P14x EN PM Hf7 V46U
P14x EN PM Hf7 V46U
P14x EN PM Hf7 V46U
P14x/EN PM/Hf7
CONTENTS
Page
TABLES
Page
Table 1: Basic conformance statement 5
Table 2: Models conformance statement 6
Table 3: Service conformance statement 9
Notes:
Important This document covers the MiCOM P14x range. This includes
the following products: P141, P142, P143, P144 & P145.
In most cases the details described here cover ALL the
products in the range.
Where a particular object applies to anything other than the
entire range, the applicable product(s) will be identified
accordingly.
This is stated as follows:
1.1 Introduction
This specification is the Protocol Implementation Conformance Statement (PICS) and
presents the ACSI conformance statements as defined in Annex A of Part 7-2 of the
IEC 61850 standard specifications.
S1 ServerDirectory TP Y
Application association
S2 Associate Y
S3 Abort Y
S4 Release Y
Logical Device
S5 LogicalDeviceDirectory TP Y
Logical Node
S6 LogicalNodeDirectory TP Y
S7 GetAllDataValues TP Y
Data
S8 GetDataValues TP Y
S9 SetDataValues TP Y
S10 GetDataDirectory TP Y
S11 GetDataDefinition TP Y
Data set
S12 GetDataSetValues TP Y
S13 SetDataSetValues TP
S14 CreateDataSet TP
S15 DeleteDataSet TP
S16 GetDataSetDirectory TP Y
Substitution
S17 SetDataValues TP
Logging
Log control block
S30 GetLCBValues TP
S31 SetLCBValues TP
Log
S32 QueryLogByTime TP
S33 QueryLogByEntry TP
S34 GetLogStatusValues TP
Control
S51 Select Y
S52 SelectWithValue TP Y
S53 Cancel TP Y
S54 Operate TP Y
Command-
S55 TP Y
Termination
S56 TimeActivated-Operate TP
File transfer
S57 GetFile TP Y
S58 SetFile TP
Only from /dr_unextracted/
S59 DeleteFile TP Y Operation may only be
performed on .cfg files.
S60 GetFileAttributeValues TP Y
Time
Nearest negative power of
T1 Time resolution of internal clock 1 ms
2 in seconds.
T2 Time accuracy of internal clock T0
1 ms T1
T2
T3
T4
T5
Nearest value of 2 ** -n in
T3 Supported TimeStamp resolution - 10
seconds
AA: Application association type
TP: Two part (for MMS)
MC: Multicast (for GOOSE and SMV)
2.1 Introduction
This specification is the Model Implementation Conformance Statement (MICS) and
presents the top-level IEC61850 data model that has been implemented. The definitions
of all used Logical Nodes and their associated Common Data Classes, components and
associated enumerated values are also included for completeness.
The reader is expected to be conversant with the terminology presented within the
IEC61850 part 7 series of specifications.
2.2 Objective
To provide comprehensive details of the standard data object model elements supported
by the device. The MICS is conformant to the devices associated ICD (Substation
Configuration Language) file, according to part 6 of the IEC61850 standards. The layout
of the presented tables within this document are conformant to the part 7 series of the
IEC61850 standard specifications with the following exceptions:
The "Trigger Options" field is not presented
The "M/O" field is not present as the definitions are as deployed within the model
An additional column "X" is used to signify MiCOM custom attributes
(LN
LN Type Description Name Space
Class)
GGIO_IND_128 (GGIO) Generic process I/O (w.r.t 128 Indication Elements) IEC 61850-7-4:2003
Generic Process I/O (w.r.t 16 Indication Elements)
GGIO_IND_18 (GGIO) IEC 61850-7-4:2003
(Applicable to P142 & P144 only)
GGIO_IND_16 (GGIO) Generic Process I/O (w.r.t 18 Indication Elements) IEC 61850-7-4:2003
GGIO_IND_32 (GGIO) Generic Process I/O (w.r.t 32 Indication Elements) IEC 61850-7-4:2003
GGIO_IND_32_CTRL (GGIO) Generic process I/O (w.r.t 32 Indications Ctrl i/p) IEC 61850-7-4:2003
GGIO_IND_64 (GGIO) Generic Process I/O (w.r.t 64 Indication Elements) IEC 61850-7-4:2003
Control Domain Logical Node 0
LLN0_CONTROL (LLN0) IEC 61850-7-4:2003
(Applicable to P143 & P145 only)
Control Domain Logical Node 0
LLN0_CONTROL_AR (LLN0) IEC 61850-7-4:2003
(Applicable to P142 & P144 only)
LLN0_SYSTEM (LLN0) System Logical Node 0 IEC 61850-7-4:2003
LLN0_PROT (LLN0) Protection Domain Logical Node 0 IEC 61850-7-4:2003
LLN0_STANDARD (LLN0) General Logical Node 0 IEC 61850-7-4:2003
LPHD_STANDARD (LPHD) Px40 Physical Device Information IEC 61850-7-4:2003
MMTR_PRIV (MMTR) Metering IEC 61850-7-4:2003
MMXU_FOURIER_P145 (MMXU) Standard measurements (w.r.t Fourier Values - P145) IEC 61850-7-4:2003
MMXU_RMS_P145 (MMXU) Standard measurements (w.r.t RMS Values - P145) IEC 61850-7-4:2003
MSQI_ALL (MSQI) Sequence and imbalance (w.r.t Pos, Neq, Zero) IEC 61850-7-4:2003
Metering Statistics (w.r.t Current, Real + Reactive Power -
MSTA_I_W_VAR (MSTA) IEC 61850-7-4:2003
Average + Max values)
Differential (w.r.t Neutral)
PDIF_NEU (PDIF) IEC 61850-7-4:2003
(Not applicable to P144)
PFRC_NO_SEG (PFRC) Rate of change of frequency (w.r.t No Phase Segregation) IEC 61850-7-4:2003
PTOC_NEU (PTOC) Timed Overcurrent (w.r.t Neutral) IEC 61850-7-4:2003
PTOC_NO_SEG (PTOC) Timed Overcurrent (w.r.t No Phase Segregation) IEC 61850-7-4:2003
PTOC_SEG (PTOC) Timed Overcurrent (w.r.t Phase Segregation) IEC 61850-7-4:2003
PTOF_NO_SEG (PTOF) Over frequency (w.r.t No Phase Segregation) IEC 61850-7-4:2003
PTOV_SEG (PTOV) Overvoltage (w.r.t Phase Segregation) IEC 61850-7-4:2003
PTOV_NEU (PTOV) Overvoltage (w.r.t Neutral) IEC 61850-7-4:2003
PTOV_NO_SEG (PTOV) Overvoltage (w.r.t Phase Segregation) IEC 61850-7-4:2003
PTRC_NO_SEG (PTRC) Protection trip conditioning (w.r.t No Phase Segregation) IEC 61850-7-4:2003
PTTR_NO_SEG (PTTR) Thermal overload (w.r.t No Phase Segregation) IEC 61850-7-4:2003
PTUF_NO_SEG (PTUF) Under frequency (w.r.t No Phase Segregation) IEC 61850-7-4:2003
PTUV_SEG (PTUV) Undervoltage (w.r.t Phase Segregation) IEC 61850-7-4:2003
RBRF_EXTTRIP (RBRF) Breaker Failure (w.r.t External Tripping) IEC 61850-7-4:2003
RDRE_BASIC (RDRE) Disturbance Recorder function (w.r.t Mandatory Attributes only) IEC 61850-7-4:2003
RFLO_BASIC (RFLO) Fault Locator (w.r.t Mandatory Attributes only) IEC 61850-7-4:2003
RREC_NO_SEG (RREC) Autoreclosing (w.r.t No Phase Segregation) IEC 61850-7-4:2003
Synchronism-check / Synchronising (w.r.t Calculated Differetial
RSYN_DIFCLC (RSYN) Measurements) IEC 61850-7-4:2003
(Applicable to P143 & P145 only)
XCBR_BASIC (XCBR) Circuit Breaker (w.r.t Mandatory Attributes Only) IEC 61850-7-4:2003
LN Class: GGIO
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behaviour
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate
Ind1 SPS_D General indication (binary input)
Ind2 SPS_D General indication (binary input)
Ind3 SPS_D General indication (binary input)
Ind4 SPS_D General indication (binary input)
Ind5 SPS_D General indication (binary input)
Ind6 SPS_D General indication (binary input)
Ind7 SPS_D General indication (binary input)
Ind8 SPS_D General indication (binary input)
Ind9 SPS_D General indication (binary input)
Ind10 SPS_D General indication (binary input)
Ind11 SPS_D General indication (binary input)
Ind12 SPS_D General indication (binary input)
Ind13 SPS_D General indication (binary input)
Ind14 SPS_D General indication (binary input)
Ind15 SPS_D General indication (binary input)
Ind16 SPS_D General indication (binary input)
Ind17 SPS_D General indication (binary input)
Ind18 SPS_D General indication (binary input)
Ordinal Semantic
3 Select-failed
4 Invalid-position
5 Position-reached
6 Parameter-change-in-execution
7 Step-limit
8 Blocked-by-Mode
9 Blocked-by-process
10 Blocked-by-interlocking
11 Blocked-by-synchrocheck
12 Command-already-in-execution
13 Blocked-by-health
14 1-of-n-control
15 Abortion-by-cancel
16 Time-limit-over
17 Abortion-by-trip
18 Object-not-selected
Ordinal Semantic
3 uniqueness-bypass
4 select-bypass
5 status-bypass
Ordinal Semantic
6 K
7 mol
8 cd
9 deg
10 rad
11 sr
21 Gy
22 q
23 °C
24 Sv
25 F
26 C
27 S
28 H
29 V
30 ohm
31 J
32 N
33 Hz
34 lx
35 Lm
36 Wb
37 T
38 W
39 Pa
41 m²
42 m³
43 m/s
44 m/s²
45 m³/s
46 m/m³
47 M
48 kg/m³
49 m²/s
50 W/m K
51 J/K
52 ppm
53 1/s
54 rad/s
61 VA
62 Watts
63 VAr
64 phi
65 cos(phi)
Ordinal Semantic
66 Vs
67 V²
68 As
69 A²
70 A²t
71 VAh
72 Wh
73 VArh
74 V/Hz
Notes:
Schneider Electric
35 rue Joseph Monier
92506 Rueil-Malmaison
FRANCE
Phone: +33 (0) 1 41 29 70 00
Fax: +33 (0) 1 41 29 71 00
www.schneider-electric.com Publisher: Schneider Electric
Publication: P14x/EN PM/HF7 Software Version: 46U 10/2012