Micom P543 and P545: Current Differential Relay (With Distance Protection) 2"

Download as pdf or txt
Download as pdf or txt
You are on page 1of 50

MiCOM P543 and P545

Current Differential Relay (with Distance Protection)

P543_P545/EN PM/2"

Software Version 54

PICS and MICS


Note: The technical manual for this device gives instructions for its installation, commissioning, and operation.
However, the manual cannot cover all conceivable circumstances or include detailed information on all topics.
In the event of questions or specific problems, do not take any action without proper authorization. Contact
the appropriate Schneider Electric technical sales office and request the necessary information.

Any agreements, commitments, and legal relationships and any obligations on the part of Schneider Electric
including settlements of warranties, result solely from the applicable purchase contract, which is not affected
by the contents of the technical manual.

This device MUST NOT be modified. If any modification is made without the express permission of
Schneider Electric, it will invalidate the warranty, and may render the product unsafe.

The Schneider Electric logo and any alternative version thereof are trademarks and service marks of Schneider Electric.

All trade names or trademarks mentioned herein whether registered or not, are the property of their owners.

This manual is provided for informational use only and is subject to change without notice.

© 2011, Schneider Electric. All rights reserved.


MiCOM P543 and P545 (with Distance Protection) PICS and MICS

CONTENTS

1 PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT (PICS) 5


1.1 Introduction 5
1.2 ACSI Basic Conformance Statement 5
1.3 ACSI Models Conformance Statement 6
1.4 ACSI Service Conformance Statement 7
2 MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) 11
2.1 Introduction 11
2.2 Objective 11
2.3 Logical Device Definitions 11
2.3.1 IEC 61850 Logical Device Data Model 11
2.4 Logical Node Definitions 14
2.4.1 Logical Node: GGIO_ALM_96 15
2.4.2 Logical Node: GGIO_IND_10 17
2.4.3 Logical Node: GGIO_IND_18 18
2.4.4 Logical Node: GGIO_IND_32 18
2.4.5 Logical Node: GGIO_IND_8 19
2.4.6 Logical Node: LLN0_CONTROL 20
2.4.7 Logical Node: LLN0_PROT 20
2.4.8 Logical Node: LLN0_STANDARD 21
2.4.9 Logical Node: LPHD_STANDARD 21
2.4.10 Logical Node: MMXU_FOURIER 21
2.4.11 Logical Node: MMXU_IDIFF 22
2.4.12 Logical Node: MMXU_RMS 22
2.4.13 Logical Node: MSQI_ALL 22
2.4.14 Logical Node: MSQI_ VOLTAGE 23
2.4.15 Logical Node: MSTA_I_W_VAR 23
2.4.16 Logical Node: PDIF_BASIC 24
2.4.17 Logical Node: PDIS_BASIC 24
2.4.18 Logical Node: PFRC_NO_SEG 24
2.4.19 Logical Node: PSCH_BASIC 24
2.4.20 Logical Node: PSOF_BASIC 25
2.4.21 Logical Node: PTOC_NEU 25
2.4.22 Logical Node: PTOC_NO_SEG 25
2.4.23 Logical Node: PTOC_SEG 26
2.4.24 Logical Node: PTOF_NO_SEG 26
2.4.25 Logical Node: PTOV_NEU 26
2.4.26 Logical Node: PTOV_NO_SEG 26
2.4.27 Logical Node: PTOV_SEG 27
2.4.28 Logical Node: PTRC_NO_SEG 27
2.4.29 Logical Node: PTTR_NO_SEG 27
2.4.30 Logical Node: PTUF_NO_SEG 27

P543_P545/EN PM/D42 Page 1


PICS and MICS MiCOM P543 and P545 (with Distance Protection)

2.4.31 Logical Node: PTUV_SEG 28


2.4.32 Logical Node: RBRF_EXTTRIP 28
2.4.33 Logical Node: RDRE_BASIC 28
2.4.34 Logical Node: RFLO_BASIC 28
2.4.35 Logical Node: RPSB_BASIC 29
2.4.36 Logical Node: RPSB_OST 29
2.4.37 Logical Node: RREC_NO_SEG 29
2.4.38 Logical Node: RSYN_DIFCLC 29
2.4.39 Logical Node: XCBR_BASIC 30
2.5 Common Data Class Definitions 30
2.5.1 Common Data Class: ACD_NEU 31
2.5.2 Common Data Class: ACD_NO_SEG 31
2.5.3 Common Data Class: ACD_SEG 31
2.5.4 Common Data Class: ACD_SEG_NEU 32
2.5.5 Common Data Class: ACT_NEU 32
2.5.6 Common Data Class: ACT_NO_SEG 33
2.5.7 Common Data Class: ACT_SEG 33
2.5.8 Common Data Class: ACT_SEG_NEU 33
2.5.9 Common Data Class: CMV_MAG_ANG_FLOAT 34
2.5.10 Common Data Class: CMV_MAG_FLOAT 34
2.5.11 Common Data Class: DEL_SEG_ANG 34
2.5.12 Common Data Class: DPC_STATUS 35
2.5.13 Common Data Class: DPL_STANDARD 35
2.5.14 Common Data Class: INC_MOD 35
2.5.15 Common Data Class: INC_MOD_D_PRIV 35
2.5.16 Common Data Class: INS_AR_STATE 36
2.5.17 Common Data Class: INS_BASIC 36
2.5.18 Common Data Class: INS_BEH 36
2.5.19 Common Data Class: INS_BEH_D_PRIV 36
2.5.20 Common Data Class: INS_HEALTH 37
2.5.21 Common Data Class: LPL_LLN0 37
2.5.22 Common Data Class: LPL_LN 37
2.5.23 Common Data Class: LPL_LN_PRIV 37
2.5.24 Common Data Class: MV_FLOAT 38
2.5.25 Common Data Class: MV_FLOAT_D 38
2.5.26 Common Data Class: SEQ_MAG_ANG 38
2.5.27 Common Data Class: SPC_STATUS 39
2.5.28 Common Data Class: SPS_D 39
2.5.29 Common Data Class: SPS_WD 39
2.5.30 Common Data Class: WYE_RES_ANG_D 40
2.5.31 Common Data Class: WYE_SEG 40
2.5.32 Common Data Class: WYE_SEG_ANG_D 40
2.5.33 Common Data Class: WYE_SEG_D 40
2.5.34 Common Data Class: WYE_SEG_RES_D 41
2.6 Common Data Attribute Type Definitions 42
2.6.1 Component: AnalogueValue_Float 42

Page 2 P543_P545/EN PM/D42


MiCOM P543 and P545 (with Distance Protection) PICS and MICS

2.6.2 Component: Unit_No_Multiplier 42


2.6.3 Component: Vector_Magnitude_Float 42
2.6.4 Component: Vector_MagnitudeAngle_Float 42
2.7 Enumerated Type Definitions 43
2.7.1 Enumerated Type: AutoRecSt 43
2.7.2 Enumerated Type: Beh 43
2.7.3 Enumerated Type: ctlModel 43
2.7.4 Enumerated Type: Dbpos 43
2.7.5 Enumerated Type: dir 43
2.7.6 Enumerated Type: Health 44
2.7.7 Enumerated Type: Mod 44
2.7.8 Enumerated Type: seqT 44
2.7.9 Enumerated Type: SIUnit 44
2.8 MMS Data-Type Conversions 46

TABLES

Table 1 - Basic conformance statement 5


Table 2 - ACSI models conformance statement 7
Table 3 - ACSI service conformance statement 10

P543_P545/EN PM/D42 Page 3


PICS and MICS MiCOM P543 and P545 (with Distance Protection)

Notes:

Page 4 P543_P545/EN PM/D42


MiCOM P543 and P545 (with Distance Protection) PICS and MICS

1 PROTOCOL IMPLEMENTATION CONFORMANCE


STATEMENT (PICS)

1.1 Introduction
This specification is the Protocol Implementation Conformance Statement (PICS) and
presents the ACSI conformance statements as defined in Annex A of Part 7-2 of the
IEC 61850 standard specifications.

1.2 ACSI Basic Conformance Statement


The basic conformance statement is defined in Table 1.
Client/ Server/ Value/
Subscriber Publisher Comments

Client-Server Roles

B11 Server side (of two-party-application-association)   c1 Y


B12 Client side (of two-party-application-association) c1 N  

SCSMs Supported

B21 SCSM: IEC 61850-8-1 used N Y


B22 SCSM: IEC 61850-9-1 used N N
B23 SCSM: IEC 61850-9-2 used N N
B24 SCSM: Other

Generic Substation Event Model (GSE)

B31 Publisher side   O Y


B32 Subscriber side O Y  

Transmission of Sampled Value Model (SVC)

B41 Publisher side   O N


B42 Subscriber side O N  
c1 - Shall be ‘M’ if support for LOGICAL-DEVICE model has been declared
O - Optional
M - Mandatory
Y - Yes (supported)
N - No (not supported)
Table 1 - Basic conformance statement

P543_P545/EN PM/D42 Page 5


PICS and MICS MiCOM P543 and P545 (with Distance Protection)

1.3 ACSI Models Conformance Statement


The ACSI models conformance statement is defined in Table 2.
Client/ Server/ Value/
Subscriber Publisher Comments

If Server Side (B1) Supported

M1 Logical device c2 N c2 Y
M2 Logical node c3 N c3 Y
M3 Data c4 N c4 Y
M4 Data set c5 N c5 Y
M5 Substitution O N O N
M6 Setting group control O N O N
Reporting
M7 Buffered report control O N O N
M7-1 sequence-number
M7-2 report-time-stamp
M7-3 reason-for-inclusion
M7-4 data-set-name
M7-5 data-reference
M7-6 buffer-overflow
M7-7 entryID
M7-8 BufTim
M7-9 IntgPd
M7-10 GI
M8 Unbuffered report control O N O Y
M8-1 sequence-number N Y
M8-2 report-time-stamp N Y
M8-3 reason-for-inclusion N Y
M8-4 data-set-name N Y
M8-5 data-reference N Y
M8-6 BufTim N Y
M8-7 IntgPd N Y
M8-8 GI N Y
Logging O N O N
M9 Log control O N O N
M9-1 IntgPd N N
M10 Log O N O N
M11 Control M N M N

If GSE (B31/32) is Supported

Page 6 P543_P545/EN PM/D42


MiCOM P543 and P545 (with Distance Protection) PICS and MICS

Client/ Server/ Value/


Subscriber Publisher Comments
GOOSE O Y O Y
M12-1 entryID N N
M12-2 dataRefInc N N
M13 GSSE O N O N

If SVC (41/42) is Supported

M14 Multicast SVC O N O N


M15 Unicast SVC O N O N
M16 Time M Y M N Time source
with required
accuracy shall
be available
M17 File Transfer O N O Y
c2 - Shall be ‘M’ if support for LOGICAL-NODE model has been declared
c3 - Shall be ‘M’ if support for DATA model has been declared
c4 - Shall be ‘M’ if support for DATA-SET, Substitution, Report, Log Control, or Time model has been declared
c5 - Shall be ‘M’ if support for Report, GSE, or SMV models has been declared
Table 2 - ACSI models conformance statement

1.4 ACSI Service Conformance Statement


The ACSI service conformance statement is defined in Table 3 (depending on the
statements in Table 1).
AA: Client/ Server/
Services Comments
TP/MC Subscriber Publisher
Server (clause 6)
S1 ServerDirectory TP N M Y
Application association (clause 7)
S2 Associate M N M Y
S3 Abort M N M Y
S4 Release M N M Y
Logical device (clause 8)
S5 LogicalDeviceDirectory TP M N M Y
Logical node (clause 9)
S6 LogicalNodeDirectory TP M N M Y
S7 GetAllDataValues TP O N M Y
Data (clause 10)
S8 GetDataValues TP M N M Y
S9 SetDataValues TP O N O Y
S10 GetDataDirectory TP O N M Y

P543_P545/EN PM/D42 Page 7


PICS and MICS MiCOM P543 and P545 (with Distance Protection)

AA: Client/ Server/


Services Comments
TP/MC Subscriber Publisher
S11 GetDataDefinition TP O N M Y
Data set (clause 11)
S12 GetDataSetValues TP O N M Y
S13 SetDataSetValues TP O N O N
S14 CreateDataSet TP O N O N
S15 DeleteDataSet TP O N O N
S16 GetDataSetDirectory TP O N O Y
Substitution (clause 12)
S17 SetDataValues TP M N M N
Setting group control (clause 13)
S18 SelectActiveSG TP O N O N
S19 SelectEditSG TP O N O N
S20 SetSGValues TP O N O N
S21 ConfirmEditSGValues TP O N O N
S22 GetSGValues TP O N O N
S23 GetSGCBValues TP O N O N
Reporting (clause 14)
Buffered report control block (BRCB)
S24 Report TP c6 N c6 N
S24-1 data-change (dchg)
S24-2 qchg-change (qchg)
S24-3 data-update (dupd)
S25 GetBRCBValues TP c6 N c6 N
S26 SetBRCBValues TP c6 N c6 N
Unbuffered report control block (URCB)
S27 Report TP c6 N c6 Y
S27-1 data-change (dchg) N Y
S27-2 qchg-change (qchg) N N
S27-3 data-update (dup N N
S28 GetURCBValues TP c6 N c6 Y
S29 SetURCBValues TP c6 N c6 Y
c6 - Shall declare support for at least one (BRCB or URCB)
Logging (clause 14)
Log control block
S30 GetLCBValues TP M N M N
S31 SetLCBValues TP O N M N
Log
S32 QueryLogByTime TP c7 N M N

Page 8 P543_P545/EN PM/D42


MiCOM P543 and P545 (with Distance Protection) PICS and MICS

AA: Client/ Server/


Services Comments
TP/MC Subscriber Publisher
S33 QueryLogAfter TP c7 N M N
S34 GetLogStatusValues TP M N M N
c7 - Shall declare support for at least one (QueryLogByTime or QueryLogByEntry)
Generic substation event model (GSE) (clause 14.3.5.3.4)
GOOSE-CONTROL-BLOCK
S35 SendGOOSEMessage MC c8 N c8 Y
S36 GetGoReference TP O N c9 Y
S37 GetGOOSEElementNumber TP O N c9 Y
S38 GetGoCBValues TP O N O N
S39 SetGoCBValues TP O N O N
GSSE-CONTROL-BLOCK
S40 SendGSSEMessage MC c8 N c8 N
S41 GetGsReference TP O N c9 N
S42 GetGSSEElementNumber TP O N c9 N
S43 GetGsCBValues TP O N O N
S44 SetGsCBValues TP O N O N
c8 - Shall declare support for at least one (SendGOOSEMessage or SendGSSEMessage)
c9 - Shall declare support if TP association is available
Transmission of sampled value model (SVC) (clause 16)
Multicast SVC
S45 SendMSVMessage MC c10 N c10 N
S46 GetMSVCBValues TP O N O N
S47 SetMSVCBValues TP O N O N
Unicast SVC
S48 SendUSVMessage TP c10 N c10 N
S49 GetUSVCBValues TP O N O N
S50 SetUSVCBValues TP O N O N
c10 - Shall declare support for at least one (SendMSVMessage or SendUSVMessage)
Control (clause 17.5.1)
S51 Select M N O N
S52 SelectWithValue TP M N O N
S53 Cancel TP O N O N
S54 Operate TP M N M N
S55 Command-Termination TP M N O N
S56 TimeActivated-Operate TP O N O N
File transfer (clause 20)
S57 GetFile TP O N M Y
S58 SetFile TP O N O N

P543_P545/EN PM/D42 Page 9


PICS and MICS MiCOM P543 and P545 (with Distance Protection)

AA: Client/ Server/


Services Comments
TP/MC Subscriber Publisher
S59 DeleteFile TP O N O Y
S60 GetFileAttributeValues TP O N M Y
Time (5.5)
T1 Time resolution of internal clock 1ms Nearest
negative power
of 2 in seconds
T2 Time accuracy of internal clock 1ms T0
T1
T2
T3
T4
T5
T3 Supported TimeStamp resolution 1ms Nearest value
of 2**-n in
seconds
according to
5.5.3.7.3.3
Table 3 - ACSI service conformance statement

Page 10 P543_P545/EN PM/D42


MiCOM P543 and P545 (with Distance Protection) PICS and MICS

2 MODEL IMPLEMENTATION CONFORMANCE STATEMENT


(MICS)

2.1 Introduction
This specification is the Model Implementation Conformance Statement (MICS) and
presents the top-level IEC 61850 data model that has been implemented. The definitions
of all used Logical Nodes and their associated Common Data Classes, components and
associated enumerated values are also included for completeness.
The reader is expected to be conversant with the terminology presented within the
IEC 61850 part 7 series of specifications.

2.2 Objective
To provide comprehensive details of the standard data object model elements supported
by the device. The MICS is conformant to the devices associated ICD (Substation
Configuration Language) file, according to part 6 of the IEC 61850 standards. The layout
of the presented tables within this document are conformant to the part 7 series of the
IEC 61850 standard specifications with the following exceptions:
 The "Trigger Options" field is not presented
 The "M/O" field is not present as the definitions are as deployed within the model
 An additional column "X" is used to signify Schneider Electric custom attributes

2.3 Logical Device Definitions


The MiCOM relay implements an IEC 61850 server that can contain one or more Logical
Devices. Each Logical Device contains a data model built from instances of specific
Logical Nodes and must consist of at least an instance of the LPHD Logical Node (which
is responsible for providing physical device information) and an instance of the LLN0
Logical Node (for addressing common issues across the Logical Device).
The IEC 61850 data model is contained within the Logical Devices detailed in the table
below. All MiCOM devices will name the supported Logical Devices consistently to ensure
that data model variables with the same purpose will have the same name within each
MiCOM server.
Logical Device Comment/Usage
Control P543/5 Controls Domain
Measurements P543/5 Measurements Domain
Protection P543/5 Protection Domain
Records P543/5 Records Domain
System P543/5 System Domain

2.3.1 IEC 61850 Logical Device Data Model


The IEC 61850 Logical Device top-level data model consists of instances of Logical
Nodes. The data model name for a Logical Node instance is constructed from an optional
prefix (known as the wrapper), the Logical Node name, and an instance ID (or suffix).
The presented data model is in an alphabetically sorted order, rather than a logical order,
because this is the natural order of the data when presented by a native MMS browser.
(Higher level browsers can of course impart any ordering that they desire).

P543_P545/EN PM/D42 Page 11


PICS and MICS MiCOM P543 and P545 (with Distance Protection)

LD LN Instance LN Type Description


Control
ArcRREC1 RREC_NO_SEG Auto-Reclose
AscRSYN1 RSYN_DIFCLC System Checks - Check Sync 1
AscRSYN2 RSYN_DIFCLC System Checks - Check Sync 2
LLN0 LLN0_CONTROL Controls Logical Device
LPHD1 LPHD_STANDARD Physical Device Information
OstRPSB1 RPSB_OST Out of Step Tripping (Main Trip)
OstRPSB2 RPSB_OST Out of Step Tripping (Predictive Trip)
PsbRPSB1 RPSB_BASIC Zone 1 Ph/Gnd Power Swing Blocking
PsbRPSB2 RPSB_BASIC Zone 2 Ph/Gnd Power Swing Blocking
PsbRPSB3 RPSB_BASIC Zone 3 Ph/Gnd Power Swing Blocking
PsbRPSB4 RPSB_BASIC Zone 4 Ph/Gnd Power Swing Blocking
PsbRPSB5 RPSB_BASIC Zone P Ph/Gnd Power Swing Blocking
XCBR1 XCBR_BASIC Circuit Breaker Monitoring (Pole 1)
XCBR2 XCBR_BASIC Circuit Breaker Monitoring (Pole 2)
XCBR3 XCBR_BASIC Circuit Breaker Monitoring (Pole 3)
Measurements
DifMMXU1 MMXU_IDIFF Current Differential Measurements
FouMMXU1 MMXU_FOURIER Fourier Measurements
LLN0 LLN0_STANDARD Measurements Logical Device
LPHD1 LPHD_STANDARD Physical Device Information
MSQI1 MSQI_ALL Sequence Measurements
MSTA1 MSTA_I_W_VAR Metering Statistics
RmsMMXU1 MMXU_RMS RMS Measurements
VolCmpMSQI1 MSQI_VOLTAGE Compensated Overvoltage Measurements
Protection
CbfRBRF1 RBRF_EXTTRIP CB Fail 1
CbfRBRF2 RBRF_EXTTRIP CB Fail 2
DfpPFRC1 PFRC_NO_SEG df/dt> 1 Frequency Rate of Change
DfpPFRC2 PFRC_NO_SEG df/dt> 2 Frequency Rate of Change
DfpPFRC3 PFRC_NO_SEG df/dt> 3 Frequency Rate of Change
DfpPFRC4 PFRC_NO_SEG df/dt> 4 Frequency Rate of Change
DifPDIF1 PDIF_BASIC Current Differential
DisPDIS1 PDIS_BASIC Zone 1 Ph/Gnd Distance
DisPDIS2 PDIS_BASIC Zone 2 Ph/Gnd Distance
DisPDIS3 PDIS_BASIC Zone 3 Ph/Gnd Distance
DisPDIS4 PDIS_BASIC Zone 4 Ph/Gnd Distance
DisPDIS5 PDIS_BASIC Zone P Ph/Gnd Distance
DisPSCH1 PSCH_BASIC Distance Protection Scheme 1
DisPSCH2 PSCH_BASIC Distance Protection Scheme 2
EfdPTOC1 PTOC_NEU IN1> 1 Earth Fault (Derived)
EfdPTOC2 PTOC_NEU IN1> 2 Earth Fault (Derived)
EfdPTOC3 PTOC_NEU IN1> 3 Earth Fault (Derived)
EfdPTOC4 PTOC_NEU IN1> 4 Earth Fault (Derived)

Page 12 P543_P545/EN PM/D42


MiCOM P543 and P545 (with Distance Protection) PICS and MICS

LD LN Instance LN Type Description


FrqPTOF1 PTOF_NO_SEG F> 1 Over Frequency
FrqPTOF2 PTOF_NO_SEG F> 2 Over Frequency
FrqPTUF1 PTUF_NO_SEG F< 1 Under Frequency
FrqPTUF2 PTUF_NO_SEG F< 2 Under Frequency
FrqPTUF3 PTUF_NO_SEG F< 3 Under Frequency
FrqPTUF4 PTUF_NO_SEG F< 4 Under Frequency
LLN0 LLN0_PROT Protection Logical Device
LPHD1 LPHD_STANDARD Physical Device Information
NgcPTOC1 PTOC_NO_SEG I2> 1 Negative Sequence
NgcPTOC2 PTOC_NO_SEG I2> 2 Negative Sequence
NgcPTOC3 PTOC_NO_SEG I2> 3 Negative Sequence
NgcPTOC4 PTOC_NO_SEG I2> 4 Negative Sequence
OcpPTOC1 PTOC_SEG I> 1 Overcurrent
OcpPTOC2 PTOC_SEG I> 2 Overcurrent
OcpPTOC3 PTOC_SEG I> 3 Overcurrent
OcpPTOC4 PTOC_SEG I> 4 Overcurrent
PTRC1 PTRC_NO_SEG Protection Trip Conditioning
SenEftPTOC1 PTOC_NEU ISEF> 1 Sensitive Earth Fault
SenEftPTOC2 PTOC_NEU ISEF> 2 Sensitive Earth Fault
SenEftPTOC3 PTOC_NEU ISEF> 3 Sensitive Earth Fault
SenEftPTOC4 PTOC_NEU ISEF> 4 Sensitive Earth Fault
SofPSOF1 PSOF_BASIC Switch onto Fault Protection
ThmPTTR1 PTTR_NO_SEG Thermal Overload
TorPSOF1 PSOF_BASIC Trip on Reclose Protection
VtpCmpPTOV1 PTOV_NO_SEG Compensated V1> 1 Overvoltage
VtpCmpPTOV2 PTOV_NO_SEG Compensated V1> 2 Overvoltage
VtpPhsPTOV1 PTOV_SEG V> 1 Overvoltage
VtpPhsPTOV2 PTOV_SEG V> 2 Overvoltage
VtpPhsPTUV1 PTUV_SEG V< 1 Undervoltage
VtpPhsPTUV2 PTUV_SEG V< 2 Undervoltage
VtpResPTOV1 PTOV_NEU VN> 1 Residual Overvoltage
VtpResPTOV2 PTOV_NEU VN> 2 Residual Overvoltage
Records
LLN0 LLN0_STANDARD Records Logical Device
LPHD1 LPHD_STANDARD Physical Device Information
RDRE1 RDRE_BASIC Disturbance Recorder
RFLO1 RFLO_BASIC Fault Locator
System
AlmGGIO1 GGIO_ALM_96 Alarms
FnkGGIO1 GGIO_IND_10 Function Keys
GosGGIO1 GGIO_IND_32 GOOSE Input Signals
GosGGIO2 GGIO_IND_32 GOOSE Output Signals
ImfInpGGIO1 GGIO_IND_8 InterMiCOM Fiber Inputs Status (CH1)
ImfInpGGIO2 GGIO_IND_8 InterMiCOM Fiber Inputs Status (CH2)

P543_P545/EN PM/D42 Page 13


PICS and MICS MiCOM P543 and P545 (with Distance Protection)

LD LN Instance LN Type Description


ImfOutGGIO1 GGIO_IND_8 InterMiCOM Fiber Outputs Status (CH1)
ImfOutGGIO2 GGIO_IND_8 InterMiCOM Fiber Outputs Status (CH2)
LedGGIO1 GGIO_IND_18 Red LED Signals
LedGGIO2 GGIO_IND_18 Green LED Signals
LLN0 LLN0_STANDARD System Logical Device
LPHD1 LPHD_STANDARD Physical Device Information
OptGGIO1 GGIO_IND_32 Opto (32) Inputs
PloGGIO1 GGIO_IND_32 Controls
RlyGGIO1 GGIO_IND_32 Output Contacts

2.4 Logical Node Definitions


The definition tables for each of the Logical Nodes in the top-level data model are
presented in the following sub-sections.
The following table presents a summary of the Logical Node templates used across the
Logical Devices within the overall IEC 61850 product data model:
LN Type (LN Class) Description Name Space
Generic Process I/O (w.r.t 10 Indication
GGIO_IND_10 (GGIO) IEC 61850-7-4:2003
Elements)
Generic Process I/O (w.r.t 18 Indication
GGIO_IND_18 (GGIO) IEC 61850-7-4:2003
Elements)
Generic Process I/O (w.r.t 32 Indication
GGIO_IND_32 (GGIO) IEC 61850-7-4:2003
Elements)
GGIO_IND_8 (GGIO) Generic Process I/O (w.r.t 8 Indication Elements) IEC 61850-7-4:2003
GGIO_ALM_96 (GGIO) Generic Process I/O (w.r.t 96 Alarm Elements) IEC 61850-7-4:2003
LLN0_STANDARD (LLN0) General Logical Node 0 IEC 61850-7-4:2003
LLN0_CONTROL (LLN0) Control Domain Logical Node 0 IEC 61850-7-4:2003
LLN0_PROT (LLN0) Protection Domain Logical Node 0 IEC 61850-7-4:2003
LPHD_STANDARD (LPHD) Px40 Physical Device Information IEC 61850-7-4:2003
MMXU_IDIFF (MMXU) Standard Measurements (w.r.t Current Diff) IEC 61850-7-4:2003
MMXU_RMS (MMXU) Standard Measurements (w.r.t RMS Values) IEC 61850-7-4:2003
MMXU_FOURIER (MMXU) Standard Measurements (w.r.t Fourier Values) IEC 61850-7-4:2003
MSQI_ALL (MSQI) Sequence and Imbalance (w.r.t Pos, Neq, Zero) IEC 61850-7-4:2003
Sequence and Imbalance (w.r.t Pos, Neq, Zero
MSQI_VOLTAGE (MSQI) IEC 61850-7-4:2003
Voltage only)
Metering Statistics (w.r.t Current, Real + Reactive
MSTA_I_W_VAR (MSTA) IEC 61850-7-4:2003
Power - Average + Max Values)
PDIF_BASIC (PDIF) Differential (w.r.t Mandatory Attributes Only) IEC 61850-7-4:2003
PDIS_BASIC (PDIS) Distance (w.r.t Mandatory Attributes Only) IEC 61850-7-4:2003
Rate of Change of Frequency (w.r.t No Phase
PFRC_NO_SEG (PFRC) IEC 61850-7-4:2003
Segregation)
Protection Scheme (w.r.t Mandatory Attributes
PSCH_BASIC (PSCH) IEC 61850-7-4:2003
Only)
PSOF_BASIC (PSOF) Switch-onto-Fault Protection IEC 61850-7-4:2003
PTOC_NEU (PTOC) Timed Overcurrent (w.r.t Neutral) IEC 61850-7-4:2003
PTOC_NO_SEG (PTOC) Timed Overcurrent (w.r.t No Phase Segregation) IEC 61850-7-4:2003

Page 14 P543_P545/EN PM/D42


MiCOM P543 and P545 (with Distance Protection) PICS and MICS

LN Type (LN Class) Description Name Space


PTOC_SEG (PTOC) Timed Overcurrent (w.r.t Phase Segregation) IEC 61850-7-4:2003
PTOF_NO_SEG (PTOF) Over Frequency (w.r.t No Phase Segregation) IEC 61850-7-4:2003
PTOV_NEU (PTOV) Overvoltage (w.r.t Neutral) IEC 61850-7-4:2003
PTOV_NO_SEG (PTOV) Overvoltage (w.r.t No Phase Segregation) IEC 61850-7-4:2003
PTOV_SEG (PTOV) Overvoltage (w.r.t Phase Segregation) IEC 61850-7-4:2003
Protection Trip Conditioning (w.r.t No Phase
PTRC_NO_SEG (PTRC) IEC 61850-7-4:2003
Segregation)
PTTR_NO_SEG (PTTR) Thermal Overload (w.r.t No Phase Segregation) IEC 61850-7-4:2003
PTUF_NO_SEG (PTUF) Under Frequency (w.r.t No Phase Segregation) IEC 61850-7-4:2003
PTUV_SEG (PTUV) Undervoltage (w.r.t Phase Segregation) IEC 61850-7-4:2003
RBRF_EXTTRIP (RBRF) Breaker Failure (w.r.t External Tripping) IEC 61850-7-4:2003
Disturbance Recorder Function (w.r.t Mandatory
RDRE_BASIC (RDRE) IEC 61850-7-4:2003
Attributes Only)
RFLO_BASIC (RFLO) Fault Locator (w.r.t Mandatory Attributes Only) IEC 61850-7-4:2003
Power Swing Detection/Blocking (w.r.t Mandatory
RPSB_BASIC (RPSB) IEC 61850-7-4:2003
Attributes Only)
Power Swing Blocking (w.r.t. Out Of Step
RPSB_OST (RPSB) IEC 61850-7-4:2003
Tripping)
RREC_NO_SEG (RREC) Auto-Reclosing (w.r.t No Phase Segregation) IEC 61850-7-4:2003
Synchronism-check/Synchronizing (w.r.t
RSYN_DIFCLC (RSYN) IEC 61850-7-4:2003
Calculated Differential Measurements)
XCBR_BASIC (XCBR) Circuit Breaker (w.r.t Mandatory Attributes Only) IEC 61850-7-4:2003

2.4.1 Logical Node: GGIO_ALM_96


Description: Generic Process I/O (w.r.t 96 Alarm Elements)
LN Class: GGIO
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behavior
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate
Alm1 SPS_D General Single Alarm
Alm2 SPS_D General Single Alarm
Alm3 SPS_D General Single Alarm
Alm4 SPS_D General Single Alarm
Alm5 SPS_D General Single Alarm
Alm6 SPS_D General Single Alarm
Alm7 SPS_D General Single Alarm
Alm8 SPS_D General Single Alarm
Alm9 SPS_D General Single Alarm
Alm10 SPS_D General Single Alarm
Alm11 SPS_D General Single Alarm
Alm12 SPS_D General Single Alarm
Alm13 SPS_D General Single Alarm

P543_P545/EN PM/D42 Page 15


PICS and MICS MiCOM P543 and P545 (with Distance Protection)

Attribute Attr. Type Explanation T X


Alm14 SPS_D General Single Alarm
Alm15 SPS_D General Single Alarm
Alm16 SPS_D General Single Alarm
Alm17 SPS_D General Single Alarm
Alm18 SPS_D General Single Alarm
Alm19 SPS_D General Single Alarm
Alm20 SPS_D General Single Alarm
Alm21 SPS_D General Single Alarm
Alm22 SPS_D General Single Alarm
Alm23 SPS_D General Single Alarm
Alm24 SPS_D General Single Alarm
Alm25 SPS_D General Single Alarm
Alm26 SPS_D General Single Alarm
Alm27 SPS_D General Single Alarm
Alm28 SPS_D General Single Alarm
Alm29 SPS_D General Single Alarm
Alm30 SPS_D General Single Alarm
Alm31 SPS_D General Single Alarm
Alm32 SPS_D General Single Alarm
Alm33 SPS_D General Single Alarm
Alm34 SPS_D General Single Alarm
Alm35 SPS_D General Single Alarm
Alm36 SPS_D General Single Alarm
Alm37 SPS_D General Single Alarm
Alm38 SPS_D General Single Alarm
Alm39 SPS_D General Single Alarm
Alm40 SPS_D General Single Alarm
Alm41 SPS_D General Single Alarm
Alm42 SPS_D General Single Alarm
Alm43 SPS_D General Single Alarm
Alm44 SPS_D General Single Alarm
Alm45 SPS_D General Single Alarm
Alm46 SPS_D General Single Alarm
Alm47 SPS_D General Single Alarm
Alm48 SPS_D General Single Alarm
Alm49 SPS_D General Single Alarm
Alm50 SPS_D General Single Alarm
Alm51 SPS_D General Single Alarm
Alm52 SPS_D General Single Alarm
Alm53 SPS_D General Single Alarm
Alm54 SPS_D General Single Alarm
Alm55 SPS_D General Single Alarm
Alm56 SPS_D General Single Alarm
Alm57 SPS_D General Single Alarm

Page 16 P543_P545/EN PM/D42


MiCOM P543 and P545 (with Distance Protection) PICS and MICS

Attribute Attr. Type Explanation T X


Alm58 SPS_D General Single Alarm
Alm59 SPS_D General Single Alarm
Alm60 SPS_D General Single Alarm
Alm61 SPS_D General Single Alarm
Alm62 SPS_D General Single Alarm
Alm63 SPS_D General Single Alarm
Alm64 SPS_D General Single Alarm
Alm65 SPS_D General Single Alarm
Alm66 SPS_D General Single Alarm
Alm67 SPS_D General Single Alarm
Alm68 SPS_D General Single Alarm
Alm69 SPS_D General Single Alarm
Alm70 SPS_D General Single Alarm
Alm71 SPS_D General Single Alarm
Alm72 SPS_D General Single Alarm
Alm73 SPS_D General Single Alarm
Alm74 SPS_D General Single Alarm
Alm75 SPS_D General Single Alarm
Alm76 SPS_D General Single Alarm
Alm77 SPS_D General Single Alarm
Alm78 SPS_D General Single Alarm
Alm79 SPS_D General Single Alarm
Alm80 SPS_D General Single Alarm
Alm81 SPS_D General Single Alarm
Alm82 SPS_D General Single Alarm
Alm83 SPS_D General Single Alarm
Alm84 SPS_D General Single Alarm
Alm85 SPS_D General Single Alarm
Alm86 SPS_D General Single Alarm
Alm87 SPS_D General Single Alarm
Alm88 SPS_D General Single Alarm
Alm89 SPS_D General Single Alarm
Alm90 SPS_D General Single Alarm
Alm91 SPS_D General Single Alarm
Alm92 SPS_D General Single Alarm
Alm93 SPS_D General Single Alarm
Alm94 SPS_D General Single Alarm
Alm95 SPS_D General Single Alarm
Alm96 SPS_D General Single Alarm

2.4.2 Logical Node: GGIO_IND_10


Description: Generic Process I/O (w.r.t 10 Indication Elements)
LN Class: GGIO

P543_P545/EN PM/D42 Page 17


PICS and MICS MiCOM P543 and P545 (with Distance Protection)

Attribute Attr. Type Explanation T X


Mod INC_MOD Mode
Beh INS_BEH Behavior
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate
Ind1 SPS_D General Indication
Ind2 SPS_D General Indication
Ind3 SPS_D General Indication
Ind4 SPS_D General Indication
Ind5 SPS_D General Indication
Ind6 SPS_D General Indication
Ind7 SPS_D General Indication
Ind8 SPS_D General Indication
Ind9 SPS_D General Indication
Ind10 SPS_D General Indication

2.4.3 Logical Node: GGIO_IND_18


Description: Generic Process I/O (w.r.t 18 Indication Elements)
LN Class: GGIO
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behavior
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate
Ind1 SPS_D General Indication
Ind2 SPS_D General Indication
Ind3 SPS_D General Indication
Ind4 SPS_D General Indication
Ind5 SPS_D General Indication
Ind6 SPS_D General Indication
Ind7 SPS_D General Indication
Ind8 SPS_D General Indication
Ind9 SPS_D General Indication
Ind10 SPS_D General Indication
Ind11 SPS_D General Indication
Ind12 SPS_D General Indication
Ind13 SPS_D General Indication
Ind14 SPS_D General Indication
Ind15 SPS_D General Indication
Ind16 SPS_D General Indication
Ind17 SPS_D General Indication
Ind18 SPS_D General Indication

2.4.4 Logical Node: GGIO_IND_32


Description: Generic Process I/O (w.r.t 32 Indication Elements)

Page 18 P543_P545/EN PM/D42


MiCOM P543 and P545 (with Distance Protection) PICS and MICS

LN Class: GGIO
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behavior
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate
Ind1 SPS_D General Indication
Ind2 SPS_D General Indication
Ind3 SPS_D General Indication
Ind4 SPS_D General Indication
Ind5 SPS_D General Indication
Ind6 SPS_D General Indication
Ind7 SPS_D General Indication
Ind8 SPS_D General Indication
Ind9 SPS_D General Indication
Ind10 SPS_D General Indication
Ind11 SPS_D General Indication
Ind12 SPS_D General Indication
Ind13 SPS_D General Indication
Ind14 SPS_D General Indication
Ind15 SPS_D General Indication
Ind16 SPS_D General Indication
Ind17 SPS_D General Indication
Ind18 SPS_D General Indication
Ind19 SPS_D General Indication
Ind20 SPS_D General Indication
Ind21 SPS_D General Indication
Ind22 SPS_D General Indication
Ind23 SPS_D General Indication
Ind24 SPS_D General Indication
Ind25 SPS_D General Indication
Ind26 SPS_D General Indication
Ind27 SPS_D General Indication
Ind28 SPS_D General Indication
Ind29 SPS_D General Indication
Ind30 SPS_D General Indication
Ind31 SPS_D General Indication
Ind32 SPS_D General Indication

2.4.5 Logical Node: GGIO_IND_8


Description: Generic Process I/O (w.r.t 8 Indication Elements)
LN Class: GGIO
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behavior

P543_P545/EN PM/D42 Page 19


PICS and MICS MiCOM P543 and P545 (with Distance Protection)

Attribute Attr. Type Explanation T X


Health INS_HEALTH Health
NamPlt LPL_LN Name Plate
Ind1 SPS_D General Indication
Ind2 SPS_D General Indication
Ind3 SPS_D General Indication
Ind4 SPS_D General Indication
Ind5 SPS_D General Indication
Ind6 SPS_D General Indication
Ind7 SPS_D General Indication
Ind8 SPS_D General Indication

2.4.6 Logical Node: LLN0_CONTROL


Description: Control Domain Logical Node 0
LN Class: LLN0
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behavior
Health INS_HEALTH Health
NamPlt LPL_LLN0 Name Plate
AscMod INC_MOD_D_PRIV Check Synchronization
AscBeh INS_BEH_D_PRIV Check Synchronization
ArcMod INC_MOD_D_PRIV Auto-Reclose
ArcBeh INS_BEH_D_PRIV Auto-Reclose
PsbMod INC_MOD_D_PRIV Power Swing Blocking
PsbBeh INS_BEH_D_PRIV Power Swing Blocking

2.4.7 Logical Node: LLN0_PROT


Description: Protection Domain Logical Node 0
LN Class: LLN0
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behavior
Health INS_HEALTH Health
NamPlt LPL_LLN0 Name Plate
DisMod INC_MOD_D_PRIV Distance Mode
DisBeh INS_BEH_D_PRIV Distance Behavior
DifMod INC_MOD_D_PRIV Differential Mode
DifBeh INS_BEH_D_PRIV Differential Behavior
OcpMod INC_MOD_D_PRIV Overcurrent Mode
OcpBeh INS_BEH_D_PRIV Overcurrent Behavior
NgcMod INC_MOD_D_PRIV Negative Sequence Mode
NgcBeh INS_BEH_D_PRIV Negative Sequence Behavior
EfdMod INC_MOD_D_PRIV Earth Fault 1 (Derived) Mode

Page 20 P543_P545/EN PM/D42


MiCOM P543 and P545 (with Distance Protection) PICS and MICS

Attribute Attr. Type Explanation T X


EfdBeh INS_BEH_D_PRIV Earth Fault 1 (Derived) Behavior
SefMod INC_MOD_D_PRIV SEF Mode
SefBeh INS_BEH_D_PRIV SEF Behavior
VtpMod INC_MOD_D_PRIV Overvoltage/Undervoltage Mode
VtpBeh INS_BEH_D_PRIV Overvoltage/Undervoltage Behavior
NvdMod INC_MOD_D_PRIV Residual Overvoltage NVD Mode
NvdBeh INS_BEH_D_PRIV Residual Overvoltage NVD Behavior
Overfrequency/Underfrequency
FrqMod INC_MOD_D_PRIV
Mode
Overfrequency/Underfrequency
FrqBeh INS_BEH_D_PRIV
Behavior
DfpMod INC_MOD_D_PRIV df/dt Mode
DfpBeh INS_BEH_D_PRIV df/dt Behavior
ThmMod INC_MOD_D_PRIV Thermal Overload Mode
ThmBeh INS_BEH_D_PRIV Thermal Overload Behavior
CbfMod INC_MOD_D_PRIV CB Fail Mode
CbfBeh INS_BEH_D_PRIV CB Fail Behavior

2.4.8 Logical Node: LLN0_STANDARD


Description: General Logical Node 0
LN Class: LLN0
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behavior
Health INS_HEALTH Health
NamPlt LPL_LLN0 Name Plate

2.4.9 Logical Node: LPHD_STANDARD


Description: Px40 Physical Device Information
LN Class: LPHD
Attribute Attr. Type Explanation T X
PhyNam DPL_STANDARD Physical Device Name Plate
PhyHealth INS_HEALTH Physical Device Health
Proxy SPS_D Indicates if This LN is a Proxy
PwrUp SPS_D Power Up Detected

2.4.10 Logical Node: MMXU_FOURIER


Description: Standard Measurements (w.r.t Fourier Values)
LN Class: MMXU
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behavior
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate

P543_P545/EN PM/D42 Page 21


PICS and MICS MiCOM P543 and P545 (with Distance Protection)

Attribute Attr. Type Explanation T X


TotW MV_FLOAT Total Active Power (Total P)
TotVAr MV_FLOAT Total Reactive Power (Total Q)
TotVA MV_FLOAT Total Apparent Power (Total S)
TotPF MV_FLOAT Average Power Factor (Total PF)
Hz MV_FLOAT Frequency
PPV DEL_SEG_ANG Phase to Phase Voltages
PhV WYE_SEG_ANG_D Phase to Ground Voltages
Phase Currents (Fourier
A1 WYE_SEG_RES_D
Magnitudes)
A2 WYE_RES_ANG_D Phase Currents (ISEF Magnitude)
A3 WYE_RES_ANG_D Phase Currents (Mutual Magnitude)
W WYE_SEG Phase Active Power (P)
VAr WYE_SEG Phase Reactive Power (Q)
VA WYE_SEG Phase Apparent Power (S)
PF WYE_SEG Phase Power Factor

2.4.11 Logical Node: MMXU_IDIFF


Description: Standard Measurements (w.r.t Current Diff)
LN Class: MMXU
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behavior
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate
A1 WYE_SEG_ANG_D Phase Currents (Local)
A2 WYE_SEG_ANG_D Phase Currents (Remote CH1)
A3 WYE_SEG_ANG_D Phase Currents (Remote CH2)
A4 WYE_SEG_D Phase Currents (IDiff)
A5 WYE_SEG_D Phase Currents (IBias)

2.4.12 Logical Node: MMXU_RMS


Description: Standard Measurements (w.r.t RMS Values)
LN Class: MMXU
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behavior
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate
PhV WYE_SEG_D Phase to Ground Voltages
A WYE_SEG_D Phase Currents

2.4.13 Logical Node: MSQI_ALL


Description: Sequence and Imbalance (w.r.t Pos, Neq, Zero)
LN Class: MSQI

Page 22 P543_P545/EN PM/D42


MiCOM P543 and P545 (with Distance Protection) PICS and MICS

Attribute Attr. Type Explanation T X


Mod INC_MOD Mode
Beh INS_BEH Behavior
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate
Positive, Negative and Zero
SeqA SEQ_MAG_ANG
Sequence Current
Positive, Negative and Zero
SeqV SEQ_MAG_ANG
Sequence Voltage

2.4.14 Logical Node: MSQI_ VOLTAGE


Description: Sequence and Imbalance (w.r.t Pos, Neq, Zero Voltage only)
LN Class: MSQI
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behavior
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate
Positive, Negative and Zero
SeqV SEQ_MAG_ANG
Sequence Voltage

2.4.15 Logical Node: MSTA_I_W_VAR


Description: Metering Statistics (w.r.t Current, Real + Reactive Power - Average + Max
Values)
LN Class: MSTA
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behavior
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate
AvAmps1 MV_FLOAT_D Average Current
AvAmps2 MV_FLOAT_D Average Current
AvAmps3 MV_FLOAT_D Average Current
AvAmps4 MV_FLOAT_D Average Current
AvAmps5 MV_FLOAT_D Average Current
AvAmps6 MV_FLOAT_D Average Current
MaxAmps1 MV_FLOAT_D Maximum Current
MaxAmps2 MV_FLOAT_D Maximum Current
MaxAmps3 MV_FLOAT_D Maximum Current
AvW1 MV_FLOAT_D Average Real Power
AvW2 MV_FLOAT_D Average Real Power
MaxW MV_FLOAT_D Maximum Real Power
AvVAr1 MV_FLOAT_D Average Reactive Power
AvVAr2 MV_FLOAT_D Average Reactive Power
MaxVAr MV_FLOAT_D Maximum Reactive Power

P543_P545/EN PM/D42 Page 23


PICS and MICS MiCOM P543 and P545 (with Distance Protection)

2.4.16 Logical Node: PDIF_BASIC


Description: Differential (w.r.t Mandatory Attributes Only)
LN Class: PDIF
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behavior
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate
Str ACD_SEG Start
Op ACT_SEG Operate
DifAClc WYE_SEG_D Differential Current
RstA WYE_SEG_D Restraint Current

2.4.17 Logical Node: PDIS_BASIC


Description: Distance (w.r.t Mandatory Attributes Only)
LN Class: PDIS
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behavior
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate
Str ACD_SEG_NEU Start
Op ACT_SEG_NEU Operate T

2.4.18 Logical Node: PFRC_NO_SEG


Description: Rate of Change of Frequency (w.r.t No Phase Segregation)
LN Class: PFRC
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behavior
Health INS_HEALTH Health
NamPlt LPL_LN_PRIV Name Plate
Str ACD_NO_SEG Start
Op ACT_NO_SEG Operate T

2.4.19 Logical Node: PSCH_BASIC


Description: Protection Scheme (w.r.t Mandatory Attributes Only)
LN Class: PSCH
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behavior
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate

Page 24 P543_P545/EN PM/D42


MiCOM P543 and P545 (with Distance Protection) PICS and MICS

Attribute Attr. Type Explanation T X


ProTx SPS_WD Teleprotection Signal Transmitted T
ProRx SPS_WD Teleprotection Signal Received T
Str ACD_NO_SEG Carrier Send
Op ACT_SEG_NEU Operate T
Carrier Received after Unblock
CarRx ACT_NO_SEG
Logic
LosOfGrd SPS_WD Loss of Guard
Operate Signal from Weak End
WeiOp ACT_SEG
Infeed Function

2.4.20 Logical Node: PSOF_BASIC


Description: Switch-onto-Fault Protection
LN Class: PSOF
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behavior
Health INS_HEALTH Health
NamPlt LPL_LN_PRIV Name Plate
Str ACD_NO_SEG Start
Op ACT_NO_SEG Operate T

2.4.21 Logical Node: PTOC_NEU


Description: Timed Overcurrent (w.r.t Neutral)
LN Class: PTOC
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behavior
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate
Str ACD_NEU Start
Op ACT_NEU Operate T

2.4.22 Logical Node: PTOC_NO_SEG


Description: Timed Overcurrent (w.r.t No Phase Segregation)
LN Class: PTOC
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behavior
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate
Str ACD_NO_SEG Start

P543_P545/EN PM/D42 Page 25


PICS and MICS MiCOM P543 and P545 (with Distance Protection)

Attribute Attr. Type Explanation T X


Op ACT_NO_SEG Operate T

2.4.23 Logical Node: PTOC_SEG


Description: Timed Overcurrent (w.r.t Phase Segregation)
LN Class: PTOC
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behavior
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate
Str ACD_SEG Start
Op ACT_SEG Operate T

2.4.24 Logical Node: PTOF_NO_SEG


Description: Over Frequency (w.r.t No Phase Segregation)
LN Class: PTOF
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behavior
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate
Str ACD_NO_SEG Start
Op ACT_NO_SEG Operate T

2.4.25 Logical Node: PTOV_NEU


Description: Overvoltage (w.r.t Neutral)
LN Class: PTOV
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behavior
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate
Str ACD_NEU Start
Op ACT_NEU Operate T

2.4.26 Logical Node: PTOV_NO_SEG


Description: Overvoltage (w.r.t No Phase Segregation)
LN Class: PTOV
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behavior
Health INS_HEALTH Health

Page 26 P543_P545/EN PM/D42


MiCOM P543 and P545 (with Distance Protection) PICS and MICS

Attribute Attr. Type Explanation T X


NamPlt LPL_LN Name Plate
Str ACD_NO_SEG Start
Op ACT_NO_SEG Operate T

2.4.27 Logical Node: PTOV_SEG


Description: Overvoltage (w.r.t Phase Segregation)
LN Class: PTOV
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behavior
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate
Str ACD_SEG Start
Op ACT_SEG Operate T

2.4.28 Logical Node: PTRC_NO_SEG


Description: Protection Trip Conditioning (w.r.t No Phase Segregation)
LN Class: PTRC
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behavior
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate
Tr ACT_NO_SEG Trip
Sum of All Starts of All Connected
Str ACD_NO_SEG
Logical Nodes

2.4.29 Logical Node: PTTR_NO_SEG


Description: Thermal Overload (w.r.t No Phase Segregation)
LN Class: PTTR
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behavior
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate
Amp MV_FLOAT Current for Thermal Load Model
Relation Between Temperature and
TmpRl MV_FLOAT
Maximum Temperature
Op ACT_NO_SEG Operate T
AlmThm ACT_NO_SEG Thermal Alarm T

2.4.30 Logical Node: PTUF_NO_SEG


Description: Under Frequency (w.r.t No Phase Segregation)
LN Class: PTUF

P543_P545/EN PM/D42 Page 27


PICS and MICS MiCOM P543 and P545 (with Distance Protection)

Attribute Attr. Type Explanation T X


Mod INC_MOD Mode
Beh INS_BEH Behavior
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate
Str ACD_NO_SEG Start
Op ACT_NO_SEG Operate T

2.4.31 Logical Node: PTUV_SEG


Description: Undervoltage (w.r.t Phase Segregation)
LN Class: PTUV
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behavior
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate
Str ACD_SEG Start
Op ACT_SEG Operate T

2.4.32 Logical Node: RBRF_EXTTRIP


Description: Breaker Failure (w.r.t External Tripping)
LN Class: RBRF
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behavior
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate
OpEx ACT_NO_SEG Breaker Failure Trip ("External Trip") T

2.4.33 Logical Node: RDRE_BASIC


Description: Disturbance Recorder Function (w.r.t Mandatory Attributes Only)
LN Class: RDRE
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behavior
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate
RcdMade SPS_WD Recording Made
FltNum INS_BASIC Fault Number

2.4.34 Logical Node: RFLO_BASIC


Description: Fault Locator (w.r.t Mandatory Attributes Only)
LN Class: RFLO

Page 28 P543_P545/EN PM/D42


MiCOM P543 and P545 (with Distance Protection) PICS and MICS

Attribute Attr. Type Explanation T X


Mod INC_MOD Mode
Beh INS_BEH Behavior
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate
FltZ CMV_MAG_FLOAT Fault Impedance
FltDiskm MV_FLOAT Fault Distance in km

2.4.35 Logical Node: RPSB_BASIC


Description: Power Swing Detection/Blocking (w.r.t Mandatory Attributes Only)
LN Class: RPSB
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behavior
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate
Str ACD_NO_SEG Start (Power Swing Detected)
BlkZn SPS_WD Blocking of Correlated PDIS Zone

2.4.36 Logical Node: RPSB_OST


Description: Power Swing Blocking (w.r.t. Out Of Step Tripping)
LN Class: RPSB
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behavior
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate
Op ACT_NO_SEG Operate (Out of Step Tripping)

2.4.37 Logical Node: RREC_NO_SEG


Description: Auto-Reclosing (w.r.t No Phase Segregation)
LN Class: RREC
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behavior
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate
Operate (Used Here to Provide
Op ACT_NO_SEG T
Close to XCBR)
AutoRecSt INS_AR_STATE Auto-Reclosing Status

2.4.38 Logical Node: RSYN_DIFCLC


Description: Synchronism-check/Synchronizing (w.r.t Calculated Differential
Measurements)

P543_P545/EN PM/D42 Page 29


PICS and MICS MiCOM P543 and P545 (with Distance Protection)

LN Class: RSYN
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behavior
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate
Rel SPS_WD Release
DifHzClc MV_FLOAT Calculated Difference in Frequency
Calculated Difference of Phase
DifAngClc MV_FLOAT
Angle

2.4.39 Logical Node: XCBR_BASIC


Description: Circuit Breaker (w.r.t Mandatory Attributes Only)
LN Class: XCBR
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behavior
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate
Loc SPS_WD Local Operation
EEHealth INS_HEALTH External Equipment Health
OpCnt INS_BASIC Operation Counter
Pos DPC_STATUS Switch Position
BlkOpn SPC_STATUS Block Opening
BlkCls SPC_STATUS Block Closing

2.5 Common Data Class Definitions


The definition tables for each of the Common Data Classes used in the Logical Node
definitions are presented in the following sub-sections.
From an application point-of-view the data attributes of a Common Data Class are
classified according to their specific use. The characterization of data attributes, and the
services that they support/provide, will be through the use of 'Functional Constraints'. The
Functional Constraints are specified by the table below:
FC Name Semantic Source Definition
BR Buffered Reports IEC 61850-7-2
CF Configuration IEC 61850-7-2
CO Control IEC 61850-7-2
DC Description IEC 61850-7-2
EX Extended Definition IEC 61850-7-2
GO GOOSE Control IEC 61850-7-2
GS GSSE Control (UCA2 GOOSE) IEC 61850-7-2
LG Logging IEC 61850-7-2
MS Multicast Sampled Value Control IEC 61850-7-2
MX Measurands (Analogue Values) IEC 61850-7-2

Page 30 P543_P545/EN PM/D42


MiCOM P543 and P545 (with Distance Protection) PICS and MICS

FC Name Semantic Source Definition


RP Unbuffered Reports IEC 61850-7-2
SE Setting Group Editable IEC 61850-7-2
SG Setting Group IEC 61850-7-2
SP Set Point IEC 61850-7-2
ST Status Information IEC 61850-7-2
SV Substitution Values IEC 61850-7-2
US Unicast Sampled Value Control IEC 61850-7-2
XX Data Attribute Service Parameters IEC 61850-7-2

2.5.1 Common Data Class: ACD_NEU


Description: Directional Protection Activation Information (w.r.t Neutral)
CDC Class: ACD
Attribute Type FC Enumeration Comment X
general BOOLEAN ST Trip or start has happened
ENUMERATED8 General direction (unknown,
dirGeneral ST dir
(MMS Type: INT8) forward, backward or both)
Trip or start event with earth
neut BOOLEAN ST
current has happened
Earth current direction
ENUMERATED8
dirNeut ST dir (unknown, forward or
(MMS Type: INT8)
backward)
Quality of the protection
q Quality ST
activation information
Timestamp of the last change
t TimeStamp ST in state of protection activation
information

2.5.2 Common Data Class: ACD_NO_SEG


Description: Directional Protection Activation Information (w.r.t No Phase Segregation)
CDC Class: ACD
Attribute Type FC Enumeration Comment X
general BOOLEAN ST Trip or start has happened
ENUMERATED8 General direction (unknown,
dirGeneral ST dir
(MMS Type: INT8) forward, backward or both)
Quality of the protection
q Quality ST
activation information
Timestamp of the last change
t TimeStamp ST in state of protection activation
information

2.5.3 Common Data Class: ACD_SEG


Description: Directional Protection Activation Information (w.r.t Phase Segregation)
CDC Class: ACD
Attribute Type FC Enumeration Comment X
general BOOLEAN ST Trip or start has happened

P543_P545/EN PM/D42 Page 31


PICS and MICS MiCOM P543 and P545 (with Distance Protection)

Attribute Type FC Enumeration Comment X


ENUMERATED8 General direction (unknown,
dirGeneral ST dir
(MMS Type: INT8) forward, backward or both)
Trip or start event of Phase A
phsA BOOLEAN ST
has happened
ENUMERATED8 Phase A direction (unknown,
dirPhsA ST dir
(MMS Type: INT8) forward or backward)
Trip or start event of Phase B
phsB BOOLEAN ST
has happened

2.5.4 Common Data Class: ACD_SEG_NEU


Description: Directional Protection Activation Information (w.r.t Phase Segregation +
Neutral)
CDC Class: ACD
Attribute Type FC Enumeration Comment X
general BOOLEAN ST Trip or start has happened
ENUMERATED8 General direction (unknown,
dirGeneral ST dir
(MMS Type: INT8) forward, backward or both)
Trip or start event of Phase A
phsA BOOLEAN ST
has happened
ENUMERATED8 Phase A direction (unknown,
dirPhsA ST dir
(MMS Type: INT8) forward or backward)
Trip or start event of Phase B
phsB BOOLEAN ST
has happened
ENUMERATED8 Phase B direction (unknown,
dirPhsB ST dir
(MMS Type: INT8) forward or backward)
Trip or start event of Phase C
phsC BOOLEAN ST
has happened
ENUMERATED8 Phase C direction (unknown,
dirPhsC ST dir
(MMS Type: INT8) forward or backward)
Trip or start event with earth
neut BOOLEAN ST
current has happened
Earth current direction
ENUMERATED8
dirNeut ST dir (unknown, forward or
(MMS Type: INT8)
backward)
Quality of the protection
q Quality ST
activation information
Timestamp of the last change
t TimeStamp ST in state of protection activation
information

2.5.5 Common Data Class: ACT_NEU


Description: Protection Activation Information (w.r.t Neutral)
CDC Class: ACT
Attribute Type FC Enumeration Comment X
general BOOLEAN ST Trip or start has happened
Trip or start event with earth
neut BOOLEAN ST
current has happened
Quality of the protection
q Quality ST
activation information

Page 32 P543_P545/EN PM/D42


MiCOM P543 and P545 (with Distance Protection) PICS and MICS

Attribute Type FC Enumeration Comment X


Timestamp of the last change
t TimeStamp ST in state of protection activation
information

2.5.6 Common Data Class: ACT_NO_SEG


Description: Protection Activation Information (w.r.t No Phase Segregation)
CDC Class: ACT
Attribute Type FC Enumeration Comment X
general BOOLEAN ST Trip or start has happened
Quality of the protection
q Quality ST
activation information
Timestamp of the last change
t TimeStamp ST in state of protection activation
information

2.5.7 Common Data Class: ACT_SEG


Description: Protection Activation Information (w.r.t Phase Segregation)
CDC Class: ACT
Attribute Type FC Enumeration Comment X
general BOOLEAN ST Trip or start has happened
Trip or start event of Phase A
phsA BOOLEAN ST
has happened
Trip or start event of Phase B
phsB BOOLEAN ST
has happened
Trip or start event of Phase C
phsC BOOLEAN ST
has happened
Quality of the protection
q Quality ST
activation information
Timestamp of the last change
t TimeStamp ST in state of protection activation
information

2.5.8 Common Data Class: ACT_SEG_NEU


Description: Protection Activation Information (w.r.t Phase Segregation + Neutral)
CDC Class: ACT
Attribute Type FC Enumeration Comment X
general BOOLEAN ST Trip or start has happened
Trip or start event of Phase A
phsA BOOLEAN ST
has happened
Trip or start event of Phase B
phsB BOOLEAN ST
has happened
Trip or start event of Phase C
phsC BOOLEAN ST
has happened
Trip or start event with earth
neut BOOLEAN ST
current has happened
Quality of the protection
q Quality ST
activation information

P543_P545/EN PM/D42 Page 33


PICS and MICS MiCOM P543 and P545 (with Distance Protection)

Attribute Type FC Enumeration Comment X


Timestamp of the last change
t TimeStamp ST in state of protection activation
information

2.5.9 Common Data Class: CMV_MAG_ANG_FLOAT


Description: Complex Measured Value (w.r.t Floating Point Magnitude and Angle)
CDC Class: CMV
Attribute Type FC Enumeration Comment X
Deadbanded complex
measured vector. Updated to
Vector_Magnitude the current value of instCVal
cVal MX
Angle_Float when the value has changed
according to the configuration
parameter db.
Quality of the measurement
q Quality MX
value
Time deadbanded magnitude
t TimeStamp MX last exceeded its db
configuration parameter
Unit of the attribute
units Unit_No_Multiplier CF
representing the data
db INT32U CF Measurement deadband

2.5.10 Common Data Class: CMV_MAG_FLOAT


Description: Complex Measured Value (w.r.t Floating Point Magnitude)
CDC Class: CMV
Attribute Type FC Enumeration Comment X
Deadbanded complex
measured vector. Updated to
Vector_Magnitude_ the current value of instCVal
cVal MX
Float when the value has changed
according to the configuration
parameter db.
Quality of the measurement
q Quality MX
value
Time deadbanded magnitude
t TimeStamp MX last exceeded its db
configuration parameter
Unit of the attribute
units Unit_No_Multiplier CF
representing the data
db INT32U CF Measurement deadband

2.5.11 Common Data Class: DEL_SEG_ANG


Description: Phase to Phase Measurements for a 3-Phase System (w.r.t Phase
Segregation + Angle)
CDC Class: DEL
Attribute Type FC Enumeration Comment X
Measurement values for
phsAB CMV_MAG_ANG_FLOAT --
Phase A to Phase B

Page 34 P543_P545/EN PM/D42


MiCOM P543 and P545 (with Distance Protection) PICS and MICS

Attribute Type FC Enumeration Comment X


Measurement values for
phsBC CMV_MAG_ANG_FLOAT --
Phase B to Phase C
Measurement values for
phsCA CMV_MAG_ANG_FLOAT --
Phase C to Phase A

2.5.12 Common Data Class: DPC_STATUS


Description: Controllable Double Point (w.r.t Status Only)
CDC Class: DPC
Attribute Type FC Enumeration Comment X
Status value of the data
CODED_ENUM
stVal ST Dbpos (Intermediate state, Off, On or
(MMS Type: _BSTR2)
Bad-state)
q Quality ST Quality of the status value
Timestamp of the last change
t TimeStamp ST
in state of status value
ENUMERATED8 Control model (corresponding
ctlModel CF ctlModel
(MMS Type: INT8) to the behavior of the data)

2.5.13 Common Data Class: DPL_STANDARD


Description: Standard Device Name Plate
CDC Class: DPL
Attribute Type FC Enumeration Comment X
vendor VISIBLE_STRING255 DC Name of the vendor
hwRev VISIBLE_STRING255 DC Hardware revision
swRev VISIBLE_STRING255 DC Software revision
serNum VISIBLE_STRING255 DC Serial number
model VISIBLE_STRING255 DC Model number
location VISIBLE_STRING255 DC Physical location of device

2.5.14 Common Data Class: INC_MOD


Description: Controllable Integer Status (w.r.t Mode)
CDC Class: INC
Attribute Type FC Enumeration Comment X
INT32
stVal ST Mod Status value of the data
(MMS Type: INT8)
q Quality ST Quality of the status value
Timestamp of the last change
t TimeStamp ST
in state of status value
ENUMERATED8 Control model (corresponding
ctlModel CF ctlModel
(MMS Type: INT8) to the behavior of the data)

2.5.15 Common Data Class: INC_MOD_D_PRIV


Description: Controllable Integer Status (w.r.t Mode, with Description (Private DO))
CDC Class: INC

P543_P545/EN PM/D42 Page 35


PICS and MICS MiCOM P543 and P545 (with Distance Protection)

Attribute Type FC Enumeration Comment X


INT32
stVal ST Mod Status value of the data
(MMS Type: INT8)
q Quality ST Quality of the status value
Timestamp of the last change
t TimeStamp ST
in state of status value
ENUMERATED8 Control model (corresponding
ctlModel CF ctlModel
(MMS Type: INT8) to the behavior of the data)
Description of the status
d VISIBLE_STRING255 DC
element
dataNs VISIBLE_STRING255 EX Data name space

2.5.16 Common Data Class: INS_AR_STATE


Description: Integer Status (w.r.t Auto-Reclose Status)
CDC Class: INS
Attribute Type FC Enumeration Comment X
INT32
stVal ST AutoRecSt The element status
(MMS Type: INT8)
q Quality ST The quality of the status value
Timestamp of the last change
t TimeStamp ST
in state

2.5.17 Common Data Class: INS_BASIC


Description: Integer Status (w.r.t Mandatory Options Only)
CDC Class: INS
Attribute Type FC Enumeration Comment X
stVal INT32 ST The element status
q Quality ST The quality of the status value
Timestamp of the last change
t TimeStamp ST
in state

2.5.18 Common Data Class: INS_BEH


Description: Integer Status (w.r.t Behavior)
CDC Class: INS
Attribute Type FC Enumeration Comment X
INT32
stVal ST Beh The element status
(MMS Type: INT8)
q Quality ST The quality of the status value
Timestamp of the last change
t TimeStamp ST
in state

2.5.19 Common Data Class: INS_BEH_D_PRIV


Description: Integer Status (w.r.t Behavior, with Description (Private DO))
CDC Class: INS

Page 36 P543_P545/EN PM/D42


MiCOM P543 and P545 (with Distance Protection) PICS and MICS

Attribute Type FC Enumeration Comment X


INT32
stVal ST Beh The element status
(MMS Type: INT8)
The quality of the status
q Quality ST
value
Timestamp of the last change
t TimeStamp ST
in state
Description of the status
d VISIBLE_STRING255 DC
element
dataNs VISIBLE_STRING255 EX Data name space

2.5.20 Common Data Class: INS_HEALTH


Description: Integer Status (w.r.t Health)
CDC Class: INS
Attribute Type FC Enumeration Comment X
INT32
stVal ST Health The element status
(MMS Type: INT8)
q Quality ST The quality of the status value
Timestamp of the last change
t TimeStamp ST
in state

2.5.21 Common Data Class: LPL_LLN0


Description: Logical Node 0 Name Plate
CDC Class: LPL
Attribute Type FC Enumeration Comment X
vendor VISIBLE_STRING255 DC Name of the vendor
swRev VISIBLE_STRING255 DC Software revision
d VISIBLE_STRING255 DC Description
Uniquely identifies the
configRev VISIBLE_STRING255 DC configuration of a local device
instance
ldNs VISIBLE_STRING255 EX Logical device name space

2.5.22 Common Data Class: LPL_LN


Description: Standard Logical Node Name Plate
CDC Class: LPL
Attribute Type FC Enumeration Comment X
vendor VISIBLE_STRING255 DC Name of the vendor
swRev VISIBLE_STRING255 DC Software revision
d VISIBLE_STRING255 DC Description

2.5.23 Common Data Class: LPL_LN_PRIV


Description: Logical Node Name Plate (w.r.t Schneider Electric Extended)
CDC Class: LPL
Attribute Type FC Enumeration Comment X
vendor VISIBLE_STRING255 DC Name of the vendor

P543_P545/EN PM/D42 Page 37


PICS and MICS MiCOM P543 and P545 (with Distance Protection)

Attribute Type FC Enumeration Comment X


swRev VISIBLE_STRING255 DC Software revision
d VISIBLE_STRING255 DC Description
lnNs VISIBLE_STRING255 EX Logical node name space

2.5.24 Common Data Class: MV_FLOAT


Description: Measured Value (w.r.t. Floating Point Value)
CDC Class: MV
Attribute Type FC Enumeration Comment X
Deadbanded magnitude of
the instantaneous value of a
measured value or harmonic
value. Updated to the current
mag AnalogueValue_Float MX
value of instMag when the
value has changed according
to the configuration parameter
db.
Quality of the measurement
q Quality MX
value
Time deadbanded magnitude
t TimeStamp MX last exceeded its db
configuration parameter
Unit of the attribute
units Unit_No_Multiplier CF
representing the data
db INT32U CF Measurement deadband

2.5.25 Common Data Class: MV_FLOAT_D


Description: Measured Value (w.r.t Floating Point Value with Description)
CDC Class: MV
Attribute Type FC Enumeration Comment X
Deadbanded magnitude of
the instantaneous value of a
measured value or harmonic
value. Updated to the current
mag AnalogueValue_Float MX
value of instMag when the
value has changed according
to the configuration parameter
db.
Quality of the measurement
q Quality MX
value
Time deadbanded magnitude
t TimeStamp MX last exceeded its db
configuration parameter
Unit of the attribute
units Unit_No_Multiplier CF
representing the data
db INT32U CF Measurement deadband
Description of the status
d VISIBLE_STRING255 DC
element

2.5.26 Common Data Class: SEQ_MAG_ANG


Description: Sequence Components of a Measurement Value (w.r.t Magnitudes +
Angles)

Page 38 P543_P545/EN PM/D42


MiCOM P543 and P545 (with Distance Protection) PICS and MICS

CDC Class: SEQ


Attribute Type FC Enumeration Comment X
Sequence component 1 (For
c1 CMV_MAG_ANG_FLOAT --
semantic meaning see seqT)
Sequence component 2 (For
c2 CMV_MAG_ANG_FLOAT --
semantic meaning see seqT)
Sequence component 3 (For
c3 CMV_MAG_ANG_FLOAT --
semantic meaning see seqT)
Sequence quantity
ENUMERATED8
seqT MX seqT measurement type (Pos-
(MMS Type: INT8)
Neg-Zero or Dir-Quad-Zero)

2.5.27 Common Data Class: SPC_STATUS


Description: Controllable Single Point (w.r.t Status Only)
CDC Class: SPC
Attribute Type FC Enumeration Comment X
stVal BOOLEAN ST Status value of the data
q Quality ST Quality of the status value
Timestamp of the last change
t TimeStamp ST
in state of status value
ENUMERATED8 Control model (corresponding
ctlModel CF ctlModel
(MMS Type: INT8) to the behavior of the data)

2.5.28 Common Data Class: SPS_D


Description: Standard Single Point Status (with Description)
CDC Class: SPS
Attribute Type FC Enumeration Comment X
The element status (TRUE or
stVal BOOLEAN ST
FALSE)
The quality of the status
q Quality ST
value
Timestamp of the last change
t TimeStamp ST
in state
Description of the status
d VISIBLE_STRING255 DC
element

2.5.29 Common Data Class: SPS_WD


Description: Single Point Status (without Description)
CDC Class: SPS
Attribute Type FC Enumeration Comment X
The element status (TRUE or
stVal BOOLEAN ST
FALSE)
q Quality ST The quality of the status value
Timestamp of the last change
t TimeStamp ST
in state

P543_P545/EN PM/D42 Page 39


PICS and MICS MiCOM P543 and P545 (with Distance Protection)

2.5.30 Common Data Class: WYE_RES_ANG_D


Description: Phase to Ground Measurements for a 3-Phase System (w.r.t Residual +
Description + Angle)
CDC Class: WYE
Attribute Type FC Enumeration Comment X
Measurement values for the
res CMV_MAG_ANG_FLOAT --
residual system current
Description of the status
d VISIBLE_STRING255 DC
element

2.5.31 Common Data Class: WYE_SEG


Description: Phase to Ground Measurements for a 3-Phase System (w.r.t Phase
Segregation)
CDC Class: WYE
Attribute Type FC Enumeration Comment X
Measurement values for
phsA CMV_MAG_FLOAT --
Phase A
Measurement values for
phsB CMV_MAG_FLOAT --
Phase B
Measurement values for
phsC CMV_MAG_FLOAT --
Phase C

2.5.32 Common Data Class: WYE_SEG_ANG_D


Description: Phase to Ground Measurements for a 3-Phase System
CDC Class: WYE
Attribute Type FC Enumeration Comment X
Measurement values for
phsA CMV_MAG_ANG_FLOAT --
Phase A
Measurement values for
phsB CMV_MAG_ANG_FLOAT --
Phase B
Measurement values for
phsC CMV_MAG_ANG_FLOAT --
Phase C
Description of the status
d VISIBLE_STRING255 DC
element

2.5.33 Common Data Class: WYE_SEG_D


Description: Phase to Ground Measurements for a 3-Phase System (w.r.t Phase
Segregation + Description)
CDC Class: WYE
Attribute Type FC Enumeration Comment X
Measurement values for
phsA CMV_MAG_FLOAT --
Phase A
Measurement values for
phsB CMV_MAG_FLOAT --
Phase B
Measurement values for
phsC CMV_MAG_FLOAT --
Phase C
Description of the status
d VISIBLE_STRING255 DC
element

Page 40 P543_P545/EN PM/D42


MiCOM P543 and P545 (with Distance Protection) PICS and MICS

2.5.34 Common Data Class: WYE_SEG_RES_D


Description: Phase to Ground Measurements for a 3-Phase System (w.r.t Phase
Segregation + Residual + Description)
CDC Class: WYE
Attribute Type FC Enumeration Comment X
Measurement values for
phsA CMV_MAG_ANG_FLOAT --
Phase A
Measurement values for
phsB CMV_MAG_ANG_FLOAT --
Phase B
Measurement values for
phsC CMV_MAG_ANG_FLOAT --
Phase C
Measurement values for
neut CMV_MAG_ANG_FLOAT --
neutral input
Description of the status
d VISIBLE_STRING255 DC
element

P543_P545/EN PM/D42 Page 41


PICS and MICS MiCOM P543 and P545 (with Distance Protection)

2.6 Common Data Attribute Type Definitions


Common data attribute types, known herein as components, are defined for use in the
Common Data Classes defined in the sections above.

2.6.1 Component: AnalogueValue_Float


Comment: General Analogue Value (w.r.t Floating Point Value)
Parent Type: AnalogueValue
Attribute Type Enumeration Comment X
f FLOAT32 Floating point value

2.6.2 Component: Unit_No_Multiplier


Comment: SI Unit Definitions
Parent Type: Unit
Attribute Type Enumeration Comment X
SIUnit ENUMERATED8 SIUnit SI Unit

2.6.3 Component: Vector_Magnitude_Float


Comment: Complex Vector (w.r.t Floating Point Magnitude Value)
Parent Type: Vector
Attribute Type Enumeration Comment X
The magnitude of the complex
mag AnalogueValue_Float
value

2.6.4 Component: Vector_MagnitudeAngle_Float


Comment: Complex Vector (w.r.t Floating Point Magnitude and Angle Values)
Parent Type: Vector
Attribute Type Enumeration Comment X
The magnitude of the complex
mag AnalogueValue_Float
value
The angle of the complex value
ang AnalogueValue_Float
(the unit is degrees)

Page 42 P543_P545/EN PM/D42


MiCOM P543 and P545 (with Distance Protection) PICS and MICS

2.7 Enumerated Type Definitions


The following sub-sections specify the enumerations that are associated to some
Common Data Class attributes. The definition of the enumerations are according to
IEC 61850-7-3 and IEC 61850-7-4 unless otherwise stated.

2.7.1 Enumerated Type: AutoRecSt


Description: Auto-Reclose Status
Ordinal Semantic
1 Ready
2 InProgress
3 Successful
4 Unsuccessful

2.7.2 Enumerated Type: Beh


Description: Behavior
Ordinal Semantic
1 On
2 Blocked
3 Test
4 Test/Blocked
5 Off

2.7.3 Enumerated Type: ctlModel


Description: Control Model
Ordinal Semantic
0 Status only
1 Direct with normal security
2 SBO with normal security
3 Direct with enhanced security
4 SBO with enhanced security

2.7.4 Enumerated Type: Dbpos


Description: Switch Positions
Ordinal Semantic
0 Intermediate
1 Off
2 On
3 Bad

2.7.5 Enumerated Type: dir


Description: Direction
Ordinal Semantic
0 Unknown

P543_P545/EN PM/D42 Page 43


PICS and MICS MiCOM P543 and P545 (with Distance Protection)

Ordinal Semantic
1 Forward
2 Backward
3 Both

2.7.6 Enumerated Type: Health


Description: Health
Ordinal Semantic
1 Ok
2 Warning
3 Alarm

2.7.7 Enumerated Type: Mod


Description: Mode
Ordinal Semantic
1 On
2 Blocked
3 Test
4 Test/Blocked
5 Off

2.7.8 Enumerated Type: seqT


Description: Sequence Measurement Type
Ordinal Semantic
0 Pos_Neg_Zero
1 Dir_Quad_Zero

2.7.9 Enumerated Type: SIUnit


Description: SI Units Derived from ISO/IEC 1000
Ordinal Semantic Ordinal Semantic
-16 years 31 J
-15 months 32 N
-14 weeks 33 Hz
-13 V/s 34 lx
-12 mins 35 Lm
-11 hours 36 Wb
-10 days 37 T
-9 °F 38 W
-8 ratio 39 Pa
-7 miles 41 m²
-6 inches 42 m³
-5 feet 43 m/s
-4 df/dt 44 m/s²
-3 Hz/s 45 m³/s

Page 44 P543_P545/EN PM/D42


MiCOM P543 and P545 (with Distance Protection) PICS and MICS

Ordinal Semantic Ordinal Semantic


-2 % 46 m/m³
-1 pu 47 M
1 none 48 kg/m³
2 m 49 m²/s
3 kg 50 W/m K
4 s 51 J/K
5 A 52 ppm
6 K 53 1/s
7 mol 54 rad/s
8 cd 61 VA
9 deg 62 Watts
10 rad 63 VAr
11 sr 64 theta
21 Gy 65 cos(theta)
22 q 66 Vs
23 °C 67 V²
24 Sv 68 As
25 F 69 A²
26 C 70 A²t
27 S 71 VAh
28 H 72 Wh
29 V 73 VArh
30 ohm 74 V/Hz
31 J

P543_P545/EN PM/D42 Page 45


PICS and MICS MiCOM P543 and P545 (with Distance Protection)

2.8 MMS Data-Type Conversions


The following table shows the relationships between the Part 7 and Part 8-1 data types.
The definitions presented above use Part 7 data types, however these are subject to
'translation' when exposed over an MMS (Part 8-1) interface:
Part 7 Type MMS Type Part 7 Description
BOOLEAN Bool Logical TRUE/FALSE value
BVstring13 BVstring13 Variable bit string (upto 13 bits)
CODED_ENUM Byte Coded enumeration
CODED_ENUM2 Byte Coded enumeration (2)
EntryTime Btime6 8.1 Section 8.1.3.7
ENUMERATED16 Short 16 bit enumerated value
ENUMERATED8 Byte 8 bit enumerated value
FLOAT32 Float 32 bit floating point value
FLOAT64 Double 64 bit floating point value
INT128 Long 128 bit signed integer value
INT16 Short 16 bit signed integer value
INT16U Ushort 16 bit unsigned integer value
INT24U Ulong 24 bit unsigned integer value
INT32 Long 32 bit signed integer value
INT32U Ulong 32 bit unsigned integer value
INT8 Byte 8 bit signed integer value
INT8U Ubyte 8 bit unsigned integer value
OCTET_STRING6 Ostring6 6 character string (8 bits per character)
OCTET_STRING64 Ostring64 64 character string (8 bits per character)
OCTET_STRING8 Ostring8 8 character string (8 bits per character)
Quality BVstring13 IEC 61850 Quality
TimeStamp Utctime IEC 61850 Time stamp
UNICODE_STRING255 UTF8Vstring255 255 character string (16 bits per unicode character)
UTC_TM Utctime UTC Timestamp
VISIBLE_STRING255 Vstring255 255 character string
VISIBLE_STRING64 Vstring64 64 character string
VISIBLE_STRING65 Vstring65 65 character string
VISIBLE_STRING97 Vstring97 97 character string

Page 46 P543_P545/EN PM/D42


Customer Care Centre
http://www.schneider-electric.com/CCC

 2011 Schneider Electric. All rights reserved.

Schneider Electric
35 rue Joseph Monier
92506 Rueil-Malmaison
FRANCE
Phone: +33 (0) 1 41 29 70 00
Fax: +33 (0) 1 41 29 71 00
www.schneider-electric.com Publisher: Schneider Electric
Publication: P543_P545/EN PM/' June 2011

You might also like