DB Schedule and SLD
DB Schedule and SLD
DB Schedule and SLD
SPARE SPARE
2C x10mm2 XLP/SWA/PVC
4C,70MM XLP/SWA/PVC +
+ 1C x 10 mm2 PVC/ECC
1C, 35MM PVC/ECC
1600/5A
R.E.F.
CLASS-X CT
RELAY
4 NOS.
LV PANEL CAG 14
NOTE: 3 NOS.
0-1600A 0-1600A 0-1600A CURRENT EDITION OF "THE REGULATIONS FOR INSTALLATION OF ELECTRICAL WIRING,
ELECTRICAL EQUIPMENT AND AIR CONDITIONING EQUIPMENT".
FORM AS PER STANDARD IEC 439-1, 3B,TYPE-'2' 2) MV PANEL DETAILS/MANUFACTURER'S DRAWINGS SHALL BE SUBMITTED TO QATAR
10 WAYS TERMINAL GENERAL ELECTRICITY AND WATER CORPORATIN(KAHRAMAA) FOR PRIOR APPROVAL
1600/5A KWHM BLOCKS FOR KAHRAMAA METER. BEFORE IT IS MANUFACTURED.
CLASS-1 CT 3) TOTAL VOLTAGE DROP SHALL NOT EXCEED 2.50% OF THE DECLALARED VOLTAGE IN QATAR.
THE MANUFACTURER DRAWINGS MUST BE FORWARDED 4) POWER FACTOR SHALL NOT BE LOWER THAN 0.90.
3 NO. 2A FUSE R Y B
TO CUSTOMER SERVICES DEPARTMENT FOR APPROVAL, 5) THIS APPROVAL COVERS ONLY THE REVISION/MODIFICATION AS INDICATED IN THE
PRIOR TO BE CONSTRUCTED. 20A HRC FUSE
SLD/DRAWING.ALL OTHER DETAILS SHALL BE AS PER THE PREVIOUS APPROVAL UNDER
PHASE INDICATING LAMP BP#.
BUSBAR MOUNTED
NOTE:
1000 KVA OIL TYPE TX TO BE SUPPLIED BY KAHRAMAA
1600A
TP ACB SHUNT TRIP
WITHDRAWABLE TYPE 30V DC
DIMENSION DETAILS MOTORIZED WITH O/L AND S/C
PROTECTION TYPE
HEIGHT OF LV PANEL=2.2 M (WITH SEALING DEVICE)
WIDE OF LV PANEL=0.80 M I CW=44 KA FOR 3 SEC MINIMUM 6A FUSE
LENGTH OF LV PANEL=2.40 M
6A FUSE
S/S V
20A HRC FUSE V SS
BUSBAR MOUNTED 7 POSITION 0-500V
7x1Cx630 MM LV2CABLE
NO.OF K.W.H.M
FOR FACTORY=1 NO.K.W.H.M
30V DC WITH FOR HT TRIP
N 1000 KVA TRANSFORMER
TOTAL=1 NO.K.W.H.M BATTERY AND
N
(OIL TYPE) CHARGER SUPPLY
(BY KAHRAMAA) WALL MOUNTED
KAHRAMAA SUPPLY