ILB ETH 24 DI16 DIO16-2TX

Inline Block IO Module


for Ethernet With 16 Digital Inputs
and 16 Digital Inputs or Outputs

AUTOMATIONWORX
Data Sheet 7 0 4 6 A 0 0 1
7046_en_02 © PHOENIX CONTACT - 03/2007

1 Description
The ILB ETH 24 DI16 DIO16-2TX module is designed for 1.2 Input Features
use within an Ethernet network. It is used to acquire and
– Connections for 16 digital sensors
output digital signals.
– Connection of sensors in 2 and 3-wire technology
1.1 Ethernet Features – Maximum permissible load current per sensor: 125 mA
– 2 x Ethernet twisted pair according to 802.3u with auto – Maximum permissible load current from the sensor
negotiation, and auto crossover connected via an supply: 2.0 A
integrated managed 3-port switch (2 external ports,
1.3 Combined Input and Output Features
1 internal port)
– Transmission rates of 10 Mbps and 100 Mbps – Connections for 16 digital sensors/actuators
– IP parameter setting via BootP – Each single channel can only be used as an input or as
– Software interface: Modbus/TCP or DDI (Device Driver an output
Interface) – Connection of sensors in 2 and 3-wire technology
– Management via WEB and SNMP – Maximum permissible load current per sensor: 125 mA
– OPC server 2.14 support – Maximum permissible load current from the sensor
supply: 2.0 A
– Connection of actuators in 2-wire technology
– Nominal current per output: 0.5 A
– Total current of all outputs: 8 A
– Short-circuit and overload protected outputs

The ILB ETH 24 DI16 DIO16-2TX module is designed for SELV operation according to DIN VDE 0805 /
EN 60950 / IEC 60950.

Please refer to the "Mounting and Removing Inline Block IO Modules" application note (see "Ordering Data"
on page 4).

Make sure you always use the latest documentation. It can be downloaded at
www.download.phoenixcontact.com.
A conversion table is available on the Internet at
www.download.phoenixcontact.com/general/7000_en_00.pdf.

For OPC server use an example configuration file can be downloaded at www.download.phoenixcontact.com.
ILB ETH 24 DI16 DIO16-2TX

Table of Contents
1 Description.................................................................................................................................. 1
1.1 Ethernet Features .......................................................................................................................................... 1
1.2 Input Features ................................................................................................................................................ 1
1.3 Combined Input and Output Features............................................................................................................ 1

2 Ordering Data ............................................................................................................................. 4


3 Technical Data............................................................................................................................ 5
4 Internal Circuit Diagram.............................................................................................................. 9
5 Relevant Notes ..........................................................................................................................10
6 Local Diagnostic and Status Indicators .....................................................................................10
7 Connecting Ethernet, the Supply, and Actuators and Sensors .................................................12
7.1 Connecting Ethernet .................................................................................................................................... 12
7.2 Connecting the Supply, Actuators and Sensors........................................................................................... 13
7.3 Terminal Point Assignment of the Power Connectors (Connectors 1 and 2 in Figure 6)............................. 13
7.4 Terminal Point Assignment of the Input and Output Connectors
(Connectors 3 and 6 in Figure 6 on page 13) .............................................................................................. 14
7.5 Terminal Point Assignment of the Input Connectors (Connectors 7 to 10 in Figure 6 on page 13) ............. 14

8 Connection Example .................................................................................................................15


9 Startup .......................................................................................................................................16
9.1 Default upon Delivery/Default Settings ........................................................................................................ 16
9.2 Starting the Firmware................................................................................................................................... 16
9.3 Sending BootP Requests ............................................................................................................................. 17
9.4 Reconfiguration Button................................................................................................................................. 17
10.1 Calling Web-Based Management ................................................................................................................ 17
10.2 Structure of the Web Pages ......................................................................................................................... 17
10.3 "IP Configuration" Menu............................................................................................................................... 18
10.4 Password Protection .................................................................................................................................... 18
10.5 Firmware Update via WBM .......................................................................................................................... 19
10.6 Process Data Access via XML ..................................................................................................................... 19
10.7 XML File Structure ....................................................................................................................................... 20

11 SNMP ........................................................................................................................................21
11.1 MIBs ............................................................................................................................................................. 21
11.2 Traps ............................................................................................................................................................ 21

12 Monitoring Functions .................................................................................................................22


12.1 Setting the Required Fault Response Mode ................................................................................................ 22
12.2 Process Data Watchdog/Process Data Monitoring ...................................................................................... 23
12.3 Fault Response Acknowledgement.............................................................................................................. 24

7046_en_02 PHOENIX CONTACT 2


ILB ETH 24 DI16 DIO16-2TX

13 Modbus/TCP Protocol ...............................................................................................................25


13.1 Modbus Connections ................................................................................................................................... 25
13.2 Modbus Interface ......................................................................................................................................... 25
13.3 Modbus Conformity Classes ........................................................................................................................ 25
13.4 Modbus Function Codes .............................................................................................................................. 25
13.5 Modbus Table .............................................................................................................................................. 25
13.6 Process Data Assignment (Modbus)............................................................................................................ 26

14 Device Driver Interface (DDI) ....................................................................................................27


14.1 Connection and Error Monitoring ................................................................................................................. 27
14.2 Services for Process Data Monitoring.......................................................................................................... 27
14.3 Services for Ethernet Connection Management .......................................................................................... 27
14.4 Structure of the DTI Area ............................................................................................................................. 27
14.5 Process Data Assignment (DDI) .................................................................................................................. 28

15 Diagnostic Register ...................................................................................................................29


15.1 Status Register............................................................................................................................................. 29
15.2 I/O Diagnostic Register ................................................................................................................................ 29
15.3 NetFail Reason ............................................................................................................................................ 29

16 Special Register ........................................................................................................................30


16.1 Modbus Connection Timeout ....................................................................................................................... 30
16.2 Process Data Watchdog Timeout ................................................................................................................ 30
16.3 Fault Response Mode .................................................................................................................................. 30
16.4 Command Register ...................................................................................................................................... 30

7046_en_02 PHOENIX CONTACT 3


ILB ETH 24 DI16 DIO16-2TX

2 Ordering Data

Product
Description Type Order No. Pcs./Pkt.
Inline Block IO module for Ethernet ILB ETH 24 DI16 DIO16-2TX 2832962 1
with 16 digital inputs and 16 digital inputs or outputs

Accessories: Ethernet
Description Type Order No. Pcs./Pkt.
Gray RJ45 connector set for linear cable FL PLUG RJ45 GR/2 2744856 2
Green RJ45 connector set for crossed cable FL PLUG RJ45 GN/2 2744571 2
Double sheathed Ethernet cable FL CAT5 HEAVY 2744814 1
Flexible Ethernet cable FL CAT5 FLEX 2744830 1
Assembly tool for RJ45 connector FL CRIMPTOOL 2744869 1

Matching dust protection covers and safety systems for RJ45 connections can be found in the product range of Reichle & De Massari/
Switzerland.

Accessories: Software
Description Type Order No. Pcs./Pkt.
Factory Manager, network management software FL SWT 2831044 1

You can use Factory Manager for Ethernet network diagnostics as well as for firmware updates of the ILB ETH 24 DI16 DIO16-2TX
module. However, it is not required for module startup.

INTERBUS OPC server IBS OPC SERVER 2729127 1


CD-ROM with German and English product version 2.1x and online
documentation.
Additional language versions are available on request.

Accessories: Connectors as Replacement Item


Description Type Order No. Pcs./Pkt.
Connector for the supply (color print) ILB SCN-12-PWR IN-CP 2863164 5
Connector for digital 4-channel or 16-channel Inline input terminals, with color IB IL SCN-12-ICP 2727611 10
print

Accessories: Other
Description Type Order No. Pcs./Pkt.
Recommended end clamp; placed both to the right and left of the module to CLIPFIX 35-5 3022276 50
secure it on the DIN rail

Documentation
Description Type Order No. Pcs./Pkt.
"Mounting and Removing Inline Block IO Modules" application note AH ILB INSTALLATION 9014931 1
"Firmware Updates for Devices Supporting TFTP Firmware Updates" AH EN TFTP FIRMWARE UPDATE 7090 1
application note
"Driver Reference Manual for G4-Based Controller Boards Using PC Bus and IBS PC SC SWD UM E 2745172 1
Ethernet" user manual

7046_en_02 PHOENIX CONTACT 4


ILB ETH 24 DI16 DIO16-2TX

3 Technical Data
General Data
Housing dimensions with connectors (width x height x depth) 156 mm x 55 mm x 141 mm
Weight 500 g (with connectors)
Operating mode Process data mode with 4 bytes
Transmission speed 10 Mbps and 100 Mbps with auto negotiation and auto crossover
Type of sensor and actuator connection 2 and 3-wire technology

Housing Dimensions

156 55

120
141

7151B005

Figure 1 Housing dimensions of the module (dimensions in mm)

Ambient Conditions
Regulations Developed according to VDE 0160/EN 50178/IEC 62103, UL 508
Ambient temperature (operation) -25°C to +60°C
Ambient temperature (storage/transport) -25°C to +85°C
Humidity (operation/storage/transport) 10% to 95%, according to EN 61131-2
Air pressure (operation) 80 kPa to 108 kPa (up to 2000 m above sea level)
Air pressure (storage/transport) 66 kPa to 108 kPa (up to 3500 m above sea level)
Degree of protection according to IEC 60529 IP20
Class of protection Class 3 according to VDE 0106/IEC 60536
Air and creepage distances According to DIN VDE 0110/IEC 60664, IEC 60664A,
DIN VDE 0160/EN 50178/IEC 62103
Housing material Plastic, PVC-free, PBT, self-extinguishing (V0)
Pollution degree according to 2; condensation not permitted during operation
EN 60664-1/IEC 60664-1, EN 61131-2/IEC 61131-2
Surge voltage class II

7046_en_02 PHOENIX CONTACT 5


ILB ETH 24 DI16 DIO16-2TX

Electrical Isolation/Isolation of the Voltage Areas


Test Distance Test Voltage
I/O / Logic 500 V AC, 50 Hz, 1 min
I/O / functional earth ground 500 V AC, 50 Hz, 1 min
Logic / functional earth ground 500 V AC, 50 Hz, 1 min
Ethernet interface signals / logic 1500 V rms, 50 Hz to 60 Hz, 1 min

Mechanical Requirements
Vibration test, sinusoidal vibrations according to 5g load, 2.5 hours in each space direction
EN 60068-2-6/IEC 60068-2-6
Shock test according to EN 60068-2-27/IEC 60068-2-27 25g load for 11 ms, half sinusoidal wave,
3 shocks in each space direction and orientation
Broadband noise according to EN 60068-2-64/IEC 60068-2-64 0.78g load, 2.5 hours in each space direction

Conformance With EMC Directive 89/336/EEC


Noise Immunity Test According to EN 61000-6-2
Electrostatic discharge (ESD) EN 61000-4-2 Criterion B
IEC 61000-4-2 4 kV contact discharge
8 kV air discharge
Electromagnetic fields EN 61000-4-3 Criterion A
IEC 61000-4-3 Field strength: 10 V/m
Fast transients (burst) EN 61000-4-4 Criterion B
IEC 61000-4-4 Remote bus: 2 kV
Power supply: 2 kV
I/O cables: 2 kV
Criterion A
All interfaces: 1 kV
Surge voltage EN 61000-4-5 Criterion B
IEC 61000-4-5 DC supply lines: ± 0.5 kV/± 1.0 kV (symmetrical/asymmetrical)
Signal lines: ± 1 kV/± 1 kV (symmetrical/asymmetrical)
Conducted interference EN 61000-4-6 Criterion A
IEC 61000-4-6 Test voltage 10 V
Noise Emission Test According to EN 61000-6-4
Noise emission of housing EN 55011 Class A

Interface
Ethernet interface 2 x Ethernet twisted pair according to 802.3u via RJ45 connector; shielding
directly connected to functional earth ground

24 V Module Supply (Communications Power, Sensor and Actuator Supply; UL, US and UA)
Nominal value 24 V DC
Tolerance -15%/+20% according to EN 61131-2
Ripple ±5% according to EN 61131-2
Permissible range 19.2 V DC to 30.0 V DC
Current consumption at UL 70 mA
Current consumption at US1 and US2 2x2A
Current consumption at UA1 and UA2 2x4A
Safety equipment for communications power Surge protection and protection against polarity reversal
Safety equipment for sensor supply Surge, overload and short-circuit protection
Safety equipment for actuator supply Surge protection
Connection Via power connectors

7046_en_02 PHOENIX CONTACT 6


ILB ETH 24 DI16 DIO16-2TX

Digital Outputs
Number 16 (freely selectable)
Connection method for actuators 2-wire technology
Nominal output voltage UOUT 24 V DC
Differential voltage at Inom ≤1V
Nominal current Inom per channel 0.5 A
Total current 2x4A
Protection Short-circuit and overload protection
Nominal load
Ohmic 48 Ω / 12 W
Lamp 12 W
Inductive 12 VA (1.2 H, 50 Ω)
Switching frequency with nominal inductive load 0.5 Hz (1.2 H, 50 Ω), maximum
Overload response Auto restart
Response with inductive overload Output may be damaged
Reverse voltage protection against short pulses Protected against reverse voltages
Resistance to permanently applied reverse voltages Protected against reverse voltages, permissible current 2 A, maximum
Response upon power down The output follows the supply voltage without delay.
Limitation of the voltage induced on circuit interruption -41.0 V
One-time unsolicited energy 1 J, maximum
Protective circuit type Integrated free running circuit in the output chip
Overcurrent shutdown 0.7 A, minimum
Maximum output current when switched off 10 µA

When not loaded, a voltage can be measured even at an output that is not set.

Error message to the higher-level control system Short circuit/overload of outputs

Digital Inputs
Number 32 (16 permanent, 16 freely selectable)
Connection method for sensors 2 and 3-wire technology
Input design According to EN 61131-2 Type 1
Definition of switching thresholds
Maximum low-level voltage ULmax < 5 V
Minimum high-level voltage UHmin > 15 V
Common potentials Sensor supply US, ground
Nominal input voltage UIN 24 V DC
Permissible range -30 V < UIN < +30 V DC
Nominal input current for UIN 5 mA, typical
Current flow Linear in the range 1 V < UIN < 30 V
Delay time ≤ 500 µs
Permissible cable length to the sensor 100 m
Use of AC sensors AC sensors in the voltage range < UIN are limited in application
Error message to the higher-level control system Sensor supply not present
Short circuit/overload of sensor supply

7046_en_02 PHOENIX CONTACT 7


ILB ETH 24 DI16 DIO16-2TX

Power Dissipation
Formula to Calculate the Power Dissipation of the Electronics
n m
PTOT = 1.68 W + (IS36 + IS710 ) x 0.06 W + S (0.129 W + ILi x 0.28 W + ILi x 0.35 V) + S 0.125 W
2 2 2

i=1 j=1
Where
PTOT Total power dissipation of the module
IS36 Current from the sensor supply at slots 3 to 6
IS710 Current from the sensor supply at slots 7 to 10
i Continuous index
n Number of set outputs (n = 1 to 16)
ILi Load current of output i
j Continuous index
m Number of set inputs (n = 1 to 32)

Limitation of Simultaneity
No limitation of simultaneity, derating

Derating
Ambient Temperature (TA) Total Current (Itot)
Outputs, Connectors 3 to 6
-25°C to +30°C 8A A
+30°C to +60°C 8 A - ((TA - 30°C) x 0.2 A/°C) 8

I to t

0
-2 5 0 3 0 6 0 ° C

6 9 9 2 B 0 1 2
T A

Sensor Supply, Connectors 3 to 6


-25°C to +30°C 2A
+30°C to +60°C 2 A - ((TA - 30°C) x 0.05 A/°C)
A
Sensor Supply, Connectors 7 to 10 2
-25°C to +30°C 2A
+30°C to +60°C 2 A - ((TA - 30°C) x 0.05 A/°C) 1 .5

1
I to t
0 .5

0
-2 5 0 3 0 6 0 ° C
6 9 9 2 B 0 1 3 T A

Approvals
For the latest approvals, please visit www.download.phoenixcontact.com.

7046_en_02 PHOENIX CONTACT 8


ILB ETH 24 DI16 DIO16-2TX

4 Internal Circuit Diagram

LNK1/2 ACT1/2 BOOT nF RDY DIA

8x 8x

8x 8x
μP

3,3 V

24 V
UA1 UA2

DIO1...8 DIO9..16 DI1...8 DI9..16

US2

US1
UL
16x 16x
IN/ IN
OUT

2 TX ETH

7046B004

Figure 2 Internal wiring of the terminal points

Power supply unit with electrical isolation


Key:
Optocoupler
LED
Short-circuit-proof output
µ P Microprocessor
Short-circuit-proof sensor supply
Switch

Transmitter

5 Relevant Notes

Shielding Electrostatic discharge


The shielding ground of the connected twisted The module contains components that can be
pair cables is electrically connected with FE. damaged or destroyed by electrostatic
When connecting network segments, avoid discharge. When handling this module,
ground loops, potential transfers, and observe the necessary safety precautions
equipotential bonding currents using the against electrostatic discharge (ESD) in
braided shield. accordance with EN 61340-5-1 and
EN 61340-5-2.

7046_en_02 PHOENIX CONTACT 9


ILB ETH 24 DI16 DIO16-2TX

Housing
Only authorized Phoenix Contact personnel
are permitted to open the housing.

6 Local Diagnostic and Status Indicators

A 1
2
E 1
2
1
2
1
2
B O O T L N K 1
3 3 3 3
n F A C T 1
4 4 4 4
I1 I2 I3 I4
R D Y L N K 2
D IA A C T 2

D
1 E 1 1 E 1
2 2 2 2
3 3 3 3
4 4 4 4
IO 1 IO 2 IO 3 IO 4

U S 1
U S 2
U A 1
U A 2
C
U L

P W R 1 P W R 2

B 7 0 4 6 A 0 0 2

Figure 3 Diagnostic and status indicators of the ILB ETH 24 DI16 DIO16-2TX module

7046_en_02 PHOENIX CONTACT 10


ILB ETH 24 DI16 DIO16-2TX

Designation Color Meaning


A: Module and Ethernet
BOOT Green OFF Boot loader inactive / firmware successfully started
Flashing Waiting for BootP reply
ON Start firmware
RDY Green OFF Firmware not active
Flashing Firmware ready to operate
ON Connection to a process data client established
nF Red OFF No network error
ON Network error occurred; connection monitoring, for example, has tripped or an
error occurred during the firmware update.
Flashing Firmware error
Flashing Hardware watchdog triggered
together with
DIA
DIA Red OFF There is no module diagnostics.
ON There is module diagnostics. (A bit is set in the diagnostic register.)
Flashing Firmware error
Flashing Hardware watchdog triggered
together with
nF
LNK1/2 Green OFF No connection established via port 1/2
ON Connection via Ethernet to a module via port 1/2 established
ACT1/2 Yellow OFF No transmission or reception of Ethernet telegrams at port 1/2
ON Transmission or reception of Ethernet telegrams at port 1/2
B: PWR
US1/2 Green ON Sensor supply 1/2 present
OFF Sensor supply 1/2 not present
UL Green ON 24 V communications power present
OFF 24 V communications power not present
UA1/2 Green ON Actuator supply 1/2 present
OFF Actuator supply 1/2 not present
C: IN/OUT, Each Connector
E Red ON Short circuit or overload of the outputs
OFF No output error
1 to 4 Yellow ON Input/output active
OFF Input/output not active
D: IN, Each Connector
E Red ON Short circuit or overload of one of the sensor supplies
OFF No sensor supply error
1 to 4 Yellow ON Input active
OFF Input not active

If the error LED (E) of a group of eight outputs (e.g., connector 3/4 or connector 5/6) lights up this indicates that
a short circuit or overload is present at one or more of the outputs in this group.

7046_en_02 PHOENIX CONTACT 11


ILB ETH 24 DI16 DIO16-2TX

7 Connecting Ethernet, the Supply, and Actuators and Sensors


7.1 Connecting Ethernet
By default upon delivery, the Ethernet connections have
been set to auto negotiation with auto crossover.
If a port is set to fixed transmission parameters (speed,
duplex mode), auto crossover is deactivated. In this case
the port acts like a switch port (MDI-X). The pin assignment
is specified accordingly. The module must be connected to
termination devices using a 1:1 cable and to other
configuration devices using a cross-over cable. R e c o n f

For further information on Ethernet cabling,


please refer to www.iaona-eu.com.

Connect Ethernet to the module using an 8-pos. RJ45


connector. For the pin assignment of the RJ45 female
connector, please refer to the following table:

Pin Assignment
1 RD+ (receive data +) 7 0 4 6 A 0 0 6

2 RD- (receive data -) Figure 5 8-pos. RJ45 female connectors


3 TD+ (transmit data +)
4 Reserved For further information on the reconfiguration
5 Reserved button, please refer to page 16.
6 TD- (transmit data -)
7 Reserved
8 Reserved

RJ45
Pin 8
Pin 7
Pin 6
Pin 5
Pin 4
Pin 3
Pin 2
Pin 1

Figure 4 Pin assignment of the RJ45 female connector

7046_en_02 PHOENIX CONTACT 12


ILB ETH 24 DI16 DIO16-2TX

7.2 Connecting the Supply, Actuators and Sensors

1 2 1 2

1 .1 1 1
2 .1 1 .1 2 .1
1 1

1 .2 2 2
2 .2 1 .2 2 .2
2 2

1 .3 3 3
2 .3 1 .3 2 .3
3 3

1 .4 4 4
2 .4 1 .4 2 .4
4 4

1 .5 5 5
2 .5 1 .5 2 .5
5 5

1 .6 6 6
2 .6 1 .6 2 .6
6 6

1 -2 3 -1 0
7 0 4 6 A 0 0 3

Figure 6 Terminal point assignment of the Inline connectors

7.3 Terminal Point Assignment of the Power Connectors (Connectors 1 and 2 in Figure 6)
Terminal Point Assignment Terminal Point Assignment
Connector 1 (PWR 1)
1.1 24 V sensor supply US1 2.1 24 V sensor supply US2
1.2 24 V communications power UL 2.2 24 V communications power UL
1.3 GND 2.3 GND
1.4 FE 2.4 FE
1.5 24 V communications power UL 2.5 24 V communications power UL
1.6 GND 2.6 GND
Connector 2 (PWR 2)
1.1 Actuator supply UA1 2.1 Actuator supply UA2
1.2 24 V communications power UL 2.2 24 V communications power UL
1.3 GND 2.3 GND
1.4 FE 2.4 FE
1.5 24 V communications power UL 2.5 24 V communications power UL
1.6 GND 2.6 GND

The terminal points can have a total current of The supply points have the same ground
8 A per terminal point. The maximum current potential. All ground supplies on a module are
carrying capacity of 8 A must not be exceeded. electrically connected with one another.
If the total output current in your application is The communications power is also electrically
> 8 A, supply the module via a minimum of two connected via all contacts. In this way, it can
terminal points connected in parallel. supply all potentials with just one supply
without the need for additional terminals, see
"Connection Example" on page 15.

7046_en_02 PHOENIX CONTACT 13


ILB ETH 24 DI16 DIO16-2TX

7.4 Terminal Point Assignment of the Input and Output Connectors (Connectors 3 and 6 in Figure 6 on page 13)
Terminal Point Assignment
Connector 3 Connector 4 Connector 5 Connector 6
(IO1) (IO2) (IO3) (IO4)
1.1, 2.1 1.1, 2.1 1.1, 2.1 1.1, 2.1 Signal input (IN) and output (OUT)
1.2, 2.2 1.2, 2.2 1.2, 2.2 1.2, 2.2 Sensor voltage UI1 for 2 and 3-wire termination
1.3, 2.3 1.3, 2.3 1.3, 2.3 1.3, 2.3 Ground contact (GND) for 3-wire termination
1.4, 2.4 1.4, 2.4 1.4, 2.4 1.4, 2.4 Signal input (IN) and output (OUT)
1.5, 2.5 1.5, 2.5 1.5, 2.5 1.5, 2.5 Initiator supply UI1 for 2 and 3-wire termination
1.6, 2.6 1.6, 2.6 1.6, 2.6 1.6, 2.6 Ground contact (GND) for 3-wire termination

Each channel on the connectors three to six If a channel is used as input, this input must
can either be used as input or output. A not be set as an output.
configuration is not required.

7.5 Terminal Point Assignment of the Input Connectors (Connectors 7 to 10 in Figure 6 on page 13)
Terminal Point Assignment
Connector 7 Connector 8 Connector 9 Connector 10
(I1) (I2) (I3) (I4)
1.1, 2.1 1.1, 2.1 1.1, 2.1 1.1, 2.1 Signal input (IN)
1.2, 2.2 1.2, 2.2 1.2, 2.2 1.2, 2.2 Sensor voltage UIS for 2 and 3-wire termination
1.3, 2.3 1.3, 2.3 1.3, 2.3 1.3, 2.3 Ground contact (GND) for 3-wire termination
1.4, 2.4 1.4, 2.4 1.4, 2.4 1.4, 2.4 Signal input (IN)
1.5, 2.5 1.5, 2.5 1.5, 2.5 1.5, 2.5 Initiator supply UI2 for 2 and 3-wire termination
1.6, 2.6 1.6, 2.6 1.6, 2.6 1.6, 2.6 Ground contact (GND) for 3-wire termination

7046_en_02 PHOENIX CONTACT 14


ILB ETH 24 DI16 DIO16-2TX

8 Connection Example

US1 US2 1 2 3 4 5 6 7 8 9 10

1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2

1 11 11 11 11 11 11 11 1

2 22 22 22 22 22 22 22 2

3 33 33 33 33 33 33 33 3

4 44 44 44 44 44 44 44 4

5 55 55 55 55 55 55 55 5

6 66 66 66 66 66 66 66 6

+ + +
OUT 14

IN 31
+24 V
OUT 6

IN 30
+24 V
IN 15
+24 V

ETHERNET
2TX - - -
UL UA1 UA2
704601007

Figure 7 Connection example

The numbers above the module illustration


identify the connector slots.

The module has an FE spring (metal clip) on


the bottom of the electronics base. This spring
creates an electrical connection to the DIN rail.
Use grounding terminals to connect the DIN
rail to protective earth ground. The module is
grounded when it is snapped onto the DIN rail.
To ensure reliable functional earth grounding
of the module even when the DIN rail is dirty or
the metal clip is damaged, Phoenix Contact
also recommends grounding the module via
one of the FE terminal points.

7046_en_02 PHOENIX CONTACT 15


ILB ETH 24 DI16 DIO16-2TX

9 Startup
9.1 Default upon Delivery/Default Settings
By default upon delivery, the following functions and features are available:
– For SNMP and web-based management the password is "private".
– IP configuration
IP address: 0.0.0.0
Subnet mask: 0.0.0.0
Default gateway: 0.0.0.0
BootP requests: Enable
– Software update
Software update on next reboot: Disable
TFTP server IP address: 0.0.0.0
Downloadable file name: -
– Port configuration
Mode of port 1: Auto negotiation
Mode of port 2: Auto negotiation
– SNMP configuration
Name of device: Inline Block I/O
Description: ILB with 16 IN and 16 IN/OUT
Physical location: Unknown
Contact: Unknown
– Trap configuration
Sending traps: Disable
Trap manager IP address 1 to 5: 0.0.0.0
– Services
HW watchdog: Enable
– Process data monitoring
Process data watchdog timeout: 500 ms
Fault response mode: Reset fault mode (default)

By default, the ILB ETH 24 DI16 DIO16-2TX


module has no valid IP parameters.

9.2 Starting the Firmware


After you have applied voltage to the module the firmware
is started. The following LED sequence is shown:

LED Meaning
BOOT flashing Boot Loader is started
BootP requests are sent
BOOT ON Firmware is extracted
BOOT and RDY ON Firmware is started
RDY flashing Operation

7046_en_02 PHOENIX CONTACT 16


ILB ETH 24 DI16 DIO16-2TX

9.3 Sending BootP Requests 10 Web-Based Management (WBM)


Initial startup:
The ILB ETH 24 DI16 DIO16-2TX module has a web
During initial startup, the module transmits a BootP request server, which generates the required pages for web-based
without interruption until it receives a valid IP address. The management and, depending on the requirements of the
requests are transmitted at varying intervals (2 s, 4 s, 8 s, user, sends them to "Factory Manager" or a standard web
2 s, 4 s, etc.) so that the network is not loaded browser.
unnecessarily.
Web-based management can be used to access static
If valid IP parameters are received, they are saved as
information (e.g., technical data, MAC address) or dynamic
configuration data by the module.
information (e.g., IP address, status information) or to
Further restarts: change the configuration (password-protected).
If the module already has valid configuration data and
10.1 Calling Web-Based Management
BootP is not disabled, it only transmits three more BootP
requests on a restart. If it receives a BootP reply, the new The ILB ETH 24 DI16 DIO16-2TX web server can be
parameters are saved. If the module does not receive a addressed using the IP address if configured
reply, it starts with the previous configuration. If BootP is correspondingly.
disabled and a valid configuration is available, the module The module homepage is accessed by entering the URL
starts immediately. (http://<ip address>) in the address line of your browser.
Example: http://192.168.2.81
For presetting the IP address via BootP, you
can use Factory Manager (see "Ordering Data"
on page 4) or any BootP server available.

9.4 Reconfiguration Button


By modifying the network parameters you can block your
access to the module via Ethernet. If, for example, BootP is
disabled and the user forgets the IP address set, the
reconfiguration button can be used to access the module
again.
If the reconfiguration button is pressed during power-on, all
permanently stored parameters are reset to the default
upon delivery. The reconfiguration button must be pressed
until the BOOT LED and the RDY LED are on. As soon as Figure 8 WBM homepage
the reconfiguration button has been released, the module
starts with the default parameters. 10.2 Structure of the Web Pages
The module web pages are divided into two parts, with the
navigation tree and the relevant submenus on the left-hand
side, and the corresponding information displayed on the
right-hand side.

7046_en_02 PHOENIX CONTACT 17


ILB ETH 24 DI16 DIO16-2TX

10.4 Password Protection


IL B E T H 2 4 D I1 6 D IO 1 6 -2 T X
All status changes to the module are only possible after
G e n e r a l In s tr u c tio n s entering a password. The password can be changed at any
In fo r m a tio n time. Your unique password must be between four and
twelve characters long (note that the password is case-
D e v ic e In fo r m a tio n sensitive). By default upon delivery, the password is
D e v ic e In fo rm a tio n "private". The password for the web is the same as for the
T e c h n ic a l D a ta SNMP read and write access.
H a rd w a re In s ta lla tio n
L o c a l D ia g n o s tic s
Forgetting the password requires resetting the
D e v ic e C o n fig u r a tio n entire configuration using the reconfiguration
IP C o n fig u r a tio n button in order to be able to access the module
S N M P C o n fig u ra tio n again.
S o ftw a re U p d a te
C h a n g e P a s s w o rd
W a tc h d o g (H a rd w a re )
P o rt C o n fig u r a tio n

B lo c k IO
P r o c e s s D a ta M o n ito r in g ( P r o c e s s D a ta W a tc h d o g )
R e m o te D ia g n o s tic s
P r o c e s s D a ta
E v e n t T a b le
6 1 5 5 A 0 0 4

Figure 9 Structure of the web pages

10.3 "IP Configuration" Menu


Figure 10 shows the set IP parameters and addressing
mechanism. To change the IP parameters via the WBM,
"BootP Request" must be set to "Disable" or the module's
BootP requests must not be answered, no BootP server
must be activated in the network.

Figure 10 "IP Configuration" menu

7046_en_02 PHOENIX CONTACT 18


ILB ETH 24 DI16 DIO16-2TX

10.5 Firmware Update via WBM


The following steps must be carried out when executing a If BootP is set to "Enable" and a reply with
firmware update via WBM: values for "TFTP Server IP Address" and
– In WBM click on "Device Configuration" and then "Downloadable File Name" is received, the
"Software Update". Enter the IP address of the TFTP entries done in WMB are overwritten with
server in the "TFTP Server IP Address" field. Then these specifications. After restart the values
enter the file name of the firmware and the path name, accepted are displayed in WBM.
if necessary, in the "Downloadable File Name" field. In
the "Software Update on Next Reboot" field, click on In the event of an error during flash
"Enable". programming (e.g., voltage interrupt) the
– Enter your password and click "Apply" to execute a device can only be restarted by repeating the
reboot at a later time; click on "Apply and Reboot" for update. The device indicates this by means of
the update to take effect immediately. the BOOT and NF LED combination. The
– Check execution of the update. After "Apply and devices starts the update automatically after a
Reboot" the browser automatically updates the web restart. Access to WBM is no longer possible.
pages and displays the result in the "TFTP Update
Status" field. After successful update and initial An application note for TFTP download using
firmware start "Firmware Update was successfully Factory Manager
executed" is displayed. In the event of an error during (AH EN TFTP FIRMWARE UPDATE) can be
downloading the corresponding error message is found at www.download.phoenixcontact.com.
indicated. The device indicates this error by means of
the BOOT, RDY and NF LED combination. A restart
repeats the downloading process. Activating "Disable" 10.6 Process Data Access via XML
in the "Software Update on Next Reboot" field allows
The web server of the ILB ETH 24 DI16 DIO16-2TX offers
for update abortion and starting the previous firmware
the possibility to access the process data via a web page in
again.
XML format.
You can access the web pages via a standard web
browser. For calling the XML pages with the process data
enter the address in the following format in the address line
of the browser:
"http:// <IP address>/processdata.xml".

Figure 11 "Software Update" menu

7046_en_02 PHOENIX CONTACT 19


ILB ETH 24 DI16 DIO16-2TX

10.7 XML File Structure


The XML file contains different data areas: PD_WORDS
Number of process data words in a group. Always
ILB_STATION one process data word with this module.
Frame for the entire XML file. The obligatory elements of
this frame are ILB_BUS_TERMINAL and ILB_BUS. PD_IN
This area is used by all group<s that use input
ILB_BUS_TERMINAL data. The number of process data words depends
on the group. Always one process data word with
This data area contains information about the module.
this module.
Belonging to this data area:

PD OUT
TERMINAL_TYPE
This area is used by all terminals with output data.
This area contains the module designation, i.e.,
The use of bits is identical with the that in "PD_IN".
always ILB ETH 24 DI16 DIO16-2TX.

NAME
Contains the user-specific station names. The
station name can be modified via SNMP or WBM.

IP_ADDRESS
Contains the IP address of the station.

GROUP_NUMBER
2: DIO and DI

DIAGNOSTIC_REGISTER
Contains the module status represented by all
bits of the I/O diagnostic register.

ILB_BUS
Frame for the existing groups.

ILB_GROUP
Frame for the data of an individual group.

GROUP_TYPE
Contains the terminal type. Possible types are DI
and DIO.

PD_CHANNELS
Number of process data channels in a group. For
digital modules the number of channels is equal to
the number of supported bits. Always 16 bits with
this module.

7046_en_02 PHOENIX CONTACT 20


ILB ETH 24 DI16 DIO16-2TX

Figure 12 Screen for XML data

11 SNMP 11.2 Traps


The ILB ETH 24 DI16 DIO16-2TX module supports the
The ILB ETH 24 DI16 DIO16-2TX module supports SNMP
following traps:
v1 and v2c.
– Cold Start - is transmitted with every restart of the
11.1 MIBs module in version v1 and V2c.
– Authentication - wrong password for SNMP access
The module supports the following MIBs:
– MIB II defined by RFC 1213
– ILB-ETH-24-MIB in version 1.0
For the object descriptions, please refer to the ASN1
descriptions of this product. It can be downloaded at
www.download.phoenixcontact.com.
The password for read access is "public" and cannot be
modified. By default upon delivery, the password for read/
write access is "private" and can be modified at any time.
The same password is used for the web interface, see
page 18.

7046_en_02 PHOENIX CONTACT 21


ILB ETH 24 DI16 DIO16-2TX

12 Monitoring Functions
Monitoring functions with different features are available for monitoring Ethernet communication.
– Process data watchdog (process data monitoring)
– Connection monitoring for Modbus (see "Modbus Connection Timeout" on page 30) and DTI (see "Connection and
Error Monitoring" on page 27).
There are monitoring functions according to the features/functions that need to be monitored. According to the application
requirements the appropriate monitoring function can be activated. By default upon delivery, process data watchdog is
activated.

Monitoring Mechanism Monitoring …


... the Client ... the ... the Ethernet ... Process Data
Application Individual Connection Exchange
Channels
Process data watchdog (process X – X X
data monitoring)
Connection monitoring for Modbus X X X –
and DTI
In the event of an error the system reacts with a fault response. The user determines the required fault response mode.

12.1 Setting the Required Fault Response Mode


The required fault response mode can be set via web-based management by writing to Modbus register 2002, using DTI
byte address 4004, or via the "ETH_SetNet FailMode" function. The following fault response modes are available:

Fault Response Mode Value Function


Reset fault mode 1 The digital outputs are set to "0".
(default)
Standard fault mode 0 All outputs are set to "0".
Hold last state mode 2 All outputs retain their last value.

As this module does not have analog outputs, the behavior in reset fault mode and standard fault mode is
identical.

7046_en_02 PHOENIX CONTACT 22


ILB ETH 24 DI16 DIO16-2TX

12.2 Process Data Watchdog/Process Data – The selected fault response mode is executed.
Monitoring – The NetFail signal is set (the Net Fail LED is red).
By default upon delivery, the process data The reason for setting the NetFail signal is listed in the
watchdog is activated with 500 ms timeout. reason code.
For safety reasons, the user cannot stop the watchdog
once it has been activated. In case the user terminates the
controlling application, there is no watchdog triggering;
when timeout has expired, the NetFail signal is set and the
selected fault response mode is executed. After the
watchdog has performed its task, the outputs are only
enabled again after acknowledgment.

When the error is acknowledged, the watchdog


is restarted. This means that it must be
triggered during timeout, otherwise an error is
detected again.

Configuration of the Process Data Watchdog

Timeout can only be changed if the watchdog


is in "INIT" state. The "INIT" state is present:
– After power-up, as long as process data
exchange has not taken place
– In case of timeout and if fault response has
Figure 13 Configuring process data monitoring in the been activated and if NetFail has not yet
WEB been acknowledged

Process data watchdog timeout can be configured from


Process Data Watchdog Function
200 ms to 65000 ms. Timeout can be set using the web-
A process data watchdog is integrated into the based management, by writing to Modbus register 2000, or
ILB ETH 24 DI16 DIO16-2TX module to avoid uncontrolled using DTI byte address 4000.
setting/resetting of the I/O station outputs in the event of an
error.
If outputs of the stations are set, ensure access of the
controlling process to the station. In the event of an error,
e.g., network line interrupted or function error in the
controlling process, the module can react appropriately. By
default upon delivery, the watchdog is activated with
500 ms timeout. The first write process activates the
process data watchdog. The next write process is expected
during timeout (default: 500 ms). During error-free
operation, the write process is performed during timeout
and the watchdog is restarted (triggered).

Reading calls do not trigger the process data


watchdog.

NET FAIL: If there is no triggering during timeout, an error


occurred. Two responses follow:

7046_en_02 PHOENIX CONTACT 23


ILB ETH 24 DI16 DIO16-2TX

Deactivating the Process Data Watchdog Possible Reasons:


The process data watchdog can only be deactivated if it is DDI_NF_TASK_CREAT_ERR 0x0001
in "INIT" state. For deactivation, the timeout value is set to /* Error when starting a task */
"zero". DDI_NF_LISTENER_ERR 0x0002
P o w e r U p /* Listener task error */
DDI_NF_RECEIVER_ERR 0x0003
/* Receiver task error */
S ta tu s "IN IT "
DDI_NF_ACCEPT_ERR 0x0004
/* Accept function error */
W r ite _ O K /
C le a r N e tF a il DDI_NF_ECHO_SERVER_ERR 0x0005
/* Echo server task error */
DDI_NF_HOST_CONTROLLER_ERR 0x0006
W a tc h d o g /* Host controller task error */
T im e o u t > 0 ?
N e in DDI_NF_DTI_TIMEOUT 0x0007
/* DTI timeout occurred */
DDI_NF_HOST_TIMEOUT 0x0008
J a /* Host timeout occurred */
DDI_NF_USER_TEST 0x0009
/* NetFail set by user */
DDI_NF_CONN_ABORT 0x000A
A C T IV E : /* Connection aborted */
W r ite _ O K
J a DDI_NF_INIT_ERR 0x000B
/* Initialization error */
N e in DDI_NF_DTI_WATCHDOG 0x000C
W a tc h d o g - T im e o u t lä u ft a b
S e t N e t F a il
/* Process data watchdog triggered */
F a u lt R e s p o n s e DDI_NF_MBUS_TIMEOUT 0x000D
6 1 5 6 0 0 2 9
/* Modbus timeout occurred */

Figure 14 Status diagram of the process data watchdog

12.3 Fault Response Acknowledgement


The NetFail signal can be acknowledged using the web-
based management, by writing command 0x0002 to the
command register (Modbus register 2006 or DTI byte
address 4012), or using the "ETH_ClrNet FailStatus"
function.

Reasons for Fault Response


The web-based management, Modbus register 6, DTI byte
address 12, or the "ETH_GetNet FailStatus" service can be
used to request the reasons for fault response mode.

7046_en_02 PHOENIX CONTACT 24


ILB ETH 24 DI16 DIO16-2TX

13 Modbus/TCP Protocol
The module supports a Modbus/TCP server with the 13.4 Modbus Function Codes
following features:
The following function codes are supported:
13.1 Modbus Connections Code No. Function Code
The module supports up to eight connections at the same fc1 Read coils
time. In this way, a connection can quickly be re- fc2 Read input discretes
established This implies that the client can successfully fc3 Read multiple registers
restore an interrupted Modbus connection. fc4 Read input registers
fc5 Write coils
13.2 Modbus Interface
fc6 Write single register
The Modbus interface according to the standard port 502 fc15 Write multiple coils
supports Modbus communication via the
fc16 Write multiple registers
ILB ETH 24 DI16 DIO16-2TX module.
fc23 Read/write registers
13.3 Modbus Conformity Classes
The ILB ETH 24 DI16 DIO16-2TX module supports
Modbus conformity classes 0 and 1.

13.5 Modbus Table


Modbus Modbus Input Modbus Access Function
Register Table Discretes Table Coil Table
(16-Bit Words) (Bits)
0 0-15 – Read only Digital inputs (DIO)
Process data

1 16-32 – Read only Digital inputs (DI)


2 – 0-15 Read/write Digital outputs
3 – – Read only Reserved

4 – – Read only Status register


5 – – Read only I/O diagnostic register
Diagnostics

6 – – Read only NetFail reason


7 – – Read only IBS diagnostic register (for compatibility
with FL IL 24 BK)
8 – – Read only IBS para register (for compatibility with
FL IL 24 BK)

1280 – – Read/write Modbus timeout connection monitoring


Special register

2000 – – Read/write Process data watchdog timeout


2002 – – Read/write Fault response mode
2004 – – Read/write NetFail test (same value as register 6)
2006 – – Read/write Command register

7046_en_02 PHOENIX CONTACT 25


ILB ETH 24 DI16 DIO16-2TX

13.6 Process Data Assignment (Modbus)

Assignment of the Terminal Points to the OUT Process Data Word (Slots 3 to 6)
(Word.bit) view Word Word 2
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Module Slot 6 (IO4) 5 (IO3) 4 (IO2) 3 (IO1)
Terminal point (signal) 2.4 1.4 2.1 1.1 2.4 1.4 2.1 1.1 2.4 1.4 2.1 1.1 2.4 1.4 2.1 1.1
Terminal point (GND) 2.6 1.6 2.3 1.3 2.6 1.6 2.3 1.3 2.6 1.6 2.3 1.3 2.6 1.6 2.3 1.3
Status indicator Slot 6 (IO4) 5 (IO3) 4 (IO2) 3 (IO1)
LED 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1

Assignment of the Terminal Points to the IN Process Data Word (Slots 3 to 6)


(Word.bit) view Word Word 0
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Module Slot 6 (IO4) 5 (IO3) 4 (IO2) 3 (IO1)
Terminal point (signal) 2.4 1.4 2.1 1.1 2.4 1.4 2.1 1.1 2.4 1.4 2.1 1.1 2.4 1.4 2.1 1.1
Terminal point (UI1) 2.5 1.5 2.2 1.2 2.5 1.5 2.2 1.2 2.5 1.5 2.2 1.2 2.5 1.5 2.2 1.2
Terminal point (GND) 2.6 1.6 2.3 1.3 2.6 1.6 2.3 1.3 2.6 1.6 2.3 1.3 2.6 1.6 2.3 1.3
Status indicator Slot 6 (IO4) 5 (IO3) 4 (IO2) 3 (IO1)
LED 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1

Assignment of the Terminal Points to the IN Process Data Word (Slots 7 to 10)
(Word.bit) view Word Word 1
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Module Slot 10 (I4) 9 (I3) 8 (I2) 7 (I1)
Terminal point (signal) 2.4 1.4 2.1 1.1 2.4 1.4 2.1 1.1 2.4 1.4 2.1 1.1 2.4 1.4 2.1 1.1
Terminal point (UI2) 2.5 1.5 2.2 1.2 2.5 1.5 2.2 1.2 2.5 1.5 2.2 1.2 2.5 1.5 2.2 1.2
Terminal point (GND) 2.6 1.6 2.3 1.3 2.6 1.6 2.3 1.3 2.6 1.6 2.3 1.3 2.6 1.6 2.3 1.3
Status indicator Slot 10 (I4) 9 (I3) 8 (I2) 7 (I1)
LED 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1

7046_en_02 PHOENIX CONTACT 26


ILB ETH 24 DI16 DIO16-2TX

14 Device Driver Interface (DDI) 14.1 Connection and Error Monitoring


– ETH_SetDTITimeoutCtrl ( )
The ILB ETH 24 DI16 DIO16-2TX module supports access
via the Device Driver Interface (DDI). – ETH_ClearDTITimeoutCtrl ( )
– ETH_SetNet Fail ( )
A driver for Windows NT and Windows 2000 – ETH_GetNet FailStatus ( )
can be found at
– ETH_ClrNet FailStatus ( )
www.download.phoenixcontact.com. It is
called "Ethernet Driver 2.0. exe". – ETH_SetNet FailMode ( )
Phoenix Contact informs you about drivers for – ETH_GetNet FailMode ( )
other operating systems on request.
14.2 Services for Process Data Monitoring
Using this interface requires the appropriate driver to be
– ETH_ActivatePDinMonitoring ( )
installed on the host. For a detailed description of the
services, please refer to the "Driver Reference Manual for – ETH_DeactivatePDinMonitoring ( )
G4-Based Controller Boards Using PC Bus and Ethernet",
see "Ordering Data" on page 4. 14.3 Services for Ethernet Connection Management

The following services are supported: Services for remote – ETH_InitiateManagement ( )


access to the DDI – ETH_AbortManagement ( )
– DDI_DevOpenNode ( ) – ETH_HardwareReset ( )
– DDI_DevCloseNode ( ) – ETH_EnableHardwareReset ( )
– DDI_DTI_ReadData ( ) – ETH_DisableHardwareReset ( )
– DDI_DTI_WriteData ( )
14.4 Structure of the DTI Area
– DDI_DTI_ReadWriteData ( )
– GetIBSDiagnostic ( ) The special registers can only be accessed
individually with a length of 2 bytes. In this way
The module only supports the process data invalid parameters can be rejected selectively.
channel (DTI). Access to the mailbox channel
(MXI) is not supported and thus rejected with
the corresponding error message.
Byte Address DTI IN DTI OUT Remark
From To Read Access Write Access
00hex 01hex 16 bit IN (DIO) 16 bit OUT (DIO)
Process data

02hex 03hex 16 bit IN (DI) Disabled


04hex 05hex 16 bit OUT (DIO) Disabled Read back output
register

08hex 09hex Status register Disabled


Diagnostics

0Ahex 0Bhex I/O diagnostic register Disabled


0Chex 0Dhex NetFail reason Disabled
0Ehex 0Fhex IBS diagnostic register Disabled For OPC compatibility
10hex 11hex IBS para register Disabled For OPC compatibility

4000dec 4001dec Process data watchdog timeout Process data watchdog timeout
Special register

4004dec 4005dec Fault response mode Fault response mode


4008dec 4009dec NetFail test NetFail test Same value as register
0Chex
4012dec 4013dec Command register Command register

7046_en_02 PHOENIX CONTACT 27


ILB ETH 24 DI16 DIO16-2TX

14.5 Process Data Assignment (DDI)

Assignment of the Terminal Points to the OUT Process Data Word (Slots 3 to 6)
(Byte.bit) view Word Byte 0 Byte 1
Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0
Module Slot 6 (IO4) 5 (IO3) 4 (IO2) 3 (IO1)
Terminal point (signal) 2.4 1.4 2.1 1.1 2.4 1.4 2.1 1.1 2.4 1.4 2.1 1.1 2.4 1.4 2.1 1.1
Terminal point (GND) 2.6 1.6 2.3 1.3 2.6 1.6 2.3 1.3 2.6 1.6 2.3 1.3 2.6 1.6 2.3 1.3
Status indicator Slot 6 (IO4) 5 (IO3) 4 (IO2) 3 (IO1)
LED 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1

Assignment of the Terminal Points to the IN Process Data Word (Slots 3 to 6)


(Byte.bit) view Word Byte 0 Byte 1
Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0
Module Slot 6 (IO4) 5 (IO3) 4 (IO2) 3 (IO1)
Terminal point (signal) 2.4 1.4 2.1 1.1 2.4 1.4 2.1 1.1 2.4 1.4 2.1 1.1 2.4 1.4 2.1 1.1
Terminal point (UI1) 2.5 1.5 2.2 1.2 2.5 1.5 2.2 1.2 2.5 1.5 2.2 1.2 2.5 1.5 2.2 1.2
Terminal point (GND) 2.6 1.6 2.3 1.3 2.6 1.6 2.3 1.3 2.6 1.6 2.3 1.3 2.6 1.6 2.3 1.3
Status indicator Slot 6 (IO4) 5 (IO3) 4 (IO2) 3 (IO1)
LED 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1

Assignment of the Terminal Points to the IN Process Data Word (Slots 7 to 10)
(Byte.bit) view Word Byte 2 Byte 3
Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0
Module Slot 10 (I4) 9 (I3) 8 (I2) 7 (I1)
Terminal point (signal) 2.4 1.4 2.1 1.1 2.4 1.4 2.1 1.1 2.4 1.4 2.1 1.1 2.4 1.4 2.1 1.1
Terminal point (UI2) 2.5 1.5 2.2 1.2 2.5 1.5 2.2 1.2 2.5 1.5 2.2 1.2 2.5 1.5 2.2 1.2
Terminal point (GND) 2.6 1.6 2.3 1.3 2.6 1.6 2.3 1.3 2.6 1.6 2.3 1.3 2.6 1.6 2.3 1.3
Status indicator Slot 10 (I4) 9 (I3) 8 (I2) 7 (I1)
LED 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1

7046_en_02 PHOENIX CONTACT 28


ILB ETH 24 DI16 DIO16-2TX

15 Diagnostic Register
15.1 Status Register
Address: 15 - 4 3 2 1 0
– Modbus: Register 4
– DDI: Word starting with 08hex 1: Short circuit / output overload

Via the Ethernet host controller, e.g., PLC, the user can 1: Short circuit / sensor supply overload
read current diagnostic information from the network 1: Sensor supply US1 missing
interface status word without using a configuration
software. 1: Sensor supply US2 missing

Only those two least significant bits (bit 0 and bit 1) have a Reserved
704601008

function. Bit 2 up to bit 15 are reserved. Figure 15 Assignment of the I/O diagnostic register

– Bit 0 = 0: An error occurred (e.g., a bit in the diagnostic The diagnostic register always indicates the
register is set). current status.
– Bit 0 = 1: No error
– Bit 1 = 0: No NetFail 15.3 NetFail Reason
– Bit 1 = 1: NetFail is present Address:
This results in the following values for the status word: – Modbus: Register 6
– DDI: Word starting with 0Chex
Register Status This register can be used to read the NetFail reason after
Contents setting the NetFail signal. If no NetFail signal is present the
0000hex An error occurred (e.g., a bit in the register is 0. For a list of the reasons, please refer to
diagnostic register is set). Section "Reasons for Fault Response" on page 24.
0001hex No error occurred.
0002hex A NetFail occurred.

The errors are indicated until they are


acknowledged.

15.2 I/O Diagnostic Register


Address:
– Modbus: Register 5
– DDI: Word starting with 04hex
The I/O diagnostic register is used to indicate detailed
information on module diagnostics. The DIA LED is red if a
bit is set here.

7046_en_02 PHOENIX CONTACT 29


ILB ETH 24 DI16 DIO16-2TX

16 Special Register
16.1 Modbus Connection Timeout 16.2 Process Data Watchdog Timeout
Modbus: Register 1280 – Modbus: Register 2000
A monitoring mechanism can be activated for every – DDI: Word starting with 4000dec
Modbus/TCP connection in order for the Setting or reading the timeout value for the process data
ILB ETH 24 DI16 DIO16-2TX module to detect an error in watchdog. The time is specified in milliseconds in the range
the network (e.g., defective cable) or in the client (operating from 200 ms to 65000 ms. A timeout value of "0"
system crash or error in the TCP/IP protocol stack) and deactivates the watchdog, see also page 23.
react accordingly. The monitoring mechanism is activated
via the relevant TCP connection upon the first read or write 16.3 Fault Response Mode
procedure.
– Modbus: Register 2002
To change the timeout value for the relevant TCP
connection, write the new timeout value to the timeout table – DDI: Value starting with 4004dec
to the special address 1280 using functions "fc 6" or "fc 16". Setting or reading the fault response mode. For information
The value of this entry is the value of the timeout table. The on fault response mode settings, please refer to Section
time is specified in milliseconds in the range from 200 ms to "Setting the Required Fault Response Mode" on page 22.
65000 ms.
A timeout value of "0" deactivates the monitoring function. 16.4 Command Register
Values between 1 ms and 199 ms, and values greater than
– Modbus: Register 2006
65000 ms generate exception response 3 (ILLEGAL DATA
VALUE). – DDI: Value starting with 4012dec
The network interface command register can be used to
Connection monitoring with the new timeout transmit commands with basic functions to the module
values is only activated after a Modbus/TCP using the Ethernet host controller, e.g., PLC.
function has been executed on the relevant
TCP connection.
Command Function Code
After the first access by a Modbus/TCP function, all other 0000hex No action
access must be carried out using the entered timeout value. 0002hex NetFail acknowledgement
Otherwise, fault response mode is activated and the
0004hex Diagnostic message acknowledgement
Modbus/TCP connection is disabled.
(I/O error)

© PHOENIX CONTACT 03/2007

7046_en_02 PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany 30