidental impacts by protections and information signs.
b) In the case of long storage of the assembled skids during the plant life, due to the disconnection from the
external plant, it is necessary to:
follow the first eigth prescriptions for the temporary storage (point b);
inspect the skids to ensure component integrity and not corrosion evidence;
remove the filtering cartridges from the filters;
accurately clean and dry all the components and equipment, included internal surfaces of piping,
tanks and any shell subjected to pressure under operation;
apply a new long storage packing or protections as described above at point a of short term storage.
check monthly the nitrogen filling pressure (0.3-0.35 bar(g)) on the dedicated pressure gauge
accessible through a dedicated opening in the wooden crate and eventually refill following the same
indications and prescriptions of the Temporary storage, point a).
Once the 12 months of guaranteed storage in the original packing are expired, pay attention to the storage
prescriptions for the following main components.
Use & Maintenance Manual 43
STORAGE
• Spare parts:
- Follow the prescriptions of the safety sheets if available;
- store provided components in their original sealed packaging, indoor, in a closed, dry and
protected site;
- add sachets of dehydrating salt (or silica gel) in the containing boxes.
• Electrical panel:
- apply vapor corrosion emitters inside the cabinet. As a limit alternative, include new sachets of
dehydrating salt (or silica gel) to adsorb humidity; hang up the salt sachets in the upper part of
the cabinet to avoid the water (which could accumulate at the bottom of the panel) contact,
which could induce corrosion. Regularly verify the adsorption capacity of the sachets;
- tape openings to minimize air infiltration;
- If disassembled from the skids, store indoor, in a closed and dry site, isolated from the ground,
protected against potential accidental impacts and wrapped with a plastic sheet or a tarpaulin.
• Small parts (threads, valve stems, flange mating faces, nuts and bolts, machined surfaces,…):
- store indoor, in a closed and dry site, isolated from the ground and protected against potential
accidental impacts;
- apply corrosion preventive compound;
44 Use & Maintenance Manual
Dryer DHRD6000
NOTE:
If the suppliers of various products prescribe specific behaviors for the material storage, they have the
priority over the previous ones.
For any doubt, contact Sinergia.
Sinergia declines any responsibility for damages due to improper storage.
Use & Maintenance Manual 45
DELIVERY TO SITE
10 DELIVERY TO SITE
At the installation site, all the units must be unloaded as close as possible to the dedicated area in order to
minimize any probability of equipment damage.
All the prescriptions described in Section 7 regarding the lifting are valid also for the unloading, thus refer to
that section for details.
10.2Receiving Inspection
Upon arrival at the final destination site, goods, shall be inspected for signs of transport damage.
WARNING!
Danger due to unpack!
Pay attention to not damage the unit with the instruments used to unpack it.
10.3Preservation
11 INSTALLATION
WARNING!
Danger due incorrect installation!
• The dryer installation must be performed by qualified and authorized technicians.
Incorrect installation could cause material damages and/or personnel injuries.
• Never stay below suspended loads.
• NEVER left tools or other objects on the units; they could fall and cause damages.
Site conditions have a high influence on the plant efficiency. In order to guarantee its operation as efficient and
continuous as possible, and with minimum maintenance, the installation site must respect the design
conditions, in agreement with the Customer’s requirements or, in any case, it must be characterized by features
less hazardous (to the operation) than the design ones.
The installation must be a safe area, indoor, with minimum allowable temperature of 2 °C and adequately
accessible for maintenance activity.
The units can be installed on any level floor with sufficient payload. A dry, well-ventilated area where the
atmosphere is as clean as possible is recommended.
If necessary, the plant components must be preserved by suitable devices from pulsations of compressed
air and transmitted vibrations.
When the ambient conditions other than the design levels listed above are encountered, contact the Supplier
for additional information.
NOTE:
For any doubt, explanations and/or support concerning installation contact Sinergia SpA.
48 Use & Maintenance Manual
Dryer DHRD6000
The Customer must provide for removal of some risks at the installation site:
• Blast:
it is important to install the skid far from components/systems at risk of explosion, which could
compromise both machineries and personnel.
• Fire:
it is important to install the skid far from components/systems at risk of fire, which could compromise
both machineries and personnel, and have a suitable fire prevention system.
NOTE:
Note that, in case of fire, fire extinguishers suitable for devices under tension have to be used.
• Accidental impacts:
the units are not protected against accidental impacts, which could induce relevant damages.
Consequently, it is fundamental to safeguard them against moving means, which could operate at the
installation site, nearby the machinery, as for instance:
o trucks;
o fork lifts;
o cranes;
o etc…
WARNING!
To prevent the risk of burn due to high temperature of the upper and lower parts of columns
and the piping upstream the cooler during operation of the dryer, Sinergia suggest to install,
during installation activities, an insulating coating on the above-mentioned parts.
Alternatively, if the previous activity cannot be performed, Sinergia prescribes the installation
of the machine in a fenced area, not accessible during normal operation of the dryer, and
equipped with protections conforming to EN 13857.
NOTE:
Sinergia declines any responsibility for damages due to blast, fire or accidental impacts.
Use & Maintenance Manual 49
INSTALLATION
11.3Mechanical installation
11.3.1 Foundation
The units must be positioned securely and on a stable foundation. Any risk of movement should be removed
by suitable means, especially to avoid strain on any rigid discharge piping.
The foundation is at Customer’s charge. Sinergia provides the necessary indications for design and
construction, namely operating loads, location of the anchor points and fixing system, as shown in the General
arrangement drawing (APPENDIX A). The anchoring system is shown in Figure 11.1; it requires drilling holes
( 18 mm) in the foundation concrete.
level the skid. This step is critical and of fundamental importance. It must be performed by qualified
personnel using a machinist level, an industrial laser or an optical level located on the top frame of
the baseplates;
WARNING!
To prevent entry of dust, debris or water during assembling/connecting activities, maintain
sealed the plugs/enclosures installed prior the transport to cover all flanged and threaded
openings, instrument and electrical devices.
It is fundamental to ensure removing of plugs only at the realization of each connection. The
original plugs should be stored for potential future use.
Furthermore, prior to the installations/connections ensure that nothing is included into the
connecting piping.
The installation must follow the P&IDs (APPENDIX B) and the general arrangement (APPENDIX A).
NOTE:
Plant tie-in points (TP n. X) are tagged, as per P&ID.
Furthermore, the post-filter F001 loosed supplies shall be connected by tie-in points TP n. 7 AND TP n. 8.
NOTE:
Any ladder is supplied to reach the elevated parts of the skid.
Use & Maintenance Manual 51
INSTALLATION
11.4Electrical installation
DANGER!
Presence of electrical supply!
Risk of electrical shock.
Danger due to improper electrical connection!
• Electrical connections must be performed by qualified personnel and under the
direct responsibility of the Customer. Incorrect installation can cause material
damages and/or personnel injuries.
• Installation must be in accordance with recognized electrical codes and any local
Health and Safety Codes.
• Keep all parts of the body and any hand–held tools or other conductive objects, away
from exposed live parts of the compressor electrical system.
• Connect the units only to electrical systems that are compatible with their electrical
characteristics and that are within their rated capacity.
• Feeder cables must be sized by a competent electrical engineer to meet all power
requirements.
Sinergia provides the signals to the terminal block of the supplied panel.
The Client shall realize the control panel and provide the power supply.
For details about the panel wiring, refer to the Local Control Panel electrical diagram in Local control panel
wiring diagram (APPENDIX D).
Furthermore, the Client shall perform the earth connections: earth cables (yellow-green cable) must be
connected to the specific ground lugs, whose location is indicated by the corresponding symbols in the General
arrangement drawing (APPENDIX A), in the particular drawings, and on the equipment.
WARNING!
Danger due to ground connection!
• Use indicated terminals for ground connections.
• Lack of earth connection can cause material damages and/or personnel injuries.
52 Use & Maintenance Manual
Dryer DHRD6000
NOTE:
Sinergia prescribes the installation of a protection system (e.g. surge protection device) against fulmination
on power lines.
NOTE:
Sinergia declines any responsibility for damages due to incorrect installation.
Use & Maintenance Manual 53
START-UP
12 START-UP
Start-up phase is planned by the Manufacturer, following a detailed procedure defined and agreed with the
Client. In the following, main aspects are reported.
This phase must follow the “ready for start-up” certificate issue.
NOTE:
Dryer start-up must be performed by specialized staff, either technicians of Sinergia or third parties
authorized by it, otherwise, Sinergia’s warranty decays.
In order to transfer smoothly the plant from Sinergia to the Client, final operators in charge of any activity
on/with the machinery should assist the Commissioning team.
NOTE:
The machine is designed to always guarantee a free path for the air passage between skid inlet and outlet,
to avoid risks resulting from overpressure. In case of emergency stop or blackout the valves remain in
position.
It is responsibility of the user to ensure correct installation of valves, shut-off devices and safety devices
upstream and downstream the skid, in order to avoid risks deriving from overpressures.
In case of restart after a prolonged shutdown or shutdown for maintenance activities, the user has the
responsibility to verify the position and status of the shut-off valves / devices installed upstream and
downstream of the skid.
12.1Document compilation
During Start-up, staff must note relevant aspects useful for the definition of the first start-up sequence and
procedure.
At the end of the start-up sequence, Start-up staff must issuance:
• certificate of ready for operation;
• punch list updated and closed.
Previous documents will be included in the start-up dossier.
Specific activities required to prepare pressurization and to bring the plant in operation must be performed:
• establish the list of available equipment;
• perform audit and technical reviews required for the issuance of the “ready for pressurization” certificate;
• check that all punch list items are clarified and treated accordingly. Verify that the punch list is updated
and closed;
• ensure safety equipment and critical utilities availability and reliability;
• issuance of the “ready for pressurization’’ document.
Once the “ready for pressurization’’ activities have been performed, pressurization, turn on and tests must
be performed.
Use & Maintenance Manual 55
START-UP
DANGER!
Automatic starting machine!
Incorrect start-up can cause material damages and/or personnel injuries.
Potential discharge of pressurized air!
• Air under pressure could be discharged; particles included in the air could be
violently ejected causing severe injuries to eyes and/or skin!
• During the expansion phase of drying process, the pressurized air is discharged
from the silencer generating a strong and sudden noise; it can cause damages
to the auditory apparatus;
• In emergency case, the safety valves installed on vessels can discharge
pressurized air. Although the discharges are conveyed in safety areas,
attention must be paid.
Risk of burn!
External surfaces could reach high temperature (>65 °C).
Risk of electrical shock!
Presence of electrical supply: keep all parts of the body and any hand–held tools or
other conductive objects, away from exposed live parts of the compressor electrical
system.
Risk of sliding!
Potential leakages of water (condensation) could cause sliding.
Obey safety precaution. Personnel in charge of start-up must be equipped with the
necessary Personal Protective Equipment (PPE), namely safeguard shoes, gloves
eye and hearing protections. In-observance can cause personnel injuries.
To pressurize and turn on the dryer the following instructions must be followed:
DANGER!
Danger due to rapid build-up of opressure!
Slowly open the compressed air inlet valve; a rapid build-up of pressure can cause dryer
damages, in particular life reduction of the molecular sieves due to desiccant bead crushing
or pulverization. Furthermore, discharge of pressure can cause severe personnel injuries.
To integrate the dryer in the external air system, after the previous steps, the following instructions must be
executed:
slowly open the outlet valve, which intercepts the dryer downstream (if it will be installed by the Client);
during outlet valve opening take under control the pressure indicators (PT001/002); pressure should
not decrease under the operating pressure. Eventually, keep the outlet valve in a slightly open
position until the downstream line has filled up completely. At that point, the valve can be completely
opened.
WARNING!
Danger due to abrupt drop in pressure!
Slowly open the compressed air outlet valve; a rapid drop in pressure can cause dryer
damages.
12.8Tests
Once the process is in operation, commissioning operational, functional and performance tests must be carried
out on plant and equipment.
Finally, product design specification conformity must be proved.
Use & Maintenance Manual 59
MONITORING
13 MONITORING
The dryer automatically runs, however, it is necessary to perform regular checks, as described in Section 16.
Since the machinery is under pressure, personnel must always pay attention to potential pressure discharges.
DANGER!
-
Potential discharge of pressurized air!
• Air under pressure could be discharged; particles included in the air could be
violently ejected causing severe injuries to eyes and/or skin!
• During the expansion phase of drying process, the pressurized air is discharged
from the silencer generating a strong and sudden noise; it can cause damages
to the auditory apparatus;
• In emergency case, the safety valves installed on vessels can discharge
pressurized air. Although the discharges are conveyed in safety areas,
attention must be paid.
Risk of burn!
External surfaces could reach high temperature (>65 °C).
Risk of electrical shock!
Presence of electrical supply: keep all parts of the body and any hand–held tools or
other conductive objects, away from exposed live parts of the compressor electrical
system.
Risk of sliding!
Potential leakages of water (condensation) could cause sliding.
During operation, the control parameters and following aspects shall be checked to ensure the guaranteed
performance. Particularly, regularly monitor (monthly):
• no alarms are active;
• no leaks;
• no damages on the units;
• tight flanged connections and no leaks occurrence;
• dryer performances in compliance with the indications in Section 3.2;
60 Use & Maintenance Manual
Dryer DHRD6000
DANGER!
Potential discharge of pressurized air!
• Air under pressure could be discharged; particles included in the air could be
violently ejected causing severe injuries to eyes and/or skin!
• During the expansion phase of drying process, the pressurized air is discharged
from the silencer generating a strong and sudden noise; it can cause damages
to the auditory apparatus;
• In emergency case, the safety valves installed on vessels can discharge
pressurized air. Although the discharges are conveyed in safety areas,
attention must be paid.
Risk of burn!
External surfaces could reach high temperature (>65 °C).
Risk of electrical shock!
Presence of electrical supply: keep all parts of the body and any hand–held tools or
other conductive objects, away from exposed live parts of the compressor electrical
system.
Risk of sliding!
Potential leakages of water (condensation) could cause sliding.
WARNING!
Danger due to incorrect shutdown!
Pay attention to execute a correct shutdown procedure.
Incorrect switch off during expansion or drying phases can cause damages to the desiccant
material due to a sudden pressure build-up in the columns.
62 Use & Maintenance Manual
Dryer DHRD6000
14.1 Shutdown
The necessity to shot down the dryer can occur in different cases:
• maintenance;
• emergency or breakdown;
• disassembly.
Attention must be paid to the sequence of the required steps to avoid the unit damage and to preserve the
dryer efficiency.
intercept the dryer. To this aim it is necessary to install interception valves at the inlet and outlet
connection of the dryer. These valves are not in the scope of supply of Sinergia, but at Client’s charge.
Close the interception valves to intercept the dryer.
The required main phases for the complete depressurization of the dryer are:
intercept the dryer. To this aim it is necessary to install interception valves at the inlet and outlet
connection of the dryer. These valves are not in the scope of supply of Sinergia, but at Client’s charge.
Close the interception valves to intercept the dryer.
disconnect the dryer power supply and perform the required maintenance activities.
Use & Maintenance Manual 63
SHUTDOWN AND RESTART
WARNING!
Prior to start any maintenance activity, wait 60 minutes from the machine shutdown in order
to let it cool down.
NOTE:
Sinergia declines any responsibility for damages due to not correct shutdown procedure.
14.2 Restart
In case of depressurization, prior to restart the unit, it is necessary to pressurize the dryer. To this aim, ensure
pilot air supply, open the valve of pilot air supply (HV006) and then follow the procedure described in Sections
12.5 and 12.6.
In case the dryer has been stopped without interception and depressurization, its operation can be
started again simply giving the starting command.
Use & Maintenance Manual 65
ANOMALIES AND TROUBLESHOOTING
Table 15.1 lists main anomalies, which could occur during the dryer operation. Related potential causes and
troubleshooting are also indicated, helping to identify the source of the problem and to effect a remedy.
Dew point deterioration Inlet air temperature higher than - Excessive increase of temperature due to
design conditions upstream compressor/s operation:
- Check compressor operation
- Repair to reduce air temperature
Excessive cooler discharge air - Check cooling water flow rate and
temperature temperature; increase water flow or
decrease water temperature as necessary
- Check against dirty cooler; clean if
necessary
(#) Actuated inlet/outlet valves do not - Check that inlet/outlet valves do not
move correctly remain open/closed when not required
Failure in columns switch
by the control system; eventually repair
- See (*) in Table 15.3
Actuated valves move, but a limit Check wiring between limit switch and PLC
switch is not working properly
Actuated valves do not move - Check supply of pilot air; restore the
Dryer constantly tripping
correctly, when they should minimum pressure of 5 bar(g)
- Check wiring between solenoid and PLC
- Check fuses on PLC terminal strip
Failure in columns pressurization Actuated vent valves do not move - Check that vent valves do not remain
correctly open when not required by the control
system; eventually repair
- See (*) in Table 15.3
Upstream line not pressurized Check upstream line and solve anomalies
Failure in columns Actuated vent valves do not move - Check that vent valves do not remain
depressurization correctly closed when not required by the control
system; eventually repair
- See (*) in Table 15.3
(o) Excessive flow rate Check flow rate and cause of increased
Excessive pressure drop in flow; restore correct flow
columns Inlet pressure below design Increase operating pressure
condition
Excessive pressure during Obstructed silencer Check the silencer; eventually replace the
regeneration cartridge or the silencer
Actuated vent valves do not move - Check that vent valves do not remain
correctly closed when not required by the control
system; eventually repair
- See (*) in Table 15.3
Use & Maintenance Manual 67
ANOMALIES AND TROUBLESHOOTING
Too low outlet pressure Excessive pressure drop in columns See (o) in Table 15.1
Too low outlet air flow rate Actuated vent valves do not move - Check that vent valves do not remain
correctly open when not required by the control
system; eventually repair
- See (*)
(*) Lack or not sufficient pilot air supply Check supply of pilot air; restore the
Faulty Actuated valve minimum pressure of 5 bar(g)
Pilot air low pressure or leak Check pilot air pressure and check
against tubing leaks
Use & Maintenance Manual 69
MAINTENANCE
16 MAINTENANCE
The dryer requires a minimal maintenance activity since most of the components are “free from maintenance”.
However, it is recommended a “preventive maintenance” in order to ensure efficient operation and high
performance for an elevate number of years.
DANGER!
Danger due to incorrect activities!
• Dryer maintenance must be performed by qualified and authorized
technicians.
• NEVER use pipes or valves as climb support or holding points; there
is the risk of injuries due to slipping components, components breaks,
damages of the unit due to applied stresses and/or discharge of compress
air.
• NEVER leave tools or other object (such as cleaning rags) on the plant;
potential falls can cause damages of other components.
• Never stay below suspended loads.
• NEVER perform welding operations or modifications on columns.
Potential discharge of pressurized air!
• Perform maintenance activity only after dryer shutdown and
depressurization.
• NEVER perform maintenance activity on pressurized components as
long as the unit is pressurized; discharge of pressurized air can cause
severe injuries!
• Loosen nipples with care. Pay attention to dynamic pressures: violent
discharge of pressurized air can cause severe injuries!
Risk of burn!
External surfaces could reach high temperature (>65 °C). Prior to start any
maintenance activity, wait 60 minutes from the machine shutdown in order to let
it cool down.
Risk of electrical shock!
Presence of electrical supply: keep all parts of the body and any hand–held
tools or other conductive objects, away from exposed live parts of the
compressor electrical system.
Risk of sliding!
Pay attention to potential condensate leakages and/or desiccant agent beads
spilled on the floor.
70 Use & Maintenance Manual
Dryer DHRD6000
DANGER!
Obey safety precaution. Personnel in charge of maintenance and repairs must
be equipped with the necessary Personal Protective Equipment (PPE),
namely safeguard shoes, gloves, eye and hearing protections. In-
observance can cause personnel injuries.
In addition to the activities prescribed during the monitoring (Section 13), which can be accomplished while
the dryer is operating, Sinergia prescribes the maintenance activity scheduled in Table 16.1, which requires
the replacement of parts.
NOTE:
Use of spare parts in compliance with the Manufacturer requirements and guidelines is recommended.
Original spare-parts guarantee these aspects; non-original parts could damage or cause not correct
operation of the dryer.
For spare part quotation contact our Service department:
Mail: [email protected]
Phone: +39 0350527200
Table 16.1: Maintenance schedule prescribed by Sinergia for the main components of the dryer.
Maintenance
24 MONTHS
Assembled components Kind of maintenance
12 MONTHS
6 MONTHS
MONTHLY
DAILY
Maintenance
24 MONTHS
Assembled components Kind of maintenance
12 MONTHS
6 MONTHS
MONTHLY
DAILY
Visual and functional check
MEASURING INSTRUMENTS
Check of system parameters
In the following sections, procedures for main maintenance activities are illustrated.
NOTE:
The machine is designed to always guarantee a free path for the air passage between skid inlet and outlet,
to avoid risks resulting from overpressure. In case of emergency stop or blackout the valves remain in
position.
It is responsibility of the user to ensure correct installation of valves, shut-off devices and safety devices
upstream and downstream the skid, in order to avoid risks deriving from overpressures.
In case of restart after a prolonged shutdown or shutdown for maintenance activities, the user has the
responsibility to verify the position and status of the shut-off valves / devices installed upstream and
downstream of the skid.
Life of desiccant material (about 18-24 months) depends on installation condition and impurities included in
the compressed air; in fact oil, dust, dirty particles sediment on desiccant material reducing its active surface.
Furthermore, replacement interval time depends on the regular replacement of the upstream filter; in fact,
malfunctioning of filter reduces the efficiency of desiccant material.
In normal operation conditions (except anomalies or emergency), the dryer Manufacturer prescribes an annual
check and the replacement of desiccant material every two years.
Dryer vessels must be filled from the top and emptied from the bottom.
72 Use & Maintenance Manual
Dryer DHRD6000
Due to the height of the unit, to reach the filling nozzles at the columns top, each column is equipped with an
eyebolt lifting where the operator must fix the safety harness. Position of filling and emptying nozzles and lifting
eyebolts is specified in APPENDIX A.
DANGER!
Danger due incorrect behaviour!
• To reach the filling nozzle at column top fix the safety harness to eyebolt lifting
located at columns top.
• NEVER use pipes or valves as climbing support or holding points; there is the
risk of injuries due to slipping components, components breaks, damages of the
unit due to applied stresses and/or discharge of compress air.
• Whenever it is necessary to use a rung ladder or a gangway, ensure that they are
appropriate to allow the operator to work in safe conditions.
• In addition to PPE mentioned in Section 16, wear an anti-dust mask to handle the
desiccant material.
WARNING!
Risk of sliding!
If the activated alumina has been spilled on the floor, there is the risk of sliding on the agent
beads. Clean promptly the floor.
carefully clean the base of the vessel from impurities and/or incrustations, draw using an industrial
vacuum cleaner;
Prior to fill the vessels make sure to have the proper equipment to discharge the material from the original
packing. The minimal required equipment is a funnel or a cone-shaped system with dimensions proper to
be inserted in the filling connection.
Furthermore, the adsorbing material container must be suitable to be lifted and to charge the adsorbing
material into the vessel.
If the adsorbing material is supplied into big bags, to discharge the material from the big bag into the
funnel/cone shape system, it is necessary to lift it by a suitable crane and correctly located above the filling
nozzle. Each big bas is equipped with proper lifting lugs on the top and regulable opening at the base to allow
regulation of adsorbing material flow.
If the adsorbing material can be in small drums it is necessary to equip the drum opening with a discharging
system with a regulating manual valve.
In any case, if the original packing is not suitable for the vessel filling, it is useful to transfer the material in a
filling container, adapt to be lifted up to the filling connection and equipped with a discharging system (manual
valve and discharging tube) which allows regulating the material discharge into the vessel (such as a
mechanical hopper).
In any case, if the original packing is not suitable for the vessel filling, it is useful to transfer the material in a
filling container, adapt to be lifted up to the filling connection.
The steps of the procedure for filling vessels with new desiccant material are:
ensure that the emptying nozzle at the bottom of the column is close;
approach the loading nozzle with a suitable portable ladder, scissor lift or aerial platform;
lift the desiccant container at the loading nozzle;
slowly discharge the desiccant material in the vessel to prevent chipping and generate dust resulting
in premature clogging of the post-filter; the manual valve of the discharging equipment allows this
activity;
ensure that there are no leakages spraying water soapy on the filling and discharge nozzles.
WARNING!
Desiccant material contact!
In case the adsorption material comes into contact with the eyes, immediately wash
them with abundant clean water. For further safety information see the desiccant material
safety data sheet (APPENDIX C).
16.2Silencer replacement
DANGER!
Danger due to obstructed silencer
Obstruction of silencer may generate the build-up of dangerous overpressure, with
consequent burst of the silencer. Fragments ejection may cause personnel injury and
material damage.
Dryer Manufacturer prescribes a daily check and a replacement of the silencer every six months. However,
replacement is always required in case of excessive pressure in the columns during regeneration.
It is recommended to replace the separator demister and clean the cooler, both tube-side and shell-side
annually. Note that this interval should be adjusted shorter or longer, based on water quality and plant
experience.
Since cooler and separator are connected and to perform the cooler maintenance it is necessary to disconnect
the separator, it is suggested to plan both cooler and separator maintenance at the same time.
To this aim, referring to both the P&Id and Figure 3.3 for connection numbering:
Use & Maintenance Manual 75
MAINTENANCE
disconnect the separator from the plant loosing the fixing nuts of the outlet (N2) flange;
carefully remove the separator securing it with a suitable sling;
place the separator on safety location and extract the demister;
inspect the separator internal surface and the drain pot;
accurately clean with compressed and dried air;
disconnect the inlet (N1) flanged connections and the flanged connection cooler-elbow (at the
opposite site of the cooler with respect to the separator); to this aim loose the fixing nuts; carefully
remove the cooler-piping connecting elbow piping securing it with a suitable sling;
disconnect the cooling water inlet (N3) and outlet (N4) flanged connections (B); to this aim loose the
fixing nuts;
once the cooler AC001 is disconnected, remove it from the package securing it with a suitable sling;
place the cooler on safety location to extract the tube bundle and clean it;
extract the tube-bundle from the cooler casing; note that a gasket is inserted between the connecting
flange and the holed flanged;
extract the gasket. Note that it should be replaced with a new one during the re-assembling;
clean both the casing and the tube-bundle (tube and shell sides). To this aim:
o circulate compressed air;
o in case of intense deposits, use water. If it is not sufficient, friendly cleaning agent or degreasing
agent that does not attack the material may be added to the water;
o agents with ammonia must not be used.
76 Use & Maintenance Manual
Dryer DHRD6000
16.4Drain check
Correct operation of condensate separator drain is fundamental; malfunctioning can cause the casing filling of
condense and consequent reduction of dryer performance. To check drain operation, open the manual drain
line opening the valve HV015 and then the bypass drain valve (HV003). Verify that no condensate drains.
DANGER!
Danger due to presence of electrical supply!
Risk of electrical shock!
Cables of electrical supply and of external lines are under power also after the dryer
shutdown. Before to start any activity on the electrical system, ensure that electrical supply
cables and external lines are voltage-free. Furthermore, ensure that electrical supply
cable to the dryer is secured against switch-on.
17 MATERIALS DISPOSAL
Sinergia is actively engaged in environmental protection in agreement with ISO 14001 standards, and it
always designs, manufactures and develops all its products as recyclable as possible.
Recycling is a source of wealth, which contributes to pollution reduction by the recovery of materials for reuse.
Recycling prevents the waste of potentially useful materials and reduces the consumption of both raw materials
and energy, consequently the emission of greenhouse gases.
Materials can be disposed in agreement with the applicable legislation.
The Table 17.1 gives indication about which main components/materials actually needs to be disposed of, and
which ones can be recycled, referring to the main constitutive components.
When the units are to be permanently decommissioned or dismantled, it is important to ensure that all hazard
risks are either eliminated or notified to the recipient of the machine. In particular:
• do not dispose of any pressure vessel that is not clearly marked with its relevant data plate information
or rendered unusable by drilling, cutting etc.;
• do not dispose of a complete machine without documentation relating to instructions for its use.
78 Use & Maintenance Manual
Dryer DHRD6000
Category
Plant component
RECYCLABLE
Cartridges
Chemical
Electrical
Other
Metal
BASEPLATE / SUPPORT LEGS / GAUGE BOARD STRUCTURE YES
ABSORBENT MATERIAL NO
SILENCERS YES
NAMEPLATES YES
18 APPENDIXES
Operation & Maintenance Manual I
APPENDIXES
Rev. Data / Date Descrizione / Description Dis. / Prep'd Contr. / Chk'd Appr. / App'd
Disegno : Cliente : Classe di
Drawing Customer Tolleranza
Tolerance
Class
Oggetto : -
Object
Scala :
Scale
S.p.A.
Office: +39 035 052 7200
Fax: +39 035 052 6085 Sist. :
Email: [email protected] Sist.
Web site: www.sinergia-it.com
Proprietà di SINERGIA S.p.A. Riproduzione e divulgazione vietate a termini di legge
Address: Via Serio 29, 24021 Albino (BG) SHEET OF
SINERGIA S.p.A. property. Reproduction and divulgation are forbidden according to the law
Operation & Maintenance Manual II
APPENDIXES
APPENDIX B: P&I
I
010
NOTE:
TP
IA
TT TW
2
INSTRUMENT IDENTIFICATION EXAMPLE:
005 005
HV
006 CS-6"-AIR-150-017
³ XX FUNCTION
DN150 PN16
CS-3"-AIR-150-016
LINE PIPING IDENTIFICATION EXAMPLE:
HCV XX-X"-XXX-XXX-XXX
001
PROGRESSIVE NUMBER
RATING
FLUID
PDI
TP
001
TP
SIZE
I ZLL ZLH I ZLL ZLH
7 8
001 003 003 002 004 004 MATERIAL
CS-3"-AIR-150-010
XY XY CV
003A 004A 001
DN150 PN16 DN150 PN16
ZSL ZSH S ZSL ZSH S
003 003 IA
004 004 IA HV
VENT VENT 007
S S
XY XY F001
003B 004B
HV
CS-6"-AIR-150-011 005
XV XV
003 004
I
002
ZLL
005
ZLH
005
I
001
ZLL
006
ZLH
006
POST FILTER (Loosed Supply)
CS-6"-AIR-150-013 CS-6"-AIR-150-014
XY XY
005A 006A
I ZLL ZLH
ZSL ZSH S ZSL ZSH S
005 011 011
005 005 IA
006 006 IA
VENT VENT
S S
XY
PAL PI 011 PAL PI
XY XY
002 002 S 001 001
005B 006B
CS-6"-AIR-150-012
ZSL ZSH IA
011 011
XV XV VENT
005 006
ALUMINA INLET ALUMINA INLET
NOZZLE NOZZLE
XY
013 CS-3"-AIR-150-015
I Set Point: PSV PSV Set Point: I
008 10 barg 002 001 10 barg 008
IA
DISCHARGE IN AIR XY XV HV
DISCHARGE IN AIR
VENT
ENVIRONMENT
ZLL ZLH XY
IA
001A S
013 013
PT
002
XV
013 S
PT
001 ITEM DESCRIPTION
I
ZSH VENT
HV 013 010 HV
010 ZLL ZLH 008
I ZSL
001 001 ³ AT001 VESSEL 1700Lt
XV
007 013
PI ZSH
001
TP
PI
001
AT002 VESSEL 1700Lt
002 001 NOTE: 30mm
1
HV
011
NOTE: 30mm
I
TW
001
TT
001
INSULATED COATING HV
009 SEP001 CYCLONIC SEPARATOR
INSULATED COATING ZSL
003 001
CS-6"-AIR-150-001
AC001 COOLER
AIR INLET
AT002 DN150 PN16
AT001 PI001 PRESSURE INDICATOR
XY
XY
002B
PI002 PRESSURE INDICATOR
PAL PI IA
002A S
004 004 PSV001 PRESSURE SAFETY VALVE SET:10 barg
CS-3"-AIR-150-009
S
VENT
PSV002 PRESSURE SAFETY VALVE SET:10 barg
ALUMINA OUTLET ZLL ZLH ALUMINA OUTLET
NOZZLE 002 002 C.W. OUTLET NOZZLE
TT001 PT100 INLET DRYER TEMPERATURE
XV
I
005 ZSH
002
C.W. INLET TT002 PT100 INLET COOLER AIR TEMPERATURE
002
HV
I
010
TT
002
4 3
TT
003
TW
003
PT001 PRESSURE TRANSMITTER COLUMN 1
AC001
004
TW
002 CS-6"-AIR-150-002 CS-6"-AIR-150-003
PT002 PRESSURE TRANSMITTER COLUMN 2
SEP001 PT004 PRESSURE TRANSMITTER TOWER EXHAUST/COOLING
XY LSH
001
XY GENERAL SOLENOID VALVE
014B
ZLL ZLH I
XY
014A
IA
S
HV
001
XV GENERAL ACTUATED VALVE
012 012 006
S
HV
002
HV HAND VALVE
HV
XY
ZLL ZLH
VENT 015
ZS POSITION SWITCH
014 014 I
012
ZSL ZSH
S
XV
014
011
HV
003 PDI001 POST FILTER PRESSURE DIFFERENTIAL INDICATOR
IA
012 012 ZSH
014 S TP
5
1/2" G - F
F001 POST FILTER
VENT
XY
I ZSL 015
IA
003 014
CS-3"-AIR-150-008 VENT
XV HV
012 013 TP 1/2" G - F
I ZLL ZLH I ZLL ZLH 6
002 007 007 001 008 008
XV
015
XY XY
007A 008A
S S
XY XY
007B 008B
CS-6"-AIR-150-005
XV XV
007 008
CS-6"-AIR-150-006 CS-6"-AIR-150-007
Rev. Data / Date Descrizione / Description Dis. / Prep'd Contr. / Chk'd Appr. / App'd
XY XY Disegno : Cliente : Classe di
009A 010A Drawing Customer Tolleranza
ZSL ZSH S ZSL ZSH S Tolerance
009 009 010 010 Class
IA IA
VENT VENT Oggetto : -
S S Object
XY XY Scala :
009B 010B Scale
S.p.A.
CS-6"-AIR-150-004 Office: +39 035 052 7200
XV XV
009 010
Fax: +39 035 052 6085 Sist. :
Email: [email protected] Sist.
Web site: www.sinergia-it.com
Proprietà di SINERGIA S.p.A. Riproduzione e divulgazione vietate a termini di legge
Address: Via Serio 29, 24021 Albino (BG) SHEET OF
SINERGIA S.p.A. property. Reproduction and divulgation are forbidden according to the law
Operation & Maintenance Manual III
APPENDIXES
Pag. 1 a 15
Denmark National Poisons +45 82 12 12 12 (Available 24 hours a day. SDS/Product information
Control Center may not be available for the Emergency Service.)
Estonia National Poisons 16662 or abroad: (+372) 626 9390 (Monday 9:00AM to Saturday
Information Center 9:00AM (closed on Sundays and on national holidays). SDS/Product
information may not be available for the Emergency Service.)
Finland National Poison (09) 471 977 (direct) or (09) 4711 (exchange) (Available 24 hours a
Information Center day. SDS/Product information may not be available for the
Emergency Service.)
France National Poisons ORFILA number (INRS): + 33 (0) 1 45 42 59 59 (Available 24 hours a
Control Center day. SDS/Product information may not be available for the
Emergency Service.)
Hungary National 36 80 20 11 99 (Available 24 hours a day. SDS/Product information
Emergency Phone Number may not be available for the Emergency Service.)
Lithuania Neatidėliotina +370 5 236 20 52 or +37068753378 (Hours of operation not
informacija apsinuodijus. provided. SDS/Product information may not be available for the
Emergency Service.)
Malta Accident and 2545 4030 (Hours of operation not provided. SDS/Product
Emergency Department information may not be available for the Emergency Service.)
Netherlands National Poisons 030‐274 88 88 (Only for the purpose of informing medical personnel
Information Center (NVIC) in cases of acute intoxications)
Norway Norwegian Poison 22 59 13 00 (Available 24 hours a day. SDS/Product information may
Information Center not be available for the Emergency Service.)
Romania Biroul RSI si 021.318.36.06 (Available 8:00AM‐3:00PM. SDS/Product information
Informare Toxicologica may not be available for the Emergency Service.)
Slovakia National Toxicological +421 2 5477 4166 (Available 24 hours a day. SDS/Product
Information Center information may not be available for the Emergency Service.)
Sweden National Poison 112 ‐ and ask for Poison Information (Available 24 hours a day.
Information Center SDS/Product
information may not be available for the Emergency Service)
Espagna Servicio de +34 91 562 04 20 (Available 24h/365 days. SDS/ Product information
informacion Toxicologica may not be available from the Emergency Service.)
Croatia Poison Control Centre +385 1 2348 342 (Available 24 hours a day. SDS/Product information
may not be available for the Emergency Service.)
Greece Poison Information 0030) 2107793777 (Available 24 hours a day. SDS/Product
center information may not be available for the Emergency Service.)
Luxembourg Centre +352) 8002‐5500 (Available 24 hours a day. SDS/Product information
Antipoisons may not be available for the Emergency Service.)
Latvia Toksikoloģijas un sepses + 371 67042473 (Available 24 hours a day. SDS/Product information
klīnikas Saindēšanās un zāļu may not be available for the Emergency Service.)
informācijas centrs
Portugal Centro de Informaçao 808 250 143 (Available 24 hours a day. SDS/Product information
Antivenenos may not be available for the Emergency Service.)
Pag. 2 a 15
This mixture does not meet the criteria for classification according to Regulation (EC) 1272/2008 as
amended.
Hazard summary
Not classified for health hazards. However, occupational exposure to the mixture or substance(s)
may cause adverse health effects.
2.2 Label elements
Label according to Regulation (EC) No. 1272/2008 as amended
Hazard pictograms: None
Signal word: None
Hazard statements: The mixture does not meet the criteria for classification
Precautionary statements
Prevention: Observe good industrial hygiene practices.
Response: Wash hands after handling.
Storage: Store away from incompatible materials.
Disposal: Dispose of waste and residues in accordance with local authority
requirements.
Supplemental Label
information: None.
Pag. 3 a 15
Skin Contact: Skin contact Wash off with soap and water. Get medical attention if irritation
develops and persists.
Inhalation: Move to fresh air. Call a physician if symptoms develop or persist.
Ingestion: Rinse mouth. Get medical attention if symptoms occur.
4.2 Most important symptoms and effects, both acute and delayed
Exposure may cause temporary irritation, redness, or discomfort.
4.3 Indication of any immediate medical attention and special treatment needed
Treat symptomatically.
Croatia. Dangerous Substance Exposure Limit Values in the Workplace (ELVs), Annexes 1 and 2,
Narodne Novine, 13/09
Components Type Value Form
Aluminium Oxide MAC 4 mg/m³ Respirable dust
(CAS 1344‐28‐1) 10 mg/m³ Total dust
Pag. 5 a 15
Czech Republic. OELs. Government Decree 361
Components Type Value Form
Aluminium Oxide TWA 0,1 mg/m³ Respirable dust
(CAS 1344‐28‐1)
Estonia. OELs. Occupational Exposure Limits of Hazardous Substances. (Annex of Regulation No.
293 of 18 September 2001)
Components Type Value Form
Aluminium Oxide TWA 4 mg/m³ Respirable dust
(CAS 1344‐28‐1) 10 mg/m³ Total dust
France. Threshold Limit Values (VLEP) for Occupational Exposure to Chemicals in France, INRS ED
984
Components Type Value
Aluminium Oxide VME 10 mg/m³
(CAS 1344‐28‐1)
Regulatory status: Indicative limit (VL)
Germany. DFG MAK List (advisory OELs). Commission for the Investigation of Health Hazards of
Chemical Compounds in the Work Area (DFG)
Components Type Value Form
Aluminium Oxide TWA 4 mg/m³ Inhalable fraction
(CAS 1344‐28‐1) 1,5 mg/m³ Respirable fraction
Germany. TRGS 900, Limit Values in the Ambient Air at the Workplace
Components Type Value Form
Aluminium Oxide AGW 10 mg/m³ Inhalable fraction.
(CAS 1344‐28‐1) 1,25 mg/m³ Respirable fraction
Pag. 6 a 15
Aluminium Oxide TWA 6 mg/m³ Respirable
(CAS 1344‐28‐1)
Latvia. OELs. Occupational exposure limit values of chemical substances in work environment
Components Type Value Form
Aluminium Oxide TWA 6 mg/m³ Decomposition
(CAS 1344‐28‐1) aereosol
4 mg/m³
Ordinance of the Minister of Labour and Social Policy on 6 June 2014 on the maximum
permissible concentrations and intensities of harmful health factors in the work environment,
Journal of Laws 2014, item 817
Components Type Value Form
Aluminium Oxide TWA 2,5 mg/m³ Inhalable fraction
(CAS 1344‐28‐1) 1,2 mg/m³ Respirable fraction
Pag. 7 a 15
Romania. OELs. Protection of workers from exposure to chemical agents at the workplace
Components Type Value Form
Aluminium Oxide STEL 5 mg/m³ Aerosol
(CAS 1344‐28‐1) TWA 2 mg/m³ Aerosol
Slovakia. OELs. Regulation No. 300/2007 concerning protection of health in work with chemical
agents
Components Type Value Form
Aluminium Oxide TWA 4 mg/m³ Inhalable fraction
(CAS 1344‐28‐1) 1,5 mg/m³ Respirable fraction
0,1 mg/m³
Sweden. OELs. Work Environment Authority (AV), Occupational Exposure Limit Values (AFS
2015:7)
Components Type Value Form
Aluminium Oxide TWA 5 mg/m³ Total dust
(CAS 1344‐28‐1) 2 mg/m³ Respirable dust
Workers
Components Value Assessment factor Notes
Aluminium Oxide (CAS 1344‐28‐1)
Long‐term, Local, 15,63 mg/m³ 3 Repeated dose toxicty
Inhalation
Long‐term, Systemic, 15,63 mg/m³ 3 Repeated dose toxicty
Inhalation
Pag. 9 a 15
Hygiene measures Always observe good personal hygiene measures, such as washing after handling
the material and before eating, drinking, and/or smoking. Routinely wash work
clothing and protective equipment to remove contaminants.
Environmental Environmental manager must be informed of all major releases
exposure controls
SECTION 9: Physical and chemical properties
9.1 Information on basic physical and chemical properties
Appearance Spheres
Physical state Solid
Form Solid
Colour White
Odour: Not available
Odour threshold: Not available
pH: Not available
Melting point/Freezing point: 2000°C (3632°F)
Initial boiling point and boiling range: Not available
Flash point: Not applicable
Evaporation rate: Not available
Flammability (solid, gas) Not available
Vapour pressure: Not available
Vapour density: Not available
Relative density: Not available
Solubility(ies):
Solubility (water) Insoluble
Auto‐ignition temperature: Not available
Decomposition temperature: Not available
Viscosity Not available
Explosive properties: Not explosive
Oxidising properties: Not oxidising
Pag. 10 a 15
10.2 Chemical Stability:
Material is stable under normal conditions
10.3 Possibility of hazardous reactions:
No dangerous reaction known under conditions of normal use.
10.4 Conditions to avoid:
Keep away from heat, hot surfaces, sparks, open flames and other ignition sources. Contact with
incompatible materials. Minimise dust generation and accumulation.
10.5 Incompatible Materials:
Acids. Bases. Strong oxidising agents. Chlorine.
10.6 Hazardous Decomposition Products:
Thermal decomposition or combustion may liberate carbon oxides and other toxic gases or vapors.
Pag. 11 a 15
Due to partial or complete lack of data the classification is not possible
Hungary. 26/2000 EüM Ordinance on protection against and preventing risk relating to
exposure to carcinogens at work (as amended)
Not listed.
Reproductive toxicity
Due to partial or complete lack of data the classification is not possible. This product is not
expected to cause reproductive or developmental effects.
Specific target organ toxicity ‐ single exposure
Due to partial or complete lack of data the classification is not possible. No information available.
Specific target organ toxicity ‐ repeated exposure
No information available. Due to partial or complete lack of data the classification is not possible.
Aspiration hazard
No information available. Due to partial or complete lack of data the classification is not possible.
Mixture versus substance information
No information available
Other information
Not available
Pag. 12 a 15
12.5 Results of PBT and vPvB assessment
Not a PBT or vPvB substance or mixture. Not available.
12.6 Other Adverse Effects
No other adverse environmental effects (e.g. ozone depletion, photochemical ozone creation
potential, endocrine disruption, global warming potential) are expected from this component.
14.1 Transport in bulk according to Annex II of MARPOL 73/78 and the IBC Code
Not applicable
Pag. 13 a 15
SECTION 15: Regulatory information
15.1 Safety, health and environmental regulations/legislation specific for the substance or mixture
EU REGULATIONS
Regulation (EC) No. 1005/2009 on substances that deplete the ozone layer Annex I Not listed
and II, as amended:
Regulation (EC) No. 850/2004 on persistent organic pollutants, Annex I and II, as Not listed
amended:
Regulation (EC) No. 649/2012 concerning the export and import of dangerous Not listed
chemicals, Annex I, Part 1 as amended:
Regulation (EC) No. 649/2012 concerning the export and import of dangerous Not listed
chemicals, Annex I, Part 2 as amended:
Regulation (EC) No. 649/2012 concerning the export and import of dangerous Not listed
chemicals, Annex I, Part 3 as amended:
Regulation (EC) No. 649/2012 concerning the export and import of dangerous Not listed
chemicals, Annex V as amended:
Regulation (EC) No. 166/2006 Annex II Pollutant Release and Transfer Registry, as Not listed
amended:
Regulation (EC) No. 1907/2006, REACH Article 59(10) Candidate List as currently Not listed
published by ECHA:
Authorisations:
Regulation (EC) No. 1907/2006, REACH Annex XIV Substances subject to Not listed
authorization, as amended:
Restrictions on use Not listed
Regulation (EC) No. 1907/2006, REACH Annex XVII Substances subject to restriction Not listed
on marketing and use as amended:
Directive 2004/37/EC: on the protection of workers from the risks related to Not listed
exposure to carcinogens and mutagens at work, as amended.
Other EU regulations:
Directive 2012/18/EU on major accident hazards involving dangerous substances, Not listed.
as amended
Other regulations:
The product is classified and labelled in accordance with Regulation (EC) 1272/2008 (CLP
Regulation) as amended. This Safety Data Sheet complies with the requirements of Regulation
(EC) No 1907/2006, as amended.
National regulations:
Follow national regulation on the protection of workers from the risks of exposure to carcinogens
and mutagens at work, in accordance with Directive 2004/37/EC.
15.2 Chemical safety assessment:
No Chemical Safety Assessment has been carried out.
Pag. 15 a 15
Operation & Maintenance Manual IV
APPENDIXES
Doc. No. P08408‐WD01
OBJECT:
Heat of Compression Dryer DHRD 6000
Oggetto:
CLIENT:
CELULOSA Y ENERGIA PUNTA PEREIRA
Cliente :
PROJECT:
MONTES DEL PLATA
Progetto :
ORDER No.:
6700001511
Ordine n. :
OUR JOB No.:
P08408
Commessa n.:
PW X2
INT
X1
X3
POWER SUPPLY PW 1
POWER SUPPLY PW 2
POWER SUPPLY PW 3
+ X1 53
LSH001 2x0,5 ARMORED
- X1 54
+ 2 X1 33
ZSH001 2x0,5 ARMORED
- 4 X1 34
12G1 ARMORED
+ 8 X2 32
XV001A 3G1 ARMORED
- 9 X2 9
+ 7 X2 34
XV001B 3G1 ARMORED
- 9 X2 9
+ 2 X1 41
ZSH002 2x0,5 ARMORED
- 4 X1 45
12G1 ARMORED
+ 8 X2 36
XV002A 3G1 ARMORED
- 9 X2 11
+ 7 X2 37
XV002B 3G1 ARMORED
- 9 X2 11
+ 2 X1 1
ZSH003 2x0,5 ARMORED
- 4 X1 2
12G1 ARMORED
+ 8 X2 16
XV003A 3G1 ARMORED
- 9 X2 1
+ 7 X2 20
XV003B 3G1 ARMORED
- 9 X2 1
+ 2 X1 17
ZSH004 2x0,5 ARMORED
- 4 X1 18
12G1 ARMORED
+ 8 X2 24
XV004A 3G1 ARMORED
- 9 X2 5
+ 7 X2 28
XV004B 3G1 ARMORED
- 9 X2 5
+ 2 X1 19
ZSH005 2x0,5 ARMORED
- 4 X1 20
12G1 ARMORED
+ 8 X2 25
XV005A 3G1 ARMORED
- 9 X2 6
+ 7 X2 29
XV005B 3G1 ARMORED
- 9 X2 6
+ 2 X1 3
ZSH006 2x0,5 ARMORED
- 4 X1 4
12G1 ARMORED
+ 8 X2 17
XV006A 3G1 ARMORED
- 9 X2 2
+ 7 X2 21
XV006B 3G1 ARMORED
- 9 X2 2
+ 2 X1 21
ZSH007 2x0,5 ARMORED
- 4 X1 22
12G1 ARMORED
+ 8 X2 26
XV007A 3G1 ARMORED
- 9 X2 7
+ 7 X2 30
XV007B 3G1 ARMORED
- 9 X2 7
LIMIT SWITCH TERMINAL BOX
+ 1 X1 13
ZSL008 2x0,5 ARMORED
- 3 X1 14
+ 2 X1 5
ZSH008 2x0,5 ARMORED
- 4 X1 6
12G1 ARMORED
+ 8 X2 18
XV008A 3G1 ARMORED
- 9 X2 3
+ 7 X2 22
XV008B 3G1 ARMORED
- 9 X2 3
+ 2 X1 7
ZSH009 2x0,5 ARMORED
- 4 X1 8
12G1 ARMORED
+ 8 X2 19
XV009A 3G1 ARMORED
- 9 X2 4
+ 7 X2 23
XV009B 3G1 ARMORED
- 9 X2 4
+ 2 X1 23
ZSH010 2x0,5 ARMORED
- 4 X1 24
12G1 ARMORED
+ 8 X2 27
XV010A 3G1 ARMORED
- 9 X2 8
+ 7 X2 31
XV010B 3G1 ARMORED
- 9 X2 8
+ 2 X1 42
12G1 ARMORED
ZSH011 2x0,5 ARMORED
- 4 X1 47
+ 8 X2 38
XV011A 3G1 ARMORED
- 9 X2 12
+ 2 X1 43
12Px1,5mm2 ARMORED
ZSH012 2x0,5 ARMORED
- 4 X1 49
+ 8 X2 39
XV012A 3G1 ARMORED
- 9 X2 13
+ 2 X1 44
12G1 ARMORED
ZSH013 2x0,5 ARMORED
- 4 X1 51
+ 8 X2 40
XV013A 3G1 ARMORED
- 9 X2 14
+ 2 X1 35
ZSH014 2x0,5 ARMORED
- 4 X1 36
12G1 ARMORED
+ 8 X2 33
XV014A 3G1 ARMORED
- 9 X2 10
+ 7 X2 35
XV014B 3G1 ARMORED
- 9 X2 10
+ X2 41
XY0015 2x0,5 ARMORED
- X2 42
+ X3 1
TT001 2x0,5 ARMORED
- X3 2
+ X3 3
TT002 2x0,5 ARMORED
- X3 4
+ X3 5
TT003 2x0,5 ARMORED
- X3 6
+ X3 7
TT005 2x0,5 ARMORED
- X3 8
+ X3 9
PT001 2x0,5 ARMORED
- X3 10
+ X3 11
PT002 2x0,5 ARMORED
- X3 12
+ X3 13
PT004 2x0,5 ARMORED
- X3 14
+ INT 1
- INT 2
INTERFACE
+ INT 3
- INT 4
Since 2003 Sinergia SpA has a quality management system in agreement with UNI EN ISO
9001. The main aim is to manage as best as possible business processes to guarantee always
full satisfaction of the customers.
To constantly improve and consolidate the company ethic, aiming at both minimum
environmental impact of the production processes, and people health and safety, in 2010
Sinergia implemented an Integrated management system in compliance with two very important
adopted certifications: the UNI EN ISO 14001 standard for an Environmental Management
System and the BS OHSAS 18001 for an Occupational Health and Safety Management
System.
At the end of the year 2020 Sinergia made the transition of its own system to the Health and
Safety international standard UNI ISO 45001.
UNI EN ISO 14001 highlights the responsible and conscious behaviour of the company towards
the environment, emphasizing the attention to energy consumption, noise pollution, emissions
into the atmosphere and waste management in full agreement with the rules applicable to the
business context.
UNI ISO 45001 is internationally recognized as the official standard on health and safety at
work. This certification specifies the ways a company knows and controls the risks and any
unexpected occurrences that can originate from its activities, and how it manages them to
optimize the performances.
Sinergia makes the best to design, propose solutions and work for products of excellence
quality, resistant, safe and in compliance with the user needs. To this aim, Sinergia avails itself
of international certifications: EN1090 for skid baseplates/structures, PED, ASME Stamp and
TR CU 010 / 032 for pressure equipment, as per European, American and Eurasian Custom
Union markets respectively.
The integrated management system, pressure vessels according to the European / American
regulations and skid baseplates/structures according to EN1090 are certified by ICIM / IQNET,
an independent international body, worldwide leader in inspection services, auditing, good
analysis and services, and industrial system.