INSTRUMENT 

CALIBRATION RANGES

DOC NO :  18001‐000‐B25‐050

PROJECT : 165 TPH @ 67 barg, 485°C Baggasse Fired Boiler 

DEPARTMENT : E & I

SHEETS : 3

REVISION: 1

1 2‐Oct‐19 With Transmitter Ranges  Faisal Akram Muhammad Asghar


0 12‐Nov‐18 Issued for instruments  Configuration Faisal Akram Muhammad Asghar
Rev Date Description Engineered By Checked By

Layyah Sugar Mills
  Doc No 18001‐000‐B25‐050
INSTRUMENT CALIBRATION RANGES   Rev No. 1
  Sheet No. 3

TRANSMITTER  DCS 
Line No.
Sr. No.

CALIBRATION RANGE CALIBRATION RANGE
TAG NO. INSTRUMENT DESCRIPTION SERVICES RANGE UNIT UNIT REMARKS
LRV URV LRV URV

1 BOILER INSTRUMENTS 

2 Reference P&ID: Deaerator System (18001‐B01‐000‐00‐01 OF 01)

3 1 LT‐100A Level Transmitter Deaerator Tank (DA‐01) ± 400 ‐89.2 0 "WC 0 100.0 %

4 2 LT‐100B Level Transmitter Deaerator Tank (DA‐01) ± 400 ‐89.2 0 "WC 0 100.0 %

5 3 LT‐100C Level Transmitter Deaerator Tank (DA‐01) ± 400 ‐89.2 0 "WC 0 100.0 %

6 4 PT‐100A Pressure Transmitter BFW Pumps common Discharge header ‐1 ~ 210 0 120 Bar‐G 0 120.0 Bar‐G

7 5 PT‐100B Pressure Transmitter BFW Pumps common Discharge header ‐1 ~ 210 0 120 Bar‐G 0 120.0 Bar‐G

8 6 PT‐500 Pressure Transmitter Deaerator Tank (DA‐01) ‐1 ~ 3.5 0 1 Bar‐G 0 1.000 Bar‐G

9 7 TT‐100 Pressure Transmitter Deaerator Tank (DA‐01) ‐50 ~ 260 0 200 °C 0 200.0 °C

10

11 Reference P&ID: Water System (18001‐B01‐001‐00‐01 OF 01)

12 1 LT‐101A Level Transmitter Steam Drum (SD‐01) ± 400 ‐39.4 0 "WC 0 100.0 %

13 2 LT‐101B Level Transmitter Steam Drum (SD‐01) ± 400 ‐39.4 0 "WC 0 100.0 %

14 3 LT‐101C Level Transmitter Steam Drum (SD‐01) ± 400 ‐39.4 0 "WC 0 100.0 %

15 4 FT‐100 Flow Transmitter BFW Pumps common Discharge line to ECO‐01 Inlet ± 400 0 312.2 "WC 0 198.0 TPH

16 5 FT‐101 Flow Transmitter De‐superheater water ± 400 0 176.8 "WC 0 11.0 TPH

17 6 TT‐101 Temperature Transmitter ECO‐01 Outlet Line to ECO‐02 Inlet ‐180 ~ 500 0 0 ~ 300 °C 0 300.0 °C

18 7 TT‐102 Temperature Transmitter ECO‐02 Outlet Line to Steam Drum ‐180 ~ 500 0 0 ~ 500 °C 0 500.0 °C

19

20 Reference P&ID: Steam System (18001‐B01‐002‐00‐01 OF 01)

21 1 FT‐600 Flow Transmitter Main SHS to Process Line  ± 400 0 538.8 "WC 0 181.5 TPH

22 2 PT‐501 Pressure Transmitter Steam Drum (SD‐01) ‐1 ~ 210 0 120 Bar‐G 0 120.0 Bar‐G

23 3 PT‐600A Pressure Transmitter Main SHS to Process Line ‐1 ~ 210 0 120 Bar‐G 0 120.0 Bar‐G

24 4 PT‐600B Pressure Transmitter Main SHS to Process Line ‐1 ~ 210 0 120 Bar‐G 0 120.0 Bar‐G

25 5 PT‐600C Pressure Transmitter Main SHS to Process Line ‐1 ~ 210 0 120 Bar‐G 0 120.0 Bar‐G

26 6 PT‐601 Pressure Transmitter SHS to Soot Blowers inlet line  ‐1 ~ 35 0 35 Bar‐G 0 35.0 Bar‐G

27 7 PT‐700A Pressure Transmitter Main Steam Header ‐1 ~ 210 0 120 Bar‐G 0 120.0 Bar‐G

28 8 PT‐700B Pressure Transmitter Main Steam Header ‐1 ~ 210 0 120 Bar‐G 0 120.0 Bar‐G

29 9 TT‐600 Temperature Transmitter SH‐01 outlet to DSH‐01 Inlet line 0 ~ 1100 0 1100 °C 0 1100.0 °C

30 10 TT‐601 Temperature Transmitter SH‐01 outlet to DSH‐02 Inlet line 0 ~ 1100 0 1100 °C 0 1100.0 °C

31 11 TT‐602 Temperature Transmitter DSH‐01 outlet to Super Heater‐02 inlet line  ‐180 ~ 500 0 500 °C 0 500.0 °C

1 of 3
  Doc No 18001‐000‐B25‐050
INSTRUMENT CALIBRATION RANGES   Rev No. 1
  Sheet No. 3

TRANSMITTER  DCS 
Line No.
Sr. No.

CALIBRATION RANGE CALIBRATION RANGE
TAG NO. INSTRUMENT DESCRIPTION SERVICES RANGE UNIT UNIT REMARKS
LRV URV LRV URV

32 12 TT‐603 Temperature Transmitter DSH‐02 outlet to Super Heater‐02 inlet line  ‐180 ~ 500 0 500 °C 0 500.0 °C

33 13 TT‐604 Temperature Transmitter SHS to Soot Blowers inlet line ‐180 ~ 500 0 500 °C 0 500.0 °C

14 TT‐605 Temperature Transmitter Soot Blowers Steam Line to Blow down Tank (For Evap's. & SH's) ‐180 ~ 500 0 500 °C 0 500.0 °C


34

35 15 TT‐606 Temperature Transmitter Soot Blowers Steam Line to Blow down Tank (For APH's. & Eco's) ‐180 ~ 500 0 500 °C 0 500.0 °C

36 16 TT‐607 Temperature Transmitter Superheater ‐2 outlet 0 ~ 1100 0 1100 °C 0 1100.0 °C

37 17 TT‐609A Temperature Transmitter Main SHS to Process Line 0 ~ 1100 0 1100 °C 0 1100.0 °C

38 18 TT‐609B Temperature Transmitter Main SHS to Process Line 0 ~ 1100 0 1100 °C 0 1100.0 °C

39 19 TT‐609C Temperature Transmitter Main SHS to Process Line 0 ~ 1100 0 1100 °C 0 1100.0 °C

40 20 TT‐608 Temperature Transmitter Main SHS to Process Line after Start up vent line 0 ~ 1100 0 1100 °C 0 1100.0 °C

41 21 TT‐700 Temperature Transmitter Main steam header 0 ~ 1100 0 1100 °C 0 1100.0 °C

42 22 TT‐701 Temperature Transmitter Main steam header 0 ~ 1100 0 1100 °C 0 1100.0 °C

43

44 Reference P&ID: Air System (18001‐B01‐003‐00‐01 OF 01)

45 1 LT‐1200 Level Transmitter Condensate Storage Vessel (CO‐01) ± 400 ‐47.2 0 "WC 0 100.0 %

46 2 FT‐1101 Flow Transmitter APH‐01 Outlet  to Dumping grate inlet Air Duct ± 1000 0 10 mBarg 0 139456 Nm³/hr

47 3 FT‐1102 Flow Transmitter APH‐01 Outlet  to Overfiring Nozzels inlet Air Duct ± 1000 0 16 mBarg 0 89682 Nm³/hr

48 4 PT‐1700 Pressure Transmitter Condensate Storage Vessel (CO‐01) ‐1 ~ 35 0 5 Bar‐g 0 5.0 Bar‐g

49 5 PT‐602 Pressure Transmitter Deaerator heating Steam to SAH‐01 inlet line ‐1 ~ 35 0 3.5 Bar‐G 0 3.5 Bar‐G

50 6 PT‐1100 Pressure Transmitter APH‐01 Outlet to Dumping grate inlet Air Duct ± 1000 0 20 mBarg 0 20.0 mBarg

51 7 PT‐1101 Pressure Transmitter APH‐01 Outlet  to Overfiring Nozzels inlet Air Duct ± 1000 0 20 mBarg 0 20.0 mBarg

52 8 PT‐1102 Temperature Transmitter PFDF‐01&02 Outlet Air Duct ± 1000 0 40 mBarg 0 40.0 mBarg

53 9 PT‐1103 Temperature Transmitter SAF‐01&02 Discharge Duct ± 1000 0 150 mBarg 0 150.0 mBarg

54 10 PT‐1800 Pressure Transmitter Instrument Air Line ‐1 ~ 35 0 10 Bar‐g 0 10.0 Bar‐g

55 11 TT‐1101 Temperature Transmitter APH‐01 Inlet Air Duct   ‐50 ~ 260 0 200 °C 0 200.0 °C

56 12 TT‐1102 Temperature Transmitter APH‐01 Inlet Air Duct  ‐50 ~ 260 0 200 °C 0 200.0 °C

57 13 TT‐1103 Temperature Transmitter APH‐01 Outlet to Dumping grate inlet Air Duct ‐180 ~ 500 0 350 °C 0 350.0 °C

58 14 TT‐1104 Temperature Transmitter APH‐01 Outlet to Overfiring Nozzels inlet Air Duct ‐180 ~ 500 0 350 °C 0 350.0 °C

59

60 Reference P&ID: Flue Gas System (18001‐B01‐004‐00‐01 OF 01)

61 1 PT‐1500A Pressure Transmitter Furnace ± 1000 ‐40 +40 mBarG ‐40.00 +40.00 mBarG

62 2 PT‐1500B Pressure Transmitter Furnace ± 1000 ‐40 +40 mBarG ‐40.00 +40.00 mBarG

2 of 3
  Doc No 18001‐000‐B25‐050
INSTRUMENT CALIBRATION RANGES   Rev No. 1
  Sheet No. 3

TRANSMITTER  DCS 
Line No.
Sr. No.

CALIBRATION RANGE CALIBRATION RANGE
TAG NO. INSTRUMENT DESCRIPTION SERVICES RANGE UNIT UNIT REMARKS
LRV URV LRV URV

63 3 PT‐1500C Pressure Transmitter Furnace ± 1000 ‐40 +40 mBarG ‐40.00 +40.00 mBarG

64 4 PT‐1501 Pressure Transmitter EVA‐01 outlet to APH‐01 inlet Duct  ± 1000 ‐40 +40 mBarG ‐40.00 +40.00 mBarG

65 5 PT‐1502 Pressure Transmitter Economizer‐01 outlet Duct  ± 1000 ‐60 +60 mBarG ‐60.00 +60.00 mBarG

66 6 TT‐1500 Temperature Transmitter EVA‐01 outlet to APH‐01 inlet Duct  ‐180 ~ 500 0 1100 °C 0 1100.0 °C

67 7 TT‐1502 Temperature Transmitter Economizer‐02 outlet Duct  ‐180 ~ 500 0 1100 °C 0 300.0 °C

68

Initial

Faisal Akram Muhammad Asghar
Abbreviation
ENGINEERED BY Checked BY

3 of 3