Conduit Wiring: Section I. Rigid Conduit Uses and Advantages
Conduit Wiring: Section I. Rigid Conduit Uses and Advantages
Conduit Wiring: Section I. Rigid Conduit Uses and Advantages
CHAPTER 5
Conduit Wiring
Conduit wiring provides mechanical protection and electrical safety to persons
and property and provides convenient and accessible ducts for the conductor.
A well-designed electrical raceway system has adequate capacity for future
expansion and is readily adaptable to changing conditions.
MATERIALS
Though the materials used in rigid conduit inches. Larger sizes (up to 6 inches) are avail-
wiring have been outlined in detail in Chap- able for special use in certain commercial
ter 2, the following discussion will review and factory installations.
the advantages of these standard materials
Though conduit is made in dimensions simi-
as well as their limitations.
lar to water pipe, it differs from water pipe in
Rigid conduit (Figure 5-1, page 5-2) has the a number of ways. It is softer than water pipe
same size designations as water pipe. Con- and thus can be bent fairly easily. In addi-
duit smaller than 1/2 inch can only be used in tion, the inner surface is smooth to prevent
finished buildings where extensions are to damage to wires being pulled through it, and
be made under plaster. In these installations, the finish is rust-resistant. Black-enamel
5/16-inch conduit or tubing is permitted. The conduit is used for dry and indoor installa-
size of conduit is determined by the inside tions, and galvanized conduit is used in out-
diameter. For example, 1/2-inch conduit has side installations to provide moisture
an inside diameter of approximately 1/2 inch. protection for the conductors. For wiring
installations in corrosive atmospheres, alu-
Standard conduit sizes used in interior wir-
minum, copper-alloy, or plastic-jacketed con-
ing are 1/2, 3/4, 1, 1 1/4, 1 1/2, 2, and 2 1/2
duit is available.
Conduit Unions. Conduit unions are conduit run. By using unions, conduit may
installed to permit the opening of a conduit be started from two outlets and joined
at any point without sawing or breaking the together at any convenient place in the run.
PROCEDURES
MAKING BENDS tools are not available, you can make bends
Bends in rigid conduit must be made with- using the lever advantage between two fixed
out collapsing the conduit wall or reducing posts or building members.
the internal diameter of the conduit at the
The following procedure (illustrated in
bend. Electricians make most bends as an
Figure 5-2) is one method of making a right-
integral part of the installation procedure.
angle bend in a length of 1/2-inch conduit. If
These are called field bends. The radius of
you are making a 90-degree bend in a length
the curve on the inner edge of any field bend
of conduit at a distance of 20 inches from
must be at least six times the internal diam-
one end, you must—
eter of the conduit for rubber-, braid-, or
thermoplastic-covered conductors and at • Mark off 20 inches from the end of the
least 10 times the internal diameter of the conduit.
conduit for lead-covered conductors. Table • Place the hickey 2 inches in front of the
B-18, page B-17, shows the minimum radii 20-inch mark and bend the conduit
for field bends. A maximum of four quarter about 25 degrees.
bends can be placed in a conduit run
between two openings. Moreover, a 10-foot • Move the bender to the 20-inch mark
length of conduit should have no more than and bring the bend up to 45 degrees.
three quarter bends. • Move the bender 1 inch behind the 20-
Factory-made bends are available as an inch mark and bring the conduit up to 70
option rather than bending conduit on the degrees.
job. However, these bends are not commonly • Move the bender back 2 inches behind
used because of the increased costs inherent the 20-inch mark and bring the bend up
in the additional cutting and threading that to 90 degrees.
is required and the additional couplings
that must be used. You can make conduit bends more accu-
rately if you use chalk to draw the contour
Conduit up to and including 3/4 inch is usu- of the bend on the floor, and then match the
ally bent with a hand conduit bender called bend in the pipe with the chalk diagram as
a hickey as shown in Figure 5-2, page 5-4. you form the bend. You will usually use a
This hickey can be slipped over the conduit. hydraulic bender to bend conduit in excess
Conduit-bending forms are also available as of 1 inch.
built-in units of pipe-vise stands. If these
Hickey
Steps in making a
90 ° bend
20”
Offset bend
30 ° Place
arrow
opposite
6” 30 ° your
marks.
3”
30 °
30 ° 3”
Step 4. Screw the bushings tightly onto the For efficient and safe operation, wire pulling
conduit ends in the boxes. (Bushings have is generally a two-man procedure. One
smooth surfaces on their inside diameter to electrician pulls the conductors through the
ensure damage-free conductor installation.) conduit, while the other feeds the conduc-
tors into the conduit. In this operation, take
Step 5. Tighten the locknuts against the
care in feeding and pulling the wires so that
boxes so that the teeth will dig into the
they maintain their same relative position
metal sides of the boxes. You can do this by
in the conduit throughout the run length,
driving a drive punch against one of the
thus avoiding insulation injury. For ease of
locknut lugs and forcing the locknut to move
operation, you may rub a wire lubricant,
on the threaded conduit against the box.
such as powdered soapstone, on the conduc-
Step 6. Fasten the box securely to the build- tors or blow the lubricant into the conduit.
ing after you have made all the box connec- In intricate runs, you may perform wire
tions. pulling in sections between boxes. This pro-
cedure requires a large amount of additional
PULLING WIRE splicing to be made in the boxes and
When installing boxes and conduit runs, pull requires that you take more time in wiring.
the conductor wires into the conduit. For The preferred practice in wire pulling is to
short runs with few wires, you can pair con- pull the conductors from the source through
ductors and push them through the conduit to the last box in the conductor run. Make
run from box to box. When the conduit run loops that extend about 8 inches from the
has several bends and more than two con- box openings for each conductor that is to be
ductors, you must use a fish tape to pull wire. tapped or connected to a device in the box. If
After baring the conductor ends of insulation, conductors are not to be tapped, pull them
connect them to the fish tape. Tape the conduc- directly through the box to their connection.
tor junction to the fish tape to preclude damag-
ing the conduit interior and existing USING SPLICES
conductors in the conduit. Taping also Wire splices in conduit installations are not
compacts and strengthens the joint to ensure under tension; therefore, you can use a
easier pulling. (See Figure 5-3.) simple pigtail splice that is carefully made
to obtain a good electrical joint. Do not make
any wire splices that will be concealed in the conduit and could easily be a source of elec-
conduit runs. This requirement is necessary trical failure.
because splices reduce the pulling area in a
CIRCUITING
LAYOUT the ends of the wire insulation may be
Follow the directions and procedures in painted to obtain proper color coding when
Chapter 3 for layout and circuiting of the colored insulation is not available. They
devices in a conduit installation. The avail- may also be identified by the use of wire
ability of different sizes of conduit, along code markers.
with their varying conductor capacities,
makes the wiring installation for conduit CONDUIT CAPACITY
somewhat different from that of the open or Cable wiring, described in Chapter 4, is nor-
cable type. For example, where cable instal- mally limited to two or three standard combi-
lation requires several runs in a particular nations of wire sizes. Conduit, however, has
location, a conduit installation would use a the capacity to accommodate several conduc-
single conduit with multiple conductors. tors in one run. Table B-19, page B-18, lists
Consequently, conduit layouts and runs the maximum number of conductors of a cer-
should be planned to use the minimum tain gauge that can be inserted in the vari-
amount of conduit possible and also to keep ous sizes of conduit used in interior wiring.
the conductor runs to each outlet short For example, the table shows that six No 14
enough to maintain a low voltage drop. wires would require the installation of a 3/4-
inch conduit run. In many installations, it is
CONDUCTOR CONNECTION necessary to use more than one wire size in a
No exceptions to the standard color coding conduit run. In such cases, the conductors
of wires, as outlined in the other systems, cannot have a combined or cross-sectional
are permitted in conduit wiring. All load uti- area equal to more than the allowable per-
lization devices (fixtures and receptacles) cent of cross-sectional area of conduit as
operating at line-to-neutral voltage in a shown in Table B-20, page B-18.
grounded neutral system must be connected
Table B-21, page B-19, lists the percent of
to both a white and a black (or substitute
conduit cross-sectional area in square inches
color) wire. The white wire is always the
available for conductor use. For example, if
grounded neutral wire. Black wires are the
three No 10, Type R, and four No 8, Type R,
hot leads that are fused and connected to
conductors are to be inserted in a conduit,
the switch when controlling power to a lamp
their combined cross-sectional area obtained
holder or an outlet. Red, blue, and orange
from Table B-22, page B-19, is 0.4420 square
insulated wires can be used as substitutes
inch (3 x 0.0460 + 4 x 0.0760). The proper size
for black wire when wire combinations are
of conduit for this installation is 1 1/4 inches
combined in a conduit or a circuit. Never
per Table B-21. You can find this by first
connect the white wire to a black or substi-
looking for the total area in column 7. You
tute-color wire. You must not fuse or switch
will see that 0.4420 lies between 0.34 square
the white wire except in a multipole device
inch (for 1-inch conduit) and 0.60 square
that opens all conductors of the circuit simul-
inch (for 1 1/4-inch conduit). The 1-inch con-
taneously. A green insulated conductor
duit is too small, so you would use the 1 1/4-
denotes a wire used to provide an auxiliary
inch size.
equipment ground. As an expedient measure,
BENDS
Use extreme care when bending metallic that you can use to check the depths of offset
tubing to avoid kinking the pipe or reducing bends.
its inside area. When using thermoplastic-
covered conductors, the radius of the curve OPERATION
of the inner edge of any field bend must be at When making a 90-degree bend, place the
least six times the internal diameter of the conduit on a level surface and hook the end
tubing. When using lead-covered conductors, of the proper-size tube bender under the
it must be at least 10 times the interior diame- conduit's stub end. Using a steady and con-
ter of the tubing. Table B-18, page B-17, tinuous force, firmly hold the conduit and
shows the minimum radii for field bends. bender (with the bending groove over the
conduit), push down on the handle, and step
CONSTRUCTION on the footstep to bend the conduit to the
The thin-wall conduit bender (Figure 5-5) desired angle. To make a 45-degree bend in
has a cast-steel head that is attached to a this manner, move the bending tool until the
steel pipe handle that is approximately 4 handle is vertical. For accurately bending
feet long. It is used in the field to form thin- conduit stubs, place the bender at a prede-
wall conduit into standard and offset bends. termined distance from the end of the con-
Benders are made for each size of conduit; duit. This distance is equal to the required
therefore, use them only on those sizes for stub dimension minus an amount commonly
which they are designed. Each size bends called a take-up height. The take-up height
the conduit to the recommended safe radius. is based on a constant allowance determined
Use the projection on the head of the bender, by the bending radii for various-size con-
sometimes called a foot step, to steady the duit. The take-up height is 5 inches for 1/2-
bender in operation and reduce the pressure inch conduit, 6 inches for 3/4-inch conduit,
required on the handle. The numbers cast and 8 inches for 1-inch conduit.
on the bender shaft are inch measurements
Lip or hook
18” stub
Bender arrow
Footstep
Take-up
mark
Bender
star
INSTALLATION
You may cut thin-wall conduit with a hack-
saw or a special thin-wall cutter. As with DANGER
rigid conduit, you should also ream the
Avoid loosening the conduit from
sharp edge in thin-wall tubing after cutting
to prevent premature wire damage. Exposed
the fittings because it could cause
thin-wall conduit is supported in a similar a loose connection, a short circuit,
manner and with the same type of supports or an electrical fire at the point of
used with rigid conduit. Since there is no wire and conduit contact. A
positive link between the couplings, box mechan-ically loose conduit joint
connectors, and thin-wall conduit, ensure will not maintain the ground
that each conduit joint is electrically and continuity required in all electrical
mechanically secure. Insert all conduit ends wiring installation. This could also
into the fittings until they touch the inner create an operating hazard for
limiting edges. Then, firmly tighten the fit- Army personnel.
tings so that they securely grip the conduit
walls.
MATERIALS
Flexible metal conduit, generally called deteriorative effect on the wire insulation.
Greenfield, resembles armored cable in This metal conduit has a thermoplastic
appearance but is more adaptable than cable outer-sheath covering similar to that used
because various sizes and numbers of wires on Type T wire, the characteristics and uses
can be pulled into it after it is installed. You of which are detailed in Table B-2, pages B-2
may use plastic-covered Greenfield when the through B-4. Figure 5-6, page 5-12, shows
internal conductors are exposed to oil, gaso- flexible conduit and the various fittings
line, or other materials that have a available.
INSTALLATION
Flexible conduit installation is similar to separate grounding wire along with the cir-
that for thin-wall conduit except that Green- cuit conductors.
field must be supported more frequently. Its
prohibitive cost limits its use to connections BENDING AND SUPPORTING
between rigid wiring systems and movable Despite its flexibility, runs of flexible con-
or vibrating equipment such as motors or duit between boxes and fittings must not
fans. It may also be installed where the con- bend more than the equivalent of four quar-
struction requires a conduit bend that is dif- ter turns. This conduit must be supported
ficult or impossible to make. with a conduit strap within 12 inches of
every box or fitting and at intervals no
GROUNDING longer than 4 1/2 feet.
Because of restrictions, you must ground
most flexible conduit systems by running a
USES
Many types of nonmetallic conduit are avail- try to substitute PVC irrigation pipe for
able, but schedule 40 polyvinyl chloride schedule 40 PVC conduit; look for the insig-
(PVC) is the one most electricians use. It is a nia of an electrical materials testing labora-
rigid, heavy-walled, flame-retardant, heat- tory. You can use nonmetallic conduit with
and sunlight-resistant conduit. It may be metal or nonmetallic boxes, but the
used in wet or dry locations, in walls, in ceil- nonmetallic boxes are not the same as those
ings, and above or below the ground. Do not used with Type NMC cable.
WIRING
Nonmetallic conduit does not constitute a separate grounding wire with the circuit
grounded system, so you must run a conductors.
TRIMMING
After cutting PVC, trim the ends inside and edges that might damage conductor insula-
out with a pocketknife to remove any rough tion.
BENDING
Bends in PVC are made by heating the con- your runs so that no piece of conduit
duit in a special infrared heater until it is between fittings bends more than the equiv-
soft. Do not try to heat PVC with a torch alent of four quarter turns.
because you will char the conduit. Design
JOINING
PVC comes in 10-foot lengths, each one with cement. Male and female adapters are avail-
a coupling. Glue the conduit together with able for transitions to other types of conduit
gray conduit cement; do not use water-pipe and for box connections.