Endura MRL - Elevator Submittal (From Other Project)
Endura MRL - Elevator Submittal (From Other Project)
Endura MRL - Elevator Submittal (From Other Project)
For Project:
TALLEY EYE INSTITUTE
TKE Job Number: 1393-752-01A
PRELIMINARY
Elevator(s): A (SIMPLEX) FOR APPROVAL
DRAWINGS
Located At:
6149 E COLUMBIA ST
EVANSVILLE, IN 47711
Company (Mail To):
WOODWARD COMMERCIAL REALTY
6149 E COLUMBIA ST
EVANSVILLE, IN 47711
GC Phone: 812-474-1900
Attention:
ZACH MARTIN
INSTRUCTIONS
Failure to complete the Contractor Verification Sheet and Approve drawings WILL result in delay of fabrication and shipping of equipment.
Check ALL hoistway dimensions, elevator travel (floor to floor heights), pit depth, clear over-head, machine room dimensions and entrance wall thickness. Mark-up drawings accordingly, and remit with necessary approval (i.e: approved or approved as noted) to
the Local ThyssenKrupp Elevator Office.
Complete all information on the Contractor Verification Sheet.
Provide a firm on-site date to the Local ThyssenKrupp Representative.
Any previously quoted manufacturing lead-times for material delivery, shall begin the date of receipt by ThyssenKrupp of ALL approvals, confirmations, and a fully executed subcontract agreement. The installation start date cannot be any
earlier than the delivery of the material to the site and the completion of all items shown on the Pre-Installation Checklist sent to you in this submittal package.
INFORMATION
"ALL DEPICTIONS, DIMENSIONS, MEASUREMENTS AND ALL OTHER INFORMATION CONTAINED IN THESE DRAWINGS ARE FOR ILLUSTRATION PURPOSES ONLY. THE CONSTRUCTION MANAGER AND/OR GENERAL CONTRACTOR BEARS FULL
RESPONSIBILITY TO PROPERLY BUILD THE NECESSARY HOISTWAYS, CONTROL-ROOMS, AND/OR MACHINE-ROOMS TO ACCOMMODATE THE ELEVATOR EQUIPMENT PURCHASED." IN NO EVENT WILL THYSSENKRUPP ELEVATOR CORPORATION BE
LIABLE FOR ANY INCIDENTAL, CONSEQUENTIAL, OR INDIRECT DAMAGES (INCLUDING BUT NOT LIMITED TO, DAMAGES FOR LOSS OF PROFITS, DELAY, BUSINESS INTERRUPTION,) ARISING OUT OF THE USE OF THESE DRAWINGS, THE INABILITY TO
USE THESE DRAWINGS (INCLUDING ANY INFORMATION CONTAINED THEREIN), OR ANY TRANSACTIONS RELATED TO THE USE OF THESE DRAWINGS. BECAUSE SOME STATES DO NOT ALLOW THE EXCLUSION OR LIMITATION OF LIABILITY FOR
CONSEQUENTIAL OR INCIDENTAL DAMAGES, THE ABOVE LIMITATION MAY NOT APPLY TO YOU. IN SUCH STATES, THYSSENKRUPP ELEVATOR CORPORATION'S LIABILITY IS LIMITED TO THE GREATEST EXTENT PERMITTED BY LAW.
TO: JENNIFER WYATT Email this PDF Construction Superintendent: MARC MASON 812-475-9419
EMAIL: 812-475-9419
Project Manager:
PHONE: 812-475-9419
General Contractor Owner Job-Site Pre-Installation Checklist (See G.C. Site Binder)
PACKAGE CONTENT:
Contractor Verification Sheet
Approval/Approved Sheet
Layout Sheet
Entrance Sheet(s)
- The enclosed submittals are in compliance with conditions of ThyssenKrupp Elevator's subcontract or supplying and installing materials and or systems for the
- Enclosed drawings are for approval purposes only and not to be used for construction.
TKE- In structi on -In forma tio n / [Bo rde r] TKE -In struc ti on -Inform atio n
CONTRACTOR VERIFICATION SHEET
ELEVATOR DESIGNATION: A FACTORY JOB NUMBER:
REQUIRED CAB INFORMATION: REQUIRED ENTRANCE INFORMATION: REQUIRED POWER CONFIRMATION:
CAB WALL COLOR: <PLASTICLAMINATED>
MAIN EGRESS/ FIRE RECALL @ FLOOR MARKED: <MAINEGRESS> WE REQUIRE THAT THE FOLLOWING POWER INFORMATION BE CONFIRMED:
CAB CEILING FRAME FINISH COLOR: <POWDERCOATED>
FLOOR MARKING: WALL TYPE: WALL THICKNESS (X): ENTRANCE DOOR FINISH: ENTRANCE FRAME FINISH:
BUILDING POWER: 208 VOLTS A.C., 3 PHASE, 60 CYCLES
_________________________________ ✔ CONFIRMED
2 Drywall
<WALLTYPE> <WALLTHK>
13.125" #4 STAINLESS STEEL #4 STAINLESS STEEL
1 Drywall
<WALLTYPE> <WALLTHK>
11.125" #4 STAINLESS STEEL #4 STAINLESS STEEL
STARTING TYPE: SOLID
_________________________
STATE STARTING
(WITH 3/8" MAXIMUM FLOOR THICKNESS) IF YES, HOW MANY ELEVATORS WILL BE CAPABLE OF RUNNING AT THE SAME
TIME WHILE ON EMERGENCY POWER ? <QTYELEV>
_________
* IF FINISHES ARE NOT FROM TKE COLOR BROCHURE, ADDITIONAL CHARGES WILL APPLY.
DESCRIPTION OF YOUR CAB FEATURES: NOTE: IF EMERGENCY POWER IS PROVIDED, ELECTRICAL CONTRACTOR MUST
PROVIDE ADDITIONAL CONTACTS TO THE CONTROLLER. SEE A LOCAL
CAB TYPE: FLAT PLASTIC LAMINATE WALLS (TKLP)
THYSSENKRUPP ELEVATOR REPRESENTATIVE FOR MORE INFORMATION.
CAB CEILING: SUSPENDED CEILING WITH LED LIGHTING
CAB DOOR: #4 STAINLESS STEEL
CAR SILLS: ALUMINUM
MATERIAL RELEASE FORM:
CAB HANDRAIL(S): (3) 1 1/2" CYLINDRICAL In an effort to meet your expectations concerning schedule for the project, we are requesting material
delivery/start dates based on the availability or anticipated completion of the items listed in the thyssenkrupp
HANDRAIL(S) FINISH: #4 STAINLESS STEEL site binder.
Note: Prior to the delivery of material and the start of installation, all items on the pre start check list inside
CAB PROTECTION: PAD BUTTONS PROVIDED. (0) PADS the thyssenkrupp elevator site binder must be completed.
FINISH FLOOR WEIGHT (3/8" MAX. THICKNESS) = 100 <MNT>
CAB FLOORING: Requested Elevator Material Delivery/Start Date: ____ /<DAY>
____ /<YR>
_____
LBS. BY OTHERS (Delivery of all remaining material, less any early shipment)
The General Contractor agrees to assume responsibility of the equipment the day of arrival from the factory
on date mentioned above. Adequate ingress and egress to this area must also be provided along with a
dumpster or area for disposing of packaging material. Any relocation of the equipment as directed by the
contractor/owner after its initial delivery will be at others
(not thyssenkrupp elevators) expense.
If the site conditions are not in place at the time of elevator delivery, the equipment will be stored per the
rates established in the contract and the thyssenkrupp elevator proposal. At such time the site becomes
ready for delivery/starting the elevator installation, thyssenkrupp will need payment of any outstanding
invoices inclusive of storage costs accrued before delivery/mobilization and in the thyssenkrupp elevator
proposal for storage fees.
CUSTOMER APPROVAL BOX
(THESE ITEMS MUST BE CONFIRMED BEFORE THE ELEVATOR WILL BE MANUFACTURED)
NET ✔ CONFIRMED AS SHOWN ON SECTION VIEW CLEAR ✔ CONFIRMED AS SHOWN ON SECTION VIEW
TRAVEL: CORRECTED: <NETTRAVELCORRECTED>
_________________________ OVERHEAD: <CLROVERHEADCORRECTED>
CORRECTED: _________________________
PIT ✔ CONFIRMED AS SHOWN ON SECTION VIEW HOISTWAY ✔ CONFIRMED AS SHOWN ON SECTION VIEW
<PITDEPTHCORRECTED>
DEPTH: CORRECTED: _________________________ <HWYSIZECORRECTED>
SIZE: CORRECTED: _________________________
FEATURES FOR YOUR FIXTURES: HAND OF ✔ CONFIRMED AS SHOWN ON SECTION VIEW FIRE SERVICE ✔ PRIMARY SERVICE AT FLOOR: 1___________
PUSH BUTTON ILLUMINATION: <COLORSELECTIONSIGNA> DOOR: <DOORHANDCORRECTED>
CORRECTED: _________________________ LOCATION: ALTERNATE SERVICE AT FLOOR: __________
<APPROVALSHEETSIGNATURE>
APPROVED BY:____________________________________________________________ <APPROVALSHEETDATE>
DATE: _______________
FAILURE TO FULLY COMPLETE THIS SHEET MAY RESULT IN DELAY OF SCHEDULE
OIL Veri fica ti on She et
POWER UNIT INFORMATION HYDRAULIC ELEVATOR CONTRACT DATA
WIDTH DEPTH HEIGHT WEIGHT W/OIL (LBS)
5'-0 1/2" 1'-10 15/16" 2'-9" 1,675 TYPE: endura 21 A ELEVATOR DESIGNATION: A
HYDRAULIC FLUID REQUIRED IN SYSTEM = 76 GALLONS SPEED: 110 FPM UP / 135 FPM DOWN CAPACITY: 2,100 LBS
HEAT PRODUCED BY ELEVATOR EQUIPMENT IN HOISTWAY = 8684 BTU/HR
CAR ENCLOSURE: TKLP DOOR HAND: RIGHT FRONT
TO OF TARGET
OF TARGET HOLES = 6'-6 5/8"
PLATFORM THICKNESS: 3 3/8" FINISHED FLOOR: BY OTHERS
GUIDE RAILS
TARGET HOLE
2"
PLUNGER LENGTH: UPPER: 13'-7 5/8" LOWER: 9'-8 7/16"
PLUNGER WALL THK: UPPER: 0.375" LOWER: 0.25"
1 3/4"
REFUGE SPACE CAR PLUNGER O.D: UPPER: 2.5" LOWER: 3.75"
FRONT OF HOISTWAY
REAR OF HOISTWAY
CYLINDER LENGTH: 9'-8 7/8" CYLINDER O.D: 5" WALL THK: 1/4"
4'-0"
SELECTOR
CAR BOLSTER ON 2'-3 7/8"
BOTTOM CAR RUNBY: 6" COMPRESSED BUFFER:
PLATFORM DEPTH
EST. WORKING PRESS: 327 PSI CAR BUFFER STROKE: 2 1/2"
(QTY) SPRING(S) #: (1) 780CB1 TOTAL SPRING(S) CAPACITY: 15,223 LBS
4'-3"
4"
5'-1"
JACK (TYP.) JACK REACTION (EA.): 5,001.00 LBS CAR BUFFER REACTION: 11,610.00 LBS
CLEAR OVERHEAD
S = 3.27 FORMED S = 5.67 FORMED S = 1.38 FORMED
CAR
IN FULL TOP OVER TRAVEL
12'-8"
FRAME
8'-8" TOP OF O.A. CAB
UNDER CROSSHEAD
A = 1.85 7GA x 6" x 2 1/2" A = 2.40 7GA x 8 1/4" x 2 3/4" R = 1.01 10GA
OVERALL CAB HEIGHT
9'-5"
CEILING HEIGHT
FRONT F1
6 1/4"
7'-11"
F2
3'-5" 3'-0" CLR. OPENING 11"
@ FLOORS OMEGA RAIL
1,2 CAR STATION FEATURES: Signa 4 Fixtures, T2 Buttons, Alarm Button, Telephone, Position
1'-4" 6'-0" ROUGH Indicator
OPENING @ TYP. FLR.
PUSH BUTTON MARKINGS: 1, 2
7'-4" ROUGH OPENING FOR
CAR RIDING LANTERN: Return
CONTROLLER ENTRANCE @ FLOOR 2
NOTE A: OIL PIPE LINES AND FITTINGS SHALL BE PROPERLY SUPPORTED TO RELIEVE STRAIN.
NOTE B: ALL REACTIONS INCLUDE ALLOWANCE FOR IMPACT.
HOISTWAY PLAN NOTE C: THYSSENKRUPP ELEVATOR TO BE NOTIFIED OF ANY CHANGE TO ELEVATOR
HOISTWAY OR MACHINE ROOM DESIGN.
NOTE D: ELEVATOR DESIGN & FABRICATION BASED ON ESTIMATED CAB WEIGHT SHOWN.
LAYOUT APPROVAL WILL BE CONSTRUED AS FINAL CAR WEIGHT, UNLESS OTHERWISE NOTIFIED.
BY OTHERS
THE FOLLOWING CONDITIONS MUST BE MET BEFORE INSTALLATION IS COMPLETED AND ARE NOT INCLUDED IN THE ELEVATOR CONTRACT
ELECTRICAL DATA
GENERAL CONTRACTOR MUST FORWARD POWER REQUIREMENTS TO THE ELECTRICAL CONTRACTOR.
NOTE: A FOURTH WIRE OF SAME SIZE AS THREE PHASE WIRES IS REQUIRED FOR GROUNDING PURPOSES TO MINIMIZE ELECTRICAL NOISE
INTERFERENCE. THE GROUNDING WIRE MUST BE CONNECTED TO THE BUILDING ELECTRICAL SYSTEM GROUND.
A MEANS TO AUTOMATICALLY DISCONNECT THE MAIN LINE PER POWER SUPPLY TO THE ELEVATOR PRIOR TO THE APPLICATION OF WATER
IN THE ELEVATOR HOISTWAY WILL BE FURNISHED BY THE ELECTRICAL CONTRACTOR THIS MEANS SHALL NOT BE SELF RESETTING.
DEDICATED 120 VOLT, 15 AMP SERVICE, ALONG WITH TELEPHONE CIRCUIT WHEN REQUIRED TO TERMINALS OF EACH REQUIRED
CONTROLLER (AS LOCATED ON ENTRANCE PAGE) FOR THE FOLLOWING: ADA PHONE PROVIDED
- CAR LIGHT AND ALARM CIRCUIT WITH GFCI PROTECTION PER NEC.
- GROUP CONTROL WHEN REQUIRED.
NET TRAVEL
ACCESS TO THESE COMPONENTS WILL BE FROM INSIDE THE HOISTWAY. THIS WILL REQUIRE THYSSENKRUPP ELEVATOR TO BE ON SITE.
NOTE: IF STANDBY POWER IS SUPPLIED TO ELEVATOR, CAR LIGHT AND ALARM CIRCUIT AND GROUP CONTROL SERVICE MUST BE
15'-0"
3 WAY LIGHT SWITCH LOCATED 4'-0" ABOVE THE CONTROLLER LANDING FLOOR.
HOISTWAY WIDTH CONDUIT AND WIRING FROM HOISTWAY TO ELEVATOR MONITORING PANELS BY OTHERS.
3'-8" 3'-8" PROVIDE A POWER TRANSFER WARNING CONTACT THAT CLOSES 20 SECONDS PRIOR TO TRANSFER IN EITHER DIRECTION AND IT OPENS
WHEN TRANSFER IS COMPLETE.
2 3/4" 6'-10 1/2" 2 3/4" TOTAL FULL LOAD UP SPEED AMPS IS BASED ON 100% OF ELEVATOR CAPACITY, THE VALUE NEEDED FOR EMERGENCY POWER SIZING.
BACK TO BACK RAILS THE HYDRAULIC MOTORS ARE RATED FOR INTERMITTENT DUTY (SEC. 620-13 AND 430-33). BRANCH CIRCUIT CONDUCTORS CAN BE SIZED
6'-3" FOR AN AMPACITY 90% OF THE MOTORS NAMEPLATE RATING AS DETERMINED BY (SEC. 430-22 [E])
DISTANCE BETWEEN RAILS HEAT SENSOR REQUIRED AT CONTROLLER FLOOR TO ACTIVATE SHUNT. HEAT SENSOR IS TO BE LOCATED WITHIN 2'-0" OF THE
PIT LADDER
SPRINKLER HEAD.
4'-0" MAX
BATTERY OPERATION LOWERING IS PROVIDED. A MECHANICAL AUXILIARY CONTACT SHALL BE INSTALLED ON THE DISC SWITCH FOR EACH CAR.
THE AUXILIARY CONTACT SHALL BE CONFIGURED AS SPST AT 1A 110VAC (MIN). THE AUXILIARY CONTACT SHALL BE OPEN WHEN THE DISC SWITCH
IS IN THE OPEN POSITION. IF A SHUNT TRIP CIRCUIT BREAKER IS PROVIDED, AN AUXILIARY CONTACT SHALL BE INSTALLED ON THE CIRCUIT BREAKER.
RAILS
PRIMARY FIRE SERVICE LOCATED AT FLOOR: 1
1'-0"
ALTERNATE FIRE SERVICE LOCATION AT FLOOR:
BREAKERS AND DISCONNECT PROVIDED BY THYSSENKRUPP ELEVATOR
HOISTWAY DEPTH
150 AMP CIRCUIT BREAKER PROVIDED IN CONTROLLER BY THYSSENKRUPP ELEVATOR.
TOTAL FULL LOAD SHORT CIRCUIT
ELEVATOR POWER HORSE STARTING RATED
PIT DEPTH
5'-9"
DESIGNATOR SUPPLY POWER A.C. AMPS A.C. AMPS (AT 600V OR LESS)
A.C. AMPS
JACKS
4'-0"
OIL LINE
7 9/16"
2 1/2"
3'-0 3/4"
GENERAL DATA
A PLUMB HOISTWAY BUILT ACCORDING TO CODE AND SIZES SHOWN.
ADEQUATE SUPPORT FOR JACK, GUIDE RAIL BRACKETS, AND BUFFERS (FOR REACTIONS SHOWN)
HOISTWAY BARRICADES AND ALL CUTTING AND PATCHING TO INSTALL HOISTWAY ENTRANCES, SILLS, HALL FIXTURES, OIL,
AND ELECTRIC LINES.
SUMP PIT SIZE TO BE PIT LADDER PER CAR (ACCORDING TO CODE) NOTE: MUST BE CLEAR OF ALL ELEVATOR EQUIPMENT.
FRONT DETERMINED BY LEAVE OFF WALL PER ROUGH OPENING DIMENSIONS WHERE ENTRANCE IS INCLUDED. SEE INSTALLATION PROCEDURES FOR
ELEVATION VIEW 6'-8"
GENERAL CONTRACTOR FRAME-TO-WALL INTERFACE DETAILS TO ENSURE CONFORMANCE WITH LABELED ENTRANCE INTERFACE CONSTRUCTION.
AT CONTROLLER FLOOR, LEAVE OUT ENTIRE WALL. SEE ENTRANCE DRAWING FOR DETAILS. CONTROLLER @ FLOOR: 2
BETWEEN CENTERLINE OF JACKS POCKETS IN CORRIDOR WALL FOR HALL FIXTURES. NOTE: MUST BE LOCATED AS DIRECTED BY ELEVATOR CONTRACTOR
SMOKE SENSORS (AS REQUIRED)
PIT PLAN PIT LADDER
ELEVATOR MEETS ASME A17.1 2010 CODE.
A PROPERLY VENTED HOISTWAY AND MAINTAINED BETWEEN 32 F (0 C) AND 104 F (40 C) WITH NON-CONDENSING HUMIDITY
POSITION OF SUMP PIT CANNOT BE RELOCATED
OF 10-95% PER LOCAL BUILDING CODE.
5"
SAFETY BEAM REQUIRED PER OSHA 1926 502 PROVIDED AND INSTALLED BY OTHERS, AS DIRECTED BY THYSSENKRUPP FIELD
OFFICE DESIGN LOAD = 5,000 LBS (STATIC, NOT IMPACT)
THIS DRAWING AND ALL INFORMATION THEREON IS THE PROPRIETARY PROPERTY OF FOR: TALLEY EYE INSTITUTE DRAWN REV JOB NUMBER DATE SHEET
THYSSENKRUPP ELEVATOR AND MUST NOT BE MADE PUBLIC OR COPIED. THIS DRAWING
IS LOANED SUBJECT TO RETURN ON DEMAND AND IS NOT TO BE USED DIRECTLY OR ADDRESS: 6149 E COLUMBIA ST
JW A 1393-752-01A 8/16/2018 4 OF 7
INDIRECTLY, IN ANY MANNER DETRIMENTAL TO THE INTEREST OF THYSSENKRUPP ELEVATOR. CITY: EVANSVILLE, IN 47711
SECTION[RH -CO]
IF A CUT STARTER RAIL IS CALLED FOR IN THE STACK,
CONFIRM THE NUMBER OF SPLICES PRIOR TO CUTTING
REAR OF HOISTWAY
RAIL SECTION
DIMENSIONS
SAFETY BEAM
4'-0 3/4"
BRACKET LOCATION
DIMENSIONS
8'-3" ROUGH FRONT OF HOISTWAY
2" OPENING HEIGHT
2 1
REFER TO SECTION SHEET FOR CONTROLLER ENTRANCE ROUGH OPENING WIDTH TYPICAL SURFACE TYP GROUT SOLID ALL AROUND. GROUT SOLID ALL AROUND.
WHERE DISTANCE BETWEEN FLOORS EXCEEDS THE MAXIMUM BRACKET SPAN, BRACKET SUPPORT MUST BE
MOUNTING DETAILS TYP TYP
PROVIDED MIDWAY. BRACKET SUPPORT WILL NEED TO BE SUPPLIED BY OTHERS TO ALLOW FOR RAIL 30" DRYWALL INSERT. BOLT TO WOOD
30 X 6" STEEL PLATE WELDED TO TUBE 30 X 6" STEEL PLATE WELDED TO TUBE 30 X 6" STEEL PLATE WELDED TO
BEAM SUPPORT (INSERT) PROVIDED
ATTACHMENT. INSIDE SUPPORT SHALL NOT BE RECESSED BEHIND WALL SYSTEM AND SHALL NOT BE PROUD BY TKE, INSTALLED BY G.C.
STEEL PROVIDED AND INSTALLED STEEL PROVIDED AND INSTALLED STEEL PROVIDED AND INSTALLED
BY G.C. MOUNT FLUSH WITH WALL. BY G.C. MOUNT FLUSH WITH WALL. BY G.C. MOUNT FLUSH WITH WALL.
BY MORE THAN 1/4 AT ANY POINT. COORDINATE WITH TKE SUPPORT/OPERATIONS MANAGER MOUNT FLUSH WITH WALL.
THIS DRAWING AND ALL INFORMATION THEREON IS THE PROPRIETARY PROPERTY OF FOR: TALLEY EYE INSTITUTE DRAWN REV JOB NUMBER DATE SHEET
THYSSENKRUPP ELEVATOR AND MUST NOT BE MADE PUBLIC OR COPIED. THIS DRAWING
IS LOANED SUBJECT TO RETURN ON DEMAND AND IS NOT TO BE USED DIRECTLY OR ADDRESS: 6149 E COLUMBIA ST
JW A 1393-752-01A 8/16/2018 5 OF 7
INDIRECTLY, IN ANY MANNER DETRIMENTAL TO THE INTEREST OF THYSSENKRUPP ELEVATOR. CITY: EVANSVILLE, IN 47711
PLEASE REFERENCE THE RAIL STACK SHEET OF THIS PACKAGE FOR
BUILDING LANDING MATRIX FOR ELEVATOR: A
ELEVATOR: A FRONT ENTRANCE SCHEDULE
WALL SIZE
FLOOR ENTRANCE DIMS. WALL TYPE
ACTUAL OA. FRAME "B" DIM.
2 7'-0" H X 3'-0" W TBD TBD TBD
1 7'-0" H X 3'-0" W TBD TBD TBD
6'-0"
ROUGH OPENING WIDTH
0 1/8"
2"
8'-3"
REACTIONS (LBS.) DUE TO LOADS ON DOOR PANELS, APPROX.
LOBBY SIDE
NOTE "A":
8" MINIMUM STRUCTURAL
SUPPORT FOR SILL INSTALLATION
EACH FLOOR
2" BELOW
THIS DRAWING AND ALL INFORMATION THEREON IS THE PROPRIETARY PROPERTY OF FOR: TALLEY EYE INSTITUTE DRAWN REV JOB NUMBER DATE SHEET
THYSSENKRUPP ELEVATOR AND MUST NOT BE MADE PUBLIC OR COPIED. THIS DRAWING
IS LOANED SUBJECT TO RETURN ON DEMAND AND IS NOT TO BE USED DIRECTLY OR ADDRESS: 6149 E COLUMBIA ST
JW A 1393-752-01A 8/16/2018 6 OF 7
INDIRECTLY, IN ANY MANNER DETRIMENTAL TO THE INTEREST OF THYSSENKRUPP ELEVATOR. CITY: EVANSVILLE, IN 47711
ENTRANCE WALL DIMENSIONS PLEASE REFERENCE THE RAIL STACK SHEET OF THIS PACKAGE FOR
DIM "C" MIN. WALL DIM "D" WALL FACE DIM "E" SHAFT
THK. REQUIRED TO FRAME FACE LINER THICKNESS
BUILDING LANDING MATRIX
FOR ELEVATOR: A
8" 3/4" 1" ELEVATOR: A FRONT ENTRANCE SCHEDULE
WALL SIZE
FLOOR ENTRANCE DIMS. WALL TYPE
ACTUAL OA. FRAME "B" DIM.
2 7'-0" H X 3'-0" W TBD TBD TBD
1 7'-0" H X 3'-0" W TBD TBD TBD
11 3/4" (DIM "E" ) SHAFT LINER FILLER BY G.C.
120V DEDICATED CAB LIGHT CIRCUIT
9 3/4"
SILL BUILDING POW ER
8 3/4" (SEE CONTROLLER KNOCK OUT DETAIL) TOTAL WEIGHT ELEVATOR A ELEVATOR
5" DIM "C" CAB AND HALL DOORS 290 LBS
4 3/4"
DIM "B" SEE FEATURES OF YOUR ENTRANCES
ENTRANCE SCHEDULE FEATURES FINISH LOCATION
7 5/8"
3"
__________ @1,2
BASE LAYER DRYW ALL LOBBY SIDE KICKPLATES:
DIM "D" __________
BINDERS: @1,2
1" 2" @1,2
FACE LAYER DRYW ALL SILL FINISH: ALUMINUM
2" CLEAR OPENING WIDTH 2"
1'- 11" FRAME REFER TO DOOR SCHEDULE FRAME
FIRE ALARM
LOBBY SIDE PHONE
ENTRANCE PLAN VIEW
CONTROLLER KNOCKOUT DETAIL
FEATURES OF ENTRANCES DATA
SILL MAXIMUM WHEEL LOADS 625 LBS
KEYHOLES TO BE INCLUDED
THIS FRAME HAS A WARNOCK HERSEY LABEL OF 2 HOURS
DUST COVERS NOT INCLUDED
0 1/8"
2"
NOTES:
GENERAL CONTRACTOR RESPONSIBLE FOR HOISTWAY REINFORCING
AT FLOOR SLAB BEFORE INSTALLATION OF ENTRANCE FRAMES.
MINIMUM OF 4" HIGH X 8" WIDE REINFORCED CONCRETE, REINFORCED
LOBBY SIDE
R2 R1 NOTE "A":
SEE NOTE "A"
8" MINIMUM STRUCTURAL
4'-6" 1'-10 1/2" SUPPORT FOR SILL INSTALLATION
CONSTRUCTION DETAIL VIEW
FOR REPRESENTATION ONLY
ENTRANCE SIDE VIEW ENTRANCE ELEVATION VIEW
ENTRANCE TYPE : M721 1 SPEED ENTRANCE CHART
FOR ELEVATOR A RIGHT HAND FRONT ENTRANCE M721 ENTRANCE:
FOR ELEVATOR A CENTER OPENING AND 1 SPEED = FRAME OPENING + 1'-3"
2 SPEED = FRAME OPENING + 1'-5"
LEAVE OFF ENTIRE WALL AT FLOOR 2 R2 254
FOR FRAME AND CONTROLLER INSTALLATION R1 609
CASE 1
DOOR REACTION
THIS DRAWING AND ALL INFORMATION THEREON IS THE PROPRIETARY PROPERTY OF FOR: TALLEY EYE INSTITUTE DRAWN REV JOB NUMBER DATE SHEET
THYSSENKRUPP ELEVATOR AND MUST NOT BE MADE PUBLIC OR COPIED. THIS DRAWING
IS LOANED SUBJECT TO RETURN ON DEMAND AND IS NOT TO BE USED DIRECTLY OR ADDRESS: 6149 E COLUMBIA ST
JW A 1393-752-01A 8/16/2018 7 OF 7
INDIRECTLY, IN ANY MANNER DETRIMENTAL TO THE INTEREST OF THYSSENKRUPP ELEVATOR. CITY: EVANSVILLE, IN 47711