FOREWORD

Thank you for using AC60E series inverter produced by Veichi Electric Co.Ltd
AC60E series inverter is a new generation of high-performance mini -frequency
inverter independently developed by Veichi, With advanced control method and
rich function design. Users will be satisfied by the simplified PLC, PID adjustor,
programming I/O terminal, RS485 interface, analog I/O terminal, and other specific
control functions for particular industries in the benefit of AC60E
This manual is the supporting data sheet for AC60E
This instruction manual includes save tips, instructions (messages) of installing
wiring, keyboard operation, simple function table, troubleshooting, maintenance
only. For parameters setting detail, pls read AC60 general used series manual or
consult us. For the best results and safe operations with the AC60 series, carefully
read and keep this manual. Make sure it is handy for the ultimate user of the
inverters for reference.
To receive technical support related to the inverter, please contact the Veichi sales
office or the dealer from whom you purchased. You can also contact our Customer
Service Center, and we will try our best to help you.

We are sparing no effort to upgrade our products and regret not to issue prior
notification if there is any revision to this instruction manual. Pray for your
consideration for the inconveniences

1
Chapter 1: Summarize
1.1 Safety requirements and cautions
To ensure safety of your health, equipment and property, please read this chapter
carefully before use the frequency inverter and act in compliance with the
instructions while carrying, installing, debugging, running and overhauling the
frequency inverter.
Warn sign and meaning
Danger: it will cause danger of serious injuries and even
death while operating against the rules
Caution: it will cause danger of light injuries or
equipment destruction while operating against the rules
Qualified operation
Only qualified person after professional train can operate the equipment.The
operator must be with professional train, familiar with installation, wiring, running
and maintain of equipment, and can deal emergency case.
Safe guide
Warn sign is for safe, to prevent operator from hurt and prevent this product and
relating equipment from being damaged. Before operating, be sure to carefully
read the manual about safety, installation, operation and maintenance and obey to
the safe rules and warn sign.

● Right transport, store, installation and careful operation and maintenance is most important
for inverter safe run. In transport and store process, make sure the inverter is free from
impact and vibration. It must be stored where is dry, without corrosive air and conductive dust,
temperature lower than 60 .℃
● This product carries dangerous voltage and controls driver machine with potential danger. If
not abide the regulations or requirements in this manual, there is danger of body injury even
death and machine system damage.
● Do not wire while the power is conneted. Otherwise there is danger of death for electric
shock. Before wiring, inspection, maintenance, please cut power supply of all related
equipments and ensure mains DC voltage in safe range. And please do operation after 5


mins.
Power wire, motor wire and control wire should be all connected firmly. Earth must be
reliable and earth resistance must be lower than 10Ω.
● Human body electrostatic will seriously damage inner sensitive components. Before
operation, please follow ESD measures. Otherwise there is danger of iverter damage.
● Inverter output voltage is pulse wave. If components such as capacitor what improves power
factor and pressure-sensitive resistance for anti-thunder and so on are installed at the output
side, please dismantle or change to input side.
● No switch components such as breaker and contactor at the output side. (If there must be
one, please make sure the output current is 0 while the switch acting).

2
● No matter where the fault is, there is danger of serious accident, even human body injury
what means dangerous malfunction possibility. So there must be additional external prevent
measures or other safety devices, such as independent current limiting switch, machinery
fense and so on.
● Only used in application fields as maker stated. No use in equipments related to special
fields such as emergency, succor, ship, medical treatment, avigation, nuclear and etc.
● Only service department of the maker or its authorized service center or professional person
trained and authorized by Veich can maintain the products. They should be very familiar with
the safety warning and operation gist in this manual.
1.2 Before use
Pls check whether any package damage while receiving the product you ordered. If the package is ok,
pls open it and check the inverter. If damage caused in transport, it is not duty of Veich company. But
please contact Veich or the transport company immediately.
After checking the product, please also check if the model is the one you ordered. The model of the
product is on the nameplate “MODEL” column. If any problem, please contact us freely.
Nameplate position and content

Model explaination

3
Single phase 220V Three phase 380V
Max Ratted Max Ratted
Model Model
motor current motor current
AC60E-S2-R40G 0.4kW 2.5A AC60E-T3-R75G 0.75kW 2.3A
AC60E-S2-R75G 0.75kW 4A AC60E-T3-1R5G 1.5kW 3.7A
AC60E-S2-1R5G 1.5kW 7A AC60E-T3-2R2G 2.2kW 5A
AC60E-S2-2R2G 2.2kW 10A AC60E-T3-3R7G 3.7kW 8.5A
1.3 Product technique specifications
Items Specifications
Single phase 220V 50/60Hz
Voltage/frequency
Three phase380V 50/60Hz
Power
Allowable
voltage:±15%, frequency:±5%
fluctuations
Frequency range 0-400Hz
Frequency
±0.5% of max frequency
ACCuracy
Frequency setting 0.01Hz:Operating“up”and”down”keys on keyboard
resolution 0.2Hz:Potentiometers analog input
Voltage 50% -100% the rated voltage adjustable,
Voltage/frequency
Motor rated frequency 25-400Hz(2000Hz)
characteristics
adjustable
Control Carrier frequency 1.0-15.0KHz/Random carrier modulation
0--25.0% adjustable/auto torque upgrade/random
Torque upgrade
V/F curve optional
Maximum 150% for one minute, 180% for 2s, 200% instant
Capacity jump.
ACC and DECtime 0.1-6500s
Take advantage of the power supply voltage
Rated output
compensation function, if motor rated voltage is
voltage
100%,the voltage can be set in the 50 -100%

4
scope(the voltage output should not exceed the
input voltage )
When the grid voltage fluctuates, changes in the
AVR adjust output voltage is very small, remained constant V /
F
Automatic ACCording to the load conditions, automatic
energy-saving optimize the V / F curves to implement energy
operation saving operation
PID control, ACC and DECtime adjustable, ACC
and DECmode variable, Carrier frequency
adjustment, Torque upgrade, Current limiting,
Speed tracking and restart, Frequency hopping,
Standard functions
Frequency fluctuation limite control, Program
running, Multi-steps speed, Pendulum frequency
operation, RS485, Analog output, Pulse output
frequency
Brake Energy-consuming braking, DC braking
Keyboard number settings, keyboard
Frequency setting potentiometers/ external terminal VS: 0 ~ 10V, the
input external terminal AS : 4-20mA, RS485 and signal
composition and terminal options
Signal Feedback External terminal VS: 0 ~ 10V external terminal AS:
input 4-20mA, RS485
Start, stop, positive and negative rotating , jog,
multi-steps speed, free parking, reset, ACC and
Input order signals
DECtime choice, frequency settings channels
choice, external malfunctions alarm
External output Relay output, the collector output, 0-10V output,
signal 4-20mA output, the frequency pulse output
Overvoltage, undervoltage, current limiting,
Protection function over-current, overload, electric thermal relays,
overheat, pressure stall, data protection
Setting Function number/data
Output frequency, give frequency, output current,
input voltage, output voltage, motor speed, PID
Running
feedback, quantitative PID, module temperature,
Display input and output terminal
Overvoltage, undervoltage, overcurrent, short
circuit, phase missing, overload, heat, pressure
Fault
stall, current limiting, data protection is damaged,
current fault operating conditions, historical fault
Installation sites Indoor, elevation of not more than 1000 m, no
Temperature, -10—+40 ℃
corrosive gases and direct sunlight
, 20%—90%RH(No condensation)
Vibration Below 20Hz less than 0.5g
Condition Storage -25—+65 ℃
Installation mode Wall-mounted mode
Protection degree IP20
Cooling Mode Forced air-cooling

5
1.4 Cautions in utilization
Frequency inverter is designed to be permit to run under industrial surrounding with
electromagnetic interference. Usually, if install quality is good, it ensures frequency
inverter safe run without fault. Pls install according to below rules to ensure reliable
run and avoid the impact of electromagnetic interference.
● Ensure all equipments connected to frequency inverter are connected to star
earth or common earth bus by short and thick cable as well as frequency
inverter. Motor earthing should be as close as possible. Do not connect motor
cruster to earth terminal of frequency inverter or protection earth of control
system.
● Conductor should be flat/ multi cores what has lower impedance at high
frequency.
● Cut cable neatly to ensure unshield cable as short as possible.
● Control wire should be away from the supply cable and motor cable as far as
possible and use independent wire slot. While it must across to the supply
cable and motor cable, should be 90º vertical acorss.
●Ensure that the contactor in the cabinet has wave surge
suppresser.Or‘R-C’damping circuit is connected to the winding of AC
contactor. Voltage dependent resistor corresponding to the winding voltage is
used. And freewheel diode or components such as voltage dependent
resistor corresponding to the winding voltage are connected to DC contactor.
It is very important while contactor, controlled by output relay of inverter, acts
frequently.
● Cable connected to motor should be shielded cable or armoured cable. The
two barriers are earthed reliably by cable grounding card.
● Build noise filter at the input side to reduce electromagnetic interference from
other equipments at the power grid side. The noise filter should be as close
to the inverter power input terminal as possible. Meantime, the filter must
earth reliably as the inverter.
● Build noise filter at the output side to reduce radio interference and inductive
disturbance. The noise filter must be as close to the inverter output terminal
as possible. Meantime, the filter must earth reliably as the inverter.
● Anytime, control circuit wire should be shielded cable.
● Add zero phase reactor in power supply wire near inverter input terminal and
add zero phase reactor in the motor wire near inverter output terminal to
reduce electromagnetic interference to the inverter efficiently.
● Earthing
Right and reliable earthing is the basic condition of safe and reliable running of

6
the product. For right earthing, please read the following notice carefully.
● In order to avoid electric shock, earthing cable
should be the size as electric equipment
technic standard required and cable length
should be as short as possible. Otherwise
inverter leakage current will causes unstable
potential of the earthing terminal which is far
from the earthing point. Electric shock accident
will happen frequently.
● Earth terminal must earth. Earth resistance must
be below 10Ω. Otherwise there is danger of
death.
● Please do not share earth cable with welder or
other big current/pulse power equipment.
Otherwise inverter will act abnormally.
● While multi inverters are using at the same time,
please do not wind the earth wire to loop-type.
Otherwise inverter will act abnormally.

7
Chapter 2: Installation
2.1 Inverter stable running environment
Install environment is very important to the best use of this product for long time.
Pls install this product in the enviorment as the folling chart requirement.
Environment Requirement
Install place Indoor without direct sunshine
Install -10 ~ ℃(
+40 hanging type )
temperature -10 ~ ℃(
+45 cabinet type )
-20 ~ +60℃
Store
temperature
Humidity <95%RH, no condensation
Please install the inverter in place as below :
、 、
● Place without oil mist corrosive gases flammable gases 、 fust
or etc.
、、
● Place without metal dust oil water or etc into inverter (please do
Surrounding not install inverter on flammable material such as food and
etc).
● Place without radioactive material or flammablematerial.
● Place without poisonous gases or liquid.
● Place with very little salification erosion.
● Place whihout direct sunshine.
Altitude <1000m
~ ∶
<10 20Hz 9.8m/s
2
Vibration
~ ∶
<20 55Hz 5.9m/s
2

● Inverter can not be installed horizontally, must be installed


vertically.
Installation and ● Please independently install high heating equipments such as
cooling braking resistor and etc which can not be installed in the same
cabinet with inverter, stalled at the air-in port of the inverter is
strictly prohibited.
2.2 Installation notice and related requirement
● AC60E inverter components

8
● Installation direction and space
Single machine installation: to ensure enough ventilation and wiring space for
inverter cooling, please follow installation conditions as below.It should adopts
hanging style or closet style with upright installation and keeps enough space with
surroundings or the wall.

9
Multi inverters paratactic installation: while install multi inverters in cabinet, please
ensure installation space as below.

2.3 Dimension of inverter and keyboard


W D
W1 D1

1
H H

INSTALLATION
MODEL WW W1 H H1 D D1
APERTURE
AC60E-S2-R40G
AC60E-S2-R75G 88 75 142.5 129.5 142 132 ф5
AC60E-S2-1R5G
10
AC60E-T3-R75G
AC60E-T3-1R5G
AC60E-S2-2R2G
AC60E-T3-2R2G 106 90 172 158 142 132 ф6
AC60E-T3-3R7G
2.4 Keyboard dimension (unit: mm)
58 16.5 58

37
5.
8
8. 1
76 0
7
5
4

20.9

2.5 Electric installation


This chapter explains the regulations that users have to obey aimed to ensuring
safe use, best performance and reliable running.

Note:Analog monitor output is special output of meters such as frequcy meter,


current meter, voltage meter and etc. It can not be used for control operations such

11
as feedback control.
●Switch terminals connection function specification
Switch Selectable Picture example Function specification
terminal position
0.2--10kHz frequency
J1
output

0--20mA current output


J2
4--20mA current output

J3 0--10V voltage output

● Suggested braking resistance


Single-phase 220V Single-phase 220V
Motor Resistance Resistance Braking Motor Resistance Resistance Braking
power value power moment power value power moment
0.4 0.75
400Ω 100W 100% 750Ω 150W 100%
kW kW
0.75 1.5
200Ω 120W 100% 400Ω 300W 100%
kW kW
1.5 2.2
100Ω 300W 100% 250Ω 400W 100%
kW kW
2.2 3.7
75Ω 300W 100% 150Ω 500W 100%
kW kW
● Main circuit terminals

Terminal Name Function definition


(+) Braking Used for external braking resistance to realize
PB resistance quick stop.
terminal
R/L
Used to connect AC power supply (R/L,S,T/N for
S AC input terminal
T3 AC input:R/L,T/N for S2AC input).
T/N
U AC output Used to connect the motor or other
V terminal sensitive/resistive load.

12
W
Earth Earth terminal, earth resistance<10 OHM
● Control loop terminals

Termina Name Function definition


l
TA Normally-open Can set the action and object by programme.
TC contact Max contact capacity: 3A/240VAC
Collector Can set the action and object by programme.
Y
open output Max contact capacity:DC30V/50mA
Auxiliary
+24V
power output +
Max output: 24VDC/100mA 。
Auxiliary
COM
power output -
FWD Forward Short connect with (COM) valid.
REV Reverse Short connect with (COM) valid.
Multi function
X1
contact input X1
Multi function
X2 Short connect with (COM) valid.
contact input X2
Multi function input terminals can be programme set
X3
Multi function
contact input X3

definition. Pls refer F-01--F-04
Multi function
X4
contact input X4
Physical type of output signal:0--10V 0--20mA
AO Analog output 4--20mA frequency pulse output, selectable by function
F-61/F-62 or switch J1 J2 J3.
Current analog As inverter control signal or feedback signal, can set
AS
input the act range and response speed by programme.
VS Voltage analog :
VS resistance 89KΩ, AS resistance 250Ω. :

input
Signal auxiliary
+10V Max output 10VDC/50mA
power terminal
Signal auxiliary Common auxiliary power of analog output, analog
GND
power terminal input signal.
Communication
A+ RS485 communication port
terminal A+

13
Communication
B-
terminal B-

14
Chapter 3: Keyboard and Operation
3.1 Keyboard layout and function specification

Key Key name Key functions

Enter menu while standby or running.Press this key to


Menu key return while modify parameter. While standby or running,
press for 1 sec to enter monitorning interface.

Confirm/mo Press to modify parameter while in menu interface.Press


difykey again to confirm aftr modify. While standby or running,
press to change LED monitoring items at stop
Select parameter group in menu interface. Modify
Up/down
parameter while in modify interface. Modify given
key
frequency or PID or given torque while at standby or
monitoring
Select (
digitstate While given
of function frequency
no modified by orup/down
PID or given
key ;
Shift key Select parameter digits modified by up/dowm key.
Change LED monitoring items while standby or running
Forward While run/stop is controlled by keyboard, press this key,
key the inverter forward rotate.

Jog/Revers While run/stop is controlled by keyboard, press it,


e key machine will reverse if this key is defined as REVERSE
and machine will jog if this key is defined as JOG.

Stop/Reset Machine stops if press it while run/stop is controlled by


key keyboard. Its efficiency range is defined via function no
F-07. Inverter reset if press it in fault state(no reset if fault
Potentiomet Can be used to adjust given frequency while it set as
er key potentiometer adjust speed.

15
3.2 Indicating lamp meaning specification
Name State Meaning
Hz Flashing display value is given frequency.
Hz On display value is output frequency.
A On display value is output current actual value.
V On display value is input voltage.
Unit
indicator V Flashing display value is output voltage.
s When "Hz" indicator and the "A" indicator light at
RPM On
the same time, display value is the motor speed.
When the "A" indicator and the "V" indicator
% Flashing flashing at the same time, display value is gived
PID value.
When the "A" indicator and the "V" indicator light
% On at the same time, display value is the amount of
PID feedback.
FWD On Frequency inverter turns forward.
stateindi
FWD Flashing Frequency inverter reverses.
cators
FWD Off Frequency inverter is close-down
Functio
n REV/JOG On This key is defined as the jog function key.
indicator

16
Chapter 4: Functional Parameter Table
Here only simple parameter table. For details, pls read AC60 series manual or
consult us.
“●”:Means that the parameter can be revised during frequency inverter in a running
state.

“ ”:Means that the parameter can not be revised during frequency inverter in a
running state.
“×”:Means that the parameters can only be read and can not be changed.
“–”:Means that the parameter is only set by the manufacturer.

“ ”:Means that the parameter is related to the type of the frequency inverter
4.1 Basic parameter

Communic
ation code
limitation
Factory
setting
Modify
Function Range of settings and
NO
description definition

0:Keyboard control
E-01
Run command given
channel selection
1:Terminal control
2:RS485communication port
0 〇 101H
control
0:Keyboard number setting
1:Keyboard potentiometer
2:Terminal VS voltage
signal,0--10V
3:Terminal AS current
signal,4--20mA
4:Reserved
5:Reserved
6 :RS485 communication

Frequency given
E-02 main channel port 1 102H
selection 7:Ascend/descent control
8:Normal PID running
9:Constant voltage PID
control
10:Program running
11:Swing frequency
running
12:Terminal selection
0:keyboard number setting


Frequency given 1:Keyboard potentiometer
E-03 auxiliary channel 2:Terminal VS voltage 0 103H
selection signal,0--10V
3:Terminal AS current

17
signal,4--20mA
4:Reserved
5:Reserved
6 :RS485 communication
port
7:Ascend/descent control
8:Normal PID running
9:Constant voltage PID
control
10:Program running

E-04
Frequency given
channel gain
0.01--5.00 1.00 〇 104H
0:Main channel valid, auxiliary
channel invalid
1: Auxiliary channel valid,main
channel invalid
2:Both channels arbitrary
nonzero value valid, the main
channel priority
3:Main channel + (K×auxiliary
channel)
4:Main channel - (K×auxiliary
Frequency given

channel)
E-05 channels 5:MAX[Main channel, 0 105H
combinations mode (K×auxiliary channel)]
6:MIN[Main channel,
(K×auxiliary channel)]
7:Auxiliary channel +(K×Main
channel)
8:Auxiliary channel -(K×Main
channel)
9:MAX[(K×Main channel),
auxiliary channel]
10:MIN [ (K×Main channel),
auxiliary channel]
Keyboard display 0:Given frequency
monitoring selections: 1:Output frequency
2:Output current
3:Input voltage
E-06 0 ● 106H
4:Output voltage
5:Mechanical speed
6:PID given value
7:PID feedback value
E-07 Reserved
Keyboard REV/JOG 0:REV
E-08 0 ● 108H
key function options 1:JOG
E-09 Maximum frequency 0.50--400.0Hz 50.0 〇 109H
Lower limit of
Upper limit of frequency--Maximum
E-10 50.00 ● 10AH
frequency frequency

18
Lower limit of 0.00--Upper limit of
E-11 0.00 ● 10BH
frequency frequency
Lower limit 0:Stop
E-12 frequency running 1:Run ACCording to lower 1 ● 10CH
mode limit frequency
E-13 ACC time 1 0.1--6500.0 second ※ ● 10DH
E-14 DECtime 1 0.1--6500.0 second ※ ● 10EH
0:Straight line
E-15 ACC/DECmode 0 ● 10FH
1:S Curve
Lower limit of
Keyboard number
E-16 frequency--Upper limit of 50.00 ● 110H
given frequency
frequency
0:Constant torque curve


1:Drop torque curve 1(1.5times)
E-17 V/F mode 2:Drop torque curve 2(1.7times) 0 111H
3:Drop torque curve 3(2.0times)
4:Auto-defined curve
E-18 Torque upgrade
0.0%:automatic
0.1%--25.0%
※ ● 112H
E-19 Reserve
E-20 Carrier frequency 0.7KHz--15.0KHz ※ ● 114H
LED “0” digit: Carrier
frequency associated with
the output setting
0:Output frequency
correlation invalid
1:Input Frequency
correlation valid
LED “10” digit: Carrier
temperature correlative
Carrier
E-21 setting 0010 ● 115H
Characteristics
0:Module temperature
Correlation invalid
1:Module temperature
Correlation valid
LED “100” digit: PWM mode
options
0:Fixed PWM
1:Random PWM
LED 1000 digit:reserved
E-22
Slip
compensation
frequency
0--200% 0 〇 116H

E-23
Energy-saving
running options
0:Invalid
1:Valid
0 〇 117H
Voltage 0:Invalid
E-24 auto-adjustment 1:Global valid 0 ● 118H
function 2:Only invalid in DEC
0.00Hz--upper limit
E-25 Jog frequency 5.00 ● 119H
frequency
19
E-26 Jog ACC time 0.1--6500.0 second 2.0 ● 11AH
E-27 Jog DEC time 0.1--6500.0 second 2.0 ● 11BH
E-28 Start-up frequency 0.00--60.00Hz 0.50 〇 11CH
E-29
Start-up
duration
frequency
0.0--20.0 second 0.0 〇 11DH
0:Start by start-up frequency
1:Firstly DC braking,then
E-30 Start-up options
start
frequency
by the start-up
0 〇 11EH
2:First rotate speed tracking
then restart
Power cut restart 0:invalid
E-31 0 ● 11FH
options 1:valid
Power cut restart
E-32 0.0--10.0 second 0.5 ● 120H
waiting time
E-33 Free stop frequency 0.00--60.00Hz 0.00 ● 121H
0:DECand stop
E-34 Stop mode 0 ● 122H
1:free stop
E-35 DC braking voltage 0.0--15.0% 5.0 ● 123H
DC braking time for
E-36 0.0--30.0 second 0.0 ● 124H
stop
DC braking initial
E-37 0.00--60.00Hz 0.00 ● 125H
frequency for stop
DC braking time for
E-38 0.0--10.0 second 0.0 ● 126H
startup
E-39 Jumping frequency 1 0.00--400.0Hz(Fmax) 0.00 ● 127H
E-40 Jumping frequency 2 0.00--400.0Hz(Fmax) 0.00 ● 128H
E-41 Jumping frequency 3 0.00--400.0Hz(Fmax) 0.00 ● 129H
Jumping frequency
E-42 0.00--5.00Hz 0.00 ● 12AH
range
0:close
E-43 Fault auto-reset times 0 ● 12BH
1--3:open
Fault auto-reset
E-44 0.1--20.0 second 1.0 ● 12CH
waiting time
E-45 Warm-up time 0.0--6500 second 0.0 ● 12DH
0:comply with the default


direction
Running direction
E-46 1:contra to the default 0 12EH
options
direction
2:Forbid reverse running
Positive/Negative
E-47 0.0--10.0 second 0.0 ● 12FH
rotation dead time
0:After frequency inverter
electrify, fans running


1:stop based on the
Cooling fan running
E-48 temperature, running while ● 130H
options
operation
2:fans stop while stop,
running related to the
20
temperature
LED 0 digit: overvoltage
protection options
0:invalid 1:valid
LED 10 digit:earth
short-circuit protection
detection
0:invalid 1:valid
LED 100 digit:input
E-49
Frequency inverter
protection options
Open-Phase
options
protection

0 11 ● 131H
0:invalid 1:valid
LED 1000 digit:inverter
over-load and
over-temperature protection
options
0:free stop
1:current limiting
running
Electronic
heat-sensitive 30%--120%(Less than 30 ,
E-50 0 ● 132H
coefficient setting the functional invalid)
values
Stall protection
E-51 current limitation 100%--250% 160 ● 133H
values.
Stall protection bus
E-52 110--150% 128% ● 134H
voltage values
Energy-consumed
E-53 braking action voltage 110--150% 122% ● 135H
values
Energy-consumed
E-54 0--100% 80% ● 136H
braking action ratio
Bus under-voltage
E-55 60--90% 65% ● 137H
protection values
E-56 Motor rated voltage 100--1140V ※ 〇 138H
E-57 Motor rated current 0.1--1000A ※ 〇 139H
E-58 Motor rated frequency 25.00--400.0Hz 50.0 〇 13AH
Motor rated rotating
E-59 0--65000 1460 ● 13BH
speed
E-60
Frequency inverter
output voltage ratio
50--100% 100% 〇 13CH
E-61 Reserved
Speed tracking
E-62 0.20--10.00 second 0.60 ● 13EH
stability time
0:all parameters can be
Parameters change changed
E-63 0 ● 13FH
protection 1:only keyboard numbers
setting can be change
21
2:all the parameter forbid
change


0:No operation
Parameter
E-64 1:reset factory setting 0 140H
initialization
2:clear fault memory
E-65 Factory password 0--9999 0 ● 141H


0:no operation
E-66 Information inquiry 1:state monitoring inquiries 0 ● 142H
2:fault information inquiries
LED 0 digit:restrain
over-voltage disturbance
0:invalid 1:valid
LED 10 digit:restrain SC
disturbance
E-67 Disturbance restrain 0001 ● 143H
0:invalid 1:valid
LED 100 digit:restrain
over-current disturbance
0:invalid 1:valid
LED 1000 digit:reserved
※ Information see appendix
4.2 Exterior terminal parameters:

Communic
Modification
Factory
serial

coding
setting

limitation

ation
num Function description range of setting and meaning
ber

0:invalid
1: positive jog operation
2:Negative jog operation
3:free stop
4:fault reset
F-01
Input signal
1(X1)
options 5:multi-step speed contol1
6:multi-step speed contol2
1 〇 201H
7:multi-step speed contol3
8:multi-step speed contol4
9:ascend/descent running
frequency UP
10:ascend /descent

22
running frequency DW
11:trilinear operation mode
control
12:PID control cancel
13:exterior fault alarm
14:ACC and DECtime
F-02
Input signal
2(X2)
options selection terminal 1
15:ACC and DECtime
2 〇 202H

selection terminal 2
16:frequency setting
channel selection
terminal 1
17:frequency setting
channel selection
terminal 2
18:frequency setting


Input signal options channel selection
F-03 terminal 3 3 203H
3(X3)
19:frequency setting
channel selection
terminal 4
20:program running
suspension
21:program running restart
22:timer trigger terminal
23:timer reset terminal
24:timer Auto-Nulling
terminal

F-04 Input signal options


25:Counter
terminal
clock input
4 〇 204H
4(X4)

F-05 Reserved
F-06 Reserved
LED 0 digit:free
F-07
Input signal action
mode selection
stop restore mode
0:after the
100
1
〇 207H

23
disconnection,
restore the original order
1:after the
disconnection,
no restore the original order
LED 10 digit:UP/DW terminal
control frequency
setting
0:UP / DW terminals regulate
after running
1:back to the last shutdown
instantaneous frequency,
then UP / DW regulate
2:First to [F-70], then UP /
DW regulate
LED 100 digit:keyboard
STOP/RESET button
effective range selection
0:only keyboard control
effective
1:all control mode effective
LED 1000 digit:after fault
reset, terminal operation
mode selection
0:terminal control can
restart directly
1:terminal control
,first stop before startup
0:standard operation control


Terminal operation 1:double-line
F-08 control mode operation mode control 0 208H
selection 2:trilinear operation mode
control.
1 step speed 20.0
F-09 ● 209H
setting 1X 0
2 step speed 10.0
F-10 ● 20AH
setting 2X 0
3 step speed 15.0
F-11 ● 20BH
setting 3X 0
0.00Hz--upper limit of
4 step speed 20.0
F-12 frequency ● 20CH
setting 4X 0
F-13 5 step speed 25.0
● 20DH
setting 5X 0
6 step speed 30.0
F-14 ● 20EH
setting 6X 0
F-15 7 step speed 35.0 ● 20FH

24
setting 7X 0
8 step speed 40.0
F-16 ● 210H
setting 8X 0
9 step speed 45.0
F-17 ● 211H
setting 9X 0
10 step speed 50.0
F-18 ● 212H
setting 10X 0
11 step speed 30.0
F-19 ● 213H
setting 11X 0
12 step speed 35.0
F-20 ● 214H
setting 12X 0
13 step speed 40.0
F-21 ● 215H
setting 13X 0
14 step speed 45.0
F-22 ● 216H
setting 14X 0
15 step speed 50.0
F-23 ● 217H
setting 15X 0
F-24 ACC time2 ※ ● 218H
F-25 DECtime2 ※ ● 219H
F-26 ACC time3 ※ ● 21AH
F-27 DECtime3
0.1--6500.0 second
※ ● 21BH
F-28 ACC time4 ※ ● 21CH
F-29 DECtime4 ※ ● 21DH
Relay output 0:zero frequency
F-30 terminal (standby mode) 1 ● 21EH
TA,TC 1:fault jump alarm

25
1(fault auto-restoration
period alarm)
2:fault jump alarm
2(fault
auto-restoration
period no alarm
3:frequency arrive detection
4:frequency level signal
detection
5:be operating
6:reversal operation
7:frequency
undervoltage
8:overload pre-alarm
9:output frequency
reach upper frequency limit
Output terminal 10:output frequency
F-31 Y reach lower frequency limit 4 ● 21FH
11:exterior fault clost-down
12:timer times up
13:Counter reach maximum
value
14:Counter reach setting
value
15:PID feedback
quantity upper limit alarm
16:PID feedback
quantity lower limit alarm
17:sensor disconnect
18:program operation
cycle period ACComplish
19:program operation
step ACComplish
F-32 Reserved
Can be detected out
F-33 0.00--50.00Hz 1.00 ● 221H
frequency range
Output frequency 30.0
F-34 0.00--400.0Hz ● 222H
detection range 0
Output frequency
F-35 detection 0.0--20.0 second 0.0 ● 223H
delay time
Overload pre-alarm
F-36 50--200% 150 ● 224H
range
Overload pre-alarm
F-37 0.0--20.0 second 1 ● 225H
delay time
F-38 Timer setting values 1--65000 second 1 ● 226H

26
Counter maximum 100
F-39 1--65000 ● 227H
value 0
F-40 Counter setting value 1--Counter maximum value 100 ● 228H

F-41
VS terminal input
Voltage lower limit
[ ]
0.00V-- F-42 0.50 ● 229H

F-42
VS terminal input
Voltage upper limit
[F-41]--10.00V 9.50 ● 22AH

VS terminal input
F-43 0.01--5.00 1.00 ● 22BH
Voltage gain
F-44 Reserved
F-45 Reserved
F-46 Reserved
F-47 Reserved
F-48 Reserved
F-49 Reserved

F-50
AS terminal
current lower limit
input
[ ]
0.00mA-- F-51 4.20 ● 232H

F-51
AS terminal
current upper limit
input
[F-50]--20.0mA 19.5
0
● 233H

AS terminal input
F-52 0.01--5.00 1.00 ● 234H
current gain
F-53 Reserved
F-54 Reserved
F-55 Reserved
F-56 Reserved
F-57 Reserved
LED 0 digit:VS1 input
characteristic selection
0:positive characteristic
1:negative characteristic
Input signal
LED 10 digit:AS input 000
F-58 characteristics ● 23AH
characteristic selection 0
selection
0:positive characteristic
1:negative characteristic
LED 100 digit: reserved
LED 1000 digit: reserved
Terminal analog
F-59 0.01--5.00 second 0.50 ● 23BH
input filter time constant
F-60 Reserved

27
0:output signal close
1:output frequency/speed
2:output current
3:given frequency/speed
Output 4:PID given
F-61 3 ● 23DH
terminal(AO)selection quantity
5:PID feedback
quantity
6:DC bus voltage
7:output voltage
0:frequency pulse
output
(AO)output signal
F-62 1:0--20mA 3 ● 23EH
selection
2:4--20mA
3:0--10V
F-63 Reserved
F-64 (AO)output signal gain 25%--200% 100 ● 240H
F-65 Reserved
(AO2)output signal
F-66 -10.0%--10.0% 0 ● 242H
zero adjustment

[ ]
Keyboard
F-67 potentiometer input 0.00V-- F-68 0.20 ● 243H
voltage lower limit

[ ]
Keyboard
F-68 potentiometer input F-67 --5.50V 4.8 ● 244H
voltage upper limit
Keyboard
F-69 0.50--5.00 1.00 ● 245H
potentiometer gain
UP/DW terminal preset 0.00Hz--frequency upper
F-70 0.00 ● 246H
frequency limit
F-71 Reserved 247H
4.3 Special functions parameter
Communic

Fact
Modification

coding
limitation

ation

Series Range of setting values ory


Function description
number and meaning setti
ng

H-01
Free-setting voltage
V1
[ ]
0.0% -- H-03 3.0 〇 301H

0.0Hz--[H-04] 〇
Free-setting
H-02 1.00 302H
frequency F1
H-03
Free-setting voltage
V2
[H-01--H-05] 28.0 〇 303H

H-04
Free-setting
frequency F2
[H-02--H-06] 10.0
0
〇 304H

H-05
Free-setting voltage
V3
[H-03--H-07] 55.0 〇 305H

28
H-06
Free-setting
frequency F3
[H-04--H-08] 25.0
0
〇 306H

H-07
Free-setting voltage
V4
[H-05--H-09] 80.0 〇 307H

H-08
Free-setting
frequency F4
[H-06--H-10] 37.5
0
〇 308H

H-09
Free-setting voltage
V5
[H-07]--100.0% 100.
0
〇 309H

H-10
Free-setting [ H-08 ] --maximum 50.0
〇 30AH
frequency F5 frequency 0
H-11
PID output
characteristic
0:positive characteristic
1:negative characteristic
0 〇 30BH
0:keyboard potentiometer
1:PID keyboard number
given
2:exterior terminal


PID controller given VS:0--10V
H-12 signal 1 30CH
3:exterior terminal
source
AS:4--20mA
4:reserved
5: reserved
6:RS485 interface setting
0:exterior terminal
VS:0--10V

PID controller 1:exterior terminal
H-13 feedback signal AS:4--20mA 1 30DH
source
2:reserved
3: reserved
PID preset 0.00HZ--upper frequency
H-14 0.00 ● 30EH
frequency limit
PID preset frequency
H-15 0.1--6500.0 second 0.0 ● 30FH
operation time
PID keyboard
H-16 0.0--100.0% 50.0 ● 310H
number given
Feedback channel
H-17 0.01--5.00 1.00 ● 311H
gain
Sensor maximum 100.
H-18 1.0--100.0 ● 312H
measuring range 0
H-19 Proportion gain P 0.1--100.0 20.0 ● 313H
H-20 integral time I 0.1--100.0 second 2.0 ● 314H
H-21 Differential gain D 0.0--10.0 0.0 ● 315H
H-22 Sampling period 0.01--60.00 second 0.10 ● 316H
PID control
H-23 0.0--20.0% 0.0 ● 317H
deviation limit
H-24 Start Threshold 0.0%--dormancy Threshold 0.0 ● 318H
100.
H-25 Dormancy Threshold Start threshold--100.0% ● 319H
0

29
Alarm upper limit Alarm lower limit 100.
H-26 ● 31AH
value value--100.0% 0
Alarm lower limit 0.0%--Alarm upper limit
H-27 0.0 ● 31BH
value value
Sensor
H-28 disconnection 0.0--20.0% 0.0 ● 31CH
detection values
Sensor
0:continued operation
H-29 disconnection alarm 0 ● 31DH
1:stop
operation selection
Upper limit lower limit demarcative 100.
H-30 ● 31EH
demarcative values values--100.0% 0
lower limit 0.0%--upper limit
H-31 0.0 ● 31FH
demarcative value demarcative values
0:single cycle (time in
seconds)
1:continuous cycle (time in
seconds)
2:single cycle, continuous
running
H-32 Program run mode
(time in seconds)
3:single cycle (time in
0 〇 320H
minute)
4:continuous cycle (time in
minute)
5:single cycle,continuous
running
(time in minute)
0:operation ACCording to
the first step speed
1:re-timing and running
ACCording to the be

Program
interrupted running
H-33 breakpoint restore 0 321H
frequency
mode selection
2:running ACCording to the
residue time after being
interrupted
running frequency


In program run
0:Power off without storage
H-34 state,power off 0 322H
1:Power off with storage
storage selection
0:FWD:ACC time
1/DECtime 1
1st step speed 1:FWD:ACC time
H-35 direction and 2/DECtime 2 0 ● 323H
ACC&DECtime 2:FWD:ACC time
3/DECtime 3

30
2nd step speed
H-36 direction and 1 ● 324H
ACC&DEC time
3rd step speed
H-37 direction and 2 ● 325H
ACC&DEC time
4th step speed
H-38 direction and 3 ● 326H
ACC&DEC time
5th step speed
H-39 direction and 4 ● 327H
ACC&DEC time
6th step speed
H-40 direction and 5 ● 328H
ACC&DEC time
7th step speed
H-41 direction and 3:FWD:ACC time 6 ● 329H
ACC&DEC time 4/DECtime 4
4:REV:ACC time
8th step speed
1/DECtime 1
H-42 direction and 7 ● 32AH
5:REV:ACC time
ACC&DEC time
2/DECtime 2
9th step speed
6:REV:ACC time
H-43 direction and 0 ● 32BH
3/DECtime 3
ACC&DEC time
7:REV:ACC time
10th step speed 4/DECtime 4
H-44 direction and 1 ● 32CH
ACC&DEC time
11th step speed
H-45 direction and 2 ● 32DH
ACC&DEC time
12th step speed
H-46 direction and 3 ● 32EH
ACC&DEC time
13th step speed
H-47 direction and 4 ● 32FH
ACC&DEC time
14th step speed
H-48 direction and 5 ● 330H
ACC&DEC time
15th step speed
H-49 direction and 6 ● 331H
ACC&DEC time
1st step speed
H-50 10.0 ● 332H
operation time T1
2nd step speed
H-51 10.0 ● 333H
operation time T2 0.0—6000 second(minute)
3rd step speed
H-52 10.0 ● 334H
operation time T3
H-53 4th step speed 10.0 ● 335H
31
operation time T4
5th step speed
H-54 10.0 ● 336H
operation time T5
6th step speed
H-55 10.0 ● 337H
operation time T6
7th step speed
H-56 10.0 ● 338H
operation time T7
8th step speed
H-57 10.0 ● 339H
operation time T8
9th step speed
H-58 10.0 ● 33AH
operation time T9
10th step speed
H-59 10.0 ● 33BH
operation time T10
11th step speed
H-60 10.0 ● 33CH
operation time T11
12th step speed
H-61 10.0 ● 33DH
operation time T12
13th step speed
H-62 10.0 ● 33EH
operation time T13
14th step speed
H-63 10.0 ● 33FH
operation time T14
15th step speed
H-64 10.0 ● 340H
operation time T15
Differential
frequency△f in swing
H-65 0.00--20.00Hz 2.00 ● 341H
frequency
operation
0:this machine is linkage
Linkage main slave station
H-66 0 ● 342H
station setting 1: main station mode 1
2: main station mode 2
H-67 Machine addresses 1--247 1 ● 343H
( )
0:non verifying N,8,1
H-68 Data format ( )
1:even verifying E,8,1 3 〇 344H
( )
2:odd verifying O,8,1
0:1200 bps
1:2400bps
H-69 Baud rate 2:4800 bps 3 〇 345H
3:9600bps
4:19200bps
Communication
H-70 setting frequency 0.01--5.00 1.00 ● 346H
ratio
Communications
H-71 0.0--6500.0 second 10.0 ● 347H
timeout time
H-72 RS485 0:stop 0 ● 348H

32
Communication 1:Continued operation
disconnection action
mode
0.00
H-73 Response delayed 0.001--1.000 second ● 349H
5
Moment stop
H-74 0%--200% 20% ● 34AH
DECvoltage lower
Moment stop
H-75 0%--200% 90% ● 34BH
DECvoltage upper
Moment stop
H-76 0.01--10.00 2.00 ● 34CH
DECbenefit
Voltage recover
H-77 0.0--100.0s 2.0s ● 34DH
steady time
H-78 reserved 34EH
H-79 reserved 34FH
H-80 reserved 350H

33
Chapter 5: Fault Information and
Troubleshooting
Fault
Type of fault Possible fault reason Troubleshooting
code
1.Lengthen ACC time.
1.ACC time is set too 2.Chect the peripheral device ,
short reset after troubleshooting.
2.Frequency inverter 3.Ask for technical support.
S.C System fault output phase or 4. Check peripheral
grounding short circuit. device,grounding line,shield
3.Module failure. line grounding
4.Disturbance. condition,distance condition of
terminals and control machine.
1.ACC time is too
short.
2. Restart the machine 1. lengthen ACC time.
2.restart after the machine
[ ]
in running when
momentary stop totally stop or set E-30 as“2”.
ACC over
o.C.1 occurs.. 3. Reset V/F curve or torque
current
3. V/F curve setup is boost value.
not suitable or torque 4. Select frequency inverter
is boosted too high with proper capacity.
4.Frequency inverter
capacity is too low.
1.DEC time is too
1.Lengthen DEC time
short.
2.Connect external resistor or
DEC over 2.Potential load or
o.C.2 braking unit.
current inertia is too big.
3.Select frequency inverter with
3. Frequency inverter
proper capacity.
capacity is too low..
1.Load change
Over current at 1. Check the load change
suddenly.
o.C.3 constant condition and eliminate it.
2.Network voltage is
speed 2.Check the input power.
relatively low.
1.Supply voltage
overrun.
1.Check the network voltage ,
ACC over 2. Restart the machine troubleshooting.

o.U.1
voltage 2. Restart after the machine
in running no tracking

start .
[ ]
totally stop or set E-30 as“2”.
1. Lengthen DEC time.
1.DEC time is too
2. DECrease potential load, or
short. amplify the frequency inverter
DEC over 2. Potential load or capacity, or install more braking
o.U.2
voltage inertia is too big..
unit.
3. Supply voltage
overrun.
3.Check the network voltage ,
troubleshooting.
34
Over voltage at
1.Supply voltage
overrun.
1.Check the network voltage ,
o.U.3 constant troubleshooting.
2.Input voltage is
speed 2.Install input reactor.
abnormal
Close down 1.Supply voltage
1. Check the network voltage ,
o.U.4 troubleshooting.
over voltage overrun.
2. Ask for technical support.
1. V/F curve setup or
torque boost is not
suitable 1. Reset V/F curve or torque
2. Network voltage is boost value.
2.Check the input power.
[ ]
relatively low.
3. Machine overload 3.Check E-57 setting.
protection parameter is 4.Adjust load or select and use
Machine
o.L.1 set improperly. frequency inverter with
overload
4.Machine block rotor matching capacity grade.
operation or heavy 5. When requiring long term
load. low speed work, please use
5.Universal machine special motor for frequency
low speed with heavy inverter.
load works for a long
time.
1.Heavy load .
2.ACC time is set too 1. Select frequency inverter
short. with proper capacity.
3. Restart the machine 2. Lengthen ACC time.
Frequency 3. Restart after the motor
[ ]
in running when
o.L.2 inverter over
momentary stop completely stop or set E-30
load
occurs.. as“2”.
4. V/F curve setup or 4. Reset V/F curve or torque
torque boost is not boost value.
suitable
1. Ameliorate periphery
environment.
1. Too high ambient 2.Replace fan.
Frequency
temperature.
2. Damaged fan.

3. Clear air duct improve the
o.H. inverter inner frequency inverter periphery
3. Blocked air duct.
overheat ventilation and dissipation
4.Carry wave
environment.
frequency is too big.
[ ] [ ]
4.Check E-20 and E-21
setting.
1.Supply power is too
Over voltage 1.check the supply voltage and
low.
LU1 of supply troubleshooting.
2.Voltage detection
power at stop 2. Ask for technical support.
circuit abnormal.
Over voltage 1.Supply power is too 1. Check the supply voltage
LU2 of supply low. and
power at 2.Capacity of power troubleshooting.

35
running network is too small , 2.Improve power supply
or instantaneous surge system.
current inside power 3. Ask for technical support.
network is too big.
3.DC main contactor
inside the frequency
inverter not close.
In PID running mode,
when the analog
1. Check wiring and re-wire
feedback channel is
Feedback again.
SEn selected, the feedback
sensor fault signal is lower than 2. Adjust the feedback signal
[ ]
H-28 setting value,
input type.
alarm
Open-phase in
Check three phase input power
Open-phase at frequency inverter
Err1 and
input side three phase input
three phase input power wiring
power Phase.
Frequency inverter has
Check peripheral device
Output device grounding short
Err2 ,grounding line,machine
grounding circuit at the output
insulation.
side.
1.Detecting circuit fault.
Current 1. Ask for technical support.2.
Err3 2.Damaged HALL
detecting fault Ask for technical support.
component.
Frequency
Exterior exterminal
Err4 inverter Check exterior device.
action.
exterior fault
Swing
frequency User set the swing
Reset the swing frequency
Err5 running running parameter
running parameters.
parameters not correctly.
setting error
1.Keyboard wiring
Keyboard fault.
1.Check the keyboard wiring.
Err6 communication 2.Keyboar
2.Ask for technical support.
fault communication
component damaged.
1. Read/write error of
keyboard control 1.Frequency inverter
Memorizer
93SE parameters. re-electrify.
fault
2. EPROM is 2.Ask for technical support.
damaged.
LIFE Reserved -- 1.Ask for technical support.

36
Chapter 6: Overhaul and Maintenance
During frequency inverter normal operation, except for daily inspections, periodic
(such as machine overhaul or inspections at least every six months as required)
inspections must be performed according to the following table, to preven t trouble
before it happens.
Inspect Inspec Inspecti
Inspection
ion tion on Inspection content Criteria
methods
period part items
At any Displa LED If display is
Vision No abnormal
time y display abnormal or not?
Coolin
If there is abnormal Visual
At any g
Fan vibration or examination No abnormal
time syste
abnormal noise. and listening
m
Surroun
Temperature , Visual
At any
time
Noum
enon
ding
environ
, , ,examination
humidity dust
smelling,
By 2-1 term
harmful gas
ment feeling
Input Detect R、S、 according to
T and U、V、
At any If input, output
termin Voltage the standards
time voltage is abnormal
al W terminal regulation
If the fastener
loosen , whether
having the hot shot
trail , whether
panora having discharging Visual, ,
ma or not ,
tighten clean
No abnormal
phenomenon , dust
are too much, if the
wind way is
periodi Main
blocked up
c circuit
Electroli
tic If surface is
Visual No abnormal
capacito abnormal
r
Wire
conducti Whether loosen Visual No abnormal
ve bar
Termina Whether the bolt or
tighten No abnormal
l screw loosen
During the examination, not allowed to dismantle or rock a component for no
reason, even pull off a connector assembly. Otherwise, it can not run or enter
malfunction display state. And it will bring faults of the component,even damage
37
the host switch component IGBT module. When needing measurement, user
should pay attention to various different meters which may reach very different
measurement results. Pointer voltmeter is recommended to use to measure input
voltage. Rectifier voltmeter is recommended to use to measure output voltage.
Pliers galvanometer is recommended to use to measure input and output current.
And electrodynamics wattmeter is recommended to use to measure power.
If the frequency inverter is not in use immediately after purchased, and need to be
temporarily stored or long-term stored up, pls obey belowing rules:
1 Frequency inverter should be stored in the place with standard temperature
range 、 fine ventilation and no humidity、 dust or metal dust.
2 If frequency inverter has not been put into use yet for more than 1 year, user
should carry on charging testing to restore the characteristic of the inner main
circuit filter capacitor. During charging, user can use the pressure regulator to
elevate slowly the input voltage of the frequency inverter to the rated input voltage.
The charging time should be above 1-2 hours. At least test once every year as
narrated above.
3 Frequency inverters are not allowed to be carried out the pressure testing,
otherwise, it will lead to frequency inverter life lessening or damage. Before the
insulation testing, user should use 500 MΩvolt megger measures the frequency
inverter. Its insulation resistance should not smaller than 4MΩ
When using the general ohmmeters to measure current, the current in the input
end will has imbalance phenomenon. Generally the difference within 50% is
regular. If using general multimeter to measure the output three-phase voltage, due
to being limited by the carry wave frequency disturbance and multimeter frequency
response, the read data, which maybe inaccurate,can be for reference only.
In order to guarantee the frequency inverter stable operation, except for periodic
maintenance, the inner component which bears long-term mechanical wear should

be periodic replaced---including the cooling fan main circuit filter capacitor for

energy caching and exchange printed circuit board. In general continuous using,
users can replace them according to below regulation. Also should according to

the concrete conditions such as the usage environment load condition and
frequency inverter current situation.
Component name Replace year criteria
Cooling fan 2—3 year
Filter capacitor 4—5 year

38
printed circuit board 8—10 year

39
Chapter 7: Quality Guarantee
This product quality guarantee is processed as the follows items:
Users can enjoy the following “three guarantee” service from the day of
buying products if meeting products quality problem:
1 We guarantee for repair, return and replacement for one month after
delivery;
2 We guarantee for repair and replacement for two months after delivery;
3 We guarantee for repair for three months after delivery;
4 When product is exported to abroad, we guarantee for repair for three
months after reaching customer.
No matter where you purchase products, you can enjoy lifelong paid service.
The agency, dealer, provider can provide “three guarantee” service after
being authorized by our company.
When quality problem appears, our company only undertakes “three
guarantee” service as the 11.1 and 11.2 responsibilities above. If user needs
more responsibility guarantee, please insure the product by cooperation
with the insurance company.
The malfunctions, caused by the reasons mentioned as below, can only
enjoy the paid service even if the product under warranty,
1 The malfunctions caused by misoperations which are not in compliance with
this user manual;
2 The malfunctions caused by unauthorized transform or over-range
operation.
3 User has not paid off the payment according to the contract; ;
4 The malfunctions caused by the earthquake, fire, flood, lightning, or
abnormal voltage, etc;
As for the “three guarantee” service, the product must be returned back to
our company and can only be replaced or mend after responsibility
belonging confirmed.

40
Appendix
1.Monitor inquiry

Select this function to enter monitoring menu group C parameters ),and inquire
each state parameters of the frequency inverter. In the monitoring state, you can
long press (1 second) PRG key and directly enter the state of the group C
parameters which namely is the state monitoring.

Monitoring Communicati
Content Units
code on code
C-1 Given frequency 0.01HZ C01H
C-2 Output frequency 0.01HZ C02H
C-3 Output current 0.1A C03H
C-4 Input voltage V C04H
C-5 Output voltage V C05H
C-6 Mechanical speed RPM C06H
C-7 PID given quantitative % C07H
C-8 PID feedback quantitative % C08H
C-9 Module temperature ℃ C09H
C-10 Accumulative operation time hour C0AH
Accumulative operation time after
C-11 latest power on Min C0BH
C-12 Output current percentage % C0CH
Step operation remainder time
C-13 percentage % C0DH
Input terminals connect/disconnect See belowing
C-14 status C0EH
diagram
Input terminals connect/disconnect See belowing
C-15 status C0FH
diagram
C-16 Terminal VS1 input value 0.1v C10H
C-17 Terminal AS input value 0.1mA C11H
C-18 Terminal VS2 input value 0.1v C12H
C-19 Terminal pulse input value ※ C13H
C-20 Counter record ※ C14H
C-21 DC bus voltage V C15H
C-22 Analog output A01 0.01V C16H
C-23 Frequency/voltage/current ※ C17H

41
outputA02
C-24 Reserved -- C18H
C-25 Inverter power grade Kw C19H
C-26 Inverter rated voltage V C1AH
C-27 Inverter rated current 0.1A C1BH
C-28 Software version ※ C1CH

Input terminal connect/disconnect state schematic diagram

X1 terminal stage REV terminal stage


X2 terminal stage FWD terminal stage
X3 terminal stage X6 terminal stage
X4 terminal stage X5 terminal stage

input terminal on input terminal off

input terminal on/off state

Output terminal connect/disconnect state schematic diagram

TA、TB、TC
Terminal stage Reserve
Y1 terminal stage Reserve
Y2 terminal stage Reserve
Reserve Reserve

output terminal on output terminal off

outputterminal on/off state

2.Fault information inquiry


After inquiry setting, can set LED display below information circularly by the
keyboard up/down keys.

42
Communic
ation code
Serial
numb Definition Remark
er

For details, pls see fault


Er.01 The latest fault information E01H
information code table
Er.02
The cumulative running time
before the latest fault

Units hour E02H

Units:Hz
Output frequency while the latest
Er.03 E03H
fault
Units:V
DC bus voltage while the latest
Er.04 E04H
fault
Units:A
Output current while the latest
Er.05 E05H
fault
Units:V
Output voltage while the latest
Er.06 E06H
fault
Units:℃
Module temperature while the
Er.07 E07H
latest fault
Running direction while the
Er.08 0.Forward 1.reverse E08H
latest fault
Running status while the latest 0.close down 1.stable speed
Er.09 E09H
fault 2.acceleration 3.deceleration
0. Normal 1.only voltage
Protection status while the latest amplitude limit 2. only current
Er.10 E0AH
fault amplitude limit 3.both voltage
and current amplitude limit
Input terminal status while the
Er.11 See above chart E0BH
latest fault
Output terminal status while the
Er.12 See above chart E0CH
latest fault
The latest one fault
Er.13 E0DH
information
The latest two fault
Er.14 E0EH
information
The latest three fault
Er.15 E0FH
Information

43