MCQ in Philippine Electrical Code PEC Part 2 REE Board Exam
MCQ in Philippine Electrical Code PEC Part 2 REE Board Exam
MCQ in Philippine Electrical Code PEC Part 2 REE Board Exam
Board Exam
pinoybix.org/2020/10/mcq-in-philippine-electrical-code-part-2-ree-board-exam.html
October 1, 2020
This is the Multiple Choice Questions Part 2 of the Series in Philippine Electrical Code (PEC)
as one of the Electrical Engineering topic. In Preparation for the REE Board Exam make sure
to expose yourself and familiarize in each and every questions compiled here taken from
various sources including but not limited to past Board Exam Questions in Electrical
Engineering field, Electrical Engineering Books, Journals and other Electrical Engineering
References.
1/19
Continue Practice Exam Test Questions Part 2 of the Series
51. For each 2-wire laundry branch circuit, a feeder load of NOT less than ______ shall be
included.
A. 1,800 VA
B. 1,500 VA
C. 2,000 VA
D. 1,200 VA
View Answer:
Answer: Option B
Solution:
52. The computed load for the branch circuit installed to supply exterior signs and outline
lighting shall be computed at a minimum of ______ volt-amperes.
A. 1,200
B. 1,500
C. 1,800
D. 1,000
View Answer:
Answer: Option A
Solution:
D. all of these
2/19
View Answer:
Answer: Option D
Solution:
A building or other structure serve shall be supplied by only one service drop EXCEPT for
B. fire pumps
D. all of these
View Answer:
Answer: Option D
Solution:
55. Air terminals exceeding 600 mm in height shall be supported at a point NOT less ______
of its height.
A. three-fourths
B. two-fifth
C. one-half
D. one-third
View Answer:
Answer: Option C
Solution:
A. Ground wire
3/19
D. Armored cable
View Answer:
Answer: Option D
Solution:
The following are common splicing rules EXPECT one. Which one is this?
View Answer:
Answer: Option D
Solution:
58. Service entrance cables shall be supported by straps or other approved means within
_______ of every service head
A. 300 mm
B. 500 mm
C. 600 mm
D. 400 mm
View Answer:
Answer: Option A
Solution:
A. Grounded
B. Conductor
4/19
C. Service entrance
D. Outlet
View Answer:
Answer: Option D
Solution:
The clearance from the top of a switchboard to a ceiling which is combustible shall NOT be
less than_________.
A. 1,000 mm
B. 800 mm
C. 900 mm
D. 1,250 mm
View Answer:
Answer: Option A
Solution:
In concealed knob and tube wiring, the clearance to be maintained between conductors is
A. 55 mm
B. 45 mm
C. 76 mm
D. 50 mm
View Answer:
Answer: Option C
Solution:
What is the total number of mechanical degrees that a PVC conduit run maybe bent between
pull points (pull boxes, junction boxes or utility boxes)?
5/19
A. 360 degrees
B. 180 degrees
C. 120 degrees
D. 270 degrees
View Answer:
Answer: Option A
Solution:
The sum of the cross sectional area of all conductors in a wireway must not exceed ____
percent of the cross-sectional area of the wireway.
A. 15
B. 20
C. 10
D. 25
View Answer:
Answer: Option B
Solution:
A lighting fixture shall be wired with a flexible lighting cord with a cross section area of NOT
less
A. 0.75 mm2
B. 2.00 mm2
C. 0.50 mm2
D. 1.25 mm2
View Answer:
Answer: Option A
Solution:
6/19
65. RME Board April 1994
A. wet locations
B. hoistways
D. all of these
View Answer:
Answer: Option D
Solution:
A. 75°C
B. 60°C
C. 90°C
D. 110°C
View Answer:
Answer: Option A
Solution:
A. Bonding
B. Interlink
C. Air terminal
D. Counterpoise
View Answer:
Answer: Option D
Solution:
7/19
The use of surface nonmetallic raceway may NOT be used in the following locations
EXCEPT one. Which one is this?
A. In dry locations
D. Where concealed
View Answer:
Answer: Option A
Solution:
69. For installation consisting of not more than two 2-wire branch circuits, the service
disconnecting mains shall be rated NOT less than what rating?
A. 20 A
B. 40 A
C. 30 A
D. 50 A
View Answer:
Answer: Option C
Solution:
70. For a dwelling unit having a floor area not more than 50 square meters shall be permitted
to have a single 20-A, 2- wire branch circuit provided the total load shall NOT exceed how
many volt-amperes?
A. 3,680
B. 3,860
C. 3,080
D. 3,068
View Answer:
Answer: Option A
8/19
Solution:
Flat conductor cable (FCC) system shall NOT be used in the locations enumerated below
EXCEPT one. Which one is this?
B. Damp locations
C. Residential buildings
D. Outdoors
View Answer:
Answer: Option B
Solution:
A run conduit between outlets, between fittings, between outlet and fitting shall not contain
more than the equivalent of _________ quarterbends.
A. 2
B. 4
C. 3
D. 5
View Answer:
Answer: Option B
Solution:
Transformers that contain liquid that will burn shall be installed only in approved vaults and
shall also comply with the following conditions EXCEPT one. Which one is this?
9/19
C. All vent ducts and openings shall be of sufficient areas to reliable explosion pressures
within the vault
D. There shall be a robust door between the vault and any non-hazardous location
View Answer:
Answer: Option D
Solution:
To provide for small appliance in a dwelling unit, the feeder should be computed at
A. 2,400 watts
B. 3,000 watts
C. 1,500 watts
D. 3,600 watts
View Answer:
Answer: Option C
Solution:
A. 2,000 V
B. 1,000 V
C. 3,000 V
D. none of these
View Answer:
Answer: Option A
Solution:
76. The nearest ground terminal shall NOT less than______ from the foundation wall.
A. 760 mm
10/19
B. 800 mm
C. 550 mm
D. 600 mm
View Answer:
Answer: Option D
Solution:
The circuit conductors between the service entrance equipment or isolated generating plant
and the branch circuit overload device or devices.
A. overcurrent protector
B. feeder
C. motor controller
D. disconnecting switch
View Answer:
Answer: Option B
Solution:
78. Conductors shall be securely attached to the buildings using fasteners. Fasteners shall
be spaced NOT more than
A. 760 mm
B. 600 mm
C. 880 mm
D. 900 mm
View Answer:
Answer: Option D
Solution:
79. The minimum diameter of air terminal used at the top of a heavy duty smoke or vent
stacks shall be ____, exclusive of the corrosion protection.
11/19
A. 10 mm
B. 15 mm
C. 13 mm
D. 20 mm
View Answer:
Answer: Option B
Solution:
80. ______ are used on conduits and are located inside and outside of the box.
A. Couplings
B. Bushings
C. Locknuts
D. Washers
View Answer:
Answer: Option C
Solution:
81. No parts of cord connected fixtures, hanging fixtures or pendants shall be located within
a zone measured ______ horizontally from a bathtub rim.
A. 900 mm
B. 1,000 mm
C. 800 mm
D. 700 mm
View Answer:
Answer: Option A
Solution:
A. 100%
12/19
B. 96%
C. 98%
D. 97%
View Answer:
Answer: Option D
Solution:
A. 60°C
B. 85°C
C. 75°C
D. 90°C
View Answer:
Answer: Option C
Solution:
84. Individual open conductors and cables other than service cables shall NOT be installed
within______ of every grade level.
A. 3,100 mm
B. 2,500 mm
C. 3,700 mm
D. 3,000 mm
View Answer:
Answer: Option A
Solution:
A. green
13/19
B. black
View Answer:
Answer: Option D
Solution:
A. industrial
B. commercial
C. both A and B
D. neither A or B
View Answer:
Answer: Option A
Solution:
87. In damp or wet locations, boxes and fittings should be properly placed or insulated to
prevent
C. wiring exposure
D. grounding
View Answer:
Answer: Option B
Solution:
88. Equipment having an open circuit voltage exceeding ____ shall NOT be installed in
dwelling occupancies.
A. 500 V
14/19
B. 300 V
C. 250 V
D. 230 V
View Answer:
Answer: Option B
Solution:
Connected knob and tube wiring conductors shall be rigidly supported on knobs not more
than a certain minimum distance apart. What is this distance?
A. 2,000 mm
B. 1,500 mm
C. 1,300 mm
D. 2,500 mm
View Answer:
Answer: Option C
Solution:
90. Which of the following materials is used to support the conductor in the open wiring
method?
B. insulated nails
C. rosettes
D. split knobs
View Answer:
Answer: Option D
Solution:
A. 100 mm2
15/19
B. 125 mm2
C. 150 mm2
D. 200 mm2
View Answer:
Answer: Option B
Solution:
92. Watercraft’s switchboards shall be provided with a clear working space of at least ____ at
the front.
A. 1,500 mm
B. 1,200 mm
C. 1,600 mm
D. 1,000 mm
View Answer:
Answer: Option D
Solution:
For grounding electrode to which portable or mobile equipment system neutral impedance is
connected, shall be isolated from the ground by at least a certain distance from any other
system or equipment grounding electrode. What is this distance?
A. 4,000 mm
B. 6,000 mm
C. 5,000 mm
D. 3,000 mm
View Answer:
Answer: Option B
Solution:
16/19
A. Steel
B. Iron
C. Aluminum
D. Copper
View Answer:
Answer: Option D
Solution:
95. Incandescent lamp fixtures shall be marked to indicate the allowable wattage of lamps.
The markings shall be permanently installed in letters at least ______ high.
A. 6.0 mm
B. 6.4 mm
C. 6.3 mm
D. 6.5 mm
View Answer:
Answer: Option B
Solution:
96. If the duty cycle of a motor-generator arc welder is 100%, the supply conductors shall
NOT be less than______ of its rated primary nameplate current.
A. 115%
B. 125%
C. 100%
D. 130%
View Answer:
Answer: Option C
Solution:
97. Most wires used in residential house wiring are usually insulated by
A. Asbestos
17/19
B. Cotton
C. Thermoplastic
D. Varnished cambric
View Answer:
Answer: Option C
Solution:
98. Open wiring on insulators shall be permitted for wiring systems of ____ or less.
A. 150 V
B. 240 V
C. 300 V
D. 600 V
View Answer:
Answer: Option D
Solution:
The branch circuit conductors that supply one or more units of data processing systems shall
have an ampacity not less than ____ percent of the total connected load.
A. 150
B. 100
C. 125
D. 200
View Answer:
Answer: Option C
Solution:
100.Communication cable and wires shall have a voltage rating NOT less than _____.
A. 400 volts
18/19
B. 300 volts
C. 600 volts
D. 250 volts
View Answer:
Answer: Option B
Solution: