Technical Data Sheet

TD_827A
ARCAPRO® Positioner Type 827A

General data
ARCA-integrated or to VDI/VDE 3847-1 or IEC 534-6 (NAMUR)
Mounting On linear actuators
Range of stroke: 3 ... 130 mm
On quarter turn Integrated to VDI/VDE 3847-2 or VDI/VDE 3845
actuators Angle of rotation: 30 ... 100°
Enclosure material Metal Aluminium cast AlSi 12 or austenitic stainless steel 1.4581

Degree of protection IP 66 to EN 60529


Any installation position possible; pneumatic connections and exhaust
Installation position
opening must not point upwards for wet applications
4K3, but -30 ... +80 C (Standard and FIP)
Climate class Operation -40…+80 °C (LT)
(see electrical data for explosion-protected devices)
Storage 1K5, but -40 ... +80 C

Transport 2K4, but -40 ... +80 C


98 m/s2, 27 ... 300 Hz
Vibration resistance
Recommended continuous range for complete fitting ≤ 30 m/s2
Classification according For fluid group 1 gases; fulfils requirements in article 4, paragraph 3
PED 2014/68/EU (good engineering practice)
CE marking Applicable directives and standards see declaration of conformity

Controller unit Five-point switch Adaptive

Dead zone Adaptive or fixed from 0.1 ... 10 %

Actuating times ≥1.5 s adjustable

A/D converter Resolution ≤ 0.5 %

Sampling time 10 ms
With / without HART
Cycle time 20 ms
communication
With PROFIBUS PA
60 ms
communication
With Fieldbus
Foundation 60 ms
communication
Dimensions See dimension drawing 1 and 2
Metal enclosure,
Weight Approx. 1.3 kg
aluminium
Metal enclosure,
Approx. 3.9 kg
stainless steel
Connections Electric Screw terminals 2.5 AWG28-12; cable inlet see order key

Pneumatic G 1/4 DIN 45141 or 1/4-18NPT, see order key

©ARCA Regler GmbH • Kempener Straße 18 • D-47918 Tönisvorst


Tel.: +49-(0)2156-7709-0 • Fax: +49-(0)2156-7709-55 • [email protected] • www.arca-valve.com
TD_827A_en_01-2022.doc - Subject to technical modifications - Page 1 of 15
Technical Data Sheet
TD_827A
ARCAPRO® Positioner Type 827A

Pneumatic data

Operation Standard At failure of electrical or pneumatic energy exhausting

Option Fail In Place At failure of electrical or pneumatic energy blocking

Inlet air pressure 1.4 ... 7 bar (Standard) / 3…7 bar (FIP)

Air quality Solids ISO 8573-1 Class 3

Dew point ISO 8573-1 Class 3 (-40 C, min. 20 K below ambient temperature)

Oil content ISO 8573-1 Class 3

Air consumption < 36 x 10-3 Nm3/h during stationary operation

Flow rate (unthrottled) Air supply valve at Δp 2 bar - 4,1 m3/h i.N., 4 bar - 7,1 m3/h i.N., 6 bar - 9,8 m3/h i.N.
2 bar – 8,2 Nm3/h, 4 bar – 13,7 Nm3/h, 6 bar – 19,2 Nm3/h (Standard)
Air exhaust valve at Δp
2 bar – 4,3 Nm3/h, 4 bar – 7,3 Nm3/h, 6 bar – 9,8 Nm3/h (FIP)
Valve leakage < 0,6 x 10-3 Nm3/h

Throttle ratio Up to ∞ : 1 adjustable

Electrical data for basic device

Explosion protection Intrinsic safety “ia” II2G Ex ia IIC T6/T4 Gb, Zone 1
Permissible ambient T4 / T6 - 30 ... + 80 C / - 30 ... + 60 C (Standard and FIP)
“ia” with/without HART
temperature T4 / T6 - 40 ... + 60 C / - 40 ... + 60 C (LT)
“ia” with PROFIBUS
T4 / T6 - 30 ... + 80 C / - 30 ... + 50 C (Standard and FIP)
PA / Foundation
T4 / T6 - 40 ... + 60 C / - 40 ... + 50 C (LT)
Fieldbus

©ARCA Regler GmbH • Kempener Straße 18 • D-47918 Tönisvorst


Tel.: +49-(0)2156-7709-0 • Fax: +49-(0)2156-7709-55 • [email protected] • www.arca-valve.com
TD_827A_en_01-2022.doc - Subject to technical modifications - Page 2 of 15
Technical Data Sheet
TD_827A
ARCAPRO® Positioner Type 827A

Electrical data for basic device with / without HART 2 wire connection

Explosion protection without „ia“

Electrical connection See Figures 5 and 6 See Figures 5 and 6

Communication HART version 7

Input signal IW 4 ... 20 mA 4 ... 20 mA


Current to maintain the
≥ 3.6 mA ≥ 3.6 mA
power supply
Required load voltage
without HART 6.5 V 8.3 V
2 wire device
Required load voltage
without HART 8.4 V -
2/3/4 wire device
Required load voltage
with HART 6.7 V -
2 wire device
Required load voltage
with HART - 8.8 V
2/3/4 wire device
Static destruction limit ± 40 mA -
certified intrinsically safe circuits with max.
Ui = 30 V
For connection to -
Ii = 100 mA
Pi = 1 W
Internal capacitance - 11 nF
207 µH without HART
Internal inductance -
310 µH with HART
Binary input BE1 Suitable for dry contact, max. contact load ≤ 5 μA at 3 V

Electrical isolation IW and BE1 electrically connected IW and BE1 electrically connected

©ARCA Regler GmbH • Kempener Straße 18 • D-47918 Tönisvorst


Tel.: +49-(0)2156-7709-0 • Fax: +49-(0)2156-7709-55 • [email protected] • www.arca-valve.com
TD_827A_en_01-2022.doc - Subject to technical modifications - Page 3 of 15
Technical Data Sheet
TD_827A
ARCAPRO® Positioner Type 827A

Electrical data for basic device with / without HART 3/4 wire connection

Explosion protection without „ia“

Electrical connection See Figure 7 See Figure 7

Communication HART version 7

Input signal IW 0/4 ... 20 mA 0/4 ... 20 mA

Required load voltage 0.2 V 1.0 V

Power supply UH DC 18 … 35 V DC 18 … 30 V
certified intrinsically safe circuits with max.
Ui = 30 V
For connection to -
Ii = 100 mA
Pi = 1 W
Internal capacitance - 11 nF

Internal inductance - 310 µH

Binary input BE1 Suitable for dry contact, max. contact load ≤ 5 μA at 3 V
UH and IW electrically isolated, UH and IW electrically isolated,
Electrical isolation
IW and BE1 electrically connected IW and BE1 electrically connected

Electrical data for basic device PROFIBUS PA

Electrical connection See Figure 8


Layers 1 + 2 to PROFIBUS PA, transmission technique to IEC 1158-2, slave function layer 7 to
Communication
PROFIBUS DP to EN 50170 with extended PROFIBUS functionality
Device profile PROFIBUS PA profile B, version 3.02, over 150 objects
Response time for a
typically 10 ms
master telegram
Device address 126 in the as-delivered condition

Electrical data for basic device Foundation Fieldbus

Electrical connection See Figure 9


H1 communication to specification of the Fieldbus Foundation, group 3, class 31 PS
(Publisher/Subscriber) V 2.4
Communication
1 resource block (RB2), 1 analogue output function block (AO), 1 PID function block (PID), 1
transducer block (standard advanced positioner valve)
Physical layer profile 123, 511

Block execution times Analogue output function block 60 ms; PID function block 80 ms

©ARCA Regler GmbH • Kempener Straße 18 • D-47918 Tönisvorst


Tel.: +49-(0)2156-7709-0 • Fax: +49-(0)2156-7709-55 • [email protected] • www.arca-valve.com
TD_827A_en_01-2022.doc - Subject to technical modifications - Page 4 of 15
Technical Data Sheet
TD_827A
ARCAPRO® Positioner Type 827A

Electrical data for basic device PROFIBUS PA / Foundation Fieldbus

Explosion protection without „ia“

Power supply Bus-powered Bus-powered

Bus voltage DC 9 ... 32 V DC 9 ... 24 V

Current consumption 10.5 mA ± 10 % 10.5 mA ± 10 %

Fault current 0 0
circuits with certified FISCO power supply with
max.
For connection to - Ui = 17,5 V
Ii = 380 mA
Pi = 5,32 W
circuits with certified barrier with max.
Ui = 24 V
-
Ii = 250 mA
Pi = 1,2 W
Internal capacitance - Negligible small

Internal inductance - 8 μH

Safety shutdown

Input resistance > 20 kΏ > 20 kΏ


Signal status 0:
DC 0 ... 4.5 V DC 0 ... 4.5 V
active
Signal status 1:
DC 13 ... 30 V DC 13 ... 30 V
inactive
certified intrinsically safe circuits with max.
Ui = 30 V
For connection to -
Ii = 100 mA
Pi = 1 W
Internal capacitance - Negligible small

Internal inductance - Negligible small

Binary input BE1 Suitable for dry contact, max. contact load ≤ 5 μA at 3 V
Bus connection and safety shutdown Bus connection and safety shutdown electrically
Electrical isolation electrically isolated, Bus connection and BE1 isolated, Bus connection and BE1 electrically
electrically connected connected

©ARCA Regler GmbH • Kempener Straße 18 • D-47918 Tönisvorst


Tel.: +49-(0)2156-7709-0 • Fax: +49-(0)2156-7709-55 • [email protected] • www.arca-valve.com
TD_827A_en_01-2022.doc - Subject to technical modifications - Page 5 of 15
Technical Data Sheet
TD_827A
ARCAPRO® Positioner Type 827A

Electrical data for option modules – analogue module

Explosion protection without „ia“

Electrical connection See Figure 10 See Figure 10

Nominal signal range 4...20 mA, short circuit resistant 4...20 mA, short circuit resistant

Dynamic range 3.6...20.5 mA 3.6...20.5 mA

Auxiliary voltage UH +12...+35 V +12...+30 V

External load RB [kΏ] (UH [V] – 12)/I [mA] (UH [V] – 12)/I [mA]
certified intrinsically safe circuits with max.
Ui = 30 V
For connection to -
Ii = 100 mA
Pi = 1 W
Internal capacitance - 11 nF

Internal inductance - Negligible small

Electrical isolation Disconnected from basic device Disconnected from basic device

Electrical data for option modules – binary module

Explosion protection without „ia“

Electrical connection See Figure 11 See Figure 11


Binary outputs A1, A2,
fault
Signal status “High”
Conductive, R = 1 kΏ ≥ 2.1 mA 1)
(not responded)
Signal status “Low”
Blocked, IR < 60 μA ≤ 1.2 mA 1)
(responded)
certified intrinsically safe circuits with max.
Ui = 15 V
For connection to -
Ii = 25 mA
Pi = 64 mW
Internal capacitance - 5,2 nF

Internal inductance - Negligible small

1) Switching thresholds for supply to EN 60947-5-6: UH = 8.2 V, Ri = 1 kΏ

©ARCA Regler GmbH • Kempener Straße 18 • D-47918 Tönisvorst


Tel.: +49-(0)2156-7709-0 • Fax: +49-(0)2156-7709-55 • [email protected] • www.arca-valve.com
TD_827A_en_01-2022.doc - Subject to technical modifications - Page 6 of 15
Technical Data Sheet
TD_827A
ARCAPRO® Positioner Type 827A

Electrical data for option modules – binary module (continuation)

Explosion protection without „ia“


Binary input BE2
Terminals 11/12
Auxiliary voltage UH ≤ DC 35 V ≤ 20 mA -

Signal status 0: ≤ DC 4.5 V or open ≤ DC 4.5 V or open

Signal status 1: ≥ DC 13 V ≥ DC 13 V

Input resistance > 25 kΏ > 25 kΏ

Static destruction limit ± 35 V -


certified intrinsically safe circuits with max.
For connection to - Ui = 25,2 V

Internal capacitance - Negligible small

Internal inductance - Negligible small


Binary input BE2
Terminals 21/22
Signal state 0: Dry contact, open Dry contact, open

Signal state 1: Dry contact, closed Dry contact, closed

Contact load 3 V, 5 μA 3 V, 5 μA
Binary outputs A1, A2, fault, binary input BE2 Binary outputs A1, A2, fault, binary input BE2
terminals 11/12 disconnected from basic terminals 11/12 disconnected from basic
Electrical isolation device; device,
binary input BE2 terminals 21/22 connected to binary input BE2 terminals 21/22 connected to
basic device basic device

©ARCA Regler GmbH • Kempener Straße 18 • D-47918 Tönisvorst


Tel.: +49-(0)2156-7709-0 • Fax: +49-(0)2156-7709-55 • [email protected] • www.arca-valve.com
TD_827A_en_01-2022.doc - Subject to technical modifications - Page 7 of 15
Technical Data Sheet
TD_827A
ARCAPRO® Positioner Type 827A

Electrical data for option modules – slot initiator module

Explosion protection without „ia“

Electrical connection See Figure 12 See Figure 12


Slotted initiators SJ2-SN or N7S20A to EN 60947-5-6 (NAMUR) for connecting to switching
Binary outputs A1, A2
amplifier, NC (normally closed) function
Signal state “High”
≥ 3 mA at Unom = 8 V ≥ 2.1 mA 1)
(not responded)
Signal state “Low”
≤ 1 mA at Unom = 8 V ≤ 1.2 mA 1)
(responded)
certified intrinsically safe circuits with max.
Ui = 15 V
For connection to Unom = 8 V
Ii = 25 mA
Pi = 64 mW
Internal capacitance - 161 nF

Internal inductance - 120 µH

Binary output fault


Signal status “High”
R = 1,1 kΏ ≥ 2.1 mA 1)
(not addressed)
Signal status “Low”
R = 10 kΏ ≤ 1.2 mA 1)
(addressed)
certified intrinsically safe circuits with max.
UH ≤ 35 V Ui = 15 V
For connection to
I ≤ 20 mA Ii = 25 mA
Pi = 64 mW
Internal capacitance - 5.2 nF

Internal inductance - Negligible small


Binary outputs A1, A2, fault disconnected Binary outputs A1, A2, fault disconnected from
Electrical isolation
from basic device basic device

1) Switching thresholds for supply to EN 60947-5-6: UH = 8.2 V, Ri = 1 kΏ

©ARCA Regler GmbH • Kempener Straße 18 • D-47918 Tönisvorst


Tel.: +49-(0)2156-7709-0 • Fax: +49-(0)2156-7709-55 • [email protected] • www.arca-valve.com
TD_827A_en_01-2022.doc - Subject to technical modifications - Page 8 of 15
Technical Data Sheet
TD_827A
ARCAPRO® Positioner Type 827A

Electrical data for option modules – contact module

Explosion protection without „ia“

Electrical connection See Figure 13 See Figure 13

Binary outputs A1, A2 dry contacts

Max. switching current 4 A AC / DC -

Max. switching voltage 250 V AC, 24 V DC -


certified intrinsically safe circuits with max.
Ui = 30 V
For connection to -
Ii = 100 mA
Pi = 750 mW
Internal capacitance - Negligible small

Internal inductance - Negligible small

Binary output fault


Signal status “High”
R = 1,1 kΏ ≥ 2.1 mA 1)
(not responded)
Signal status “Low”
R = 10 kΏ ≤ 1.2 mA 1)
(responded)
certified intrinsically safe circuits with max.
UH ≤ 35 V Ui = 15 V
For connection to
I ≤ 20 mA Ii = 25 mA
Pi = 64 mW
Internal capacitance - 5.2 nF

Internal inductance - Negligible small


Binary outputs A1, A2, fault disconnected Binary outputs A1, A2, fault disconnected from
Electrical isolation
from basic device basic device

1) Switching thresholds for supply to EN 60947-5-6: UH = 8.2 V, Ri = 1 kΏ

©ARCA Regler GmbH • Kempener Straße 18 • D-47918 Tönisvorst


Tel.: +49-(0)2156-7709-0 • Fax: +49-(0)2156-7709-55 • [email protected] • www.arca-valve.com
TD_827A_en_01-2022.doc - Subject to technical modifications - Page 9 of 15
Technical Data Sheet
TD_827A
ARCAPRO® Positioner Type 827A

Figure 1 Metal enclosure, standard

Figure 2 Metal enclosure, stainless steel

©ARCA Regler GmbH • Kempener Straße 18 • D-47918 Tönisvorst


Tel.: +49-(0)2156-7709-0 • Fax: +49-(0)2156-7709-55 • [email protected] • www.arca-valve.com
TD_827A_en_01-2022.doc - Subject to technical modifications - Page 10 of 15
Technical Data Sheet
TD_827A
ARCAPRO® Positioner Type 827A

+ 4 … 20 mA E
6 Control input
7 A

8
9 +3V
10 Binary input BE1

Figure 5 Electrical connection of 2 wire basic device

2
+ 4 … 20 mA
3
4
5

E
6 Control input
7 A

8
9 +3V
10 Binary input BE1

Figure 6 Electrical connection of 2/3/4 wire base device, 2 wire connection

©ARCA Regler GmbH • Kempener Straße 18 • D-47918 Tönisvorst


Tel.: +49-(0)2156-7709-0 • Fax: +49-(0)2156-7709-55 • [email protected] • www.arca-valve.com
TD_827A_en_01-2022.doc - Subject to technical modifications - Page 11 of 15
Technical Data Sheet
TD_827A
ARCAPRO® Positioner Type 827A

+ 18 … 35 V
2
3
4
5

+ 0/4 … 20 mA E
6 Control input
7 A

8
9 +3V
10 Binary input BE1

Figure 7 Electrical connection of 2/3/4 wire base device, 3/4 wire connection

+  30 V 81
Input safety shutdown
82

 32 V
6 E
PROFIBUS PA Control input
7 A
8
9 +3V
10 Binary input BE1

Figure 8 Electrical connection of base device, PROFIBUS PA

©ARCA Regler GmbH • Kempener Straße 18 • D-47918 Tönisvorst


Tel.: +49-(0)2156-7709-0 • Fax: +49-(0)2156-7709-55 • [email protected] • www.arca-valve.com
TD_827A_en_01-2022.doc - Subject to technical modifications - Page 12 of 15
Technical Data Sheet
TD_827A
ARCAPRO® Positioner Type 827A

+  30 V
81
Input safety shutdown
82

 32 V
6 E
Foundation Fieldbus Control input
7 A Stellungsregler
8
9
Input simulation release
10

Figure 9 Electrical connection of base device, Fieldbus Foundation

+ 12 … 35 V
61 E
Position
62 J feedback

Figure 10 Electrical connection of analogue module

+ 13 … 35 V
11 
12
Binary input BE2
1
21 +3V
22
+ 8,2 V
31
Fault
32

+ 8,2 V
41
Limit value A1
42

+ 8,2 V
51 Limit value A2
52

Figure 11 Electrical connection of binary module

©ARCA Regler GmbH • Kempener Straße 18 • D-47918 Tönisvorst


Tel.: +49-(0)2156-7709-0 • Fax: +49-(0)2156-7709-55 • [email protected] • www.arca-valve.com
TD_827A_en_01-2022.doc - Subject to technical modifications - Page 13 of 15
Technical Data Sheet
TD_827A
ARCAPRO® Positioner Type 827A

+ 8,2 V
31
Fault
32

+ 8,2 V
41
Limit value A1
42

+ 8,2 V
51 Limit value A2
52

Figure 12 Electrical connection of slot initiator module

+ 8,2 V
31
Fault
32

41
Limit value A1
42

51 Limit value A2
52

Figure 13 Electrical connection of contact module

©ARCA Regler GmbH • Kempener Straße 18 • D-47918 Tönisvorst


Tel.: +49-(0)2156-7709-0 • Fax: +49-(0)2156-7709-55 • [email protected] • www.arca-valve.com
TD_827A_en_01-2022.doc - Subject to technical modifications - Page 14 of 15
Technical Data Sheet
TD_827A
ARCAPRO® Positioner Type 827A

Order keys for ARCAPRO® type 827A

1. Series 7. Enclosure material


827A M Aluminium (single-acting only)
2. Explosion protection 1)
E Without E Stainless steel
X Explosion-proof “ia” II2G 2) 8. Pneumatics
1 Single-acting
2 Double-acting (aluminium housing excluded)

3. Connection of base device 9. Mechanical actuation


2 2 wire 0 Standard
4 2/3/4 wire 4) 1 with internal non contacting sensor 5)
2 None (for external sensor)
4. Analogue output 10. Connection thread, electric / pneumatic
0 Without analogue output G M20x1.5 / G 1/4
A Analogue module N 1/2“ NPT / 1/4“ NPT
5. Binary output M M20x1.5 / 1/4“ NPT
0 Without binary output P 1/2“ NPT / G 1/4
B Binary module
S Slot initiator module R connector M12 for input signal / G 1/4
K Contact module S connector M12 for input signal / 1/4“ NPT
6. Communication 11. Options
0 Without communication FIP Fail In Place 3)
H HART LT - 40 °C 5)
P PROFIBUS PA SA connector M12 for Analogue module 5)
F Fieldbus Foundation SB connector M12 for Binary module 5)
SS connector M12 for Slot initiator module 5)
SW connector M12 for External stroke sensor 5)
1
) ATEX and IECEx approval
2
) With HART communication 2/3/4 wire only
3
) only for stainless steel housing
4
) PROFIBUS PA and Foundation Fieldbus excluded
5
) On request

Example:
827A.E2-A0H- Positions 1 - 6
Positioner 827A – no explosion-proof – 2-wire connection – analogue module – without binary output – HART communication
M10-G-LT Positions 7 - 11
Aluminium enclosure – single-acting – mechanical actuation (standard) – connection thread electric M20x1.5 /
pneumatic G 1/4 / - 40 °C

Accessories
Mounting kits For integrated mounting ARCA linear actuators type 812
For integrated mounting ARCA linear actuators type 813
For integrated mounting on linear actuators acc. to VDI/VDE 3847-1
For mounting on linear actuators acc. to IEC 534 (NAMUR)
For integrated mounting ARCA quarter turn actuators type 840
For mounting on quarter turn actuators acc. to VDI/VDE 3845
Pressure gauge blocks Pressure gauge block for single-acting or double-acting positioner
Extern. position detection External rotary potentiometer for strokes to 130 mm or external linear potentiometer

©ARCA Regler GmbH • Kempener Straße 18 • D-47918 Tönisvorst


Tel.: +49-(0)2156-7709-0 • Fax: +49-(0)2156-7709-55 • [email protected] • www.arca-valve.com
TD_827A_en_01-2022.doc - Subject to technical modifications - Page 15 of 15