HVX Ags531301-01 01

Download as pdf or txt
Download as pdf or txt
You are on page 1of 52

Medium Voltage Switching Devices

HVX
Vacuum circuit-breaker 12–24 kV

Assembly
Operation
Maintenance
No. AGS 531 301-01
Edition 11/2018

Released for Manufacturing


www.schneider-electric.com Printed on 2019/04/25
Schneider Electric
35, rue Joseph Monier
92500 Rueil-Malmaison - France
( +33 (0)141297000
www.schneider-electric.com

© Schneider Electric 2018


All rights reserved to this technical manual.
Reproduction and making available of this technical manual, or extracts, to third parties are prohibited. Only integral reproduction
of this technical manual is permitted with the written permission from Schneider Electric.
Electronic copies in e.g. PDF-format or scanned version have the status “for information only” .
The only valid version of this technical manual is always enclosed directly to the product in question by the factory.

Released for Manufacturing


Printed on 2019/04/25
HVX Content

Remarks on this manual ............................................................................. 4


Purpose and target group ........................................................................................... 4
Reference documents ................................................................................................ 4
Terms and symbols used ............................................................................................ 4
Abbreviations used ..................................................................................................... 4
Any questions or suggestions?................................................................................... 4

1 Safety Provisions .............................................................................. 5

2 Variants and technical details .......................................................... 6


2.3 Dimensions ................................................................................................... 10
2.4 Applied standards ......................................................................................... 10
2.5 Environmental and operating conditions ....................................................... 10
2.6 Nameplate ......................................................................................................11
2.7 Technical data of electrical control and operating devices ............................ 12
2.8 Intended use ................................................................................................. 14
2.9 Disposal after the end of service life ............................................................. 14

3 Packaging, transport, storage........................................................ 15


3.1 Shipping units................................................................................................ 15
3.2 Transport ....................................................................................................... 16
3.3 Delivery ......................................................................................................... 16
3.4 Storage.......................................................................................................... 16

4 Assembly ......................................................................................... 17
4.1 Safety provisions and instructions for assembly ........................................... 17
4.2 Transport using a crane ................................................................................ 17
4.3 Mechanical assembly of the fixed version HVX-F ......................................... 19
4.4 Earth terminal ................................................................................................ 22
4.5 Connecting conductor bars ........................................................................... 23
4.6 Mounting the circuit-breaker HVX-E (truck-type) .......................................... 25
4.7 Connecting the control lines .......................................................................... 27

5 Commissioning ............................................................................... 29
5.1 Final steps ..................................................................................................... 29
5.2 Checking switching functions and interlocks ................................................. 29
5.3 Checks for the circuit-breaker HVX in conjunction with panels/switching
cells ............................................................................................................... 30

6 Operation ......................................................................................... 31
6.1 Operator interface ......................................................................................... 31
6.2 Operation accessories .................................................................................. 33
6.3 Interlocks ....................................................................................................... 34
6.4 Operating specifications ................................................................................ 35
6.5 Charging the energy storing device .............................................................. 36
6.6 Switching operations ..................................................................................... 37
6.7 Position indicators on circuit-breaker and possible operating sequences..... 37
6.8 Moving truck into service / disconnected position ......................................... 38

7 Maintenance..................................................................................... 40
7.1 Safety provisions ........................................................................................... 40
7.2 Maintenance and maintenance specifications .............................................. 40
7.3 Cleaning insulating components ................................................................... 41
7.4 Avoiding condensation .................................................................................. 41
7.5 Corrosion protection ...................................................................................... 41
7.6 Replacement of components ........................................................................ 41
7.7 Lubrication instructions ................................................................................. 42
7.8 Maximum admissible numbers of breaking operations of vacuum
chamber ........................................................................................................ 46

8 Annex ............................................................................................... 47
8.1 Auxiliary products .......................................................................................... 47
8.2 Treatment of firmly screw-connected contact surfaces ................................. 47
8.3 Specifications for screw connections ............................................................ 48

Released for Manufacturing


AGS 531 301-01 | Edition 11/2018 Printed on 2019/04/25 3
HVX Remarks on this manual

As our products are subject to continuous further development, we reserve the right
to make changes regarding standards, illustrations and technical data.
All dimensions specified in this manual are in millimeters.

Purpose and target group


This Technical Manual describes transport, assembly, operation and maintenance
of the series HVX vacuum circuit-breakers. It is exclusively intended for specialist
electricians who have been certified for the HVX series (training certificate).
This Technical Manual is an integral part of the product and must be kept accessible
at all times to persons performing assembly, operation of or maintenance on the
circuit-breaker. If the circuit-breaker is sold to new owners, they must receive this
document along with the switching device.
This Technical Manual cannot describe every imaginable individual case or every
customer-specific version of the product. For information which is not included in this
manual, please contact the manufacturer.

Reference documents
The following additional documents must be complied with:
■ Purchase agreement with the stipulations regarding the switch-specific equip-
ment and the legal details
■ Switch-specific circuit diagrams and documentation
■ Project notes regarding the HVX circuit breaker
■ For assembly and operation of the circuit-breaker, the operating manual of the
switchgear in which it is operated must be complied with.

Terms and symbols used


This manual uses certain terms and symbols. They warn about dangers or provide
important information which must be complied with at all costs so as to avoid danger
and damage:

The addition of this symbol either to a “Danger” or “Warn-


ing” safety label indicates that an electrical hazard exists
which will result in personal injury if the instructions are
not followed.

This is the safety alert symbol. It is used to alert you to


potential personal injury hazards. Obey all safety messages
that follow this symbol to avoid possible injury or death.

INFORMATION-ADVICE
We draw your attention on this particular point.

Abbreviations used
HVX-F: HVX circuit-breaker for fixed mounting
HVX-E: HVX circuit-breaker for truck-mounting
U r: Rated voltage
Ir: Rated current
Isc: Rated short-circuit breaking current

Any questions or suggestions?


Do you have any questions or suggestions regarding this manual, or do you require
further information?
We always strive to provide you with the best-possible information for optimum, safe
use of our products. Thus, do not hesitate to contact us if you have any recommen-
dations, amendments or proposals for improvement.

Released for Manufacturing


4 Printed on 2019/04/25 AGS 531 301-01 | Edition 11/2018
HVX 1 Safety Provisions

The work described in this manual may only be performed by specialist electricians
who have proved their experience with the HVX series and the applicable safety
provisions.
Please read the whole manual carefully before working on the circuit-breaker.

Applicable standards ■ High-voltage switchgear and control gear, part 100: AC circuit-breaker
and regulations: (IEC 62271-100)
■ The locally applicable accident prevention, operating and work instructions
must be complied with.
■ Installation: IEC 61936-1/HD 637 S11
■ Operation of electrical equipment: EN 50110-11
1
The national standards applicable in the country where the equipment is to be
installed must be complied with.

Before performing work on the circuit-breaker, it is essential that you comply with the
following instructions:

DANGER
DANGER indicates a hazardous situation which, if not avoided,
will result in death or serious injury.

WARNING
WARNING indicates a hazardous situation which, if not avoided,
could result in death or serious injury.

CAUTION
CAUTION indicates a hazardous situation which, if not avoided,
could result in minor or moderate injury.

NOTICE
NOTICE is used to address practices not related to physical injury.

Behaviour in case of incidents In case of fire or of internal faults, toxic and caustic decomposition products may be
or accidents produced. Comply with the locally applicable accident and safety provisions.
In case of personal injury, take first-aid measures or cause them to be taken.

Released for Manufacturing


AGS 531 301-01 | Edition 11/2018 Printed on 2019/04/25 5
HVX 2 Variants and technical details

2.1 Vacuum circuit-breaker HVX-E (truck-mounted version)

Rated voltage Ur [kV] ≤ 12


Rated lightning
[kV] 75
impulse withstand voltage Up
Rated power
[kV] 28
frequency withstand voltage Ud
Rated normal current Ir [A] ≤ 1250
Rated short-circuit breaking
[kA] ≤ 25
current Isc
Rated short-time current Ik (3 s) [kA] ≤ 25

Rated frequency fr [Hz] 50/60


approx.
Weight (without packaging) [kg]
135

Rated voltage Ur [kV] ≤ 24


Rated lightning
[kV] 125
impulse withstand voltage Up
Rated power
[kV] 50
frequency withstand voltage Ud
Rated normal current Ir [A] ≤ 2500
Rated short-circuit breaking
[kA] ≤ 40
current Isc
Rated short-time current Ik (3 s) [kA] ≤ 40

Rated frequency fr [Hz] 50/60


approx.
Weight (without packaging) [kg]
160

Fig. 1
Models of the vacuum circuit-breaker HVX-E
1 Moving contacts 6 Nameplate
2 Vacuum interrupter chambers 7 Handles
3 Rollers 8 Operator interface
4 Truck for PI-, PIB- and PIX panels 9 Drive casing
5 Insertion opening for crank to move 10 Low-voltage connector for
the circuit-breaker into its discon- control lines
nected/service position

Released for Manufacturing


6 Printed on 2019/04/25 AGS 531 301-01 | Edition 11/2018
HVX 2 Variants and technical details

1
12
Rated voltage Ur [kV] ≤ 17.5
2 11
Rated lightning
10 [kV] 95
impulse withstand voltage Up
3 Rated power
9 [kV] 38
frequency withstand voltage Ud
8 ≤ 3150
Rated normal current Ir [A]
40001
Rated short-circuit breaking
[kA] ≤ 50
current Isc
4 Rated short-time current Ik (3 s) [kA] ≤ 50
7
Rated frequency fr [Hz] 50/60

6a approx.
5
Weight (without packaging) [kg]
330

1 with fan in PIX standard panel

1
12
11
Rated voltage Ur [kV] ≤ 17.5
2
Rated lightning
10 [kV] 95
impulse withstand voltage Up
3 9 Rated power
[kV] 38
8 frequency withstand voltage Ud
≤ 3150
Rated normal current Ir [A] 40002
16 50002
15 Rated short-circuit breaking
[kA] ≤ 50
4 14 current Isc
7 Rated short-time current Ik (3 s) [kA] ≤ 50
13
6b Rated frequency fr [Hz] 50/60
approx.
5 Weight (without packaging) [kg]
135

2 with fan in PIX High panel

Fig. 2
Models of the vacuum circuit-breaker HVX-E
1 Pole partitions 10 Operator interface
2 Moving contacts 11 Drive casing
3 Vacuum interrupter chambers 12 Low-voltage connector for
4 Press rod (transfer of ON/OFF control lines
switching movement) 13 Slide for opening the insertion
5 Transport rollers opening (7) for racking the truck in
6a Truck für PIX panels and out manually
6b Truck für PIX High panels 14 Lever for locking/unlocking the
7 Insertion opening for crank to move truck in the panel
the circuit-breaker into its discon- 15 Position indicator - truck in service
nected/service position position
8 Nameplate 16 Position indicator - truck in discon-
9 Handles nected position

Released for Manufacturing


AGS 531 301-01 | Edition 11/2018 Printed on 2019/04/25 7
HVX 2 Variants and technical details

2.2 Vacuum circuit-breaker HVX-F (fixed version)

Rated voltage Ur [kV] ≤ 12


8
Rated lightning
[kV] 75
impulse withstand voltage Up
7 Rated power
[kV] 28
frequency withstand voltage Ud
2 Rated normal current Ir [A] ≤ 1250
6 Rated short-circuit breaking
[kA] ≤ 25
current Isc
3 5 Rated short-time current Ik (3 s) [kA] ≤ 25
4
Rated frequency fr [Hz] 50/60
approx.
Weight (without packaging) [kg]
135

8
Rated voltage Ur [kV] ≤ 24
7 Rated lightning
[kV] 125
impulse withstand voltage Up
Rated power
[kV] 50
2 frequency withstand voltage Ud
3 Rated normal current Ir [A] ≤ 2500
6
Rated short-circuit breaking
[kA] ≤ 40
current Isc
Rated short-time current Ik (3 s) [kA] ≤ 40
5
4
Rated frequency fr [Hz] 50/60
approx.
Weight (without packaging) [kg]
160

Fig. 3
Models of the vacuum circuit-breaker HVX-F
1 Low-voltage connector for 4 Drive mechanism for pole sections
control lines 5 High-voltage connection, bottom
2 Front control panel (not visible in 6 Vacuum interrupter chambers
this illustration) 7 High-voltage connection, top
3 Drive casing 8 Pole section

Released for Manufacturing


8 Printed on 2019/04/25 AGS 531 301-01 | Edition 11/2018
HVX 2 Variants and technical details

1
9 Rated voltage Ur [kV] ≤ 17.5
2 8 Rated lightning
[kV] 95
impulse withstand voltage Up
7
Rated power
[kV] 38
frequency withstand voltage Ud
3 6
3150
5 Rated normal current Ir [A]
40001
Rated short-circuit breaking
[kA] ≤ 50
current Isc
Rated short-time current Ik (3 s) [kA] ≤ 50

Rated frequency fr [Hz] 50/60


4
approx.
Weight (without packaging) [kg]
230

1 with fan (available on request from the manufacturer

Fig. 4
Models of the vacuum circuit-breaker HVX-F
1 Pole partitions
2 Conductor bar terminal
3 Vacuum interrupter chambers
4 Press rod (transfer of ON/OFF switching movement)
5 Nameplate
6 Handles
7 Operator interface
8 Drive casing
9 Low-voltage connector for control lines

Released for Manufacturing


AGS 531 301-01 | Edition 11/2018 Printed on 2019/04/25 9
HVX 2 Variants and technical details

2.3 Dimensions
The dimensions of the individual HVX variants are specified in the selection list HVX.
This document or additional customized dimensional drawings are available on
request.

2.4 Applied standards


Series HVX circuit-breakers are
■ type-tested
■ dimensioned for indoor installation

HVX series circuit-breakers


Designation IEC standard EN standard
meet the following standards
and regulations: High-voltage switchgear and controlgear -
Part 1: Common specifications IEC 62271-1 EN 62271-1

Circuit-breaker IEC 62271-100 EN 62271-100


Disconnector truck IEC 62271-102 EN 62271-102
Regarding the switching capacity and the insulation level, the series HVX complies
with the following ANSI specifications1:
ANSI C37.04
ANSI C37.06
ANSI C37.09
1 other standards available on request

Type approval of vacuum The vacuum interrupter chambers have been approved by the X-Ray Ordinance
interrupter chambers acc. to. (RöV) of the Federal Republic of Germany up to a maximum voltage amounting to
the rated short-time power-frequency voltage (rated power frequency withstand volt-
RöV
age) defined by DIN VDE/IEC. Thus, they satisfy the conditions for operation exempt
of approval up to the voltage in question according to the X-Ray Ordinance (RöV).

2.5 Environmental and operating conditions


HVX circuit-breakers may only be operated under normal operating conditions acc.
to IEC 62271-1. Operation under conditions deviating from these is only admissible
upon consultation with and with the written approval of the manufacturer.

(Ambient conditions in accordance with IEC 62271-1)


Temperature class "Minus 5 indoors”1
Min./max. ambient temperature °C –5/+401
Average value over 24 hours °C ≤ 351
mean rel. air humidity: 24 hour/1 month % ≤ 95/≤ 90
Installation altitude above sea-level m ≤ 10001
1 other values available on request

Released for Manufacturing


10 Printed on 2019/04/25 AGS 531 301-01 | Edition 11/2018
HVX 2 Variants and technical details

2.6 Nameplate
The type designation on the nameplate (Fig. 5) specifies essential technical data.

1 Type HVX 12–25–08–F No. TH242884 2010 4


IEC 62271–100 / 2001 IEC 60056 / 1987
Ur 12 kV Ir 800 A fr 50 Hz E1
2 Isc 25 kA Ic 25 A tk 3 s C1
Up 75 kV 0–0,3s–CO–15s–CO M2

Made in .......................
AGSH30799-02

Fig. 5
Nameplate
1 Type designation
2 Technical data
3 Serial number
4 Year of construction

The following example shows the composition of the type designation:

HVX 12 - 25 - 08 - F

Series HVX

Rated Voltage 12 kV

Rated short-circuit breaking current 25 kA

Rated normal current 800 A

F: for fixed installation


E: truck-mounted

When submitting enquiries to the manufacturer or ordering spare parts, the following
information is required:
■ Type designation
■ Serial number
■ Year of construction

Released for Manufacturing


AGS 531 301-01 | Edition 11/2018 Printed on 2019/04/25 11
HVX 2 Variants and technical details

2.7 Technical data of electrical control and operating


devices
The circuit-breaker (Q0) and the truck versions (Q1) have been designed on princi-
ple for manual operation. The drive mechanisms can be equipped, depending on the
specific customer's model, with additional electrical control and operating devices.
These are defined in the switch-specific circuit diagram (see separate documenta-
tion).
Component fitting options:
■ Motor (M1)
– for charging the energy-storing device
– HVX-E: electric actuation of the disconnector truck
■ Shunt closing release (F2)
– 1 pce.
■ Shunt tripping coil (F11/F12/F13)
– 3 ea. max.
■ Secondary release (transformer-operated release) (F31/F32/F33)
– 3 ea. max.
■ Undervoltage release (F4)
– 1 pce.
■ Blocking coil (Y1)
– Blocking coils prevent the circuit breaker from being closed and opened
via the push-buttons “ON“ or “OFF“, as well as manual actuation of the
disconnector truck.
– If the rated supply voltage has failed or is shut off, all blocking coils are in
"blocked" position.
■ Auxiliary switch for circuit-breaker ON/OFF position (S11/S12/S13)
– Auxiliary switches are always actuated directly by the switch shaft via an
intermediate linkage. Their position always corresponds to that of the main
contacts. The circuit breaker is equipped as standard with S11 / S12 auxil-
iary switches, as option S13.
– The switching functions have been set in the factory according to the wir-
ing diagram.
■ Micro switch actuated by energy-storing device (S2)
■ Micro switch actuated by ON/OFF push-button (S41/42)
■ Micro switch actuated by OFF pushbutton (S43)
■ Micro switch actuated by truck in intermediate position or by crank being in-
serted (S6)
The circuit-breaker (Q0) and the truck versions (Q1) can be equipped with ad-
ditional micro switches, depending on customers' design.
■ Anti-pumping relay (K01)
– If an ON and OFF command is simultaneously and permanently present
at the circuit-breaker, the latter returns to its initial position after closing. It
remains in this initial position until the ON command is issued again. This
prevents continuous closing and opening (“pumping”).
■ Terminal strip (X01)

Released for Manufacturing


12 Printed on 2019/04/25 AGS 531 301-01 | Edition 11/2018
HVX 2 Variants and technical details

Overview of rated
Overview of rated supply voltages
supply voltages
Direct voltage DC [V] 24 48 60 110 125 220

Alternating voltage AC [V] (110)/120 (220)/230

Technical data of the electrical


releases and motors Power consumption [W]
Solenoids / motor
DC [W]/AC 50/60 Hz [VA]
Rated normal current [A] ≤2500 >2500
Closing release ≤ 250

Opening release ≤ 250

Undervoltage release approx. 12

Motor for energy-storing device approx. 100 approx. 150

Motor for disconnector truck approx. 120 <200

Secondary release approx. 12 (AC)


Information about the power consumption of solenoids and the motor is available
from the manufacturer. The supply voltage data is required to this effect.

Times for solenoids and motor


Minimum command time “OFF“ el. tripping [ms] 20

Minimum command time “ON“ el. tripping [ms] 20

Motor charging time for energy storing device [s] ≤ 12

Technical data of the


auxiliary switches on the Rated supply DC [V] AC [V]
circuit-breaker voltage [V] ≤ 48 125 220 120 230
Switching capacity [A] 10 3.8 1 10

Rated short-time current 250 A / 3 s

Time constant T = L/R [ms] 10 20 –

Rated continuous current [A] 15 –

Technical data of auxiliary


switches on the disconnector Rated supply DC [V] AC [V]
truck for PIX High panels voltage [V] 24 48 60 110 220 120 230
Switching capacity [A] 8 4 3 2 1 10

Rated short-time current 100 A/30 ms

Time constant T = L/R [ms] ≤ 20

Rated continuous current [A] 10

Released for Manufacturing


AGS 531 301-01 | Edition 11/2018 Printed on 2019/04/25 13
HVX 2 Variants and technical details

2.8 Intended use


Series HVX vacuum circuit-breakers are exclusively intended as switching units in
air-insulating medium-voltage switchgear. They may only be used in the scope of the
specified standards and the switchgear-specific technical data. Any other utilization
constitutes improper use and may result in dangers and damage.

Liability Disclaimers The manufacturer shall not be held responsible for damage which occurs if
■ instructions in this manual are not complied with,
■ the circuit-breaker is not operated according to its intended use (Chapter 2.8)
■ the circuit-breaker is assembled, connected or operated improperly,
■ accessories or spare parts are used which have not been approved by the
manufacturer,
■ the circuit-breaker is converted without the manufacturer’s approval, or if inad-
missible parts are attached.

2.9 Disposal after the end of service life


A material and recycling data sheet is available for disposal of the vacuum circuit-
breaker unit at the end of its service life; this can be provided on request.
Disposal is performed by the manufacturer’s Service Center as a service subject to
a fee.

Released for Manufacturing


14 Printed on 2019/04/25 AGS 531 301-01 | Edition 11/2018
HVX 3 Packaging, transport, storage

3.1 Shipping units


■ The conditions and types of transport have been stipulated in the contract
details. The type of packaging depends on the type of transport and the storage
conditions.
■ The circuit-breakers are delivered ready for connection. The accessories are
included.

Packaging ■ If packed exclusively for truck transport, the circuit-breakers are delivered,
depending on their outside dimensions, either
– in cardboard boxes and delivered on a pallet (Fig. 6),
– directly fixed to the pallet and packed in PE protective film,
– delivered in wooden crates with PE protective film (Fig. 7).
■ For sea transport, the units are packed in sealed aluminium foil with desiccant
and in a closed wooden case with tightly closed wooden base (also for con-
tainer transport).
■ In case of air transport, the panels are packaged in wooden crates with a
protective PE film hood (dust protection) or in wooden crates, also with closed
wooden bases, however without protective hoods (dust protection, Fig. 7).

Important:
The weight of the entire transport unit is indicated on the packaging.

Fig. 6 Fig. 7
Packed in cardboard box on a pallet Packed in a wooden case

Released for Manufacturing


AGS 531 301-01 | Edition 11/2018 Printed on 2019/04/25 15
HVX 3 Packaging, transport, storage

3.2 Transport
■ Transport using a forklift truck:
Move packing unit only complete with pallet. Move the forks completely under
the whole pallet. The circuit-breaker must be fixed safely on the pallet.

3.3 Delivery
■ Handle shipping units carefully when unloading and unpacking them.
■ Shipping units must be checked upon receipt. Any damage which may have
occurred in transit must be recorded and reported to the manufacturer immedi-
ately.
■ Check completeness of consignment based on the transport documents. The
Fig. 8 supplier must be notified in writing without delay about any possible deviations.
Transport using a forklift truck
3.4 Storage

WARNING
Risk of injury due to sliding or tilting of transport units. Sufficient stability and evenness of the
supporting area (floor) must be ensured.

The transport packaging is not intended for storage.


If the circuit-breakers are not put into operation immediately after delivery, they can
be stored under the following conditions:
■ only indoors
■ Circuit-breakers must be packed in a wooden crate with a dessicant and sealed
in aluminium foil (storage period max. 2 years after date of packaging).

+ 40 ºC

– 5 ºC

Fig. 9
Schematic diagram of the storage conditions for HVX circuit-breakers

Released for Manufacturing


16 Printed on 2019/04/25 AGS 531 301-01 | Edition 11/2018
HVX 4 Assembly

4.1 Safety provisions and instructions for assembly

WARNING
● Risk of injury due to movable parts in mechanical drives. Do not charge the circuit-breaker's
energy-storing device during assembly.
● Please comply with the safety provisions in Chapter 1.

The circuit-breakers may only be assembled and installed by the manufacturer’s


staff or by persons who have been certified for this work.
The circuit-breakers are delivered in circuit-breaker position "OFF" and with the
energy storing device "released".

Instructions for assembly ■ For all screw connections which are not specified directly in the assembly
description, the tightening torques mentioned in Chapter 8.3 must be used.
■ Check technical data on nameplate.
■ Dimension drawings are provided on request.
■ Any other than standard installation positions must be agreed upon with the
manufacturer.
■ Screws, bolts and attachments are not included in the scope of supplies.
■ Parts designed for fastening must be suitable for the weight of the circuit-breaker.
■ The circuit-breaker must not be deformed by the fastening.

4.2 Transport using a crane

WARNING
Risk of injury during crane transport. Comply with the relevant provisions for hoisting
equipment. Make sure the crane mounting harness is sufficiently strong.

For crane transport, a crane mounting harness with a rope (not a metallic steel
cable) with a diameter of Ø 12–15 mm or a strap is used. The specified weight must
be complied with.

Released for Manufacturing


AGS 531 301-01 | Edition 11/2018 Printed on 2019/04/25 17
HVX 4 Assembly

HVX model designed for


Ur ≤ 24 kV
Ir ≤ 2500 A
Isc ≤ 40 kA

>50„

Fig.10
Transport by means of a crane

Released for Manufacturing


18 Printed on 2019/04/25 AGS 531 301-01 | Edition 11/2018
HVX 4 Assembly

HVX model designed for Important:


Ur ≤ 17.5 kV Position circuit-breaker with guide rollers on the truck on wooden bars
Ir ≤ 3150 A or rails in order not to damage the guide rollers (Fig. 11).
Isc ≤ 50 kA

• 20

Fig. 11
Transport by means of a crane
1 Guide rollers (only on truck with pole center spacing 254)
2 Wooden bars or rails as a support

Released for Manufacturing


AGS 531 301-01 | Edition 11/2018 Printed on 2019/04/25 19
HVX 4 Assembly

Remove the transport support 4.3 Mechanical assembly of the fixed version HVX-F
The circuit-breakers shown below are protected against overturning by a transport
support (U section rail on the central circuit-breaker pole) (Fig. 12). Unscrew trans-
port support after or - if required - during assembly.

Fig.12
1 Transport support

For fastening, the circuit-breaker HVX-F features 4 bore-holes with a Ø of


12.5 mm. Fasten the circuit-breaker to the frame below the drive casing using
4 screws M 10 (Fig. 13).

Fig. 13
Dimension drawing of the fastening points on circuit-breakers HVX-F for rated nor-
mal current Ir ≤ 2500 A
Released for Manufacturing
20 Printed on 2019/04/25 AGS 531 301-01 | Edition 11/2018
HVX 4 Assembly

Distance between
Pole center
Version HVX-F fastening bore-holes B
distance A [mm]
[mm]

150 408

Model designed for


Ur ≤ 12 kV
Ir ≤ 1250 A
Isc ≤ 25 kA

210 534

165 471

Model designed for 185 471


Ur ≤ 24 kV
Ir ≤ 2500 A
Isc ≤ 40 kA 210 534

275 664

Released for Manufacturing


AGS 531 301-01 | Edition 11/2018 Printed on 2019/04/25 21
HVX 4 Assembly

Fastening the circuit-breaker The circuit-breaker cannot be fastened using an L rail (not included in scope of sup-
HVX-F dimensioned for plies) (Fig. 14). Fastening points are the lateral bore-holes (Ø 13) in the lower circuit-
breaker housing. A dimensional drawing is provided on request. Please clarify further
Ir ≤ 3150 A,
technical details with the manufacturer.
Isc ≤ 50 kA

340
/254
732

210
/254
210

6
8 /70
61

Fig. 14
Dimensions and fastening points of the circuit-breaker HVX-F with
Ir ≤ 3150 A, Isc ≤ 50 kA

4 bore-holes for fastening are provided in the base plate of the rack for M12 screw
connections.

Released for Manufacturing


22 Printed on 2019/04/25 AGS 531 301-01 | Edition 11/2018
HVX 4 Assembly

4.4 Earth terminal


Important:
Treat contact surfaces and comply with specified tightening torques
(see Chapter 8).

Earthing devices are not included in the scope of supplies.


Design and dimensioning of the earth terminal for the circuit-breaker in accordance with
■ IEC 62271-100 and
■ national design specification (Germany: DIN VDE 0101)

The mechanical fastening of the circuit-breaker (see Chapter 4.3) is simultaneously


used to earth the circuit-breaker.

Additional earth connection Additionally, both sides of the rack of the smaller fixed-type versions feature bore-
holes Ø 12.5 mm for a further earth terminal (Fig. 15).

Fig. 15
1 Earth terminal Ø 12.5 (on both sides) on circuit-breakers HVX-F with rated
normal current Ir ≤ 2500 A

4.5 Connecting conductor bars

WARNING
Danger due to contact corrosion in case of inadmissible matching of materials! Aluminium
conductor bars must not be connected to the connection areas of the circuit-breaker.

Important:
■ Treat contact surfaces and comply with specified tightening tor-
ques (see Chapter 8).
■ The circuit-breaker must not be deformed in the process of con-
nection.

Released for Manufacturing


AGS 531 301-01 | Edition 11/2018 Printed on 2019/04/25 23
HVX 4 Assembly

Material of connection surfaces Rated normal Connection areas


current Ir on circuit-breaker on the conductor bar
Copper, metallically
630 A Copper
bright
> 630 A Copper, silver-plated Copper or copper, silver-plated

Note for connection of the conductor bars or cables:


■ Adjust conductor bars so that after screw-fastening, no mechanical forces are
acting on the circuit-breaker.
■ Conductor bars must be dimensioned sufficiently according to the specifications
for rated and short-circuit current. National standards must be complied with.
■ In case of short-circuit current, make sure that the circuit-breaker pole is not ex-
posed to higher electrodynamic forces. The connecting bars must be provided
with sufficient support in the vicinity of the circuit-breaker connectors.

Thread reach
20 ± 2 mm

239

50
26
M12
26

50

Fig.16
High-voltage terminal of circuit-breaker HVX-F (Ur ≤ 12 kV, Ir = 1250 A,
Isc ≤ 25 kA)

Released for Manufacturing


24 Printed on 2019/04/25 AGS 531 301-01 | Edition 11/2018
HVX 4 Assembly

630/1250 A 40 1600 A 60

25 25

25
25

15
15
25

25
Ø9 Ø9

458
458
458

80
2000 A
2500 A 40

25
10,5
348
M12

9,5

Fig. 17
High-voltage terminal for fixed mounting HVX-F (Ur ≤ 24 kV, Ir ≤ 2500 A, Isc ≤ 40 kA)

M12
Thread reach
15-22 mm

340 60
50
90

30

Fig. 18
High-voltage terminal of circuit-breaker HVX-F (Ur ≤17.5 kV, Ir ≤ 3150 A, Isc ≤ 50 kA)

Released for Manufacturing


AGS 531 301-01 | Edition 11/2018 Printed on 2019/04/25 25
HVX 4 Assembly

4.6 Mounting the circuit-breaker HVX-E (truck-type)


A transport trolley must be used for racking the circuit-breaker into the panel (Fig. 19
and Fig. 20). The transport trolley depends on the panel type and is not included in
the scope of supplies. For the design and method of operation of the transport trolley
used, please refer to the instructions for the panel in question.

Fig. 19
Circuit-breaker HVX-E (≤ 40 kA) on transport trolley in front of the panel PIX
Standard

Fig. 20
Circuit-breaker HVX-E (50 kA) on transport trolley in front of the panel PIX High

Released for Manufacturing


26 Printed on 2019/04/25 AGS 531 301-01 | Edition 11/2018
HVX 4 Assembly

Placing circuit-breaker on Important:


transport trolley and racking it ■ When performing the following assembly steps, observe and com-
into the switchgear ply with the instructions given for the panel used.
■ Optionally, HVX trucks and panels may be coded to match (Fig.
21). This is to prevent a truck from being racked completely into
the panel if the ratings do not match.

1. Check the ratings indicated on the nameplate of the HVX-E against those of the
appropriate panel.
2. Place the circuit-breaker on the transport trolley rails.
3. Lock the circuit-breaker on the transport trolley.
4. Couple the transport trolley to the panel.
5. Unlock the circuit-breaker from the transport trolley. Push the circuit-breaker
into the panel.
– The HVX trucks must latch in the lock rockers of the panels (Fig. 21).
– HVX trucks for PIX High Panels are anchored in the panel by actuation of
the truck interlock (Fig. 22).
6. Release the transport trolley from the panel.

1 2
Fig. 21 Fig. 22
HVX-E underside Truck interlock in PIX High panel
1 Circuit-breaker coding
2 Spindle nut of truck
(must be latched in the cell)
3 Earth bar (optional)
4 Spindle of disconnector truck

Earth terminal The equipotential bonding connection of the circuit-breaker and the panel is effected
via the two front truck rollers (Fig. 23).

The HVX-E circuit-breaker is optionally available with short-circuit proof earthing


(Fig. 21 item 3 and Fig. 24).

X
HV

Fig. 23 Fig. 24
Equipotential bonding in the cell above 1 Earth bar on circuit-breaker HVX-E
the truck rollers for PIX High panels
Released for Manufacturing
AGS 531 301-01 | Edition 11/2018 Printed on 2019/04/25 27
HVX 4 Assembly

4.7 Connecting the control lines


The control lines are connected, depending on design, via control connectors (Fig.
25, Fig. 26, Fig. 27 and Fig. 29) or via control lines to the terminal strips in the drive
casing (Fig. 28 and Fig. 29). The control lines are wired in the circuit-breaker up to
the control connector or up to the terminal strip.
Single-wire conductors or strands can be connected
■ on terminal strip, up to 2.5 mm2
■ in the control connector, up to 1.5 mm2.

Connection via control Push the control connector onto the 64-(36-) pin right-angle plug-and socket connec-
connector tor of the circuit-breaker, and lock it (Fig. 25, Fig. 26, Fig. 27 and Fig. 29).

Important:
Connector interlock of HVX-E: The control connector on the cell end
can only be inserted or removed while the circuit-breaker is in discon-
nected position.

Connection to terminal strip 1. Remove the cover plate.


2. Connect external control lines via the terminal strip (Fig. 28 and Fig. 29). The
switch-specific circuit diagram (electric diagram) is enclosed with each circuit-
breaker and must be observed during connection.
If additional control lines are laid in the drive casing, keep a sufficient distance
from moved parts of the drive.
3. After connecting the external control lines, mount the cover plate.
HVX dimensioned for
Ur = 12–24 kV 1

2
Fig. 25 Fig. 26
Control connector, 64-pole 1 Control connector, 64-pole
1 Insert control connector
2 Lock

Fig. 27 Fig. 28
1 Insert control connector, 36-pole 1 Control line connector on terminal
strip

Released for Manufacturing


28 Printed on 2019/04/25 AGS 531 301-01 | Edition 11/2018
HVX 5 Commissioning

5.1 Final steps

DANGER
Risk of fatalities due to high voltage.
All active parts must be earthed.

Checking assembly ■ Check securing bolts.


■ Check the conductor bars’ screw connections using a torque wrench.
■ Check the screw connections of the earth terminal.
■ Check wiring laid on site.

Damaged paint Minor damage to the paint can be repaired using a commercially available touch-up
pen (standard colour RAL 7044 or corresponding colour) (see Chapter 8.1 “Auxiliary
products”).

Inspection ■ Check the circuit-breaker for damage which might be due to transport or as-
sembly work.
■ Compare the data on the nameplate (see Chapter 2.6) to the required rating
specifications.
■ Check rated supply voltage of control and operating devices.
■ Check surfaces of insulating components for impurities. If necessary, clean (see
Chapter 7.3).

5.2 Checking switching functions and interlocks

DANGER
The high-voltage supply must not be connected.
All active parts must be earthed.

Important:
■ For switching operations, comply with Chapter 6 “Operation”.
■ In case supply voltage is not available,
– blocking coils (optional; lock circuit-breaker button and/or
truck in disconnected position) are in locked position, thus
blocking manual switching operations;
– there is a dropped-out undervoltage release in the circuit-
breaker (optional).
■ The energy-storing device of the circuit-breaker drive is charged
autonomously as soon as the supply voltage is applied.

Released for Manufacturing


AGS 531 301-01 | Edition 11/2018 Printed on 2019/04/25 29
HVX 5 Commissioning

Checking switching functions 1. Charge energy-storing device using the crank. Check position indicator on the
and interlocks: circuit-breaker.
2. Apply supply voltage.
3. Switch circuit-breaker on and off several times manually.
Check position indicator.
4. Move truck to its operating and disconnected positions via the crank
(only HVX-E). Check mechanical interlocks between the HVX-E and the cell.
Check position indication.
5. Check electrical functions of control and operating devices:
– Closing and opening releases for circuit-breaker
– Optional motor-operated drives for the truck (only HVX-E)
6. Check switch position indicators and interlocks (Chapter 6).

5.3 Checks for the circuit-breaker HVX in conjunction


with panels/switching cells

Verification of the required Before commissioning, panels or switching cells must be qualified completely with
ratings and performance the switching devices installed by means of type tests in acc. with IEC 62271-200/
IEC 62271-1 or national regulations.
characteristics
If the circuit-breaker HVX is used in panels or switching cells which have not yet
been qualified together, type tests in acc. with IEC 62271-200 and IEC 62271-1 or
national regulations must be performed.

Released for Manufacturing


30 Printed on 2019/04/25 AGS 531 301-01 | Edition 11/2018
HVX 6 Operation

HVX Circuit-breaker 6.1 Operator interface


dimensioned for
Ur = 12-24 kV

5
6
00815

Fig. 29
Operating interface of HVX circuit-breaker with a rated voltage of 12-24 kV
1 OFF button (rocker “0”)
2 ON button (rocker “I”)
3 Nameplate
4 Operation counter
5 Position indicator of circuit breaker
6 Position indicator of spring mechanism
7 Insertion opening for charging the closing spring

Fig. 30
Operating interface of HVX circuit-breaker (rated voltage 12-24 kV) with push-but-
tons (optional)

Released for Manufacturing


AGS 531 301-01 | Edition 11/2018 Printed on 2019/04/25 31
HVX 6 Operation

6.2 Operation accessories


Important:
Only the auxiliary equipment required for operation (depending on the
circuit-breaker design) is supplied in the accessories. Only these ac-
cessories may be used to operate the circuit-breaker.

Position
Designation Ref. no.
(Fig. 31)
1 Operating rod for ON/OFF actuation AGS H35 446-01
Spring charging crank for energy-storing
2 AGS H30 498-01
device
AGS H31 601-011
Moving crank handle with integrated slip
3 AGS H32 532-012
coupling for disconnector truck (HVX-E)
AGS H31 674-013
Moving crank handle for disconnector truck
4 AGS C66 911-01
in PIX High panels
1 Disconnector truck, manually actuated, shape of insertion opening: hexagonal
2 Disconnector truck, manually actuated, shape of insertion opening: square
3 Emergency crank handle for disconnector truck, motor-actuated

1
1

5 4
3 5

Fig. 31
Accessories for circuit-breaker HVX-F and HVX-E
1 Operating rod for ON/OFF actuation
2 Spring charging crank for energy-storing device
3 Moving crank handle with integrated slip coupling for disconnector truck (HVX-E)
4 Moving crank handle for disconnector truck in PIX High panels
5 Closed door of switchgear panel

Released for Manufacturing


32 Printed on 2019/04/25 AGS 531 301-01 | Edition 11/2018
HVX 6 Operation

6.3 Interlocks

WARNING
Risk of injury. You must be familiar with these interlocks before operating the circuit-breaker.

Electromagnetic The manual operating facilities on the circuit-breaker can be locked optionally by
interlocks (optional) blocking coils. Electromagnetic blocking coils can be used for inter-panel as well as
intra-panel interlocks:
■ The circuit-breaker’s ON and OFF pushbuttons are blocked.
■ The insertion opening for the crank to move the circuit-breaker into its discon-
nected/service position is blocked (only for HVX-E).

Important:
■ In case of failure of the supply voltage, all electrical interlocks are
in their "locked" position.
■ Please note the purchase contract and the switchgear-specific cir-
cuit diagram as regards the design of the interlocking systematics.

Mechanical interlocks in the The circuit-breaker HVX-E (truck) features mechanical basic interlocks to prevent
HVX-E operating errors:

Interlock Function of interlock Method of operation of interlock


The truck cannot be racked in unless the low- The opening for the moving crank handle
voltage connector is inserted and locked. is locked.
Between truck and low-voltage
connector The low-voltage connector can only be inserted
The interlock for the low-voltage connector
or removed while the truck is in its discon-
on the drive end has been activated.
nected position.
Circuit-breaker cannot be racked in or out while The opening for the moving crank handle
it is switched on is locked.
Between the truck and the oper- Circuit-breaker cannot be switched on unless
ating state of the – it is completely in its disconnected or ser-
circuit-breaker The circuit-breaker cannot be switched ON
vice position and
or OFF.
– the operating crank for the racking-in
mechanism has been removed.

Released for Manufacturing


AGS 531 301-01 | Edition 11/2018 Printed on 2019/04/25 33
HVX 6 Operation

6.4 Operating specifications

WARNING
● Risk of injury. Please comply with the safety provisions in Chapter 1.
● To rule out risks due to faulty switching operations, the operating sequences described
below must be complied with. Each switching operation must be completed.

Check whether the supply voltage is ON.

Important:
■ When operating the circuit-breaker, observe and comply with the
instructions given for the panel used.
■ After each switching operation for which you have used a crank or
a lever, remove this tool.
■ In case supply voltage is not available
– blocking coils (optional, see Chapter 6.3) are in "locked" position;
– an undervoltage release (optional) has dropped out.
Measure: Re-establish the supply voltage.
■ Comply with the switch-specific mechanical and electromechani-
cal interlocking conditions; see also Chapter 6.3.

Specifically for truck actuation


WARNING
Risk of an arc occurring on switching unless the truck is operated in isolated or deenergized
condition. The circuit-breaker must always be switched off previously.

Important:
Do not pull the crank out before the truck in question has reached its
end position; do not pull it out in an undefined intermediate position.

Released for Manufacturing


34 Printed on 2019/04/25 AGS 531 301-01 | Edition 11/2018
HVX 6 Operation

6.5 Charging the energy storing device

Initial position:
■ Circuit-breaker in “OFF” position

■ Energy storing device released

Manually 1. Insert crank into opening for tensioning the energy storing device (Fig. 32).
2. Turn clockwise, until the charge drive mechanism is uncoupled (sound).
The energy storing device indicates the “charged” condition:

3. Remove crank. The circuit-breaker is ready for closing


(Chapter 6.7, Table item 2).

Fig. 32
Charging the energy storing device manually

Via motor-drive The energy storing device of motorized circuit-breakers is charged automatically as
soon as the supply voltage is applied.

Released for Manufacturing


AGS 531 301-01 | Edition 11/2018 Printed on 2019/04/25 35
HVX 6 Operation

6.6 Switching operations


All available versions for switching the circuit-breaker ON and OFF are listed below.
Depending on the switch-specific equipment, versions may be shown, but not be
available.

Switching ON (Closing) Important:


Max pressure time: 1s (Do not keep pressure on the button).

■ Press ON button (I) using the operating rod (Fig. 33, item 1) or
■ press ON button (I) (Fig. 34, item 3) or
■ actuate closing release electrically.
Position indicator indicates the “ON” position (2).

Fig. 33 Fig. 34
1 Switching ON by means of an 3 Switching ON via pushbutton
operating rod 2 Position indicator indicates "ON"
2 Position indicator indicates "ON"

The energy storing device can be charged again immediately after switching ON
(manually or by motor). If voltage is applied to the motor, charging is performed
automatically.
The position indicator shows the energy storing device position “charged” (Chaper
6.7, table item 4).

Switching OFF (Opening) Important:


Max pressure time: 1s (Do not keep pressure on the button).

■ Press OFF button (O) by means of the operating rod or


■ Press OFF button (O) or
■ actuate opening release electrically, or
■ by undervoltage release or secondary release
The position indicator indicates the switch position OFF (Chapter 6.7, Table
item 1 or 2).

Released for Manufacturing


36 Printed on 2019/04/25 AGS 531 301-01 | Edition 11/2018
HVX 6 Operation

6.7 Position indicators on circuit-breaker and possible


operating sequences
Item Position indicator, Position Possible
energy-storing device indicator operating
ON/OFF sequence

1 released OFF none

2 charged OFF C–O

3 released ON O

4 charged ON O–C–O

C = ON (Close) O = OFF (Open)

6.8 Moving truck into service / disconnected position


Initial situation:
■ Circuit-breaker OFF

Racking-in the truck from The crank features an integrated slip coupling which prevents damage to the drive
disconnected into service mechanism due to an excessive torque. The slip coupling can react if the truck is
moved to its final stop in disconnected or service position.
position
1. Open cover in panel (Fig. 35, item 1) and insert crank (2).
2. Turn crank clockwise (3) until the truck has been racked in. Remove crank.
3. Check position of the truck (Fig. 36) through the inspection port.

Fig. 35 Fig. 36
1 Open panel cover Truck in service position
2 Insert crank
3 Turn crank clockwise

Released for Manufacturing


AGS 531 301-01 | Edition 11/2018 Printed on 2019/04/25 37
HVX 6 Operation

Racking-out the truck from 1. Open cover in panel (Fig. 37, item 1) and insert crank (2).
service into disconnected 2. Turn crank counter-clockwise (3) until the truck has been racked out. Remove
position crank.
3. Check position of the truck (Fig. 38) through the inspection port.

Fig. 37 Fig. 38
1 Open panel cover Truck in disconnected position
2 Insert crank
3 Turn crank counter-clockwise

Racking-in the truck for PIX 1. Press the interlocking slide (Fig. 39, item 1) to the left and hold it. Insert crank
High panels from disconnected through the opening in the door onto the drive shaft of the truck (2).
into service position 2. Turn crank clockwise until the position indicator above the crank indicates “I”
(Fig. 39, item 3). Remove crank.
3. Check position of the truck (Fig. 38) through the inspection port.

Fig. 39 Fig. 40
1 Press interlocking slide to the left Truck in service position
2 Insert crank and turn it clockwise
3 Position indicator “I”

Released for Manufacturing


38 Printed on 2019/04/25 AGS 531 301-01 | Edition 11/2018
HVX 6 Operation

Racking-out the truck for PIX 1. Press the interlocking slide (Fig. 41, item 1) to the left and hold it. Insert crank
High panels from service into through the opening in the door onto the drive shaft of the truck (2).
disconnected position 2. Turn crank counter-clockwise until the position indicator above the crank indi-
cates “O” (Fig. 41, item 3). Remove crank.
3. Check position of the truck (Fig. 42) through the inspection port.

Fig. 41 Fig. 42
1 Press interlocking slide to the left Truck in disconnected position
2 Insert crank and turn it counter-
clockwise
3 Position indicator: „O“

Released for Manufacturing


AGS 531 301-01 | Edition 11/2018 Printed on 2019/04/25 39
HVX 7 Maintenance

7.1 Safety provisions

WARNING
● Risk of injury. Please comply with the safety provisions in Chapter 1.
● Risk of injury due to mechanically precharged drive components. The circuit-breaker must
not be disassembled for maintenance work.

Maintenance and maintenance work may only be performed by specialist electri-


cians who have been certified by the manufacturer for series HVX vacuum circuit-
breakers and who are familiar with the appropriate safety provisions.
For inspection and maintenance the circuit breaker HVX-E have to be on the trans-
port trolley (Fig. 43).

Fig. 43
Transport trolley

7.2 Maintenance and maintenance specifications


Series HVX vacuum circuit-breakers are indoor switching devices designed for nor-
mal operating conditions in acc. with IEC 62271-1.

Inspection It is recommended to check the circuit-breakers visually at regular intervals depend-


ing on the strain they are subject to during operation and in accordance with national
regulations.

Important:
In case of frequent condensation or air pollution (dust, smoke or cor-
rosive gases), the maintenance intervals must be adapted to the actual
conditions.

A visual inspection includes a complete check of the circuit-breaker for contamina-


tion, condensation and damage, to be performed by certified staff.

Maintenance If there are signs of contamination or condensation, the circuit-breakers must be


cleaned in an expert manner (see Chapters 7.3 and 7.4) and subsequently the drives,
interlocks and position indicators checked for proper functioning (see Chapter 6).

Overhauling If damage is detected, it must be repaired immediately, or components replaced (see


Chapter 7.5 and 7.6).
In case of ambiguities or irregularities, please contact the manufacturer’s Service
Center immediately.

Maintenance interval Maintenance Qualification /


work Work performed by
After 10 000 operating cycles Revision of circuit-
breaker
after 1,000 truck operations Revision of the truck
Manufacturer’s Service
once the max. admissible Replacement of Center
number of breaking operations vacuum chambers
for the vacuum chambers has
been reached (see Chapter 7.8)

Released for Manufacturing


40 Printed on 2019/04/25 AGS 531 301-01 | Edition 11/2018
HVX 7 Maintenance

7.3 Cleaning insulating components


To ensure the specified insulating level, the insulating components must be clean.
On principle, general cleanliness of the circuit-breaker and of its external parts
should be ensured.

Slight contamination Clean using a dry, lint-free cloth. Depending on the degree of soiling, replace cloth
as often as necessary.

Severe soiling Cleaning agent, 1 l can (see Chapter 8.1) must be used for cleaning.
The use of other cleaning agents is not admissible.
■ Wear protective gloves
■ Use cleaning agent according to manufacturer’s instructions.
■ Soak the cloth thoroughly and wipe the insulating components. Keep duration
of exposure as short as possible.
■ Expose the cleaned surface to the air for at least two hours.
When cleaning, make sure that the lubrication in the drive mechanisms is not
removed. If the drives are no longer sufficiently lubricated, replace the grease (see
Chapter 7.7).

7.4 Avoiding condensation


To ensure the specified insulating level, the circuit-breaker – especially its insulating
components – must not be exposed to condensation.
1. If condensation is detected, clean the circuit-breaker (see Chapter 8.3).
2. Check heating system or install a heating. It must provide a sufficient heating
performance to prevent condensation on the circuit-breaker.
3. Condensation can also be prevented by ensuring suitable ventilation and heat-
ing of the station or by using de-humidification devices.

7.5 Corrosion protection


Drive mechanisms and covers have a long-term protection against corrosion. Any
damage to the paint, scratches and other damage must be repaired immediately to
avoid corrosion. Contact the manufacturer’s Service Center.

7.6 Replacement of components


Drive or live high-voltage components may be replaced as required.
The following data on the nameplate are relevant for replacement of components or
in case of any queries (see also Chapter 2.6):
■ Type designation
■ Serial number
■ Year of construction
If you have any queries regarding replacement of components, please contact the
manufacturer’s Service Center.

Released for Manufacturing


AGS 531 301-01 | Edition 11/2018 Printed on 2019/04/25 41
HVX 7 Maintenance

7.7 Lubrication instructions


Important:
■ For units produced before September 2018, refer to the End User
Guide of January 2011 to find out about the type of grease to use.
■ The bearings and joints must not be washed out by the cleaning
agent.
■ The following elements must not be lubricated:
− Motor
− Ball bearings
− Auxiliary releases
− Micro switches
− Blocking coils
− Auxiliary switches
■ Only approved Mobilith SHC 100 grease must be used
(see Chapter 8.1).

Truck mechanism ■ Spindle of truck mechanism (Fig. 44, item 1). The spindle is accessible from
below.
■ Geared wheels of truck mechanism (only in case of motor-drive) (Fig. 44, item
2). The geared wheels are accessible once the lower front cover has been
removed.

1
Fig. 44
Points of lubrication of the racking-in mechanism
£ Mobilith SHC 100 grease
1 Spindle
2 Geared wheels

Released for Manufacturing


42 Printed on 2019/04/25 AGS 531 301-01 | Edition 11/2018
HVX 7 Maintenance

Truck mechanism in the HVX-E To have access to the points of lubrication, make sure that the disconnecting truck is
for PIX High panels in service position.

Fig. 45
Points of lubrication of the racking-in mechanism of HVX circuit-breakers in PIX High
panels
£ Mobilith SHC 100 grease

Released for Manufacturing


AGS 531 301-01 | Edition 11/2018 Printed on 2019/04/25 43
HVX 7 Maintenance

Moving contacts

630 A (< 20 kA) 1250 A / 630 A (> 25 kA)

1600 A / 2000 A 2500 A

3150 A 3150 A

Fig. 46
Greasing the moving contacts
£ Mobilith SHC 100 grease

Released for Manufacturing


44 Printed on 2019/04/25 AGS 531 301-01 | Edition 11/2018
HVX 7 Maintenance

Circuit-breaker Remove operating Interface:


Tools: TORX screwdriver, size T25 / slotted screwdriver
Remove the five M5 screws on the front and remove the operating panel.

Fig. 47
Points of lubrication on the circuit-breaker drive mechanism
£ Mobilith SHC 100 grease

Final steps Mount operating interface and insert circuit-breaker in panel (see Chapter 4 “Assem-
bly”). Check circuit-breaker in acc. with Chapter 5 “Commissioning”.

Released for Manufacturing


AGS 531 301-01 | Edition 11/2018 Printed on 2019/04/25 45
HVX 7 Maintenance

7.8 Maximum admissible numbers of breaking


operations of vacuum chamber
The diagram (Fig. 49) defines exclusively the max. admissible numbers of breaking
operations of the circuit-breaker depending on the rated normal current Ir and of the
short-circuit breaking current Isc. It indicates when the vacuum interrupter chambers
need to be replaced.
The diagram shows examples of values for the rated normal current Ir and the short-
circuit breaking current Isc.
The data for the rated normal current Ir and the short-circuit breaking current Isc are
indicated on the nameplate (Fig. 48).

Type HVX 12–25–08–F No. TH242884 2010


IEC 62271–100 / 2001 IEC 60056 / 1987
Ur 12 kV Ir 800 A fr 50 Hz E1
2 Isc 25 kA Ic 25 A tk 3 s C1
Up 75 kV 0–0,3s–CO–15s–CO M2
1

Made in .......................
AGSH30799-02

Fig. 48
Data for rated normal current Ir (1) and short-circuit breaking current Isc (2) on the
nameplate

100000

10000
Number of breaking operations [n]

1000

100

10

1
0 0,8 1 2,5 10 25 100

Ratings Ir und ISC [kA]


Fig. 49
Admissible breaking numbers for the vacuum chamber with values (example)
Ir = rated normal current = 0.8 kA
Isc = short-circuit breaking current = 25 kA

Released for Manufacturing


46 Printed on 2019/04/25 AGS 531 301-01 | Edition 11/2018
HVX 8 Annex

8.1 Auxiliary products


The auxiliary products are available from the manufacturer. The use of alternative
auxiliary products is not permissible.

WARNING
Risk of injury if these products are handled improperly. Observe the safety data sheets of the
manufacturers of the auxiliary products.

Designation Symbol Ref. no.


Cleaning agent, 1-l can S 008152
Mobilith SHC 1001 £ 87635
Touch-up pen RAL 7044, silk-grey, 50 ml S 009 561
Touch-up pen, special paint (specify colour shade) S 009 562
1 The size of the packing unit is not defined. It will be defined upon consultation with
the manufacturer.

8.2 Treatment of firmly screw-connected contact


surfaces
Important:
Caution when handling bars insulated by heat-shrinkable sleeves: The
heat-shrinkable sleeve must not get into contact with contact grease
(swelling).

1. Contact areas must be subjected to preliminary treatment before screw-fasten-


ing (see Table below)
2. Immediately after the pre-treatment, coat the contact surfaces with contact
grease.

Material of contact surfaces Pre-treatment


Silver-plated Cleaning1
Copper or copper alloy Clean1, expose metallic surface2
Steel Clean1, expose metallic surface2
Zinc-plated steel Remove passivation, not, however, the zinc
layer3
Hot-galvanized sheet-metal Clean1, passivation need not be removed
1 by means of lint-free cloth; use cleaning agent in case of serious contamination
2 – by treating the entire surface with emery cloth or a rotating grinding tool (grain
size 100 or 80) or
– using a wire brush which is clearly marked for use exclusively for aluminium
or exclusively for copper
3 with brass or steel brush

Released for Manufacturing


AGS 531 301-01 | Edition 11/2018 Printed on 2019/04/25 47
HVX 8 Annex

8.3 Specifications for screw connections


Important:
The threads of screws and bolts must generally not be pre-treated.
■ Max. tolerance for the effective tightening torques: ±15 %
■ The nut must correspond in strength to the grade of the screw/bolt
used or be of better quality.

General screw connections

Grade or material
Self-locking screw
Screw/bolt Plastics ≥ 8.8 ≤ 10.9
≥ 8.8
Thread Ø Tightening torques [Nm]
M4 0.25 2.6
M5 0.5 5.0 7.0
M6 0.8 8.8 12.3
M8 1.8 21.0 30.0
M 10 3.5 42.0 59.0
M 12 6.0 70.0 97
M 16 12 170
M 20 330

Screw fastening for power Screw connection for terminal


transmission strips

Screws and bolts: Grade ≥ 8.8

Conductor material: copper Thread Ø Tightening


Thread Ø Tightening torques [Nm]
torques [Nm] M 2.5 (M 2.6) 0.5
M6 6.5 M3 0.7
M8 17 M 3.5 1.0
M 10 35 M4 1.5
M 12 68 M5 2.5
M 16 135

Released for Manufacturing


48 Printed on 2019/04/25 AGS 531 301-01 | Edition 11/2018
Notes:

Released for Manufacturing


Printed on 2019/04/25
Notes:

Released for Manufacturing


Printed on 2019/04/25
Released for Manufacturing
Printed on 2019/04/25
© 2018 Schneider Electric - All rights reserved

Schneider Electric As standards, specifications and designs change from time to time, please ask for
35, rue Joseph Monier confirmation of the information given in this publication.
CS 30323
92506 Rueil-Malmaison Cedex, France This document has been printed
on ecological paper
RCS Nanterre 954 503 439
Capital social 896 313 776 € Publishing: Schneider Electric
www.schneider-electric.com Design: Schneider Electric
Printing: Released for Manufacturing
AGS 531 301-01 Printed on 2019/04/25 11-2018

You might also like