202 Rate Totaliser Manual
202 Rate Totaliser Manual
202 Rate Totaliser Manual
RATE TOTALISER
MODEL 202
June 1998
CONTENTS
1. Introduction 3
1.1 Model Number Designation 4
1.2 Operation 6
1.3 Intrinsic Safety Considerations 7
2. Specification 9
3. Programming 11
3.1 Program Steps 12
3.2 Calculation of Rate and Total 15
3.3 Total Conversion 16
3.4 Filtering 17
3.5 Example 19
4. Versions 20
4.1 Battery Powered Version 20
4.2 4-20mA Output Version 21
4.3 DC Power Version 24
5. Flowmeter Input 26
7. Installation 34
7.1 Wall Mounting 34
7.2 Removing the Front Panel 35
7.3 The Main Electronics 37
7.4 Wiring 38
7.5 Terminal Designations 39
Index 40
Introduction 3
1. INTRODUCTION
The Model 202 Rate-Totaliser is designed to accept frequency or pulse
inputs from a wide range of flowmeters and to display flowrate, a resetable
total and an accumulated total directly in engineering units. The instrument
is compatible with a wide range of flowmeters and a DIP switch on the input
board enables the circuit to be configured for millivolt signals, reed
switches, pulse trains and most other signal types.
Model 202i. 2 0
i Denotes Version
Intrinsically Safe 0 Battery Powered (Lithium Batteries)
Version 1L Loop Powered with 4-20mA
output and lithium batteries
3L DC Powered with alarm Outputs and
lithium backup batteries
Mounting Options
0 No holes drilled for cable entries
2 Wall Mount (stand
4 Turbine Adapter
6 2" Pipe Mount (Galvanised)
Introduction 5
1.2 OPERATION
Both the Rate and Resetable Total are continuously displayed while the
Accumulated Total is only displayed when the ACCUM TOTAL key is
pressed. The Resetable Total can be reset at any time by pressing the
RESET key.
Hi Test By pressing the RESET key, the high alarm output (if
installed) will go low. If a 4-20mA option is installed,
the output will go to 20mA.
To exit the test mode, press the ACCUM TOTAL key and while still
holding, simultaneously press the RESET and PROGRAM keys.
Introduction 7
At the date this manual was issued (see front page), two versions of the
Model 202 were certified for use in hazardous areas to both CENELEC
and Australian Standards.
Model 202i.x0
Model 202i.x1L
Flowmeter Inputs
Ui = 24V
Ii = 20mA
Pi = 320mW
Uo = 10.0V
lo = 9.0mA
4-20mA Output
Ui = 28V
Ii = 93mA
Pi = 653mW.
Specification 9
2. SPECIFICATION
General
DC Power/Alarm Version
Physical
3. PROGRAMMING
The Model 202 is fully programmable, with all parameters being stored in
memory.
1. By removing the lower cover strip (i.e. the dark grey strip along
the bottom of the enclosure) and replacing it the wrong side up.
This brings a small magnet on the inside of the cover strip in
contact with a reed switch inside the instrument.
Step Comment
Step Comment
CAL 6 Filter.
Fluctuations in the flowrate can be filtered
out so that the Rate and 4-20mA
transmission are held steady. The filter
value is programmed between 1 - 99 where
"1" represents no filtering and 99 is
maximum.
Step Comment
The user programs the Scaling Factor and selects the timebase during the
Programming procedure.
16 Programming
The Scaling Factor is always programmed in the unit relating to Rate, and
the Total Conversion constant is a division factor which can be used to
convert the totals to the different unit. The Total Conversion factor affects
the resetable and accumulated totals and is limited between 0.01 and
2000.
For Example.
If the Rate is required in gallons per minute:
1. The Scaling Factor would be programmed as pulses per gallon.
2. The timebase would be programmed as minutes.
Some common units are given below together with the Total Conversion
constant which should be programmed.
3.4 FILTERING
The Flow Computer has a digital filter which will average out these
fluctuations and enable the Rate to be read to four digit accuracy. The
ability to select a suitable filtering level means that highly accurate and
stable readings can be obtained without excessive lag. When the Rate is
retransmitted via the 4-20mA output, the filtering will also average out any
fluctuations on the output.
The diagram below shows a pulsating signal input together with the effect
of filtering.
A 90% 99%
1 0 0
2 1 2
4 2 4
6 3 6
10 5 11
15 8 17
20 11 22
25 14 28
35 20 40
45 25 51
60 34 69
75 43 86
90 52 103
99 57 113
3.5 EXAMPLE
A flowmeter produces 20.538 pulses per litre and has a maximum output
frequency on 200Hz. It is required to display the flowrate in litres/min with 1
decimal point and the total in litres with no decimals. A 4-20mA output is
installed and 4mA is to represent 0 litres/m and 20mA is to represent 500
litres/m. The instrument is then programmed as follows.
4. VERSIONS
4.1 BATTERY POWERED VERSION
The battery powered version of the Model 202 is designed for operation in
the field without external power sources. Lithium batteries provide
sufficient power to operate the instruments for up to 5 years and the
operator is warned of a low power condition by a message on the LCD
display.
The response rate of the output is very fast, making the instrument suitable
as a frequency to current converter in closed loop systems where a fast
response is normally required.
The instrument draws its operating power from the 4-20mA loop and uses
lithium batteries for backup if the 4-20mA loop is interrupted.
Specification
Since the 4-20mA output is designed to provide power to the Model 202, it
is not isolated from the input. Hence, all sensors must be self powering
(such as reed switches & coils). If external power is required to power the
sensor leg. Namur switches, Hall Effect sensors or opto-sensors), the
power supply delivering the external power must be isolated from the
4-20mA loop supply.
22 Versions
Typical Connection
Open collector outputs are also provided for high and low flowrate alarms.
They can sink up to 200mA and can be used to power external relays,
lights or audible alarms. The outputs are internally protected against
voltage spikes caused by relays and coils.
The switching points can be programmed during the setup mode and the
low flow alarm will switch on whenever the flowrate drops below the
programmed flowrate. Similarly, the high alarm switches on whenever the
flow exceeds the high setpoint.
Connections
26 Flowmeter Input
5. FLOWMETER INPUT
The Model 202 has an input conditioning circuit which will accept signals
from most pulse or frequency producing flowmeters. A 6 position DIL
switch on the rear panel enables the input circuit to be configured for
different signal types.
Turbine Flowmeters
Open Collector Outputs
Reed Switches
Logic Signals
Two Wire Proximity
Switches.
For pulse or logic type signals, the input switching threshold is 1.3 volts.
Hence, the input signal must have a "low" voltage of less than 1.2 volts and
a "high" voltage of greater than 1.4 volts.
Separate input terminals are provided for the coil input so that high
inductance values can be handled, while maintaining the intrinsic safety of
the system. For a coil, the minimum input voltage is 40mV P-P.
S6 must be open
except with an
external DC supply
2. Open-Collector
Note: For a switch or reed input with contact bounce, S4 can be switched
“on”. This will eliminate the e ffect of switch bounce, while limiting
the input frequency to 200 Hz.
5. Coils
6. INTRINSIC SAFETY
CONNECTIONS
When installing the Model 202i in hazardous areas, the wiring and
installation must comply with appropriate installation standards.
The approval uses entity parameters on the input for connections to the
flowmeter, and an associated apparatus type approval for the 4-20mA
output. The 4-20mA output must, therefore, only be connected as shown
on the following page, to barriers with the specified parameters.
Ui = 24V
Ii = 20mA
Pi = 320mW
Cext = 60uF
Lext = 1.5H
The internal capacitance and inductance of the Model 202 seen on the
input are negligibly small and the maximum voltage and current produced
by the Model 202 on its inputs (terminals 1 to 4) are:
The Model 202 has two pulse inputs, a high impedance balanced input for
coils and a pulse input for other devices. It is not allowable to connect to
both inputs at the same time.
Ui = 24V
Ii = 20mA
Pi = 120mW .
32 Intrinsic Safety Connections
Intrinsic Safety Connections 33
34 Installation
7. INSTALLATION
7.1 WALL MOUNTING
1. Remove both the top and bottom cover strips (i.e. the dark plastic
strips on the front) by levering a screwdriver under one end.
2. Undo the seven screws retaining the front. Note that the screws
should not be removed from the front panel as they are retained
by O-rings.
When replacing the lithium battery packs, only one battery pack should be
replaced at a time so that there is always one pack connected to power
the memory.
Adjacent to this control is a RESET switch which can be used to reset the
microprocessor. Note that pressing this button will reset all Setup
Parameters and set all totals to zero.
7.4 WIRING
When connecting the Model 202, it is good practice to use shielded cable.
The shield should be connected to earth near the instrument. The other
end of the shield should not be connected.
1 Coil Input
2 Coil Input
3 Pulse Input (+)
4 Pulse Input (-)
4-20mA Output
7 4-20mA (-)
8 4-20mA (+)
DC Power Versions
7 DC Power 0V
8 DC Power +12 to 28 VDC
9 Low Alarm (+)
10 Low Alarm (-)
11 High Alarm (+)
12 High Alarm (-)
40 Index
NOTES