Maharashtra State Electricity Distribution Co. Ltd. of the Chief Engineer (Commercial),
"Prakashgad", 5111 Floor, Station Road, Bandra (E), Mumbai - 400 051.
Tel.: (P) 26474753, (0) 26474211, Fax: (022) 26472366
(A Govt. of Maharashtra Undertaking)
CIN: U40109MH2005SGC153645
Email: cecommhogmail.com, Website: www.mahadiscom.com
Sub: Guidelines in the matter of RE generators intending to connect their power plants
"Behind the meter" as per the provisions of MERC (Grid Interactive Rooftop
Renewable Energy Generating Systems) Regulations, 2019.
7.9
Page lof 2
Clarification:
As per the above Clause 7.9, the consumer is permitted to install and connect his
RE generating system behind the meter only after giving prior intimation to the
host Distribution Licensee.
Therefore, the consumer is required to submit an application online at the "RE
Energy Portal" provided under Consumer Portal at the official website of
Mahavitaran. This on-line application shall be treated as prior intimation. No
separate sanction is required.
Only on-line applications will be considered and processed further in the IT billing
system for proper tagging of the consumer.
As per the regulatory provisions, the consumer shall ensure that all the safety
norms specified by the Central Electricity Authority (CEA) are adhered to and
followed.
Therefore, the consumer shall be asked to obtain the charging permission!
certificate about compliance of safety norms from the concerned Electrical
Inspector office and to upload the same while submitting the online application.
The application will not be considered as prior intimation in absence of the said
charging permission/certificate. If plant capacity is ~ 200 KW, the certificate
about compliance of safety norms issued by Licensed Electrical Contractor shall
be obtained and uploaded.
c) Authority to deal the matters:
As per the existing practice, the matters related to HT consumers shall be dealt
by the O&M Circle and the matters related to the LT consumers shall be dealt by
the O&M Subdivision in consultation with Testing Department.
The application and the uploaded charging permission/certificate about
compliance of safety norms shall be verified and acknowledged by the concerned
authority online. In case of discrepancy, if any, the application will not be
accepted and intimation will be triggered to the consumer via sms/email for
compliance & resubmit.