ARROW RH203-RH224 Heatless Desiccant Air Dryer
ARROW RH203-RH224 Heatless Desiccant Air Dryer
ARROW RH203-RH224 Heatless Desiccant Air Dryer
Form: F-0072
MODELS RH203-RH224
ARROW PNEUMATICS
Table of Contents
Unpacking/Application/Analysis 3
Specifications 4
Installation/Start-up 8
Maintenance 13-14
Drawings 17
Warranty 20
2
Unpacking/Application/Analysis
UNPACKING
VISUALLY CHECK THE DRYER FOR DAMAGE THAT MAY HAVE OCCURRED IN TRANSIT. IF
THERE IS EVIDENCE OF DAMAGE, IMMEDIATELY ENTER A CLAIM WITH THE CARRIER,
AND NOTIFY YOUR ARROW REPRESENTATIVE.
TO ACHIEVE THE BEST DRYER PERFORMANCE, YOU SHOULD CAREFULLY CHECK THAT
THE DESIGN AND INSTALLATION REQUIREMENTS OUTLINED BELOW ARE SATISFIED.
1 Standard operating pressure of your Arrow Dryer can range from 75 minimum to 150 maximum
PSIG. Check dryer label to verify maximum service pressure. Air available for your air usage will
vary with operating pressure.
2 The dryer should not be installed where compressed air and/or ambient temperature exceeds
120°F or drops below 32°F. Locate dryer to avoid extremes of heat and cold from other conditions.
Best results occur when dryer is located as close to point of use as practical. Where applicable,
dryer towers should be insulated to reduce heat loss. Avoid locating dryer outside or where it is
exposed to the elements.
3 Arrow dryers are sized according to air flow not pipe size. The dryer requires 10% to 15% of inlet
airflow (SCFM) for regeneration. The difference between the inlet and outlet flow is the amount of
purge air required. This air is purged to atmosphere and is not available for use downstream.
Make certain air supply to dryer meets your air demand plus purge air requirements.
Twin tower regenerative air dryers are the dryers of choice when traditional refrigerated dryers do not
provide sufficient air quality required for today’s applications. Arrow’s reliable ”RH” series of heatless
twin tower regenerative dryers normally produce –40°F and can optionally be as low as –100°F dew
points. The dryer utilizes activated alumina for efficient drying of compressed air and will operate
under extreme environmental conditions. Activated alumina is aluminum oxide that is highly porous
and exhibits tremendous surface area (350 sq. meters/gram). Activated alumina is resistant to ther-
mal shock and abrasion. It has a smooth, uniform ball size that prevents channeling of the air flow,
which maintains low bed velocities. This maintains air contact time for efficient moisture removal and
minimal pressure drop. Arrow’s printed circuit board dryer controls are housed in a NEMA 4X
rated enclosure and provide control of pneumatically piloted valves chosen for long life
and high air flow.
3
Specifications
SPECIFICATIONS
Drying
Model Capacity Pipe Size Height Width Depth Weight Purge Flow Purge Pressure
No. SCFM Connection Inches Inches Inches Lbs. SCFM Setting
RH203 35 3/4” NPT 40 31 18 360 4.9 45 PSIG
RH204 50 3/4” NPT 57 39 24 508 7.00 45 PSIG
RH205 75 3/4” NPT 57 39 24 599 10.60 42 PSIG
RH206 100 1” NPT 66 39 24 627 14.12 60 PSIG
RH207 125 1” NPT 66 39 24 657 17.50 39 PSIG
RH208 150 1-1/2” NPT 73 45 36 739 21.20 50 PSIG
RH209 200 1-1/2” NPT 73 45 36 797 28.50 50 PSIG
RH210 250 1-1/2” NPT 73 45 36 855 35.30 45 PSIG
RH211 300 2” NPT 70 51 36 918 42.37 42 PSIG
RH212 350 2” NPT 70 51 36 1,124 48.10 50 PSIG
RH213 400 2” NPT 88 52 36 1,187 56.50 45 PSIG
RH214 500 2” NPT 88 52 36 1,245 70.60 38 PSIG
RH215 650 2-1/2” NPT 95 60 36 1,905 88.70 35 PSIG
RH216 750 2-1/2” NPT 95 60 36 2,022 105.90 44 PSIG
RH217 900 2-1/2” NPT 95 60 36 2,197 127.10 40 PSIG
RH218 1,100 3” FLG 103 71 48 2,500 155.40 40 PSIG
RH219 1,300 3” FLG 103 71 48 3,350 183.60 47 PSIG
RH220 1,500 3” FLG 113 83 60 3,775 211.80 55 PSIG
RH221 1,800 3” FLG 113 83 60 4,550 254.00 55 PSIG
RH222 2,100 3” FLG 113 83 60 5,725 297.00 43 PSIG
RH223 2,500 4” FLG 110 95 60 6,500 353.00 36 PSIG
RH224 3,000 4” FLG 110 95 60 8,500 424.00 46 PSIG
ADDITIONAL SPECIFICATIONS
• Specifications and dimensions are subject to change without notice.
• Standard design conditions are 100°F inlet temperature, 100 psig and 100˚F ambient temperature. For other
than standard design conditions or capacities up to 12,000 scfm, consult your factory representative.
• Maximum pressure drop of 2 PSIG
• Maximum Working Pressure: 150 PSIG
• Minimum Working Pressure: 75 PSIG
• Maximum Inlet Temperature: 120ºF
• Minimum Inlet Temperature: 32ºF
• Standard Pressure Dew Point: -40ºF
• Electrical Construction: NEMA 4X
• Standard Voltage: 120V/1PH/60HZ
• AMPS: 0.5
4
Dimensional Drawing
MODEL NO.
DIMENSIONED IN INCHES
208 209 210 211 212 213 214 215 216 217
A 72.78 72.78 72.78 69.77 69.77 A 88.27 88.27 95.32 95.32 95.32
B 9.73 9.73 9.73 9.65 9.65 B 10.65 10.65 12.05 12.05 12.11
C 61.32 61.32 61.32 57.95 57.95 C 75.45 75.45 80.70 80.70 80.64
D 1.25 1.25 1.25 1.25 1.25 D 1.25 1.25 1.25 1.25 1.25
E 42.25 42.25 42.25 48.75 48.75 E 49.00 49.00 57.40 57.40 57.40
F 44.75 44.75 44.75 51.25 51.25 F 51.50 51.50 59.90 59.90 59.90
G 30.00 30.00 30.00 30.00 30.00 G 30.00 30.00 30.00 30.00 30.00
H 36.00 36.00 36.00 36.00 36.00 H 36.00 36.00 36.00 36.00 36.00
J 3.00 3.00 3.00 3.00 3.00 J 3.00 3.00 3.00 3.00 3.00
K 0.8125 0.8125 0.8125 0.8125 0.8125 K 0.8125 0.8125 0.8125 0.8125 0.8125
L 22.375 22.375 22.375 22.125 22.125 L 25.75 25.75 29.95 29.95 29.95
M 5.59 5.59 5.59 6.46 6.46 M 6.47 6.47 7.77 7.77 7.74
5
Dimensional Drawing
6
Installation
MOUNTING SPECIFICATIONS AND DRYER LOCATION
1 Electrical connection must be hard piped with an external fused disconnect switch and
proper overload protection. See electrical connection section for connection location.
WARNING
ARROW DRYERS ARE WIRED FOR HIGH VOLTAGE. ONLY QUALIFIED ELECTRICIANS
ARE AUTHORIZED TO SERVICE THIS ELECTRICAL EQUIPMENT
3 Generally locate your dryer downstream from the air receiver. The only exception would be
on applications with a fluctuating demand. Then the dryer should be located upstream of the
receiver to avoid air surges through the dryer’s desiccant beds.
4
Provide adequate space around the dryer for servicing.
Bolt dryer skid to foundation where possible.
1 Remove all pipe plugs from the dryer. Take care to insure that pipe dope, pipe tape,
scale or metal chips are not trapped before the inlet port.
Note: In situations where air supply is required 24 hours a day (it is undesirable
to interrupt the airflow), a three valve bypass system is recommended to
bypass the dryer and filters. Use the fewest elbows and taper connections
necessary to keep pressure drop at a minimum.
2 Wet air inlet is at the dryer’s bottom piping assembly. Dry air outlet is from the dryer’s top
piping assembly (see flow diagram on page 9).
4 Install After Filter to “Outlet Air” connection on the top piping assembly.
• Dry, service air should be connected to after-filter.
• After filters, located after the dryer, help eliminate the possibility of desiccant dusting
and carry over into the air system.
7
Installation/Start-up
ELECTRICAL CONNECTION
Standard Voltage - 120V/1ph/60Hz All Other Voltages
START-UP OPERATIONS
Touch Pad Control Panel
1. Power On/Off Push Button - Energizes circuit board timer,
initiating dryer operation. OUTLET
2. Power ON LED - Illuminates when dryer is in operation.
3. Failure to Shift Alarm LED - Illuminates when dryer has
failed to shift. LEFT RIGHT
4. Failure to Purge Alarm LED - Illuminates when dryer has TOWER TOWER
12
failed to purge.
13
5. Failure to Repressurize Alarm LED - Illuminates when dryer DRYING DRYING
8
Dryer Operation
AFTER ALL PIPING AND ELECTRICAL CONNECTIONS ARE MADE, PROCEED AS FOLLOWS:
1 SLOWLY PRESSURIZE THE DRYER!
2 When the dryer reaches full operating pressure, check the system for air leaks. Soap test
all joints and fittings. To maintain desired dew point, any leaks detected must be fixed,
especially those on the outlet side of the dryer.
3 Energize electrical circuit by simply pressing the power on/off button.
4 The Power On LED will be illuminated when the dryer is in operation.
When the electrical circuit has been energized, the control circuit board will
start to operate and automatically initiate dryer operation. The timer is factory set,
so that no field adjustment is necessary.
5 Adjust purge adjustment valve so that the center purge pressure gauge reads appropriate
pressure (see specifications chart for purge pressure on page 2).
Dryer Operation
Compressed air saturated with water vapor passes through the inlet valve and flows upward through
the desiccant in tower “A”. Tower “A” is said to be “on line”. The activated alumina desiccant adsorbs
the water vapor in the compressed air and the pressure dew point is lowered to a minimum of –40°F.
The dried air then passes through a check valve assembly to the outlet piping and then to the factory
tools or equipment.
While the air is being dried in tower “A”, the desiccant in tower “B” that adsorbed moisture in the previ-
ous cycle is simultaneously regenerated. Tower “B” is “off line”. At the start of the regeneration cycle,
tower “B” is depressurized from the operating pressure to atmospheric pressure with a downward air
flow and passes through the purge valve and out the purge muffler. Regeneration continues with a
portion of the dry air from tower “A” passing through an orifice assembly and downward through
tower “B” out to atmosphere.
This process takes about ten minutes to complete, with the drying cycle using about five minutes to
provide the desired dew point. The regeneration cycle takes approximately 45 seconds less to allow for
repressurization before switchover. The complete operation therefore consists of two cycles, one for
drying and the other for regeneration. Required purge air is generally 15% of rated flow. As pressure
is a direct function of purge air, the higher the pressure, the lower the purge.
NOTE: At Initial Start-Up, check the dryer operation for one or two cycles, especially at the time
of the tower shift. Verify that all systems are operating in their proper order and sequence.
If the dryer is not functioning properly, contact your Arrow Representative.
9
Dryer Operation
DRYER OPERATION cont’d
Cycle Timing
0 Min 5 Min 10 Min
Closed
Open
Moisture Indicator
The Moisture Indicator is located in the top center piping. The Moisture indicator is provided to
warn operating personnel of dryer malfunction. If the dryer is functioning properly, the desiccant in
the Moisture Indicator will be blue. Should the blue color fade or turn pink, discontinue dryer use
and refer to elevated dew point section in Troubleshooting Guide.
Failure to Depressurize – Senses for pressure on the offline tower after tank shift-over. Should the
tower fail to depressurize do to a malfunctioning system component (i.e. purge valve, solenoid valve,
purge check valve or circuit board timer) the Failure to Depressurize LED will be illuminated. The Failure
to Shift LED will also be illuminated to show a shift failure. Should the alarm LED be observed, refer to
Troubleshooting Guide.
Failure to Repressurize – Senses for pressure on the offline tower before tank shift-over. Should the
tower fail to repressurize do to a malfunctioning system component (i.e. purge valve, solenoid valve, or
circuit board timer) the Failure to Repressurize LED will be illuminated. The Failure to Shift LED will also
be illuminated to show a shift failure. Should alarm LED be observed, refer to Troubleshooting Guide.
Failure to Purge – Senses for pressure on the center purge piping at all times during dryer operation.
Should a low purge pressure condition occur (i.e. purge flow regulator turned down or debris in the
purge pressure piping) the Failure to Purge LED will be illuminated. Should alarm LED be observed, refer
to Troubleshooting Guide.
Failure to Shift – The Failure to Shift LED will be illuminated when a dryer shift failure has occurred.
The shift failure was due to a Failure to Depressurize or Failure to Repressurize. Observe dryer operation
to determine which failure caused the Failure to Shift and refer to Troubleshooting Guide.
10
Optional Equipment
The purpose of the probe and its associated electronics is to first measure the “wetness”
of the air within the desiccant beds and then regenerate the desiccant beds only when
the moisture loading reaches a pre-set maximum, desired dewpoint.
The Dew Point Demand Plus is packaged with a digital dew point controller and High
Humidity Alarm option. The digital dew point controller allows the end user to pre-set a
desired dew point at which the dryer will start the Energy Savings Mode. This controller
also allows the end-user to pre-set a dew point at which a high humidity alarm condition
would occur. See High Humidity Alarm option for full description. See the digital dew point
1
controller Owners Manual enclosed for changing desired dew points.
1 Press the Dew Point Demand ON/OFF button to energize Dew Point Demand Logic. DEWPOINT DEMAND SYSTEM
ENERGY SAVINGS MODE
ON/OFF
2 Slowly open the DDP sample valve1. This valve should be fully opened. DEW POINT DEMAND (OPTIONAL)
ALARM CONDITIONS
3 Slowly open the DDP sample valve2 so that a small flow of air passes across the PURGE REPRESSURIZE HEATER OVERTEMP
probe (approximately 2 to 3 SCFH). This valve should be open at all times when (OPTIONAL)
S
dryer is in operation.
4 When the desired dew point is reached, the energy savings mode LED will be energized to
indicate the dryer is in energy savings mode; eliminating unnecessary dryer cycling, purge
air flow and compressor power consumption.
–100˚F Pressure Dew Point: This option lowers the outlet dew point from the standard –40˚F to –100˚ F. The cycling time is
adjusted accordingly and a repressurizing system is added. The cycle time will be adjusted from a five minute cycle, 2-1/2 minutes
each tower. A normally closed valve will be added to the upper center piping to assist repressurizing each tower.
Remote Alarm Contacts: Contacts will be supplied for: Energy Saving Mode, High Humidity Alarm, Failure to Depressurize alarm,
Failure to Repressurize, Failure to Purge and Failure to Shift, allowing an easy connection method for energizing remote visual or
audible alarms. A 120-volt signal is sent when a failure occurs. (Refer to attached diagram.)
Remote Alarm Dry Contacts: Contacts will be supplied for: Energy Saving Mode, High Humidity Alarm, Failure to Repressurize,
Failure to Depressurize alarm, Failure to Purge and Failure to Shift, allowing for Customer supplied alarm circuits to be easily
connected. Maximum voltage and current is 120V, 3 amperes.(Refer to attached diagram.)
Low Ambient Package: Low ambient temperature protection is accomplished by encasing both towers with a rugged insulation.
This insulation along with heat trace cables eliminates “freeze-ups” from low ambient conditions such as cold outdoor or unheated
indoor installations.
1 Check to see that the power supply to the heat trace cable is 120V.
RS-232 Serial Communications Interface: Allows serial port connections for computer monitoring of dryer functions and
operating statuses. (Refer to attached diagram.)
3
7-Valve Bypass w/Pre-piped Connection3
Prefilter and afterfilter mounted to dryer with integral piping and 7 bypass valves for individually
bypassing either filter and/or dryer. Ready to install in system.
12
Maintenance
WARNING:
BEFORE MAINTENANCE OF DRYER ALWAYS SHUT DRYER OFF,
DISCONNECT THE ELECTRICAL SUPPLY, AND DEPRESSURIZE
THE PNEUMATIC SYSTEM TO AVOID PERSONAL INJURY
Solenoid Valves
Periodically clean entire solenoid valve block. If any of the normally closed solenoid valves fail to
operate, use the air flow diagram below to check operation, and then check the following:
1. Control Voltage - Check the outlet voltage sequence from the circuit board to verify that
the solenoid is receiving electric voltage.
2. Burned out solenoid cell
3. High/low voltage - Voltage should be plus or minus 10% of nameplate reading.
4. Solenoid valve leaking - Disassemble, clean and repack or replace.
Timer
Should the sequencing of towers fail, first check the red light marked “Status” located on the timer
circuit board. When blinking, the timer board is energized. If the light is not blinking, check the
voltage across the 3 Amp 3 AG fuse located on the board. Replace fuse if “blown”. If fuse is not
“blown” check voltage sequence to the appropriate solenoid valve.
VOLTAGE SEQUENCE
120 Voltage
0 Voltage
13
Maintenance cont’d
WARNING
WHEN REPLACING THE PURGE MUFFLERS IT IS RECOMMENDED THE DRYER BE TURNED
OFF AND FULLY DEPRESSURIZED. BACKPRESSURE CAUSED BY CLOGGED MUFFLER CAN
CAUSE INJURY SHOULD YOU ATTEMPT TO DISASSEMBLE WHILE PRESSURIZED.
Purge Muffler
At high pressures a clogged muffler could result in a high backpressure and could result in mechanical failure
or personal injury. For this reason the purge muffler must be periodically checked for any restrictive debris. If
pressure is observed on the offline tower replace muffler immediately.
PREVENTATIVE MAINTENANCE
WARNING
TO AVOID INJURY, DEPRESSURIZE DRYER BEFORE PERFORMING ANY SERVICE
Purge Valve
Should either of the normally closed purge valves fail to operate check the following:
1. Check air signal to valve.
• If air signal is present; disassemble, clean and replace diaphragm and seals.
• If no air signal is present; see solenoid valve information in Maintenance Section.
Inlet Valve
Should either of the normally open inlet valves fail to operate check the following:
2. Check air signal to valve.
• If air signal is present; disassemble, clean and replace diaphragm and seals.
• If no air signal is present; see solenoid valve information in Maintenance Section.
Periodically check the outlet and purge check valves for an absolute seal.
Procedure:
1. Close purge adjustment valve. Verify offline tower pressure is 0 PSIG.
2. Check offline purge muffler for airflow. No airflow should be present.
• If no airflow is present, the outlet and purge check valve have a positive seal.
Repeat procedure next cycle to check opposite outlet and purge check valves.
• If airflow is present, the outlet and/or purge check valves do not have a positive seal. Clean
and/or replace corresponding check valves. See air flow diagram for corresponding check valves.
14
Maintenance/ Trouble Shooting Guide
Monthly
1. Check your operating conditions: inlet flow, inlet pressure, and inlet temperature.
2. Check prefilters and after filters.
3. Check dryer cycle and sequence of operations, (i.e. drying and regenerating).
Annually
1. Check desiccant and replace if necessary.
2. Inspect and clean pilot operated valves and replace packing as necessary.
3. Inspect and clean solenoid valves, check valves and purge lines.
4. Test electrical components, replace as necessary.
Dryer fails to Purge valve does not open Check purge valve,air signal to valve and its solenoid valve.
depressurize Refer to earlier steps if pilot air is detected. Refer to
Preventative Maintenance (PM) Section. Check timer voltage
sequencing.
System air Outlet and/or purge check See outlet/purge check valve PM section
being drained valve stuck open for positive seal.
15
Trouble Shooting Guide
Flow rate higher than Check flow rate and causes for increased demand.
design condition
Excessive pressure Excessive flow rate Check flow rate. Locate cause for increased air demand.
drop in dryer
Dryer fails to pressurize Purge Valve does not close Check purge valve,air signal to purge valve and its solenoid
valve. Refer to earlier steps if pilot air is detected.
Check timer sequencing.
Dryer depressurizes too Purge valve does not close; Check purge valve,air signal to purge valve and its solenoid
rapidly dryer depressurizing valve. Refer to earlier steps if pilot air is detected.
through purge valve Check depressurization timer circuit.
16
Drawings
17
Replacement Parts
Part Description M O D E L
RH203 RH206 RH208 RH211 RH213
RH204 RH207 RH209 RH212 RH214
RH205 RH210
ACTIVATED ALUMINA
50 LBS. FIBER DRUM 1/8” BEADS 34011 34011 34011 34011 34011
18
Replacement Parts
Part Description M O D E L
ACTIVATED ALUMINA
50 LBS. FIBER DRUM 1/8" BEADS 34011 34011 34011 34011 34011 34011
DEWPOINT DEMAND126048
PLUS SENSOR (OPT) 126048 126048 126048 126048 126048 126048
DEWPOINT DEMAND
PLUS CONTROLLER (OPT) 126536 126536 126536 126536 126536 126536
HIGH HUMIDITY SENSOR (OPT) 123079 123079 123079 123079 123079 123079
TRANSFORMER
(230V & 480V OPT) 122297 122297 122297 122297 122297 122297
19
Warranty
The Arrow Regenerative type compressed air dryer is warranted to be free from
defects in material and workmanship, when used under conditions recommended by
the manufacturer, for a period of 12 (twelve) months from date of shipment from
factory to job site of original owner. Products purchased from warehouse stock are
warranted for a period of 12 (twelve) months from date of shipment from that
warehouse provided Arrow is furnished full name, address and date of shipment
information.
This warranty is limited to parts and labor F.O.B. factory, and is subject to the same
restrictions as outlined below concerning misuse, abuse or accident.
During the life of this warranty, Arrow Pneumatics will repair or replace (at Arrow’s
option) free of charge, F.O.B. its plant, any defective part of assembly, if such defect
occurred in normal service and was not due to apparent misuse, abuse, or accident.
(This warranty good only in the continental boundary of the United States. For export, contact the factory)