CESAB BT BLITZ 318-416-418-320-420-C3E120 Service Manual
CESAB BT BLITZ 318-416-418-320-420-C3E120 Service Manual
CESAB BT BLITZ 318-416-418-320-420-C3E120 Service Manual
C3E120 C4E120
C3E150 C4E150
C3E160 C4E160
C3E160L C4E160L
C3E180 C4E180
C3E180L C4E180L
C3E200 C4E200
036-0410-07 04/2005
PAGINA INTENZIONALMENTE BIANCA
036-0410-07
SERVICE MANUAL index
page 1
Copyright by
CESAB S.p.A
via Persicetana Vecchia, 10
40132 Bologna - Italy
Tel. (0039) 051.20 54 11
Fax (0039) 051.72 80 07
E-mail: [email protected]
INDEX
036-0410-07
SERVICE MANUAL chapter A
page 1
CHAPTER A
GENERAL INFORMATION
1,2 - 2,0 t A.C. Electric
chapter A SERVICE MANUAL 036-0410-07
page 2
036-0410-07
SERVICE MANUAL chapter A
page 3
TECHNICAL DATA
1,2 - 2,0 t A.C. Electric
chapter A SERVICE MANUAL 036-0410-07
page 4
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter A
page 5
1,2 - 2,0 t A.C. Electric
chapter A SERVICE MANUAL 036-0410-07
page 6
036-0410-07
SERVICE MANUAL chapter 0000
page 1
CHAPTER 0000
CHASSIS
1,2 - 2,0 t A.C. Electric
chapter 0000 SERVICE MANUAL 036-0410-07
page 2
CHASSIS INDEX
PEDALS page 4
DASHBOARD page7
PLATES page 9
036-0410-07
SERVICE MANUAL chapter 0000
page 3
B A
J
H
C DESCRIPTION OF MAIN PARTS
K
D
A) Mast frame
B) Opening for lifting battery
I
E F C) Seat
D) Electronic control unit compartment
G
E) Counterweight
F) Hydraulic valve commands
N M Q G) Control valve cover
H) Lifting jack
I) Lifting fork carriage
B J) Overhead guard
J A K) Present man device
M) Driven wheels
N) Steered wheels
C
K H Q) Forks
D
E
F
I
G
N M Q
1,2 - 2,0 t A.C. Electric
chapter 0000 SERVICE MANUAL 036-0410-07
page 4
OPERATOR'S SEAT
A
Parking brake lever (A)
B
G
036-0410-07
SERVICE MANUAL chapter 0000
page 5
M
STEERING COLUMN PUSH BUTTONS
N
It is strongly recommended to avoid operating
both push buttons when the truck is running.
M
N
Functions
BATTERY COVER
- Handle for a better opening / closing (1)
- Hook with opening button(2)
2 1
036-0410-07
SERVICE MANUAL chapter 0000
page 7
DASHBOARD
The dashboard consists of a series of instruments and warning lights to check the correct operation of
the truck.
15 1 6 2 3 4 5 14
9 10 11 12 8 7 13
DASHBOARD CONTROLS
1 1) Battery charge status indicator:
This bar consists of 3 green LEDS on the right side, 4 orange LEDS in the
middle and 3 red LEDS on the left side; when the battery is charged the
first green LED on the right is On; while the battery discharges, the LEDS
2 turn On or Off, one per time, from the right to the left according with the
battery charging status. When the battery is 80% discharged, the first red
LED on the left is On, the display (10) shows the alarm code 1C so the
battery must be recharged (reserve). There is an indication on the dashboard
3 (4) and the lifting speed is reduced because there is a current cutback by
50%. The battery charge indicator does not rearm if the battery charging
status is between 70% and 100%. It can be adjusted (see at chapter 5000).
036-0410-07
SERVICE MANUAL chapter 0000
page 9
PLATES
A IDENTIFICATION PLATE
B CAPACITY PLATE
The plates positions, as shown in the picture, are refered to the standard fork lift trucks; those positions
can be modified in case of special truck configuration.
B (1,2 - 1,5 t)
B (1,6 - 2,0 t)
V
Cod. 0312005
Cod. 0312004
DERATED CAPACITY Kg
036-0410-07
SERVICE MANUAL chapter 1000
page 1
CHAPTER 1000
MOTORS/ ENGINES
1,2 - 2,0 t A.C. Electric
chapter 1000 SERVICE MANUAL 036-0410-07
page 2
036-0410-07
SERVICE MANUAL chapter 1000
page 3
TRACTION MOTORS
LIFTING MOTOR
036-0410-07
SERVICE MANUAL chapter 1000
page 5
TRACTION MOTORS
LIFTING MOTOR
1,2 - 2,0 t A.C. Electric
chapter 1000 SERVICE MANUAL 036-0410-07
page 6
036-0410-07
SERVICE MANUAL chapter 2000
page 1
CHAPTER 2000
036-0410-07
SERVICE MANUAL chapter 2000
page 3
036-0410-07
SERVICE MANUAL chapter 2000
page 5
Pignon
1,2 - 2,0 t A.C. Electric
chapter 2000 SERVICE MANUAL 036-0410-07
page 6
036-0410-07
SERVICE MANUAL chapter 3000
page 1
CHAPTER 3000
BRAKES / WHEELS
1,2 - 2,0 t A.C. Electric
chapter 3000 SERVICE MANUAL 036-0410-07
page 2
036-0410-07
SERVICE MANUAL chapter 3000
page 3
BRAKE SYSTEM
M N O P SERVICE BRAKE
Oil-bath brakes are inside the reduction gear box and use
the same oil.
PARKING BRAKE
The hand parking brake operates by means of the same disks as the service brake.
J) Release system
K) Parking brake lever
V) Microswitch
W)Brake block anchor
X) Parking brake lever adjusting screw
V
W
X
W
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 3000
page 5
Main piston
Pad
Brake pin
Fulcrum
Brake cylinder
Wheel cylinder
Oil area
Spring
Disks group
The brake effect is activated when the brake cylinder of the reduction gear is moving. It moves when the
parking brake pedal or the brake pedal is pressed.
When the brake pedal is pressed the oil moves the wheel cylinder which, by pressing against the side surface
of the reduction gear, moves the wheel brake cylinder. This turns around the fulcrum and presses against the
brake pin that pushes the pad. The pad pushes the main piston that closes the brake disks, obtaining the
braking effect.
When the brake pedal is released the springs push the main piston in the neutral position, freeing the disks.
The same movement around the fulcrum is obtained by pulling the parking brake lever that moves the brake
cylinder mechanically.
1,2 - 2,0 t A.C. Electric
chapter 3000 SERVICE MANUAL 036-0410-07
page 6
BRAKE DISKS
Gear group 1
Plate disk
Gear group 2
Pinion
036-0410-07
SERVICE MANUAL chapter 3000
page 7
A: Wheel
A B: Reduction gear
D
C: Electric motor
D: Wheel brake cylinder
E: Metal parking brake cable
C
F: Oil brake hose
B
G: Threaded bar M8
H: Threaded bar M14 (see next page)
In order to replace the wheel brake cylinder D it is possible to proceed in two different ways:
1st WAY
1) Lift the truck
E F D
2) Remove cable E and hose F
3) Remove wheel A
2nd WAY
036-0410-07
SERVICE MANUAL chapter 3000
page 9
STANDARD TYRES
C
CUSHION
→ →
SE
SUPERELASTICHE
→
PN
PNEUMATICHE
→
STANDARD TYRES
Type Size Air Truck
Pressure
(C)
FRONT 432x152 1,2-1,6L t
FRONT 457x178 1,8-2,0 t
REAR 381x127 ALL
(SE)
FRONT 18x7-8 1,2-1,6L t
FRONT 200/50-15 1,8-2,0 t
REAR 16x6-8 ALL
(PN)
FRONT 18x7-8 10 bar ALL
TIGHTENING TORQUES
WHEEL TORQUE
14 daNm steering wheels
14 daNm driving wheels
DRIVE UNIT TORQUE
2,3 daNm electric motor securing
13,5 daNm unit securing to frame
5 daNm service brake delivery pipes screw
5 daNm parking brake cable fixing screw
2,2 daNm oil filling and draining cap
VARIOUS TORQUES
4,9 daNm mast-securing U-bolts
0,8÷1,2 daNm jack collar self-locking nuts
20 daNm counterweight locking screws
1,2 - 2,0 t A.C. Electric
chapter 3000 SERVICE MANUAL 036-0410-07
page 10
036-0410-07
SERVICE MANUAL chapter 4000
page 1
CHAPTER 4000
STEERING SYSTEM
1,2 - 2,0 t A.C. Electric
chapter 4000 SERVICE MANUAL 036-0410-07
page 2
036-0410-07
SERVICE MANUAL chapter 4000
page 3
STEERING CONTROL
The steering uses the same oil as the lifting by means of a priority valve, which guarantees a sufficient
oil flow to the power steering.
The oil capacity is checked by the Ls signal (load - sensing), coming from the steering unit so that the
oil quantity sent to the power steering is equal to its real request.
The exceeding oil is sent to the control valve for other functions.
When the steering wheel is turned, proportionally to the above rotation, the steering unit “measures” a
volume of oil and sends it into the steering cylinder.
In order to set the power steering pressure, the following operation are necessary:
1 - Fit a manometer on the pressure access point (A) on the punp;
2 - In order reach the adjusting screw (B) remove the cap (by means of an Allen wrench) positioned
on the upper side of the orbitrol (power steering unit);
- screw in to increase the pressure
- screw out to decrease the pressure
A
1,2 - 2,0 t A.C. Electric
chapter 4000 SERVICE MANUAL 036-0410-07
page 4
STEERING CYLINDER
ORBITROL
PRIORITY
VALVE
A A
PUMP
FILTER
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 4000
page 5
3 WHEELS
R
L
LOAD
SENSOR R L
R
è
L 4 WHEELS
LOAD
è è R
SENSOR
L
è
ORBITROL
PRESSURE SETTING
90-100 BAR
Adjusting:
Screw in = highter pressure
Screw out = lower pressure
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 4000
page 7
3 WHEELS VERSION
The 3 wheels uses a static system. It means that the oil reaches the load sensor on the priority valve only when the
steering is moving.
PRIORITY VALVE
4 WHEELS VERSION
The 4 wheels uses a dinamic system. It means that the oil always reaches the load sensor on the priority valve.
On the priority valve there is a channel that connect LS to PP in order to guarantee always a flow of oil for a prompt
replay of the steering. The increasing of the pressure on the system can create a return pressure on the line LS (that
is connected to PP) and a conseguent kickback on the steering. Another no return valve is used on the line LS to
avoid this situation.
PRIORITY VALVE
24 daNm
036-0410-07
SERVICE MANUAL chapter 4000
page 9
I
B = 80° Standard
ANGLE MEASURED FROM THE
AXLE FRAME TO THE INTERNAL
WHEEL THROUGH A SPECIAL
I
DEVICE
I
6 daNm
12 daNm
1,2 - 2,0 t A.C. Electric
chapter 4000 SERVICE MANUAL 036-0410-07
page 10
BEARING ADJUSTMENT
Steering wheels
- lift the steering wheels
- remove cap (1);
- fasten the nut with a torque setting of 6 dNm;
- turn the hub of 2-3 turns in both senses;
- unfasten nut (3) and retighten with a 2-1 daNm torque;
- check that the wheels slide correctly (max. rolling final torque: 0.2 dNm) and that there is no side play
(maximum axial play of 0.05 mm);
- reassemble the cap (1);
- lower the wheels again and check that all bolts fixing the wheel disk (5) to hub (2) are well tightened.
3
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 5000
page 1
CHAPTER 5000
036-0410-07
SERVICE MANUAL chapter 5000
page 3
Warning
The battery normal working range is from 100% to 20% of the capacity. For the battery protection,
don’t let the residual capacity to drop down under 20% of the charge. Under this limit you can have
possible battery damages and, above all, logic units malfunctions and stops that could invalidate the
truck safe use.
LIFTING MOTOR
036-0410-07
SERVICE MANUAL chapter 5000
page 5
ENCODER
The encoder function is to generate motors feed-back signals to
the logic unitis (motor running; R.P.M.; rotation direction). It is
Encoder built-in the bearing placed on the opposite side of the motor drive
shaft
12V !
_ +V > 13Volts
_ Short circuit between signal and supplay
_ Induction heating
_ Hammer mounting
036-0410-07
SERVICE MANUAL chapter 5000
page 7
D G F C
A) Traction module
B) Lifting module
C) Contactors
D) Panel cooling fan
E) Power fuses
F) Fuses (covered by the light board)
G) Light card
ACCELERATOR PEDAL
180 mm
FUSE BOX
The fuse box is located next to the battery connector, covered by the light card.
1 3
4 FUSE DESCRIPTION
1. F1 key fuse 10 Amp
2. F2 horn fuse 5 Amp
3. F3 DC/DC converter fuse 20 Amp
4. Diode
LIGHT CARD 2 1 3
CONTACTORS
24 VOLT FUSES
This box is located under the dashboard and it is used for all the
24 V fuses only.
5 Connector for the wiring.
6 Connection bars transfer the positive pole to all fuses.
7 Direction lights intermittence connector.
This box is present on the truck only if optional equipments are
foreseen
5 6 7
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 5000
page 9
DC/DC CONVERTER
The DC/DC converter is located on the truck front side, under the I/O card fixed on the same plate. The STD
machines use a converter to 140 Watt. It is under contactor (see electrical diagram).
CONVERTER
P/N Power
2773040 140W
2773041 240W
2773042 360W
2773043 720W
2773044 960W
STD. MACHINE 86 W
REVERCE ACUSTIC WARNING 05 W
FLASH BEACON 03 W
ROTARY BEACON 70 W
WIPER 100W
2 WORKING LIGHTS 140W
LIGHTENING EQUPIMENT (STREET LIGHT) 200W
HEATER 150W
Choose the right converter rounding up the calculation of the maximum power used and considering a margin
of 10%.
A std machine uses a converter of 140W and the maximum power used is 86W.
It means that there are 40W still available.
1,2 - 2,0 t A.C. Electric
chapter 5000 SERVICE MANUAL 036-0410-07
page 10
ELECTRONIC PANELS
TECHNICAL SPECIFICATIONS
“DUALAC2” TRACTION
“AC2” LIFTING
036-0410-07
SERVICE MANUAL chapter 5000
page 11
OPERATIONAL FEATURES
- Speed control.
- Very good behaviour on a slope due to the speed feedback.
- The motor speed follows the accelerator, starting a regenerative braking if the speed overtakes the speed
set point.
- Stable speed in every position of the accelerator.
- Regenerative release braking based upon deceleration ramps.
- Regenerative braking when the accelerator pedal is partially released (deceleration).
- Direction inversion with regenerative braking based upon deceleration ramp.
- Regenerative braking and direction inversion without contactors: only the two main
contactors are present.
- The release braking ramp can be modulated by an analog input, so that a proportional brake feature is obtained.
- Very good sensitivity at low speeds.
- Voltage boost at the start and with overload to obtain more torque (with current control).
- High efficiency of motor and battery due to high frequency commutations.
- Self diagnosis with indication of the fault shown by numeric display.
- Modification of parameters through the programming console.
- Internal hour-meter with values that can be displayed on the console.
- Memory of the last five alarms with relative hour-meter and temperature displayed on the console.
- Test function within console for checking main parameters.
- Hydraulic steering function:
1) traction inverter
- the traction inverter sends a "hydraulic steering function" request to the pump inverter on the can-bus line
2) pump inverter
- the pump inverter manages a "hydraulic steering function". That is, it drives the pump motor at the
programmed speed for the programmed time.
DIAGNOSIS
The microprocessor continually monitors the inverter and carries out a diagnostic procedure on the main
functions. The diagnosis is made in 4 points:
1) Diagnosis on key switch closing that checks: watchdog circuit, current sensor, capacitor charging, phases’
voltages, contactor drives, can-bus interface, if the switch sequence for operation is correct and if the
output of the accelerator unit is correct.
2) Standby diagnosis at rest that checks: watchdog circuit, phases’ voltages, contactor driver, current sensor,
can-bus interface.
3) Diagnosis during operation that checks: watchdog circuits, contactor driver, current sensors, can-bus
interface.
4) Continuous diagnosis that checks: temperature of the inverter.
GENERAL PRECAUTIONS
- Do not connect the inverter to a battery with a nominal value different from the value indicated on the
chopper plate. If the battery value is greater, the MOS may fail; if it is lower, the control unit does not
"power up".
- During the battery charge, disconnect the INVERTER from the battery.
- Supply the INVERTER only with battery for traction; do not use a power supply.
- When the chopper is installed, make tests with the wheels raised from the ground, in order to avoid danger-
ous situations due to connection errors.
- After the chopper is switched off (key off), the filter capacitors remain charged for some minutes; if you
need to work on the inverter, discharge them using a
10W ÷ 100W resistance connected from the +Batt to the -Batt.
- Before carrying out any arc-welding on the trucks, disconnect the battery and short-circuit the unit between
positive (+) and negative (-).
PROTECTIONS
- Connection Errors:
All inputs are protected against connection errors.
- Thermal protection:
If the chopper temperature exceeds 75°C, the maximum current is reduced in
proportion to the thermal increase. The temperature can never exceeds 100°C.
- External agents:
The inverter is protected against dust and the spray of liquid to a degree of
protection meeting IP54.
- Protection against uncontrolled movements:
The main contactor will not close if:
- the Power unit is not functioning.
- the Logic is not functioning perfectly.
- the output voltage of the accelerator does not fall below the minimum voltage value stored, with 1V
added.
- running microswitch in closed position.
- Protection against accidental Start up
A precise sequence of operations are necessary before the machine starts.
Operation cannot begin if these operations are not carried out correctly.
Drive requests must be made after closing the key switch.
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 5000
page 13
CONNECTORS
B1 PCLRXD
B2 NCLRXD
B3 PCLTXD
B4 NCLTXD console connecto
B5 GND
B6 +12
B7 FLASH
B8 FLASH
036-0410-07
SERVICE MANUAL chapter 5000
page 15
By connecting a wire between the pin C10 and the positive (+Vb) from the seat switch, it is possible to disable
the reduction of speed (CUTBACK SPEED 3) normally on.
By connecting a microswitch on the wire between the pin C10 and the seat switch, it is possible to set ON or
OFF the CUTBACK SPEED 3 (parameter located in the menu PARAMETER CHANGE).
Disconnect the connector from the logic unit and and remove the red part
that is fixed inside by means of two tongues on the external side.
AMP770854 - 3.
CONTROL LOGIC
1,2 - 2,0 t A.C. Electric
chapter 5000 SERVICE MANUAL 036-0410-07
page 16
STEERING SYSTEM
3 WHEELS
When the potentiometer reaches approximately
70° the traction logic unit controls the motor in
order to stop one motor completely according
to the direction. In this case the truck turns
around point A. If the stroke of the potentiometer
increases the motor that was stopped starts
running in the opposite direction and the truck
starts turning around point B.
4 WHEELS
When the potentiometer reaches the maximum
stroke the traction logic unit controls the motor
in order to stop one motor completely according
to the direction. In this case the truck turns
around point A.
3 WHEELS
Transducer steering-wheel with potentiometer
The potentiometer has the following characteristics:
- Resistance 2,2 Kohm.
- The potentiometer supply is 12 V (5 V on the console). The
potentiometer should be installed so that in the "zero position"
(straightened wheels) the output voltage is 2,5 V. The
potentiometer has to be fitted so that when the trolley turns
clockwise the voltage decreases.
4 WHEELS
RIGHT
STEERING
POTENTIOMETER
LEFT
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 5000
page 17
3 WHEELS
-90° +90°
Steering potentiometer (3 wheels)
Yellow : ~ 12 V
Green : ~ 0,7 V with max. steering angle right hand + 90°
2,5 V with straight wheel
~ 4,3 V with max. steering angle left hand - 90°
Black : 0V
Grey
) Black
Red
2,2 KOhm Í ) Green
Black
) Yellow
4 WHEELS
-58° +80°
Steering potentiometer (4 wheels)
Yellow : ~ 12 V
Green : ~ 0,9V with max. steering angle right hand + 80°
2,5 V with straight wheel
~ 3,8 V with max. steering angle left hand - 58°
Black : 0V
Grey
) Black
Red
2,2 KOhm Í ) Green
Black
) Yellow
1,2 - 2,0 t A.C. Electric
chapter 5000 SERVICE MANUAL 036-0410-07
page 18
036-0410-07
SERVICE MANUAL chapter 5000
page 19
CONNECTORS
A1 PCLRXD
A2 NCLRXD
A3 PCLTXD
A4 NCLTXD Console connector
A5 GND
A5 GND
A6 +12
A7 FLASH
A8 FLASH
E4 CM Common of LIFT ENABLE / 1st SPEED / 2nd SPEED/ 3rd SPEED /4th SPEED /
HYDRO / SR microswitches.
E12 HYDRO REQ. Input for hydraulic steering request. Active high.
F1 KEY Connected to +Batt through the series costituited by the key switch, the protection
diode and a 10A fuse
F5 SAFETY If not connected to -Batt the MC coil power output will be disabled.
Can also be used as a general purpose input.
F6 PTHERM Input for motor temperature sensor.
F11 GND -Batt.
F12 NTHERM -Batt.
1,2 - 2,0 t A.C. Electric
chapter 5000 SERVICE MANUAL 036-0410-07
page 20
KEY
CONTROL LOGIC
POTENTIOMETER
MICROSWITCHES
PROGRAMMING
CONSOLE
KEY
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 5000
page 21
ELECTRICAL CIRCUIT CONNECTION
DUAL AC2 TRACTION UNIT AND AC2 LIFTING UNIT
355 A FUSE
SEGNALI
CAN-BUS
300 A FUSE
1,2 - 2,0 t A.C. Electric
chapter 5000 SERVICE MANUAL 036-0410-07
page 22
1. TRACTION ACQUISITION
2. ADJUST BATTERY
3. STEERING POTENTIOMETER
4. Vacc PROGRAM
5. STEER TABLE
for all references see “MAPS FOR USING THE CONSOLE - TRACTION” in the following pages
1. LIFTING ACQUSITION
2. Vacc PROGRAM (with mechanic distributor only)
for all references see “MAPS FOR USING THE CONSOLE - LIFTING” in the following pages
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 5000
page 23
ARM
COMMANDS
LIFTING ON BOARD
COMMAND
LIGHT CARD I / O CARD
TRACTION ON
BOARD COMMAND
MHYRIO ELECTRO
CONTROL VALVE
LEGEND
- forward switch
- backward switch
- horn switch
- lifting fingertip
- tilt fingertip
fingertip - sideshift fingertip
- 4° way fingertip (opt)
- 5° way fingertip (opt)
ARM CARD *
LIGHT CARD *
I / O CARD *
MHYRIO *
CONTROL VALVES *
036-0410-07
SERVICE MANUAL chapter 5000
page 25
The CAN BUS technology is a way to assemble the electronic parts of the machines. It has been designed to avoid
the enormous quantity of cables that normally are used to connect two or more electric components. For example,
in case you want to connect all potentiometers to control the distributor, it is necessary to fix a lot of wires with
consequent reduction of space. Normally a cable in an electric installation is used for only one function: either
positive, or negative, or signal.
In order to avoid the above problem the NEW TECHNOLOGY is used for saving in space given that all the
information go only through two cables and they are decoded by microchips located in different parts of the truck.
One of the greatest advantages is that all microchips can communicate with each other and control functions which
work contemporaneously in a short time.
The CAN transfers all data giving priority to the most important signals.
The CAN is composed of four cables: two for the feeding and two for the signals.
It is necessary to have two cables for the feeding given that the microchips are not fed.
BUS: In electronics and computer science it indicates a set of wires connecting several microchips,
thus allowing information exchange within the circuit.
BIT: Figure of the binary numeration that can have only two values: 1 (high) - 0 (low).
In computer science it defines the information unit. The bit/sec. defines the capacity of a channel,
that is the quantity of information which can be transmitted through the channel in one second.
1,2 - 2,0 t A.C. Electric
chapter 5000 SERVICE MANUAL 036-0410-07
page 26
ARM CARD
The arm card, located inside the seat arm is present in fingertips /
joysticks truck version. It is supplied by the dc / dc converter with
24 V.
The fingertips /joysticks version requires also the use of an
additional logic unit (Mhyrio)
FUNCTIONS
It controls and converts from analogic to digital the fingertips /
joysticks potentiometers signals in order to drive, via Mhyrio, the
electric distibutor, equipped with solenoid valves.
It also controls the push buttons signals of the forward / backward
directions and of the horn.
CONNECTIONS
The card is connected by the cab-bus wiring to the light card
SETTINGS
In order to inform the card about the potentiometers type used, the
following setting is required:
LAY-OUT
036-0410-07
SERVICE MANUAL chapter 5000
page 27
FINGERTIP
JOYSTICK
PB1=Horn pushbutton
PB2=Backward pushbutton
PB3=Forward pushbutton
PB1
PB2
PB3
1,2 - 2,0 t A.C. Electric
chapter 5000 SERVICE MANUAL 036-0410-07
page 28
LIGHT CARD
FUNCTIONS
- Controlling of the back lights.
5
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 5000
page 29
CONNECTOR DESCRIPTION
Connector 1
5 1 It is a connector to 8 Pins used for controlling the lights.
PINS 1-5 are connected together = 24 Volt.
6 2
PINS 2-6 are connected together = output of the stop lights 0-24 Volt. It is a proportional
7 3 value given that the voltage depends on the temperature of the lamp bulbs
PINS 3-7 are connected together = output of the reverse lights 0-24 Volt.
8 4 It is a proportional value given that the voltage depends on the temperature of the
lamp bulbs
PINS 4 negative signal
PIN 8 24 Volt input for the converter 24-5 Volt located on the card.
Connector 2
4 1 It is a connector to 6 Pins.
5 2 PIN 1 CAN L
PIN 2 CAN H
6 3 PIN 3 GND
PIN 4 Not used
PIN 5 Out put 24 Volt
PIN 6 Not used
Connector 3
4 1 It is a connector to 6 Pins.
5 2 PIN 1 CAN L
PIN 2 CAN H
6 3 PIN 3 GND
PIN 4 Not used
PIN 5 Out put 24 Volt
PIN 6 Not used
Connector 4
4 1 It is a connector to 6 Pins.
5 2 PIN 1 CAN L
PIN 2 CAN H
6 3 PIN 3 GND
PIN 4 Not used
PIN 5 Out put 24 Volt
PIN 6 Not used
Led 5
shows that the light card is fed but is not receiving the CAN-BUS input
C B A Converter 6
PIN A 24 Volt
PIN B GND
PIN C 5 Volt
24 V / 5 V
Resistance 7
It is the input resistance. R17 = 100 Ohm 3 Watt.
The connectors 2-3-4 are connectors for the CAN-BUS and they can be inverted without
problem
Connector J1 (J38*) for input of the brake oil tank LED, button for the
programmed performance, button for the speed reduction.
Connector J2 not used
Connector J3 (J5*) to control the electric horn. The horn is electronic and this is
the electric connection on the card:
J3/1 command signal (B white cable) from Arm Card
via CAN-BUS
J3/2 negative (N black cable)
Connector J4 (J34*) for the pedals: accelerator pedal, brake pedal, parking
brake lever, horn.
Connector J5 (J135*) CAN-BUS (light card) and feeding to 24V
Connector J6 (J136*) CAN-BUS (dashboard) and feeding to 24V
Connector J7 (J1*) for traction motors temperature sensors.
Connector J8 (J98*)(+BV) feeding for Mhyrio logic unit
Connector J10 (J40*) for the mechanic distributor (in this case the voltage on the
micro is 5 volt).
Connector J13 (J139*) CAN-BUS signals and feeding to 48V for Mhyrio logic
unit
NOTE: (Jxxx*) WIRING DIAGRAM CONNECTORS
J3/1 J3/2
HORN ELECTRIC CONNECTION
J7 J3 ( horn side)
The horn is electronic and needs a signal to
J2 J5 work. It is continually supplied by the following
10
cables: A, light blue, positive cable + 48 V
["+" on the horn] and N black cable negative
["-" on the horn]. The command signal on cable
J6 B white cable ["IN" on the horn] is a high signal,
J10 when the horn push button is pressed the signal
J8 goes to the negative and the horn begins to beep.
J1 J4 J13
On the I/O card there is another resistance of pull up for the CAN BUS. It
could be connected in case of disconnection of the dashboard. To perform
this operation it is enough to connect the two free PINS circled in the
picture by means of a brigde.
PINS for connecting the extra resistance for the CAN BUS
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 5000
page 31
MHYRIO CARD
The cables for the CAN-BUS (it means for digital input) arrive
to the same connector used for the feeding:
POTENTIOMETER CONFIGURATION
è
è
è
è
036-0410-07
SERVICE MANUAL chapter 5000
page 33
FINGERTIPS
RED : 5V
GREEN : 0 ÷ 5(AT REST 2,5 V)
S1 - S3 - S5 - S7
BLACK : 0V
S2 - S4 - S6 - S8
JOYSTICK
(FORWARD-BACKWARD MOV.)
S1 - S5
ORANGE : 5 V
S2 - S6 YELLOW : 0 ÷ 5 (AT REST 2,5 V)
PB4 - PB5
RED : 0V
JOYSTICK
S3 - S7 (LEFT-RIGHT MOV.)
S4 - S8
GREEN : 5V
BLACK : 0 ÷ 5 (AT REST 2,5 V)
WHITE : 0V
The test of the potentiometer can be carried out in two different ways:
There is a difference between the values obtained in the two methods because, in case of voltage
measurement, the console increases the real value of 0.4 volt and it is a default condition
Yellow Yellow
)
1,2 KOhm Red Green
ç )
4,5 KOhm
é
Green Black
)
036-0410-07
SERVICE MANUAL chapter 5000
page 35
LIFTING POTENTIOMETER CONFIGURATION
(CONTROL VALVE VERSION)
The test of the potentiometer can be carried out in two different ways:
There is a difference between the values obtained in the two methods because, in case of voltage
measurement, the console increases the real value of 0.4 volt and it is a default condition
137 Yellow
)
1
é 5 KOhm
2 135 Green
ç )
3 136 Black
)
136
137
3
135
1,2 - 2,0 t A.C. Electric
chapter 5000 SERVICE MANUAL 036-0410-07
page 36
CONSOLE FUNCTION
GENERAL DESCRIPTION
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 5000
page 37
HOUR METER
The hour meter appears in the second line of the display when the chopper is connected. It shows the real working
hours.
PARAMETER CHANGE
The chopper parameters can be displayed and programmed via the keyboard, in real time and with operating
machine, thereby making it possible to set the chopper easily.
TESTER
It makes it possible to display the state of the chopper analogue and digital values and thereby to have a useful tool
for the analysis of chopper operation and external cables.
SAVE PARAMETER
It makes it possible to store all values relating to the parameters and the chopper hardware configuration into the
console with a program which can be selected from the keyboard.
RESTORE PARAMETER
It makes it possible to program a chopper with the parameters contained in a program generated by a SAVE.
ALARMS
The console features the possibility to read the last five alarm messages stored in the chopper and displayed together
with the time of occurrence, the number of times the alarm was sent and the temperature value at the time of the
alarm.
PROGRAM VACC
It allows to program the accelerator max. stroke.
CONSOLE DESCRIPTION
KEYBOARD
Description of key functions:
1 PROGRAM I MAX B.REVERSE ROLL 2 = Allows selection of an option or the previous menu
BRAKING COMPENS.
2 TESTER
ACCEL. R.BRAKE item
MAX SP. SPEED I
S.P. I SPEED II
3 SAVE S.P. II SPEED III
BYPASS FIELD WEAK... ENTER = Allow confirmation of selected options
4 RESTORE I MOT V.POT.
TEMP. V.BATT.
5 ALARMS TEMP. VMN.MOT.
M.SW.TEST OUT = Retains the current function
6 PROGRAM PEDAL
7 MOTOR DATA
PARAM = Allows an increase in the parameters or selects the
1 3 5 type of connected I/O
ROLL ENTER PARAM.
ROLL OUT SET SET = Allows a reduction in the parameters or selects the
2 4 6 type of connected I/O
1,2 - 2,0 t A.C. Electric
chapter 5000 SERVICE MANUAL 036-0410-07
page 38
CONSOLE CONNECTION
LIFTING UNIT
TRACTION UNIT
MHYRIO UNIT
036-0410-07
SERVICE MANUAL chapter 5000
page 39
PARAMETER CHANGE
PARAMETER CHANGE
NOT AVAILABLE.
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 5000
page 41
PARAMETER CHANGE
PARAMETER CHANGE
MHYRIO UNIT
036-0410-07
SERVICE MANUAL chapter 5000
page 43
PARAMETER CHANGE
DASHBOARD UNIT
HOURS COUNTER RUNNING/KEY: key on / lifting unit working hours counter switch
DISPLAY ON/OFF: displaied speed switch
SPEED RATIO 0-5 12: speed calculation ratio
1,2 - 2,0 t A.C. Electric
chapter 5000 SERVICE MANUAL 036-0410-07
page 44
TESTER
036-0410-07
SERVICE MANUAL chapter 5000
page 45
TESTER
TESTER
036-0410-07
SERVICE MANUAL chapter 5000
page 47
TESTER
MHYRIO UNIT
BATTERY VOLTAGE: level of battery voltage measured with the key switch ON.
CAN POT EVP: single proportional valve current setpoint, received by the canbus
(% of the current supplied to the valve).
CAN POT GROUP 1: group 1 proportional valves current setpoint, received by canbus
(0-100 % of the current supplied to the lifting, proportional % for the
lowering valve).
CAN POT GROUP 2: group 2 proportional valves current setpoint, received by the canbus
(0-100 % of the current supplied to the tilt box)
CAN POT GROUP 3: group 3 proportional valves current setpoint, received by the canbus
(0-100 % of the current supplied to the side-shift box)
CAN POT GROUP 4: group 4 proportional valves current setpoint, received by the canbus
(0-100 % of the current supplied to the 4° Way box)
TESTER
MHYRIO UNIT
NOT AVAILABLE.
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 5000
page 49
TESTER
DASHBOARD UNIT
NOT AVAILABLE.
1,2 - 2,0 t A.C. Electric
chapter 5000 SERVICE MANUAL 036-0410-07
page 50
ALARMS FUNCTIONS
1 WATCH - DOG It is a self-diagnostic test within the logic between the Master and Slave
µcontrollers. This alarm could also be caused by the canbus malfunctioning
or data transmission interferences.Therefore, before replacing the Dual AC2
unit check the correct canbus functioning and the general turck insulation.
2 EEPROM KO Fault in the area of memory in which the adjustment parameters are stored;
this alarm inhibits the truck operation, but the controller will use default
parameters. If the defect persists when the key is switched OFF and ON
again, replace the logic. If the alarm disappears, remember that the
parameters previously stored have been deleted and replaced by the default
values (see adjustin tables).
3 LOGIC FAILURE #3 Logic defect. Replace the traction unit.
4 LOGIC FAILURE #2 Fault in the hardware section of the logic boardwhich manages the phase
voltage feedback. Check the 3 power cables connected to the right traction
motor. If the fault is not caused by external reasons, replace the traction unit.
5 LOGIC FAILURE #1 This alarm signals that the interruption of protection against undervoltage /
overvoltage has been triggered. The possible reasons are:
a. Real battery undervoltage / overvoltage, or voltage loss after tht ignition
key or after the battery connector
b. Fault in the hardware section of the logic board which controls the
overvoltage protection. Logic defect. Replace the traction unit.
c. The alarm appears also when one or more phases of the right traction
motor doesn't present a correct insulation. Check the motor insulation
(with deconnected battery): it must be higher than 1 Mohm. Otherwise
check the insulation of the power cables to the motor.
6 VMN LOW Failure in the VMN test. This test starts when the ignition key is turned ON.
The alarm appears if there is a creepage on one or more phases; check
the connections of the 3 power cables from the Master unit to the right
traction motor and the cables condition also. In order to point out if the
fault is produced by an internal or external cause invert the connection of the
traction motors. It means Slave to right motor and Master to left motor.
If the problem jumps on the Slave it means that the right traction motor is
demaged, otherwise replace the traction unit.
7 VMN HIGH Failure in the VMN test. This test starts when the ignition key is turned on.
The alarm appears if one or more pover cables are not connected; check
the connections of the 3 power cables from the Master unit to the right
traction motor and the cables condition also. In order to point out if the
fault is produced by an internal or external cause invert the connection of the
traction motors. It means Slave to right motor and Master to left motor.
If the problem jumps on the Slave it means that the right traction motor is
demaged, otherwise replace the traction unit
8 CONTACTOR OPEN Failure on the contactor driver.
- Check main contactors coils and relevant wirings.
9 STBY I HIGH Failure on the current sensor.
- Replace the traction unit.
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 5000
page 51
10 CAPACITOR When the key is switch ON, the inverter tries to charge the capacitor
CHARGE through a power resistance, and check if the capitor are charged within a
timout. If they do not charge, an alarm is signalled;
the main contactor is not closed.
- Check the negative connection.
- Check voltage in the input of the key. Battery voltage must be present.
- Execute a short circuit between the key terminals.
- Replace the traction unit.
Traction
Vb D1 F1 PB1 S1 power
capacitor
11 HIGH Master or Slave or both temperatures are higher than 75°C. The maximum
TEMPERATURE current is reduced proportionally to the temperature increase. At 100°C the
max current of both inverters is reduced to zero. If the alarm is signalled
when the controller is cold:
- Replace the traction unit.
12 MOTOR This warning is signalled if the sensor of the right motor is opened (digital
TEMPERATURE sensor)
- identify the on wiring diagram the connector J1 (J7 on I/O card):
- If between the positive pin (1) and negative pin (2) there is 5V = the
sensor is open
- If between the positive pin (1) and negative pin (2) there is 0V = the
sensor is closed
- 5V must be present on the positive pin (1) and negative pin (2) in the I/O
card connector J7 (with the wiring diagram J1 connector disconnected).
In the opposite case, replace the I/O card.
1,2 - 2,0 t A.C. Electric
chapter 5000 SERVICE MANUAL 036-0410-07
page 52
036-0410-07
SERVICE MANUAL chapter 5000
page 53
14 THERMIC SENS KO The values indicated by the temperature sensor of the inverter are always
checked and if they are out of range this warning appears.
- Replace the logic unit.
15 SAFETY Replace the logic unit.
16 CAN BUS KO Comunication failure between the logic units: traction (Master & Slave),
lifting, Mhyrio and all the cards. The alarm appears if:
- CAN H and / or CAN L signals deconnected
- there is no comunication from one logic unit.
If the problem starts from one card the system recognizes in which one:
CAN BUS KO 0A : I/O card
CAN BUS KO 05 : Lifting logic unit
CAN BUS KO 04 : Slave logic unit
CAN BUS KO : Master logic unit (no suffix after the alarm message)
- Before replacing any logic unit it is suggested a preliminary check of the
CAN BUS connections.
Using the console, through connection numbersand selecting the
TESTER function, try to carry out a link with all the junction knots
toward the different logic units. Verify the links by, at least, one of the
signals from the field, i.e. microswitches, potentiometers. Where you
don’t reach the link, there is a line interruption.
17 WAITING Time lag fault on the CAN BUS comunication. The Master logic unit detects
FOR NODE wich logic unit has generated the problem
#4 The Master logic unit receives the informations caming from the Slave
logic unitwith a time lag fault.
The fault can be caused by
- interference on the can bus. Check the CAN-BUS comunication.
- broken logic. Replace the traction logic unit.
#5 The Master logic unit receives the informations caming from the
Lifting logic unit with a time lag fault.
The fault can be caused by
- interference on the can bus. Check the CAN-BUS comunication.
- false contact. Check the connections of CAN H and CAN L wires.
- broken logic. Replace the lifting logic unit.
#9 The Master logic unit receives the informations caming from the
Mhyrio logic unit with a time lag fault.
The fault can be caused by
- interference on the CAN-BUS. Check the CAN-BUS comunication.
- false contact. Check the connections of CAN H and CAN L wires.
- broken logic. Replace the Mhyrio logic unit.
18 AUX OUTPUT KO Failure on the contactor driver.
- Replace the traction unit.
19 DRIVER SHORTED Failure on the contactor driver.
Check the main contactors coils and relevant wirings.
If the failure is not due to external causes, replace the traction logic unit.
20 CONTACTOR Failure on the contactor driver.
DRIVER - Replace the traction unit.
21 COIL SHORTED Failure on the contactor driver. Check the main contactors coils and
relevant wirings. Control that there are no short-circuits in the wiring and
that the coil resistance value is correct. If the failure is not due to external
causes replace the logic unit.
1,2 - 2,0 t A.C. Electric
chapter 5000 SERVICE MANUAL 036-0410-07
page 54
CODE ALARM DESCRIPTION
22 VACC NOT OK Failure on the acceleration potentiometer signal at rest. The alarm points out
that the voltage value detected on the accelerator potentiometer is 1Volt
higher than the least value programmed with the Vacc function. Check:
- The traction potentiometer (it could be damaged or not correctly
calibrated)
- The traction potentiometer wiring.
- Carry out the Vacc setting again.
23 INCORRECT START replace the traction logic unit.
24 PEDAL WIRE KO Not used
25 WRONG BATTERY When the key is turned ON, the controller checks the battery voltage and
compares it with the “SET BATTERY” parameter setting. If the actual value
is 20% higher or lower than the nominal value, there is a fault. Replace the
battery with a correct one.
26 REMOTE IMPUT incorrect starting procedure.
28 STEER SENSOR KO This alarm signals that the steering potentiometer is out of range. There is a
fault in the following conditions:
- the “Set steer 0 pos” (straight wheels programmation) parameter is
wrong (lower than “Set steer min” or higher than “Set steer max”).
- the feedback signal of the steering potentiometer is outside the window
defined by the “Set steer min” and the “Set steer max” parameters.
In the first case, repeat the steering potentiometer acquisition. In the second
case, check the steering potentiometer and its wiring again. In case, repeat
once again the steering potentiometer acquisition .
29 FORW + BACK Incorrect sequce by starting. Check:
- Microswitch for forward/backward directions and relevant wires.
- Microswitch for parking brake and relevant wires.
1A SLAVE KO Failure on the slave module.
- Replace the traction unit.
1C BATTERY_LOW Discharged battery. If the “battery check” option is ON, a battery discharge
algorithm is carried out. When the charge level is 10% , this alarm is
ignalled and the current is reduced to the half of the programmed level.
2A CHOPPER The Dual AC2 traction unit has an erroneous configuration. Using the
NOT CONF. programming console it is possible to set the unit correctly according to the
truck configuration:
(0)double pedal version;
(1)manual inversor version;
(2)with inversor on the armrest.
(3)arm comand + direction selector on the steering column
1E CONTACTOR Failure on the contactor driver. Check the main contactors coils
CLOSED and the relevant wirings.
2C GAIN ACQUISITION This warning communicates that the logic is in phase of input acquisition. In
this phase the logic doesn't start.
2E HANDBRAKE Failure on parking brake. Check: the parking brake microswitch and the
relevant cables.
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 5000
page 55
61 WATCH - DOG It is a self-diagnostic test within the logic between the Master and Slave
µcontrollers. This alarm could also be caused by the canbus malfunctioning
or data transmission interferences.Therefore, before replacing the Dual AC2
unit check the correct canbus functioning and the general turck insulation.
62 EEPROM KO Fault in the area of memory in which the adjustment parameters are stored;
this alarm inhibits the truck operation, but the controller will use default
parameters. If the defect persists when the key is switched OFF and ON
again, replace the logic. If the alarm disappears, remember that the
parameters previously stored have been deleted and replaced by the default
values (see adjusting tables).
63 LOGIC FAILURE #3 Logic defect. Replace the traction unit.
64 LOGIC FAILURE #2 Fault in the hardware section of the logic boardwhich manages the phase
voltage feedback. Check the power cables connected to the left traction
motor. If the fault is not caused by external reasons, replace the Dual AC2
traction unit.
65 LOGIC FAILURE #1 This alarm signals that the interruption of protection against undervoltage /
overvoltage has been triggered. The possible reasons are:
a. Real battery undervoltage / overvoltage, or voltage loss after tht ignition
key or after the battery connector
b. Fault in the hardware section of the logic board which controls the
overvoltage protection. Logic defect. Replace the traction unit.
c. The alarm appears also when one or more phases of the left traction
motor doesn't present a correct insulation. Check the motor insulation
(with deconnected battery): it must be higher than 1 Mohm. Otherwise
check the power cables insulation to the motor.
66 VMN LOW Failure in the VMN test. This test starts when the ignition key is turned ON.
The alarm appears if there is a creepage on one or more phases; check
the connections of the 3 power cables from the Slave unit to the left traction
motor and the cables condition also. In order to point out if the fault is
produced by an internal or external cause invert the connection of the
traction motors. It means Slaveto right motor and Master to left motor.
If the problem jumps on the Master it means that the left traction motor is
demaged, otherwise replace the traction unit.
67 VMN HIGH Failure in the VMN test. This test starts when the ignition key is turned on.
The alarm appears if one or more pover cables are not connected; check
the connections of the 3 power cables from the Slave unit to the left traction
motor and the cables condition also. In order to point out if the fault is
produced by an internal or external cause invert the connection of the
traction motors. It means Slaveto right motor and Master to left motor.
If the problem jumps on the Slave it means that the right traction motor is
demaged, otherwise replace the traction unit.
68 CONTACTOR OPEN Failure on the contactor driver.
- Check main contactor coil and relevant wirings.
69 STBY I HIGH Failure on the current sensor.
- Replace the traction unit.
1,2 - 2,0 t A.C. Electric
chapter 5000 SERVICE MANUAL 036-0410-07
page 56
CODE ALARM DESCRIPTION
70 CAPACITOR When the key is switch ON, the inverter tries to charge the capacitor
CHARGE through a power resistance, and check if the capitor are charged within a
timout. If they do not charge, an alarm is signalled;
the main contactor is not closed.
- Check the negative connection.
- Check voltage in the input of the key. Battery voltage must be present.
- Execute a short circuit between the key terminals.
- Replace the traction unit.
Traction
Vb D1 F1 PB1 S1 power
capacitor
71 HIGH Master or Slave or both temperatures are higher than 75°C. The maximum
TEMPERATURE current is reduced proportionally to the temperature increase. At 100°C the
max current of both inverters is reduced to zero. If the alarm is signalled
when the controller is cold:
- Replace the traction unit.
72 MOTOR This warning is signalled if the sensor of the right motor is opened (digital
TEMPERATURE sensor)
- identify the on wiring diagram the connector J1 (J7 on I/O card):
- If between the positive pin (3) and negative pin (4) there is 5V = the
sensor is open
- If between the positive pin (3) and negative pin (4) there is 0V = the
sensor is closed
- 5V must be present on the positive pin (1) and negative pin (2) in the I/O
card connector J7 (with the wiring diagram J1 connector disconnected).
In the opposite case, replace the I/O card.
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 5000
page 57
74 THERMIC SENS KO The values indicated by the temperature sensor of the inverter are always
checked and if they are out of range this warning appears.
- Replace the logic unit.
75 SAFETY Replace the logic unit.
76 CAN BUS KO Comunication failure between the logic units: traction (Master & Slave),
lifting, Mhyrio and all the cards. The alarm appears if:
- CAN H and / or CAN L signals deconnected
- there is no comunication from one logic unit.
If the problem starts from one card the system recognizes in which one:
CAN BUS KO 0A : I/O card
CAN BUS KO 05 : Lifting logic unit
CAN BUS KO 03 : Master logic unit
CAN BUS KO : Slave logic unit (no suffix after the alarm message)
- Before replacing any logic unit it is suggested a preliminary check of the
CAN BUS connections.
Using the console, through connection numbersand selecting the
TESTER function, try to carry out a link with all the junction knots
toward the different logic units. Verify the links by, at least, one of the
signals from the field, i.e. microswitches, potentiometers. Where you
don’t reach the link, there is a line interruption.
77 WAITING Time lag fault on the CAN BUS comunication. The Slavelogic unit detects
FOR NODE wich logic unit has generated the problem
#4 The Slave logic unit receives the informations caming from the Master
logic unitwith a time lag fault.
The fault can be caused by
- interference on the can bus. Check the CAN-BUS comunication.
- broken logic. Replace the traction logic unit.
#5 The Slave logic unit receives the informations caming from the
Lifting logic unit with a time lag fault.
The fault can be caused by
- interference on the can bus. Check the CAN-BUS comunication.
- false contact. Check the connections of CAN H and CAN L wires.
- broken logic. Replace the lifting logic unit.
#9 The Slave logic unit receives the informations caming from the
Mhyrio logic unit with a time lag fault.
The fault can be caused by
- interference on the CAN-BUS. Check the CAN-BUS comunication.
- false contact. Check the connections of CAN H and CAN L wires.
- broken logic. Replace the Mhyrio logic unit.
78 AUX OUTPUT KO Failure on the contactor driver.
- Replace the traction unit.
79 DRIVER SHORTED Failure on the contactor driver.
Check the main contactors coils and relevant wirings.
If the failure is not due to external causes, replace the traction logic unit.
80 CONTACTOR Failure on the contactor driver.
DRIVER - Replace the traction unit.
81 COIL SHORTED Failure on the contactor driver. Check the main contactors coils and
relevant wirings. Control that there are no short-circuits in the wiring and
that the coil resistance value is correct. If the failure is not due to external
causes replace the logic unit.
82 VACC NOT OK Not used.
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 5000
page 59
CODE ALARM DESCRIPTION
84 PEDAL WIRE KO Failure on the acceleration potentiometer signal at rest. This alarm appears
when there is an interruption on the potentiometer positive (PPOT) or the
negative (NPOT). Check:
- Traction potentiometer (could be damaged)
- Traction potentiometer wiring.
85 WRONG BATTERY When the key is turned ON, the controller checks the battery voltage and
compares it with the “SET BATTERY” parameter setting. If the actual value
is 20% higher or lower than the nominal value, there is a fault. Replace the
battery with a correct one.
89 Not used.
7C Not used.
7A MASTER KO Failure on the Master module. Replace the Dual AC2 traction unit.
8E Not used.
8A Not used.
8C GAIN ACQUISITION This warning communicates that the logic is in phase of input acquisition.
In this phase the logic doesn't start.
31 WATCH - DOG It is a self-diagnostic test of logic lifting µcontroller . This alarm could also be
caused by the canbus malfunctioning or data transmission
interferences.Therefore, before replacing the AC2 lifting unit check the
correct canbus functioning and the general turck insulation.
32 EEPROM KO Fault in the area of memory in which the adjustment parameters are stored;
this alarm inhibits the truck operation, but the controller will use default
parameters. If the defect persists when the key is switched OFF and ON
again, replace the logic. If the alarm disappears, remember that the
parameters previously stored have been deleted and replaced by the default
values (see adjustin tables).
33 LOGIC FAILURE #3 Logic defect. Replace the lifting unit.
34 LOGIC FAILURE #2 Fault in the hardware section of the logic boardwhich manages the phase
voltage feedback. Check the 3 power cables connected to the liftilg motor.
If the fault is not caused by external reasons, replace the traction unit.
35 LOGIC FAILURE #1 This alarm signals that the interruption of protection against undervoltage /
overvoltage has been triggered. The possible reasons are:
a. Real battery undervoltage / overvoltage, or voltage loss after tht ignition
key or after the battery connector
b. Fault in the hardware section of the logic board which controls the
overvoltage protection. Logic defect. Replace the lifting unit.
c. The alarm appears also when one or more phases of the lifting motor
doesn't present a correct insulation. Check the motor insulation(with
deconnected battery): it must be higher than 1 Mohm. Otherwise check
the insulation of the power cables to the motor.
36 VMN LOW Failure in the VMN test. This test starts when the ignition key is turned ON.
The alarm appears if there is a creepage on one or more phases; check
the connections of the 3 power cables from the Lifting unit to the lifting
motor and the cables condition also. In order to point out if the fault is
produced by an internal or external cause connect the lifting motor.to one of
the traction logic units: Slave or Master. If the problem jumps on the traction
unit connected it means that the lifting motor is demaged, otherwise replace
the lifting unit.
1,2 - 2,0 t A.C. Electric
chapter 5000 SERVICE MANUAL 036-0410-07
page 60
37 VMN HIGH Failure in the VMN test. This test starts when the ignition key is turned on.
The alarm appears if one or more pover cables are not connected; check
the connections of the 3 power cables from the Lifting unit to the lifting
motor and the cables condition also. In order to point out if the fault is
produced by an internal or external cause connect the lifting motor.to one of
the traction logic units: Slave or Master. If the problem jumps on the traction
unit connected it means that the lifting motor is demaged, otherwise replace
the lifting unit.
38 CONTACTOR OPEN Failure on the contactor driver.
- Check main contactors coils and relevant wirings.
39 STBY I HIGH Failure on the current sensor.
- Replace the lifting unit.
40 CAPACITOR When the key is switch ON, the inverter tries to charge the capacitor
CHARGE through a power resistance, and check if the capitor are charged within a
timout. If they do not charge, an alarm is signalled;
the main contactor is not closed.
- Check the negative connection.
- Check voltage in the input of the key. Battery voltage must be present.
- Execute a short circuit between the key terminals.
- Replace the lifting unit.
Lifting
Vb D1 F1 PB1 S1 power
capacitor
41 HIGH Logic unit temperature is higher than 75°C. The maximum current is
TEMPERATURE reduced proportionally to the temperature increase. The logic unit stops at
100°C. If the alarm is signalled when the chopper is cold replace the lifting
unit.
42 MOTOR This warning is signalled if the sensor of the right motor is opened (digital
TEMPERATURE sensor). If it occurs when the motor is cold, check
- the sensor (it should be closed) and the relevant wiring loop.
- If everything is OK replace the logic unit.
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 5000
page 61
44 THERMIC SENS KO The values indicated by the temperature sensor of theinverter are always
checked and if they are out of range there is a warning.
- Replace the logic unit.
45 SAFETY This alarm appears if the connection between the pins 5 and 11 on the JFP
connector is open.
46 CAN BUS KO Comunication failure between the logic units: traction (Master & Slave),
lifting, Mhyrio and all the cards. The alarm appears if:
- CAN H and / or CAN L signals deconnected
- there is no comunication from one logic unit.
If the problem starts from one card the system recognizes in which one:
- CAN BUS KO 0A: I/O
- CAN BUS KO 00: arm card
- CAN BUS KO 03: Master
- CAN BUS KO 04: Slave
- CAN BUS KO : Lifting logic unit (no suffix after the alarm message)
- Before replacing any logic unit it is suggested a preliminary check of the
CAN BUS connections.
Using the console, through connection numbersand selecting the
TESTER function, try to carry out a link with all the junction knots
toward the different logic units. Verify the links by, at least, one of the
signals from the field, i.e. microswitches, potentiometers. Where you
don’t reach the link, there is a line interruption.
47 WAITING Time lag fault on the CAN BUS comunication. The Lifting logic unit detects
FOR NODE wich logic unit has generated the problem
#4 The Lifting logic unit receives the informations caming from the Slave
logic unitwith a time lag fault.
The fault can be caused by
- interference on the can bus. Check the CAN-BUS comunication.
- false contact. Check the connections of CAN H and CAN L wires.
- broken logic. Replace the traction logic unit.
#3 The Lifting logic unit receives the informations caming from the Master
logic unitwith a time lag fault.
The fault can be caused by
- interference on the can bus. Check the CAN-BUS comunication.
- false contact. Check the connections of CAN H and CAN L wires.
- broken logic. Replace the traction logic unit.
#9 The Lifting logic unit receives the informations caming from the
Mhyrio logic unit with a time lag fault.
The fault can be caused by
- interference on the CAN-BUS. Check the CAN-BUS comunication.
- false contact. Check the connections of CAN H and CAN L wires.
- broken logic. Replace the Mhyrio logic unit.
48 AUX OUTPUT KO Failure on the contactor driver.
- Replace the lifting unit.
49 DRIVER SHORTED Failure on the contactor driver.
Check the main contactors coils and relevant wirings.
If the failure is not due to external causes, replace the lifting logic unit.
50 CONTACTOR Failure on the contactor driver.
DRIVER - Replace the lifting unit.
51 COIL SHORTED Failure on the contactor driver. Check the main contactors coils and
relevant wirings. Control that there are no short-circuits in the wiring and
that the coil resistance value is correct. If the failure is not due to external
causes replace the logic unit.
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 5000
page 63
CODE ALARM DESCRIPTION
52 VACC NOT OK Failure on the lifting potentiometer signal at rest. The alarm points out
that the voltage value detected on the lifting potentiometer is 1Volt
higher than the least value programmed with the Vacc function. Check:
- The tlifting potentiometer (it could be damaged or not correctly
calibrated)
- The lifting potentiometer wiring.
- Carry out the Vacc setting again.
53 INCORRECT START Incorrect sequence from the start. Check:
- Control valve microswitcheis and relevant wires.
If the failure is not due to external causes replace the traction logic unit.
54 PEDAL WIRE KO Failure on the lifting potentiometer signal at rest. This alarm appears
when there is an interruption on the potentiometer positive (PPOT) or the
negative (NPOT). Check:
- lifting potentiometer (could be damaged)
- lifting potentiometer wiring.
55 WRONG BATTERY When the key is turned ON, the controller checks the battery voltage and
compares it with the “SET BATTERY” parameter setting. If the actual value
is 20% higher or lower than the nominal value, there is a fault. Replace the
battery with a correct one.
56 REMOTE INPUT Incorrect starting procedure.
57 WAITING The Lifting logic unit receives the informations caming from the
Mhyrio logic unit with a time lag fault.
The fault can be caused by
- interference on the CAN-BUS. Check the CAN-BUS comunication.
- false contact. Check the connections of CAN H and CAN L wires.
- broken logic. Replace the Mhyrio logic unit.
58 I= 0 EVER Failure on the current sensor. Replace the lifting unit.
59 Not used.
4A Not used
4C BATTERY_LOW Discharged battery. If the “battery check” option is ON, a battery discharge
algorithm is carried out. When the charge level is 10% , this alarm is
signalled and the current is reduced to the half of the programmed level.
5A CHOPPER The lifting unit has an erroneous configuration. Using the programming
NOT CONF. console it is possible to set the unitcorrectly according to the truck
configuration:
a. (joystick ON) control valve version
b. (joystick OFF) fingertip - joystick version.
4E Not used.
5C GAIN ACQUISITION This warning communicates that the logic is in phase of input acquisition. In
this phase the logic doesn't start.
5E Not used.
MHYRIO UNIT
A1 EEPROM KO Fault in the area of memory in which the adjustment parameters are stored;
this alarm inhibits the truck operation, but the controller will use default
parameters. If the defect persists when the key is switched OFF and ON
again, replace the logic. If the alarm disappears, remember that the
parameters previously stored have been deleted and replaced by
the default values.
A2 DRIVER SHORTED The transistor that controls the lifting and lowering valvespositive supply is
closed when it should be open. Replace the logic unit.
1,2 - 2,0 t A.C. Electric
chapter 5000 SERVICE MANUAL 036-0410-07
page 64
CODE ALARM DESCRIPTION
A3 CAN BUS KO Failure wires connecting the logic units: traction (Master & Slave), lifting,
Mhyrio and all the cards.
A4 FF VALVES Replace the logic unit.
A5 DRIVER OPEN The transistor that controls the lifting and lowering valvespositive supply is
open when it should be closed. Replace the logic unit.
A6 DRIVER EPV GR1 One or more MOS controlling the valves are inshort-circuit.
Replace the logic unit.
A7 DRIVER EPV GR2 One or more MOS controlling the valves are inshort-circuit.
Replace the logic unit.
A8 DRIVER EPV GR3 One or more MOS controlling the valves are inshort-circuit.
Replace the logic unit.
DASHBOARD
d1 the dashboard doesn't receive information from the traction Master unit.
d2 the dashboard doesn't receive information from lifting logic unit.
d4 the dashboard doesn't receive information from traction Slave unit
d8 the dashboard doesn't receive information from joystick card.
b1 the dashboard doesn't receive information from I/O card (Input output)
b2 the dashboard doesn't receive information from Mhyrio unit
b4 the dashboard doesn't receive information from lights card
d3 d1+d2
d5 d1+d4
d6 d2+d4
d7 d1+d2+d4
dA d2+d8
dB d1+d2+d8
dC d4+d8
dD d1+d4+d8
dE d2+d4+d8
dF d1+d2+d4+d8
b3 b1+b2
b5 b1+b4
b6 b2+b4
b7 b1+b2+b4
E1 Not used.
E2 BAD LIFT POT Failure on the lifting potentiometer in the fingertips / joysticks group.
Check, and if necessary replace the relevant fingertip / joystick.
E3 BAD TILT POT Failure on the tilting potentiometer in the fingertips / joysticks group.
Check, and if necessary replace the relevant fingertip / joystick
E4 BAD SIDESH. POT Failure on the sideshift potentiometer in the fingertips / joysticks group.
Check, and if necessary replace the relevant fingertip / joystick.
E5 BAD IV POT Failure on the 4th way potentiometer in the fingertips / joysticks group.
Check, and if necessary replace the relevant fingertip / joystick.
E6 BAD V POT Failure on the 5th way potentiometer in the fingertips / joysticks group.
Check, and if necessary replace the relevant fingertip / joystick.
E7 INCORRECT START Incorrect start sequence.
E8 BAD POTENTIOMETER
BF FW+BW Incorrect start sequence. Check, and if necessary replace the forward
pushbutton (PB3), the backward pushbutton (PB2) and the relevant
cables on the arm.
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 5000
page 65
C1 STOP-OPEN Failure on the stop lights. Check the bulbs of the stopstreetlights and the
relevant cables.
C2 Not used.
C3 Not used.
C4 RETRO-OPEN Failure on the backup lights. Check the bulbs of the backup streetlights and
the relevant cables.
C5 C1+C4 Failure on the stop and the backup lights. Check the relevant bulbs and the
cables of both light types.
C6 Not used.
C7 Not used.
C8 Not used.
ALARM COMBINATION
PROGRAMMEDLEVEL
PARAMETER
UNIT 0 1 2 3 4 5 6 7 8 9
RELEASE BRAKING (**) SEC 5.5 5.0 4.5 4.0 3.5 3.0 2.5 2.0 1.5 1.0
INVERS BRAKING (**) SEC 5.5 5.0 4.5 4.0 3.5 3.0 2.5 2.0 1.5 1.0
PEDAL BRAKING (**) SEC 5.5 5.0 4.5 4.0 3.5 3.0 2.5 2.0 1.5 1.0
SPEED LIMIT BRAKING (**) SEC 8.9 8.3 7.7 7.1 6.6 6.0 5.5 4.9 4.4 3.8
BRAKE CUTBACK (**) SEC 5.5 5.0 4.5 4.0 3.5 3.0 2.5 2.0 1.5 1.0
FREQUENCY CREEP HZ 0.3 0.6 0.9 1.2 1.5 1.8 2.1 2.4 2.7 3.0
ACC. SMOOTH
INV. SMOOTH
STOP SMOOTH HZ
(*) The acceleration time shown is the time from 0 Hz to 100 Hz. This is the ideal ramp calculated by the
software; the real ramp could change according to the motor parameters setting and, obviously, according
to the load.
(**) The braking feature is based upon deceleration ramps. The value shown in the table is the time to
decrease the speed from 100 Hz to 0 Hz. This is the ideal ramp calculated by the software; the real ramp
could change according to the motor parameters setting and, obviously, according to the load.
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 5000
page 67
PROGRAMMEDLEVEL
PARAMETER
UNIT 0 1 2 3 4 5 6 7 8 9
ACCELERATION DELAY (*) SEC 0.5 0.7 1.0 1.4 1.9 2.5 3.2 4.0 4.8 5.5
DELERATION DELAY (**) SEC 0.5 0.7 1.0 1.4 1.9 2.5 3.2 4.0 4.8 5.5
MIN SPEED UP HZ 12.0 13.5 15.0 16.5 18.0 19.5 21.0 22.5 24.0 25.5
AUXILIARY TIME SEC 0 0.2 0.4 0.8 1.0 1.5 2.0 3.0 4.0 5.0
(*) The acceleration time shown is the time from 0 Hz to 100 Hz (maximum selectable speed). This is the ideal
ramp calculated by the software; the real ramp could change according to the motor parameters setting and,
obviously, according to the load.
(**) The deceleration time shown in the table is the time from 100 Hz to 0 Hz. This is the ideal ramp calculated
by the software; the real ramp could change according to the motor parameters setting and, obviously,
according to the load.
(***) Adjustable with a 1Hz resolution in the 0 to 200 Hz range.
1,2 - 2,0 t A.C. Electric
chapter 5000 SERVICE MANUAL 036-0410-07
page 68
036-0410-07
SERVICE MANUAL chapter 5000
page 69
TRACTION
1,2 - 2,0 t A.C. Electric
chapter 5000 SERVICE MANUAL 036-0410-07
page 70
036-0410-07
SERVICE MANUAL chapter 5000
page 71
The console can be connected to the traction logic unit in two different ways:
1. Directly, by means of an interface cable in the concerned connector of the traction logic unit.
2. By connecting the console in another logic unit (pump or Mhyrio) and selecting the relevant connection
number as shown in the map here below.
AC2P2B D CE 1.06 In case the console is connected to the lifting logic unit
48V 350A 00000
* CONFIG. MENU *
SET MODEL
Press ENTER
Press SET and select the connection number of the traction logic unit
Press OUT
3 TRACTION MASTER
Press ENTER
to confirm
4 TRACTION SLAVE
5 PUMP
* CONFIG. MENU * 9 MHYRIO
SET MODEL
11 DASHBOARD
HEADING
MAIN MENU
RESTORE
PARAMETER
CODE
ALARMS
h, N°, C°
PROGRAM
VACC SETTING MIN/MAX
VACC
STEER
NOT AVAIBLE
TABLE
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 5000
page 73
MAIN MENU
MOTOR VOLTAGE %
FREQUENCY Hz
ENCODER Hz
SLIP VALUE Hz
CURRENT RMS A
TESTER TEMPERATURE °C SET BATTERY TYPE 48/72/80/96
SEAT SWITCH ON-OFF ADJUST BATTERY ....V
ADJUSTMENTS
FORW. SWITCH ON-OFF AUX OUTPUT VOLT ....V
BACK. SWITCH ON-OFF
ENABLE SWITCH ON-OFF
VOLTAGE BOOSTER %
BATTERY VOLTAGE V
SAVE
PARAMETER
RESTORE
PARAMETER
CODE
ALARMS
h, N°, C°
PROGRAM
VACC SETTING MIN/MAX
VACC
STEER
NOT AVAILABLE
TABLE
1,2 - 2,0 t A.C. Electric
chapter 5000 SERVICE MANUAL 036-0410-07
page 74
DA2M2B C CE 1.13
48V 280A 00000
Press ENTER
MAIN MENU
PARAM. CHANGE
Press ENTER
Scroll the parameters using ROLL and save the new values pressing OUT and after ENTER
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 5000
page 75
DA2M2B C CE 1.13
48V 280A 00000
Press ENTER
MAIN MENU
PARAM. CHANGE
Press ROLL
MAIN MENU
TESTER
Press ENTER
MOTOR VOLTAGE
FREQUENCY
ENCODER
SLIP VALUE
CURRENT RMS
TEMPERATURE
TEMPERATURE #1
TEMPERATURE #2
ACCELERATOR
STEER ANGLE
BRAKE PEDAL POTI
INTERNAL WHEEL CUTBACK Scroll the parameters using ROLL.
SEAT SWITCH
FORWARD SWITCH Press OUT to escape.
BACKWARD SWITCH
ENABLE SWITCH
BRAKE SWITCH
CUTBACK SWITCH
EXCLUSIVE HYDRO
HAND BRAKE
VOLTAGE BOOSTER
BATTERY VOLTAGE
BATTERY CHARGE
1,2 - 2,0 t A.C. Electric
chapter 5000 SERVICE MANUAL 036-0410-07
page 76
Press ENTER
MAIN MENU
PARAM. CHANGE
Press ROLL
MAIN MENU
TESTER
Press ROLL
MAIN MENU
SAVE PARAM
Press ENTER
Select the box (0-31) where you want to save the program:
SELECT Mod 00 = Program number
FREE/DA2M2B C = Program version stored
OVERWRITE DATA?
READING........
RUN ALL PARAMETERS YES=ENTER NO=OUT
MAIN MENU
SAVE PARAM
Press ENTER Press OUT
to confirm to escape
MAIN MENU
SAVE PARAM
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 5000
page 77
MAIN MENU : RESTORE PARAMETER (MASTER connection number 3)
DA2M2B C CE 1.13
48V 280A 00000
Press ENTER
MAIN MENU
PARAM. CHANGE
Press ROLL
MAIN MENU
TESTER
Press ROLL
MAIN MENU
SAVE PARAM
Press ROLL
MAIN MENU
RESTORE PARAM
Press ENTER
OVERWRITE DATA?
YES=ENTER NO=OUT
MAIN MENU
RESTORE PARAM
1,2 - 2,0 t A.C. Electric
chapter 5000 SERVICE MANUAL 036-0410-07
page 78
DA2M2B C CE 1.13
48V 280A 00000
Press ENTER
MAIN. MENU
PARAM. CHANGE
MAIN. MENU
ALARM
Press ENTER
CLEAR LOGBOOK
YES=ENTER NO=OUT
LOGBOOK CLEARED
(PRESS OUT)
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 5000
page 79
DA2M2B C CE 1.13
48V 280A 00000
Press ENTER
MAIN MENU
PARAM. CHANGE
MAIN MENU
PROGRAM VACC
Press ENTER
Press ENTER
VACC SETTING
0.6 1.6
DA2M2B C CE 1.13
48V 280A 00000
* CONFIG. MENU *
SET MODEL
Press ROLL
* CONFIG. MENU *
SET OPTIONS
Press ROLL
* CONFIG. MENU *
ADJUSTMENTS
Press ENTER
SET POT BRK MIN ....V Scroll the parameters using ROLL
SET POT BRK MAX ....V
SET BATTERY TYPE 48/72/80/96 1. Select MAX STEER RIGHT (pressing ENTER
ADJUST BATTERY ....V to delete the old parameter) with the wheels turned
completely right and store the parameter pressing
MAX STEER RIGHT ....V OUT and then ENTER to confirm. (This value
MAX STEER LEFT ....V corresponds to the min. voltage)
SET STEER 0-POS 2.5V
2. Select MAX STEER LEFT (pressing ENTER to
SET STEER RIGHT ....° delete the old parameter) with the wheels turned
SET STEER LEFT ....° completely left and store the parameter pressing
THROTTLE 0 ZONE ....% OUT and then ENTER to confirm. (This value
THROTTLE X ZONE ....% corresponds to the max. voltage)
THROTTLE Y ZONE ....%
ADJUSTMENT #02 1-9 3. Select SET STEER 0-POS (pressing ENTER to
ADJUSTMENT #01 1-9 delete the old parameter) with straight wheels and
MAIN CONT VOLT ....V store the parameter pressing OUT and then ENTER
AUX OUTPUT VOLT ....V to confirm the new value.
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 5000
page 81
STEER TABLE (MASTER connection number 3)
Select the type of truck according to the 3 wheels or 4 wheels configuration.
DA2M2B C CE 1.13
48V 280A 00000
* CONFIG. MENU *
SET MODEL
Press ROLL
* CONFIG. MENU *
SET OPTIONS
Press ENTER
OPTION #3
Select OPTION #1 for the 3 wheels and store the parameter pressing OUT and then ENTER to
confirm.
Select OPTION #2 for the 4 wheels and store the parameter pressing OUT and then ENTER to
confirm.
Select OPTION #3 for the cenTAURO 160-200 L AC/C4E 160-200 NL AC and store the parameter
pressing OUT and then ENTER to confirm.
1,2 - 2,0 t A.C. Electric
chapter 5000 SERVICE MANUAL 036-0410-07
page 82
DA2M2B C CE 1.13
48V 280A 00000
* CONFIG. MENU *
SET MODEL
Press ROLL
* CONFIG. MENU *
SET OPTIONS
Press ENTER
Select STOP ON RAMP and change the status using PARAM or SET
ON ACTIVATED
OFF DEACTIVATED
and store the parameter pressing OUT and then ENTER to confirm.
After releasing the pedals the truck can stay still on a ramp for about 1 second.
This parameter activates/deactivates this function.
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 5000
page 83
SLIP CONTROL (MASTER connection number 3)
This function is useful to understand if a traction problem is due to the encoder or not.
In case the truck stops or works with low speed with high consumption of current (and relevant alarm code shown
on the dashboard) it is possible to disable the encoder for some seconds, no longer, given that the logic unit cannot
control the motor any longer.
DA2M2B C CE 1.13
48V 280A 00000
Press ENTER
MAIN MENU
PARAM. CHANGE
Press ROLL
until reaching ALARM menu
MAIN MENU
ALARM
With the SLIP CONTROL OFF push the
Press ENTER accelerator pedal slowly otherwise the motor
stands still.
DESCRIPTION OF THE
ALARM CODE
* MENU *
SPECIAL ADJUST
Press ROLL
* MENU *
HARDWARE SETTING
Press ENTER
BATTERY INDICATOR
The control of the battery LED indication on the dashboard and the relevant reduction of the speed are
managed by the traction logic unit.
The dashboard reads only the information coming from the logic unit and shows, using the led battery indicator,
the status of the battery.
In order to have a precise reading of the logic unit it is necessary to set the parameter ADJUST
BATTERY everytime the traction logic unit is replaced or you received a new truck without battery.
In order to have a pricise measure of the battery voltage you have to set the parameter ADJUST BATTERY
with the same value read directly on the battery by a multimeter.
Note that the logic uses as refernce voltage the key input which is not at the same potential of the positive pole
of the battery due to the fact that between them different devices are locatet (connectors, the fuse F1 the push
button PB1).
M S Z M
F1 PB1 S1
Once taken the measure of the voltage set the parameter adjust battery following the instruction
explained in the BATTERY SETTING MAP.
ADVICE
Set the multimeter in volt and join the two terminal togheter. On the display you have to read zero.
If you read other value that it in consideration during the measure of the battery voltage.
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 5000
page 85
V
ADJUSTMENT
DISCHARGE CURVE
ADJUSTMENT
>
t
DA2M2B C CE 1.13
48V 280A 00000 Scroll the parameters using ROLL and
save the new values pressing OUT and
then ENTER
Press ROLL and
PARAM together
HOUR COUNTER RUNNING/ KEY ON
* CONFIG. MENU *
SET MODEL
BATTERY CHECK ON
Press OUT
Press ENTER
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 5000
page 87
ADJUSTMENT #01
CONSOLE VALUE VOLT RESETTING
indicatore della batteria
0 49.20 49.10
1 49.48 49.39
2 49.73 49.58
3 50.02 49.87
4 50.26 50.11
5 50.54 50.35
6 50.83 50.64
7 51.02 50.83
8 51.26 51.27
9 51.80 51.55
ADJUSTMENT #02
By means of the config menu of the programming console, the user can configure the following
functions.
SUBMENU “ADJUSTMENT”
DA2S2B C CE 1.13
48V 280A 00000
Press ENTER
MAIN MENU
PARAM. CHANGE
Press ENTER
NOT AVAILABLE
036-0410-07
SERVICE MANUAL chapter 5000
page 89
DA2S2B C CE 1.13
48V 280A 00000
Press ENTER
MAIN MENU
PARAM. CHANGE
Press ROLL
MAIN MENU
TESTER
Press ENTER
MOTOR VOLTAGE
FREQUENCY Scroll the parameters using ROLL.
ENCODER
SLIP VALUE Press OUT to escape
CURRENT RMS
TEMPERATURE
SEAT SWITCH
FORWARD SWITCH
BACKWARD SWITCH
ENABLE SWITCH
VOLTAGE BOOSTER
BATTERY VOLTAGE
1,2 - 2,0 t A.C. Electric
chapter 5000 SERVICE MANUAL 036-0410-07
page 90
Press ENTER
MAIN MENU
PARAM. CHANGE
Press ROLL
MAIN MENU
TESTER
Press ROLL
MAIN MENU
SAVE PARAM
Press ENTER
MAIN MENU
SAVE PARAM
MAIN MENU
SAVE PARAM
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 5000
page 91
DA2S2B C CE 1.13
48V 280A 00000
Press ENTER
MAIN MENU
PARAM. CHANGE
Press ROLL
MAIN MENU
TESTER
Press ROLL
MAIN MENU
SAVE PARAM
Press ROLL
MAIN MENU
RESTORE PARAM
Press ENTER
OVERWRITE DATA?
YES=ENTER NO=OUT
MAIN MENU
RESTORE PARAM
1,2 - 2,0 t A.C. Electric
chapter 5000 SERVICE MANUAL 036-0410-07
page 92
DA2S2B C CE 1.13
48V 280A 00000
Press ENTER
MAIN. MENU
PARAM. CHANGE
MAIN. MENU
ALARM
Press ENTER
CLEAR LOGBOOK
YES=ENTER NO=OUT
LOGBOOK CLEARED
(PRESS OUT)
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 5000
page 93
DA2M2B C CE 1.13
48V 280A 00000
* CONFIG MENU *
SET MODEL
Press ENTER
CONNECTED TO 3
Press ROLL
Press OUT
036-0410-07
SERVICE MANUAL chapter 5000
page 95
LIFTING
1,2 - 2,0 t A.C. Electric
chapter 5000 SERVICE MANUAL 036-0410-07
page 96
036-0410-07
SERVICE MANUAL chapter 5000
page 97
The console can be connected to the lifting logic unit in two different ways:
DA2M2B C CE 1.13 In case the console is connected to the traction logic unit
48V 280A 00000
* CONFIG. MENU *
SET MODEL
Press ENTER
Press SET and select the connection number of the lifting logic unit
Press OUT
CONNECTION NUMBERS
ARE YOU SURE?
YES=ENTER NO=OUT 3 TRACTION MASTER
4 TRACTION SLAVE
Press ENTER 5 PUMP
to confirm 9 MHYRIO
11 DASHBOARD
* CONFIG MENU *
SET MODEL
AC2P2B D CE 1.06
48V 350A 00000 Connected to the lifting logic unit
1,2 - 2,0 t A.C. Electric
chapter 5000 SERVICE MANUAL 036-0410-07
page 98
DESCRIPTION OF THE CONSOLE STANDARD MENU
AC2 LIFTING UNIT MENU
HEADING
MAIN MENU
SAVE
PARAMETER
RESTORE
PARAMETER
CODE
ALARMS
h, N°, C°
PROGRAM
VACC SETTING MIN/MAX
VACC
STEER
NOT AVAILABLE
TABLE
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 5000
page 99
AC2P2B D CE 1.06
48V 350A 00000
Press ENTER
MAIN MENU
PARAM. CHANGE
Press ENTER
Scroll the parameters using ROLL and save the new values pressing OUT and then ENTER
1,2 - 2,0 t A.C. Electric
chapter 5000 SERVICE MANUAL 036-0410-07
page 100
AC2P2B D CE 1.06
48V 350A 00000
Press ENTER
MAIN MENU
PARAM. CHANGE
Press ROLL
MAIN MENU
TESTER
Press ENTER
MOTOR VOLTAGE
FREQUENCY
ENCODER
SLIP VALUE
CURRENT RMS
TEMPERATURE
MOTOR TEMPERATURE
SEAT SWITCH
ACCELERATOR
LIFTING SWITCH Scroll the parameters using ROLL.
1 ST SPEED SWITCH
2 ND SPEED SWITCH Press OUT to escape.
3 RD SPEED SWITCH
4 TH SPEED SWITCH
HYDRO SPEED REQ.
CUTBACK SWITCH
CUTBACK SWITCH 1
VOLTAGE BOOSTER
BATTERY VOLTAGE
COS FI
BATTERY CURRENT
BATTERY CHARGE
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 5000
page 101
MAIN MENU : SAVE PARAMETER (PUMP connection number 5)
AC2P2B D CE 1.06
48V 350A 00000
Press ENTER
MAIN MENU
PARAM. CHANGE
Press ROLL
MAIN MENU
TESTER
Press ROLL
MAIN MENU
SAVE PARAM
Press ENTER
Select the box (0-31) where you want to save the program:
SELECT Mod 00 = Program number
FREE/AC2P2B D = Program version stored
MAIN MENU
SAVE PARAM
MAIN MENU
SAVE PARAM
1,2 - 2,0 t A.C. Electric
chapter 5000 SERVICE MANUAL 036-0410-07
page 102
Press ENTER
MAIN MENU
PARAM. CHANGE
Press ROLL
MAIN MENU
TESTER
Press ROLL
MAIN MENU
SAVE PARAM
Press ROLL
MAIN MENU
RESTORE PARAM
Press ENTER
OVERWRITE DATA?
YES=ENTER NO=OUT
MAIN MENU
RESTORE PARAM
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 5000
page 103
AC2P2B D CE 1.06
48V 350A 00000
Press ENTER
MAIN. MENU
PARAM. CHANGE
MAIN. MENU
ALARM
Press ENTER
CLEAR LOGBOOK
YES=ENTER NO=OUT
LOGBOOK CLEARED
(PRESS OUT)
1,2 - 2,0 t A.C. Electric
chapter 5000 SERVICE MANUAL 036-0410-07
page 104
AC2P2B D CE 1.06
48V 350A 00000
Press ENTER
MAIN MENU
PARAM. CHANGE
MAIN MENU
PROGRAM VACC
Press ENTER
VACC SETTING
These are the old parameters stored
0.2 4.8
Press ENTER
VACC SETTING
0.2 4.8
036-0410-07
SERVICE MANUAL chapter 5000
page 105
SLIP CONTROL (PUMP connection number 5)
This functions is useful to understand if a lifting problem is due to the encoder or not.
In case the truck stops or works with low speed with high consumption of current (and relevant alarm code
displayed on the dashboard) it is possible to disable the encoder for some seconds, no longer, given that the logic
unit cannot control the motor any longer.
AC2P2B D CE 1.06
48V 350A 00000
Press ENTER
MAIN MENU
PARAM. CHANGE
Press ROLL
until reaching ALARM menu
MAIN MENU
ALARM
With the SLIP CONTROL OFF pull the lever of
the potentiometer slowly otherwise the motor
Press ENTER stands still.
DESCRIPTION OF THE
ALARM CODE
* MENU *
SPECIAL ADJUST
Press ROLL
* MENU *
HARDWAR E SETTING
Press ENTER
Press ENTER
* CONFIG. MENU *
SET OPTIONS
036-0410-07
SERVICE MANUAL chapter 5000
page 107
AC2P2B D CE 1.06
48V 350A 00000
* CONFIG. MENU *
SET MODEL
Press ENTER
CONNECTED TO 5
Press ROLL
Press OUT
036-0410-07
SERVICE MANUAL chapter 5000
page 109
MHIRIO
1,2 - 2,0 t A.C. Electric
chapter 5000 SERVICE MANUAL 036-0410-07
page 110
036-0410-07
SERVICE MANUAL chapter 5000
page 111
The console can be connected to the MHYRIO logic unit in two different ways:
DA2M2B C CE 1.13 In case the console is connected to the traction logic unit
48V 280A 00000
* CONFIG. MENU *
SET MODEL
Press ENTER
Press SET and select the connection number of the Mhyrio logic unit
Press OUT
CONNECTION NUMBERS
ARE YOU SURE?
YES=ENTER NO=OUT 3 TRACTION MASTER
4 TRACTION SLAVE
Press ENTER to 5 PUMP
confirm 9 MHYRIO
* CONFIG. MENU *
11 DASHBOARD
SET MODEL
HEADING
MAIN MENU
SAVE
PARAMETER
RESTORE
PARAMETER
CODE
ALARMS
h, N°, C°
PROGRAM
VACC SETTING MIN/MAX
VACC
STEER
NOT AVAILABLE
TABLE
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 5000
page 113
MHY CB ZP 0.11
48V 0A 00000
Press ENTER
MAIN MENU
PARAM. CHANGE
Press ENTER
Scroll the parameters using ROLL and save the new values pressing OUT and then ENTER
1,2 - 2,0 t A.C. Electric
chapter 5000 SERVICE MANUAL 036-0410-07
page 114
MHY CB ZP 0.11
48V 0A 00000
Press ENTER
MAIN MENU
PARAM. CHANGE
Press ROLL
MAIN MENU
TESTER
Press ENTER
BATTERY VOLTAGE V
VALVES SUPPLY V
CAN POT EVP %
CAN POT GROUP 1 %
CAN POT GROUP 2 % Scroll the parameters using ROLL.
CAN POT GROUP 3 %
CAN POT GROUP 4 % Press OUT to escape.
INPUT 0 ON/OFF
INPUT 1 ON/OFF
INPUT 2 ON/OFF
ANALOG INPUT 1 0/256
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 5000
page 115
MHY CB ZP 0.11
48V 0A 00000
Press ENTER
MAIN MENU
PARAM. CHANGE
Press ROLL
MAIN MENU
TESTER
Press ROLL
MAIN MENU
SAVE PARAM
Press ENTER
Select the box (0-31) where you want to save the program:
SELECT Mod 00 = Program number
FREE/MHY CB = Program version stored
MAIN MENU
SAVE PARAM
MAIN MENU
SAVE PARAM
1,2 - 2,0 t A.C. Electric
chapter 5000 SERVICE MANUAL 036-0410-07
page 116
MHY CB ZP 0.11
48V 0A 00000
Press ENTER
MAIN MENU
PARAM. CHANGE
Press ROLL
MAIN MENU
TESTER
Press ROLL
MAIN MENU
SAVE PARAM
Press ROLL
MAIN MENU
RESTORE PARAM
Press ENTER
MAIN MENU
RESTORE PARAM
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 5000
page 117
MHY CB ZP 0.11
48V 0A 00000
Press ENTER
MAIN. MENU
PARAM. CHANGE
MAIN. MENU
ALARM
Press ENTER
CLEAR LOGBOOK
YES=ENTER NO=OUT
LOGBOOK CLEARED
(PRESS OUT)
1,2 - 2,0 t A.C. Electric
chapter 5000 SERVICE MANUAL 036-0410-07
page 118
Not available
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 5000
page 119
DASHBOARD
1,2 - 2,0 t A.C. Electric
chapter 5000 SERVICE MANUAL 036-0410-07
page 120
036-0410-07
SERVICE MANUAL chapter 5000
page 121
The console can be connected to the dashboard unit in the following way:
By connecting the console to another logic unit (traction, lifting or mhyrio) and selecting the relevant connection
number as shown in the map here below.
DA2M2B C CE 1.13 In case the console is connected to the traction logic unit
48V 280A 00000
* CONFIG. MENU *
SET MODEL
Press ENTER
Press SET and select the connection number of the lifting logic unit
Press OUT
CONNECTION NUMBERS
ARE YOU SURE?
YES=ENTER NO=OUT 3 TRACTION MASTER
4 TRACTION SLAVE
Press ENTER 5 PUMP
to confirm 9 MHYRIO
11 DASHBOARD
* CONFIG MENU *
SET MODEL
DASH CE V 1.00
24 0A 00000
Connected to the dashboard unit
1,2 - 2,0 t A.C. Electric
chapter 5000 SERVICE MANUAL 036-0410-07
page 122
DASH CE V 1.00
24 0A 00000
Press ENTER
MAIN MENU
PARAM. CHANGE
Press ENTER
HOURS COUNTER RUNNING/KEY: key on / lifting unit working hours counter switch
DISPLAY ON/OFF: displaied speed switch
SPEED RATIO 0-5 12: speed calculation ratio
Scroll the parameters using ROLL, store the new parameters pressing OUT and then ENTER.
If the parameter HOURS COUNTER is switched in KEY ON option the hourglass will start to blink
whenever the ignition key will be tourned on (=key workhours count).
If the parameter DISPLAY SPEED is switched ON on the display used to point off the alarm codes, will
appear two zeros (=truck speed displayed).
In case of folt the speed indication disappears and the alarm code appears.
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 5000
page 123
WIRING DIAGRAMS
1,2 - 2,0 t A.C. Electric
chapter 5000 SERVICE MANUAL 036-0410-07
page 124
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 5000
page 125
1,2 - 2,0 t A.C. Electric
chapter 5000 SERVICE MANUAL 036-0410-07
page 126
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 5000
page 127
1,2 - 2,0 t A.C. Electric
chapter 5000 SERVICE MANUAL 036-0410-07
page 128
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 5000
page 129
1,2 - 2,0 t A.C. Electric
chapter 5000 SERVICE MANUAL 036-0410-07
page 130
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 5000
page 131
1,2 - 2,0 t A.C. Electric
chapter 5000 SERVICE MANUAL 036-0410-07
page 132
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 6000
page 1
CHAPTER 6000
036-0410-07
SERVICE MANUAL chapter 6000
page 3
HYDRAULIC DIAGRAM
Control valve version
STEERIG AXLE
ORBITROL
SIDESHIFT
TILTING
LIFTING
1,2 - 2,0 t A.C. Electric
chapter 6000 SERVICE MANUAL 036-0410-07
page 4
Control valve
Manometer connection
Priority valve
Drain hose
Hydraulic oil filter
0,5 Bar
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 6000
page 5
4th way
CONTROL VALVE
Tilting Lifting
4th way Sideshift
036-0410-07
SERVICE MANUAL chapter 6000
page 7
LIFTING PERFORMANCE
Here below the table with the performance of a STD machine.
Q1 = It corresponds to the maximum load of the machine at 3mt. (See capacity plate).
Q2 = It corresponds to the maximum load of the machine at maximum load.
FFL = Full free loft mast
TV = Total visibility mast
m/sec = Lifting speed: min 0.30 m/sec = it means 3.3 sec to cover 1 meter.
max 0.50 m/sec = it means 2 sec to cover 1 meter.
max 0.60 m/sec = it means 1.7 sec to cover 1 meter
Amp = Consuption of Ampere
P = Pressure
LIFTING
*
* = Max pressure to max high
For fingertips / mini joysticks version the maximum pressure valve is set to 240 Bar
1,2 - 2,0 t A.C. Electric
chapter 6000 SERVICE MANUAL 036-0410-07
page 8
Q1 = It corresponds to the maximum load of the machine at 3mt. (See capacity plate).
bw = Backward
fw = Forward
036-0410-07
SERVICE MANUAL chapter 6000
page 9
HYDRAULIC DIAGRAM
STEERIG AXLE
Joysticks / fingertips version
ORBITROL
4th WAY
SIDESHIFT
TILTING
LIFTING
1,2 - 2,0 t A.C. Electric
chapter 6000 SERVICE MANUAL 036-0410-07
page 10
Electric
Control valve
Manometer connection
Priority valve
Drain hose
Hydraulic oil filter
036-0410-07
SERVICE MANUAL chapter 6000
page 11
Proportional valve
4th way
Sideshift
Lifting
Tilting
Drain line
Plug
6
5
4
3 9
The solenoid valve EVP has been integrated in the circuit given that there is only one motor for both functions,
lifting and power steering. It allows the oil in excess to return into the tank, thus reducing the pressure in the
hydraulic control valve circuit.
By means of this valve it is possible to increase or decrease the sensitivity of the lifting by acting on control of
the valve (SEE MHYRIO setting funtion).
Lifting box uses a solenoid valve EV2 ON/OFF for the lifting, a proportional solenoid valve for
the drain EVP1 and a valve for the maximum pressure.
Tilting box has a governor of oil capacity (12 l/m’). In this way the oil quantity is reduced when using
the double function: lifting-tilt. In this box there is also an OVER CENTER valve to avoid
any forward movement of the mast with load on the forks and the emptying of the tilt
cylinders in case of min. rpm of the motor.
Sideshift box has a governor of oil capacity (12 l/m’). In this way the oil quantity is reduced when using
the double function: lifting-sideshift. For safety reason the logic unit is set to the lower
speed.
4th WAY has two valves already set to 150 Bar. Shims are used in order to increase or decrease the
pressure. Each shim corresponds to 17 bar.
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 6000
page 13
POWER STEERING HYDRAULIC DIAGRAM
STEERING CYLINDER
ORBITROL
PRIORITY
VALVE
PUMP FILTER
1,2 - 2,0 t A.C. Electric
chapter 6000 SERVICE MANUAL 036-0410-07
page 14
C
A The hydraulic oil tank is located under the
platform.
The filter cartridge (A) is beneath the screw
D cap (C).
C
D
036-0410-07
SERVICE MANUAL chapter 6000
page 15
B
A
PUMP REPLACEMENT
Before fitting the new pump to the motor pay attention to the gasket right
positioning.
1,2 - 2,0 t A.C. Electric
chapter 6000 SERVICE MANUAL 036-0410-07
page 16
clean carefully the motor coupling surface
After the pump replacement it is suggested to fill the suction hose C (see previous page). It is also
possible to use the manometer connection point D (see previous page) to fill the main hose C with oil in order
to avoid that the pump turns without oil during the first working period. Once ending the assembling operation
switchthe truck on and wait for the lifting motor automatic stop.
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 7000
page 1
CHAPTER 7000
MAST GROUP
1,2 - 2,0 t A.C. Electric
chapter 7000 SERVICE MANUAL 036-0410-07
page 2
036-0410-07
SERVICE MANUAL chapter 7000
page 3
MAST GROUPS
The mast profile with double stiffening flange is characterised by a high flexural and torsional strength.
It allows wide visibility thanks to the reduced dimensions of the profile itself.
Cylinders are single-acting type.
The sideshift system has been housed inside the profiles.
The mast group is a roller type with a variable centre distance (i.e. a fixed roller is fitted on the outer mast and a
mobile one on the inner mast, instead of a number of mobile rollers only on the inner mast). This solution ensures
better grip and stability on operation.
Other features: side plays adjustable from outside. Plastic guide shoes. Roller bearings with grease nipples, ball
joints on axle couplings and tilt cylinders.
Fork carriage
Internal
section bar
Intermediate
section bar
External
section bar
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 7000
page 5
LIFTING CYLINDERS ON THE MAST
1,2 - 2,0 t A.C. Electric
chapter 7000 SERVICE MANUAL 036-0410-07
page 6
Surface C
Oil inlet
>
Unidirectional
valves D-E
Safety valve
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 7000
page 7
Surface D
Hole F
Profile E
Safety valve
Unidirectional
valve C
>
Oil inlet
1,2 - 2,0 t A.C. Electric
chapter 7000 SERVICE MANUAL 036-0410-07
page 8
Safety valve
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 7000
page 9
Piston (2)
Seal (1)
Chamber
1ST CHECK
Remove the drain pipe from the cylinder (fig. C)
Lift the cylinder some times to end stroke, so as to discharge any oil
residual.
After 10 minutes, measure the amount by which the load has lowered.
A drop of a few millimetres is quite normal, as in the distributor there
are always some leakages.
Now, lift the cylinder to its end stroke, if no oil leaks from the drain
pipe coupling, it means that the load lowering is only due to the leakages
on the distributor.
Fig. C
2nd CHECK
(To be carried out if the 1st inspection has been successful and after
seal replacement).
Lift the cylinder some times to end stroke, so that all the possible
remaining oil is discharged.
Put a load on the forks. Lift and lower it for 10 minutes, making sure
that the limit stop is never reached.
036-0410-07
SERVICE MANUAL chapter 7000
page 11
MASTS
D
After the first 50 hours
- adjust the guide shoes through socket head (Allen) screw (D)
E For this purpose use a 0.2-0.5 mm thickness gauge, inserting it
from below upwards to the centre of the Allen screw (D) passing
behind the roller (F) and sliding on the outer mast..
P Sideshift unit
- the lifting chain stay bolts are free of defects and the adjusting
nuts are locked by the appropriate cotter pins (A);
E - the fork carriage safety end stops (G) are present and tightly
E
fixed.
Locking torques:
- collar self-locking nuts 0.8-1.2 daNm
036-0410-07
SERVICE MANUAL chapter 7000
page 13
4) remove the safety clip of the chain pin on the carriage (Picture 3)
5) remove the nut stopping the chain pin with a tool as shown in
Picture 2 Picture 4. After that move the two chains to the opposite side in
order to have more space.
8) remove the guide shoes with two screw drivers (Picture 6) and
screw out the Allen screw G (see page 12) in the opposite
Picture 3 side, in order to let the new guide shoes go inside completely.
9) remove the snap ring A and take out the guide roller (Picture 7)
10) reassemble all parts in reverse order and adjust the guide shoes.
Picture 4
A
Picture 5 Picture 6 Picture 7
1,2 - 2,0 t A.C. Electric
chapter 7000 SERVICE MANUAL 036-0410-07
page 14
5) reassemble all parts in reverse order and adjust the guide shoes.
E
Picture
Picture 7
9
Picture 10
B C
D
E
A
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 7000
page 15
Replacing the chains use original spare parts which will guarantee that the safety
requirements stated by the regulations in force are complied with.
The tilt angle can easily be checked using a plumb-line dropped from
the front outside edge of the top of the fixed masts and measuring the
distance between the line and the front edge at a metre from the top of
the masts.
1° = 17,4 mm
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter 8000
page 1
CHAPTER 8000
ATTACHEMENT
1,2 - 2,0 t A.C. Electric
chapter 8000 SERVICE MANUAL 036-0410-07
page 2
036-0410-07
SERVICE MANUAL chapter 9000
page 1
CHAPTER 9000
OPTIONS
1,2 - 2,0 t A.C. Electric
chapter 9000 SERVICE MANUAL 036-0410-07
page 2
036-0410-07
SERVICE MANUAL chapter B
page 1
CHAPTER B
MAINTENANCE TABLES
1,2 - 2,0 t A.C. Electric
chapter B SERVICE MANUAL 036-0410-07
page 2
036-0410-07
SERVICE MANUAL chapter B
page 3
OIL AND GREASE SPECIFICATIONS
STANDARD TYRES
TIGHTENING TORQUES
WHEEL TORQUE
14 daNm steering wheels
14 daNm driving wheels
DRIVE UNIT TORQUE
2,3 daNm electric motor securing
13,5 daNm unit securing to frame
5 daNm service brake delivery pipes screw
5 daNm parking brake cable fixing screw
2,2 daNm oil filling and draining cap
VARIOUS TORQUES
4,9 daNm mast-securing U-bolts
0,8÷1,2 daNm jack collar self-locking nuts
20 daNm counterweight locking screws
1,2 - 2,0 t A.C. Electric
chapter B SERVICE MANUAL 036-0410-07
page 4
LEGEND
'
and cleaning of the parts indicated; replacement
/ lubrification / clamping according to necessity.
&
In the maintenance table showing the
replacement of the parts indicated.
"
In the maintenance table showing lubrification
of the parts indicated.
,
In the maintenance table showing tightening
or adjustment of the parts indicated.
The servicing periods are divided into hours, considering an average working day of 8 hours
of effective operation.
If the truck is used on average for less than 8 hours per day, refer to the schedules expressed
in days/months
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter B
page 5
8 50 250 500 1000 2000 5000 10000 after # hours FOR MEDIUM/INTENSE USE
1/- 7/- -/1 -/3 -/6 -/12 -/24 -/60 after # days/months FOR OCCASIONAL USE
LIFTING EQUIPMENT - MASTS
- - - - ', - - - carriage - sideshift unit
- - - - '" - - - forks positioning pins
- - - ' - - - - mast guide pads
- - - - ' - - - mast, carriage and chain rollers
- - - - - - & - tilting jacks supply pipes
- - - - - & - - lifting oil filter
- - - ' - & - - lifting system oil
- - - - ' - - - mast guides, mast and jack fixing
- - - , - - - - lifting jack retaining collars
- - - ' - - - - fork carriage position
- - - - ' - - - forks
- - - ' - - - - mast inclination
- - - , " - - - mast fixing to the frame
- - - - '" - - & lifting chains
- - - - '" - - & chain stay bolts
- - - - - - - & high pressure hydraulic pipe system
- - - - ' - - - hydraulic seals and connection
- - - , - - - - tilting jacks nuts
DRIVE UNIT(S)
- - - - ' - - - system seal
- - - ' - & - - transmission reduction gear oil - differential gear oil
- - - - , - - - transmission complete unit
1,2 - 2,0 t A.C. Electric
chapter B SERVICE MANUAL 036-0410-07
page 6
8 50 250 500 1000 2000 5000 10000 after # hours FOR MEDIUM/INTENSE USE
1/- 7/- -/1 -/3 -/6 -/12 -/24 -/60 after # days/months FOR OCCASIONAL USE
ELECTRICAL SYSTEM
- - - - ' - - - electronic control
- - - ' - - - - contactors, pushbuttons, pedals and control valves
microswitches
- - - ' - - - - safety control circuit
- - - - ' - - - lead terminals - lead insulation
- ' - - - - - - BATTERY - specific gravity and charge level
- - - ' - - - - ELECTRIC MOTORS - external cleaning
- - - ' - - - - electric fans
- - - - ' - - & motor bearings
- - - - ', - - - motor supports
CHASSIS AND CONTROLS
- - - - ' - - & steering and pipe systems seal
- - - - ' - & - hoses from orbitrol to steering jack
- - - - ' - - - steering axle and wheel hub bearing
- - - - ' - - - steering lock pedals in general - linkage
- - - - ' - - - parking brake pedal or lever
- - - - ' - - - service brake pedal
- - - - ' - & - service brake hoses
- - - - ' & - - brake fluid
- - - - - ' - - brake fluid low level warning light
- - - - ' - - - chassis cleaning - bolts in general
- - - ' - - - - driver’s seat
- - - - ' - - - wheel tyres
- ' - - - - - - tyre pressure and completeness - wheels tightness
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter C
page 1
CHAPTER C
SAFETY INFORMATION
1,2 - 2,0 t A.C. Electric
chapter C SERVICE MANUAL 036-0410-07
page 2
WELDING page 5
036-0410-07
SERVICE MANUAL chapter C
page 3
SAFETY INFORMATION
Work clothes
1 protective gloves
2 overalls
3 safety boots
4 protective goggles
Work place
To carry out correctly all the lifting operation of the truck it is necessary to have the following tools:
ELECTRIC PART
It is obligatory to disconnect the battery before doing any job to avoid the risk of accident.
- Do not connect the chopper to a battery with a nominal voltage different from the voltage stated on the unit plate.
If the battery voltage is higher, it may cause the MOS failure.
If the battery voltage is lower, the unit does not run.
- During the battery recharging no units must be connected to the battery as the unit can be
damaged by the overvoltage generated by the battery charger.
- Supply the unit only with the traction battery, do not use any output rectifiers or power supplies.
- With the key switched off, the filter capacitors could remain charged for some minutes. To ensure safe working
conditions, we advise:
. To wait some seconds with the machine stopped and the key inserted until the display turns
completely off to disconnect the battery.
Or
. To short-circuit the capacitors through a resistor (56 Ohm 1W) between the B+ and B- chopper
power connections.
Do not wear jewellery, necklaces, watches, etc because they can be causes of short circuit.
In order to fill in the battery or control the level of the acid it is necessary to wear gloves and glasses.
It is prohibited to smoke.
Electric 1,2 - 2,0 t A.C.
036-0410-07
SERVICE MANUAL chapter C
page 5
Welding
It is obligatory to wear gloves and protective goggles during the grinding operations because they could cause
the projection of metallic particles.
Make sure that these two operations are performable inside the working area where you are.
When these operations are carried out on a truck, in order to avoid the danger of explosion, cover and protect
the battery and the parts in contact with fuel carefully.
Make sure that around the working area there are not any inflammable products.
Disconnect the battery and short-circuit the logic units through a resistor (56 Ohm 1W) between the positive
(+) and the negative (-) before carrying out any arc-weldings on the truck.
Truck washing