Manual PV500&PV150A-V1.8
Manual PV500&PV150A-V1.8
Manual PV500&PV150A-V1.8
Preface
PV500 special inverters are developed for power supply of water pumps, based on the core
control arithmetic of FR500 vector control inverters, combined with the control requirements of PV
water pump application. The function of maximum power tracking, dormant at weak light, wake up at
strong light, high water level dormant, under-load pre-warning and other control protection functions
can ensure normal operation of water pumps according to the customers’ requirements to switch to the
grid power supply.
Please refer to this manual to commission the inverter, product maintenance refer to FR500 user
manual.
IMPORTANT NOTES
◆To illustrate the details of the products,pictures in this manual based on products with outer
casing or safety cover being removed. When using this product, please be sure to well install
outer casing or covering by the rules, and operating in accordance with the manual contents.
◆The illustrations in this manual are for illustration only and may vary with different products
you have ordered.
◆The company is committed to continuous improvement of products, product features will
continue to upgrade, the information provided is subject to change without notice.
◆If there is any questions when using, please contact our regional agents or our customer
service center:(+86-0755-88605930)
◆For other products, please visit our website. http://www.frecon.com.cn
-1-
PV500&PV150A Series Solar Pumping Inverter
-2-
PV500&PV150A Series Solar Pumping Inverter
Contents
PREFACE..................................................................................................................................... - 1 -
CONTENTS .................................................................................................................................. - 3 -
CHAPTER 1 PRODUCT OVERVIEW ........................................................................................... - 4 -
1.1 NAME PLATE ......................................................................................................................... - 4 -
1.2 PRODUCT SPECIFICATIONS ....................................................................................................... - 5 -
1.3 DIMENSION DRAWING ........................................................................................................... - 11 -
CHAPTER 2 COMMISSIONING GUIDE .................................................................................... - 15 -
2.1 PV PANEL POWER SUPPLY COMMISSIONING ............................................................................. - 15 -
2.2 GRID OR GENERATOR POWER SUPPLY WIRINGS ......................................................................... - 18 -
2.3 WIRING DIAGRAM BETWEEN FRECON VFD AND SINGLE PHASE MOTOR ....................................... - 20 -
2.4 PRODUCT TERMINAL CONFIGURATION .................................................................................... - 24 -
CHAPTER 3 FUNCTION PARAMETERS ................................................................................... - 32 -
3.1 THE BASIC FUNCTION PARAMETERS........................................................................................ - 32 -
3.2 H00 GROUP: DETAILED EXPLANATION OF FUNCTION CODE ........................................................ - 60 -
CHAPTER 4 TROUBLESHOOTING AND COUNTERMEASURES ............................................. - 65 -
-3-
PV500&PV150A Series Solar Pumping Inverter
Model Instruction
Model numbers on name plate consist of numbers, symbols, and letters, to express its respective
series, suitable power type, power level and other information.
PV500-4T-2.2B
Products series Number
Braking Unit (Built-in )
PV: Solar Pump Inverter
-4-
PV500&PV150A Series Solar Pumping Inverter
1.2 Product Specifications
1.2.1 Electric specification of AC110V Input product
Table 1-1Electric specification of AC110V Input product
Recommend Maximum Rated Input Rated
ed Solar Input DC AC Current Output Adaptive
Model Power (kW) Current (A) (A) Current (A) Motor (kW)
PV150A-1S-0.7B 0.4 7.5 9.3 4.2 0.25
PV150A-1S-1.5B 0.6 10.6 15.7 7.5 0.4
PV150A-1S-2.2B 1.0 10.6 24 9.5 0.75
Input specification
PV Input
Maximum Input DC
450VDC
Voltage
Recommended Voc
170~300VDC
Range
Recommended MPPT
140~240VDC
Voltage Range
Starting Voltage
80~450VDC
Range
Output specification
Protection
Lighting Protection, over-current, overvoltage, output phase-lose,
Built-in Protection under-load, under-voltage, short circuit, overheating, water pump run
dry etc.
-5-
PV500&PV150A Series Solar Pumping Inverter
1.2.2 Electric specification of AC220 Input product
Input specification
PV Input
Maximum Input DC
450VDC
Voltage
Recommended Voc
360~430VDC
Range
Recommended MPPT
250~350VDC
Voltage Range
PV150A: 80~450VDC
Starting Voltage Range
PV500: 230~450VDC
Grid or backup generator input
-6-
PV500&PV150A Series Solar Pumping Inverter
2S: 1PH 220V(-15%~20%)
Input voltage
2T: 3PH 220V(-15%~20%)
Output specification
Protection
Lighting Protection, over-current, overvoltage, output phase-lose,
Built-in Protection under-load, under-voltage, short circuit, overheating, water pump
run dry etc.
-7-
PV500&PV150A Series Solar Pumping Inverter
Input specification
PV Input
Maximum Input DC
800VDC
Voltage
Recommended Voc
550~750VDC
Range
Recommended MPPT
450~600VDC
Voltage Range
Starting Voltage Range 230~800VDC
Output specification
Protection
Input specification
PV Input
Maximum Input DC
450VDC
Voltage
Recommended Voc
360~430VDC
Range
-9-
PV500&PV150A Series Solar Pumping Inverter
Recommended MPPT
250~350VDC
Voltage Range
Output specification
Protection
Lighting Protection, over-current, overvoltage, output phase-lose,
Built-in Protection under-load, under-voltage, short circuit, overheating, water pump run
dry etc.
- 10 -
PV500&PV150A Series Solar Pumping Inverter
1.3.1 PV150A
W D W1
d1
H3
H2
H H1
d2
Fig 1-3 Product size chart
- 11 -
PV500&PV150A Series Solar Pumping Inverter
1.3.2 PV500
◆4~22kW Dimensions and wall mounting dimensions
D
H1
H
4X
W1 d
W
Figure 1-4 4~22kW Wall Installation Diagram
- 12 -
PV500&PV150A Series Solar Pumping Inverter
- 13 -
PV500&PV150A Series Solar Pumping Inverter
1.3.3 PV150I
◆ Dimensions and wall mounting dimensions
W D W1
d1
H3
H2
H H1
d2
- 14 -
PV500&PV150A Series Solar Pumping Inverter
PV panels
Q1
+
-
S/L2 V/T2 M
T/L3 PV500 W/T3
+24V
Short film
PLC +24V
RUN/STOP Y1
DI1 Operation panel
DI2
DI3 Y2/HO
DI4
R1A
DI5
R1B
DI6
R1C
DI7/HI
COM R2A
AI2 AO2
GND GND
AI3
485+
485-
PE
GND
- 15 -
PV500&PV150A Series Solar Pumping Inverter
PV panels
Q1
-
+
(+) (-) U
L
N V M
W
+24V
Short film
PLC +24V
PV150A
RUN/STOP Y1
DI1
DI2
DI3 Y2/HO
DI4
R1A
R1B
R1C
DI7/HI
GND
AI2
GND
485+
485-
PE
GND
S V M S V M
T W T W
+24V +24V
Short film Short film
PLC +24V PLC +24V
PV150A PV150A
RUN/STOP Y1 RUN/STOP Y1
DI1 DI1
DI2 DI2
R1B R1B
R1C R1C
DI7/HI DI7/HI
GND GND
AI2 AI2
GND GND
485+ 485+
485- 485-
PE PE
GND GND
Figure 2-2(b) PV150A(4T, new design) Figure 2-2(c) PV150A(4T, old solution)
- 16 -
PV500&PV150A Series Solar Pumping Inverter
Commissioning steps:
1. Please wirings as Figure2-1&Figure2-2 according to different inverter powers, check and confirm
the wirings to be correct, and then close Q1.
2. Setting the Motor Parameters
Setting the parameter of name plate on motor F08.01~F08.05。
3. Testing the water yield of pump
Press the operation key “RUN”, under normal circumstance of light strength, if the operation
frequency low or water yield less, which means the motor wiring may be reversed, please exchange
two wirings of motor.
4. System Effluent Speed PI Regulating
If the user has a high requirements for the effluent speed, PI parameters can be regulated
appropriately(H00.09~H00.10), the larger PI parameter, the stronger affection, the faster effluent,
but the larger fluctuation of motor frequency; Otherwise, the slower water effluent, the more steady
frequency of motor operation.
5. MPPT Tracing Speed Commissioning
H00.04 and H00.05 are respectively the lowest voltage and highest voltage under the MPPT mode,
the smaller the range between them two, the faster tracing the maximum power, but the premise if
that the bus voltage during normal operation must fall within this range, or the maximum power point
may not be tracked. Generally speaking, the factory default value is OK.
6. Setting of fault point and fault delay reset time
If clients need to use the pre-warning of weak light, water-logged, under-load, failure monitoring point,
delay time and reset time, water-logged/controlled function can be set as H00.15~H00.19 on
demand; under-load function set as H00.20~H00.22; weak light function set as H00.13~H00.14.
Users also can adopt the default value.
7. Parameter setting after the system operation normally
When the water yield is normal, and system run steadily, the commissioning will be finished. And
then setting F02.00=1, change to terminal operation mode, setting failure auto reset times
F11.27=5.
- 17 -
PV500&PV150A Series Solar Pumping Inverter
2.2 Grid or Generator power supply wirings
Wiring drawings of below inverters shown as below
PV panels
Q1
Q2
(-) (+) PB U/T1
R/L1
Grid or
S/L2 V/T2 M
generator set
T/L3 PV500 W/T3
+24V
PLC +24V
RUN/STOP
Y1
DI1
Operation panel
DI2
PV Voltage
Given selection DI3 Y2/HO
DI4
R1A
DI5
R1B
DI6
R1C
DI7/HI
COM R2A
AI2 AO2
GND GND
AI3
485+
485-
PE
GND
PV panels
Q1
-
+
Q2
(+) (-) U
Grid or L
generator set
N V M
W
+24V
Short film
PLC +24V
PV150A
RUN/STOP Y1
DI1
DI2
DI3 Y2/HO
DI4
R1A
R1B
R1C
DI7/HI
GND
AI2
GND
485+
485-
PE
GND
- 18 -
PV500&PV150A Series Solar Pumping Inverter
PV panels PV panels
Q1 Q1
- -
+ +
Q2 Q2
(+) (-) U (+) PB U
R R
Grid or
generator set S V M Grid or
generator set S V M
T W T W
+24V +24V
Short film Short film
PLC +24V PLC +24V
PV150A PV150A
RUN/STOP Y1 RUN/STOP Y1
DI1 DI1
DI2 DI2
R1B R1B
R1C R1C
DI7/HI DI7/HI
GND GND
AI2 AI2
GND GND
485+ 485+
485- 485-
PE PE
GND GND
Figure 2-4(b) PV150A(4T, new design) Figure 2-4(c) PV150A(4T, old solution)
NOTE:
When the bus input terminal does not install the diode protection, PV panel switch Q1 will be
prohibited to close together with grid power input switch Q2, or the panel will be damaged.
- 19 -
PV500&PV150A Series Solar Pumping Inverter
2.3 Wiring diagram between FRECON VFD and single phase motor
2.3.1 Single phase motor introduction
Single phase motor generally means asynchronous single phase motor powered by single phase
AC 220V, there’re two phase winding in motor stator and motor rotor is common squirrel cage. The
distribution of two phase winding and different power supply will lead to different starting
characteristics and operating characteristics
Usually single phase motor is with single capacitor or double capacitor, photos of motor are as
below:
M
Starting
capacitor
U1 Z1
Main Secondary
220VAC winding winding
Z2
U2
Figure 2-6 Operation mode: Internal wiring of motor with single capacitor
M
Starting Centrifugal
capacitor switch
U1 Z1
Main Secondary
220VAC winding winding
Z2
U2
Figure 2-7 Starting mode: Internal wiring of motor with single capacitor
- 20 -
PV500&PV150A Series Solar Pumping Inverter
Running
capacitor
Starting Centrifugal
capacitor switch
U1 Z1
Secondary
220VAC Main winding winding
Z2
U2
Resistor starting mode single phase motor, and internal wiring is as below:
Centrifugal
R
switch
U1 Z1
Main Secondary
220VAC winding winding
Z2
U2
U1 Z1
Secondary
Main winding
winding
U2 Z2
- 21 -
PV500&PV150A Series Solar Pumping Inverter
2.3.2 Wiring between VFD and motor(Capacitor removable)
Connect main and secondary winding of motor to inverter UVW, then inverter can work. But due
to the motor winding difference, motor forward wiring must be as below, if not cause motor too heat
(-) (+) PB
M
KM1
L1 U
U1 Z1
220VAC
L2 V Secondary
Main winding winding
W
PV150A U2 Z2
Motor reverse can’t be completed through parameter setting of inverter or change any two
phase wirings, motor reverse wiring must be as below:
(-) (+) PB
M
KM1
L1 U
U1 Z1
220VAC
L2 V Main Secondary
winding winding
W
PV150A U2 Z2
Motor forward and reverse wiring of 0.75Kw/220V PV500 is same with PV150A, and wiring of
PV500 above 1.5kW are as below:
(-) (+) PB
M
KM1
L1 U
U1 Z1
220VAC
L2 V Secondary
Main winding winding
W
PV500 U2 Z2
- 22 -
PV500&PV150A Series Solar Pumping Inverter
(-) (+) PB
M
KM1
L1 U
U1 Z1
220VAC
L2 V Main Secondary
winding winding
W
PV500 U2 Z2
(-) (+) PB
KM1
L1 U
220VAC
L2 V
W
M
PV150A
(-) (+) PB
KM1
M
L1 U
220VAC
L2 V
W
PV500
- 23 -
PV500&PV150A Series Solar Pumping Inverter
2.4 Product Terminal Configuration
2.4.1 PV150A Main Circuit Terminals
- 24 -
PV500&PV150A Series Solar Pumping Inverter
(+) (-) R S T UV
POWER
RFI
(+) (-)
DC
PB
(+) (-)
PB
DC
- 25 -
PV500&PV150A Series Solar Pumping Inverter
(+) (-)
PB
DC
- 26 -
PV500&PV150A Series Solar Pumping Inverter
(+) (-) R S T UV
POWER
RFI
(+) (-)
DC
PB
- 27 -
PV500&PV150A Series Solar Pumping Inverter
Table 2-1 Main Circuit Terminal Functions
Remarks: No phase sequence requirements on wiring of the input side of inverter. Wiring
Precautions:
1)Power input terminals R/L1, S/L2 , T/L3
◆ The cable connection on the input side of the AC drive has no phase sequence requirement.
2)DC bus (+), (-)
◆ Terminals (+) and (-) of DC bus have residual voltage after the AC drive is switched off. After
indicator CHARGE goes off, wait at least 10 minutes before touching the equipment Otherwise, you
may get electric shock.
◆ Do not connect the braking resistor directly to the DC bus. Otherwise, it may damage the AC drive
and even cause fire.
3)Braking resistor connection terminals (+), PB
◆ The cable length of the braking resistor shall be less than 5 m. Otherwise, it may damage the AC
drive.
4)AC drive output terminals U/T1, V/T2, W/T3
◆ The capacitor or surge absorber cannot be connected to the output side of the AC drive. Otherwise,
it may cause frequent AC drive fault or even damage the AC drive.
If the motor cable is too long, electrical resonance will be generated due to the impact of distributed
capacitance. This will damage the motor insulation or generate higher leakage current, causing the AC
drive to trip in overcurrent protection. If the motor cable is greater than 100 m long, an AC output
reactor must be installed close to the AC drive.
5)Terminal PE
◆ This terminal must be reliably connected to the main earthing conductor. Otherwise, it may cause
electric shock, mal-function or even damage to the AC drive.
◆ Do not connect the earthing terminal to the neutral conductor of the power supply.
- 28 -
PV500&PV150A Series Solar Pumping Inverter
DI1 DI2 DI3 DI4 DI7/HI GND 485+ 485- R1A R1B R1C
+24V PLC GND Y1 +10V AI1 AI2 AO1
DI1 DI2 DI3 DI4 DI7/HI GND 485+ 485- R1A R1B R1C
+24V PLC COM Y1 +10V AI1 AI2 AO1
485+ 485- AO1 AO2 DI1 DI2 DI3 DI4 DI7/HI R2A R2B R2C
GND AI1 AI2 +10V Y2/HO COM COM PLC +24V R1A R1B R1C
Figure 2-28c PV500 Control Circuit Terminals
- 29 -
PV500&PV150A Series Solar Pumping Inverter
- 31 -
PV500&PV150A Series Solar Pumping Inverter
Att
Param. Parameter Name Setting Range Default
r
Group F00: System Parameters
Setting of User
F00.00 0~65535 0 ×
Password
0: Display all parameters
1: Only display F00.00, F00.01 and
user-defined parameters
F00.01 Display of Parameters F17.00~F17.29 0 ×
2: Only display A0-00, A0-01, and
the parameters different with
factory default
0: All parameter programmable
F00.02 Parameter Protection 1: Only F00.02 and this parameter 0 ×
programmable
0: G type (constant torque load)
F00.03 G/P type display 1: P type (variable torque load 0 ×
e.g. fan and pump)
0: No operation
1: Restore all parameters to factory
default (excluding motor
parameters)
2: Clear fault record
F00.04 Parameter Initialization 3: Back up current user parameters 0 ×
4: Restore user backup parameters
5: Restore factory default(include
motor parameter)
6: Power consumption zero
clearing(U00.35)
0: No operation
1: Upload parameter
Copy of Parameters(Need
2: Download parameter (excluding
F00.05 an uploading and 0 ×
motor parameters)
downloading module)
3: Download parameter (including
motor parameters)
0:Editable via keypad and
Parameter RS485
F00.06 0 ×
editing mode 1:Editable via keypad
2:Editable via RS485
0: Voltage/Frequency (V/F)
control
F00.08 Motor 1 control mode 1 ×
1:Sensor-less vector control 1
2: Sensor-less vector control 2
0:Digital input terminal 7
F00.09 DI7/HI input mode 0 ×
1: Pulse input
Unit's place: AI1
0: Analog input
F00.10 AI1\AI2\AI3 input mode 000 ×
1: Digital input
Decade: AI2 (same as AI1)
- 32 -
PV500&PV150A Series Solar Pumping Inverter
Hundreds place: AI3 (same as AI1)
0: Digital 0utput terminal 2
F00.11 Y2/HO input mode 0 ×
1: Pulse output
Unit' place: PWM modulation mode
0: Fixed carrier
1: Random carrier
2: Derating of fixed carrier
3: Derating of random carrier
Ten’ place: PWM modulation mode
0: Seven-segment mode
1: Five-segment mode
F00.12 PWM optimization 000 ×
2: Five-segment and
seven-segment automatic
switchover
Hundred’ place: over-modulation
adjustment
0: Invalid
1~9: 1.01~1.09 times of
over-modulation
Model
F00.13 Carrier frequency 0.700~16.000kHz △
defined
Upper carrier 8.000kH
F00.14 0.700~16.000kHz ×
frequency z
Lower carrier 2.000kH
F00.15 0.700~16.000kHz ×
frequency z
F00.16 Output voltage 5.0~150.0% 100.0% ×
0: Disabled
1: Enabled
2: AVR is disabled if the DC
F00.17 AVR bus voltage > the rated 1 ×
voltage of DC bus, and it will be
enabled if the DC bus voltage≤the
rated voltage of DC bus.
0: Run at power-on
F00.18 Fan control 1 ×
1: Fan working during running
F00.19 Factory password 0~65535 0 ×
Model
F00.20 Inverter rated power 0.2~710.0kW ⊙
defined
Model
F00.21 Inverter rated voltage 60~660V ⊙
defined
Model
F00.22 Inverter rated current 0.1~1500.0A ⊙
defined
Model
F00.23 Software version 0.00~655.35 ⊙
defined
F00.24 Dealer password 0~65535 0 ×
F00.25 Setting operation time 0~65535h(0: Invaild) 0h ×
Group F01: Frequency Command
0: Master frequency source
1: Auxiliary frequency source
2: Master +Auxiliary
Frequency source 3: Master - Auxiliary
F01.00 0 ×
selection 4: MAX{Master, Auxiliary }
5: MIN {Master, Auxiliary }
6: AI1( Master + Auxiliary)
7: AI2( Master +Auxiliary)
F01.01 Master Frequency 0:Master digital setting (F01.02) 1 ×
- 33 -
PV500&PV150A Series Solar Pumping Inverter
Command Source 1: keypad potentiometer
2: Analog input AI1
3: Communication
4: Multi-reference
5: PLC
6: Process PID output
7: X7/HI pulse input
8:AI2
9:AI3
Digital Setting of Master
F01.02 0.00~Fmax 50.00Hz △
Frequency
0: Auxiliary digital setting (F01.04)
1: keypad potentiometer
2: Analog input AI1
3: Communication
Auxiliary Frequency 4: Multi-reference
F01.03 0 ×
Command Source 5: PLC
6: Process PID output
7: X7/HI pulse input
8: Analog input AI2
9: Analog input AI3
Digital setting of
F01.04 0.00~Fmax 50.00Hz △
auxiliary frequency
Range of auxiliary 0: Relative to maximum frequency
F01.05 0 ×
frequency 1: Relative to master frequency
Coeff of auxiliary
F01.06 0.0~150.0% 100.0% △
frequency
F01.07 Jog frequency 0.00~Fmax 5.00Hz △
F01.08 Maximum frequency 20.00~600.00Hz 50.00Hz ×
Fdown~Fmax
F01.09 Upper limit frequency Lower limit frequency~maximum 50.00Hz ×
frequency
F01.10 Lower limit frequency 0.00~Fup 0.00Hz ×
Operation when 0: Run at lower limit frequency
command frequency
F01.11 1: Run at 0 Hz would be activated 0 ×
lower than lower limit
after the time delay set by F01.12
frequency
Lower limit frequency
F01.12 0.0~6000.0s 60.0s ×
running time
Up to this frequency, start
F01.13 0.00~600.00Hz 50.00Hz △
frequency compensation
Frequency compensation
F01.14 0.00~50.00Hz 0.00Hz △
per 50Hz
Group F02: Start/Stop Control
0: Keypad control (LED off)
1: Terminal control (LED on)
F02.00 Run command 0 ×
2: Communication control (LED
blinking)
0: Forward
F02.01 Running direction 0 △
1: Reverse
0: Reverse enabled
F02.02 Reverse-proof action 0 ×
1: Reverse disabled
Dead time between
F02.03 0.0~6000.0s 0.0s ×
forward and reverse
Unit’s place:
F02.04 Start mode 0000 ×
0:Start directly
- 34 -
PV500&PV150A Series Solar Pumping Inverter
1:Rotational speed track and restart
Ten’s digit:
0:Ungrounded short-circuit
detection
1:Grounding short-circuit detection
before the first starts
2:Grounding short-circuit detection
before each starts
Hundred’s digit
0:Track from zero speed
1:Track from max frequency
Thousand’s:Select if Jog function
takes the priority
0:Disable
1:Enable
Ten thousand’s place: speed
tracking direction
0: last parking direction
1: forward
2: reverse
3: Starting direction
F02.05 Start frequency 0.00~10.00Hz 0.00Hz ×
Startup frequency holding
F02.06 0.0~100.0s 0.0s ×
time
F02.07 Startup DC brakin current 0.0~150.0% 0.0% ×
F02.08 DC braking time at start 0.0~100.0s 0.0s ×
F02.09 Speed search current 0.0~180.0% 130.0% △
F02.10 Sped search decel time 0.0~10.0s 1.0s ×
F02.11 Sped search coefficient 0.01~5.00 0.30 △
0: Ramp to stop
F02.12 Stop mode 0 ×
1: Coast to stop
Initial frequency of stop
F02.13 0.01~50.00Hz 2.00Hz ×
DC braking
F02.14 Stop DC braking current 0.0~150.0% 0.0% ×
Waiting time of stop DC
F02.15 0.0~30.0s 0.0s ×
braking
F02.16 Stop DC braking time 0.0~30.0s 0.0s ×
0: Disabled
1: Enabled
F02.17 Dynamic brake 0 ×
2: Enabled at running
3: Enabled at deceleration
Voltage of dynamic
F02.18 480~800V 700V ×
braking
F02.19 Brake use ratio 5.0~100.0% 100.0% ×
0: No voltage output
F02.20 0Hz output selection 0 ×
1: Voltage output
Auto-start of power-on 0: Invalid
F02.21 0 △
again 1: Valid
Waiting time between
F02.22 auto-start and power-on 0.0~10.0s 0.5s △
again
Group F03: Accel/Decel Parameters
F03.00 Accel time 1 0.0~6000.0s 15.0s △
F03.01 Decel time 1 0.0~6000.0s 15.0s △
F03.02 Accel time 2 0.0~6000.0s 15.0s △
- 35 -
PV500&PV150A Series Solar Pumping Inverter
F03.03 Decel time 2 0.0~6000.0s 15.0s △
F03.04 Accel time 3 0.0~6000.0s 15.0s △
F03.05 Decel time 3 0.0~6000.0s 15.0s △
F03.06 Accel time 4 0.0~6000.0s 15.0s △
F03.07 Decel time 4 0.0~6000.0s 15.0s △
F03.08 Jog accel time 0.0~6000.0s 15.0s △
F03.09 Jog decel time 0.0~6000.0s 15.0s △
0: Linear Accel/Decel
F03.10 Accel/Decele curve 0 ×
1: S-curve Accel/Decel
Initial segment time of
F03.11 0.0~6000.0s 0.0s ×
acceleration of S curve
Time unit of acceleration 0: 0.1s
F03.12 0 ×
and deceleration 1: 0.01s
Frequency switchover
point
F03.13 between acceleration time 0.00~Fmax 0.00Hz ×
1
and acceleration time 2
Frequency switchover
point
F03.14 between deceleration time 0.00~Fmax 0.00Hz ×
1
and deceleration time 2
End segment time of
F03.15 0.0~6000.0s 0.0s ×
acceleration of S curve
Initial segment time of
F03.16 0.0~6000.0s 0.0s ×
deceleration of S curve
End segment time of
F03.17 0.0~6000.0s 0.0s ×
deceleration of S curve
Group F04 Digital Input
F04.00 Function of terminal DI1 00: No function 1 ×
F04.01 Function of terminal DI2 01: Running forward (FWD) 2 ×
F04.02 Function of terminal DI3 02: Running reverse (REV) 7 ×
F04.03 Function of terminal DI4 03: Three-wire control 13 ×
F04.04 Function of terminal DI5 04: JOG forward 0 ×
F04.05 Function of terminal DI6 05: JOG reverse 0 ×
F04.06 Function of terminal DI7 06: Coast to stop 0 ×
F04.07 Function of terminal AI1 07: Fault reset (RESET) 0 ×
08: Running suspended
F04.08 Function of terminal AI2 0 ×
09: External fault input
10: Terminal UP
11: Terminal DOWN
12: UP/DOWN (including ∧/∨
key) adjustment clear
13: Multi-step frequency terminal 1
14: Multi-step frequency terminal 2
15: Multi-step frequency terminal 3
16: Multi-step frequency terminal 4
F04.09 Function of terminal AI3 17: Accel/Decel time determinant 1 0 ×
18: Accel/Decel time determinant 1
19: Accel/Decel disabled(ramp stop
not inclusive)
20: Switch to auxiliary speed
setting
21: PLC status reset
22: Simple PLC paused
23: Simple PLC paused
- 36 -
PV500&PV150A Series Solar Pumping Inverter
24: PID adjustment direction
25: PID integration paused
26: PID parameter switch
27: Swing frequency pause(output
the currentfrequency)
28: Swing frequency reset(output
the central frequency)
29: Run command switched to
keypad contro
30: Run command switched to
terminal control
31: Run command switched to
communication control
32: Count input
33: Count clear
34: Length count
35: Length clear
36: DC brake input command at
Stop
37: Speed/torque control switch
38:No reverse
39:No forward
50: Special machine enable
51: Solar panel power supply
enable
52: Enter into dormancy
Filtering time of digital
F04.10 0.000~1.000s 0.010s △
input terminal
Delay time before terminal
F04.11 0.0~300.0s 0.0s △
DI1 is valid
Delay time before terminal
F04.12 0.0~300.0s 0.0s △
DI2 is valid
DI5, DI4, DI3, DI2, DI1
0: Positive logic(Terminals are on at
Terminal DI1~DI5
F04.13 0V/off at 24V) 00000 ×
positive/negative logic
1: Negative Logic (Terminals are off
at 0V/on at 24V)
AI3, AI2, AI1, DI7, DI6
Terminal DI6~AI3
F04.14 0: Positive logic 00000 ×
positive/negative logic
1: Negative Logic
0: Two-wire mode 1
FWD/REV terminal 1: Two-wire mode 2
F04.15 0 ×
control mode 2: Three-wire mode 1
3: Three-wire mode 2
Unit's place: action when stop
0: Clear
1: Holding
Decade: action on power loss
0: Clear
1: Holding
Terminal UP/DOWN Hundreds place: integral function
F04.16 frequency adjustment 00001 ×
0: No integral function
control
1: Integral function enabled
Thousand’s place:Select if it can be
reduced to negative frequency
0: Disable
1: Enable
Ten thousand’s place: Select if Jog
- 37 -
PV500&PV150A Series Solar Pumping Inverter
action can clear UP/DOWN or not
0: Not zero-clearing
1: Zero-clearing
Terminal UP/DOWN
1.00Hz/
F04.17 frequency change step 0.00~50.00Hz 0.00:Disabled △
200ms
size
0: Level effective
1: Edge trigger +Level
Terminal action selection
F04.18 effective(When power on) 0 ×
when power on
2: Edge trigger +Level
effective(Every start)
Delay time before terminal
F04.19 0.0~300.0s 0.0s △
DI1 is invalid
Delay time before terminal
F04.20 0.0~300.0s 0.0s △
DI2 is invalid
Group F05 Digital Output
F05.00 Y1 output function 0: No output 1 ×
F05.01 Y2 output function 1: Drive is running 3
F05.02 Relay 1 output function 2: Fault output 2 ×
3: Frequency-level detection FDT1
output
4: Frequency-level detection FDT2
output
5: Drive in 0Hz running 1(no output
at stop)
6: Drive in 0Hz running 2(output at
stop)
7: Upper limit frequency attained
8: Lower limit frequency attained
9: Frequency attained
10: Inverter is ready to work
11: Drive (motor) overloaded alarm
12: Inverter overheat warning
13: Current running time attained
14: Accumulative power-on time
attained
15: Consecutive running time
F05.03 Relay 2 output function attained 11 ×
16: PLC cycle completed
17: Set count value attained
18: Designated count value
attained
19: Length attained
20: Under load alarm
21:Brake output
22: DI1
23: DI2
24:When reach the range of set
frequency(FDT1)
25:Reserved
26: PID feedback lost
27: operation status (inching
without output)
28: communication setting (address
2007h)
30:Grid and solar power autoswitch
F05.04 Y1 output delay time 0.0~6000.0s 0.0s △
F05.05 Y2 output delay time 0.0~6000.0s 0.0s △
- 38 -
PV500&PV150A Series Solar Pumping Inverter
F05.06 R1 output delay time 0.0~6000.0s 0.0s △
F05.07 R2 output delay time 0.0~6000.0s 0.0s △
Unit's place: Y1
0: Positive logic
1: Negative logic
Enabled state of digital Decade: Y2 (same as unit's place)
F05.08 0000 ×
output Hundreds place: Relay 1 output
(same as unit's place)
Thousands place: Relay 2 output
(same as unit's place)
Detection width of
F05.09 0.00~20.00Hz 5.00Hz ×
frequency attained
F05.10 FDT1 upper bound 0.00~Fmax 30.00Hz ×
F05.11 FDT1 lower bound 0.00~Fmax 30.00Hz ×
F05.12 FDT2 upper bound 0.00~Fmax 30.00Hz ×
F05.13 FDT2 lower bound 0.00~Fmax 30.00Hz ×
Consecutive running
F05.14 0.0~6000.0Min 0.0:Disabled 0.0Min ×
time
Accumulative power-on
F05.15 0~65535h 0:Disabled 0h ×
time setting
Accumulative running
F05.16 0~65535h 0:Disabled 0h ×
time setting
0: Disabled
F05.17 Brake control selection 0 ×
1: Enabled
F05.18 Brake opened frequency Closed frequency ~30.00Hz 2.50Hz ×
F05.19 Brake opened current 0.0~200.0% 0.0% △
F05.20 Brake open waiting time 0.00~10.00s 0.00s ×
F05.21 Brake open operating time 0.00~10.00s 0.50s ×
F05.22 Brake closed frequency 0.00Hz~opened frequency 2.00Hz ×
F05.23 Brake close waiting time 0.00~10.00s 0.00s ×
Brake close operating
F05.24 0.00~10.00s 0.50s ×
time
Group F06 Analog and Pulse Input
Minimum input of curve 0.0%~input of inflection point1
F06.00 1.0% △
AI1 of curve AI1
Set value corresponding
F06.01 to minimum input of -100.0~100.0% 0.0% △
curve AI1
Input of inflection point Minimum input of curve AI1~Input
F06.02 100.0% △
1 of curve AI1 of inflection point 2 of curve AI1
Set value corresponding
F06.03 to input of inflection -100.0~100.0% 100.0% △
point 1 of curve AI1
Input of inflection point Input of inflection point 1 of curve
F06.04 100.0% △
2 of curve AI1 AI1~Maximum input of curve AI1
Set value corresponding
F06.05 to input of inflection -100.0~100.0% 100.0% △
point 2 of curve AI1
Maximum input of curve Input of inflection point 2 of curve
F06.06 100.0% △
AI1 AI1~100.0%
Set value corresponding
F06.07 to maximum input of -100.0~100.0% 100.0% △
curve AI1
Minimum input of curve 0.0%~input of inflection point1 of
F06.08 1.0% △
AI2 curve AI2
- 39 -
PV500&PV150A Series Solar Pumping Inverter
Set value corresponding
F06.09 to minimum input of -100.0~100.0% 0.0% △
curve AI2
Input of inflection point Minimum input of curve AI1~Input
F06.10 100.0% △
1 of curve AI2 of inflection point 2 of curve AI2
Set value corresponding
F06.11 to input of inflection -100.0~100.0% 100.0% △
point 1 of curve AI2
Input of inflection point Input of inflection point 1 of curve
F06.12 100.0% △
2 of curve AI2 AI2~Maximum input of curve AI2
Set value corresponding
F06.13 to input of inflection -100.0~100.0% 100.0% △
point 2 of curve AI2
Maximum input of curve Input of inflection point A of curve
F06.14 100.0% △
AI2 AI2~100.0%
Set value corresponding
F06.15 to maximum input of -100.0~100.0% 100.0% △
curve AI2
Minimum input of curve 0.0%~input of inflection point1
F06.16 0.0% △
AI3 of curve AI3
Set value corresponding
F06.17 to minimum input of -100.0~100.0% -100.0% △
curve AI3
Input of inflection point Minimum input of curve AI1~Input
F06.18 25.0% △
1 of curve AI3 of inflection point 2 of curve AI3
Set value corresponding
F06.19 to input of inflection -100.0~100.0% -50.0% △
point 1 of curve AI3
Input of inflection point Input of inflection point 1 of curve
F06.20 75.0% △
2 of curve AI3 AI3~Maximum input of curve AI3
Set value corresponding
F06.21 to input of inflection -100.0~100.0% 25.0% △
point 2 of curve AI3
Maximum input of curve Input of inflection point A of curve
F06.22 100.0% △
AI3 AI3~100.0%
Set value corresponding
F06.23 to maximum input of -100.0~100.0% 100.0% △
curve AI3
Minimum input of curve 0.0~Maximum input of curve
F06.24 0.5% △
keypad potentiometer keypad potentiometer
Set value corresponding
to minimum input of
F06.25 -100.0~100.0% 0.0% △
curve keypad
potentiometer
Maximum input of curve Minimum input of curve keypad
F06.26 99.9% △
keypad potentiometer potentiometer~100.0
Set value corresponding
to maximum input of
F06.27 -100.0~100.0% 100.0% △
curve keypad
potentiometer
F06.28 AI1 terminal filtering time 0.000~10.000s 0.100s △
F06.29 AI2 terminal filtering time 0.000~10.000s 0.100s △
F06.30 AI3 terminal filtering time 0.000~10.000s 0.100s △
Keypad potentiometer
F06.31 0.000~10.000s 0.100s △
filtering time
F06.32 Minimum input of curve HI 0.00 kHz~Maximum input of curve 0.00kHz △
- 40 -
PV500&PV150A Series Solar Pumping Inverter
HI
Set value corresponding
F06.33 to minimum input of curve -100.0~100.0% 0.0% △
HI
Maximum input of curve Minimum input of curve HI~ 50.00kH
F06.34 △
HI 100.00kHz z
Set value corresponding
F06.35 to maximum input of curve -100.0~100.0% 100.0% △
HI
F06.36 HI terminal filtering time 0.000~10.000s 0.100s △
Group F07 Analog and Pulse Output
F07.00 AO1 output function 00: No output 1 ×
F07.01 AO2 output function 01: Output frequency 2 ×
02: Command frequency
03: Output current
04: Output voltage
05: Output power
06: Bus voltage
07: +10V
Y2/HO output function 08: keypad potentiometer
F07.02 3 ×
(when used as HO) 09: AI1
10: AI2
11: AI3
12: HI
13: Output torque
14: Ao communication given 1
15: Ao communication given 2
F07.03 AO1 offset -100.0~100.0% 0.0% △
F07.04 AO1 gain -2.000~2.000 1.000 △
F07.05 AO1 filtering time 0.000~10.000s 0.000s △
F07.06 AO2 offset -100.0~100.0% 0.00% △
F07.07 AO2 gain -2.000~2.000 1.000 △
F07.08 AO2 filtering time 0.000~10.000s 0.000s △
HO maximum output 50.00kH
F07.09 0.01~100.00kHz △
pulse frequency z
F07.10 HO output filtering time 0.000~10.000s 0.010s △
Group F08 Parameters of Motor 1
0: Three phase asynchronous
motors
1: Synchronous motors
2: Single phase asynchronous
F08.00 Motor 1 type selection motors(Remove capacity) 0 ×
3: Single phase asynchronous
motors(No need to remove
capacity)
Model
F08.01 Power rating of motor 1 0.1~1000.0kW ×
defined
Model
F08.02 Rated voltage of motor 1 60~660V ×
defined
Model
F08.03 Rated current of motor 1 0.1~1500.0A ×
defined
Rated frequency of Model
F08.04 20.00~Fmax ×
motor 1 defined
Model
F08.05 Rated speed of motor 1 1~30000 ×
defined
F08.08 Stator resistance R1 of 0.001~65.535Ω Model ×
- 41 -
PV500&PV150A Series Solar Pumping Inverter
async motor 1 defined
Rotor resistance R2 of Model
F08.09 0.001~65.535Ω ×
async motor 1 defined
Leakage inductance L1 Model
F08.10 0.01~655.35mH ×
of async motor 1 defined
Mutual inductance L2 of Model
F08.11 0.1~6553.5mH ×
asynchronous motor 1 defined
No-load current of Model
F08.12 0.1~1500.0A ×
async motor 1 defined
Field weakening coeff 1
F08.13 0.0~100.0 87% ×
of async motor 1
Field weakening coeff 2
F08.14 0.0~100.0 75% ×
of async motor 1
Field weakening coeff 3
F08.15 0.0~100.0 70% ×
of async motor 1
Stator resistance of sync Model
F08.16 0.001~65.535Ω ×
motor defined
Direct axis inductance of Model
F08.17 0.01~655.35mH ×
sync motor defined
Quadrature axis Model
F08.18 0.01~655.35mH ×
inductance of sync motor defined
Model
F08.19 Back EMF of sync motor 0~65535V ×
defined
Installation angle of
F08.20 0.0~359.9° 0.0° ×
encoder
F08.21 Motor’s pole number 0~1000 4 ⊙
Find encoder origin at 0: Not find
F08.22 1 ×
begining 1: Find
0: No autotuning
F08.30 Autotuning of motor 1 1: Static autotuning of motor 0 ×
2: Rotary autotuning of motor
Group F09 V/f Control Parameters of Motor 1
00: Linear V/f
01: Multi-stage V/f
02:1.2nd power V/F
03:1.4th power V/F
04:1.6th power V/F
05:1.8th power V/F
06: 2.0nd power V/F
F09.00 V/f curve setting 0 ×
07: V/F complete separation
08: V/F half separation
09: 1.2 power inverse curve V/F
10: 1.4 power inverse curve V/F
11: 1.6 power inverse curve V/F
12: 1.8 power inverse curve V/F
13: 2.0 power inverse curve V/F
0.1%–30.0% 0.0% (fixed torque
F09.01 Torque boost 0.0% △
boost)
Cut-off frequency of
F09.02 0.00~Fmax 50.00Hz △
torque boost
Multi-point V/F frequency
F09.03 0.00~F09.05 0.00Hz △
1(F1)
Multi-point V/F voltage 1
F09.04 0.0~100.0 5.0% △
(V1)
Multi-point V/F frequency
F09.05 F09.03~F09.05 5.00Hz △
2(F2)
- 42 -
PV500&PV150A Series Solar Pumping Inverter
Multi-point V/F voltage 2
F09.06 0.0~100.0 14.0% △
(V2)
Multi-point V/F frequency
F09.07 F09.05~F09.09 25.00Hz △
3(F3)
Multi-point V/F voltage 3
F09.08 0.0~100.0 50.0% △
(V3)
Multi-point V/F frequency
F09.09 F09.07~rated motor frequency 50.00Hz △
4(F4)
Multi-point V/F voltage 4
F09.10 0.0~100.0 Ue=100.0% 100.0% △
(V4)
V/F slip compensation
F09.11 0.0~300.0% 80.0% △
gain
Stator voltagedrop
F09.12 0.0~200.0% 100.0% △
compensation gain
F09.13 Excitation boost gain 0.0~200.0% 100.0% △
F09.14 Oscillation Suppression 0.0~300.0% 100.0% △
0: Digital setting (F09.16)
1: keypad potentiometer
2: AI1
Voltage source for V/F 3: Multi-reference
F09.15 0 ×
separation 4: Pulse setting ( DI7/HI )
5: PID
6: AI2
7: AI3
Voltage digital setting for
F09.16 0 V to rated motor voltage 0.0% △
V/F separation
0.0~6000.0s
Voltage rise time of V/F It indicates the time for the
F09.17 0.1s △
separation voltage rising from 0 V to rated
Motor voltage.
IQ filtering time below
F09.18 F09.19~3000ms 500ms ×
VVF 0.5Hz
IQ filtering time above
F09.19 1ms~F09.18 100ms ×
VVF 2Hz
F09.20 Forward torque correction 0.0~5.0% 0.0% △
F09.21 Reverse torque correction 0.0~5.0% 1.0% △
PMSM acceleration
F09.22 current compensation 0.0~200.0% 0.0% △
setting
PMSM compensation time
F09.23 decreased after 0.0~100.0s 2.0s △
acceleration
PMSM ID current value
F09.24 will be maintained after 0.0~200.0% 0.0% △
accelerating.
Group F10 Vector Control Parameters of Motor 1
0: speed control
F10.00 Speed/torque control 0 ×
1: torque control
ASR low-speed
F10.01 0.0~100.0 15.0 △
proportional gain Kp1
ASR low-speed
F10.02 0.001~30.000s 0.050s △
integration time Ti1
ASR switching
F10.03 0.00~F10.06 5.00Hz △
frequency 1
ASR high-speed
F10.04 1~100.0 10.0 △
proportional gain Kp2
- 43 -
PV500&PV150A Series Solar Pumping Inverter
ASR high-speed
F10.05 0.001~30.000s 0.100s △
integration time Ti2
ASR switching
F10.06 F10.03~Fmax 10.00Hz △
frequency 2
F10.07 ASR input filtering time 0.0~500.0ms 3.0ms △
F10.08 ASR output filtering time 0.0~500.0ms 0.0ms △
F10.09 Vector control slip gain 50~200% 100% △
Digital setting of torque
F10.10 upper limit in speed 80.0~200.0% 165.0% ×
control mode
Excitation adjustment
F10.11 0.00~10.00 0.50 △
proportional gain Kp1
Excitation adjustment
F10.12 0.0~3000.0ms 10.0ms △
integral gain Ti1
Torque adjustment
F10.13 0.00~10.00 0.50 △
proportional gain Kp2
Torque adjustment
F10.14 0.0~3000.0ms 10.0ms △
integral gain Ti2
F10.15 Excitation gain coefficient 50.0~200% 100% △
0:Set by F10.17
1:Keypad potentiometer
2:AI1
Torque setting source
F10.16 3:AI2 0 ×
under torque control
4:AI3
5:Pulse setting ( DI7/HI )
6:Communication setting
F10.17 Digital setting of torque -200.0~200.0% 50.0% △
Forward speed limited
F10.18 0.00~Fmax 50.00Hz △
value under torque control
Reverse speed limited
F10.19 0.00~ Fmax 50.00Hz △
value under torque contro
F10.20 Set torque accel time 0.0~6000.0s 0.0s △
F10.21 Set torque decel time 0.0~6000.0s 0.0s △
Static friction torque
F10.22 0.0~100.0% 5.00% △
compensation
Static friction frequency
F10.23 0.00~20.00Hz 1.00Hz △
range
Sliding friction torque
F10.24 0.0~100.0% 1.0% △
compensation
0: Optimization method 1
F10.25 SVC optimization method 1: Optimization method 2 1 ×
2: Optimization method 3
0:Set by F10.18 & F10.19
1:Keypad potentiometer
Max Frequency source 2:AI1
F10.26 0 ×
under torque control 3:AI2
4:AI3
5:Pulse setting ( DI7/HI )
PMSM Start excitation
F10.27 0.0~150.0% 50% ×
current
PMSM flux-weakening 0: Invalid
F10.28 1 ×
control 1: Valid
PMSM flux-weakening
F10.29 70.0~100.0% 95% △
voltage
- 44 -
PV500&PV150A Series Solar Pumping Inverter
PMSM r flux-weakening
F10.30 0.0~500.0% 50.0% △
gain Kp
PMSM flux-weakening
F10.31 0.00~60.00s 0.50s △
integral Ti
PMSM flux-weakening
F10.32 0.0~200.0% 100.0% △
limit
PMSM excitation current
F10.33 F10.34~600.00Hz 15.00Hz △
frequency high point
PMSM excitation current
F10.34 0.0~F10.33 10.00Hz △
frequency low point
PMSM excitation current
F10.35 0.0~10.0s 1.0s △
conversion delay
PMSM speed estimation
F10.36 0.00~10.00 2.00 △
Kp
PMSM speed estimation
F10.37 0.1~1000.0ms 20.0ms △
Ti
Group F11 Protection Parameters
0: Current limit disabled
F11.00 Current limit control 1: Current limit mode 1 2 ×
2: Current limit mode 2
F11.01 Current limit 100.0~200.0% 150.0% ×
Frequency decreasing
F11.02 time(limit current in 0.0~6000.0s 5.0s △
constant speed operation)
Current limit mode 2
F11.03 0.1~100.0% 3.0% △
proportion gain
Current limit mode 2
F11.04 0.00~10.00s 10.00s △
integral time
0: Overvoltage stall disabled
F11.05 Overvoltage Stall Control 1: Overvoltage stall mode 1 1 ×
2: Overvoltage stall mode 2
F11.06 Overvoltage stall voltage 600~800V 730V ×
Overvoltage Stall
F11.07 0.0~100.0% 50.0% △
Mode 2 Proportion Gain
Overvoltage stall mode 2
F11.08 0.00~50.00Hz 5.00Hz ×
frequency limit
Unit's place: Bus undervoltage
0: Fault reported and coast to stop
1: Stop according to the stop mode
2: Fault reported but continue to run
3: Fault protection disabled
Ten's digit :Power input phase
Loss (Err09)(Same as unit's
place )
F11.10 Protection action 1 03330 ×
Hundred's digit :Power output
phase loss(Err10)(Same as unit's
place )
Thousand's digit:Motor overload
(Err11)(Same as unit's place )
Ten thousand's digit:Inverter
overload(Err11)(Same as unit's
place )
External equipment fault(Err13)
0: Fault reported and coast to stop
F11.11 Protection action 2 00000 ×
1: Stop according to the stop mode
2: Fault reported but continue to run
- 45 -
PV500&PV150A Series Solar Pumping Inverter
Ten's digit: EEPROM read/write
fault (Err15) (Same as unit's place)
Hundred's digit: Communication
overtime error (Err18) (Same as
unit's place)
Thousand's digit: PID feedback loss
(Err19) (Same as unit's place)
Ten thousand's digit: Continuous
running time reached (Err20)
(Same as unit's place)
Unit's place: Module temperature
detection disconnection(Err24)
0: Fault reported and coast to stop
F11.12 Protection action 3 1: Stop according to the stop mode 00030 ×
2: Fault reported but continue to run
Ten's digit: Load becoming 0
(Err25) (Same as unit's place)
0: Current running frequency
1: Set frequency
Frequency selection for
2: Frequency upper limit
F11.14 continuing to run upon 1 ×
3: Frequency lower limit
fault
4: Backup frequency upon
abnormality
Backup frequency upon
F11.15 0.00~Fmax 0.00Hz ×
abnormality
Motor overload protection
F11.17 30.0~300.0s 60.0s ×
time
Unit's place: detection option:
0: Always detect
1: Detect at constant speed only
Ten's digit : compared object
0: Rated current of motor
1: Rated current of drive
Hundred’s digit: Fault reported
0:No fault reported
1:Fault reported
Thousand’s digit: whether to
F11.18 Overload alarm decelerate or not when overload 00010 ×
alarm
0: No deceleration
1: Deceleration
Ten thousand’s place: Set overload
level mode
0:F11.19 set
1:F11.19 * VP
2:F11.19 * AI1
3:F11.19 * AI2
4:F11.19 * AI3
F11.19 Overload alarm threshold 20.0~200.0% 130.0% ×
Overload alarm
F11.20 activated time that 0.1~60.0s 5.0s ×
exceeding threshold
Inverter overheat warning Model
F11.21 50~overheat Temperature ×
threshold defined
Detection level of load
F11.22 5.0~100.0% 20.0% ×
loss
F11.23 Detection time of load loss 0.1~60.0s 5.0s ×
- 46 -
PV500&PV150A Series Solar Pumping Inverter
Action selection at 0: Disabled
F11.24 instantaneous power 1: Deceleration 0 ×
failure 2: Bus voltage constant control
Decel time at
F11.25 instantaneous power 0.0~6000.0s 5.0s △
failure
0: Disabled
F11.26 Rapid current limit 0 ×
1: Enabled
Times of automatic
F11.27 0~20 0 ×
trip(fault) reset
Interval of automatic
F11.28 0.1~100.0s 1.0s ×
trip(fault) reset
DO action during fault 0: Not act
F11.29 0 ×
auto reset 1: Act
Instantaneous power
F11.30 60.0%~Recovery voltage 80.0% △
off bus voltage
Instantaneous power off
F11.31 Power off voltage~100.0% 85.0% △
recovery voltage
Instantaneous power off
F11.32 0.01~10.00s 0.10s △
voltage detection time
Instantaneous power off
F11.33 0.1~100.0% 40.0% △
Kp
Instantaneous power off 0.00~10.00s (0.00:Integration
F11.34 0.10s △
integration time Ti invalid)
0:None
Motor temperature sensor 1:PT100
F11.35 0 ×
type 2:PT1000
3:KTY84
Zero drift value of motor
F11.36 -100~100℃ 0 △
temperature sensor
F11.37 Reserved
Motor temperature
F11.38 0~200℃ 90℃ △
warning action threshold
Motor temperature
F11.39 protection action 0~200℃ 110℃ △
threshold
Group F12: Multi-Reference and Simple PLC Function
F12.00 Reference 0 -100.0~100.0% 0.0% △
F12.01 Reference 1 -100.0~100.0% 0.0% △
F12.02 Reference 2 -100.0~100.0% 0.0% △
F12.03 Reference 3 -100.0~100.0% 0.0% △
F12.04 Reference 4 -100.0~100.0% 0.0% △
F12.05 Reference 5 -100.0~100.0% 0.0% △
F12.06 Reference 6 -100.0~100.0% 0.0% △
F12.07 Reference 7 -100.0~100.0% 0.0% △
F12.08 Reference 8 -100.0~100.0% 0.0% △
F12.09 Reference 9 -100.0~100.0% 0.0% △
F12.10 Reference 10 -100.0~100.0% 0.0% △
F12.11 Reference 11 -100.0~100.0% 0.0% △
F12.12 Reference 12 -100.0~100.0% 0.0% △
F12.13 Reference 13 -100.0~100.0% 0.0% △
F12.14 Reference 14 -100.0~100.0% 0.0% △
F12.15 Reference 15 -100.0~100.0% 0.0% △
F12.16 Reference 0 source 0: Digital setting(F12.00) 0 ×
- 47 -
PV500&PV150A Series Solar Pumping Inverter
1: keypad potentiometer
2: AI1
3: Process PID output
4: X7/HI pulse input
5: AI2
6: AI3
Unit's place: PLC running mode
0: Stop after a single cycle
1: Continue to run with the last
frequency after a single cycle
2: Repeat cycles
Decade: started mode
0: Continue to run from the step of
stop (or fault)
1: Run from the first step “multi-step
frequency 0”
Running mode of simple 2: Run from the eighth step
F12.17 0000 ×
PLC “multi-step frequency 8”
3: Run from the fifteenth step
“multi-step frequency 15”
Hundreds place:power loss
memory
0: Memory disabled on power loss
1: Memory enabled on power loss
Thousands place: unit of simple
PLC running time
0: Second (s)
1: Minute (min)
F12.18 Running time of step 0 0.0~6000.0s(h) 0.0s(h) △
F12.19 Running time of step 1 0.0~6000.0s(h) 0.0s(h) △
F12.20 Running time of step 2 0.0~6000.0s(h) 0.0s(h) △
F12.21 Running time of step 3 0.0~6000.0s(h) 0.0s(h) △
F12.22 Running time of step 4 0.0~6000.0s(h) 0.0s(h) △
F12.23 Running time of step 5 0.0~6000.0s(h) 0.0s(h) △
F12.24 Running time of step 6 0.0~6000.0s(h) 0.0s(h) △
F12.25 Running time of step 7 0.0~6000.0s(h) 0.0s(h) △
F12.26 Running time of step 8 0.0~6000.0s(h) 0.0s(h) △
F12.27 Running time of step 9 0.0~6000.0s(h) 0.0s(h) △
F12.28 Running time of step 10 0.0~6000.0s(h) 0.0s(h) △
F12.29 Running time of step 11 0.0~6000.0s(h) 0.0s(h) △
F12.30 Running time of step 12 0.0~6000.0s(h) 0.0s(h) △
F12.31 Running time of step 13 0.0~6000.0s(h) 0.0s(h) △
F12.32 Running time of step 14 0.0~6000.0s(h) 0.0s(h) △
F12.33 Running time of step 15 0.0~6000.0s(h) 0.0s(h) △
Acceleration/deceleration
F12.34 time of simple PLC 0~3 0 △
reference 0
Acceleration/deceleration
F12.35 time of simple PLC 0~3 0 △
reference 1
Acceleration/deceleration
F12.36 time of simple PLC 0~3 0 △
reference 2
F12.37 Acceleration/deceleration 0~3 0 △
- 48 -
PV500&PV150A Series Solar Pumping Inverter
time of simple PLC
reference 3
Acceleration/deceleration
F12.38 time of simple PLC 0~3 0 △
reference 4
Acceleration/deceleration
F12.39 time of simple PLC 0~3 0 △
reference 5
Acceleration/deceleration
F12.40 time of simple PLC 0~3 0 △
reference 6
Acceleration/deceleration
F12.41 time of simple PLC 0~3 0 △
reference 7
Acceleration/deceleration
F12.42 time of simple PLC 0~3 0 △
reference 8
Acceleration/deceleration
F12.43 time of simple PLC 0~3 0 △
reference 9
Acceleration/deceleration
F12.44 time of simple PLC 0~3 0 △
reference 10
Acceleration/deceleration
F12.45 timeof simple PLC 0~3 0 △
reference 11
Acceleration/deceleration
F12.46 time of simple PLC 0~3 0 △
reference 12
Acceleration/deceleration
F12.47 time of simple PLC 0~3 0 △
reference 13
Acceleration/deceleration
F12.48 time of simple PLC 0~3 0 △
reference 14
Acceleration/deceleration
F12.49 time of simple PLC 0~3 0 △
reference 15
Unit’s digit: Action selection when
power off
0:Zero clearing when power off
UP/DOWN function
1:Hold when power off
F12.50 selection of Multi- 00 ×
Ten’s digit: select if it can be
reference
reduced to negative
0:Disable
1:Enable
UP/DOWN speed of
F12.51 0.0~100.0% (0.0%Invalid) 0.0% △
Multi-reference
Group F13 Process PID
0: F13.01 digital setting
1:keypad potentiometer
2: AI1
3: Communication
F13.00 PID setting 0 ×
4: Multi-Reference
5: DI7/HI pulse input
6: AI2
7: AI3
- 49 -
PV500&PV150A Series Solar Pumping Inverter
F13.01 PID digital setting 0.0~100.0% 50.0% △
0: AI1
1: AI2
2: Communication
3: AI1+AI2
F13.02 PID feedback 4: AI1-AI2 0 ×
5: Max{AI1,AI2}
6: Min{AI1,AI2}
7: DI7/HI pulse input
8: AI3
PID setting feedback
F13.03 0.0~6000.0 100.0 △
range
0: Forward action
F13.04 PID action direction 0 ×
1: Reverse action
Filtering time of PID
F13.05 0.000~10.000s 0.000s △
setting
Filtering time of PID
F13.06 0.000~10.000s 0.000s △
feedback
Filtering time of PID
F13.07 0.000~10.000s 0.000s △
output
F13.08 Proportional gain Kp1 0.0~100.0 1.0 △
F13.09 Integration time Ti1 0.01~10.00s 0.10s △
F13.10 Differential time Td1 0.000~10.000s 0.000s △
F13.11 Proportional gain Kp2 0.0~100.0 1.0 △
F13.12 Integration time Ti2 0.01~10.00s 0.10s △
F13.13 Differential time Td2 0.000~10.000s 0.000s △
0: No switch, determined by
parameters Kp1, Ti1 and Td1
F13.14 PID parameter switch 1: Auto switch on the basis of input 0 ×
offset
2: Switched by terminal
PID parameter switchover
F13.15 0.0~100.0% 20.0% ×
deviation 1
PID parameter switchover
F13.16 0.0~100.0% 80.0% ×
deviation 2
F13.17 PID offset limit 0.0~100.0% 0.0% ×
Unit's digit (Whether to stop
integral operation when the output
reaches the limit)
0: Continue integral operation
F13.18 PID integral property 00 ×
1: Stop integral operation
Ten's digit (Integral separated)
0: Invalid
1: Valid
F13.19 PID differential limit 0.0~100.0% 0.5% ×
F13.20 PID initial value 0.0~100.0% 0.0% ×
Holding time of PID
F13.21 0.0~6000.0s 0.0s ×
initial value
PID output frequency lower limit~
PID output frequency
F13.22 100.0%(100.0% corresponds to 100.0% ×
upper limit
maximum frequency )
PID output frequency –100.0%~PID output frequency
F13.23 0.0% ×
lower limit lower limit
Down limit of
F13.24 0.1~100.0% 0.0% ×
PID feedback loss
- 50 -
PV500&PV150A Series Solar Pumping Inverter
0.0%: Not judging feedback loss
Detection time for
F13.25 down limit of PID 0.0~30.0s 1.0s ×
feedback loss
Unit’s digit: PID operation selection
when stop
0:Do not operate when stop
1:Operate when stop
Ten’s digit: output is limited by
output frequency
0:No limited
1:limited
Hundred’s digit: UP/DOWN digital
given of PID
F13.26 PID operation selection 00000 ×
0:Zero clearing when power off
1:Hold when power off
Thousand’s place: PID feedback
loss detection mode
0:No detection when stop
1:Do detection when stop
Ten thousand’s place: Action when
PID feedback loss
0:Report fault
1:Ramp to stop
UP/DWON speed of PID
F13.27 0.0~100.0% (0.0% Invalid) 0.0% △
digital given
Up limit of 0.1~100.0%
F13.28 100.0% ×
PID feedback loss 0.0%: Not judging feedback loss
Detection time for
F13.29 up limit of PID feedback 0.0~30.0s 1.0s ×
loss
0:F13.22
1:F13.22* keyboard potentiometer
PID upper limit source 2:F13.22*AI1
F13.30 0 ×
selection 3:F13.22*AI2
4:F13.22 * HI (pulse input)
5:F13.22*AI3
0:F13.23
1:F13.23* keyboard potentiometer
PID lower limit source 2:F13.23*AI1
F13.31 0 ×
selection 3:F13.23*AI2
4:F13.23 * HI (pulse input)
5:F13.23*AI3
Group F14: Swing Frequency, Fixed Length , Wakeup and Count
0: Relative to the setting
Swing frequency setting frequency
F14.00 0 ×
mode 1: Relative to the maximum
frequency
Swing frequency
F14.01 0.0~100.0% 0.0% △
amplitude
Jump frequency
F14.02 0.0~50.0% 0.0% △
amplitude
Rising Time of Swing
F14.03 0.0~6000.0s 5.0s △
frequency
Dropping Time of Swing
F14.04 0.0~6000.0s 5.0s △
frequency
F14.05 Set length 0m~65535m 1000m ×
- 51 -
PV500&PV150A Series Solar Pumping Inverter
Number of pulses per
F14.06 0.1~6553.5 100.0 ×
meter
Unit’s place: stop when the length
reaches
0: Not stop
1: Stop
Ten’s place: length calculation
Command when the
F14.07 method 00 ×
length attained
0: pulse by pulse
1: Reference maximum frequency
2: Refer to Ai1 channel
3: Refer to AI2 channel
4: Refer to AI3 channel
F14.08 Set count value 1~65535 1000 ×
F14.09 Designated count value 1~65535 1000 ×
Dormant frequency (F14.12)~
F14.10 Wakeup frequency 0.00Hz △
Fmax
F14.11 Wakeup delay time 0.0~6000.0s 0.0s △
F14.12 Dormant frequency 0.00~Wakeup frequency 0.00Hz △
F14.13 Dormant delay time 0.0~6000.0s 0.0s △
0: Frequency
F14.14 Wake up mode selection 0 ×
1: Pressure
0: Frequency
F14.15 Dormancy mode selection 0 ×
1: Pressure
Unit’s place: pressure feedback
channel
0: AI1
1: AI2
2: DI7/HI pulse input
F14.16 Voltage feedback source 3: AI3 00 ×
Ten’s place: Dormancy mode
0:Dormancy on high pressure and
wake up on low pressure
1:Dormancy on low pressure and
wake up on high pressure
F14.17 Wake up pressure 0.0%~Dormancy pressure 10.0% △
F14.18 Dormancy pressure Wake up pressure~100.0% 50.0% △
Group F15: Communication Parameters
0: 4800bps
1: 9600bps
2: 19200bps
F15.00 Baud rate 1 ×
3: 38400bps
4: 57600bps
5: 115200bps
No check, data format (1-8-N-2) for
RTU
1: Even parity check, data format
(1-8-E-1) for RTU
F15.01 Data format 0 ×
2: Odd Parity check, data format
(1-8-O-1) for RTU
3: No check, data format(1-8-N-1)
for RTU
F15.02 Local address 1~247 0: Broadcast address 1 ×
F15.03 Communication timeout 0.0~60.0s 0.0s ×
F15.04 Response time delay 0~200ms 1ms ×
F15.05 Master-slave 0:The inverter is the slave 0 ×
- 52 -
PV500&PV150A Series Solar Pumping Inverter
Communication Mode 1:The inverter is the master
The Master 0: Set frequency
F15.06 Communication 0 ×
1: Current running frequency
Sending Data
Message return when 0: No return
F15.07 1
communication error 1: Return
0: Positive and negative
F15.08 U group return value 0 △
1: Absolute value
Group F16 Keys and Display of Keypad Parameters
0: No function
1: Jog
F16.00 MF.K key setting 2: Forward/reverse switchover 1 ×
3: Run command sources shifted
4: Jog reverse
Unit’s digit: Function selection of
STOP/RESET key
0: stop function of STOP/RESET
key is valid only in keyboard
operation mode
1: Stop function of STOP/RES key
is valid in any operation mode
Keyboard operation Ten’s digit: Speed display(U00.05)
F16.01 001 ×
display 0: According to the actual speed
1: Multiply frequency by speed
coefficient(F16.11)
Hundred’s digit: Decimal places
0: No decimal places
1: One decimal places
2: Two decimal places
3: Three decimal places
0: Not locked
1: Full locked
2: Keys locked other than RUN,
F16.02 Keys locked option STOP/RST 0 ×
3: Keys locked other than
STOP/RST
4: Keys locked other than >>
LED displayed
0~99(correspond U00.00~
F16.03 parameters setting 1 on 0 △
running status U00.99)
LED displayed
0~99(correspond U00.00~
F16.04 parameters setting 2 on 6 △
running status U00.99)
LED displayed
0~99(correspond U00.00~
F16.05 parameters setting 3 on 3 △
U00.99)
running status
LED displayed
0~99(correspond U00.00~
F16.06 parameters setting 4 on 2 △
U00.99)
running status
LED displayed
0~99(correspond U00.00~
F16.07 parameters setting 1 on 1 △
stop status U00.99)
LED displayed
0~99(correspond U00.00~
F16.08 parameters setting 2 on 6 △
stop status U00.99)
LED displayed 0~99(correspond U00.00~
F16.09 15 △
parameters setting 3 on U00.99)
- 53 -
PV500&PV150A Series Solar Pumping Inverter
stop status
LED displayed
0~99(correspond U00.00~
F16.10 parameters setting 4 on 16 △
U00.99)
stop status
F16.11 Speed display coefficient 0.00~100.00 1.00 △
F16.12 Power display coefficient 0.0~300.0% 100.0% △
Display error between
F16.13 0.00Hz~5.00Hz 0.10Hz △
U00.00 and U00.01
Group F17 User-defined Display Parameters
User-defined Display
F17.00 00.00~49.99 00.03 △
Parameter 0
User-defined Display
F17.01 00.00~49.99 01.01 △
Parameter 1
User-defined Display
F17.02 00.00~49.99 01.02 △
Parameter 2
User-defined Display
F17.03 00.00~49.99 01.08 △
Parameter 3
User-defined Display
F17.04 00.00~49.99 01.09 △
Parameter 4
User-defined Display
F17.05 00.00~49.99 02.00 △
Parameter 5
User-defined Display
F17.06 00.00~49.99 02.01 △
Parameter 6
User-defined Display
F17.07 00.00~49.99 02.12 △
Parameter 7
User-defined Display
F17.08 00.00~49.99 03.00 △
Parameter 8
User-defined Display
F17.09 00.00~49.99 03.01 △
Parameter 9
User-defined Display
F17.10 00.00~49.99 04.00 △
Parameter 10
User-defined Display
F17.11 00.00~49.99 04.01 △
Parameter 11
User-defined Display
F17.12 00.00~49.99 04.02 △
Parameter 12
User-defined Display
F17.13 00.00~49.99 04.03 △
Parameter 13
User-defined Display
F17.14 00.00~49.99 05.02 △
Parameter 14
User-defined Display
F17.15 00.00~49.99 08.01 △
Parameter 15
User-defined Display
F17.16 00.00~49.99 08.02 △
Parameter 16
User-defined Display
F17.17 00.00~49.99 08.03 △
Parameter 17
User-defined Display
F17.18 00.00~49.99 08.04 △
Parameter 18
User-defined Display
F17.19 00.00~49.99 08.05 △
Parameter 19
User-defined Display
F17.20 00.00~49.99 08.30 △
Parameter 20
User-defined Display
F17.21 00.00~49.99 11.10 △
Parameter 21
User-defined Display
F17.22 00.00~49.99 13.00 △
Parameter 22
User-defined Display
F17.23 00.00~49.99 13.01 △
Parameter 23
- 54 -
PV500&PV150A Series Solar Pumping Inverter
User-defined Display
F17.24 00.00~49.99 13.02 △
Parameter 24
User-defined Display
F17.25 00.00~49.99 13.08 △
Parameter 25
User-defined Display
F17.26 00.00~49.99 13.09 △
Parameter 26
User-defined Display
F17.27 00.00~49.99 00.00 △
Parameter 27
User-defined Display
F17.28 00.00~49.99 00.00 △
Parameter 28
User-defined Display
F17.29 00.00~49.99 00.00 △
Parameter 29
F22Group:Virtual IO
Function selection of
F22.00 The same as function code F04.00 0 ×
virtual VDI1 terminal
Function selection of
F22.01 The same as function code F04.00 0 ×
virtual VDI2 terminal
Function selection of
F22.02 The same as function code F04.00 0 ×
virtual VDI3 terminal
Function selection of
F22.03 The same as function code F04.00 0 ×
virtual VDI4 terminal
Function selection of
F22.04 The same as function code F04.00 0 ×
virtual VDI5 terminal
(VDI5、VDI4、VDI3、VDI2、VDI1)
Valid status setting mode 0:Validity of VDI depends on virual
F22.05 VDOx’s status 00000 ×
of virtual VDI terminals
1:Validity of VDI set by function
code F22.06
(VDI5、VDI4、VDI3、VDI2、VDI1)
Settings of virtual VDI
F22.06 0: Invalid 00000 △
terminal status
1: Valid
0 : Internal short circuited to
Function selection of
physics DIx
F22.07 virtual VDO1 terminals 0 △
Other: The same as function code
output
F05.00
0 : Internal short circuited to
Function selection of
physics DIx
F22.08 virtual VDO2 terminals 0 △
Other: The same as function code
output
F05.00
0 : Internal short circuited to
Function selection of
physics DIx
F22.09 virtual VDO3 terminals 0 △
Other: The same as function code
output
F05.00
0 : Internal short circuited to
Function selection of
physics DIx
F22.10 virtual VDO4 terminals 0 △
Other: The same as function code
output
F05.00
0 : Internal short circuited to
Function selection of
physics DIx
F22.11 virtual VDO5 terminals 0 △
Other: The same as function code
output
F05.00
Virtual VDO1 output
F22.12 0.0s~6000.0s 0.0s △
delay time
Virtual VDO2 output
F22.13 0.0s~6000.0s 0.0s △
delay time
Virtual VDO3 output
F22.14 0.0s~6000.0s 0.0s △
delay time
- 55 -
PV500&PV150A Series Solar Pumping Inverter
Virtual VDO4 output
F22.15 0.0s~6000.0s 0.0s △
delay time
Virtual VDO5 output
F22.16 0.0s~6000.0s 0.0s △
delay time
VDO output terminal VDO5、VDO4、VDO3、VDO2、VDO1
F22.17 positive and negative 0: Positive logic 00000 △
logic 1: Negtive logic
U00 Group: Status Monitoring
U00.00 Output Frequency 0.00~Fup 0.00Hz ⊙
U00.01 Setting Frequency 0.00~Fmax 0.00Hz ⊙
Actual value of output
U00.02 0~660V 0.0V ⊙
voltage
Actual value of output
U00.03 0.0~3000.0A 0.0A ⊙
current
U00.04 Output Power -3000.0~3000.0kW 0.0kW ⊙
U00.05 Output Rotation-rate 0~60000rpm 0rpm ⊙
U00.06 DC Bus Voltage 0~1200V 0V ⊙
Synchronization
U00.07 0.00~Fup 0.00Hz ⊙
Frequency
U00.08 PLC Stage 1~15 1 ⊙
U00.09 Program Running Time 0.0~6000.0s(h) 0.0s(h) ⊙
U00.10 PID Given 0~60000 0 ⊙
U00.11 PID Arithmetic Feedback 0~60000 0 ⊙
U00.12 DI1~DI5 Input Status DI5 DI4 DI3 DI2 DI1 00000 ⊙
U00.13 DI6~DI7 Input Status DI7 DI6 00 ⊙
U00.14 Digital Output Status R2R1 Y2 Y1 0000 ⊙
U00.15 AI1 Input 0.0~100.0% 0.0% ⊙
U00.16 AI2 Input 0.0~100.0% 0.0% ⊙
U00.17 AI3 Input -100.0~100.0% 0.0% ⊙
Keyboard Potentiometer
U00.18 0.0~100.0% 0.0% ⊙
Input
U00.19 HI Pulse Input Frequency 0.00~100.00kHz 0.00kHz ⊙
U00.20 A01 Output 0.0~100.0% 0.0% ⊙
U00.21 A02 Output 0.0~100.0% 0.0% ⊙
HO Pulse Output
U00.22 0.00~100.00kHz 0.00kHz ⊙
Frequency
Temperature of Inverter
U00.23 -40.0℃~120.0℃ 0.0℃ ⊙
Module
U00.24 The Power-on Time 0~65535min 0min ⊙
U00.25 The Running Time 0~6553.5min 0.0min ⊙
Cumulative Power-on
U00.26 0~65535h 0h ⊙
Time
U00.27 Cumulative Running Time 0~65535h 0h ⊙
U00.28 Actual Count Value 0~65535 0 ⊙
U00.29 Actual Length Value 0~65535m 0m ⊙
U00.30 Line Speed 0~65535m/min 0m/Min ⊙
U00.31 Output Torque 0.0~300.0% 0.0% ⊙
U00.35 Power consumption 0~65535KWh 0 ⊙
U00.36 VDI1~VDI5 input status VDI5 VDI4 VDI3 VDI2 VDI1 00000 ⊙
VDO1~VDO5output
U00.37 VDO5 VDO4 VDO3 VDO2 VDO1 00000 ⊙
status
High speed pulse X7 or
U00.38 0~65535 0 ⊙
the line number of
- 56 -
PV500&PV150A Series Solar Pumping Inverter
extension card monitoring
U01 Group: Failure Record
U01.00 Current Fault Category Err00~Err41 Err00 ⊙
Output frequency of the
U01.01 0.00~Fup 0.00Hz ⊙
current fault
Output current of the
U01.02 0.0~3000.0A 0.0A ⊙
current fault
U01.03 c of the current fault 0~1200V 0V ⊙
Cumulative runtime of the
U01.04 0~65535h 0h ⊙
current fault
U01.05 Former one fault category Like the latest one fault record Err00 ⊙
Output frequency of the
U01.06 0.00~Fup 0.00Hz ⊙
former one fault
Output current of the
U01.07 0.0~3000.0A 0.0A ⊙
former one fault
Bus Voltage of the former
U01.08 0~1200V 0V ⊙
one fault
Cumulative runtime of the
U01.09 0~65535h 0h ⊙
former one fault
Former two fault
U01.10 Like the latest one fault record Err00 ⊙
categories
Output frequency of the
U01.11 0.00~Fup 0.00Hz ⊙
former two faults
Output current of the
U01.12 0.0~3000.0A 0.0A ⊙
former two faults
Bus Voltage of the former
U01.13 0~1200V 0V ⊙
two faults
Cumulative runtime of the
U01.14 0~65535h 0h ⊙
former two faults
Previous 3 categories of
U01.15 The same with U01.00 Err00 ⊙
faults
Previous 4 categories of
U01.16 The same with U01.00 Err00 ⊙
faults
Previous 5 categories of
U01.17 The same with U01.00 Err00 ⊙
faults
Previous 6 categories of
U01.18 The same with U01.00 Err00 ⊙
faults
Previous 7 categories of
U01.19 The same with U01.00 Err00 ⊙
faults
Previous 8 categories of
U01.20 The same with U01.00 Err00 ⊙
faults
Previous 9 categories of
U01.21 The same with U01.00 Err00 ⊙
faults
Previous 10 categories of
U01.22 The same with U01.00 Err00 ⊙
faults
Previous 11 categories of
U01.23 The same with U01.00 Err00 ⊙
faults
Previous 12 categories of
U01.24 The same with U01.00 Err00 ⊙
faults
Previous 13 categories of
U01.25 The same with U01.00 Err00 ⊙
faults
H00 Group: PV Pump Special Set
0:Null
H00.00 Pump Machine Control 1 ×
1:Valid
Selection of Inverter 0:Mains
H00.01 1 ×
Power 1:Solar Panel
H00.02 Vmpp Selection of 0:CVT 3 ×
- 57 -
PV500&PV150A Series Solar Pumping Inverter
Voltage Given Mode (Constant Voltage appr Given)
1:Tracking of Max Power Point
(MPPT)
2:Automatic MPPT
3:Fast MPPT
4:Quick start MPPT
H00.03 Vmpp voltage CVT setting 0~750V 540V △
Mini voltage reference of
H00.04 0~Max Voltage 500V ×
MPPT
Max voltage reference of
H00.05 Max Voltage~750V 600V ×
MPPT
H00.06 PID Filter Time Given 0.000~10.000s 0.000s △
H00.07 PID Filter Time Feedback 0.000~10.000s 0.000s △
H00.08 PID Filter Time Output 0.000~10.000s 0.000s △
H00.09 Ratio Gain Kp1 0.00~100.00 0.10 △
H00.10 Points Time KI 0.00~100.00 0.10 △
PID Lower Limit of Output
PID Upper Limit of Output
H00.11 Frequency~100.0%(100.0% 100.0% ×
Frequency
corresponds to the max frequency)
PID Lower Limit of Output 0.0%~PID Upper Limit of Output
H00.12 20.0% ×
Frequency Frequency
Dormant Delay Time of
H00.13 0.0~6000.0s 600.0s △
Weak light Pre-warning
Wake-up Delay Time of
H00.14 0.0~6000.0s 100.0s △
Weak Light
0:Null
Feedback Channel
1:AI1
H00.15 Selection of Reservoir 0 ×
2:AI2
Water Level
3:AI3
Clean up the delay time of
H00.16 0~10000s 600s △
full-water pre-warning
Threshold of reservoir
H00.17 0.0~100.0 25.0% △
water level
Dormant Delay Time of
H00.18 0~10000s 60s △
Overtank Pre-warning
Detection of reservoir
H00.19 0.0~100.0 100.0% △
hydraulic probe
Pre-warning delay time of
H00.20 0.0~1000.0s 60.0s △
pump under-load
Pre-warning current level
H00.21 0.0~100.0% 0.0:Null 0.0% △
of pump under-load
Reset delay time of pump
H00.22 0.0~1000.0s 60.0s △
under-load
Threshold of
H00.23 0.00~200.00Hz 0.30Hz △
lag-frequency
0:Positive direction,higher
Water level direction detection value higher water level
H00.24 1 ×
detection 1:Negative position,higher
detection value lower water level
80V~MPPT minimum
voltage(220V inverter) 80V
H00.25 Weak light voltage ×
230V~MPPT minimum 230V
voltage(380V inverter)
0: Maximum frequency
H00.26 Frequency given mode 0 ×
1: Master frequency given mode
- 58 -
PV500&PV150A Series Solar Pumping Inverter
Power automatic switch 0:disable
H00.27 0 ×
function 1:Enable
Time of automatic switch
H00.28 1~600Min 60Min △
to solar power
H00.29 Automatic switch delay 0.1~10.0s 3.0s △
Current power source in 0: Grid power
H00.30 0 ⊙
automatic switch function 1: Solar power
H00.31 Pump rated flow Q 0.0~1000.0 m3/h 6.0 m3/h △
N
- 59 -
PV500&PV150A Series Solar Pumping Inverter
1:Valid
For PV pumps special inverter,H00 Group: Invalid
0:Mains
H00.01 Selection of Inverter Power 1 ×
1:Solar Panel
0:Mains
Inverter power supply through the grid, frequency given refer to group of F01, HOO.02~H00.12
invalid.
1:PV Panels
Inverter power supply through solar panels, frequency given mainly through tracking and
adjusting the max power-point PI of solar panels to get.For more details, please refer to H00.02~
H00.12.
0:CVT
( Constant Voltage appr Given )
1:Tracking of Max Power Point
Vmpp Selection of Voltage
H00.02 (MPPT) 2 ×
Given Mode
2:Automatic MPPT
3:Fast MPPT
4:Quick start MPPT
0:CVT(Constant Voltage appr Given)
Adopt voltage given mode; reference voltage is a fixed value, given by H00.03.
2:Automatic MPPT
System track the maximum power point automatically, adaptive to different solar panel, can track
and get maximum power point rapidly.
No matter which reference voltage mode adopted, when bus voltage higher than reference voltage,
the target frequency will change to upper limit of PI output frequency; when bus voltage lower than
reference voltage, target frequency will change to lower limit of PI output frequency.
3:Fast MPPT
System fast track the maximum power point automatically, adaptive to different solar panel, can
track and get maximum power point rapidly.
No matter which reference voltage mode adopted, when bus voltage higher than reference
voltage, the target frequency will change to upper limit of PI output frequency; when bus voltage lower
than reference voltage, target frequency will change to lower limit of PI output frequency.
- 60 -
PV500&PV150A Series Solar Pumping Inverter
PI lower
limit
Dormancy Wake up
delay time delay time
of weak of weak
Frequency
light light
output
PI lower
limit
Running
Running status Dormancy status
status
1:AI1
AI1 for analog signal source of water-level control
2:AI2
AI2 for analog signal source of water-level control
3:AI3
AI3 for analog signal source of water-level control
Detection of reservoir
H00.19 0.0~100.0 100.0% △
hydraulic probe
0.0% means Null.
When not 0.0%, when the detected water level control analog signal larger than H00.19 hydraulic
probe damaged point, hydraulic probe fault (Err32) will be reported directly, and stopped.
- 62 -
PV500&PV150A Series Solar Pumping Inverter
0:Positive direction,higher
detection value higher water
Water level direction level
H00.24 1 ×
detection 1:Negative position,higher
detection value lower water
level
To set the relationship between hydraulic probe detected signal and water level
0: Positive direction, higher detection value higher water level
1: Negative position, higher detection value lower water level
0: Maximum frequency
H00.26 Frequency given mode 0 ×
1: Master frequency given mode
0:Maximum frequency
Given frequency is the maximum frequency adjusted by MPPT function
- 63 -
PV500&PV150A Series Solar Pumping Inverter
PV panels
KM1
R (-) (+) U
Grid S
T
V
W
M
+24V
PLC
Run
DI1
DI2
DI3
DI4
R1A
DI5
R1B
DI6
KM1
R1C
DI7/HI
COM
Figure 3-2 Automatic switch between grid and solar power wiring
- 64 -
PV500&PV150A Series Solar Pumping Inverter
PV150A & PV500 inverters supply many kinds of warning information and protection functions,
when failure occurred, function of protection actives, inverters will stop output, fault relay contact of
inverter active, and display the fault code on inverter operation panel. Before asking support, users
can self-check according to this chapter tips, and analyze the fault reasons, get the solutions. If fault
still can’t be solved, please ask for service, contact with agents or directly to FRECON
Operator
Panel Fault Name Fault Reasons Troubleshooting
Displays
1、Peripheral
troubleshooting
1、Inverter output circuit 2、Prolong the acceleration
grounding or shorted time
2、Acceleration time is too short 3、Adjust the V/F curve
Or manually-torque-boost
3、Manually boost the torque or
Acceleration 4、The voltage adjusted to a
Err01 V/F curve unsuitable
Over-current normal range
4、Voltage is too low
5、Select start on
5、Start the rotating motor
rotational-speed tracking or
6、Shock load on acceleration waiting for motor stopped
7、Inverter selection is too small 6、Cancel shock-load
7、Select inverter with a
larger power
1、Inverter output circuit 1、Peripheral
grounding or shorted troubleshooting
2、Deceleration time is too 2、Prolong the deceleration
Deceleration short time
Err02
Over-current 3、Voltage is too low 3、The voltage adjusted to a
4、Shock load on deceleration normal range
5、No installation of braking 4、Cancel shock-load
resistor 5、Install braking resistor
1、Peripheral
1、Inverter output circuit
troubleshooting
grounding or shorted
2、The voltage adjusted to a
Constant-speed 2、Voltage is too low
Err03 normal range
Over-current 3、If there is shock-load during
3、Cancel shock-load
running
4、Select inverter with a
4、Inverter selection is too small
larger power
1、The voltage adjusted to a
1、Input voltage is high
normal range
2、There is an external force
2、Cancel the external
during acceleration dragging
Acceleration power or install braking
Err04 the motor to work
Overvoltage resistor
3、Acceleration time is too short
3、Prolong the acceleration
4、No installation of braking time
resistor
4、Install braking resistor
1、Input voltage is high 1、The voltage adjusted to a
Deceleration 2、There is an external force normal range
Err05
Overvoltage during deceleration dragging 2、Cancel the external
the motor to work power or install braking
- 65 -
PV500&PV150A Series Solar Pumping Inverter
3、Deceleration time is too resistor
short 3、Prolong the deceleration
4、No installation of braking time
resistor 4、Install braking resistor
1、The voltage adjusted to a
1、Input voltage is too high
normal range
Constant-speed 2、There is an external force
Err06 2、Cancel the external
Overvoltage during running dragging the
power or install braking
motor to work
resistor
1、Momentary power failure 1、Reset Failure
2、The inverter input voltage 2、Adjust voltage to normal
Bus Under 3、Bus voltage abnormal range
Err07 voltage 4、Rectifier bridge and buffer 3、Ask for technical support
protection resistance are abnormal 4、Ask for technical support
5、Drive board abnormal 5、Ask for technical support
6、Control panel abnormal 6、Ask for technical support
1、Peripheral
1、Inverter output circuit troubleshooting
shorted 2、Prolong the
2、Acceleration/ Deceleration acceleration/deceleration
time is too short time
3、Wirings between motor and 3、Install the reactor or
Short circuit inverter is too long output-filter
Err08
protection 4、Module Overheating 4、Check and confirm the
5、Internal wirings of inverter air-channel unblocked, fans
loosened operation normal
6、Main Board Abnormal 5、All cables plugged
7、Drive Board Abnormal 6、Ask for technical support
8、Inverter Module Abnormal 7、Ask for technical support
8、Ask for technical support
1、Check and solve the
1、Power of three-phase-input
problems in peripheral
is abnormal
Input wirings
Err09 2、Drive board abnormal
Open-phase 2、Ask for technical support
3、Lightning board abnormal
3、Ask for technical support
4、Main board abnormal
4、Ask for technical support
Lead-wire from inverter to 1、Peripheral
motor is abnormal troubleshooting
Three-phase output of inverter 2、Check and confirm the
Output is unbalanced during
Err10 motor three-phase winding
Open-phase motor-running to be normal
3、Drive board abnormal 3、Ask for technical support
4、Inverter Module Abnormal 4、Ask for technical support
1、Setting the parameters
1、Motor-protection parameters correctly
F11.17 set incorrectly 2、Lowering the load and
Err11 Motor Overload 2、Load is too large or motor check the conditions of
rocked rotor motor and mechanical
3、Inverter selection is too small 3、Select inverter with a
larger power
1、Reduce load and check
1、Load is too large or motor
Inverter the conditions of motor and
Err12 rocked rotor
Overload mechanical
2、Inverter selection is too small
2、Select inverter with a
- 66 -
PV500&PV150A Series Solar Pumping Inverter
larger power
Fault protection 1、Input the external fault signal
Err13 1、Reset to run
of external input by multi-function terminal
1、Ambient temperature is too 1、Lowering the ambient
high temperature
2、Air-channel blocked 2、Clean up the air-channel
Err14 Overheat 3、Fans damaged 3、Replace the fans
4、Module thermistors 4、Replace the thermistors
damaged 5、Replace the inverter
5、Inverter module damaged module
Err15 Memory Failure 1、EEPROM Chips damage 1、Replace the Main Board
1、Press the button of
Cancel the 1、Press STOP/RST for
Err16 STOP/RST during
self-identification restoration
self-identification
1、Check the wirings
1、Motor and the inverter output
between inverter and motor
Self-identificatio terminals are not connected
Err17 2、Motor breaks away from
n failure 2、Motor connects to load
load
3、Motor Failure
3、Check motor
Upper computer works 1、Check the wirings of
abnormally upper computer
485
2、Communication cable is 2、Check the
Err18 Communication
abnormal communication cable
Timeout
3、F15 communication 3、Set the communication
parameters set incorrectly parameters correctly
PID feedback 1、Check the PID feedback
1、PID feedback lower than the
Err19 disconnection on signal or set F13.24 to be a
running value set by F13.24
suitable value
The running time 1、Setting the function of 1、Refer to description of
Err20
arrives running time arrives F05.14
1、Copy card uninstalled or
1、Parameter copy card
plugged unsuitable
Parameter installed correctly
Err21 2、Parameters copy card
Upload Error 2、Ask for technical support
abnormal
3、Ask for technical support
3、Control board abnormal
1、Copy card uninstalled or
1、Parameter copy card
plugged unsuitable
Parameter installed correctly
Err22 2、Parameters copy card
Download Error 2、Ask for technical support
abnormal
3、Ask for technical support
3、Control board abnormal
1、Braking wirings fault or 1.Check the brake unit, and
Braking Unit braking tube damaged replace the new brake tube
Err23
failure 2、Value of external braking 2.Increasing the braking
resister is too small resistor
Disconnection
Fault of 1、Temperature sensor failure
Err24 1、Ask for technical support
temperature or cable break
sensor
1、Confirm whether the load
loss or parameters of
Inverter 1、Running current of inverter is
Err25 F11.22、F11.23 conform
loss-load less than F11.22
to the actual running
conditions.
Err26 With-wave 1、Load is too large or motor 1、Reduce the load or
- 67 -
PV500&PV150A Series Solar Pumping Inverter
current limit fault rocked-rotor check the conditions of
2、Inverter selection is too small motor or mechanical
2、Select the inverter with
larger power
Soft-start relay 1、Grid voltage is too low 1、Check the grid voltage
Err27
unclosed 2、Rectifier module failure 2、Ask for technical support
1、Parameter version of
EEPROM
up/download module is 1、Re-upload parameters to
Err28 Version
Incompatible inconsistent with the one of up/download modules
control panel
1、Prolong the
1、Acceleration/Deceleration
acceleration/deceleration
time is too short
Hardware detect time
Err29 2、Motor Parameters is
Overcurrent 2、Setting the correct motor
Inaccurate
parameter
3、Hardware failure of Inverter
3、Ask for technical support
1、Deceleration time is too 1、Prolong the deceleration
short time
Hardware detect
Err30 2、No installation of braking 2、Install the braking
overvoltage
resistors resistor
3、Hardware failure of Inverter 3、Ask for technical support
Hydraulic Probe
Err32 Hydraulic Probe Failure Hydraulic Probe Changed
Failure
The setting
Running time more than
Err40 running time 1. Contact the dealer
F00.25
ends
1、check F11.19
Overload
Err41 Overload 2、Select an AC drive of
warning
higher power class.
Output frequency lower than or
equal with lower limit of PI Check the lower limit of PI
Pre-warning of output frequency, and output frequency and
A33
Weak Light continues this status until weak-light delay the set
arrives at delay time of weak value
light.
Water-lever feedback lower
Pre-warning of Check the pre-warning
A34 than the set threshold, and
Full-water point of water level
continue to the delay time
- 68 -